1. AMERICAN POWER CONVERSION UXBP Battery Pack Models UXBP24 UXBP24L UXABP48 Installation Instructions 1 Introduction The UXBP is a large Battery Pack module designed to be used with a Smart UPS system to provide a significant increase in on battery runtime for your protected equipment For complete information on the Smart UPS system refer to the Owner s Manual that came with your UPS Note Ifyou are installing your Smart UPS system for the first time be sure to read the Smart UPS Owner s Manual first Set up your UPS system before installing the UXBP 2 Safety CAUTION e Use the UXBP only with a UPS that is properly installed according to the UPS Owner s Manual and connected only to a two pole three wire grounding mains receptacle The receptacle must be connected to appropriate branch protection fuse or circuit breaker Connection to any other type of receptacle may result in a shock hazard and may violate local electrical codes e Avoid installing the UXBP in locations where there is water or excessive humidity e Do not allow water or any foreign object to get inside the UXBP Do not put objects containing liquid on or near the unit e Toreduce the risk of overheating the UXBP avoid exposing the unit to the direct rays of the sun Avoid installing the unit near heat emitting appliances such as a room heater or stove e Do not move the UXBP with its batteries installed Doing so may
2. maintenance free sealed lead acid Battery type Nominal battery pack voltage 24 Vdc Model UXBP24 UXBP24L 48 Vdc Model UXABP48 Typical battery life 3 to 6 years depending on environment and use Recharge time See table in Section 7 4 7 2 Environment Operating 0 to 40 C 32 to 104 F temperature Storage 15 to 45 C 5 to 113 F temperature Operating and storage relative 0 to 95 non condensing humidity Operating 0 to 3 000 m 10 000 ft elevation Storage 0 to 15 000 m 50 000 ft elevation 990 0191C 04 2007 7 3 Physical UXBP24L UXBP24 UXABP48 Size H W D 31 0 x 44 7x75 4cm 31 0 x 44 7 x 75 4 cm 12 2 x 17 6 x 29 7 in 12 2 x 17 6 x 29 7 in UXBP weight 74 5 kg 164 0 lbs 127 3 kg 280 0 Ibs with batteries Shipping weight 90 0 kg 198 0 Ibs with batteries 142 7 kg 314 0 Ibs 7 4 Runtime versus load Run times are typical at 25 C 77 F Run Time Runtime with SUA1000UXI load thr 2hr 3hr 4hr 6hr 8n 1 UXBP24 500 VA 1 UXBP24L 1 UXBP24 1 UXBP24L 1 UXBP24 1000 VA 1 UXBP24L 1 UXBP24 UXBP24L Runtime with SUA2200UXI SUA3000UXI Runtime required koat om ee om em om o 500 VA 1 UXABP48 2 UXABP48 2000 VA 1 UXABPAS S UXABPAS 3000 vA 1 UXABPAS 6 UXABPAS Recharge Time oe eee 3000 VA UPS Recharge to 90 capacity after discharge into 50 of rated full load Technical Support and Custome
3. Battery Pack Use only factory authorized batteries in the Battery Pack Move the pallet containing the Battery Pack to the desired operating location before installing the batteries see Section 4 3 Do not move the Battery Pack with the batteries installed 4 4 1 Warning It is important that you read and understand the following warnings and cautions before installing the batteries in the UXBP e Only personnel familiar with the dangers of batteries and the required precautions should perform or supervise battery replacement Keep unauthorized personnel away from batteries Replace batteries with the same number and type of sealed lead acid batteries as originally installed in your UXBP e WARNING Use only factory authorized sealed batteries in the Battery Pack Use of unsealed batteries may result in a hazardous chemical spill e CAUTION Do not dispose of batteries in a fire The batteries may explode e CAUTION Do not open or mutilate batteries They contain an electrolyte which is toxic and harmful to the skin and eyes e CAUTION A battery can present a risk of electrical shock and high short circuit current When replacing batteries remove wrist watches and jewelry such as rings Use tools with insulated handles e The batteries in this UPS are recyclable Dispose of the batteries properly The batteries contain lead and pose a hazard to the environment and human health if not disposed of properly Refer
4. cabinet A DC voltmeter is required to perform this simple test Warning Do not install the UXBP until this test procedure has been performed 1 Locate the gray UXBP24 UXBP24L or the blue UXABP48 coupler at the end of the DC power bus cable See item 2 in Section 3 2 2 Measure the DC voltage across the two conductors in the coupler Warning Care must be taken not to short circuit the coupler with the test leads 3 Refer to the following table for the status of the UXBP Table 1 UXBP24 UXBP24L Battery Pack Voltage Battery Pack Voltage Battery Pack Status 22 5 Vdc 28 5 Vdc Ready to Install 0 0 Vdc 22 4 Vdc ae 28 6 Vde 57 0 Vde Miswired or Bad Battery Table 2 UXABP48 Battery Pack Voltage Battery Pack Voltage Battery Pack Status 45 0 Vdc 57 0 Vdc Ready to Install 0 0 Vde 45 0 Vdc Miswired or Bad Battery 4 When the Battery Pack Status is Ready to Install complete the final steps of the installation If the Battery Pack Status is Miswired or Bad Battery disconnect the internal battery connections Do not connect the UXBP to any other equipment Review the Installation and Test Procedures and if necessary contact APC s Technical Support for additional help with the installation and troubleshooting When calls are placed to the Technical Support Line please have the following information ready when the representative answers 1 The UXBP serial number 2 The battery pack vo
