Home

Altronix AL802ULADAJ power extension

image

Contents

1. Mount the unit in desired location Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure Install two upper fasteners and screws in the wall with the screw heads protruding Place the enclosure s upper keyholes over the two upper screws level and secure Mark the position of the lower two holes Remove the enclosure Drill the lower holes and install the two fasteners Place the enclosure s upper keyholes over the two upper screws Install the two lower screws and make sure to tighten all screws Enclosure Dimensions pg 12 Secure enclosure to earth ground Fig 1 pg 3 2 Connect the line L ground G and neutral N terminals to a separate unswitched AC circuit 120VAC 60Hz dedicated to the Fire Alarm System 3 Measure output voltage before connecting devices This helps avoid potential damage 4 Connect battery to terminals marked BAT on the Power Supply Board battery leads included Use two 2 12VDC batteries connected in series Set output selection switches marked OUT1 through OUT4 to follow corresponding input IN1 amp IN2 and desired output signal type Output Programming Selection Table pg 4 Connect FACP output to desired AL800LGK logic board inputs and notification appliances to desired ALS00LGK logic board outputs see Application Guide CA ON AL802ULADAJ Note The 2 wire horn strobe sync mode will only synchronize horns horn strobes strobes
2. Supervised able pg 4 Maximum line loss or voltage drop tested wi SV C FAULT NC An open circuit across this pair of terminals will cause INI and IN2 to simultaneously Common signal a trouble condition back to the FACP Typically used to report AC or BAT Fail trouble input form contact 1 amp 28VDC Fig 2 pg 7 NC C NO These are dry contact trouble outputs that follow any general loop system trouble conditions Common Typically used to trigger a digital communicator or other reporting device trouble input form contact 1 amp 28VDC 0 35 Power Factor Fig 2 pg 7 AUX This separate 1 amp max auxiliary Special Application Power output circuit is typically used to power 4 wire smoke detectors See attached list of devices Appendix A pgs 10 12 DC 24VDC from power supply Note Unit is equipped with 1 amp max auxiliary output AUX will remain battery backed up during power outage For loads connected to AUX please refer to battery Stand by Specifications above for ratings When loads are connected to AUX output during alarm condition the remaining outputs may not exceed 8 amp total alarm current example AUX 1 amp outputs up to 7 amp AL802ULADAJ Terminal Identification Table AL800ADA Power Supply Board Terminal iri Eesend Function Description L G N Connect 120 VAC to these terminals L to hot N to neutral G
3. IN1 IN1 polarity is shown in alarm condition During an alarm condition these inputs will cause the selected IN2 IN2 outputs chosen to drive notification appliances The designated outputs are set by output switches Supervised OUTI1 through OUT4 Output Programming Selection Table pg 4 A trouble condition on an output loop will cause the corresponding input to trip the FACP by opening the FACP loop An alarm condition will always override trouble to drive notification appliances RET1 RETI For Class A Style Z hookups these terminal pairs return to FACP NACI and or NAC2 For Class RET2 RET2 B Style W Y hookups the FACP EOL resistor from the NAC1 and or NAC2 outputs are Supervised terminated at these terminals C DRY1 NC An open across these inputs will cause the selected outputs chosen to drive 5 notification appliances The designated outputs are set by output switches OUT1 through OUT4 C DRY NC e Dry input trigger Output Programming Selection Table pg 4 Note these inputs are unidirectional and will not report a trouble condition to the FACP POL Notification appliances are connected to these regulated outputs see Application Guide pg 2 4 OUT2 UE s OUT3 Each power limited output will supply 2 5 amp Total supply current is 8 amp see note below Outputs are controlled by designated input 1 IN1 or input 2 IN2 Output Programming Selection oe Tabl 4 Maxi line Itage d tested with 2 5V
