Home
        Emerson Liebert NXE 20kVA
         Contents
1.                                                                                                                                                                                                                                                                                                                                                                    2 4  2 4 1                                           Battery Power Cables    Connection Principles  The following notes  in conjunction with the diagrams  illustrate the broad principles to be followed  when fitting and connecting the majority of battery installations        22    Battery Installation       2 4 2    2 4 3    2 4 4    Fitting the Batteries    1     2     In general  at least 10mm  3 8   must be left unobstructed on all vertical sides of the battery  blocks to permit free air movement around the cells    Clearance should be allowed between the top of the cells and the underside of the shelf above  this  is necessary for monitoring and servicing the cells     When installing the batteries on racks always work from the bottom shelf upwards to prevent  raising the centre of gravity     Connecting the Battery    1     When the battery cabinet is installed on a raised floor the battery power cables and optional circuit  breaker control cables can be routed to the UPS cabinet via the floor of the cabinet  If the UPS and  battery cabinet are located adjacent to each other and located on a solid floor these cables can be
2.                        Supported Status Value  Units  Battery Time Remaining 563  min  Battery Voltage 546 9  Y  Battery Current  Charge Discharge  02 A  Battery Charge Percentage 99    Battery Temperature 24 3    C  Battery Charge Compensation False  Battery Test Result Unknown  Battery Charge Mode Float                                           Supported Alarms Status  Battery Under Test Normal  Load On Battery Normal  Charger Failed Normal  Low Battery   Shutdown Imminent Normal  Battery Fault Normal  Battery Contact Fail Normal  Battery Converter Over Temperature Normal  Battery Converter Over Current Normal  Battery Converter Fail Normal  UPS Load Joint Mode Normal                      Supported Settings Value Units     E  http   142 100 150 244 monitorfupsBattery htm       Aset 050  gt    Prerthons     AN ne NA KENEN LE NANA  1234       63    Options   For Assembly Inside the UPS Cabinet       8 1 4 Relay Card  The Relay card provides voltage free contact closures for remote monitoring of alarm conditions     Delivering On Battery  On Bypass  Low Battery  Summary Alarm  UPS Fault and On UPS signals   the easy to install card integrates with AS 400 computers  additional cable required  and other relay  contact monitoring systems     The Relay card is rated for 24 VAC VDC at 1A and supported in any of the three NX Intellislot bays   Table 26 Relay Card pin configuration                                                                      Pin Function Operation  1 UPS Faul
3.        RAM   Remote Alarm Monitor    NXAOCFXRAM Reguires RELAYCARD INT       Modem card    NXAOCFXMOD          Extended LBS box          NXAOUFXLBS             vi          SAFETY PRECAUTIONS    This manual contains information concerning the installation and operation of this Emerson Network  Power Liebert NX Uninterruptible Power System  UPS      This manual should be read before commencing installation    The UPS must be commissioned and serviced by an engineer approved by the manufacturer  or  agent     Failure to do so could result in personnel safety risk  equipment malfunction and invalidation of war     ranty     The Liebert NX has been designed for Commercial Industrial use only  and is not recommended for  use in life support applications     This is a low emission CLASS A Uninterruptible Power System  UPS  product  In a residential envi   ronment  this product may nevertheless cause radio interference  in which case  the user may be  required to take additional measures     Conformity and Standards    This equipment complies with CE directives 73 23  amp  93 68  LV Safety  and 89 336  EMC   with Aus   tralia and New Zealand EMC Framework  C Tick  and with the following product standards for Unin   terruptible Power System  UPS      lt  EN IEC   AS 62040 1 1   General and safety requirements for use in operator access area    lt  EN IEC   AS 62040 2   EMC requirements  Class A compliant     EN IEC   AS 62040 3   Performance requirements and test methods    For more d
4.      ee ce een ees 20  2 3 7 Moving the Battery Cabinets              e aa eee eaaa aa eaaa ae 20  ZIS     Cable ENEY ice aga a a ag E a a a an ole Seen tal a ER ats ete tls ga oh adie BA eh wae elite Boson uh 20  2 3 9 General Arrangement Drawings                Anna  21          2 4    2 5    3 0  3 1  3 2    3 3    3 4    4 0    5 0  5 1    5 2    5 3    5 4    Battery Power Cables  ri dd ae 22    2 4 1 Connection Principles  kira a nera KNA Aa Tk na 22  2 4 2 Fitting the Batteries                    ag Ba ANA Ka ABA ga a Da AA AR a Ba AN a b aaa Tg aa aai 23  2 4 8 Connecting the Battery    23  2 4 4 Battery Room Design    23  Battery Controls  amabas ARA BN A OS ad bed BA 23  UPS MULTI MODULE INSTALLATION         cocccocococoooocococococcoccococccocoooo c  y   24  General  osori eee ede aie hh ao a Bl NE REEL AOE EE AEE IES LRA EO Sel us 24  Paralleled UPS Modules          ii    25  3 2 1    Cabinet  Installation sn td a Ig le Na ap a a dence Ge 25  3 2 2 External Protective Devices                ii    26  3 23  Power Cables  ooo  a gress Be SAE ae D ene al a BEG BOIS  Bea    ego ae a zac 26  324  Control  Cables 4  dig ane ban odes NA A A Ged A eh ea Ft Raed ESAS a Be 27  Hot Standby UPS Modules               cc rererere eee e eee eens 27  331 Cabinet Installation ss    2 Ghat Secs eek Bw eee ew a es um Base Ka a a a Wis e ae 27  3 3 2 External Protective Devices                 inn 27  3390    Power Caples oct hovel a Wb Cheat ole ales ele  Be Shale bh ta teed ete eee
5.     Hi   O    i 1   P     NXe 10 20kVA Top View  Figure 21 Internal battery layout and connecting  TOP LAYER    BOTTOM LAYER    Layer 5    W501 2 pcs    Layer 4       Layer 3    Layer 2    Layer 1                                                    W506 CB2 5       N W504 CB2 3       W508 CB2 1       34    Installation Drawings       Figure 22 Internal battery layout       E       o                                                                                                                                                                                                                                     E                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       D     A  O D  151mm     O  x  O D  160mm 562mm  a CS D O  E    E     T A  G D    d 160mm      ca    O  iS e c    O    160mm  3 CS  L  gt  a C  T A    160mm  Battery  y  SS       gt   136mm             35    
6.     The earthing and neutral bonding arrangement must be in accordance with local and national  codes of practice     Identify and make power connections for incoming cables according to one of the two procedures  below  depending on the type of installation     Common Input Connections    4  For common bypass and rectifier inputs  connect the AC input supply cables between the mains  distribution panel and the UPS input  mA mB mC N terminals  and tighten the connections to  5Nm  M6 Bolt   Ensure correct phase rotation     Split Bypass Connections    5  Ifa split bypass configuration is used  connect the AC input supply cables to the rectifier input  busbars  nA mB mC N terminals  and the AC bypass supply cables to the bypass input   bA bB bC N terminals  and tighten the connections to 5 Nm  M6 Bolt   Ensure correct phase  rotation       NOTE  For split bypass operation  ensure that the linking busbars between bypass and rectifier input  are removed     The AC input and the AC bypass supplies must be referenced to the same neutral point     Output System Connections    6  Connect the system output cables between the UPS output  oA oB oC N terminals  and the  critical load and tighten the connections to 5 Nm  M6 Bolt   Ensure correct phase rotation     WARNING    If the load equipment will not be ready to accept power on the arrival of the commissioning  engineer  ensure that the system output cables are safely isolated at their ends        Single Module UPS Installation      
7.     gt   Load 5d System     gt       Battery       Records  Sout  kVA  Sout  kVA  Battery voltage  V   history log   Pout  kW  Pout  kW  Battery current  A   Qout  kVAR  Qout  kVAR  Battery temperature    C   Loadlevel   Single unit  no Remain Time Min   Crest factor parallel data Battery capacity      Battery boost charging  Battery float charging  Battery disconnected        Language       Settings       Command  gt    Choices for Display contrasi Battery maintenance test UPS version  display  Date format set Battery capacity test UPS model       System test  Stop testing       Communication address        When configured  input transformer voltages are    displayed on the front LCD  When not activated  the  values are hidden       When configured  output transformer voltages are  displayed on the front LCD  When not activated  the  values are hidden        52    Operator Control Panel and Display       7 1 5 Detailed Description of Menu Items  The description that follows refers to the graphic LCD monitor window shown on Figure 28     UPS System Window  This fixed pane window displays current time and date and identifies the UPS     its configuration and its status                 Table 21 UPS system window  Description Explanation  Liebert NX UPS family name  2005 10 22 YYYY MM DD  see Settings menu for other date formats   12 30 36 Current Time  24 hr HH MM SS format   020kVA 3x3 20kVA   UPS rated output  3 x 3   3 phase input and output        Configuration     Single  
8.    Figure 23 Single unit block diagram with split bypass input    SW1 D Maintenance Bypass           Static Switch    Sw1 C      Rectifier Inverter Static Switch       Bypass Input    UPS       AC Utility Input yy       CB1        Neutral Wire Battery    Charger         Battery        5 1 1 Split Bypass Input    Figure 23 illustrates the Liebert NX UPS in what is known as the split bypass configuration wherein  a separate power switch to a dedicated bypass power source that also feeds the maintenance bypass  line connects the static bypass line  Where a separate power source is not available  the bypass and  rectifier input supply connections are linked        36    Operation       5 1 2 Static Transfer Switch    The circuit blocks labeled Static Switch in Figure 23 contain electronically controlled switching cir   cuits that enable the critical load to be connected to either the inverter output or to a bypass power  source via the static bypass line  During normal system operation the load is connected to the  inverter  but in the event of a UPS overload or inverter failure  the load is automatically transferred  to the static bypass line     To provide a clean  no break  load transfer between the inverter output and static bypass line  the  static switch activates  connecting the load to bypass  To achieve this  the inverter output and bypass  supply must be fully synchronized during normal operating conditions  This is achieved through the  inverter control electronics  wh
9.   62    Options   For Assembly Inside the UPS Cabinet       8 1 3 OC Web Card   SNMP HTTP Network Interface Card    This network interface card provides all real time data and status information as SNMPv1 traps for  connection to a 10 100 baseT Ethernet network and in addition the same card will also transmit the  same status information and all measured parameters for display via a Web browser     This card is supported in the top  middle and bottom Intellislot bays     Figure 35 OC Web Card data summary window    F Liebert OpenComms Web Card   Microsoft Internet Explorer  File Edit View Favorites Tools Help    e         Back Forward Stop Refresh  Address  2  http   142 100 150 244    amp   EMERSON     Network Power monitor                                         5 Summary   Device Information  Yy    3 U    Legend  A Normal  EM Marginal Fautt  WN Absent          Output    Active Alarms         No Alarms Present          E  Copyright Liebert Corporation 2000 200 aa  D  Astart    8 KO       Geer thoms      winzip  Po     Enza manua     Gjexpense        lmerosorte      Ejtieberto  HALSUA 1229  Figure 36 OC Web Card battery data summary    2 Liebert OpenComms Web Card   Microsoft Internet Explorer    File Edit View Favorites Tools Help    Sa CA OA  Back    Forward Stop Refresh ft  Favorites Mail Edit                                                  ry  EMERSON     Network Power monitor   configure    support    Deven infonnatan  Battery  Updated  July 13  2004 12 34 05PM        
10.   battery charged  kW 1 6 1 8 2 2  ECO Mode  full load  battery charged  kW 1 3 1 4 1 4  No Load kW 1 3 1 3 1 3  Forced Air Cooling  front intake  back exhaust  L sec  m  hr  254  917           Input and output voltage 400VAC  battery chargea  full rated linear load       67       Technical Specifications                                                                            Table 33 Mechanical characteristics  Unit of  Rated Power  kVA Measurement 10 15 20        600x700x1400  Dimensions  WxDxH mm  in   23 9 16x27 5 8x55   Mass  Mass without batteries kg  Ib  180  397  204  450  204  450   Mass with internal batteries   with typical 12Ah battery  kg  Ib  550  1213  574  1265  574  1265   Pantone 877  Silver grey   Finish N A equivalent Becker Silver epoxy polyester powder 041   37 2  Protection Degree  IEC  60529  N A IP20  finger proof with front doors open or closed   Table 34 Rectifier AC input  mains   Unit of  Rated Power  kVA Measurement 10 15 20  1 380 400 415  Rated AC Input Voltage VAG  3 phase and sharing neutral with the bypass input   2 305V to 477V  input voltage To  erance VAC 304V to 208V  output derated below 70    Frequency 2 Hz 50 60Hz  tolerance 40Hz to 70Hz   kW KVA  full load  Power Factor  half load  0 99  0 98   kVA rated 3  Input Power  maximum 4  10 0  15 9  13 9  19 6  18 4  24 0   Input Current A rated 3  maximum 4  15  22  20  28  27  35   Harmonic Current 2  Distortion THDI   FL 3 3 3    E 10 seconds to reach full rated current  bed Bas sec  
11.   ina ia ead RS Pe r Ba ana ancy  Foe Bag pa td Haare le eal  a 66  TECHNICAL SPECIFICATIONS 5x25 resin Gavin ce cock Em Wha ie ese Sw ea Se ae 67  Conformityand  Standards    a A So Aaa NBA BEN eas    67       iii       Figure 1  Figure 1  Figure 2  Figure 3  Figure 4  Figure 5  Figure 6  Figure 7  Figure 8  Figure 9  Figure 10  Figure 11    Figure 12  Figure 13  Figure 14  Figure 15  Figure 16  Figure 17  Figure 18  Figure 19  Figure 20  Figure 21  Figure 22  Figure 23  Figure 24  Figure 25  Figure 26  Figure 27  Figure 28  Figure 29  Figure 30  Figure 31  Figure 32  Figure 33  Figure 34  Figure 35  Figure 36  Figure 37  Figure 38    FIGURES    Model number nomenclature             ii    vi  Residual current circuit breakers  RCCB  symbols    0 0 0 0    ccc eens 7  Auxiliary terminal block detail ask sosis kaa Bag geg BANK ene KK KE KERN NS 11  Input dry contacts  ti NGGE a aides A aie bp a a a Rs E KANE IE Burn 12  Output dry contacts and EPO wiring sirier trir AAAA na  13  Battery startion UR ne a A bE A AA ee a Ne Bac ed ee A HREM oO a 16  Single temperature sensor and monitor board U2         eens 20  Battery cabinet bottom cable entry location             rara 21  Battery cabinet with fuse or optional circuit breaker locations                            22  Battery tooni design A Bek Be hintaan AN Wickes wee cee ds 23  Emergency power off connections     0 0    susunane renne na 24  Typical 1 N system block diagram with common input supply  with separate batteries   an
12.   key to move the cursor to the menu at the top of the  screen     Press F2 and F3  left and right arrows  as needed to select the Language menu   Press F1  shift  to move the cursor to the data and settings area of the LCD   Use F2 and F3  up and down  to select the required language    Press the F4  enter  key to accept the language selection     Return to the main menu by repeatedly pressing F1  ESC  as needed  all text on the LCD will now  be displayed in the selected language     Aa A wh       47    Operating Procedures       6 10 Changing the Current Date and Time    To change the system date and time     6 11    1     Ore 3    From the main menu  press the F1  shift  key to move the cursor to the menu at the top of the  screen     Press F2 and F3  left and right arrows  as needed to select the Settings menu    Press F1  shift  to move the cursor to the data and settings area of the LCD    Use F2 and F3  up and down  to select the Date     Time option  then press F4  enter     Position the cursor on the row in which the date and time are displayed  then press F4  enter    Using the F2 and F3  up and down  keys  enter the current time and date information    Press F4  enter  to save the settings  then press F1  ESC  to return to the main menu     Command Password    Password protection is used to limit the control functions accessible to the operator  The default pass   word is 123456  This password provides access to UPS and battery test functions        48    Operator 
13.   passed between the cabinets via the lifting apertures located in the lower sides of the cabinets    In general it is recommended that the inter connecting cables be fitted to the batteries within  their particular level before fitting the inter level connecting cables  followed finally by the cables  to the circuit breaker    An insulating shroud should be fitted to each terminal after its connection has been made    When connecting the cables between the battery string ends to the optional circuit breaker always  connect the circuit breaker end of the cable first     Battery Room Design  Whatever the type of mounting system selected  the following conditions should be noted     Cell Layout   1   Whichever battery mounting system is used  the batteries should be arranged to prevent the pos   sibility of simultaneous contact with two exposed live parts having a potential greater an 150V   Where this is not possible  insulated terminal shields must be installed and insulated cables must  be used for connections    Service Platform   2   The service platform  or duckboard  must be slip proof  insulated from the floor and at least one  metre  39 in   wide    Connections   3   All connections must be as short as possible    Battery Protection Fuses Circuit Breaker   4   The battery circuit breaker is generally installed at the front of the battery room  See 2 5   Bat   tery Control for details on connecting the circuit breaker box available for the Liebert NX     Figure 9 Batter
