Home
        Max Caddy Owners Manual
         Contents
1.                                                                                                                                                               HEAT SHIELD    HEAT SHIELD  CEILLING     3 4  CEILLING       60   1    3 4       j   xj      6         1    18     i HOT AIR PLENUM      1 45   ELBOW 8 MIN   e  L 24        NNN   STATIC PRESSURE CHECK  TN       POINT MIN  0 20  W C   NC N            se 1 q     OIL UNIT ip WALL        WALL  Sh        SMOKE PIPE b     d                poo     24       24     N B  FOR THE AIR RETURN  RESPECT THE OPENING SURFACE OF THE COLD AIR PLENUM OF THE  FURNACE     50    3 2 POSITIONING THE APPLIANCE    For a safe and quiet operation  the furnace must be levelled in both directions  Give each    U    shape track an equal  support so that the weight is evenly distributed     3 3 PIPE CONNECTOR AND DAMPER    The pipe connecting the furnace to the chimney must be as short as possible  If a deviation is required  the use of 45    elbows is highly recommended for a better evacuation of the smoke in the chimney of the wood burning furnace  The  barometric damper provided with the appliance must be installed on the oil unit evacuation pipe  approximately 24   from the flue outlet of the unit        PSG  UH MAX CADDY    ol    34 POSSIBLE INSTALLATIONS    FOR THE WOOD OIL MAX CADDY             ELBOW 45                     MINIMUM DRAUGHT IN  WOOD FLUE PIPE  0 04  W C                               REDUCER 7     6           L   lt  77            
2.                                                                                                    BAROMETRIC DAMPER 5   DRAFT 0 02  W C                                                                                                                                                        VERIFICATION HOLE  FOR OIL COMBUSTION                                                                FURNACE TYPE CHIMNEY PIPE  DIAMETER  MAX CADDY  7                     REQUIRE A FLUE PIPE REDUCER  CEILING                                           MINIMUM DRAFT IN    WOOD FLUE PIPE  0 04  W C                      REDUCER 7       6                                                                                      BAROMETRIC DAMPER 5   DRAFT 0 02  W C                                                                                   5  A                              VERIFICATION HOLE  FOR OIL COMBUSTION                                                             CETT                                                                                                                   52    3 5 COMBUSTION AIR    Consult Section A of this manual for more details     3 6 ELECTRICAL WIRING    The whole wiring from the distribution panel to the heating unit shall comply with the applicable electrical standards and  local codes  The unit should be connected to its own 15 amp 120VAC electric circuit  Consult section A of this manual  for the electrical wiring diagram using a Beckett or Riello burner     
3.                                                                               5  2 SAFELY RULES                          aa ua             5  2 1 GENERAL REOUIRE MENTS 2 5 mmn                               ME 6  2 2 ODOURJPRONETEIIE PAP AT u u aa                               eee            6  23 SM BV Gos  ak                 LLL eR 6  2 4                          IP AND REMOVA                                                      6  2 5 SMOKE DETECTOR C                                       7       DOOR Gi                   datus eMe reer nero mor cba tue uM              7  2 7 GLASS SPECIFICATIONS iiie tissues        qusha                    pen bu as                       7  2 8 ASHDRAWER             te atts asda                            7  222    7  2  APPETIANCE INSTALLATION                                            tae 8  DSAPELIANCEINSTACLA TION                                                  8  3 1 COLD AIK  RETURN BOX INSTALLATION        9  3 2 COLD AIR DUCTING SUPPORT     5                                       1   3 3 CONTROL PCB INSTALLATION AND CONNECTION                                                          14  34   RTD SUPPORT BRACKET INSTALLATION AND CONNECTION  RESISTANCE  TEMPERATURE DETECTOR                   ue Ro                 TCA    16  3 5 SERVOMOTOR INSTALLATION AND CONNECTION                                                          18              INS TART HON                                        desea tunt etat bomi                    aes 2
4.                            39  5 4 FEIER    39  229 DPDOORGASKEFMAINTENANC E                                               39   O REPEACBMENT PAR LS                                                                                                                 41  6 1               u u                         41  6 2  A T    usni m usia u             EE SE MI M IU 41   7  GENERAL ELECTRIC DIAGRAM WITH BECKETT OIL BURNER                                      42  8  GENERAL ELECTRIC DIAGRAM WITH RIELLO OIL BURNER                                          43  9  ELECTRIC DIAGRAM WITH OPTIONAL ELECTRICAL ELEMENT                                        44                                                                          A        45  IO  GENERALE TECHNIC               56                                             45  10 2  ZTECHNICAT DATA  FLECTRIC AL                        45  11 MAX CADDY BRICKS                                                        46  I2 TROUBLE SHOOTING                             ced        ee        47  SECTION e nu uu kus                 48  WOOD OIL COMBINATION FURNACE                                                                                               48  GENERAL NOTES u                                                 C NUN 49  1DRAFTAND CHIMNEY i  uy                                               49  2  8 1 LEM IT ANK AND PIPING coe 50  2 1 isi        RG al                                                          50   DS APPLIANCE INSTALIUAT
5.             10 X 1 2       type metal screw       Cold air return box door         14 6 electric wire    Manual kit SE45447       Limiting board       3 1 COLD AIR RETURN BOX INSTALLATION    Before installing the cold air return box  you need to remove the back panel gasket and the back panel as shown  below  To do so  remove the 8 screws        Back panel gasket    Back panel     10 X 1 2   A  type metal screw    Remove the cold air ducting support from the cold air return box  To do so  remove the 12 screws as shown below   Keep these screws  You will need them to install the cold air ducting support in the new location        Cold air ducting support                10    Then  secure the cold air return box to the furnace  To do so  use the 8 screws as shown below  Then  level the cold  air return box by screwing or unscrewing the elevator bolts          10 X 1 2   A  type metal screw            Cold air return            1 4 20 x 1  elevator bolt E    3 2   COLD AIR DUCTING SUPPORT INSTALLATION    On the cold air return box  you will find two side plates and the cold air return box door  The cold air ducting support  can be configured in several ways  You have the flexibility to choose the desired configuration depending of your  installation  Indeed  some installations have obstacles making the installation of the cold air ducting support difficult   Configurations differ depending on the chosen location of the cold air ducting support  You will find the different  confi
6.     30  4 3                                                            30  QOO dhe use of the BIFENERGY JUNCO                            31                RD eT      TEN           uuu      31    4 5 MODES  OPTIONS  AND PROGRAMMING      eile ede 31    Sd                                                                                    MELDE 32  ADD                   acusada                                             32  ADS HEAT MOde  GULOMGHC heating                                                           22  o4           Mode Q r cond Onine         pst      pA M Ds CR aic i  33  4 9 95   CIRC CGI CIP CI GUI OD                                            33  40 0  MANU  manual Heaut sens a                                                               33        34   4 6              C n nus s nus Dau                     35  4 7 PREHEATING i u                                                          ee 35  4 8 HEA TING       T 35  4 9 EARLY SIGNS OF AN OVERFIRED FURNACE H                                                                     36  AIO  WOODAS HEATING FUF                   ien         akana tha        een 36  all PROLONGED POW PR PALL GRE             a bush uei ansa ka as aaa 36   RI o  CHMNE T FIRE                            37       MAINTENANC E                                                       38  5 1 MAINTENANCE OF THE EXCHANGER Dieu ic hae ee ean eee 38  5 2 CHIMNEY  MAINTENANCE uu                              39  5 3 MAINTENANCE OF THE BLOWER            
7.   The blower speed must conform  to the recommendations of local codes and should respect the static pressure ranges in the warm air  plenum of the furnace     We recommend that our wood burning hearth products be installed and serviced by professionals who are certified  in the United States by NFI  National Fireplace Institute   or in Canada by WETT  Wood Energy Technical Training   or in Quebec by APC  Association des Professionnels du Chauffage      1  CHIMNEY AND DRAFT    This furnace must be connected to a chimney certified for use with wood burning heating appliances  A 7 inch  chimney and connector are recommended for the Max Caddy if it is used as a wood oil unit or a wood oil electric  unit  If an oil option may be installed in the future  we also recommend a 7 inch chimney  If the furnace is to be  used as a wood only unit  then a 6 inch chimney is recommended     The unit is not to be connected to a chimney flue serving another appliance     If the chimney draft exceeds 0 06 IN W C   a barometric draft control should be installed on the smoke pipe  Never  install a manual damper     The barometric control must be adjusted so that the maximum draft measured at the furnace outlet does not exceed   0 06 IN W C  Please note that a draft exceeding 0 06 IN W C  will reduce the efficiency and could produce an  uncontrollable fire  On the other hand  the minimum draft required is 0 04 IN W C  in the evacuation pipe on  the wood side  no matter what type of furnace  WOOD  