5. abinet one for each battery 4 Selecta battery and using firm pressure slide the battery all the way to the rear of the cabinet 5 Connect the battery s coupler to the matching coupler located on the cabinet wall Warning Do not connect the couplers mounted to the cabinet together 6 Select the second battery and move it into place UXBP24L If you have a UXBP24L place the second battery on the same side of the cabinet and in front of the first battery Note The batteries may be installed on either side of the cabinet but both batteries must be installed on the same side of the cabinet UXBP24L UXBP24 and UXABP48 If you have a UXBP24 or UXABP48 slide the second battery all the way to the rear of the cabinet beside the first battery UXBP24 and UXABP48 7 Connect the second battery s coupler to the matching coupler mounted on the side of the enclosure and route the battery cable over the top of the battery Warning Do not connect the batteries together 8 Ifyou have a UXBP24L proceed to Section 4 4 4 If you have a UXBP24 or UXABP48 repeat steps 5 through 7 for the front battery pair 9 Refer to Section 4 4 4 for Test Instructions before replacing the battery door front panel 4 4 4 Installing and Replacing Batteries Test Instructions Before coupling the UXBP to a Smart UPS or another battery pack a test must be performed to insure that the batteries have been properly installed within the
6. ltage measured at the gray UXBP24 UXBP24L or the blue UXABP48 coupler 3 Each of the individual battery voltages 4 4 5 Final Installation When the correct battery voltage has been verified perform the following steps to complete the battery installation 1 Replace the battery door front panel and reinstall the five 5 phillips screws that were removed in Step 1 2 Connect the UXBP gray UXBP24 UXBP24L or blue UXABP48 DC coupler to the UPS or to another matching battery pack if desired This procedure is described in Section 4 5 4 5 Module interconnections After you have positioned the Battery Pack and installed the batteries you can connect the Battery Pack to the UPS or to other Battery Packs in the system Refer to the following instructions to properly install the battery pack couplers Remove clamp ia Sia Connect couplers Secure clamp 1 Use a phillips screwdriver to remove the battery pack coupler clamps from the UPS and from all but the last Battery Pack 2 Connect the blue battery pack couplers as shown Do not attempt to connect the gray UXBP24 UXBP24L or the blue UXABP48 battery pack couplers with the gray battery couplers inside the cabinet Use the supplied UXABP48 adaptor cable when appropriate 3 Fasten the battery pack coupler clamp to secure the couplers in place 4 Repeat for any additional Battery Packs Installation of the Battery Pack is com
7. ner inspect it for damage that may have occurred in transit Immediately notify the carrier and place of purchase if any damage is found The packing materials are made from recyclable materials and should be saved for reuse or disposed of properly 4 2 Moving the UXBP The UXBP and its batteries are quite heavy and should be moved on the original shipping palette using a fork type hand truck or separately on a hand truck Never move the Battery Pack while its batteries are installed Warning Do not move the UXBP with its internal batteries installed Doing so could result in severe physical damage to the Battery Pack and cause a shock hazard 4 3 Placement The UXBP may be installed in any protected environment that is suitable for the UPS Refer to the Owner s Manual that came with the UPS Identify a location convenient to the UPS with enough room in front of and behind the unit for servicing There should be at least 30 5 cm 1 ft clearance behind the UXBP Leave enough clearance in front that you can comfortably access the battery compartment Caution Do not stack more than 4 UXBPs on top of each other or on top of other components of the UPS system Damage to the unit could result 4 4 Unpacking and Installation The UXBP is shipped with the cabinet secured to the shipping pallet and its batteries unconnected You must unpack the batteries and unbolt the cabinet from the pallet before you can use your