14.   then verify the bypass voltage  and frequency presented to the UPS  Check the external bypass supply if it is found  to be faulty  If the utility is likely to trigger this alarm frequently  the bypass limit can be  changed a little larger through the configuration software according to the customer   s  agreement        This alarm is triggered by an inverter software routine when the inverter and bypass  waveforms are misaligned by more than 6 degrees in phase  This alarm resets  automatically once the condition is no longer true    Inverter Asynchronous 1  First check if the alarm    Bypass unable to trace    or    Bypass abnormal    occurs  If so   solve it first    2  Verify the waveform of the bypass voltage  If it is too distorted  ask the customer to  verify and seek any possible measurements        Inverter Fault Inverter output voltage beyond limits  Load transfers to bypass        The temperature of the inverter heat sink is too high to keep inverter running    This alarm is triggered by the signal from a temperature monitoring thermostat on the  inverter bridge heat sink    The UPS will recover automatically after a 5 minute delay from the disappearance of  the overtemperature signal    If the overtemperature condition is true  then check for and verify    1  high ambient air temperature    2  blocked cooling airway    3  any fan failure    4  prolonged inverter overload    Inverter Overtemp        Fan Fault At least one of the cooling fans has failed       At lea
15.  43 42 30 29 28 44  1  Input mains current listed for common rectifier and bypass AC input  For split input the rectifier current is 94  of the currents    listed    2  Non linear loads  switch mode power supplies  affect the design of the output and bypass neutral cables  The current  circulating in the neutral cable may exceed the nominal phase current  A typical value is 1 5 In    3  Protective earth cable  Connect each cabinet to the main ground system must follow the most direct route possible   The earth conductor shall be sized in accordance with the AC supply fault rating  cable lengths and type of protection  Typical  cross sectional areas are 2 5mm   10kVA   6mm   15kVA   10mm   20kVA   as per AS   IEC 60950 1   4  When sizing battery cables  a maximum volt drop of 4 VDC is permissible at the current ratings given in Table 1  The load  equipment is generally connected to a distribution board containing individually protected busbars rather than connected  directly to the UPS output  The output cables from paralleled units to the parallel distribution bus should be of same length so  as to optimise the sharing of current  Do not form coils  so as to minimise the formation of electromagnetic interference    5  For terminal location     refer to 4 0   Installation Drawings              A WARNING    Failure to follow adequate earthing procedures may result in electromagnetic interference or  in hazards involving electric shock and fire     Table 2 Distance from floor to
16.  Internal UPS Battery Connection    7  The battery consists of a series string connection of 5 x 8  or 10  x 12V 6 cell battery blocks     a     b   c   d    Ensure that the 8  or 10  battery blocks in each tier  tray  are interconnected   Connect the positive  neutral and negative cables to the UPS terminals   Plug in the cables between the tiers     Ensure correct polarity battery string series connections  i e   intertier and  interblock connections are from positive to negative terminals     WARNING    Hazardous Battery Terminal Voltage 480VDC    Ensure correct polarity of string end connections to the UPS terminals  i e   positive to  positive  negative to negative and neutral to neutral  but leave these UPS terminal cables  disconnected until connection is authorised by the commissioning engineer     Ensure correct polarity of string end connections to the battery circuit breaker and from the  battery circuit breaker to the UPS terminals  i e   positive to positive and negative to negative   but disconnect one or more battery cell links in each tier     Do not reconnect these links and do not close the battery circuit breaker before authorised by  the commissioning engineer     8  Refit all protective covers removed for cable installation        10    Single Module UPS Installation       1 7 Control Cables and Communication    1 7 1 Monitor Board Features   Based on your site   s specific needs  the UPS may require auxiliary connections to manage the battery  system  ex
17.  a Nan 4  L1  L2  L3  N L1  L2  L3  N  E E aa    Q1EXT 9 Q2EXT         QUPS eee A 5 PQBYP    Distribution Cabinet         See A  TO LOAD       25    UPS Multi Module Installation       Figure 12 Dry contacts  multiple UPS modules with distribution panel       Input Distribution                                                                      UPS N  M3 Board M3 Board M3 Board  X3 X3 X3  Ext  Maint  Ext  Out Ext  Maint  Ext  Out Ext  Maint  Ext  Out  TN MN NX  TN nan AN  4     Q1Ext Li Q2Ext ai QnExt  ues Distribution Panel aByp  _     To Load    3 2 2 External Protective Devices  Refer to the instructions in 1 0   Single Module UPS Installation     3 2 3 Power Cables    The wiring of power cables is similar to that of single module system  The Bypass and the Main input  sources must be referenced to the same neutral potential and input earth leakage monitoring devices   if installed  must be located upstream of the common neutral sinking point  Refer to the instructions  in 1 0   Single Module UPS Installation         NOTE  The length and specification of power cables including the bypass input cables and UPS output  cables should be the same  This facilitates load sharing when operating in bypass mode        26    UPS Multi Module Installation       3 2 4    Figure       3 3  3 3 1    3 3 2    Control Cables    Intermodule Control    Shielded and double insulated control cables available in lengths of 5  10 and 15 meters must be must  be interconnected in a ring configura
18.  aN y 28  Dual Bus  System  msi id MERASA SRG nds Sid bee dd Ade Ochs te AAA hes 28  SAA   Cabinet Tas ball abon  san atei AR Spotless aa KG ah Kaga ag Hache S09 a a ghee nenas giant 28  3 4 2 External Protective Devices                aaa e eea eaaa aee 29  34 3   Power Gables ap aa EA A A Na apa bai are aaa aga a aa a a a a A Ba si 29  3 4 47  Control Wirest it gang a A Ba jaka aaah a at do sods a a Teen 30  3 4 5 Extended Dual Bus Synchronization Option  DBS Interface Box                        30  INSTALLATION DRAWINGS 3 x doa bo be mkn dina Aaa 31  OPERATION 50 pure ere POLO os ABE bia ak eee ede ADA 36  INTO bles in kona    ii AE A ARA BBB KN e EN E ASA a 36  STD Split Bypass Input xe sede A ok nes A A BEN Dd a ga a NG 36  531 2 A Static Transfer Switch oc i053 ts doe CO HG once Sable Ol iS ati eh 08 37  5 1 3 Battery Temperature Compensation                ccc eee eea 37  5 1 4 Redundant Control Power Supply Board                             ahhh 38  blih Socket Outlet ma ati O wine 38  Multi Module UPS   1 N         coco  38  5 2 1 Features of NX Multi Module UPS Configurations o    39  5 2 2 Requirements for Paralleling of UPS Modules    o   n nananana ccc eee ee 39  Modes Of Operations  a an isa a he ae alae eed ead 39  DSL  Normal Mode oi das asana exe dre dd tds 39  5 3 2 Battery Mode  Stored Energy Mode     39  5 3 3 Auto Restart Mode                ee eee eee a ap gg  ah aba a aaa akar 39  9 9 4    Bypass Mode tit dale lense nag a dika dt IA e 40  5 3 5 Maintena
19.  batteries are protected against overcurrents through a DC compatible dis   connect device     UPS Output    Any external distribution board used for load distribution shall be fitted with protective devices that  discriminate with those used at the bypass input to the UPS and with the UPS overload characteris   tics  see Table 36      Power Cables    The cable design must comply with the voltages and currents provided in this section  follow local wir   ing practices and take into consideration the environmental conditions  temperature and physical  support media      For cable entry terminal  refer to Figure 19     A WARNING    Before starting the UPS  ensure that you are aware of the location and operation of the  external isolators that connect the ups input bypass supply to the mains distribution panel     Check that these supplies are electrically isolated and post any necessary warning signs to  prevent their inadvertent operation        Single Module UPS Installation       Table 1 Maximum steady state AC and DC currents                                                          Nominal Current  Amps Busbar Stud Size  Input Mains Current 12  With Full Battery Output Current  Input Output   Recharge at Full Load Bypass  3ph   N 3ph   N Cables External  UPS Battery at Hole battery   Torque   Rating End of Dia  Cables Load   KVA  380V   400V 415V   380V   400V   415V   Discharge   Bolt    mm   Bolts   Nm    10 22 21 20 15 14 13 22   15 33 32 31 22 21 20 33 M6 6 M6 5   20 44
20.  battery terminal voltage will exceed 400VDC and is hazardous     Eye protection should be worn to prevent injury from accidental electrical arcs   Remove rings  watches and all other metal objects    Use only tools with insulated handles    Wear rubber gloves     If a battery leaks electrolyte or is otherwise physically damaged  it must be replaced  stored in  a container resistant to sulfuric acid and disposed of in accordance with local regulations     If electrolyte comes into contact with the skin  the affected area should be washed  immediately with water     Preliminary Checks    Before installing the UPS  please carry out the following preliminary checks     1  Visually examine the UPS and battery equipment for transit damage  both internally and  externally  Report any damage to the shipper immediately     2  Verify that the correct equipment is being installed  The equipment supplied has an identification  tag on the back of the main door reporting  the type  size and main calibration parameters of the  UPS        Single Module UPS Installation       1 3  1 3 1    1 3 2    1 3 3    Location  UPS Room    The UPS and its internal battery is intended for indoor installation and should be located in an envi   ronment with clean air and with adequate ventilation to keep the ambient temperature within the  specified operating range  see Table 31      All models in the Liebert NX UPS range are air cooled with the aid of internal fans  Cold air enters  through ventilation g
21.  connected to the normally open or normally closed remote stop  switch between these two terminals using shielded cable  see Figure 4 and Table 7   If this function  is not used  terminals X2  3 amp 4 must be opened and X2  1 amp 2 must be closed     Table 7 EPO input contact relays                         Position Name Description   J28 1 EPO_NC EPO Activated when shorted to J28 2  J28 2 EPO_NC EPO Activated when shorted to J28 1  J28 3 EPO_NO EPO Activated when opened to J28 4  J28 4 EPO_NO EPO Activated when opened to J28 3          NOTE     The emergency stop action within the UPS shuts down the rectifier  inverter and static bypass   It does not internally disconnect the input power supply  To disconnect ALL power to the UPS   open the upstream feeder breaker s  when the remote EPO is activated     NOTE    Normally closed EPO     X2  1 2  these terminals are supplied factory linked on the monitor  board     X3 Ancillary Control and Alarms  X3 IN DRY  Environmental  Battery Ground Fault and Generator Contacts    The UPS accepts external signalling from voltage free  dry  contacts connected to finger proof  push   in terminal X3 IN DRY  Subject to prior software programming  the signalling is accepted by the UPS  when connection between the relevant terminal and the  12V terminal is altered  Cables connected to  X3 IN DRY must be segregated from power circuits  for screening purposes   double insulated and of a  typical 0 5 to 1mm  cross section area for maximum runs betwe
22.  connection point on the equipment                   UPS 10 20 kVA  Minimum Distance  UPS mm  in    Rectifier A C  Input supply 284  11 1 5   Bypass A C  Input supply 284  11 1 5   UPS Output A C  369  14 1 2   Battery Power 369  14 1 2   Auxiliary cables  Monitor board  U2  1104  43 1 2                    Single Module UPS Installation       1 6 1    Cable Termination    NOTE   The operations described in this section must be performed by authorised electricians or  qualified technical personnel  If you have any difficulties  do not hesitate to contact our  Customer Service and Support Department  See the back page of this manual for contact  information     Once the equipment has been finally positioned and secured  connect the power cables as described in  the following procedure     Refer to the appropriate cable connection drawing in 4 0   Installation Drawings     1  Verify that the UPS equipment is isolated from its external power source and all the UPS power  isolators are open  Check that these supplies are electrically isolated and post any necessary  warning signs to prevent their inadvertent operation     2  Open the door to the UPS cabinet and remove the front protective cover to gain access to the  connections bars     3  Connect the safety earth and any necessary bonding earth cables to the copper earth busbar  located on the floor of the equipment below the power connections  All cabinets in the UPS must  be connected to the user   s ground connection     NOTE
23.  following general battery safety precautions and warnings should be observed at all  times     A battery can present risk of electric shock or burn from high  short circuit currents       The full nominal string voltage  when the battery blocks are interconnected  is 480VDC   which is hazardous      Only qualified personnel should install or service batteries      Eye protection should be worn to prevent injury from electrical arcs    e Remove rings  watches  necklaces  bracelets and all other metal objects     Use only tools with insulated handles      Wear rubber gloves and a rubber apron when handling batteries       Ifa battery leaks electrolyte or is otherwise damaged  it should be placed in a container  resistant to sulfuric acid and disposed of in accordance with local regulations         If electrolyte comes into contact with the skin the affected area should be washed immedi   ately with plenty of clean water       Batteries must always be disposed of according to local environmental laws       When replacing batteries  use the same number and type that were originally fitted       Disconnect charging source before connecting or disconnecting battery terminals       Determine whether the battery is inadvertently grounded  If it is inadvertently grounded   remove the source of the ground  Contact with any part of a grounded battery can result in  electrical shock        18    Battery Installation       2 3 Battery Cabinet    2 3 1 Introduction    This cabinet can als
24.  ins dt Gas 60  Battery ground fault detection set connections           eee ene nes 61  Redundant power module fan set    62  Communication bays and cable location    62  OC Web Card data summary Wide 63  OC Web Card battery data summary           0  na 63  SiteNet MultiPort4 Intellislot pin configuration               eee nes 65  OGAH Web card rap a tie ya he ela es MR tra neo yas ha ea E eve cent ica Gack Seats a ee eGo ean A 66          Table 1   Table 2   Table 3   Table 4   Table 5   Table 6   Table 7   Table 8   Table 9   Table 10  Table 11  Table 12  Table 13  Table 14  Table 15  Table 16  Table 17  Table 18  Table 19  Table 20  Table 21  Table 22  Table 23  Table 24  Table 25  Table 26  Table 27  Table 28  Table 29  Table 30  Table 31  Table 32  Table 33  Table 34  Table 35  Table 36    TABLES    Distance from floor to connection point on the equipment            0    ees 8  Maximum steady state AC and DC currents                      eee eens 8  Input idty contacts at  XB    A KAE a ieee R E A eR a EN a Re a 12  Maintenance bypass cabinet Interface    12  External circuit breaker interface                 ii    13  Output dry contatt relay  nee dd es E A ARE EE BN 13  EP Oanput contact rolas e haters o s ND eden san a a a ab  14  Input dry contact Telay S5 sr ag GA BE GENEA GN  TB EN eee Oe Ra BE eee BE Ng eee Gg 14  Dimensions and weight          0  aa eaaa aaa aa aa eaaa eaaa aaa 19  UBS operatineimodes A lan sadap a Sas da a td aia bce tut dae o were ng 42  Rotar
25.  installation must be segregated from all but appropriately qualified maintenance  personnel by locating the cells in a key lockable cabinet or in a purpose designed  dedicated battery  room  When the batteries require maintenance  these precautions must be taken         The rotary switch must be turned to Maint  position       The input circuit breaker  CB1  must be opened     The ANDERSON connector must be disconnected      E  E    NOTE  The fuse on the battery EMI board  UHK241A2 PCB  is 600VDC 30A  High Speed Fuse    NOTE    Full safety instructions concerning the use and maintenance of UPS batteries are provided in  the appropriate battery manufacturers manuals  The battery safety information contained in  this section relates to key considerations that must be taken into account during the  installation design process and might affect the design outcome depending on localised  conditions     WARNING    Hazardous battery voltage present behind covers    No user serviceable parts are located behind covers that require a tool for their removal  Only  qualified service personnel are authorised to remove such covers    When using internal batteries in 10 to 20kVA units  the batteries are always connected  through power fuses to the UPS and to the segregated terminal bars available for connection  to an external battery     Isolate any internal battery connections before attempting to access the segregated terminal  bars available for connection to an external battery     The
26.  lIf a split bypass is used  install separate protective devices for the rectifier and for  the bypass in the incoming mains distribution panel         NOTE  Rectifier and bypass input sources must be referenced to the same neutral potential     NOTE  For IT power systems  four pole protective devices must be used  external to the UPS  both  upstream of the input distribution panel and downstream  toward the load         Single Module UPS Installation       Earth Leakage  RCD    Any residual current detector  RCD  installed upstream of the UPS input supply must be       sensitive to DC unidirectional pulses  Class A     insensitive to transient current pulses  and    must have an average sensitivity  adjustable between 0 3 and 1A     Figure 1 Residual current circuit breakers  RCCB  symbols    1 5 2    1 5 3    1 6    ON  AN    To avoid false alarms  earth leakage monitoring devices when used in systems with split bypass input  or when used in paralleled UPS configurations  must be located upstream of the common neutral  sinking point  Alternatively  the device must monitor the combined four wire rectifier and split   bypass input currents     The residual earth current introduced by the RFI suppression filter inside the UPS is greater than  3 5mA and less than 300mA  Liebert recommends verifying the selectivity with all other differential  devices both upstream of the input distribution board and downstream  toward the load      External Battery    The UPS and its associated