4. gen eral loop system trouble A common trouble input is provided for optional NC normally closed devices to report trouble to the FACP Two 2 FACP signaling outputs can be employed and directed to control supervision and power delivery to any combination of the four 4 outputs Specifications Agency Listings UL Listed Control Units for Fire Protective Signaling Systems UL 864 MEA NYC Department of Buildings Approved CSFM California State Fire Marshal Approved Factory Mutual Approved NFPA 72 Compliant Input Supervision AC fail supervision form C contact 1 amp 28VDC Factory set for 30 seconds with optional 2 5 to 3 hour delay setting field selectable nstant local AC trouble reporting relay form contact 1 amp 28VDC Battery presence and low battery supervision form C contact 1 amp 28VDC Power input 120VAC 60 Hz 5 amp Visual Indicators Two 2 Class A Style Z or two 2 Class B nput and output status LED indicators Style W Y FACP inputs Special Features Two 2 NC dry contact trigger inputs 2 wire horn strobe Sync mode allows audible Output notification appliances horns to be silenced Class 2 Rated power limited outputs while visual notification appliances strobes 24VDC 8 amp max total alarm current continue to operate 2 5 amp max current per output Temporal Code 3 Steady Mode Input to Output Separate 1 0 amp auxiliary
5. with synchronization capability 7 For connection of smoke detectors digital dialer Optional Hookup Diagram pg 7 Class A Style Z Class B Style W Y SW1 amp SW2 Settings For all Class B Style W Y hookups SW1 amp SW2 on the AL800LGK logic board must be open For all Class A Style Z hookups SW1 amp SW2 on the AL800LGK logic board must be closed Output Programming Selection Table Outputs must be programmed independently OUT1 OUT4 Switch Positions Function Descriptions ON OFF Output follows signal it receives from the corresponding input Input to Output Follower Mode 1 2 3 i e FACP Sync module maintains synchronization of notification appliance circuit Enables Temporal Code 3 signal generation output Temporal Codes Meds 3 d This mode will accept a steady or a pulsing input A steady output signal will be generated Spady Mode This mode will accept steady or pulsing input For the above modes Dip Switch 4 determines which Input controls AL800LGK Board the corresponding output Output Dip Switches Switch 4 in the ON position causes output s to be controlled by input 1 INPUT SELECT Switch 4 in the OFF position causes output s to be controlled by input 2 17 TEMPORAL 17 STROBE SYNC Sync Mode Selection Table CO IN gt 0UT SYNC Switch Positions Function Descriptions ON OFF This mode is designed to work with the Amseco series of h
6. 8 5 Contact manufacturer for current draws A 2 Relays Table A 3 below lists relays compatible with AL802ULADAJ AUX output Manufacturer Model Current mA PR 1 15 PR 2 30 PR 3 30 EOLR 1 30 R 10T 23 System Sensor RE 2 R 20T 40 R 24T 40 R 10E 23 R 14E 23 R 20E 40 R 24E 40 AL802ULADAJ Enclosure Dimensions 18 H x 14 5 W x 4 5 D 14 50 1 50 2 50 2 50 1 1 50 MD AN YY YY 1 25 41 00 1 50 4 125 l j 1 50 Jiu dl 1 09 1 50 AN z N YZ 2 50 AN YY 8 50 ZO o 6 00 0 0 0 O 0 O 000000 18 00 18 00 18 00 du piu z 1 1 00 1 00 t 1 00 1 501 14 50 2 75 4 50 4 50 2 75 LO Altronix is not responsible for any typographical errors m imu 140 58th Street Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 IME web site www altronix com e mail info altronix com Lifetime Warranty Made in U S A MEMBER IIAL802ULADAJ G26J AL802ULADAJ 232235
7. AL802ULADAJ NAC Power Extender Installation Guide See Application Guide for additional information Rev 042010 Altron IX AL802ULADAJ NAC Power Extender Overview The Altronix AL802ULADAJ is an extremely cost effective 8 amp remote power supply battery charger It may be con nected to any 12 or 24 volt Fire Alarm Control Panel FACP Primary applications include Notification Appliance Circuit NAC such as strobes and horns expansion support to meet ADA requirements It also provides auxiliary power to sup port system accessories The unit delivers electronically regulated and filtered 24 volt power to Class B Style W Y or Class A Style Z NAC loop circuits Additionally a separate 1 0A auxiliary output with reset for four 4 wire smoke detectors is available The 8 amp max alarm current can be divided between the four 4 outputs for powering NAC devices Each output is rated at 2 5 amp max and can be independently programmed for Steady Temporal Code 3 or Strobe Synchronization All outputs may be programmed for Input to Output Follower Mode output will follow input i e March Time Input March Time Output In non alarm condition independent loop supervision for Class A Style Z and or Class B Style W Y FACP NAC circuits is provided In the event of a loop trouble the FACP will be notified via the steered input input 1 or input 2 In addition there are common trouble output terminals NC C NO which are used to indicate
