APC Smart-UPS VT

image

Contents

1. oE L Connect the AC input cables and the neutral to the input cable landings Connect the AC output cables and the neutral to the output cable landings Connect the ground cables to the studs earth symbol beneath using a screw Dual mains Remove the three busbars A B and C by removing two M6 screws from each busbar Connect the AC input cables and the neutral to the input cable landings Connect the bypass cables and the neutral to the bypass cable landings Connect the output cables and the neutral to the output cable landings Connect the ground cables to the studs earth symbol beneath using a screw Connect the DC Battery Cables if applicable Connect battery cables BAT BAT and N to the battery cable landings a VA a TE JT Note ONLY APC Smart UPS VT XR Battery Enclosure Q SUVTRBXRB6 must be connected to the UPS Connect the Communication Cables J106 and J108 pin connections Note The UPS must be connected to either a dry contact or Q a 24 VDC EPO Emergency Power Off switch supplied through other vendors Q Note The external EPO 24 VDC 1500 mA circuit can be Note Always follow the pin connection procedures from Q the top and work down J106 8 1 J108 1 6 oi 5108 pin
2. 30 kVA Mains input Bypass input Output Duration 40 kVA Mains input Bypass input Output Duration Internal fault 2 kA 1 7 kA 9 kA lt 10 ms 2 1 kA 1 8 kA 9 kA lt 10 ms 2 5 kA 2 3 kA 9 kA lt 10 ms 2 5 kA 2 3 kA 9 kA lt 10 ms 3 kA 2 3 kA 14 kA lt 10 ms 800 overload bypass operation 121 5 A 121 5 A 500 ms 182 A 182 A 500 ms 244 A 244 A 500 ms 244 A 244 A 500 ms 487 A 487 A 500 ms 150 overload normal battery operation 22 8 A 10s 34 2 A 60 s 68 4 A 60 s 68 4 A 60 s 91 2 A 60 s 125 overload normal battery operation 19A 10 min 25 4 A 10 min STA 10 min 57A 10 min 76 A 10 min Conti nuously 16 4 A 16 7 A 16 7 A 24 6 A 25 1 A 25 1 A 32 5 A 33 4 A 33 4 A 32 5 A 33 4 A 33 4 A 65 6 A 66 9 A 66 9 A For the output value the short circuit level is indicated Recommended lug size and torque value Note Power terminal lug diameter 6 mm Torque value 7 Nm Checklist m Check that the power wiring is torqued to 7 Nm m Verify phase rotation to the right L1 L2 L3 and make sure a neutral connection is present Leave a wiring diagram on site for service personnel Re install the cable landing cover Re mount the front panel O OO O If XR Battery Enclosures are installed make sure that all DC breakers if applicable are in the OFF
3. system is level Caution Do not move the enclosure after the leveling feet AN have been lowered Floor Anchoring if applicable Anchor the UPS enclosure to the floor Note Floor anchoring bolts are not provided with the UPS Purchase the bolts locally minimum size M8 Follow the specifications given by the manufacturer of the floor anchoring system when bolting the UPS system to the floor Reuse the two transport brackets one on each side that were used to secure the UPS to the pallet during transport Drill two to six holes in the floor for each bracket Attach with bolts Prepare for Cables Bottom cable entry T UET WO ih ULLET TITI A From the rear of the UPS loosen the six M4 screws from the upper cover the cable landing area on the back and remove Route the cables from the slanted back plate up through the punched bracket and into the cable landing area Fasten the cables with cable ties Note A conduit box part no SUVTOPT001 is available Q as an option Connect the AC Input and AC Output Cables Warning Use compression type lugs ONLY Do not loosen or add cables to any factory preinstalled cables on busbars Use the front part of busbar for connection only A Single mains WILila i L2 4 L3l A i o o Jo llo lo lo lle To INI Ni GS amp LEa L2 Loe g N