27.  mode        Battery Period Testing    Automatic periodic battery maintenance discharge test  20  capacity discharge        Batt  Capacity Testing    User initiated battery capacity discharge test  100  capacity discharge        Batt  Maint  Testing    User initiated maintenance discharge test  20  capacity discharge        UPS System Testing    User initiated UPS self test       Inverter in Setting    Inverter starting up and synchronising       Rectifier in Setting    Rectifier starting up and synchronising       MBP T cabinet Fan Fault    Maintenance bypass cabinet fans fault        Ext Input TX Overtemp    External Input Isolation Transformer Over Temperature       Ext Output TX Overtemp    External Output Isolation Transformer Over Temperature       Battery Room Alarm    Environment in Battery Room Needs Attention       Rotary Sw  Test Pos     Rotary switch is in test position        Rotary Sw  Normal Pos     Rotary switch is in normal position        Rotary Sw  Bypass Pos     Rotary switch is in bypass position        Rotary Sw  Maint  Pos     Rotary switch is in maintenance position        Battery Contactor Open    Battery Contactor Open       Battery Contactor Close    Battery Contactor Closed       Battery Reverse    Connect the battery again and check the wiring of batteries       No Battery    Check the battery and the wiring of batteries       Auto start          After UPS was shutdown at EOD  inverter auto starts when utility restore          58       Operator Co
28.  rules  the following requirements apply    1  All UPS modules must be of the same rating and must be connected to the same bypass source   2  The bypass and the main input sources must be referenced to the same neutral potential     3  Any RCD  Residual Current monitoring device  if installed  must be of an appropriate setting and  located upstream of the common neutral bonding point  Alternatively  the device must monitor  the combined 4 wire rectifier and split bypass input currents of the system  Refer to the High  Leakage Current Warning on page 1    4  The outputs of all UPS modules must be connected to a common output bus         NOTE  Optional isolation transformers are available for applications where sources do not share the  same neutral reference or where the neutral is not available     Modes of Operation    The NX UPS is an on line  double conversion  reverse transfer UPS that permits operation in these  modes      Normal Mode  Battery Mode  Stored Energy Mode   Auto Restart Mode  Bypass Mode  Maintenance Mode  Manual Bypass   ECO Mode  Parallel Redundancy Mode  Hot Standby Mode    Frequency Converter Mode    Normal Mode    The UPS inverter continuously supplies the critical AC load  The rectifier charger derives power from  the AC mains input source and supplies DC power to the inverter while simultaneously FLOAT or  BOOST charging its associated backup battery     Battery Mode  Stored Energy Mode     Upon failure of the AC mains input power  the inverter  whic
29.  single UPS   y quency  0 1 to 1 0Hz sec  paralleled UPS                 EN 50091 3  1 4 58  crest facto    PO  Es    r3 1    output voltage within half a cycle     Factory set to 400V     380 or 415V selectable by commissioning engineer   Factory set to 50Hz  60 Hz selectable by commissioning engineer  Frequency converter operation also selectable     IEC 62040 3   EN 50091 3 also for 0 100 0  load transient  Transient recovery time  return to within 5  of steady state       69          Technical Specifications                                                                   Table 37 Bypass mains input  Unit of  Rated power  kVA Measurement 10 15 20  380 400 415 V  Rated AC Voltage   VAC three phase four wire  sharing neutral with the rectifier input  and providing neutral reference to the output  Rated Current  380V A 15 23 30  400V A 15 22 29  415V A 14 21 28  135  long term  Overload Capacity   170  10 min  1000  100 ms  Upstream Protection  N A Thermomagnetic circuit breaker  rated up to 125   Bypass Line  by others  of nominal output current  IEC 60947 2 curve C   Current Rating of Neutral Cable A 1 7xIn  Frequency 2 Hz 50 60  Transfer Time  between Synchronous transfer   lt  0 5  bypass and inverter  ms Asynchronous transfer  default   15 ms  50 Hz   13 3 ms  60 Hz   yp or 40  60  80  100 ms  selectable  Upper limit   10   15 or  20  default  15  Bypass Voltage Tolerance   VAC Lower limit    10   20   30 or  40  default   20   delay time to accept steady bypass voltag
30.  will shut down and the battery is isolated to avoid further battery discharge  EOD is  settable from 1V to 1 9V per cell       Battery Low Warning Time   Settable between 3 and 60 minutes  The default is 5 minutes     5 4 2 Advanced Functions  Software Settings Performed by the Commissioning Engineer     5 5    Battery Self Test and Self Service    At periodic intervals 20  of the rated capacity of the battery will be discharged automatically at a  rate equal to 15   kW  of the rated UPS  kVA  capacity  During discharge the rectifier provides the  balance necessary to feed the load  The minimum amount of load must exceed 20  of the nominal rat   ing of the UPS module  If the load is less than 20   auto discharge cannot be executed  The periodic  interval can be set from 30 to 360 days  The periodic testing can also be inhibited         Conditions   Battery fully charged  load 20 100  of rated UPS capacity      Trigger   Manually through LCD panel or automatically   lt  Battery Self Test Interval   30 360 days  default setting is 60 days     Battery Protection  settings by commissioning engineer   Battery Undervoltage Pre warning    The battery undervoltage pre warning occurs before the end of discharge  After this pre warning  the  battery should have the capacity for 3 remaining minutes discharging with full load  The time is user  configured from 3 to 60 minutes     Battery End of Discharging  EOD  Protection    If the battery voltage is lower than the EOD  the battery con
31. 2V Power                   1   Must be configured by configuration software before becoming active   2   When activated  the charger current can be limited  via software  to a percentage of the full charger current  0 100     3   Activating this feature turns the battery charger off     1 8 2 Maintenance Bypass Cabinet Interface  J26 and J30 are the MBC interface   Table 4 Maintenance bypass cabinet interface                                        Position   Name   Description   J26 1 TIT  Input transformer overtemperature  NC   J26 2 AUK     Reserved   J26 3  12V    12V Power   J26 4 GND Power Ground   J30 1 FUSE   Reserved   J30 2 F_FAN   Fan Fail Alarm  NC    J30 3 T OT    Output Transformer Overtemperature  NC   J30 4 AUX_O   Reserved       1  Must be configured by software before becoming active    NOTE    All auxiliary cables must be double insulated  Wire should be 0 5   1 5mm   16 20AWG  stranded     2       12    Single Module UPS Installation       1 8 3 External Circuit Breaker Interface  J10 is the interface to any external battery circuit breaker  BCB    Table 5 External circuit breaker interface                            Position   Name   Description   J10 1 DRV   BCB Driver Signal   Output  N O     J10 2 FB BCB Contact State   Input  N O     J10 3 GND   Power Ground   J10 4 OL BCB On Line   Input   This pin will become active when  BCB interface is connected   N O         NOTE    All auxiliary cables of terminal must be double insulated  Wire should be 0 5 1 5
32. 5  with  24 hr safety timeout  selectable 8 30 hr     boost mode inhibit also selectable       End Of Discharge    V cell  VRLA     1 63 V cell  selectable from 1 60 1 90 V cell  Auto Inverse EOD voltage x discharge current mode   The end of discharge voltage increases at low discharge currents         2 4 V cell  selectable from 2 3 2 4V cell                    Battery Charge V cell Constant current and constant voltage  IU  charge mode  Programmable auto trigger or inhibit of boost mode   Battery Charging Power kW 2 5 5 5   max current  adjustable  A 3 75 7 5 7 5               At low input voltage the UPS recharge capability increases with load decrease  up to the maximum capacity indicated                                      Table 36 Inverter output to critical load  Unit of  Rated Power  kVA  kW  Measurement 10  8  15  12  20  16    380 400 415 V   Rated AC Voltage   VAC  three phase  four wire with neutral referenced  to the bypass neutral    Frequency 2 Hz 50 60   110  for 60 min  Overload   Rated a     gt 150  for 200 msec  Fault Current   Rated 340  current limitation for 200 msec  Non linear load capability     Rated 100   Neutral current capability   Rated 170   Steady state voltage stability   os Hoos aba ada d   Transient voltage response       5  Total Harmonic Voltage        3  Distortion  THDV  Yo   1  linear load      4  non linear load       Synchronisation   Window Rated freguency je T AN     0 5 to  1 Hz sec  de Arda ge rate Hz sec selectable 0 1 to 3Hz s 
33. Control Panel and Display       7 0 OPERATOR CONTROL PANEL AND DISPLAY       7 1 Introduction    The operator control panel and display is located on the front door of the UPS  The panel is the access  point for operator control and monitoring of all measured parameters  UPS and battery status and of  event and alarm logs     Figure 27 UPS control and display panel    The operator control panel is divided into three functional areas    Mimic Power Flow Chart    O6    Status    Output    Graphic LCD monitor with menu keys       Table 12 UPS control and display panel components    Direct Access keys    INVERTER ON INVERTER OFF             FAULT CLEAR SILENCE ON OFF       Component      Function    Button       Function             1 Rectifier  Input AC to DC  EPO Emergency Power Off button  Battery  DC Back up  Inverter ON Inverter start button  Bypass Input Inverter OFF Inverter shutdown button  Inverter  DC to AC  Fault Clear Reset button       Load  AC Output     Silence On Off    Audible Alarm Mute       UPS Status and Alarm indicator       Audible Alarm  Buzzer _    F1 F4  Help    LCD Menu keys          COIN  OD  om  AJOJN       Emergency Power Off Button cover                49    Operator Control Panel and Display       7 1 1 Mimic Power Flow    The LEDs mounted on the mimic flow chart represent the various power paths and current UPS oper   ational status     Table 13 Rectifier indicator   1                Green Rectifier in Normal Operation   Flashing Input AC Normal  
34. ECO  Master  Slave or Unit   1    Single   single double conversion unit   ECO   single stand by unit with double conversion fall back  Master   master in a 1 1 Hot Stand By system   Slave   slave in a 1 1 Hot Stand By system   Unit   1   of max 6 double conversion units in a parallel system        Status   Normal  Warning or Fault          Normal   UPS operating Normal  Warning   System attention required  e g  AC Input Failure  Fault   UPS Fuse or Hardware Failure       Menu and Data Window    Use the horizontal arrow keys to navigate between any of the selectable menu and data windows                                                        Table 22 Descriptions of UPS menus and data window items  Menu  Type Item Type Explanation  L N voltage  V  Phase voltage  L N current  A  Phase current  Mains Frequency  Hz  Input frequency   input   L L voltage  v Line line voltage  Power factor Power factor  L N voltage  V  Phase voltage  TX Input Ng  L L voltage  V  Line line voltage  L N voltage  V  Phase voltage  Bypass Frequency  Hz  Bypass frequency  L L voltage  A  Line line voltage  L N voltage  V  Phase voltage  L N current  A  Phase current  Output Frequency  Hz  Input frequency  L L voltage  V  Line line voltage  Power factor Power factor  L N voltage  V  Phase voltage  TX Output    L L voltage  V  Line line voltage  Sout  KVA  Sout  Apparent power  Pout  kW  Pout  Active power  Load Qout  kVAR  Qout  Reactive power  Loadlevel   The percent of the UPS rating load  Crest facto
35. Io  Liebert            POWER AVAILABILITY    Liebert NX     USER MANUAL    10 20kVA    50 60Hz  400V       4          EMERSON     Network Power          1 0  1 1  1 2  1 3    1 4    1 5    1 6    1 7    1 8    2 0  2 1  2 2  2 3    TABLE OF CONTENTS    SINGLE MODULE UPS INSTALLATION    aaa aa eaaa aaa aaa aaa aa aaa 3  TAtroductiON es et GN ABANGAN ee KANG NE KAG  WS AKNG AA AKE DR A A a 3  Preliminary  Check 4 eyed ccs an ana AA Ga a aa NE Wana a BANG Age a ag BAP ES ni KAN uu 3  LOCATION aran aa D a a Ca A ROAR BIG AT ts te dt BE R NG Doe 4  LIL UB Rooms Ben Bee LAN sae We at s  ONES  Siem Se wake eg eed he erate a e ted 4  1 3 2 External Battery Room    4  1333 Storan E O a Gg coup trea SMart A adi a  ee te tla Cade Maat elec ag aia Dei 4  Position Gv  5  ak eS RAE a a bed Ae Bl AA A teh Ave aie ae Soe ted A Ba we 5  PAT  System  Cabinets  a ana KA oe dc A a Maca ed data age sete hs Ma bg BB 5  ALDO LO 2OKV ASU PS rina sa e e aa a tae baie tates eee OO nee das 5  1 4 9 Moving the  Cabinets sais  00105000201 BAT a WA Mags oie BAR Nate beard es 5  O Pe a E a Ba ON gue dba een Us apd Bartel RE Ba E dome Maude hap ca 6  14195  SACCESS ag esse sce al aga dd eels cido Sate  econ E Baa igre a a E ya GE A Rea  E A EA aia Gs 6  14 6  Final Positioning onta nan ged grana  Pads ede a Baja at a Sas Gan gg pa Mead ang ido Tenaga 6  LA   Floor Anchoting sit si a dt Tn SP gg Aa Bebe saia 6  1 478       Cable Entry  vio sa d baba tt AN ata an Tan E a date NN dt 6  External Protective Devi
36. Operation       5 0 OPERATION    A WARNING    Hazardous Mains and   or Battery Voltage present behind covers     No user serviceable parts are located behind covers that require a tool for their removal  Only  qualified service personnel are authorised to remove such covers        5 1 Introduction    Liebert   s NX    Uninterruptible Power System system provides continuous  high quality AC power to  your business critical equipment  such as telecommunications and data processing equipment  The  NX UPS supplies power that is free of the disturbances and variations in voltage and frequency com   mon to utility power  which is subject to brownouts  blackouts  surges and sags     The NX utilizes the latest in high frequency  double conversion pulse width modulation  PWM  tech   nology and fully digital controls to enhance its reliability and increase the ease of use     The standard NX consists of the UPS and internal batteries in a compact  single cabinet     As shown in Figure 23  the AC utility source is input at CB1 and the rectifier converts the AC utility  into DC power  The inverter converts that DC power from the utility   or DC power from the batteries     into AC power for the load  The batteries power the load through the inverter in the event of a  power failure  The utility source can also power the load through the static bypass     If maintenance or repair of the UPS is necessary  the load can be switched without interruption in  service to the maintenance bypass  
37. PS       EN 50091 3   IEC 62040 3   AS 62040 3  VFI SS 111           The product standards in Table 30 incorporate  standards for safety  IEC EN AS60950   electro    relevant compliance clauses with generic IEC and EN  magnetic emission and immunity  IEC EN AS61000    series  and construction  IEC EN AS60146 series and 60529                                                                                             Table 31 Environmental characteristics  Unit of  Rated power  kVA Measurement 10 15 20  Acoustic Noise Level at 1 Meter  39 in  dBa 51 0 51 5 51 6   lt 1000m  3280 ft  above sea level  Altitude of Operation m  ft  de rate power by 1  per 100m 328 ft  between  1000 and 2000 m  3280 and 6560 ft   Relative Humidity   0 to 95  non condensing  0 to 40  32 104     Operating Temperature   C    F  Battery life is halved for every 10    18    increase  above 20    68     Storage Transport Temperature for UPS   C    F   20 to 70   4 to 158   Recommended Battery Storage   C  F   20 to 30   4 to 86  F   Temperature  20  C  68  F  for optimum battery storage   Table 32 Overall efficiency  heat losses and air exchange  Unit of  Rated Power  kVA Measurement 10 15 20  Normal Mode  dual conversion    90 4 91 2 91 3  ECO Mode   93 2 94 2 94 7  Inverter Efficiency  DC AC    battery at nominal voltage 480VDC and full rated linear load   Rated Power  kVA 10 15 20  Battery Mode   91 3 91 7 92 0  Heat Loss  amp  Air Exchange  Ventilation   Rated Power kVA 10 15 20  Normal Mode  full load
38. be configured as    distributed redundant    systems with inde   pendent outputs that nevertheless are synchronised through a Load Bus Synchroniser  LBS  so that  critical loads can be seamlessly transferred from one system to another  See 5 3   Modes of Opera   tion for more information        38    Operation       5 2 1    5 2 2    5 3    5 3 1    5 3 2    5 3 3    Features of NX Multi Module UPS Configurations   1  The hardware and firmware of single module UPS units is completely compatible with the  requirements of a multi module system  Multi module configuration is achieved merely through  settings in configuration software     2  Parallel control cables are connected in a ring  providing both performance and redundancy   Dual bus control cables are connected between any two UPS modules of each bus  The intelligent  paralleling logic provides the user with maximum flexibility  For example  shutting down or  starting up UPS modules in a parallel system can be done in any sequence  Transfers between  Normal and Bypass modes of operation are synchronised and self    ecovering e g  following  overloads and their clearance     3  The total load of the multi module system can be queried from each module s LCD display     Requirements for Paralleling of UPS Modules    A group of paralleled modules behave as if it were one large UPS with the advantage of presenting  higher reliability  In order to assure that all modules are equally utilised and to comply with relevant  wiring
39. but rectifier not operating   Green   Red Rectifier Failed   Off Rectifier Not operating  Input AC Not Available or out of normal range                Table 14 Battery indicator   2          Green Battery Normal  but discharging and powering the load  Flashing Battery End of Discharge pre warning  Green       Battery abnormal  Failed  Absent or Polarity Reversed  or Battery  Red Converter abnormal   Failed  overcurrent  overtemperature                 Off Battery and Converter Normal  Battery charging        Table 15 Bypass indicator   3             Green Load on Bypass power  Red Bypass not available  out of normal range or Static bypass switch fault   Off Bypass Normal  load not on bypass          Table 16   Inverter indicator   4                Green Inverter Normal and powering the load  Flashing Inverter ON  starting up  synchronising   Green or standing by  ECO mode    Red Inverter failed   Off Inverter not operating       Table 17 Load indicator   5             Green UPS output ON and Normal  Red UPS output ON and Overloaded  Off UPS output OFF        Table 18 Status  Alarm  indicator   6             Green Normal Operation  Yellow UPS Warning e g  AC Input Failure  Red UPS fault e g  Fuse or Hardware failure                7 1 2 Audible Alarm  Buzzer   UPS activity is accompanied by the following sounds  Table 19 Audible alarm key    Single beep   Direct Access key acknowledgement          One beep UPS Warning e g  AC Input Failure  per second       Continuous   Fault 