8.   will reduce efficiency and could result in an uncontrollable fire  On the other hand  the minimum  draft to be respected is 0 04 IN W C  in the evacuation pipe on the solid fuel side  no matter what type of  furnace is use  WOOD  WOOD ELECTRIC  WOOD OIL  or WOOD OIL ELECTRIC      3 10 FRESH AIR INTAKE ADAPTER INSTALLATION  OPTIONAL     When the furnace and the chimney are completely cold  it may be necessary to provide fresh air by opening a door  or a window for a few minutes while lighting the fire     Take note that a house constructed or renovated in order to be airtight may lack the volume of fresh air necessary  for the proper combustion of a solid fuel heating appliance     In such a case  when starting up the fire  do not operate appliances that evacuate air outside the house  such as         Range hood     Air exchanger     Clothes dryer     Bathroom fan     Ventilated central vacuum system    A fresh air supply may be necessary to prevent solid fuel units from rejecting products of combustion into the house   The indications used to determine if an additional fresh air supply is necessary are not appropriate for all the  situations  When in doubt  it is recommended to install a fresh air supply     A fresh air supply may be needed if       Solid fuel units present anomalies  such as irregular draft  smoke return  bad combustion  and or  reversed draft  whether there is combustion or not       Existing solid fuel units such as a stove or fireplace release odours  h
9.  2  Chimney connector is glowing red     3  Extreme heat coming from the furnace  If this occurs  DO NOT OPEN THE DOOR  Shut off the air inlet opening  completely  and wait until the glow has completely subsided     ALWAYS KEEP THE DOOR AND THE ASH DRAWER CLOSED   except for lighting and maintenance         4 10 WOOD AS HEATING FUEL   We recommend that you burn dry hard wood only  There are two important factors to be considered when choosing  a type of wood  the moisture content and the wood density  Hardwood  oak and beech for example  will provide  better results because of the high density and minimal tar produced during combustion  It is highly recommended to  use wood that has been dried for at least six months  Do not use coal as heating fuel in this appliance   Whenever a high rate of smoke is noticed in the room  you must     1  Open doors and windows     2  Make sure the furnace door is closed as well as the damper  if necessary  lower the thermostat starting point or  unhook the damper chain and close the barometric draft control manually      3  When the furnace has cooled down  inspect the chimney to detect obstructions and consult a specialist to  determine the cause of the smoke spillage     4 11 PROLONGED POWER FAILURE   DURING PROLONGED POWER FAILURE  YOU CAN USE YOUR FURNACE  THE DAMPER REMAINS IN  CLOSED POSITION AND THE FURNACE FUNCTIONS AT THE MINIMUM BURN RATE  IT IS VERY  IMPORTANT YOU ENSURE THE HOLES   4    DIAMETER  LOCATED UNDER THE LOADING DOOR INS
10.  be conform to the rules of the authorities having jurisdiction and the CAN CSA B139  amp  NFPA 31  standard regarding installation of oil burning heating appliances  The installation of the connecting pipes to the oil unit  must be done and approved by a professional     The barometric damper provided with the appliance must be properly installed on the flue pipe of the oil unit  The  purpose of the damper is to limit the draft  if necessary  in the oil unit evacuation pipe     Since the evacuation pipe of the oil unit is connected to the evacuation pipe of the wood burning furnace  the  minimum draft to be respected at all times in the evacuation pipe of the wood burning side is  0 04 IN W C     Also make sure to install the blocked vent shut off system      00600  in case of vent blocking     49    2  OIL TANK AND PIPING    The maximum capacity of the tank must not exceed 200 imperial gallons and the tank must be located at least 7 feet  from the burner  Local codes will govern the size of the air inlets and filling openings as well as the type of plugs to be  used  1 1 4  IPS and 2  IPS are usually accepted as minimum dimensions for the air intake pipes and fill pipes   respectively  The oil line to the burner must be a 3 8  outside diameter copper tubing for runs up      50 feet and 1    o d   for longer runs  A manual shut off valve and an oil filter shall follow in sequence on the oil line between the oil tank and  the burner  The oil line must be buried or protected a
11.  electric system     Therefore  under normal wood electric combination use  you should set the wood system thermostat 2   to 4   higher  than the electric system thermostat  The bigger the gap  the more the wood heating will contribute to the overall  heating needs     If the temperature of the electric unit exceeds the high limit   the thermostatic sensor will disengage the elements   To reactivate  press the red    manual reset    button on the thermostatic sensor   L 170 Thermodisc  after finding and  fixing the problem that has caused the unit to overheat  static pressure too high  fan breakdown  etc      INSIDE VIEW OF THE ELECTRIC ELEMENT        gt                                      M  w    PE as              Red button  manual reset    L 170 Thermodisc    RESET       27    3 13 THERMOSTAT INSTALLATION    3 13 1 Wood furnace only    The thermostat must be installed on an inside wall and located where it is not likely to be affected by the draft  coming from an air outlet  It must be installed at a minimum of 55 inches above the floor     3 13 2 Combination wood electric or wood oil furnace    The combination model uses two thermostats which must be located at the same height from the floor  When the  main thermostat  wood  calls for heat and the demand cannot be satisfied by the furnace with wood as a  combustible  the option  oil burner or electric unit  will take over and maintain the house at the temperature  programmed on the second thermostat  option   If the the
12.  in soil  wait until all embers have thoroughly cooled before burying     2 4 CREOSOTE BUILD UP AND REMOVAL    When wood is burned slowly  it produces tar and other organic vapours which  when combined with moisture  form  creosote  The creosote vapours condensate in a relatively cool chimney flue  As a result  creosote residues  accumulate inside the flue lining and the exchangers     N B   To minimize the frequency of the chimney cleaning  buy your firewood at least one year before using it  Store  it in a dry place in order to obtain the minimum moisture rate and optimize the efficiency  Do not store wood or  combustible materials within the installation minimum clearances or the space required to reload the appliance and  remove ashes     When ignited  creosote produces an extremely hot fire inside the chimney   In the first year of use  in order to avoid chimney fires  inspect the chimney system at regular intervals to determine a  cleaning cycle  Depending on the type of wood used and its quality  a semi annual cleaning may be required  A    yearly cleaning is mandatory     If a significant layer of creosote has accumulated  it must be removed immediately to eliminate the risk of  chimney fire     Remember that a small  hot fire is preferable to a large smouldering one to prevent creosote build ups within the  system  Prepare an emergency procedure in case of a chimney fire     It is recommended to clean the heat exchangers thoroughly at the end of season in order to pr
13.  mode and cut the fuel supply to the burner for 60 seconds  After this delay  the control goes back to   IGNITION  mode  If the flame goes out 3 times in a row  the control will switch to the  LOCKOUT  mode to prevent a  continuous cycling of the ignition process  which would cause a premature soot up of the combustion chamber and  smoke pipe  To deactivate the  LOCKOUT  mode  press and hold the reset button of the control for 30 seconds     A green diagnostic LED on the control has four states     On   Flame present    Off   No flame    2 seconds       2 seconds         Recycle  mode    1   2 second On  1 2 second Off    Lockout  mode TEMPORARY SHUT OFF    By pressing and holding the reset button  the burner will shut off until the reset button is released  When the button is  released  the control will start over at the beginning of the normal cycle     53    FOR ADDITIONAL INFORMATIONS ON OPERATION SEQUENCES OF THE BURNER  CONSULT THE BURNER  INSTRUCTION MANUAL     3 10 COMBUSTION ADJUSTMENT AND VERIFICATION  To enjoy the efficiency of our oil burning units  you must respect the following criterion     Oil burning units must be connected to flue pipes having at all times a sufficient draft to ensure an efficient and safe  operation of unit     Before turning on the oil unit  make sure that the sealed vision         SE53352  15 installed and secured on the vision  tube with the screw provided  The chamber is calibrated so that there is a slight positive pressure  which opti
14.  to penetrate into the fan and motor carters  causing some  defects  Clean and replace filters as often as required     Note   The operation cost is higher when using a dirty filter     97    7  ELECTRICAL DIAGRAMS    Refer to SECTION A of this manual     NOTES     OO    8  TECHNICAL DATA    8 1 UH     MAX CADDY  BURNER BTU STATIC PRESSURE        FAN   TUBULATOR AIR                BECKETT 0 65  70 W   0 65 GAL US H 100 PSI         UH MAX   BECKETT 0 65  70 W   0 86 GAL US H 175 PSI       copy   Ara 120000                    FO     meses        c   9                        RIELLO 40 0 50  70      0 60 GAL US H 150 PSI    5  CADDY 9000                   osea                RIELLO 40 0 65  70 W   0 84 GAL US H 165 PSI       ADD   es     120000                                              For any additional information  consult the rating plate on the left hand side of the appliance     59    WHY PURCHASE THROUGH AN AUTHORIZED PSG DEALER     To make sure your PSG furnace provides comfort and energy savings in your home for many  years  your choice of installer is extremely important  An authorized PSG dealer will ensure that the  system is optimized and installed according to standards  Given the importance of the installation   PSG recommends that it is carried out by a professional certified in the Building Code so that the  furnace delivers its full potential  This is why PSG offers an additional warranty that covers the cost    of labor if your furnace has been purchased thro