4. 0 70 40 70 E zE the side panel hole and run Nominal input current A 19 4 18 5 17 8 26 0 247 2338 Nominal output current A 22 8 21 7 20 9 30 4 28 9 27 8 the cable upwards inside the panel Max input current A 21 4 20 3 19 6 28 6 27 2 26 2 Input current limit A 25 2 25 2 25 2 33 8 33 8 33 8 30 kVA 40 KVA Pull the cable out of the side panel through the hole Input current based on rated load and batteries fully charged UPS ratings 380V 400V 415V 380V 400V 415V l he N k Input current based on fully battery recharge nominal voltage and rated load Closest to the ore 3 Current limitation through electronic current limiting is based on full battery Nominal output current A 45 6 43 3 41 7 60 8 57 7 55 6 Management Card area recharge and 15 input voltage Plug the cable into the probe socket PowerChute inlet Reattach the cable inlet plate Battery input UPS ratings ISkVA 15kVA 20kKVA 30kKVA 40 kVA Nominal voltage V 192 192 192 192 192 External battery fuse A 125 125 125 125 125 125 1 6 1 75 V cell automatic depending on load Bypass input 10 kVA UPS ratings 380 V 400V 415V Input frequency Hz 50 60 50 60 50 60 Nominal input current A 13 0 12 3 11 9 Input current based on rated load and batteries fully charged 15 kVA 20 kVA UPS ratings 380 V 400V 415V 380V 400V 415V Input frequency Hz 50 60 50 60 50 60 50 60 50 60 50 60 Nominal input c
5. 990 1986B 001 ArC by Schneider Electric Installation Smart UPS VT 10 40 kVA 380 400 415 V with batteries aa j JOG W ta T li H MT H 10 40 kVA 20 40 kVA without front panel 10 15 kVA without front panel 10 40 kVA from the rear 10 20 kVA 10 20 kVA without front panel 10 20 kVA from the rear IOI 10 2008 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS Warning ALL safety instructions in the Safety Sheet 990 2822 must be read understood and followed when installing the UPS system Failure to do so could result in equipment damage serious injury or death Caution All electrical power and power control wiring must be installed by a qualified electrician and must comply with local and national regulations for maximum power rating Note Ensure that the unit is in its final location prior to installation Warning After the UPS has been electrically wired do not start it up Start up is commissioned to APC authorized personnel only Note Battery and utility mains power must not be Q connected until all other wiring has been completed Level the Enclosure Warning The system must be installed on a level floor AN The leveling feet will stabilize the enclosure but will not account for a badly sloped floor Use a 13 14 mm wrench to adjust the four leveling feet Ensure that the
6. connections Normally open EPO Normally open EPO return Normally closed EPO Normally closed EPO return 24 V SELV supply SELV ground 106 pin connections Ext charging control return External control of charging Q3 active return Q3 active Battery measurement supply Battery unit quantity Max battery temperature Battery measurement return Should be used with APC XR Enclosures NOUR ODN CO CGC ooh WD EPO wiring pin connections J108 Connect the EPO cable using one of the following four wiring configurations J108 1 Dry Contracts Normally Open 1 ae EPO is activated when pin 1 is connected 2 EPO circuit to pins 3 and 5 3 Connections 2 4 6 3 5 and 4 m 1 gt 5 6 J108 2 24 V Normally Open 1 a EPO is activated when an isolated SELV 24 2 EPO circuit VDC voltage is supplied on pin 1 with 3 reference to pin 2 4 Connections 3 5 and 4 6 5 6 J108 3 Dry Contacts Normally Closed 1 EPO is activated when a connection from 2 pin 3 to pin 5 is opened 3 Connections 4 6 EPO circuit 5 6 J108 4 24 V Normally Closed 1 EPO is activated when a SELV 24 VDC 2 voltage is removed from pin 3 with 3 reference to pin 4 4 EPO circuit 5 6 Pin connect