40. by system  the master must be turned on first     External Protective Devices  Refer to the instructions in 1 0   Single Module UPS Installation        27    UPS Multi Module Installation       3 3 3    Power Cables    The wiring of power cables is similar to that of single module system except that the output of the  upstream UPS is fed into the bypass input of the downstream UPS  and the load is fed by the down   stream UPS through its inverter or bypass  The bypass and the main input sources must be refer   enced to the same neutral potential and input earth leakage monitoring devices  if installed  must be  located upstream of the common neutral sinking point  Refer to the instructions in 1 0   Single Mod   ule UPS Installation     No control wires other than those specified for the single module configuration are required     Figure 14 Hot standby configuration    3 4  3 4 1    INPUT DISTRIBUTION                   UPSTREAM DOWNSTREAM  Mains L1  Bypass L1  Mains L1  Bypass L1   L2  L3  N L2  L3  N L2  L3  N L2  L3  N       RECTIFIER  STATIC         oa oo E E Pein matah    L1  L2  L3  N    TO LOAD    Dual Bus System    Cabinet Installation    The Dual Bus System consists of two independent UPS configurations each consisting of one or more  UPS modules  Dual Bus Systems are high availability configurations suitable for loads with multiple  input terminals  For single input loads an optional Static Transfer Switch may be added and the stan   dard Load Bus Synchroniser activa
41. ces               ii    6  15 1  Rectifier and Bypass  Imputado Re hg wae 6  1 5 2   Exter  al Ba tye ty iiss ecco  RDA ESA RR RA TS A AE FORE CDI 7  1 95 95 UPS Outputs ura ds Ba a rs ld mana anang 7  Power Cables  oir A oh tht A a TA A 7  1 61    Cable Terminator ad 9  Control Cables and Communication              inn  11  1 7 1 Monitor Board Features ina eame daaa aa i eee eee een aan meg a 11  Dry Contact s mui as Pros ara 12  1821    Input Dry Contacts  ses a a Bae ee a then oo 12  1 8 2 Maintenance Bypass Cabinet Interface                 or 12  1 8 3 External Circuit Breaker Interface                 ii    13  1 84    Output Dry  Contacts aana eke b kag Kan BI a 13  1 8 5 Emergency Power Off Input    14  1 8 6 External Bypass Switch Interlock                hn  16  87  Battery Start Facility  020 a ta BAG na ag at Akers BANG a GAB thee 16  BATTERY INSTALLATION see me an A RT A ee Bem mo an 17  Introduction sana sana sun AN E ERE SW Led BES ba A de 17  DALE yes at BN he a eee Ga ae A an SA ana 18  Battery Cabinet iia a cheered id as Mice ied ang Sade ga a hese ES a eh ANS tii 19  2 3      Introduction  La bu Berau Be BAB Se SR BRA iB D NA 19  2 3 2 Temperature Considerations              ccc na 19  23 3  DIMENSIONS Wied Bc cl PELAN UN Bae A ald aaa eb ated aoa PE ada 19  DBA  Wedhi bana Gerth Be NN BAIR Bese BN OT hte Be at che sig ate dea BNN 19  2 3 5 Circuit Isolator Features              aa Ka KE eee KK a Be nee nes 19  2 3 6 Battery Temperature Board  Optional     
42. ch of  them takes inputs from the AC and DC sources  When one of the sources or even if one of the control  power boards fails  the UPS system can still operate normally  This feature further enhances the reli   ability of the system     Socket Outlet    One single phase Shuko type universal outlet of 3A current handling capability provides nominal  UPS output voltage of up to 3A current capacity for the ease of testing  commissioning  amp  servicing of  the UPS     Multi Module UPS   1 N    Multi module UPS are formed by several    single unit    UPS modules to constitute    1 N   system where  groups of one or more  up to six  single units operate together for the purpose of providing additional  power or reliability or both  The load is equally shared between any paralleled UPS     Figure 25 1 N multi module UPS with external maintenance bypass switch    Supplied by Others    Input Mains Supply    Qin UPS1 Qin UPS2 Qin UPS3            Qin Ext  AA A ee E eee at O Nees apes anes ace E eee eee ad ees eee E A    Byp         L1 L2 L3 N                     Input Mains Supply    Bypass Mains Supply  L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N    Input Mains Supply    Bypass Mains Supply  L1 L2 L3 N L1 L2 L3 N             RECTIFIER RECTIFIER RECTIFIER    STATIC STATIC    SWITCH    STATIC            UPS1 UPS2  L1 L2 L3 N   OUTPUT L1 L2 L3 N   OUTPUT L1 L2 L3 N    pc y Qout UPS2 Qout UPS3      Qout all UPS                 Distribution Cabinet Qout Byp    Further  single unit or 1 N groups may 
43. critical load when the UPS  becomes unavailable e g  during a maintenance procedure  This manual bypass switch is fitted in all  UPS modules and rated for full load of one module     ECO Mode  Single UPS Only     IF ECO mode is selected  the double conversion UPS operation is inhibited at most times for the pur   pose of saving energy  In this mode of operation  not unlike UPS of line interactive or stand by tech   nology  the bypass is the preferred source and only when the voltage and   or frequency of the bypass  supply are beyond pre defined and adjustable limits the critical AC load is transferred to the inverter   This transfer takes place with an interruption of less than 3 4 of an electrical cycle  e g   less than  15ms  50Hz  or less than 12 5ms  60Hz      Parallel Redundancy Mode  System Expansion     For higher capacity or higher reliability or both  the outputs of up to six UPS modules can pro   grammed for directly paralleling while a built in parallel controller in each UPS ensures automatic  load sharing     Hot Standby Mode    This is an alternative 1 1 redundancy application that ensures higher availability or better usage  control or both  Two UPS are connected in Hot Stand By mode as follows  UPS 1connects to the criti   cal load  and UPS 2 connects to the bypass of UPS 1  The remaining AC inputs are connected to the  incoming AC mains supply  UPS 1 synchronises to the output of the UPS 2 ensuring uninterrupted  load transfer from UPS 1 to UPS 2 or vice ver
44. d optional output   bypass distribution panel             eens 25  Dry contacts  multiple UPS modules with distribution panel             c eee 26  Connection of 1 N system parallel control cables    0 0    0 0 0 0  ccc eee een 27  Hot standby configuration    saa a bk a Aan BER Ed Fate a KA a De HA Ba an ee aa Di 28  Typical dual bus system configuration with static transfer switch and Load Bus Synch        29  Connections of a typical dual bus system utilising Load Bus Synch  0000 a ee 30  Electrical connections a ete BEE a Bee he eee a AS  Gen He Goa a Sea an Sel Be 31  General arrangement   10 20kVA UPS module                 teen eens 32  10 20kVA NX front view with doors open           ii    33  Location of parallel logic board MB    cc eee teen eens 34  Internal battery layout and connecting              ii    34  Internal battery layout    0    na  35  Single unit block diagram with split bypass mput          0  cee eens 36  Multiple battery temperature SeENSOYS   1 1    eee eens 37  1 N multi module UPS with external maintenance bypass switch                         38  Example of configuration for single UPS with external maintenance bypass cabinet           46  UPS control and display padel    49  Graphic LCD monitor windows and keypad                  Lo    51  Meri tree  ii secs RAS ban ben Se ah aoa A BB Da Ba SN ban Ba Mena mn geen ite oa aa a ag AAK Kaba cde aes 52  Help Seret et ee nana aa ON 59  Detault screen  cara sass blac MBA a a aka SA Ba eae AGE an SBB
45. disturbances in AC input power in this mode     The UPS is shut down but the load is connected to utility power via the  2 eee MAINT Maintenance Bypass Supply line  NOTE  The load is not protected  yP against disturbances in AC input power in this mode                   NOTE  1  The user controls and indicators mentioned in these procedures are identified in 7 0    Operator Control Panel and Display     2  The audible alarm may sound at various points during these procedures  It can be canceled  at any time by pressing the SILENCE ON OFF push button     NOTE    4    This unit refers to some modes and conditions that are set or adjusted using proprietary service    software  To take advantage of all the available features for the NX  the unit must be  commissioned by a Liebert factory trained service engineer     Power Switches  The UPS unit power switches are CB1 and SW1      CB1   Input Isolator  Connects the utility supply to the UPS input        SWI   Rotary switch  Has four positions   NORMAL  BYPASS  TEST and MAINT   that corre    spond to different positions of the SW1 A B C D    The positions of the rotary switch  SW1  are        SW1 A   Output Isolator  Connects the output of the UPS to the load        SW1 B   Neutral Isolator  Connects neutral to the UPS        SW1 C   Bypass Isolator  Connects the UPS with the bypass supply       SW1 D   Maintenance Bypass Isolator  Permits supply of the load directly by the bypass line for  maintenance of the UPS unit     The funct
46. e  10 sec   Bypass Frequency Tolerance    2 5 5 10 or   20 default  10  Synchronisation   Window Hz Rated frequency  1 Hz  selectable   0 5 to  3Hz   1 Hz sec  Branch regi rate Hz Sec selectable 0 1 to 3Hz s  single UPS    y quency 0 1 to 1 0Hz sec  paralleled UPS   Inverter Voltage Tolerance   VAC  5          1  Factory set to 400V     380 or 415V selectable by commissioning engineer   2  Factory set to 50Hz  60 Hz selectable by commissioning engineer  Bypass condition ignored when UPS set as frequency converter        70       Io  Liebert    Liebert NX        The Company Behind the Products    With over a million installations around the globe   Liebert is the world leader in computer protection  systems  Since its founding in 1965  Liebert has  developed a complete range of support and  protection systems for sensitive electronics      lt  Environmental systems   close control air  conditioning from 1 to 60 tons      Power conditioning and UPS with power  ranges from 300 VA to more than 1000 kVA      Integrated systems that provide both  environmental and power protection in a  single  flexible package      Monitoring and control   from systems of any  size or location  on site or remote     lt  Service and support through more than 100  service centers around the world and a 24 7  Customer Response Center    While every precaution has been taken to ensure the  accuracy and completeness of this literature  Liebert  Corporation assumes no responsibility and disclaims all  l
47. e 23 UPS messages       Message Description   Suggested Action  if any     This alarm is triggered by an inverter software routine when the amplitude or  frequency of bypass voltage is beyond the normal range    The amplitude threshold is fixed for positive and negative 10  rating    This alarm automatically resets once the bypass voltage goes normal    1  First verify that the bypass voltage and frequency displayed on the panel is within  the selected range  Note here the rated voltage and frequency are specified by     Output voltage level    and    Output frequency level    respectively    2  If the displayed voltage is believed to be abnormal  then verify the bypass voltage  and frequency presented to the UPS  Check the external supply if it is found to be  faulty     Bypass Unable to Trace       This alarm is triggered by an inverter software routine when the amplitude or  frequency of bypass voltage exceeds the limit    This alarm automatically resets once the bypass voltage goes normal    First check if there are some relevant alarms such as    Bypass disconnect open         Bypass phase reverse    and    Mains neutral lost     If they appear  solve them first    1  Then verify that the bypass voltage and frequency displayed on the panel is within  Bypass Abnormal the bypass limit  Note here the rated voltage and frequency are specified by    Output  voltage level    and    Output frequency level    respectively    2  If the displayed voltage is believed to be abnormal
48. e 28 Graphic LCD monitor windows and keypad    Cl    F1 F2    O a    1   UPS System  Window    2   UPS Menu  Window    Output    3   UPS Data  Window    4   Current Record  Window    5   Keypad Window    HELP    oo        51       Operator Control Panel and Display       The function of keys F1 to F4 is shown by a self explanatory icon as appropriate for the particular  window  As shown in Figure 28 above  pressing F1 moves the cursor  resting in    OUTPUT     from the    UPS Menu Window  2  to current reco    rd window  4  where it would first rest in    Input breaker closed        In a similar manner  pressing F2 would move the cursor from the Output data window to the Bypass    data window     The summary menu tree is shown below  Refer to 7 2   All Status and Event Messages Displayed  on the UPS Front Panel for a detailed description of each menu item     Figure 29 Menu tree       Mains  input  TX Input      Bypass Output TX Output          L N voltage  V   L N current  A   Frequency  Hz   L L voltage  V   Power factor    L N voltage  V   L L voltage  V                 L N voltage  V   Frequency  Hz   L L voltage  V     L N voltage  V   L N current  A   Frequency  Hz   L L voltage  V   Power factor    L N voltage  V   L L voltage  V                                                                             Date  amp  time   Commi baud rate  Comm2 baud rate  Comm3 baud rate    Communication mod  Callback times  Phone No 1   Phone No 2   Phone No 3  Command password       
49. e g  Fuse or Hardware failure  beep                   50    Operator Control Panel and Display       7 1 3 Direct Access Push Buttons  Keys        Emergency Power Off  EPO     Disconnects Power to the Load  Disables rectifier  inverter  static bypass  and battery operation              Inverter ON Enables Inverter Operation  Inverter OFF Disables Inverter Operation  Fault clear Resets blocked UPS functions  subject to any fault being cleared        Silence ON OFF             Toggle type buzzer mute  Any new fault re enables the buzzer        Press and hold Direct Access key briefly until acknowledged by a single beep     LCD Monitor and Menu keys  The user friendly and menu driven 320 x 240 dot graphic LCD monitor displays real time data and at    the same time stores 512 historical records that can retrieve for reference and diagnosis     The user can perform commands or easily browse through the input  output  load and battery param   eters  For quick reference  the UPS status and any warnings are always highlighted without the need  of navigating through the menu  The versions of converter firmware  inverter firmware and internal    monitor firmware can also be displayed on the LCD     Menu keys F1 to F4 are used to navigate within the graphic LCD monitor windows              Table 20 Menu key Icons and their meaning  Key F1 F2 F3 F4 Help  Window Type 1 Li  LEFT RIGHT  Next Data Window ENTER HELP       Window Type 2    ESC    Escape          UP DOWN                   Figur
50. e personnel and lifting aids are available  when removing the shipping pallet     Ensure that the UPS weight is within the designated surface weight loading of any handling equip   ment  See Table 33     UPS and optional cabinets  battery cabinets  top cable entry cabinets  etc   can be handled by means  of a forklift or similar equipment     The UPS cabinet also can be moved short distances by its casters         NOTE  Care must be taken when maneuvering units fitted with batteries  Keep such moves to a  minimum        Single Module UPS Installation       1 4 4    1 4 5    1 4 6    1 4 7    1 4 8    1 5    1 5 1    Clearances    The Liebert NX has no ventilation grilles at either side of the UPS  To enable routine tightening of  power terminations within the UPS  in addition to meeting any local regulations  Liebert recom   mends providing adequate clearance in the front of the equipment for unimpeded passage of person   nel with the doors fully opened  It is important to leave of 150mm  5 9   clearance behind the UPS to  permit adequate circulation of air coming out of the unit     Access    The component layout of the UPS supports front and top access while servicing  diagnosing and  repairing the UPS  thus reducing the space requirement for side and rear access     Final Positioning    The UPS cabinets are fitted with casters on the base to allow ease of movement and positioning     A WARNING    Casters are strong enough for movement across even surfaces only  Caster fail
51. e right side of the operator control panel for longer than 2  seconds     The Inverter indicator will turn off and the status indicator  6  will turn amber and an audible  alarm will sound  The load will transfer to static bypass and the inverter will shut off         NOTE  Pressing the Alarm Silence Switch cancels the audible alarm  but leaves the warning message  displayed until the appropriate condition is rectified     2  Open the UPS door to gain access to the main power switches  SWI and CB1     3  Turn the rotary switch to BYPASS position  The UPS Bypass Static Switch still supply power to  load     4  Turn the rotary switch to TEST  The load is now on maintenance bypass   5  Turn the rotary switch to MAINT     6  Open rectifier switch CB1  All operator indicators and messages will turn off as the utility driven  internal power supplies decay  The unit will power down  but the load will continue to be supplied  by the manual maintenance bypass     WARNING    Wait 5 minutes for the internal DC busbar capacitors to discharge before attempting to  remove the internal protective barriers     A WARNING    Even with the UPS rotary switch in maintenance bypass position portions of the unit are still  energized  Service is to be performed by qualified personnel only     A CAUTION    The load equipment is not protected from normal supply aberrations when operating in the  maintenance bypass mode     Powering Down the UPS    To power down the UPS completely  follow the procedure
52. en 25 and 50 meters  82 164 ft    respectively     Table 8 Input dry contact relays                X3 Terminal   Name Event Description  1 ENV  normal closed to  12V    Environment detection  IN DRY 2 BtG  normal closed to  12V    Battery ground fault detection  invokes alarm   3 GEN  normal open to  12V  On Generator detection  4  12V  12V power                      X5  Auxiliary DC Power Output   Auxiliary DC power for modem or external SNMP card  The voltage is between 9V to 12V  The maxi   mum current is 500mA    X6  Analog Input Interface   Two analog signal channels with an input range is from 0 to  12V  The precision of detection is  3        X6 pin 1  Not used     X6 pin 2   12V   e X6 pin 3  ENV T     environment temperature detection    X6 pin 4  GND       14    Single Module UPS Installation       X7  External Battery Temperature Detector Interface    Interface for TMP12Z temperature detector  normally connected to an external battery cabinet  see  Figure 6      Pin reference       X7 pin 1  Not used       lt  X7 pin 2   12V  Power supply for Temperature Monitoring Probe     X7 pin 3  BAT T  Battery Temperature signal      X7 pin 4  GND    Serial Ports RS232 1 and RS232 2    RS232 1 provides serial data and is intended for direct use with Liebert MultiLink monitoring and  server shutdown software     RS232 2 provides serial data and is intended for use by authorized commissioning and service person   nel     These serial ports are shared with the optional Web brows