8. D Photoelectric 0 05 50 System Sensor 2112 24R Photoelectric 0 50 60 70 System Sensor 2112 24TR Photoelectric 0 50 60 70 System Sensor 2112 24T D Photoelectric w 135 Thermal 0 05 50 System Sensor 2112 24TSRB Photoelectric w 135 15 45 Thermal Supervisory Relay System Sensor 2312 24TB Photoelectric 0 12 50 System Sensor 2412 12 volt Photoelectric 0 12 TI System Sensor 2412AT 12 volt Photoelectric 0 12 58 System Sensor 2412TH 12 volt Photoelectric 0 12 77 System Sensor 2424 Photoelectric 0 10 41 System Sensor 2424TH Photoelectric 0 10 41 System Sensor 2451 Photoelectric 0 10 39 System Sensor 2451TH with B402B Base Photoelectric 0 10 39 System Sensor 2W MOD Loop Test Maintenance Mod 30 50 AL802ULADAJ A 1 Four 4 Wire Smoke Detectors cont Max Standby Alarm Smoke Detector Base Detector Type Current mA Current nA System Sensor 4W B 12 24 volt Photoelectric P 05 23 System Sensor 4WT B 12 24 volt Photoelectric w Therm 05 23 System Sensor 4WTA B 12 24 volt P Photo w Therm Sounder 05 35 System Sensor 4WTR B 12 24 volt P Photo w Therm Relay 05 35 P Photo w Therm System Sensor 4WTR B 12 24 volt SounderRelay 05 50 F Photo w Isolated System Sensor 4WITAR B 12 24 volt Therm Sounder Relay 05 50 System Sensor 2W MOD2 a 05 System Sensor RRS MOD 05 Module System Sensor 6424 Projected Beam 10 28 4 System Sensor Beam 1224 S Projected Beam 17 3
9. apter 1 1 5 2 5 G Multiply lines E and Total stand by AH AH H Alarm sounding period in hours H For example 5 minutes 0833 hours I Multiply lines E and H Total alarm AH AH J Add lines G and I Total stand by and alarm AH AH Multiply line J by 1 30 K 30 extra insurance to meet desired performance AH Total ampere hours required Units are capable of recharging 40 AH battery max If total ampere hour required exceeds 40 AH decrease AUX current to provide enough stand by time for the application AL802ULADAJ Appendix A UL Listed Compatible Devices A 1 Four 4 Wire Smoke Detectors Table A 1 below lists four 4 wire smoke detectors compatible with AL802ULADAJ AUX output Smoke Detector Base Detector Type System Sensor B112LP Base 0 12 36 System Sensor B114LP Base System Sensor B404B Base System Sensor DH100ACDC Photoelectric 0 15 0 70 System Sensor DH100ACDCLP Photoelectric 0 15 0 70 System Sensor DH100ACDCLPW Photoelectric 0 15 0 70 System Sensor DH400ACDCI Ionization Duct 25 95 System Sensor DH400ACDCP Photoelectric Duct 25 95 System Sensor 1112 24 D Ionization 0 05 50 System Sensor 1424 Ionization 0 10 41 System Sensor 1451 w B402B Base Ionization 0 10 39 System Sensor 2112 24ATR Photoelectric 0 50 60 70 System Sensor 2112 24AITR Photoelectric 0 50 60 70 System Sensor 2112 24
10. bes to provid f synchronizing the l coded h Sva Made and horn strobes to provide a means of synchronizing the Temporal coded horns D 2 2 3 4 1 synchronizing the one second flash timing of the strobe and silencing the horns registered trademark of of the horn strobe combination over a two wire circuit while leaving CooperWheelock strobes active Note The AL802ULADAJ will only synchronize horns horn strobes and strobes that contain synchronization capability Contact signal manufacturer for more detailed info The same synchronization mode must be selected for all outputs 4 AL802ULADAJ Note It is required to control visual notification appliances strobes via input 1 IN1 and audible notification appliances horns via input 2 IN2 This allows audible notification appliances horns to be silenced while visual notification appliances strobes continue to operate Amount of Notification Appliances per unit Amseco 27 per NAC System Sensor 32 per NAC Faraday 39 per NAC CooperWheelock 32 per NAC Gentex 32 per NAC Not to exceed a maximum of 2 5 amp per NAC Terminal Identification Table AL800LGK Logic Board Terminal T Legend Function Description These terminals connect to the 12VDC or 24VDC FACP notification appliance circuit outputs Class A Style Z or Class B Style W Y Input trigger voltage is 8 33VDC 5mA min Terminal
11. emory Battery connection non power limited Battery 1 Battery 2 AL802ULADAJ Reset Button Optional hookups 1 Battery and AC monitoring AC or Battery Fail condition will cause the common trouble input C FAULT NC to report back to the FACP via input 1 and input 2 The common trouble input may also be used for other optional supervisory monitoring To report AC and Battery Trouble connect the battery and AC Fail relay output shown in Fig 2a to the common trouble input 2 Dry contact input C DRY1 NC C DRY NC can be used to alarm output from an addressable module these inputs are unidirection and cannot report back to trigger module Connection to triggering devices must be made within 20ft of distance and using conduit for wiring 3 Auxiliary output AUX 24VDC at 1 amp max 4 AC Local NC C NO should connect to the host control panel for local annunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to remain inactive For optional hookups Fig 2b Maintenance Unit should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions the DC output voltage should be checked for proper voltage level 26 2 26 4VDC recommended range Battery Test Under normal load co