15.  up chimney     Wet wood or low grade wood   Too much cold air return for the  hot air ducts  Unbalanced  ventilation system     IMPORTANT NOTE    SOLUTIONS    Adjust the damper  minimize the  chimney length and use 45    elbows     Reinstall the ducts correctly   Respect the minimum static  pressure of 0 20 IN W C     Relocate the thermostat  Adjust  the chain that links the damper to  the servo motor  Rebalance the  ventilation system in order to  increase the air flow in the room  where the thermostat is located     Lower the temperature starting  point  Usually  start up  temperature can be adjusted on  the PC board between 125 and  150 degrees F  Reduce the fresh  air flow     Use dry wood  Adjust the  barometric damper  Clean the  chimney flue and the furnace  exchangers     Use dry wood  Reinstall the  ventilation system correctly     FOR THE INSTALLATION OF A CENTRAL HEATING SYSTEM  IT 15 HIGHLY  RECOMMENDED TO CONSULT A HEATING SYSTEM VENTILATION SPECIALIST     47    SECTION B  WOOD OIL COMBINATION FURNACE    INSTALLATION  AND OPERATION INSTRUCTIONS  FOR UH MAX CADDY WOOD OIL  COMBINATION FURNACE    READ THIS MANUAL THOROUGHLY  BEFORE OPERATING THE FURNACE    CAUTION CAUTION    EXPLOSION OR FIRE HAZARD  DO NOT ATTEMPT TO LIGHT THE  FOR YOUR SAFETY  DO NOT BURNER WHEN EXCESS OIL HAS  STORE OR USE GASOLINE OR ACCUMULATED  WHEN THE    ANY FLAMMABLE LIQUIDS OR APPLIANCE IS FULL OF VAPOR  OR  VAPORS IN THE VICINITY OF WHEN THE COMBUSTION  THIS HEATING UNIT  CHAMBER IS VER
16. 0  3 7 WINEDT BOCA TION           a                                20  3 8 CLEARANCES      COMBUSTIBLES AND FLOOR PROTECTOR                                        21  39 FLUE AND BAROMETRIC DRAFT CONTROL                      rn 23  on P ENDS                                                        24  3 10 FRESH AIR INTAKE ADAPTER INSTALLATION  OPTIONAL                                             24  Sus PARALLELINSTALEA TON                                           26  3 12 ELECTRICAL ELEMENT INSTALLATION   WOOD ELECTRIC MAX CADDY   OPTION ATS                     EUR TUE 27  212 THERMOS TATINSTALCA ION                                                                 28  Sob Wood TUNA CONI Y unun pus upa          Saa                      28  3 13 2 Combination wood electric or wood oil furnace                                                                   28  3 13 3 Trio furnace  wood oil electric or wood electric oil                                                            28  3 14 INSTALLATION OF A DOMESTIC WATER PRE HEATING SYSTEM  OPTIONAL           28  3 15 INSTALLATION OF AN AIR CONDITIONING UNIT                                                              29  3 16       BURNER INSTALLATION   WOOD OIL MAX CADDY  OPTIONAL                           29  4 OPERA TING INS PRUC LIONS   iu u Q Fee ees eee Debe             a us               30  4 1 CON ERO Te SY SE    utin                                          MEI MAUI 30  42 FIRST USE   GENERAL INFORMATION               
17. 3   THERMOSTAT   Both the wood and oil thermostats must be installed side by side on an interior wall  in a location where they are not  affected by the air draft coming from the furnace   s blower  they must be level and at least 55 inches above the floor   Consult section A of this manual for more details regarding the thermostats    3 8 FAN CONTROL   In the case of the oil option  the blower starts once the request for heat is activated by the oil option   s thermostat    The adjustment of all controls must be performed by a qualified technician  For continuous operation of the blower  during Summer  the mode must be changed to CIRC on the PC board  Then  the appropriate blower speed must be    selected     It is not recommended to let the blower run on continuous mode when heating with wood since the wood  furnace must reach a certain temperature before the blower starts in order to operate efficiently     3 9   COMBUSTION SAFETY CONTROL    The AFG type oil burner is equipped with an electronic control    R7184B1032  including a pre purge function and a  new  more durable drive motor     PRE PURGE    When there is a call for heat  the burner s fan will run for 15 seconds before the actual ignition takes place to vent the  combustion chamber and generate a proper draft  This will result in a smoother ignition of the oil burner     SAFE OPERATION    If the flame goes out while the burner is running  the CAD cell will detect it  the control will then switch to the   RECYCLE 
18. AIR IS MORE HUMID WITH MINIMAL NATURAL FLOW IN THE FURNACE  IN  THESE CONDITIONS  REMAINING CREOSOTE AND OR SOOT IN THE EXCHANGERS WILL PRODUCE AN  ACID THAT WILL ACCELERATE THE CORROSION PROCESS AND WILL PERFORATE THE STEEL  PREMATURELY  WHICH IN RETURN  WOULD NOT BE COVERED UNDER THIS WARRANTY        Before cleaning the three exchanger pipes  move the upper vermiculite baffle board of the combustion chamber  forward  see drawing on next page   Using the scraper  clean the three exchanger pipes  The accumulated dirt in  the lateral exchangers will fall into the combustion chamber  the dirt in the central exchanger will have to be removed  from the front or the back of the furnace  Then  ensure that the upper baffle board is free of ashes  Do not forget  to push the upper baffle board back to it   s original position  Finally  close the exchanger access door     MAX CADDY SECTION VIEW    SCRAPER FLUE ADAPTOR       REAR BRICKS    Sey    C CAST BOARD BAFFLE  HE    i         4 Fa rss    MAINTENANCE                         5 2 CHIMNEY MAINTENANCE    The most efficient method to sweep the chimney is using a hard brush  Brush downwards so soot and creosote  residues will come off the inner surface and fall at the bottom of the chimney where they can be removed easily     The chimney must be checked regularly and if creosote has accumulated  it must be removed without delay     smoke flue inspection           smoke flue  connector  should be inspected regularly during the heating se
19. CE    At the beginning of heating season  have the complete installation inspected by a qualified service man  especially the  lighting system and the controls     NOTE  THE UNIT S MAINTENANCE  REPAIRS AND THE CLEANING OF  THE OIL FILTER MUST BE DONE BY A QUALIFIED TECHNICIAN     Before calling for service  first check the following     SERVICE    Fuel supply   Electric fuses or breakers   Thermostat setting   PC board settings   The state of the green diagnostic LED on the burner control     MAINTENANCE    WARNING  Turn off electric power supply before servicing the unit     The furnace  the burner and the flue pipe should be cleaned at least once a year    The nozzle should be inspected and replaced if needed  Handle with care to avoid damaging its surface   The electrodes should be adjusted as indicated in the burner manual    Lubricate the burner motor bearings twice a year   2 or 3 drops of SAE 20 non detergent lubricating oil    The oil filter should be verified annually and replaced if needed     OT FS      o    Burner no   Date of installation   Service telephone no   Day  Night     Dealers name and address     TEST REPORT      CO    Temp  at stack  Draft at stack   Nozzle output  GPH Smoke colour     Inspected by         FILTERS    The furnace should never be operated without filters    This applies especially to temporary heating during construction period  Operating the furnace without filters would  allow dust and other particles in the air to circulate freely and
20. DOMESTIC WATER PRE HEATING SYSTEM  OPTIONAL     A water heating loop option is also available to pre heat domestic water using the energy produced by the Max  Caddy wood furnace  This water loop kit will be inserted between the wood combustion chamber and the heat  exchangers  When heating with wood  the heat from the furnace will pre heat domestic water that will be stored in a  feed tank before entering your existing water heater  Removable panels are installed on both sides of the furnace for  quick and easy installation of the loop  A 24 volt solenoid valve must be installed at the inlet of the loop and must be  connected to the WATR SOLN terminal on the PC board  when the plenum temperature reaches 140  F  the valve  opens to allow water circulation  It closes when the temperature drops below 120  F to prevent overcooling the  combustion chamber during low firing rates    The WATR SOLN terminal may also be used to activate the 24 volt relay of a humidifier installed in the system  which  when connected to the PC Board  will be activated and deactivated at the same temperatures as the water    solenoid valve  140  F et 120  F   Complete installation and operation instructions for the hot water loop kit  are supplied with the kit and        be downloaded from the PSG web site at www psg distribution com     28    3 15 INSTALLATION OF AN AIR CONDITIONING UNIT    The MAX Caddy wood furnace has been tested with an optional air conditioning unit  If this option is chosen  we  
21. EILING     HEAT SHIELD      i 1 x            SHIELD  N 3   4 E      F 3 4                               AIR PLENUM     MIN 7  pis     54i mE ie  45  ELBOW        gt  lt               ES          e  PRESSURE  TM fe CHECK POINT  18  er        N MIN 0 20  W C                                            m                                                                                                                                                           U          24   F    UH MAX    NEN CADDY    24                               AAR AR AAA RAR AAS 5           21      CLEARANCES    24     610 mm  recommended for       maintenance     24     610 mm      Note 1    48     1219 mm        Note 1  24   610 mm  recommended for maintenance on the option   s side  combo units      un FLOOR PROTECTOR          CANADA     18   457 mm  16   406 mm             From door opening From door opening    N A  USA only  8     203 mm     F  8   203          N A Canadaony           8  03        N A Canadaony                                               Steel with a minimum thickness of 0 015     0 38       or ceramic tiles sealed together with grout   No protection is required if unit is installed on a non combustible floor  ex  concrete      Note 2   Only required under the horizontal section of the connector  Must exceed each side of  the connector by at least 2 inches  51 mm      22    3 9 FLUE AND BAROMETRIC DRAFT CONTROL CONNECTION    Before connecting the stove pipe  make sure you have removed 