53. equired for Battery or UPS test  default   12345        Dynamic Energy Flow Chart and UPS Help Screen    This screen displays a mimic diagram of the UPS that includes energy flow and status of isolation and  transfer switches  Press the    Help    key to activate this screen  Press again to toggle between this    screen and the main screen     Figure 30 Help screen       F1 F2 F3    O a    F4 HELP               59       Operator Control Panel and Display       7 5 Default Screen Saver    This default screen is displayed following at least 2 minutes of operation with no new alarm  After  another delay  the backlight turns off  Press any key to reactivate the screen     Figure 31 Default screen       Liebert Nxe 2005 05 22 12 30 36  20 kVA 3x3 UNIT  1 NORMAL                 EMERSON         Liebert     Press any key  back to main menu    F1 F2 F3 F4 HELP        Sd a                   60    Options   For Assembly Inside the UPS Cabinet          8 0 OPTIONS   FOR ASSEMBLY INSIDE THE UPS CABINET  Several items of optional equipment are available for connection to the Liebert NX UPS  These are  described in this section of the manual and should be fitted prior to installation    8 1 Protection   8 1 1 Battery Ground Fault Detection    In addition to any residual current device mounted externally and upstream the UPS or when  optional isolation transformers are fitted to the UPS  an optional residual battery current device can  be fitted to detect leakage current from the battery int
54. er  SNMP  ModBus and relay cards  Refer  to Table 29 regarding compatibility of simultaneous use     Intellislot Web Browser  SNMP  ModBus and Relay Cards Interface    There are three interface slots available for optional Web browser  SNMP  ModBus and Relay cards  as illustrated in 8 0   Options   For Assembly Inside the UPS Cabinet        15    Single Module UPS Installation       1 8 6 External Bypass Switch Interlock  EXT Maint X3 1 amp 2 on UPS Parallel Board M3  leave open if no external bypass switch is used     Provides external maintenance bypass interlock protection for the UPS  Short circuit means external  bypass closed     EXT Out  X3 3 amp 4  on UPS Parallel Board  leave shorted if no external output switch is used   Pro   vides external output interlock protection for paralleled UPS modules  Short circuit means external  output switch closed     NOTE    UPS Parallel Board M3 is located behind protective covers accessible after opening the UPS  front door     removal of this barrier requires the use of a tool and is restricted to service  personnel     1 8 7 Battery Start Facility  1  Rotate the switch to Normal Mode   2  Verify that the batteries are connected   3  Press Battery Start Button     The LCD begins to show startup screens  The rectifier indicator flashes green while the rectifier is  starting up  It stops flashing and becomes solid green about 30 seconds after the rectifier enters  the normal operation state     4  After UPS has initialized  press I
55. er Shutdown for Emergency Stop  EPO Action  or Other Conditions            47  Language Selection    47  Changing the Current Date and Time           ve daa mna KON ds 48  Command  Passwords retea Ki A A oA oe ce AA oe at ee vues 48  OPERATOR CONTROL PANEL AND DISPLAY        000 eee eee eee eee eee eee 49  Introduction 5  ska nah x a bee sa aa rata aaa bade a Baad wa die a 49  TRL  Mimic Power  Flow osien an oe sib a SR NAN an aa SW ies 50  7 1 2 Audible Alarm  Buzz    50  71 3 Direct Access Push Buttons  Keys                 ii    51  7 1 4 LCD Monitor and Menu keys    51  7 1 5 Detailed Description of Menu Items    53  All Status and Event Messages Displayed on the UPS Front Panel                    55  Prompt  Pop Up  Windows    59  Dynamic Energy Flow Chart and UPS Help Screen      59  Default Screen Saver io o buar a eek aes we Oe O PRE a eae eee A ag a 60  OPTIONS   FOR ASSEMBLY INSIDE THE UPS CABINET            cc oococoo  61  Protection Paw Ka an A E BE TEE area as bts ee ee eS 61  8 1 1 Battery Ground Fault Detection         nanana naasa aanerer 61  8 1 2 Redundant Fan for Power Module               ccc ete tenet ea 62  8 1 3 OC Web Card   SNMP HTTP Network Interface Card                               63  SkA Relay    Card     sa A a Se A asa ee Nth hath Tales E teat eek ah 64  8 19     Multiport 4 Card  os marar A sae Bia a ana he fe Bale ahs OR EA  oO ee a Rais Iu 64  OC485 Web Card     Modbus  Jbus  IGM Net            ce eee ene 66  8 2 1     Remote Alarm Monitors
56. er indicator Green  Battery indicator Off   Bypass indicator Off   Inverter indicator Green  Output indicator Green  Status indicator Green          6 2 2 Verify Switching Between Operation Modes  Switch from normal mode to battery mode      Open CB1 to enter battery mode  This breaks the utility connection to the NX     To return to normal mode  wait a few seconds and close CB1  The rectifier will restart automati   cally after 10 seconds and resume feeding power to the inverter     Switch from Normal Mode to Bypass Mode      Press INVERTER OFF button to switch to bypass mode       NOTE  In bypass mode  the load is being powered by the utility and is not receiving conditioned power  through the inverter     Switch from Bypass Mode to Normal Mode        Turn the rotary switch to NORMAL       In bypass mode  press the INVERTER ON button  When the inverter is ready  the UPS will  switch to normal mode        44    Operating Procedures       6 3    6 4    Switching the UPS from Normal to Maintenance Bypass    Follow the procedure below to transfer the load from the inverter output to the Maintenance Bypass  line of the UPS     A CAUTION    Before performing this operation  read the messages on the LCD to be sure that bypass supply  is regular and the inverter is synchronous with it  If those conditions are not present  there is  a risk of a short interruption in powering the load     This procedure assumes that UPS is operating normally     1  Press the INVERTER OFF button on th
57. etails  see 9 0   Technical Specifications    Continued compliance reguires installation in accordance with these instructions and the use of man   ufacturer approved accessories only     A WARNING    High Leakage Current  EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY   Earth leakage current exceeds 3 5 mA and is less than 860 mA     Transient and steady state earth leakage currents  which may occur when starting the  equipment  should be taken into account when selecting instantaneous RCCB or RCD devices     Residual Current Circuit Breakers  RCCBs  must be selected sensitive to DC unidirectional  pulses  class A  and insensitive to transient current pulses     Note also that the earth leakage currents of the load will be carried by this RCCB or RCD     This equipment must be earthed in accordance with the local electrical code of practice     A WARNING    Back Feed Protection Notice    This UPS is fitted with a voltage free contact closure signal for use with an external  automatic disconnect device  supplied by others  to protect against back feeding voltage into  the bypass input  If this signal is not used by the installer  a label must be added at the  external bypass input disconnect device to warn service personnel that the circuit is  connected to a UPS     The text to use is the following or equivalent     ISOLATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON THIS  CIRCUIT           User Serviceable Parts    All equipment maintenance and serv
58. h obtains power from the battery  sup   plies the critical AC load  There is no interruption in power to the critical load upon failure or restora   tion of the AC mains input power after which the    Normal Mode    operation will continue without the  necessity of user intervention     Auto Restart Mode    The battery may become exhausted following an extended AC mains failure  The inverter shuts down  when the battery reaches the End Of Discharge voltage  EOD   The UPS may be programmed to     Auto Recovery after EOD    after a delay time  This mode and any delay time are programmed by the  commissioning engineer        39    Operation       5 3 4    5 3 5    5 3 6    5 3 7    5 3 8    5 3 9    Bypass Mode    If the inverter overload capacity is exceeded  or if the inverter becomes unavailable for any reason   the static transfer switch will perform a transfer of the load from the inverter to the bypass source   with no interruption in power to the critical AC load  Should the inverter be asynchronous with the  bypass  the static switch will perform a transfer of the load from the inverter to the bypass with inter   ruption in power to critical AC load  This is to avoid paralleling of unsynchronised AC sources  This  interruption is programmable but typically set to be less than 3 4 of an electrical cycle  e g   less than  15ms  50Hz  or less than 12 5ms  60Hz      Maintenance Mode  Manual Bypass     A manual bypass switch is available to ensure continuity of supply to the 
59. hat the alarm is true by checking the system load percent indicated on the  LCD panel to determine which phase is being overloaded    2  If the alarm is true  measure the actual output current to verify that the indications  are valid    Disconnect unnecessary load and ensure the safety  In a parallel system  a severe  load sharing error can also leads to the alarm        Unit Over load Timeout    The UPS is confirmed to overload and the overload times out    Note 1  the highest loaded phase will indicate overload timing out first    Note 2  When the timer is active then alarm    unit overload    should also be active as  the load is above nominal    Note 3  When the timer has expired  the inverter Static Switch is opened and the load  transferred to bypass  The inverter shutdown and will restart after 10 seconds    Note 4  If the load decreases lower than 95  after 5 minutes  the system will transfer  back to inverter mode    Confirm that the alarm is genuine by checking the load percent indicated on the LCD   If an overload is indicated then check the load  and investigate any additional load  connected prior to the alarm  if applicable         Byp  Abnormal Shutdown    Both bypass and inverter voltages unavailable  Load interruption       Inverter Over Current    Inverter Pulse Width Modulation module overloaded        Bypass Phase Reversed    The phase sequence direction of bypass voltage is reversed    Normally  the phase of phase B lags 120 degrees behind phase A  and t
60. he phase of  phase C lags 120 degrees behind phase B    Verify that the phase rotation of the bypass supply presented to the UPS is correct   and rectify it if it is found to be in error       Load Impact Transfer    A transfer to bypass occurred due to a large step load  The UPS should recover  automatically  Turn on connected equipment in sequential order to reduce the step  loading of the inverter        Transfer Time out    The load is on bypass power due to excessive number of transfers that occurred  within the last hour    The UPS will recover automatically and will transfer the load back to inverter power  within an hour        Load Sharing Fault    UPS modules within a parallel system are not sharing the load current equally        DC Bus Abnormal    DC input voltage to inverter beyond limits  Inverter shuts down  Load transfers to  bypass        System Transfer    The whole paralleled UPS system transferred to bypass at the same time  This  message will appear on the UPS which passive transfer to bypass       Parallel Board Fault    Malfunction of the paralleling control circuits of this UPS module  Can cause    System  Transfer    to bypass        DC Bus Over Voltage    Rectifier  inverter and battery converter were shutdown because DC bus voltage is  too high  Check whether there is a fault in rectifier side  If no  then check whether  overload occurs  Restart the inverter after resetting the fault       Parallel Connect Fault    The parallel cables are not connec
61. iability for damages resulting from use of this information  or for any errors or omissions        2005 Liebert Corporation  All rights reserved throughout the world  Specifications  subject to change without notice        Liebert and the Liebert logo are registered trademarks  of Liebert Corporation  All names referred to are  trademarks or registered trademarks of their respective  owners     SL 25410  9 05  Rev  1    POWER AVAILABILITY    USER MANUAL    Technical Support Service    Web Site  www liebert com    Monitoring   800 222 5877  monitoring liebert com  Outside the US  614 841 6755    Single Phase UPS  800 222 5877  upstech liebert com   Outside the US  614 841 6755    Three Phase UPS  800 543 2378  powertech liebert com    Environmental Systems  800 543 2778    Outside the United States  614 888 0246    Locations  United States   1050 Dearborn Drive  P O  Box 29186  Columbus  OH 43229    Italy   Via Leonardo Da Vinci 8   Zona Industriale Tognana  35028 Piove Di Sacco  PD    39 049 9719 111   Fax   39 049 5841 257   Asia   7 F  Dah Sing Financial Centre  108 Gloucester Road  Wanchai  Hong Kong   852 25722201   Fax  852 28029250         EMERSON     
62. ich make the inverter frequency track that of the static bypass supply   provided that the bypass remains within an acceptable frequency window     A manually controlled  maintenance bypass supply is incorporated into the UPS design  It enables the  critical load to be powered from the utility  bypass  supply while the UPS is shut down for routine  maintenance     NOTE  When the UPS is operating in bypass mode or on maintenance bypass  the connected    equipment is not protected from power failures or surges and sags   5 1 3 Battery Temperature Compensation    For 10 20kVA UPS with internal batteries  a standard temperature probe is installed to measure the  internal battery temperature to optimize battery management  The measured temperature can be  displayed from the UPS front panel    For UPS with external batteries  an optional battery temperature interface equally optimises the  external battery management by connecting up to four external temperature sensors from the battery  cabinet s  to a control unit inside the UPS     Figure 24 Multiple battery temperature sensors    Temperature  Sensor                         Sensor      eocccceccoccocccce                e  Temperature                                 BCB Control  Board  C2    e  Temperature       a oooooosenosooooooe          BCB Box       37    Operation       5 1 4    5 1 5    5 2    Redundant Control Power Supply Board    The UPS is equipped with two identical and fully redundant control power supply boards  Ea
63. icing procedures involving internal access requires the use of a  tool and should be carried out only by trained personnel  There are no user serviceable parts behind  covers requiring a tool for removal     This UPS is fully compliant with safety regulations for equipment located in an operator accessible  area  Hazardous voltage is present within the UPS and battery enclosure but out of reach of non ser   vice personnel  Contact with hazardous voltage is minimized by housing live parts behind safety pan   els that require a tool for their removal  No risk exists to any personnel when operating the  equipment in the normal manner  following the recommended operating procedures     Battery Voltage Exceeds 400VDC    All physical battery maintenance and servicing requires the use of a tool or a key and should be car   ried out only by trained personnel     WARNING    Special care should be taken when working with the batteries associated with this equipment     When connected together  the battery terminal voltage will exceed 400VDC and is potentially  lethal     Battery manufacturers supply details of the necessary precautions to be observed when working on   or in the vicinity of  a large bank of battery cells  These precautions should be followed implicitly at all  times     Attention should be paid to the recommendations concerning local environmental conditions and the  provision of protective clothing  first aid and fire fighting facilities        Single Module UPS Instal
64. ions of the rotary switch are shown in Table 11                    Table 11 Rotary switch configurations  e a a OUTPUT  SW1 A    BYPASS  SW1 C  Sa Di NEUTRAL  SW1 B   NORMAL V V v  BYPASS v 7  gt   TEST 2 F z  MAINT V                         42       Operating Procedures       6 2    6 2 1    UPS Startup    The NX must be fully installed and commissioned before startup  and external power isolators must  be closed  Once those general conditions are met  the UPS may be started     Start Up Procedure  To start the UPS from a fully powered down condition     1  Open the UPS door to gain access to the main power switches     WARNING    During this procedure the output terminals will become live     If any load equipment is connected to the UPS output terminals  please check with the load  user and ascertain whether it is safe to apply power to the load  If the load is not ready to  receive power  then ensure that it is safely isolated from the UPS output terminals     A CAUTION    Do not operate the rotary switch too fast  Always wait at least three seconds when rotating  the switch from one position to another    2  Close CBI   3  Turn the rotary switch to TEST     The bypass contactor  M2  closes automatically and the LCD begins to show start up screens  The  rectifier indicator flashes green while the rectifier is starting up  It stops flashing and becomes  solid green about 30 seconds after the rectifier enters the normal operation state  After initializa   tion  the bypass s
65. ith full load   The time is user configured from 3 to 60 minutes    Shut down the load in time        Battery End of Discharge    Inverter turned off due to low battery voltage  Check the utility failure and try to  recover it        Mains Volt  Abnormal    Mains Voltage exceeds the upper or lower limit and results in rectifier shutdown   Check the input line to neutral voltage amplitude of rectifier        Mains Undervoltage    Mains Voltage is undervoltage with derated load   Check the input line to line voltage amplitude of rectifier       Mains Freq  Abnormal    Mains frequency is out of limit range and results in rectifier shutdown   Check the rectifier s input voltage frequency       Rectifier Fault    Rectifier detected faulty  Rectifier shuts down  Battery discharges        Rectifier Overtemp     The temperature of heat sink is too high to keep the rectifier running   The UPS can recover automatically  Check the environment and ventilation        Batt  Contactor Fail    Battery contactor or circuit breaker not responding to control signals        Batt  Charger Fault    The voltage of the battery charger is too high        Control Power 1 Fail    UPS operates but Redundant Control Power is not available        Mains Phase Reversed    AC Input phase sequence is reversed        Rectifier Overcurrent    Rectifier is overloaded        Soft Start Fail          Rectifier could not start due to low DC bus voltage             55    Operator Control Panel and Display       Tabl
66. lation       1 0 SINGLE MODULE UPS INSTALLATION       1 1    1 2    Introduction    This following section describes the requirements that must be taken into account when planning the  positioning and cabling of the Liebert NX uninterruptible power supply and related equipment     This chapter is a guide as to general procedures and practices that should be observed by the install   ing engineer  The particular conditions of each site will determine the applicability of such proce     dures     4    WARNING    Professional Installation Required    Do not apply electrical power to the UPS equipment before being authorised to do so by the  commissioning engineer     The UPS equipment shall be installed by a qualified electrical tradesperson in accordance  with the information contained in this manual  All equipment not referred to this manual is  shipped with details of its own mechanical and electrical installation     NOTE  Three phase  4 wire input supply required     The standard Liebert NX UPS is suitable for connection to 3 phase  4 wire    Earth  TN  TT  and IT AC power distribution systems  1EC60364 3   Optional 3 wire to 4 wire conversion  transformers are available  If it is used in IT AC power distribution systems  a 4 pole circuit  breaker must be used on the input and refer to the relative IT Systems    standard    WARNING    Battery Hazards    Special care should be taken when working with the batteries associated with this equipment   When connected together  the