12. g 7 The LED s will extinguish Note If indicating circuits have been restored memory reset is not required for normal operation of the unit Optional Hookup Diagram Fig 2 CAUTION De energize unit prior to servicing For continued protection against risk of electric shock and fire hazard replace fuse with the same type and rating Replace fuse cover before energizing Do not expose to rain or moisture 22 Fuse Divider CS 9 2 5 3 o 9 e Fig 2b FO O Cover a is Wc Non Supervised g o P o EE a ET z o ON Wire St 286 Ie zO BB oloooo Enclosure 05 O HL Fig 2a to Door 82 2 a S o n d S DR UUW E 8g E 3 SO sil 8 9158 2 8 n ClO 4 i L el B P 9j ij lege 0 2 ELO 28165 Hp 3ESG BLO 8 BE 2 uS E ci Battery and AC Supervision Circuit power limited Trouble M
13. nditions check that the battery is fully charged Check specified voltage both at battery terminal and at the board terminals marked BAT to insure there is no break in the battery connection wires Fuses Check input and output fuses on the power supply board replace if necessary Input fuse rating is 8 amp 250V Output fuse rating is 15 amp 32V Note Maximum charging current is 3 2 amp Note Expected battery life is 5 years however it is recommended changing batteries in 4 years or less if needed 8 AL802ULADAJ Battery Calculation Worksheet Device Current Device Pind by Alarm Devices Current Current For each device use this formula This column x Thiscolumn Equals Current per number of devices AL802ULADAJ Stand by 90mA 90mA Current draw from battery Alarm 175mA 175mA A AL802 Current 90mA 175mA Auxiliary Devices Refer to device manual for current ratings Alarm Stand by mA mA mA Alarm Stand by mA mA mA Alarm Stand by mA mA mA B Auxiliary Devices Current must not exceed 1 amp Refer to device manual for current ratings Alarm mA OmA mA Alarm mA OmA mA Alarm mA OmA mA Alarm mA OmA mA Notification Appliances Current must not exceed 8 amp 8000mA OmA mA D Total alarm current mA mA E Total current ratings converted to amperes line D x 001 A F Number of standby hours 24 for NFPA 72 Ch
14. orns strobes and Amseco Sync 1 3 2 horn strobes to provide a means of synchronizing the Temporal coded horns Mode 4 synchronizing the flash timing of the strobe and silencing the horns of the horn strobe combination over a two wire circuit while leaving strobes active This mode is designed to work with the Faraday series of horns strobes and Faraday 2 4 1 3 horn strobes to provide a means of synchronizing the Temporal coded horns Sync Mode synchronizing the flash timing of the strobe and silencing the horns of the horn strobe combination over a two wire circuit while leaving strobes active This mode is designed to work with the Gentex series of horns strobes and Gentex D 1 2 horn strobes to provide means of synchronizing the Temporal coded horns Sync Mode ae oe Gentex is a registered trademark of 3 4 synchronizing the flash timing of the strobe and silencing the horns of the ec horn strobe combination over a two wire circuit while leaving strobes active This mode is designed to work with the System Sensor series of horns strobes System Sensor and horn strobes to provide a means of synchronizing the Temporal coded horns Sync Mode 1 2 4 3 synchronizing the one second flash timing of the strobe and silencing the horns of the horn strobe combination over a two wire circuit while leaving strobes active This mode is designed to work with the CooperWheelock series of horns strobes DU DUNT d horn stro
15. output Follower Mode maintains synchronization of Programmable supervised indicating circuit outputs notification appliances circuit Four 4 Class B Style W Y or Two 2 Class A Style Z or One 1 Class A Style Z and Two 2 Class B Style W Y see Application Guide Thermal and short circuit protection with auto reset Battery Backup Built in charger for sealed lead acid or gel type batteries Compatible with 12VDC or 24VDC fire panels Output loop supervision steered to input 1 or input 2 Signal circuit trouble memory helps identify intermittent loop problems Common trouble input and output Ground fault detection Automatic switchover to stand by battery when AC Fails Zero voltage drop when switching over to battery backup Added Features Unit includes power supply red enclosure cam lock and battery leads Enclosure Dimensions and Descriptions AL802ULADAJ 18 H x 14 5 W x 4 5 D Product Weight 19 165 AL802ULADAJ Power Supply Specifications AC Input 120VAC 60Hz 5 amp supplied by a maximum 15 amp dedicated branch circuit Four 4 regulated supervised NAC output circuits 24V DC 2 5 amp maximum current Output One 1 aux special application 24VDC power output circuit 1 amp non supervised total output current must not exceed current 8 amp in Alarm Condition Use two 2 12VDC 12AH or two 2 I2VDC 7AH batteries connected in series Battery S