22. IDE  THE FURNACE S COMBUSTION CHAMBER ARE FREE TO ENSURE A GOOD PERFORMANCE     CARBON MONOXYDE IS A LETHAL GAS  ODOURLESS AND COLOURLESS   WHICH YOU MUST BEWARE  OF     36    4 12 CHIMNEY FIRES    This might occur when the fire gets extremely hot  Burning cardboard  branches  or small pieces of wood can ignite  the creosote residue accumulated in the evacuation flue system  The usual signs are     1  Rumbling   2  The flue gets extremely hot  red      3  Flames or sparks are coming out of the chimney     In case of a chimney fire  call your local fire department immediately and sprinkle the roof  around the chimney with water     Make sure that the furnace door is closed as well as the damper  if necessary  lower the thermostat starting point or  release the chain from the damper and close the barometric draft control manually      If the fire gets uncontrollable due to an improper use or because the draft is too strong  follow the same procedure  as in a chimney fire except that you will have to OPEN the barometric draft control manually     LOCAL FIRE DEPARTMENT    Phone number     37    5  MAINTENANCE    5 1 MAINTENANCE OF THE EXCHANGERS    The flue pipe and the exchangers should be inspected regularly during the burning season  Easy access is provided   without the use of tools   simply unscrew the wing nut on the exchangers access door  See pictures below     WARNING  THE HEAT EXCHANGERS ARE TO BE CLEANED THOROUGHLY AT THE END OF EACH HEATING  SEASON  DURING THE SUMMER 
23. ION vecsscccsesceusksecssdvcdvessetcsceascacsessdeshsecsducdvesseetsesascacseedsanaevesseeetsesnatvelesseeedes 50  3 1            50    32 POSITIONING THE APPLDPENNCE   4    4  35              51    3 3 PIPE CONNECTOR AND DAMPER                                                 51  34 POSSIBLEETNSTALLDATIONS                     52  3 5                         53  IO FER                      53  7                                53        JT N                                     53  59            53  3 10 COMBUSTION ADJUSTMENT AND VERIFICATION                                                            54  Ou PPTLECTECODII ie  CIIN                 4       eee 55  A  APPLIANCE                             56       PROLONGED  CLOSING                56      MAINTENANCE scesero sner aeniei E SEENE ENEAS aa SEEE NE EEEa 56  I ELECTRICACGDIAGRAMS   uuu                                                                   58       Bo Os LOT        rc                                                   59  8 1                                            59  WHY PURCHASE THROUGH AN AUTHORIZED PSG DEALER                                                    60  PSG LIMITED LIFETIME WARRANTY  REGULAR                                                                         61  PSG LIMITED LIFETIME WARRANTY  PRIVILEGE                                                                      62    REGISTER YOU WARRANTY ONLINE    To receive full warranty coverage  you will need to show evidence of the date  you 
24. In the case of the electrical or oil option  the blower starts as soon as that there is a request for heat from the  option   s thermostat  In other words  for security reasons  the distribution blower does not wait for a minimum  temperature to be reached inside the hot air plenum before starting  However  the rest of the logic remains the  same  That is  for as long as there is a heat demand  the PC board will vary the distribution blower   s speed in order  to maintain the BEP inside the hot air plenum        4 2 FIRST USE     GENERAL INFORMATION    The RTD probe reads the temperature inside the hot air plenum and plays the same role as a mechanical fan limit  control found on most conventional wood furnaces  The main difference is that the RTD is connected to a PC board      is an electronic fan limit  First  you must configure your PC board  In order to do so  it is important to Know which  options are installed on your furnace  During the start up  the PC board will display some information such as the  name of the company  the version of the program  as well as a four digit number corresponding to the default  configuration of the furnace     4 3 FIRST USE   SETTTINGS    Using the arrows  you must select the four digit number corresponding to your installation as per the table below   When your selection is made  push the SELECT button in order to save your setting  Should you need to change  this selection  switch the electrical breaker of the furnace to  OFF  then se
25. N WC  A back flow damper should be installed in the plenum  The back flow damper  assures that when either unit is operated by itself  the hot air will flow into the home  and not back through the other  furnace  Depending on your installation  see figures examples below   a back flow damper may be required in each  plenum                          w    gu   D      DAMPER    7        DAMPER  EXISTING SOLID FUEL  FURNACE FURNACE                                     EXISTING SOLID FUEL  FURNACE FURNACE          26    3 12 ELECTRICAL ELEMENT INSTALLATION     WOOD ELECTRIC MAX CADDY  OPTIONAL     The high limit control is a manual reset thermostatic sensor that is located inside the electrical unit  The electric unit  must be connected as shown on the diagram  see WIRING DIAGRAM   The connections must conform to the  diagram     Electrical connections must conform to the wiring diagram supplied with the option     The wood   electric combination model uses two thermostats  one thermostat controls the electric heating  and the  other one controls the wood heating  With this system  the electric heating has priority over the wood heating   When the thermostat activates the electric heating  the air inlet damper closes down  if opened   the blower starts   and the electric elements are successively activated per block of 5 kW  When the call for electric heating is  satisfied  the wood system will take over if the starting point of the wood system thermostat is superior to that of the 
26. PSG     x 250 de Copenhague    SG saint Augustin de Desmaures      Quebec  Canada          2  3       Eco Energy    at the heart of your home    Installation and operating instructions  for the MAX CADDY wood furnace    READ THE MANUAL THOROUGHLY  BEFORE OPERATING THE FURNACE    CERTIFIED ACCORDING TO CSA B415 1 10  CAN CSA B366 1 M91 UL391 4   EDITION 2006  CAN CSA C22 2  NO 236 05  UL 1995 3   EDITION 2003  CSA   140 4 04 AND UL 727 9   EDITION 2006    FURNACE MODELS INCLUDED IN THIS MANUAL    MAX CADDY WOOD AND COMBINATION FURNACE  20kW 25kW and UH Max Caddy    Read these instructions carefully before installing    and operating your furnace     CONGRATULATIONS     You have purchased one of the finest wood or combination furnaces  avallable on the market  We are confident that your furnace will provide  years of comfort and safe operation  Please keep this document     This manual is available for free download on the manufacturer s web site  It is a   copyrighted document  Re sale is strictly prohibited  The manufacturer may update this      manual from time to time and cannot be responsible for problems  injuries  or damages    US    US  i LigTEO    arising out of the use of information contained in any manual obtained from  unauthorized sources  Intertek Intertek             45446A  Printed in Canada 15 04 2013    TABLE OF CONTENT    WOOD OR WOOD ELECTRIC COMBINATION FURNACES                                                             5  Ry                              
27. Recommended Installation  3 16 OIL BURNER INSTALLATION     WOOD OIL MAX CADDY  OPTIONAL     Refer to section B for the installation and operation instructions for the UH MAX CADDY wood oil combination  furnace     29    4  OPERATING INSTRUCTIONS    4 1 CONTROL SYSTEM    On the Max Caddy furnace  a new electronic control was developed  This system is more polyvalent  All connections  are done from the PC board  There are connector ports available for all components and options  Under the HEAT  mode  a logic was developed to provide you with the best comfort and efficiency  when you are heating with wood   the distribution blower starts at soeed  1 based on a preselected temperature programmed into the PC board  this  temperature is called the KIP     Kick in Point   The temperature is read by the RTD probe located inside the hot air  plenum  As the temperature continues to rise inside the hot air plenum  the PC board changes the speed of the  blower to speed  2  This speed should maintain the most efficient temperature  BEP     Best Efficiency Point  inside  the hot air plenum  The BEP has been set at 160F by the manufacturer when wood supplies the energy required for  heat  If the optional oil burner or electrical unit provide the heat  the BEP is set at 150F  Whenever the temperature  inside the hot air plenum continues to rise above the BEP  the PC board selects a higher speed in order to stabilize  the temperature into the ducting system and therefore maintain the BEP     
28. S   BREAKER   FEEDER VOLTAGE ELEMENTS  CFM TOTAL   REQUIRED r SINGLE PHASE QTY    20 kW 1800 68 240 125 amps 120 240 4 x 5 kW       85 325      iSoams   2        5 x 5 kW  WOOD 180 000   5   15              40     45    11  MAX CADDY BRICKS LAYOUT                                  B             46    12  TROUBLE SHOOTING    PROBLEM    Heating inefficient during the first  combustions  Lack of draft     Furnace heats well  warm air  plenum is very hot but there is  not much heat coming out in the  room     Furnace consumes a lot of wood     Fan start up is too slow     A lot of creosote  moderate heat  output     Furnace heats a lot but the warm  air plenum does not get hot     CAUSES    Improper adjustment of the  barometric damper  opened too  wide   Chimney flue restriction   too long  90   elbows     Improper installation of the ducts   unbalanced system  too many  warm air outlets and not enough  cold air inlets      The thermostat which controls  the damper is continuously  activated and is too close to     source of cold air  Damper not  properly adjusted  House not  insulated enough  Ash drawer is  not tightly closed  Furnace too          for the surface to be  heated  Unbalanced ventilation  system  very little heat where the  thermostat is located     Fan            setting too high   Return air is too cold   temperature lower than 65  degrees          not well located  in the warm air plenum     Wet wood  lack of draft   Barometric damper not properly  adjusted  Soot