67. load                ii    69  Batteries Ban Be wh so Pisin as Be eee Gun Bon dn beb han an a dod 69  Bypass mains Inputs  om end td athe Kal aga rang saa a Ges Welle dete dae SBN 70          Figurei Model number nomenclature                                                                NXe 0 AO 010 U  Input  amp  ie  Feature Set for Region Output        gt  50 60Hz  AO   EMEA Voltage    Voltage Code  220 380 F         BO   Aust NZ  230 400 U         CO   Japan  240 415 G  kVA      D0   China Sapuh         EO   Latin Amer 010  Revision to Base Unit 020  030  future   NX Product Line  UPS Single Module  Liebert NXe UPS module ratings   10  15  20kVA  with internal battery   Example  NXE0A0010U    10kVA module for Europe and Middle East  400V 230V  output  Options Model  Identification Note  Battery cabinet NXEONBCS  Battery Ground Fault detection kit NXAOUFXBGF  Battery temperature probe  for external battery  NXAOUFXBTS  Maintenance bypass cabinet  separate bypass input  NXEONMBX Specify total system kVA  Fan Redundancy kit NXEOUFXRF   f  a A Specify UPS kVA rating  Seismic Anchor kit NXAOUFXSAN  Dual bus control cable 05 10 15 metres NXAOUFXD        Specify lengih in metres  Parallel control cable kit 05 10 15 metres NXAOUFXP       Relay Card  On Bat  Bat Low  On Byp  Sum  UPS Fail   MultiPort4  4 sets On Bat  bat Low    Web browser TCPIP SNMP Card   Jbus Modbus Card    RELAYCARD INT   MULTIPORT 4 These are Intellislot plug in cards  OCWEB LB  3 slots available     0C485CARD
68. mm      16 20AWG  stranded for maximum runs between 25 and 50 meters  82 164ft   respectively     1 8 4 Output Dry Contacts  There are three output dry contact relays at the X1 slot  see Figure 4 and Table 6     Figure 4 on dry contacts and EPO MN       Table 6 Output dry contact relays                                           Position Name Description   413 2 Gen_O Generator Start Relay  N O     413 3 Gen_S Generator Start Relay Center   413 4 Gen_C Generator Start Relay  N C     J21 2 BPS O Bypass Feedback Alarm Relay  N O    J21 3 BPS S Bypass Feedback Alarm Relay Center  J21 4 BPS C Bypass Feedback Alarm Relay  N C    J25 2 ACF O Main Input Fault Relay  N O     J25 3 ACF S Main Input Fault Relay Center   J25 4 ACF_C Main Input Fault Relay  N C             NOTE  All auxiliary cables must be double insulated  Wire should be 16 20AWG stranded        13    Single Module UPS Installation       1 8 5 Emergency Power Off Input    The UPS has an Emergency Power Off  EPO  function that operates by a button on the control panel  or by a remote contact provided by the user  The EPO button is under a hinged  clear plastic shield     The X2 slot  shown in Figure 4  is the remote EPO input interface  The EPO has an NO NC contact  point that becomes active when shorting terminals X2  3 and 4 or open terminal connection X2  2 and 1    If an external emergency stop facility is required  it is connected terminals X2  1 amp 2 or X2  3 amp 4 of the  auxiliary terminal block  X2   It also is
69. nce Mode  Manual Bypass     40  5 3 6 ECO Mode  Single UPS Only               ii    40  5 3 7 Parallel Redundancy Mode  System Expansion             oooooooo omo    40  51318  Hot Standby Mode  ee id lada Sele  haat Bea ta heh 40  5 3 9 Frequency Converter Mode              ii    40  Battery Management   Set During Commissioning            0 0000 cee eee ee eee 41  5 4  Normal Functions i A Goss a ee iB Gres oe eo Bie ec Nu Meld ba lee es 41       if       5 5    6 0  6 1    6 2    6 3  6 4  6 5  6 6  6 7  6 8  6 9  6 10  6 11    7 0  7 1    7 2  7 3  7 4  7 5    8 0  8 1    8 2    9 0  9 1    5 42 Advanced Functions  Software Settings Performed by the Commissioning Engineer        41    Battery Protection  settings by commissioning engineer  e 41  OPERATING  PROCEDURES   i2u   nd vet ee on cies oust wee a a E ja ewe tw Geert oe 42  Introduction nn OA Soe nol okt renal aha ate Oe MeN Ns A ar ars na 42  o a Power Switches ici  E eave he eine Sle idk ee Minh lee Gow he lenis 42  UPS Startups  td IG  aaa oe ee pee oth  whee aa 43  621    Start Up Procedures 0x meat Grew pi ceiver dotted hs eee als a a Be eee Wa ache a ee 43  6 2 2 Verify Switching Between Operation Modes            0 0 cece teen eens 44  Switching the UPS from Normal to Maintenance BypasS            oo    oo        o  45  Powering  Down the UPS ici Sethe Matec A A EN NN eS 45  Powering Down the UPS and Maintaining Power to Load         0 0 0 0 46  Emergency Shutdown With EPO            io    47  EE 47  Reset Aft
70. ntrol Panel and Display       7 3    7 4    Prompt  Pop Up  Windows    The prompt window is displayed during the operation of the system to alert the user to certain condi   tions and   or to require user confirmation of a command     Table 24 Prompt windows  meanings       Prompt    Transfer with interrupt  please confirm or cancel    Meaning    Inverter and Bypass supplies are not synchronised and  any load transfer between the supplies will cause a brief  load interruption        The load is too high to be transferred with interrupt    The total load must be less than the capacity of one unit  to allow a parallel system to perform an interrupted  transfer from bypass to inverter        This Operation Leads to Output Shutdown  Confirm or  Cancel    No alternative supply is available and any Inverter Off  operation will cause the load to be de energised        This operation leads to inverter overload  confirm or  cancel    The turn off this inverter will lead to the overload of  remaining inverter s  in a parallel system        Turn on more UPS to carry current load    The number of paralleled inverters already turned on is  insufficient to carry the existing load        Battery will be depleted  confirm    Battery Capacity test discharges the battery 100        System self test finished   everything is ok     No action required       System self test finished   Please check the current  warnings     Check    Current Records    window       Enter control password          R
71. nverter On  Figure 5 Battery start for UPS    Battery Start Button    2       a    Kap PP ah  il  ngan unani       16    Battery Installation       2 0    BATTERY INSTALLATION       2 1    Introduction    The UPS battery bank consists of battery blocks connected in series to provide a D C  string voltage as  required by the UPS converter  The  AUTONOMY TIME   the time during which the battery can  maintain supply to the load in the event of a mains failure  is limited by the ampere hour capacity of  the battery blocks and in some cases this results in several strings being connected in parallel    The NX usually has internal batteries  but longer run time is available by using an external battery  cabinet     The battery cabinet will be supplied in one of the following forms     1  Complete installation  comprising the battery cabinet  batteries and protective device   2  Battery cabinets and protective device only   batteries supplied by others      NOTE  10kVA to 20kVA UPS models contain an internal battery compartment that can accommodate  up to 44 blocks 12 Ah 12V batteries     The battery bank may be disconnected from the UPS for maintenance or service  The isolator may be  switched manually ON or OFF        17    Battery Installation       2 2    Safety    Special care should be taken when working with the batteries associated with the Liebert NX UPS  system  When all the cells are connected together  the battery terminal voltage is potentially hazard   ous  The battery
72. o be used in conjunction additional cabinets  to provide the necessary accommoda   tion required by the larger cells associated with system   s having a long autonomy time     Where two  or more  cabinets are used they are positioned alongside each other and secured and  bonded together  If the cabinet s  is located immediately adjacent to the main UPS equipment the two  units are bolted together     2 3 2 Temperature Considerations    Valve regulated  lead acid battery cells are sensitive to ambient temperature and should be operated  between 15  C and 25  C  59 77  F   Battery capacity is increased by 1  for every 1  C  2  F  increase in  temperature up to 25  C  77  F   Battery life is reduced at temperatures above 25  C  77  F      When batteries are mounted in the same room as the UPS unit  it is the battery that dictates the  designed maximum ambient temperature  not the UPS      i e  in the case of valve regulated cells  the  ambient room temperature should be kept between 15  C and 25  C  59 77  F   and not between 0  C  and 40  C  32 104   F   which is the specified main equipment operating temperature range   Tempera   ture deviations are permissible for short periods  provided the average temperature does not exceed  25  C  77  F      2 3 3 Dimensions    The external dimensions are shown in Table 9  These are the same height and depth as the UPS  module and provide a matching appearance when bolted together  All cabinets are fitted with doors   which must be fully 
73. o the PE  Protective Earth  Residual current  range monitored  30 3000mA     Power supply voltage for the set  AC230V  L N     When a battery ground fault is detected  an alarm will appear on the UPS display panel   An additional Dry contact fault Alarm signal is available for remote monitoring    Table 25 Dry contact fault alarm signal is available for remote monitoring       Terminal   Name Definition  Battery Ground Fault Detection     can be          21 Common programmed as Alarm or Pre Alarm  22 NC  24 NO                   The Battery ground fault detection set contains one CT  current transformer  and one DC sensitive  residual current monitor  The connection of this set for UPS is illustrated as follows     Figure 32 Battery ground fault detection set connections          La  0 1 Current    Transformer BCB or  W1 A358 Contactor      A  suis             Battery                               Monitor Board                       Ka K2   2      Socket Output  Phase  Al 11  IN DRY X3  Output  Neutral Battery Ground       Fault Detection  Resys B470   AC230               The Battery Ground Fault Detection Set is assembled within the UPS cabinet        61    Options   For Assembly Inside the UPS Cabinet       8 1 2 Redundant Fan for Power Module    In addition to ensure sufficient cooling power at various operation modes with 100  rated load  a  redundant power module fan set can be supplied  thus ensuring continuity of UPS operation even  with the failure of some fans  No ext
74. o the batteries themselves  and  connected using the most direct route possible     Storage    Should the equipment not be installed immediately  it must be stored in a room for protection against  excessive humidity and or heat sources  see Table 31      CAUTION    An unused battery must be recharged periodically per battery manufacturer  recommendation  Temporarily connecting the UPS to a suitable AC supply mains and  activating it for the time required for recharging the batteries can achieve this        Single Module UPS Installation       1 4    1 4 1    1 4 2    1 4 3    Positioning    The cabinet is mounted on four castor wheels for ease of positioning and for short distance movement   Jacking feet are provided to prevent the UPS from moving once it has been wheeled to its final posi   tion     For optimal design life  the place chosen must offer       Easy connection     Enough space to easily work on the UPS     Sufficient air exchange of enough to dispel heat produced by UPS       Protection against atmospheric agents   e Protection against excessive humidity and very high heat sources   e Protection against dust     Compliance with the current fire prevention requirements     Operating environment temperature between 20  C and 25  C  68 and 77  F   The batteries are at  maximum efficiency in this temperature range  see Table 31      The UPS cabinet is constructed around a steel chassis with removable panels  The top and side panels  are secured to the chassis by sc
75. opened in order to fit or remove the batteries  The door swing must therefore be  taken into consideration when planning the positioning of the cabinets     2 3 4 Weight    The unladen weight is shown below in Table 9  When designing the battery installation the weight of  the batteries and cables must be added to the unladen weight  This is particularly important when  placing the NX on a raised floor     Table 9 Dimensions and weight       Optional Maximum Cabinet Weight  Circuit Breaker   Discharge Current   External Cabinet   Without Batteries  Model Amperes  at EOD  WxDxH mm  in  kg  Ib   10kVA 22A  Battery Cabinet 50A 15KVA 33A eee an 170  375   20kVA 44A BEN Ban                          2 3 5 Circuit Isolator Features    The UPS is fitted with internal Anderson connectors and fuses for connection and disconnection of  batteries  External battery banks are protected by battery fuses or a optional circuit breaker  with  status contacts and undervoltage trip coil   Refer to 2 5   Battery Control for details        19    Battery Installation       2 3 6 Battery Temperature Board  Optional     The optional external battery temperature sensor kit contains one probe and one temperature trans   port board as illustrated in Figure 6  It is connected to the UPS Monitor Board     Figure 6 Single temperature sensor and monitor board U2    Name  W2 L 5m  Temperature E  Sensor       Name  W1 L 30m                Cable W2 is packed with the temperature sensor     2 3 7 Moving the Bat
76. ort 4 any  f Relaycard int any  Top Intellislot 2 Comm 1   2  Intellislot    On Monitor Board  OCWEB LB 2400   Not simultaneous with  Multilink in RS232 2  Modbus Jbus 2400  Multiport 4 any    f Relaycard int any  Middle Intellislot 1 Comm 2      Intellislot    On Monitor Board  OCWEB LB 2400   Not simultaneous with  Multilink in RS232 2  Modbus Jbus 2400  Multiport 4 any  Bottom Intellislot 3 Comia Relaycard int   any  Intellislot  On Monitor Board  OCWEB LB 2400  Modbus Jbus 2400  Top    Multilink Serial  DB9 port RS232 1 Comm 1 9600  Bottom Multilink Serial Not simultaneous with Web  DB9 port RS232 2 Comm 2 2400   card in middle intellislot                          Remote Alarm Monitor    Status and alarm conditions are available on an optional remote alarm monitor  RAM  panel that is  driven by volt free alarm status contacts from an optional relay alarm board        66       Technical Specifications       9 0    TECHNICAL SPECIFICATIONS       9 1    Conformity and Standards    The UPS has been designed to conform to the following European and international standards     Table 30    Compliance with European  international standards       Description    General and safety requirements for UPS used in  operator access areas    Normative reference    EN 50091 1 1  IEC 62040 1 1   AS 62040 1 1       Electromagnetic compatibility  EMC  requirements for  UPS    EN 50091 2   IEC 62040 2   AS 62040 2  Class A        Method of specifying the performance and test  requirements of U
77. r Output current Crest Factor                   53          Operator Control Panel and Display          Table 22 Descriptions of UPS menus and data window items  continued   Menu  Type Item Type Explanation   Sout  kVA  Sout  Apparent power   Pout  kW  Pout  Active power  System Qout  kVAR  Qout  Reactive power   Single unit  no parallel data can configured as a single unit  UPS has only native load  no system   Battery voltage  V  Battery bus voltage   Battery current  A  Battery bus current   Battery temperature    C  Internal battery temperature   C  Battery Remain Time Min  Battery run time remaining   Battery capacity     Percentage of battery life remaining   Battery boost charging Battery is boost charging   Battery float charging Battery is float charging   Battery disconnected Battery is not connected  Records  history log  Displays all records in the history log  Language    choices for text displayed    User may select any of 12 languages for LCD text    Display contrast Adjust the LCD display contrast   Date format set Choose the format for date display  M D Y  D M Y  M D Y  Y M D   Date  amp  time Set the date and time   Comm1 baud rate Communication baud rate setting for Intellislot 1   Comm2 baud rate Communication baud rate setting for Intellislot 2   Comm3 baud rate Communication baud rate setting for Intellislot 3   Communication address This setting is applicable to RS485 communication mode  Settings Communication mode Communication Mode Setting   Callback 
78. r to the Records tab of the Menu and Data Window     Refer to Table 23 for a complete list of supported status messages     All Status and Event Messages Displayed on the UPS Front Panel    This is the complete list of UPS events and status messages supported for display in either the Record  window  Historic data  or in the Current window  Prevailing data  as described in 7 1 4   LCD Moni     tor and Menu keys   Table 23    UPS messages       Message  Inverter Comm  Fail    Description   Suggested Action  if any   Internal RS485 communication failure between monitor and inverter       Rectifier Comm  Fail    Internal RS485 communication failure between monitor and rectifier       Parallel Comm  Fail    The CAN communication between different UPSs within a parallel system fails   1 Check if there are some UPSs not powered on in the parallel system  If so  power  on these UPSs and check if the alarm disappears    2  Press Fault Clear push button        Battery Overtemp     The Battery temperature is over limit  Check the battery temperature and ventilation       Ambient Overtemp     The Ambient temperature is over limit  Check the ventilation of UPS room        Battery Fault    Battery detected faulty  Reserved        Battery Replaced    Battery test failed  Battery should be replaced        Battery Low Pre warning    Before the end of discharge  battery undervoltage pre warning should occur  After this  pre warning  battery should have the capacity for 3 minutes discharging w
79. ra footprint is required    Figure 33 Redundant power module fan set    Redundant AC Fan                                                                                            nggabag a nak daa aia Naba anaa abaan aa aab Ne aa aa kaka aana baia na a aane agan 3 Standard AC Fan     AC Fan 1 1   AC Fan 1 2   AC Fan 1 3     AC Fan 1 4     3 Fant20 E Fant20    Fant20   3   Fant20       A A A TAn    W353X1_J6    TOP VIEW    Figure 34 Communication bays and cable location    Location Preferred Device This Location    RS 232 1 DB 9  COM Port 1    Serial MultiLink Software   Port Setting 2400 Baud   RS 232 2 DB 9  COM Port 2   Service Access Software  DB 9  Port Setting 9600 Baud   Monitor  Board    Location Preferred Device This Locatior  Top Bay  COM Port 1  Relay Card  no port setting req   d   Mid Bay  COM Port 2  Multiport4  no port setting req   d     Bottom Bay  COM Port 3  OCWeb LB   0C485  port setting 2     Top  Mid    Suggested routing of customer supplied  communication cables    Notes    a  All Intellislot cards are supported in any bay    b  Port sharing is      PERMITTED between RS232 x DB9 devices and Relay    Multiport4 Intellislot cards  i e   Serial Multilink software  will work from RS232 1 DB9 also when relay card is  inserted in the top bay      NOT PERMITTED between RS 232 x D B9 devices and  OCWeb   OC485 cards  i e   Serial MultiLink software will  not work from RS232 1 DB 9 when OCWeb card is inserted    Gland plate for cable exit in the top bay         