16. tand by Alarm Current Consumption EOL Resistor end of line 2 2K 2200 ohm Altronix Model AL EOL22 included Ground fault maximum 90mA 175mA test impedance Stand by Specifications Stand by Batteries Stand by Time Total Amp Minutes Alarm Output Current Aux Output 24VDC 7AH 24 Hours 8 amp 5 minutes batteries in series WMA 24VDC 36AH 24 Hours 8 amp 5 minutes 1 amp Note Unit is equipped with 1 amp max auxiliary output AUX will remain battery backed up during power outage For loads connected to AUX please refer to battery Stand by Specifications above for ratings When loads are connected to AUX output during alarm condition the remaining outputs may not exceed 8 amp total alarm current example AUX 1 amp outputs up to 7 amp Installation Instructions Wiring methods shall be in accordance with the National Electrical Code NFPA 70 NFPA 72 ANSI and with all local codes and authorities having jurisdiction Product is intended for indoor use only Carefully review Application Guide for AL602ULADAJ AL802ULADA J ALI002ULADA J Power Supply Specifications pg 3 Stand by Specifications pg 3 Output Programming Selection Table pg 4 Sync Mode Selection Table pg 4 neutral Terminal Identification Table pgs 5 6 Fig 1 LED Status Indication Table pg 6 E
17. ted missing or removed A restored battery will report within 30 seconds LED Diagnostics AL800ADA Power Supply Board Red DC Green AC Power Supply Status ON ON Normal operating condition ON OFF Loss of AC Stand by battery supplying power OFF ON No DC output OFF OFF Loss of AC Discharged or no stand by battery No DC output AL800LGK Logic Board LED OFF ON BLINK LONG BLINK SHORT ON Normal Alarm Condition Trouble Condition Trouble Condition Memory ON Normal Alarm Condition Trouble Condition Trouble Condition Memory OFF Normal Alarm Condition Trouble Condition Trouble Condition Memory OFF Normal Alarm Condition Trouble Condition Trouble Condition Memory Input 1 Normal Alarm Condition Trouble Condition Input 2 Normal Alarm Condition Trouble Condition Fault Normal Alarm Condition AL802ULADAJ ndicates current trouble condition When trouble open short or ground occurs on a specific output the corresponding red output LED OUT1 OUT4 will blink The corresponding green input LED will blink as well Loop trouble will report within 30 seconds Indicates trouble condition memory When a trouble condition restores the units red output LED OUT1 OUT4 will blink with a shorter and distinctly a different duration The green input LEDs will be off normal condition To reset the memory depress the reset button Fig 2c p
18. to ground DC 24VDC 8 amp in alarm non power limited output AC FAIL Form C dry contacts used to instantaneously signal the loss AC to local annunciation NC C NO devices with AC present terminals marked NO and C are open NC and C are closed D When loss of AC occurs terminals marked NO and C are closed NC and C are open AC LOCAL Form dry contacts used to instantaneously signal the loss AC to local annunciation NC C NO devices with AC present terminals marked NO and C are open NC and C are closed When loss of AC occurs terminals marked NO closed and C are open Form dry contacts used to signal low battery voltage or loss of battery voltage BAT FAIL Under normal conditions terminals marked NO and C are open NC and C are closed NC C NO During a trouble condition terminals marked NO and C are closed and NC and C are open Fig 2 pg 7 BAT Stand by battery input leads provided Fig 2 pg 7 Power Board Parameter Specifications AC Fail condition will report approximately 30 seconds after loss of AC To delay report for 2 5 to 3 hours cut jumper AC DELAY on the Power Supply Board AC trouble output delay option If this mode is selected the Power Supply Board must be reset by removing all power to it for 30 seconds e Low battery condition will report at approximately 21 VDC Battery presence detection will report with in 180 seconds after battery remains undetec

Download Pdf Manuals

image

Related Search

Related Contents

n° 22 - Juillet 2007  Manuel d`utilisation - Finishing Brands logo  Energy Display Meter User Guide  Trust 20190 USB cable  (案) 高松市公共施設長寿命化指針  

Copyright © All rights reserved.
Failed to retrieve file