29. TER HEATER OPTION   OUTPUT 5  IRIELLO 40 F3 MODEL           0411 5                                        LINE                                   IF ANS  F ANG    AC LINE       HOT   FRAME  FRAME GROUND        COMMON       COMMON     e  r                                                  w le                       43    9  ELECTRIC DIAGRAM WITH OPTIONAL ELECTRICAL ELEMENT    MAX CADDY WOOD ELECTRIC COMBINATION FURNACE    CONTROL PCB  O 9                     ELEMENT              ee    44    10  MAX CADDY TECHNICAL DATA                                                    CADDY       b  ux                                                                                                                                                                                                                                                                                                                                              FLUE       h              oOr       Reducer required                                                                                                                                                                                                                                                                                  10 1 GENERAL TECHNICAL DATA    TEMP BTU STATIC  MODEL DIRECT DRIVE    INPUT PRESSURE FILTER        me     eme     en   ox   Ww T W 8       7242    IN W C         pa       10 2 TECHNICAL DATA   ELECTRICAL ELEMENT    MODEL OUTPUT TEMP        BTU HR AMP
30. WOOD   ELECTRIC OR WOOD   OIL      The adjustment should in no case be modified to increase combustion     2  SAFETY RULES    WARNING   e THE INFORMATION GIVEN ON THE CERTIFICATION LABEL AFFIXED TO THE APPLIANCE ALWAYS    OVERRIDES THE INFORMATION PUBLISHED  IN ANY OTHER MEDIA  OWNER S MANUAL  CATALOGUES   FLYERS  MAGAZINES AND OR WEB SITES         2 1 GENERAL REQUIREMENTS    Make sure the chimney outlet and the pipes are clean and in good condition    DO NOT USE CHEMICAL PRODUCTS OR LIQUIDS TO LIGHT THE FIRE    Do not burn wood coated with paint  glue or chemical products    DO NOT BURN WASTES OR FLAMMABLE LIQUIDS SUCH AS GASOLINE  NAPHTHA  MOTOR OIL  OR  OTHER UNSUITABLE MATTERS      Do not install an automatic feeder on this furnace      Do not store wood in the vicinity of the furnace  Respect the required clearances between combustible materials  and the source of heat     WARNING    THE ASH DRAWER AND EXCHANGERS ACCESS PANEL GET VERY HOT  DO NOT  MANIPULATE WITH BARE HANDS        2 2  ODOUR FROM THE PAINT       is normal that smoke and odours emanate from the unit when you first light it  It is recommended to burn it at high  rate and ventilate the building until the odours disappear  The smoke is not toxic     2 3 ASH DISPOSAL    Ashes must be placed in a metal container with a tight fitting lid  The container should be stored outdoors  well away  from combustible materials  This container should not receive any other type of waste  If the ashes are meant to be  buried
31. Y HOT        DO NOT BURN WASTE OR PAPER IN THE APPLIANCE   DO NOT LEAVE PAPER OR ANY COMBUSTIBLE MATERIAL  AROUND THE APPLIANCE     DO NOT TRY TO MODIFY THE UNIT OR ITS COMMANDS    CALL A TECHNICIAN    PLEASE SAVE THIS DOCUMENT     GENERAL NOTES    This instructions manual treats mainly of the oil burning unit of your wood oil combination furnace   For any additional information concerning this wood burning furnace  please consult Section A of this manual     To obtain the maximum efficiency out of your furnace  follow the advice below regarding the installation and operation  of your WOOD OIL combination furnace     e Respect the local codes  when in doubt  consult your local dealer     e Respect the clearances indicated on this instructions manual and make sure that they match those indicated  on the                  5 certification label    e          sure that your furnace is installed in conformity with the instructions on the certification label    e     the controls adjustments must be performed by a qualified technician     THE INSTALLATION OF THE WOOD OIL COMBINATION FURNACE MUST BE  DONE IN ACCORDANCE WITH THE RULES OF THE AUTHORITIES HAVING    JURISDICTION AND FOR CANADA  THE CAN CSA B 139 STANDARD FOR OIL  BURNING HEATING APPLIANCES        This oil burning furnace is not approved for use with combustible heavier than No 2 oil  furnace oil   DO  NOT USE GASOLINE  TRANSMISSION OIL  OR OTHER TYPE OF OIL CONTAINING GASOLINE     1  DRAFT AND CHIMNEY    The chimney must
32. and     44        CONTROL    We recommend that the HEAT mode be programmed for the MAX Caddy  Under the HEAT mode  the distribution  blower uses various speeds that are controlled by the PC board based on the hot air plenum temperature  The  plenum temperature is read by the RTD temperature probe  The manufacturers programmed settings should  provide the most efficient operation for a majority of installations  The PC board also has a manual mode                     consult the MODES section of this manual   Under the manual mode  the MAX Caddy operates as a conventional  furnace  That is  the distribution blower starts at the speed programmed in the PC board  one single speed  based  on only one temperature point read by the RTD probe inside the hot air plenum     The adjustment of all controls must be performed by a qualified technician  In order to obtain a continuous air  circulation during summer  you simply need to change the PC board mode to  CIRC   To do so  consult the  MODES section of this manual    It is not recommended to let the blower run on the continuous mode when heating with wood since the  wood furnace must reach a certain temperature before the blower starts in order to operate efficiently     4 5 MODES  OPTIONS  AND PROGRAMMING    Your PC board is equipped with four operating modes   HEAT  automatic heating   COOL  air conditioning   CIRC   recirculation   and MANU  manual heating   You can pass from one mode to the other by pressing on the arrows  butto
33. any accessory from    the flue pipe such as the scraper  shovel  and the poker        The flue outlet on the Max Caddy furnace is 6    in diameter and the wood only or wood electric models may be  installed with a 6    chimney approved for use with wood burning heating appliances  2100  F   However  we  recommend the use of a 7    chimney if the retrofit to a wood oil configuration is probable  In that case  a 6    to 7     reducer must be installed at the flue outlet of the furnace  If the draft exceeds 0 06 IN W C   a barometric control  must installed  Never install a manual damper  Secure the exhaust pipe to the flue adapter with three screws     FLUE  ADAPTER                                                                                                       LEO SB OIL UNIT   S  OUTLET  WOOD ONLY WOOD OIL    For a proper installation  follow the advice below        1  All the exhaust pipe joints must be secured with three screws  Make sure that each screw goes through the  inner wall of both connectors  male and female   See pictures below showing a male female coupling     PROPER INSTALLATION IMPROPER INSTALLATION       CAUSES RESTRICTION    2  Aminimum rise of 14    per horizontal foot must be respected     29    3 9 1 Damper    If the draft exceeds 0 06 INW C   a barometric damper must installed  The barometric damper must be adjusted so  that the maximum draft measured at the furnace outlet is limited to 0 06 IN W C  Please note that a draft higher than  0 06 IN W C
34. ason      f possible  the smoke flue should be dismantled and cleaned     The flue should be inspected for possible damage      fitis in good condition  put the flue back in place  otherwise  it must be replaced     REGULARLY  EXAMINE THE FLUE PIPES  THE JOINTS  AND THE SEALING TRIMS TO ENSURE THAT  2    AND THE COMBUSTION GASES ARE        TRANSPORTED INTO THE AIR DUCTING      Use only wood as a combustible       Seasoned hard wood logs 18  to 22  long are recommended as combustible     5 3 MAINTENANCE OF THE BLOWER MOTOR    The two motor bearings must be lubricated once a year using non detergent SAE 20 oil  Marathon motor only      DO NOT OVERLUBRICATE    5 4 FILTERS   The furnace must not be operated without filters  In order to efficiently and safely operate a slow combustion  heating system   you have to ensure a regular maintenance  This means that the chimney  the joints and the flue  must be kept in good condition and the air filters must be replaced regularly  use the same size and same type as  the original filters  High efficiency 2 ply  3 ply  or 4 ply filters are recommended    Filters dimensions    Max Caddy  16  x 20    filters  5 5 DOOR GASKET MAINTENANCE       is important to maintain the door gasket in good condition  After a while  the gasket might sag  a door adjustment  may then be required  If the door adjustment is not sufficient  replace the door gasket with a genuine one     39    Door adjustment procedure     1  Unscrew completely the locking pin  se
35. burning unit is connected on the evacuation pipe of the  wood burning furnace  the minimum draft to be respected is 0 04 IN W C  in the evacuation pipe of the wood    burning side  at all times       fact  a barometric damper that would be opened too wide could cause       important loss of draft in the evacuation pipe of the wood burning furnace     ELECTRODES SETTING    The electrodes must be adjusted by a qualified technician  A proper positioning of the electrodes 15 important to get an  efficient lighting of the oil     ELECTRODE SETTING FOR  F  HEAD    5 32  ELECTRODE    7 16        1 16   NOZZLE    DO    WARNING    1  REFER TO THE RATING PLATE FOR THE PUMP PRESSURE AND THE NOZZLE TYPE   2  REFER TO THE OIL BURNER S INSTRUCTIONS MANUAL FOR DETAILS ON THE PUMP   3  FOR ELECTRODES SETTING  SEE THE OIL BURNER S MANUAL     4  FOR THE START UP AND ADJUSTMENT OF THE BURNER  SEE THE INSTRUCTIONS MANUAL OF  THE BURNER     5  IN CASE OF BURNER FAILURE  REFER TO THE BURNER MANUAL     4  APPLIANCE START UP    The start up must be performed by a qualified technician  Make sure the installation is completed and the oil tank has  been filled up  The oil line must also have been purged     CAUTION  CLOSE THE BLOWER COMPARTMENT ACCESS  PANEL BEFORE STARTING THE BURNER     5  PROLONGED CLOSING    A  Cut off the electric circuit  B  Close the oil shut off valve    NOTE  THE SHUT OFF VALVE MUST BE CLOSED WHEN THE APPLIANCE IS OUT OF SERVICE FOR A  PROLONGED PERIOD OF TIME     6  MAINTENAN