8. plete Refer to the UPS s Owner s Manual for information on starting up the system 4 6 Estimating Runtime with BackPack exe The diskette included with the UXBP contains an MSDOS utility that will provide the estimated runtime for your configuration at a given load Follow the instructions printed on the diskette label with the following exception When the program asks for the number of battery packs installed multiply the number of installed UXBP packs by 5 if you have a UXBP24 or UXABP48 and by 3 if you have a UXBP24L and insert this result For example if you have 2 UXBPs installed use 10 as the result 2 x 5 10 5 Storing the Battery Pack The Battery Pack should be stored in a covered location and with its batteries in a fully charged state reports 100 capacity to the UPS In extended storage use the UPS to refresh the Battery Pack every six months in environments where the temperature is 15 to 30 C 5 to 86 F Refresh the Battery Pack every three months in environments where the temperature is 30 to 45 C 86 to 113 F 6 Battery Life 6 1 Battery life You can expect to receive three to six years of service from the Battery Pack s batteries When the batteries can no longer sustain a charge the Replace Battery indicator on the front panel of the UPS lights Refer to Section 4 to replace the batteries 7 Specifications 7 1 Battery Two UXBP24L or Four UXBP24 UXABP48 spill proof
9. r Service All customers use Web site www apc com American Continent contact American Power Conversion 132 Fairgrounds Road West Kingston Rhode Island 02892 1 800 800 4APC 1 401 789 5735 European Continent contact American Power Conversion Ballybritt Business Park Galway Ireland 1 800 702000 353 91 702020 AMERICAN POWER CONVERSION
10. result in damage to the Battery Pack and or a shock hazard e Install only factory authorized batteries in the UXBP Improper batteries may result in a hazardous chemical spill and or a shock hazard 3 Presentation 3 1 UXBP front ee Front View panel removed Front View UXBP Battery Pack The UXBP contains either two UXBP24L or four UXBP24 UXABP48 user replaceable sealed lead acid batteries and the associated cables and connectors 1 Front panel Battery door The front panel of the Battery Pack provides access for battery installation and replacement Refer to Section 4 when installing or replacing batteries 2 Battery internal coupler These four couplers connect the UXBP s replaceable internal batteries See Section 4 3 Batteries The Battery Pack contains either two UXBP24L or four UXBP24 UXABP48 nominal 12 Vdc sealed lead acid batteries Use only factory authorized batteries in the UXBP 3 2 UXBP rear Rear View 1 Battery Pack rear panel coupler Additional UXBP Battery Packs are connected to this coupler Refer to Section 4 5 for information on making connections with this coupler 2 In line Battery Pack coupler This coupler connects the Battery Pack to the UPS or to the rear panel coupler on another matching Battery Pack 4 Installation 4 1 Receiving inspection When you remove the UXBP from its shipping contai
11. to local codes for proper disposal requirements or return the battery to a factory authorized Service Center 4 4 2 Unpacking the Battery Pack To unpack the UXBP follow the procedure outlined below 1 Remove the five 5 phillips screws securing the battery door front panel to the Battery Pack 2 Tilt the battery door front panel forward then lift it away from the cabinet 3 Remove each of the batteries and all corrugated packing material from inside the cabinet Remove the corrugated sleeves from the batteries Warning Do not connect the batteries together Note For safety reasons it is important that all packing material be removed from the interior of the cabinet 4 On the outside of the cabinet there are four 4 1 4 20 screws that secure the cabinet to the shipping pallet Use a phillips screwdriver to remove these four 4 screws 5 Move the empty cabinet to its permanent location 6 Proceed to Section 4 4 3 Step 3 to complete the battery installation 4 4 3 Battery installation and replacement To install the batteries follow the procedure outlined below 1 Remove the five 5 phillips screws securing the battery door front panel to the Battery Pack 2 Tilt the battery door front panel forward then lift it away from the cabinet 3 Position the batteries on the floor in front of the cabinet The terminals should be up and to the inside of the cabinet Note the gray couplers 4 located inside the c

Download Pdf Manuals

image

Related Search

Related Contents

GE EDW5000 User's Manual  Please read this manual before operating this scanner  Unimatic TW - V  Lenovo Yoga Tablet 10 16GB Silver  DTP-3A 取扱説明書  3004_9700 Quick Start Manual_121713.indd - DayMark  組 立 説 明 書  Mitsubishi Electric EX320U data projector  S-32® Sanctuary Series™  MANUEL D`INSTALLATION  