80. rces must be referenced to the same neutral potential and input earth leakage monitoring devices   if installed  must be located upstream of the common neutral sinking point  Refer to the instructions  in 1 0   Single Module UPS Installation       29    UPS Multi Module Installation       3 4 4 Control Wires    For Liebert NX to NX dual bus configuration  interconnect the optional DBS cable between any DBS  ports of two parallel systems as illustrated in Figure 16     Figure 16 Connections of a typical dual bus system utilising Load Bus Synch    UPS UPS    Parallel Board Parallel Board Parallel Board Parallel Board                DBS Cable                                                             Parallel System    A  Parallel System Il      NOTE  Example shown with ring control cables   8   for DSB applied to two 1 1 paralleled systems     3 4 5 Extended Dual Bus Synchronization Option  DBS Interface Box     For Liebert NX to non  NX  whether another Liebert UPS range or not  dual bus configuration  one  DBS interface box shall be mounted on the non  Liebert NX UPS  In this situation  the other UPS sys   tem is always treated as a master and the following conditions are covered         Master and slave are both on inverter  e Master on bypass  slave on inverter       30    Installation Drawings       4 0 INSTALLATION DRAWINGS       Figure 17 Electrical connections    o   x3 Ext  Maint  fo  Parallel Board  Ext  Out C o     X2 Ext EPO       Earth To Customer   s Safety    Ea
81. rews     Access to the power terminals  auxiliary terminals blocks and power switches is from the front  Oper   ational status and alarm information is provided through the front door operator control panel  Mod   els 20kVA and below house both the power components and an internal battery  Cooling air enters  the front of the NX and is exhausted out the rear     System Cabinets    A UPS may comprise a number of cabinets  depending on the design requirements  e g   UPS cabinet   external battery cabinet  external bypass cabinet   In general  all the Liebert cabinets used in a particu   lar installation are of the same height and designed to be positioned side by side to form a matching  array     Refer to 4 0   Installation Drawings for assistance on positioning the cabinets described below     10 to 20kVA UPS    The UPS consist of a single cabinet  which uses typically forty  40  12V battery blocks  fitted inter   nally and connected in series to provide a nominal battery voltage  The UPS may be shipped without  the batteries fitted     An extended battery option is available  This comprises a separate cabinet containing additional bat   teries that can be connected to the UPS to increase its battery run time     Moving the Cabinets    WARNING    Ensure that any equipment used to move the UPS cabinet has sufficient lifting capacity     The UPS is fitted with casters  Take care to prevent the NX from moving when unbolting the  unit from its shipping pallet  Ensure that adequat
82. rilles at the front of the cabinet and hot air is released through the grilles at the  back  Do not cover the ventilation openings     If necessary to avoid room temperature build up  install a system of room extractor fans  Optional air  filters are available if the UPS is to operate in a dusty environment     The UPS heat dissipation detailed in Table 32 can be used as a guide for air conditioning sizing   depending on the selected mode of operation       Normal Mode  VFI SS 111 Double Conversion UPS    lt  ECO Mode  VFD SS 311 Stand By UPS     If in doubt use Normal Mode figures       NOTE  The UPS is suitable for mounting on concrete or other non combustible surface only     External Battery Room    Batteries should be mounted in an environment where the temperature is consistent and even over  the whole battery  Temperature is a major factor in determining the battery life and capacity  Typical  battery manufacturer performance data are quoted for an operating temperature between 20 and  25  C  68 and 77  F   Operating above this range will reduce the battery life while operation below this  range will reduce the battery capacity  In a normal installation the battery temperature is main   tained between 15  C and 25  C  59 and 77  F   Keep batteries away from main heat sources or main air  inlets etc     Where the batteries are located externally to the main UPS cabinet  a battery protection device   e g   fuses or circuit breakers  must be mounted as close as possible t
83. rth    To Critical Load    Main Bypass Input  Supply    External Battery    Power  Cables       31    Installation Drawings       Figure 18 General arrangement   10 20kVA UPS module       700         a  600    7                               1400                                                                                                                                                                                                                                                                                            a    FRONT VIEW       10 20 kVA 1 3          LEFT SIDE VIEW    10mm dia threaded  mounting holes                   Detail A  rear of unit  shown without side panel    Leveling feet                420  1 80             on TTI       ly                                                             625          TOP VIEW                                                 38 gam  A Bee  700  Air  Intake  103     321  O 1  6   o o Ol  Lg 3299          430    520  BOTTOM VIEW    1  Air inlet grille   2  Air outlet grille   3  Adjustable fixing feet   4  Castors for maneuvering   5  Seismic anchors  option    6  Cable entry   7  Operator control and display panel    All dimensions are in mm        32    Installation Drawings       Figure 19 10 20kVA NX front view with doors open  5                                                             PAI    1  Main Bypass Input terminal  T1   2  Battery  Output terminal  T2    3  Internal battery Input switch  CB2   4  Rotary swi
84. s    enter    key to acknowledge that the all paralleled UPS will be  disconnected from the load        Fault Reset    Fault clear direct access key pressed       Alarm Silence    Silence On Off direct access key pressed       Inverter failed to turn on when Inverter On direct access key was pressed  This may       Turn On Fail be as a result of Invalid Operation  Maintenance bypass on  or DC bus or rectifier not  ready   Alarm Reset Fault clear or Silence On Off direct access key pressed       Bypass Mode    Load supplied from AC input bypass supply        Normal Mode    Load supplied from Inverter output through double conversion of the AC mains input  supply        Battery Mode    Load supplied from Inverter output through double conversion of the Battery supply        Source share mode    Load supplied from Inverter output through shared double conversion of the AC  mains input supply and of the Battery supply        UPS Shutdown    UPS Shutdown  output power down       Check UPS Output    Inverter off during normal startup  diagnostics information only        Generator Connected    Generator active signal received  Source share mode may be activated pending UPS  settings        BCB open    Battery Circuit Breaker status  open        BCB closed    Battery Circuit Breaker status  closed        Battery Float Charging    Battery status  Float charge mode        Battery Boost Charging    Battery status  Boost charge mode        Battery Discharging    Battery status  discharge
85. s in 6 3   Switching the UPS from Nor   mal to Maintenance Bypass     To completely isolate the UPS from the AC supplies  the main external power input isolator  both iso   lators  where separate supplies are provided for rectifier and bypass  should be opened  see  Figure 26      A WARNING    To prevent injury to personnel  lockout or tagout the service supplies        45    Operating Procedures       6 5    Powering Down the UPS and Maintaining Power to Load    NOTE  An external Maintenance Bypass Cabinet must be installed before attempting to perform the  following procedure    If the UPS needs to be shut down completely while maintaining power to the load  follow these steps     1  Perform Steps 1 through 5 in 6 3   Switching the UPS from Normal to Maintenance  Bypass   2  Close the external maintenance bypass rotary switch to Maint position     A WARNING    On the primary input distribution panel  which is often located distant from the UPS area  a  label should be posted advising service personnel that the UPS circuit is under maintenance     WARNING    Wait 5 minutes for the internal DC busbar capacitors to discharge     The UPS is now completely powered down       NOTE  The maintenance bypass power switch may be operated at any time while the UPS is powered  down to connect the load to the maintenance bypass supply if required    The procedure can be performed only after the installation has been completed  which includes the  maintenance bypass cabinet   after the sy
86. sa  This ensures that any specified load is supplied by a  UPS while still providing a bypass path to cater for overloads  Further  the system can also be pro   grammed to reverse UPS1 between Normal and Bypass Modes so that each UPS is equally utilised   This interval is programmable from 1 to 4 320 hours  180 days      Frequency Converter Mode    The NX UPS can be programmed into frequency converter mode for either 50Hz or 60Hz stable out   put frequency  The input frequency may vary from 40Hz to 70Hz  In this mode the static bypass oper   ation is disabled  and the battery becomes optional depending on any requirement to operate in  battery mode  stored energy mode         40    Operation       5 4    5 4 1    Battery Management   Set During Commissioning    Normal Function     Constant charging current   Current can be set up to limit charging power      Constant boost voltage boost  if applicable    Voltage of boost charging can be set as required  by the type of battery   For Valve Regulated Lead Acid  VRLA  batteries  maximum boost charge voltage should not  exceed 2 4V   cell   Float Charge   Voltage of float charging can be set as required by the type of battery   For VRLA  float charge voltage should be between 2 2V to 2 3V   Float Charge Temperature Compensation  optional    A coefficient of temperature compen   sation can be as required by the type of battery   End of discharge protection  EOD    If the battery voltage is lower than the EOD  the battery  converter
87. selectable 5 through 30 seconds in 5 second  intervals                    1  Rectifier operates at any of the rated supply voltages and frequencies without further adjustment    2  At 305V input mains the UPS maintains the specified output voltage at rated load without discharging a previously charged  battery   3  IEC 62040 3   EN 50091 3  at rated load and input voltage 400V  battery charged   4  IEC 62040 3   EN 50091 3  at rated load and input voltage 400V  battery charging at maximum rated power        68    Technical Specifications             Table 35 Battery  Intermediate DC Circuit  Unit of  Rated Power  kVA Measurement 10 15 20  Battery Bus Voltage VDC Nominal  480V  VRLA Float charge is 540V     Range  400V   600V       Number of Lead Acid Cells             Nominal 240    40 x 6 cell  12V  blocks   Maximum 264    44 x 6 cell  12V  blocks   Minimum 228    88 x 6 cell  12V  blocks        Float Voltage    V cell  VRLA     2 25 V cell  selectable from 2 2    2 3V cell   Constant current and constant voltage  IU  charge mode                Temperature Compensation mV  C cl   3 0  selectable 0 to     5 0 around 25  C or 30  C  or inhibit   Ripple Voltage Yo V float  lt 1   Ripple Current   C49  lt 5   Boost Voltage VRLA 2 35 V cell  selectable from 2 30 2 40V cell     Constant current and constant voltage  IU  charge mode       Boost Control      float boost current trigger 0 050 C19  selectable 0 030 0 070     boost float current trigger 0 010 C19  selectable 0 005 0 02
88. st one of the static switches of inverter side is open or short circuit  This fault is    La oral locked until power off        At least one of the static switches of bypass side is open or short circuit  This fault is    Bypass STS Fail locked until power off                Operation Invalid This record is registered following an incorrect operation     At least one of the inverter output fuses is blown  Inverter shuts down  Load transfers  Output Fuse Fail  to bypass   Control Power 2 Fail UPS operates but Redundant Control Power is not available   The UPS is confirmed to be overload when the load arises above 105  nominal  rating     The alarm automatically resets once the overload condition is removed    1  Confirm that the alarm is true by checking the load percent indicated on the LCD  Unit Over load panel to determine which phase is being overloaded    2  If the alarm is true  measure the actual output current to verify that the indications  are valid    Disconnect unnecessary load and ensure the safety  In a parallel system  a severe  load sharing error can also leads to the alarm                    56    Operator Control Panel and Display       Table 23    UPS messages       Message    System Over load    Description   Suggested Action  if any     The UPS parallel system is confirmed to overload when the total load arises above  105  nominal rating for the set basic number of UPSs  The alarm automatically  resets once the overload condition is removed    1  Confirm t
89. stem has been placed in operation by authorized personnel   See Figure 26 for more information     Figure 26 Example of configuration for single UPS with external maintenance bypass cabinet           46    Operating Procedures       6 6    6 7    6 8    6 9    Emergency Shutdown With EPO    This circuit has been designed to switch off the UPS in emergency conditions  i e   fire  flood  etc    The  system will turn off the rectifier  inverter and stop powering the load immediately  including the  inverter and bypass   and the battery stops charging or discharging     If the input utility is present  the UPS   s controls will remain active  however  the output will be  turned off  To remove all power from the UPS  the external feeder breaker should be opened     Auto Restart    When the main and bypass sources fail  the UPS draws power from the battery system to supply the  load until the batteries are depleted  When the UPS reaches its end of discharge  EOD  threshold  it  will shut down     The UPS will automatically restart and enable output power       After utility power is restored     If    Auto Recovery after EOD Enabling    is enabled       After the    Auto Recovery after EOD Delay Time    expires  the default delay is 10 minutes  During  the auto recovery delay  the NX will be charging its batteries to provide a safety margin for equip   ment shutdown if input power fails again     If the    Auto Recovery after EOD Enabling    feature is disabled  the user may restar
90. t Closed if no UPS failure  2 3 Not Used  4 UPS Fault Closed if UPS fails  5 Summary Alarm   Closed if SUMMARY ALARM   occurs  6 Summary Alarm   Closed if no alarm conditions are present  7 Any Mode Shutdown return Not     use External EPO terminal  8 Not Used  9 Common   Low Battery  10 Low Battery Closed if battery is OK  11 Low Battery Closed if LOW BATTERY point occurs   12 13   Not Used  14 UPS Any Mode Shutdown Not support  use External EPO terminal  15 On UPS Closed if ON UPS  inverter  power  16 On Battery Closed if ON BATTERY power  Utility failure   17 Common   UPS Fault  Summary Alarm   On UPS  On Battery  On Bypass  18 On Battery Closed if not ON Battery power  Utility OK   19 23   Not Used  24 On Bypass Closed if ON BYPASS  25 Not Used            A Summary Alarm occurs when any of the following conditions exist    lt  Utility power is out of the acceptable range  voltage and or frequency     UPS is in BYPASS MODE  load not on Inverter power    lt  UPS Battery is LOW    UPS fault has occurred    Table 27          Connection Description  JPO1   Pin9to Pin 17   Allows all relay COMMONS to be tied together     REMOVE    Interconnects all relay COMMONS and the  not supported   ANY MODE SHUTDOWN Return        JPO2   Pin 7 to Pin 17                   8 1 5 Multiport 4 Card    The Multiport 4 card provides 4 sets of voltage free contact closures for remote monitoring of alarm  conditions UPS operation On Battery and battery low condition  A typical application is to allo
91. t the system man   ually by pressing    Fault Clear    button     Reset After Shutdown for Emergency Stop  EPO Action  or Other Conditions    Once all appropriate measures have been taken to correct the problem indicated by the alarm mes   sage appearing on the operator control panel display  carry out this procedure to restore the UPS to  regular operation following an EPO action or for the following reasons  Inverter Overtemperature   Cut off Overload  Battery Overvoltage  excessive switching  BYP  XFER COUNT BLOCK   etc     When the user confirms that the fault is cleared     1  Press the FAULT CLEAR button to clear all alarms   2  Follow Steps 2  6 in Section 6 3 to turn off the UPS  3  Follow steps in Section 6 2 1to turn the UPS on     After the EPO button is pressed  if the input utility is removed  the UPS will shut down completely   When input utility is returned  if the rotary switch  SW1  is in either Bypass or in Normal position   the UPS will start up on Bypass  There will be power at the output terminals of the UPS     A WARNING    If the rotary switch is in the Maint  position and input utility is present  there will be power at  the output terminals of the UPS     Language Selection    The LCD menus and data display are available in 12 languages  Chinese  Dutch  English  French   German  Italian  Japanese  Polish  Portuguese  Russian  Spanish and Swedish To select a different  language than the one being displayed     1  From the main menu  press the F1  shift
92. tatic switch closes    Because output switch SW1 A is still open  the UPS channels power through Maintenance Bypass  Supply line  SW1 D   The bypass indicator extinguishes  provided that the bypass is normal     The UPS mimic display indicators will be        Indicator State  Rectifier indicator Off       Battery indicator Off       Bypass indicator Off             Inverter indicator Off  Load indicator Off  Status indicator Off                A WARNING    Do NOT turn the rotary switch until the rectifier indicator stops flashing green   4  Turn the rotary switch to BYPASS                             Indicator State  Rectifier indicator   Green  Battery indicator Off   Bypass indicator Green  Inverter indicator Off   Load indicator Green  Status indicator Amber          The maintenance switch SW1 D opens and output switch SW1 A closes  The UPS powers from  static bypass instead of from maintenance bypass  The bypass and load indicators turn on  The  design of the rotary switch ensures uninterrupted output        43    Operating Procedures       5  Turn the rotary switch to NORMAL  then press the INVERTER ON control button for 2 seconds   The inverter will start and the inverter indicator will flash green  After the inverter is ready  the  UPS transfers from bypass to inverter  the bypass indicator turns off and the inverter and load  indicators turn on     The UPS is operating normally  The UPS mimic display indicators will                             Indicator State  Rectifi