36. ctions  section in order to obtain a complete definition  of the terms KIP  TEMP  and UNIT     32    When your choice is made  press SELECT  Then  use the arrows to make the appropriate adjustment  Press  SELECT to memorize your adjustment  To change the selection   KIP  TEMP  or UNIT  push an arrow button  To  go back to the main menu  HEAT  COOL  CIRC  MANU   push on the MODE button  After two minutes of inactivity  on the keyboard  the display will shut itself off     4 5 4 COOL Mode  air conditioning   Operation        an air conditioning unit is installed  the PC board will have to be connected to a dual function wall thermostat  e g      heat cool     in order to synchronize the start of the furnace blower with the start of the air conditioning condenser   Upon receiving the wall thermostat   s signal  the furnace blower will start functioning at the speed selected by the  user     Programming    Make sure that your wall thermostat is well connected to the PC board  Make sure that the right port has been  selected based on the type of thermostat  e g  24VAC or Millivolt      In the MODE menu  select COOL by pushing the SELECT button  Then  using the arrows buttons  choose from the  different selections  TEMP  UNIT  or FAN  Consult the    Selections    section in order to obtain a compete definition  of the terms TEMP  UNIT  and FAN     When your choice is made  press SELECT  Then  use the arrows to make the appropriate adjustment  Press  SELECT to memorize your adjustme
37. dequately to avoid any damage     2 1 BURNER PUMP    The oil burner is easy to install  Use the three screws and nuts to fix the burner on the combustion chamber     The burner is equipped with a single stage pump  When the pump is connected to a single feeder pipe  a maximum  rise of 8 feet is allowed  This height is measured from the tank outlet level to the burner inlet     When the rise is more than 8 feet and not exceeding 10 feet  a by pass plug  provided with the burner  must be  inserted in the pump and an oil return pipe must be installed  For more details  see    INSTALLATION  INFORMATIONS     Part No  21844 on the burner pump       the rise is higher than 10 feet     two stage pump may be required along with an oil return pipe     3  APPLIANCE INSTALLATION    3 1 LOCATING THE UNIT    Consult Section A of this manual for more details     N B  This appliance must be installed in conformity with the instructions on    the certification label                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                         
38. e picture below        i    4 et Locking pin                      L        2  To increase the pressure of the door on the gasket  turn the handle counter clockwise  to decrease the pressure  of the door on the gasket  turn the handle clockwise until desired pressure is attained     3  Then  screw back the locking pin about 1 4    deep and make sure you lock it in place with the nut     40    6  REPLACEMENT PARTS    Your PSG furnace is designed to burn clean and requires little maintenance  It is recommended to conduct a visual  inspection at least once a month to uncover any damage to the unit  Any defect must be repaired without delay  using genuine PSG replacement parts  You can find a complete list of replacement parts in our website at www psg   distribution com     6 1 DOOR GLASS    e Inspect the glass regularly to detect any glass failure  If you find any defect  stop using the wood furnace  immediately  Never operate a wood furnace with a broken glass       lf you have to change your door glass  you must use Pyroceram 3 16   5mm  thick  Use genuine parts sold  by a PSG authorized dealer       To replace the glass  remove the screws that hold the glass retainers in place  Removed these retainers  and replace the defective glass  the glass gasket should be replace at the same time  To put back in place   reverse the procedure    e Do not use abrasive cleanser  Special cleansers for wood fireplaces glass are available in any good  hardware store or specialty hearth retail
39. eat badly  cause smoke returns  or  reversed draft  whether there is combustion or not               opening of a window  even slightly  in calm weather  windless   eliminates every problem mentioned  above              house is equipped with a tight vapour barrier and adjusted windows  and or is equipped with an  interior air mechanical evacuation device       There is excessive condensation on the windows in winter  and            house is equipped with a ventilation system     If  according to these symptoms or other similar ones  there is insufficient combustion air  it is necessary to ensure  an additional combustion air supply     Additional combustion air can be provided following the following methods  provided that they satisfy chapter 4 of the  CSA B365 standard for Canada     e Direct connection  solid fuel units can be connected directly to a source of new combustion air only if they  are certified for this kind of installation  which must respect the manufacturer s instructions  The MAX Caddy  can be installed with an optional sealed fresh air kit that has been tested with the unit  Consult your dealer    e Indirect method  new combustion air can be brought into a pipe located within approximately 300mm  12  inches  of the unit  If the pipe is too close to the furnace  it may interfere with its operation    e Mechanical ventilation system  if the house is equipped with a ventilation system  air exchanger or heat  recovery   the ventilation system may provide suff
40. er    e Clean glass ONLY when the unit has cooled down     6 2 GASKET    We recommend replacing the gasket that seals the door once a year  in order to maintain a good control of the  combustion for maximum efficiency and security  To replace your door gasket  remove the old gasket and adhesive   Clean the surface thoroughly  apply a high temp adhesive silicone  650  F  sold for that particular use  and put the  new gasket onto the door  Wait for at least 4 hours before lighting your furnace     41    7 GENERAL ELECTRIC DIAGRAM WITH BECKETT OIL BURNER  CONTROL PCB   RTD     2      A          24V         WOOD DMPR  MOTOR  DAMPER         DMPR          CONDITIONNER BYPASS  MOTOR DAMPER     ELEC HEAT  HEATING  ELEMENT SEQUENCER   WATR SOLN  WATER   HEATER OPTION   OUTPUT 5     BECKETT AFG  ce         CC      LINE FAN      77777 4    LINE      HOT   FRAME  FRAME GROUND   AC COMMON  AC COMMON     42                    MIL          BIENERGY INPUT                    E E WOOD T STAT MECH    Ooo  v  WOOD THERMOSTAT     USER T STAT MECH   OPTION THERMOSTAT            PCBO411 059009                 c            MEDHIGH                            iw                   je          8  GENERAL ELECTRIC DIAGRAM WITH RIELLO OIL BURNER  RTD IN  CONTROL PCB               P 7       BIENERGY INPUT                                us             m             24  AC  WOOD DMPR   MOTOR DAMPER   AIC DMPR          CONDITIONNER BYPASS  MOTOR DAMPER     ELEC HEAT  HEATING  ELEMENT SEQUENCER   WATR SOLN  WA
41. event  corrosion     2 5 SMOKE DETECTOR    We highly recommend the use of a smoke detector  It must be installed at least 15 feet  4 57 m  from the appliance  in order to prevent undue triggering of the detector when reloading     2 6 DOOR GLASS    To maintain a clean and safe installation  do not build your fire too close to the glass or allow logs to lean on the  glass     Do not operate your furnace at too low a setting  Keep the air inlet opened long enough during the fire start up to  prevent the fire from smouldering  which could stain the glass     An intense fire will help keep the glass clean  However  in the event that your glass gets stained  which should not  occur under normal operating conditions  you will have to clean it using a wet cloth and a fireplace glass cleaner     Clean the glass ONLY when the unit has cooled down  Do not use abrasive cleanser  Fireplace glass cleaners are  available in most home centers and specialty hearth retailers     WARNING  Avoid knocking or scratching the glass    could crack or break     2   GLASS SPECIFICATIONS  The glass is made of 3 16     5mm  thick Pyroceram   Do not operate your wood furnace with a broken glass  as this could seriously damage your furnace     You can purchase a replacement glass from your PSG dealer     2 8 ASH DRAWER  Your furnace is equipped with an ash drawer to collect ashes produced by the combustion of wood  This drawer    must not be left open during combustion as this may cause over firing and se
42. gurations in the following pages    In order to realize the various configurations  you must remove the three screws retaining the side plate where you  wish to install the cold air ducting support  Keep the screws which retained the side plate to install the side plate at  the new desired location  The side plate and the cold air ducting support must be secured using nine screws each   kept from the previous step   Remaining screws are provided with the cold air return box     11    Installation of the cold air ducting support at the RIGHT of the cold air return box       Installation of the cold air ducting support at the LEFT of the cold air return box          Installation of the cold air ducting support ON TOP of the cold air return box with filter exit towards the RIGHT          Installation of the cold air ducting support ON TOP of the cold air return box with filter exit towards the LEFT          13    3 3 CONTROL PCB INSTALLATION AND CONNECTION    The control PCB may be installed on either side of the furnace  Remove the 4 screws secured on the side of the  furnace where you wish to install the control PCB  either on the left or on the right side  and keep these screws   Remove the access panel of the control PCB  Secure the control PCB where you removed the screws from the  furnace  Refer to the electric wiring diagram in section 7 for the electrical connections  Do not screw the access  panel back on the control PCB until all connections are made     Control PCB in