7. erface display to the UPS ratings 380 V 400V 415V Input current limit A 50 1 50 1 50 1 66 9 66 9 66 9 right to the unlocked position l Input current based on rated load and batteries fully charged Lift the front panel to free Input frequency Hz 40 70 40 70 40 70 A Input current based on fully battery recharge nominal voltage and rated load 3 Current limitation through electronic current limiting is based on full battery the two tabs at the bottom of Nominal input current A 13 0 12 3 11 9 recharge and 15 input voltage the enclosure Max input current A 14 3 13 5 131 Input current limit A 16 8 16 8 16 8 AC output Remove the two screws l Input current based on rated load and batteries fully charged Fom thecablednietatthe Input current based on fully battery recharge nominal voltage and rated load 10 kVA Current limitation through electronic current limiting is based on full battery front and remove the cable recharge and 15 input voltage UPS ratings 380 V 400V 415V inlet plate palei Nominal t t A 15 2 144 13 9 mina rren i Management Guide the cable through output curre the hole in the bottom plate 15 kVA 20 KVA and up through the cable ao PE UPS ratings 380V 400V 415V 380V 400V 415V 15 kVA 20 kVA inlet ee UPS ratings 380 V 400V 415V 380V 400V 415V Guide the cable through Input frequency Hz 40 70 40 70 40 70 40 70 4
8. ions J106 UPS J106 Pins 1 to 4 are for battery measurement only applicable to APC XR Battery Enclosures 8 Charging control switch Pins 5 and 6 are for external maintenance bypass Q3 auxiliary switch N C type When Q3 is closed signals are fed back to the UPS controller Q3 switch Pins 7 and 8 are for external charge control When 7 and 8 are closed the UPS charges batteries with a pre defined percentage 0 25 50 75 100 of the maximum charging power J200 XR Batteries e DO WO LP OD NA e NORA To be used in generator applications or if special codes require control of charging When Q3 is closed signals are fed back to the UPS controller plated N C auxiliary switch Q Note Reinstall the cable landing cover Note When connecting the Q3 auxiliary signal use gold Connect APC communication options Specifications Note The cable routing of the power chute software and 30 kVA 40 kVA the temperature sensor 1S identical Warning The UPS must be supplied from a 380 220 V Q AN 400 230 V or 415 240 V L1 L2 L3 N PE 50 Hz UPS ratings 380 V 400V 415V 380V 400V 415V Note The temperature sensor is provided in a plastic bag Q attached to the front of the UPS behind the front panel Input frequency Hz 40 70 40 70 40 70 40 70 40 70 40 70 AC input Nominal input current A 38 6 36 7 35 3 51 7 49 1 47 3 user int
9. position and that both 125 A fuses are removed from the XR Battery Enclosures For any optional equipment refer to the product specific manuals Contact Information For local country specific centers go to www apc com support Appendix Wiring diagrams Diagram with Maintenance Bypass Panel Bypass Bypass breaker Mains Maintenance breaker Enclosure Diagram without Maintenance Bypass Panel Bypass breaker fuses Bypass Bypass Input Mains breaker fuses Mains Load Output Battery Enclosure
10. urrent A 19 4 18 5 17 8 26 0 24 7 23 8 l Input current based on rated load and batteries fully charged 30 kVA 40 kVA UPS ratings 380 V 400V 415V 380V 400V 415V Nominal voltage V 50 60 50 60 50 60 50 60 50 60 50 60 Nominal input current A 38 6 36 7 35 3 51 7 491 473 i Input current based on rated load and batteries fully charged Recommended current protection input output disconnect must be provided by the customer Q Note AC input output over current protection and AC Q1 Q5 Q3 Q2 10kVA 16 16 16 16 15kVA 25 25 25 25 20kVA 35 35 35 35 30kVA 50 50 50 50 40kVA 63 63 63 63 Required upstream current protection mains input gL type fuse 2 Required upstream current protection bypass input gL type fuse Recommended cable sizes Note The recommended cable sizes are based on an Q environment with an ambient temperature of 30 C Sag Battery input A tput o B t Mains input C outpu mm 70 P i A inpu mm mm Wire 10 kVA 25 2 5 6 2 5 15 kVA 6 6 10 6 20 kVA 10 10 16 10 30kVA 16 16 35 16 40 kVA 25 25 50 25 Note Use Molex lug type or equivalent and crimp to Q manufacturer s specifications Warning At 100 switch mode load the neutral must AN be rated for 200 phase current Minimum breaker settings 10 kVA Mains input Bypass input Output Duration 15 KVA Mains input Bypass input Output Duration 20 kVA Mains input Bypass input Output Duration