93. tch  SW1    5  Monitor board  U2     3    2       N     A oB oC oN   T2    LU oma Battery Input  Output    mA bA mB bB mC bC mN bN T1    AL an a  Bypass Input          Installation Drawings       Figure 20 Location of parallel logic board M3                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  an     5    O   3  o E o  11 11 11    11 Li 11    11 Li 10 i E  ui ui ui E  Battery 7 an ii i  Start ui 11 ui    a   B  Interface R E om m      o  e         o  E e      wg aa Parallel  E   Logic  E F m Board    o o  i      Si Fa       El  E   E    e ke  Bl lo ollo  UP   Y      O  
94. ted  Depending on the configuration  follow the appropriate instal   lation instructions for each system     Place the UPS modules side by side and interconnect as shown below     The objective of the Dual bus Synchronizer  DBS  is to keep the output of two independent UPS sys   tems  or parallel systems  in synchronization  One system is designated as the master  the other is  designated as the slave  The operating modes covered comprise master and or slave operating  inverter or bypass mode        28    UPS Multi Module Installa    tion       Figure 15 Typical dual bus system configuration with static transfer switch and Load Bus Synch    Bypass  supply       I    Bypass  supply    I                                                                                                                                                                                                                                                                                                                         Input Input Input Input   Rectifier Rectifier Rectifier Rectifier    ara wa  me        LH    ME  wv   Vv    y  i av  SK  LAR SAI LARA   AD A K  LA  E A LBS ico eee  Intermodule    opt  control cable control cable    STS    KH    Lo So OS e  v  Load    3 4 2 External Protective Devices  Refer to the instructions supplied in 1 0   Single Module UPS Installation     3 4 3 Power Cables    The wiring of power cables is similar to that of single module system  The Bypass and the Main input  sou
95. ted correctly in a parallel system   Reset the fault by pressing the  fault clear  button  then restart the inverter by  pressing the  inverter on  button        Bypass Over Current    Bypass current is over limit above 135  rating  The UPS just alarms and does  nothing        LBS Active    Load Bus Synchronisation is active  The UPS is acting as an LBS master or slave ina  dual bus configuration        Setting Save Error    History records not saved   Reserved        Mains Neutral Lost    AC Input mains reference neutral not detected        Protocol version clash    Firmware incompatibility between Monitor Board and Digital Signal Processor Board        Battery ground fault    Battery leakage to ground detected  option        Manual Turn On    Manual Turn On via front panel       Manual Turn Off          Manual Turn Off via front panel          57       Operator Control Panel and Display          Table 23 UPS messages  Message Description   Suggested Action  if any   EPO Emergency Power Off direct access key pressed or external command received       Transfer Confirm    Prompt to press    enter    key to acknowledge that an interrupted load transfer to  bypass will happen        Transfer Cancel    Prompt to press    ESC    key to avoid that an interrupted load transfer to bypass will  happen        Unit Off Confirm    Prompt to press    enter    key to acknowledge that the UPS will be disconnected from  other paralleled UPS modules        System Off Confirm    Prompt to pres
96. ternal battery circuit breaker  battery temperature sensor   communicate with a personal  computer or provide alarm signaling to external devices or for Remote Emergency Power Off  REPO    The monitor board  arranged for this purpose  is located on the rear of the operator access door  The  main features are      Input and Output dry contacts signal  one pair of contacts of relay      Emergency Power Off control  EPO      Environmental parameter input interface       User communication  for data setting and user background monitor      Intellislot    interface     Modem interface       Temperature detect interface    Figure 2 Auxiliary terminal block detail    O    oL  eng       PWR  J15     Modem X5    SNMP Card      Intellislot 2   2 X4 E pu    Lo Intelisot 1  1  O J13 J21 J25 J28 J4 J26 J30 J10           e n  eeen ooon  eO beeper     intelisiot 3      EPO Dry In MBC BCB  BEP   ONV  AGF  gt  y The black square  MH    X4 X2 X3 on each slot indicates Pin 1        11    Single Module UPS Installation       1 8 Dry Contacts  The UPS provides input dry contacts and output dry contacts     1 8 1 Input Dry Contacts    There are several input dry contacts at the X8 slot     Figure 3 Input dry contacts    kal Kal ka kal kal karl Kal Se Ge Aa    33 3 33 3 3 3 38 33 33 38    12V       Table 3 Input dry contacts at X3                Position Name Description   J4 1 ENV  Battery Room Alarm  NC    J4 2 BtG Battery Ground Fault Detection  NC   J4 3 GEN     On Generator  NO    J4 4  12V  1
97. tery Cabinets    A WARNING    Ensure any lifting equipment used in moving the cabinet has sufficient lifting capacity     Ensure that the weight is within the designated surface weight loading of any handling equipment   See Table 9 for weight details     Battery cabinets can be handled by means of a fork lift or similar equipment       NOTE  Care must be taken when maneuvering units fitted with batteries  Keep such moves to a  minimum     When the equipment has been finally positioned ensure the adjustable feet are set so that the  battery cabinet will remain stationary and stable     Seismic anchors option is available for anchoring the unit to a concrete floor     2 3 8 Cable Entry    Cables enter the battery cabinet from the bottom  Cable entry is made possible by removing a blank   ing piece fitted at the bottom to reveal the cable entry hole        20    Battery Installation       2 3 9 General Arrangement Drawings    Refer to Figures 7 and 8 for general arrangement of battery cabinet models     Figure 7 Battery cabinet bottom cable entry location               z     Bottom View  700               LITA       250  1  82 5  1  100 83  T F  1400          L 620      828          All dimensions are  expressed in millimeters        21    Battery Installation       Figure 8 Battery cabinet with fuse or optional circuit breaker locations                                                                                        1   Bottom cable entry                                 
98. times When Intellislot 1 Communication mode is Modem  this parameter sets   the number of times a number is redialed to send an alarm notification    Phone No 1 When Intellislot 1 Communication mode is Modem  this is the first   phone number to be dialed  to send an alarm notification     Phone No 2 When Intellislot 1 Communication mode is Modem  this is the second   phone number to be dialed  to send an alarm notification     Phone No 3 When Intellislot 1 Communication mode is Modem  this is the third   phone number to be dialed  to send an alarm notification     Command password User can modify the command password    Battery maintenance ost     Xn tho ty aoe el mut a aos an  Ea   Bety capacity Ar  a j System test This is a self test of the UPS  When the user activates this function  a  tests  pop up window appears about 5 seconds later to show the results    Stop testing leer ee ae a battery maintenance test  battery capacity test or  oa  UPS version a sey bee  version numbers for the inverter  rectifier and   UPS model Provides UPS model information   for example  208V 60Hz                                                                                                  54       Operator Control Panel and Display       7 2    Current Record Window    Keeps a log the events that resulted in the current mode of operation  Ignores transient conditions    that have been resolved     Use    page     F1  and up   down arrow to read the events     For a complete history log  refe
99. tion between UPS modules as shown below  The parallel control  board is mounted on the top  behind protective cover of each UPS module  refer to Figure 20   The  ring configuration ensures high reliability of the control  Refer to Figure 13     13 Connection of 1 N system parallel control cables    2  D UPS 6     Parallel Board Parallel Board Parallel Board Parallel Board Parallel Board                                                                                                             Hot Standby UPS Modules    Cabinet Installation    Place the UPS modules side by side and interconnect as shown below     The hot standby mode comprises two series connected UPS modules of the same rating  One module  is designated as the hot standby master  and the other module is designated as the hot standby slave   Their roles are determined by power connection and configuration software  In normal operation  both  slave and master operate in normal mode and the output from one upstream UPS feeds the bypass  input to the other  downstream  UPS  The output of the downstream UPS is connected to the critical  load and is always synchronised to the output of the upstream UPS  If the inverter of the UPS con   nected to the load fails  the inverter of the upstream UPS supplies the load through the downstream  UPS bypass circuit  The system can be programmed to cycle the downstream UPS between Normal  mode and bypass mode so that both ups are equally exercised     NOTE  If it is a hot stand
100. tted with  remote trip units     4  Normally Closed EPO   X2  1 amp 2  these terminals are supplied factory linked on the monitor  board     Figure 10 Emergency power off connections         lt   yos    x2 4 Monitor Board                           X2 3    et X2 4 Monitor Board          EPO y         X2 3   F X2 4    Monitor Board    EPO         24    UPS Multi Module Installation       3 2  Paralleled UPS Modules    The basic installation procedure of a parallel system comprising two or more UPS modules is the  same as that of single module system  The following sections only introduce the installation proce   dures specific to the parallel system     3 2 1 Cabinet Installation    Place the UPS modules side by side and interconnect as shown in Figure 11  The distribution panel   external bypass cabinet  is optional but recommended for ease of maintenance and system testing     Figure 11 Typical 1 N system block diagram with common input supply  with separate batteries and  optional output   bypass distribution panel    SUPPLIED BY OTHERS  INPUT MAINS INPUT MAINS  SUPPLY L1  L2  L3  N SUPPLY L1  L2  L3  N  OPRY Ipa A 1 Ka a ska AE    UPS1 CB1     SWI C    l   l   l   I   l   Ser Y wic    l   l   p4 l  STATIC l  SWITCH A    l   l   l       l   I    l l  l l  l l  l              l    l  FUSES        FUSES  IT STATIC        SWITCH pA    I l  I            l    l  l    l         HZ    CHARGER     CHARGER  BATTERY 1 BATTERY2    INVERTER l 1    SW1 D  l  SW1 A l SW1 A  Lee a E 4 A ee
101. ure could occur  if they are subjected to shock loading     When the equipment has been finally positioned  ensure the adjustable feet are set so that the UPS  will remain stationary and stable     Floor Anchoring    Diagrams in 4 0   Installation Drawings show the location of the holes in the base plate through  which the equipment may be bolted to the floor  If the equipment is to be installed on a raised floor it  should be mounted on a pedestal suitably designed to accept the equipment point loading  Refer to the  base view Figure 18 to design this pedestal     Cable Entry    Cables can enter the Liebert NX UPS and battery cabinet from below  Cable entry is made possible by  removing a blanking piece fitted at the bottom of equipment to reveal the cable entry hole     External Protective Devices    Circuit breakers or other protective devices must be installed in the AC supply  external to the UPS   This chapter provides guidelines for qualified installers who must have knowledge of local wiring  practices pertaining to the equipment to be installed     Rectifier and Bypass Input    Overcurrent protection must be installed at the distribution panel of the incoming main supply  The  protection must discriminate with the power cables current capacity and with the overload capacity of  the system  see Table 36   As a guideline  a thermomagnetic circuit breaker  with an IEC 60947 2  trip curve C  normal  for 125  of the current listed in Table 1 is suitable     Split Bypass  
102. verter will be shut down  EOD is settable  from 1V to 1 9V per VRLA cell  or 1 0 to 1 3 V per NiCd cell      Battery Isolator Open Warning  If the battery isolator is open  this warning will occur     The external battery to the UPS through an external battery isolator  which is manually closed and  electronically tripped via the UPS control circuits        41    Operating Procedures       6 0 OPERATING PROCEDURES       6 1    6 1 1    A    WARNING    Hazardous mains and   or battery voltage present behind covers     No user serviceable parts are located behind covers that require a tool for their removal  Only  qualified service personnel are authorised to remove such covers     Introduction    The NX can operate in any of four modes  as shown in Table 10  This section provides instructions on  switching between modes  resetting the UPS  switching the inverter On and Off and performing other                operations   Table 10 UPS operating modes  Rotary Switch  Operating Mode Position Description  Normal Operation   NORMAL The UPS is powering the load   BYPASS or The load power is supplied through the static bypass line  This may be  On Static Bypass considered as a temporary mode during load transfers between inverter  NORMAL   y A  and maintenance bypass or supply under abnormal operating conditions   No load power is supplied by the UPS  The load is connected to utility  On Test TEST power via the Maintenance Bypass Supply line  NOTE  The load is not  protected against 
103. ws a  maximum of four computer systems to simultaneously monitor the status  e g   utility power failure    low battery  of a single UPS     This card is supported in any of the three NX Intellislot bays        64    Options   For Assembly Inside the UPS Cabinet       Figure 37 SiteNet MultiPort4 Intellislot pin configuration    Table 28    ups  Tp    PA   st    A     c                       A  0  sul E    SiteNet MultiPort4 Intellislot pin assignment       Y  5    Assignment  Description    Low Battery       Not Used       Not Used       Not Used       Not Used       Not Used       Low Battery Common       Utility Fail Common          OJO J O OI  BR  Ww  Mm               Utility Fail       CPU    CPU    CPU    CPU       65    Options   For Assembly Inside the UPS Cabinet       8 2    OC485 Web Card     Modbus  Jbus  IGM Net  The OpenComms 485 Card facilitates SiteScan Web or Building Management Systems monitoring     The RS232 port is used for connection to a personal computer for setting up     The RS 485 port supports IGM Net and Modbus JBus protocols and maps the operation of the UPS  including status  alarms and data  voltages  currents  frequency  power  power factor  temperatures    etc      Figure 38 OC485 Web card    8 2 1                                                 Table 29 NX communication options  On the UPS  Physical Labeled LCD screen  Monitoring  description ID Name under Settings  Devices Baud  of port of Port controlled by  supported rate Comments  Multip
104. y room design    2 5                                                                                                       Battery Control    Battery temperature sensor cables are connected between UPS auxiliary terminal block X3 BCB  the  Battery Temperature sensor and the battery as shown in Figure 6     Cables connected to X3 BCB must contain a protective earth wire or a shield  be segregated from  power circuits  double insulated and of a typical 0 5 to 1mm2 cross section area for maximum runs  between 25 and 50 meters respectively  The shield should be connected to the protective earth of the  battery cabinet or battery breaker  not at the UPS       23    UPS Multi Module Installation       3 0 UPS MULTI MODULE INSTALLATION       3 1 General    The installation of a multi module UPS configuration must follow the installation procedure for a sin   gle UPS module with the additional requirements detailed in this chapter     In addition to the local EPO push button on the front panel of the UPS module  that stops operation of  that module   the UPS supports also a remote emergency stop to permit simultaneous multi module  shutdown         NOTES  1  The remote emergency power off switch must be voltage free and Normally Open or  Normally Closed     2  The open voltage supplied is 12VDC   lt  20mA    3  This external emergency stop may be supplied with a second set of contacts that can be used  to trip incoming mains or bypass supply circuit breakers supplied by others and fi
105. y switch configurations             e na  42  UPS control and display panel components                 na  49  Rectifier indicator     cack Re ayes NS CARE wad ae ete WER en as EN a eden dein ates 50  Battery ni dica tor 2 so ar Nas a A A Uu Pca HUA RO had ab Sansa is 50  Bypass indicator 5354224 Ae NR A A BEAR bE ERS BER ERR al 50  Inverter InGic A ged ee Re ae tes oa Bh en de as Oe RN 50  Load indicator 425 Ea deed ESA a Ga Bw ah at SD Ba eda 50  Status  Alarm  IOndicator   E      aaa a aaa ee cee eee a a a GE a a aga aa a 50  Audible alarm key sa tds Beb Bah Gs Bh aS ak Re Se TK NG kage ooh re eh 50  Menu key Icons and their meaning           eea 51  UPS system  window A a a A a aa aa WOR aka be nh ank 53  Descriptions of UPS menus and data window items         eee 53  UPS Messages a este Ra eels  Whine Nae cinch at alte oats bag a E R fel 55  Prompt windows  Meanings            Tag e ai a Ba aaa an 59  Dry contact fault alarm signal is available for remote monitoring               e  61  Relay Card pin configuration    64  SiteNet MultiPort4 Intellislot pin assignment              ii    65  NX communication Options  66  Compliance with European  international standards           0 0    ccc eee eens 67  Environmental characteristics                ii    67  Overall efficiency  heat losses and air exchange    67  Mechanical characteristics pss ga An Wade  mann RAN e E EA BRA Pn Aa ana Rass 68  Rectifier AC input  mains              ii    na  68  Inverter output to critical 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
【BP16-35,-50】 取扱説明書    TECHNICAL BULLETIN  Read This First - Firmware Center  情報公開審査会第1部会開催記録 1 日時 平成16年7月14日  1 Pressione    HANDLEIDING USER MANUAL MODE D'EMPLOI  T'nB IPH48SLOVE mobile phone case  Kurzanleitung - SAM Antriebstechnik    Copyright © All rights reserved. 
   Failed to retrieve file