43. icient auxiliary air to the solid fuel unit  Otherwise  the  owner should be informed that the ventilation system may have to be rebalanced by a ventilation technician  after the installation of the solid fuel unit     24    NOTE        is recommended to install an outside air inlet with a diameter of at least 4 inches in the room where the heating  appliance is installed  see drawing below   It is preferable to choose a wall which is not exposed to dominant winds   depending on the conditions surrounding your house     Insulated pipe  full length        Free air Presh air    entry    Exterior  wall    N B  The owner of the furnace is responsible for the room   s air quality in case of negative pressure or  temporary negative pressure     For more information regarding the installation of fresh air intake adapter  refer to the option   s manual     25    311 PARALLEL INSTALLATION    The installation of the Max Caddy with another furnace using the same ductwork is not allowed in Canada  This  type of installation is only allowed in the United States  Ideally  the maximum BTU input of the existing oil  gas   or electric furnace should be equal or higher than the maximum BTU input of the wood furnace  It is mandatory to  respect minimum clearances between the ductwork and combustible material as if the wood furnace was installed as  a standalone unit  The ductwork and furnace should be adjusted in order to reach a static pressure of at least 0 20  IN WC  but not more than 0 50 I
44. ion of the furnace  It is simply a  preference chosen by the technician or the user of the product      FAN  blower speed     Using the arrows  increase or decrease the blower speed  You can choose from six preselected speeds  This  selection is very important for the modes COOL  MANU  or CIRC  There is a choice of 6 different speeds  Under  the COOL mode  the speed selected is the speed at which the distribution blower will work when a cooling demand  will be sent by the thermostat  Under the MANU mode  it is the speed at which the distribution blower will work    34    when a heating demand will be sent by the thermostat and that the hot air plenum will have reached its kick in  temperature  KIP   Under the CIRC mode  it is the speed at which the distribution blower will run to circulate the air  inside the house during summer  The CIRC mode will also be used by the technician to manually select speed  4 in  order to balance the system upon installation of the furnace     Note  The FAN selection is not necessary under the HEAT mode because it is the PC board that automatically  chooses the speed at which the distribution blower runs in order to maintain the BEP inside the hot air plenum     4 6 LIGHTING  1  Open the furnace door    Note  If there is already a bed of coals in the firebox  go to pre heating     2  Place one or two dry kindlings at the front of the furnace   3  Place newspaper strips on top of the kindlings   4  Cover the newspaper with more kindlings and smal
45. l for heat  see detail G   Refer to the electric wiring diagram in section 7 for the electrical    connections        DETAIL G    WARNING  USE WIRING SUITABLE FOR 75  C  not supplied     18    Then  you need to connect the servomotor to the control PCB  To do so  refer to the electric wiring diagram in  section 7  To run the wire properly  refer to the drawings below     Wire running to the control PCB installed on the LEFT side of the furnace       SERVOMOTOR TO PCB WIRING       Wire running to the control PCB installed on the RIGHT side of the furnace       SERVOMOTOR TO PCB WIRING       WARNING  USE WIRING SUITABLE FOR 75   C  not supplied     19    3 6   HANDLES INSTALLATION    The following step consists of installing the handles on the handle rods of the ash drawer and the door as shown  below        DETAIL         37 UNIT LOCATION    The furnace must be installed where outside air supply is sufficient for proper combustion  In airtight houses  it  might be necessary to install an outside air intake     The furnace must be positioned so that the connector is as short as possible  minimize the use of 90   elbows     The owner must ensure a proper installation to allow for a safe operation of the appliance     20    3 8 CLEARANCES TO COMBUSTIBLES AND FLOOR PROTECTOR    N B  This appliance must be installed according to the instructions on the unit s certification label                                                                                                        C
46. l pieces of dry wood     5  Add newspaper strips  then light the fire a low as possible and leave the door 1 2   13 mm  opened  If you        lighting the fire  you might experience a back draft through the air inlets     47 PREHEATING    1  Once the kindling is well ignited or the coals revived  put 2 or 3 fire logs in such a way that the flames can  interlace between the logs  Then  close the door  It is important to respect these loading sequences so that the  wood will burn from the front to the back of the furnace     2  Wait 15 to 20 minutes  then proceed with loading the furnace     48   HEATING    1  When loading the furnace  lower the kindled pieces of wood and place them at the center of the combustion  chamber before adding new logs     2  Do not overload  Air must circulate freely in the upper part of the combustion chamber in order to obtain an  efficient operation of the appliance  secondary burn   Please note that a small hot fire will produce much less  residues than a large  smouldering one     IMPORTANT  DURING THE HEATING PROCESS  REMOVE THE ASHES AND WOOD THAT COULD  OBSTRUCT THE 1 4   6 4 mm  HOLE  PILOT  LOCATED BELOW THE DOOR  INSIDE THE  FURNACE S COMBUSTION CHAMBER     PROCEDURE TO OPEN THE LOADING DOOR    TO MINIMIZE THE RISK OF SMOKE SPILLAGE  OPEN THE DOOR 1   AND WAIT ABOUT 10 SECONDS BEFORE OPENING IT COMPLETELY   THE PURPOSE IS TO STABILIZE THE PRESSURE INSIDE THE FURNACE        35    4 9 EARLY SIGNS OF AN OVERFIRED FURNACE   1  Roaring fire    
47. lect and hold in a few second the  MODE   button while putting the breaker back to    ON     You will then be able to select the option corresponding to you  installation using the arrows     30    Table 1   Configuration    1111 Wood only  2222 Wood oil combo  3 9 93 Wood electric combo    4444 Trio  wood followed by oil and electricity  5555 Trio  wood followed by electricity and oil  6666       4 3 1 The use of the  BI ENERGY   function    The bi energy function is used when a local utility company  Hydro Quebec for instance  offers a bi energy program  under which a preferential rate is given  provided that the appliance is equipped with an electronic control that  guaranties the use of a particular source of energy  ex  electricity  based on a given criterion  ex  the outdoor  temperature      When the MAX Caddy is programmed for bi energy  a temperature sensor  normally open contact  is connected to  the PC board  see electric diagram        BIENERGY    port   The contact remains open for as long as the outside  temperature is above a certain value  this reference value is programmed into the system provided by the utility  company   As long as the contact remains open  the electrical unit supplies the heat when the wood is not able to  satisfy the thermostatic demand  If  however  the outside temperature reaches a level below the reference value   the contact closes and the oil unit is used as the option for heat if the wood is not able to satisfy the thermostatic  dem
48. mizes the  efficiency of combustion  The presence of the sealed vision cap thus prevents the return of oil odor        TOOLS REQUIRED       DRAFT GAUGE     SMOKE TESTER     PUMP PRESSURE GAUGE     NOZZLE AND ELECTRODES POSITION TESTER    COMBUSTION TESTER    CHECK LIST       SELECTION OF NOZZLE AND HEAD     NOZZLE   ELECTRODES POSITION IN RELATION TO THE HEAD      PUMP PRESSURE      OILLINE IS BLEED      FAN SPEED     BAROMETRIC DAMPER POSITION    COMBUSTION VERIFICATION PROCEDURE     A     B     C                          G     H     N B     3 11    DRILL A 9 32  DIAMETER HOLE IN THE EVACUATION PIPE APPROXIMATELY 18  FROM THE OUTLET   CLOSE THE DOOR AND THE AIR INTAKE S  OF THE WOOD BURNING FURNACE     LIGHT THE BURNER FOR AT LEAST 10 TO 15 MINUTES     OVER THE FIRE DRAFT   0 01 TO 0 02 IN W C   THE DRAFT OVER THE FIRE MUST BE MEASURED IN  THE OPENING OF VISION TUBE   S PULSATION TRAP      SMOKE TEST BETWEEN 0 AND 1 ON THE SHELL BACHARACH SCALE  TRACES     DRAFT IN THE CHIMNEY   0 02 IN W C    PERCENTAGE OF EXCESS AIR   20 TO 40   12      2  5          AVERAGE EFFICIENCY OF 83  TO 87  BASED ON THE TYPE OF BURNER AND ITS INPUT    TIGHTEN ALL THE LOCKING SCREWS AFTER COMPLETING THE FINAL ADJUSTMENT    The barometric damper provided with the appliance must be properly installed on the flue pipe of the oil burning  unit  The purpose of the damper is to adjust the draft in the evacuation pipe of the oil burning unit to the  recommended level  Since the evacuation pipe of the oil 
49. ns  For each mode  some selections are available  A definition is provided below  see      The Selections         31    4 5 1        speeds    Your furnace is equipped with a 4 speed blower  Using the PC board  we have created 6 functional speeds  Refer to  Table 2 below for the various speed configurations     Table 2   The Speeds    Corresponding data Static pressure  Blower speed  1 using 98V 60     0 2    H2O  Blower speed  1 using 115V 0 2    H2O      6  Blower speed  4 using 115V  1260  02 H0            These results were measured at exit of plenum during laboratory tests  Results may vary depending of the  configuration and installation     4 5 2 System Balancing       is important to call upon a professional installer for the installation of the furnace and the ducting system  configuration  Certain check ups must be performed and certain rules must be respected in order not to damage the  blower  When all components are installed on the furnace and the ducting system is connected to the various rooms  of the house  you must balance the ducting system  In order to do so  start the furnace blower by selecting the  recirculation mode  CIRC   Then  in the FAN section  use the arrows to select speed  4  refer to Table 2   It is  important to respect the velocity in the main duct  the secondary ducts  as well as the velocity at the room outlets   The static pressure of your system must be adjusted to at least 0 2 IN W C  and must not exceed 0 5 IN W C   Finally  make sure 
50. nt  To change the selection  TEMP  UNIT  or FAN  push an arrow button  To  go back to the main menu  HEAT  COOL  CIRC  MANU   push on the MODE button  After two minutes of inactivity  on the keyboard  the display will shut itself off     4 5 5 CIRC  air circulation   Operation    This mode is used to circulate air during summer  Thus you will benefit from your ducting system to circulate fresh  air from your basement throughout the house     Programming    In the MODE menu  select CIRC by pushing the SELECT button  Then  using the arrows buttons  choose from the  different selections  TEMP  UNIT  or FAN  Consult the  Selections  section in order to obtain a compete definition  of the terms TEMP  UNIT  and FAN     When your choice is made  press SELECT  Then  use the arrows to make the appropriate adjustment  Press  SELECT to memorize your adjustment  To change the selection  TEMP  UNIT  or FAN  push an arrow button  To  go back to the main menu  HEAT  COOL  CIRC  MANU   push on the MODE button  After two minutes of inactivity  on the keyboard  the display will shut itself off     4 5 6 MANU  manual heating   Operation    The mode allows you to run your system manually without taking into account the blower variation around the BEP   Best Efficiency Point   Therefore  you will simply have to select the KIP  i e  Kick in Point   the hot air plenum  temperature at which the blower will start   as well as the blower speed based on your system s static pressure     33    When the 
51. nts  blowers  heat sensors  switches  rheostat    relays  damper motor  fan limit control  PC board  wiring  and other   controls    Ceramic glass  thermal breakage only    paint  peeling   gaskets    insulation  and ceramic fibre blankets    Firebrick    Pictures required                               Shall your unit or a components be defective  contact immediately your PSG dealer  Prior to your call make sure you  have the following information necessary to your warranty claim treatment     e Your name  address and telephone number  e Serial number and model name as indicated on the  e Bill of sale and dealer   s name  nameplate fixed to the back of your unit   e Nature of the defect and any relevant information     Before shipping your unit or defective component to our plant  you must obtain from your PSG dealer  an Authorization Number  Any merchandise shipped to our plant without authorization will be  refused automatically and returned to sender     61       po                       i          PSG LIMITED LIFETIME WARRANTY  PRIVILEGE     The warranty of the manufacturer extends only to the original consumer purchaser and is not transferable  This  warranty covers brand new products only  which have not been altered  modified nor repaired since shipment from  factory and purchased through an authorised dealer  Proof of purchase  dated bill of sale   model name and serial  number must be supplied when making any warranty claim to your PSG dealer     This warranty applie
52. pport bracket installed on the LEFT side of the furnace        10 X 1 2   A  type metal screw      RTD probe  RTD support bracket       DETAIL C       16    Once the RID probe is installed on the        support bracket  you need to connect the RTD probe to the control  PCB  To run the wire properly  refer to the drawings below  Refer to the electric wiring diagram in section 7 for the  electrical connections     RTD probe installed on the RIGHT side of the furnace       RTD probe wiring        DETAILE           probe installed on the LEFT side of the furnace             RTD probe wiring       DETAIL       17    3 5 SERVOMOTOR INSTALLATION AND CONNECTION    Your Max Caddy furnace is equipped with a servomotor  You need to secure it in place in the two pre drilled holes  using two screws as shown below     Servomotor    10 24 F 5 8  hex washer head thread cutting screw       DETAIL    Once installed  you need to install the chain that links the air inlet damper to the servomotor as shown below  For  more information regarding this installation  refer to the furnace owner s manual  The chain that links the air inlet  damper to the motor must have a play of 1 8        must be secured in place by the hook  When there is no call for  heat  the air inlet damper must be completely closed and the chain must be hooked to the servo motor at the  8  o clock  position  This way  the air inlet damper should be about 3 4  open and the chain at the    5 o clock  position  when there is a cal
53. purchased your furnace  Keep your sales invoice  We also recommend    that you register your warranty online at  http   www psg distribution com warranty registration aspx  Hegistering your warranty online will help us track rapidly the information we  need on your furnace        IMPORTANT NOTE     THE INSTALLATION OF THIS CENTRAL HEATING SYSTEM MUST BE PERFORMED BY A   QUALIFIED TECHNICIAN  PSG RESERVES ITSELF THE RIGHT TO VOID ITS WARRANTY   OR DENY TECHNICAL ADVICE IF THE FURNACE HAS NOT BEEN SOLD OR INSTALLED  BY A PROFESSIONAL     WARNING   THE INSTALLATION OF THIS APPLIANCE REQUIRES THE ADITION OF A  BLOWER BOX  amp  ELECTRONIC FAN LIMIT KIT   PA08565     Emissions  5 9 g h or 0 316 g MJ  Average efficiency  85    LHV    77   HHV     SECTION A   WOOD OR WOOD ELECTRIC COMBINATION FURNACES    Take note that this furnace operates like an EPA wood burning stove  This applies to the lighting  the ember bed   and the minimum combustion air intake which was determined based on the use of good seasoned cordwood     The Max Caddy furnace was tested and approved according to the CSA B415 1 10 Standard     To optimize the efficiency of your furnace  here is some advice that you should follow when installing or operating  your Max Caddy    e Respect the local codes  when in doubt  consult your local dealer        Make sure your furnace is installed according to the instructions on the certification label     e All controls and adjustments must be performed by a qualified technician
54. r to your call make sure you  have the following information necessary to your warranty claim treatment     e Yourname  address and telephone number  e Serial number and model name as indicated on the  e      of sale and dealers name  nameplate fixed to the back of your unit     e Nature of the defect and any relevant information     Before shipping your unit or defective component to our plant  you must obtain from your PSG dealer  an Authorization Number  Any merchandise shipped to our plant without authorization will be  refused automatically and returned to sender     62    
55. re limited according to the table below     The manufacturer at its discretion may decide to repair or replace any part or unit after inspection and investigation of  the defect  The manufacturer may  at its discretion  fully discharge all obligations with respect to this warranty by  refunding the wholesale price of any warranted but defective parts  The manufacturer shall in no event be responsible  for any special  indirect  consequential damages of any nature  which are in excess of the original purchase price of the  product  A one time replacement limit applies to all parts benefiting from a lifetime coverage  This warranty applies to  products purchased after April 1st  2013      WARRANTY APPLICATION  DESCRIPTION   PARTS   LABOUR  Castings  combustion chamber  welds only   castings  and heat exchanger        welds only     Lifetime    Stainless steel firebox components  secondary air tubes   surrounds and   heat shields  ash drawer  and plating   defective manufacture        Carbon steel firebox components  glass retainers  handle assembly  C  Cast   baffle   and vermiculite baffle      Oil burner  electrical elements  blowers  heat sensors  switches  rheostat     relays  damper motor  fan limit control  PC board  wiring  and other     Ceramic glass  thermal breakage only    paint  peeling   gaskets  insulation  x  and ceramic fibre blankets  x    Firebrick   Pictures required       Shall your unit or a components be defective  contact immediately your PSG dealer  Prio
56. recommend an installation as per the graphic provided below  This installation will provide the most efficient and  safe operation of the air conditioning unit using the distribution blower of the MAX Caddy furnace during summer  In  order to complete the installation of an air conditioning unit  the main thermostat must be a    heat cool    type   Furthermore  the PC board of the furnace must be in a COOL mode and the desired distribution blower speed must  be programmed  see MODES section for complete instructions   It must be noted that upon thermostatic demand  for cooling  the distribution blower will start immediately     The capacity and characteristics of the air conditioning unit that has been tested with the MAX Caddy are stated  below  The use of another brand with similar capacity and characteristics is adequate     Condenser brand  Goodman GSX13048  Capacity  4 ton  Coil type  Type A  CAUF uncased indoor coil                                     Damper                                                                                                    MAH  n  Te                                     gt  E    1 A               V               L                                                 A C coil     Damper                                                                                                                                                                                                                                                                       
57. rious damages to the furnace   The drawer must be emptied regularly        is important that the door and the ash drawer be kept closed while the appliance is in use     Maintain all gaskets in good condition  in case of deterioration  contact your dealer for a genuine  replacement gasket        2 9   ASH GRATE    You must replace the ash grate if it is damaged and a replacement may be obtained from your dealer     3  APPLIANCE INSTALLATION    The installation instructions of this section apply to the wood only Max Caddy  the wood electric Max Caddy  the  wood oil Max caddy  and the wood oil electric trio Max Caddy     WARNING  THE INSTALLATION OF THIS APPLIANCE REQUIRES THE ADITION OF A  BLOWER BOX 8 ELECTRONIC FAN LIMIT KIT       08565     CAUTION  The following instructions do not supersede the local code   Detailed content of the blower box  amp  electronic fan limit kit       08565      CONTENT OF THE BOX  1 X BLOWER ASSEMBLY MANUAL KIT FOR MAX CADDY  27 X  10 X     A  TYPE METAL SCREW  2 X 4 20 X 1  ELEVATOR BOLT  1 X 100 OHM RTD   38  WIRE  1X RTD SUPPORT    1 X  8 X     METAL SCREW   1    3 8    1 SCREW CONNECTOR FOR BX WIRE   1 X RED PLASTIC SLEEVE FOR BX WIRE   2 X RED PLASTIC SLEEVE FOR BX WIRE  ANTI SHORT SIZE 2   1 X 34    SCREW CONNECTOR FOR BX WIRE       Mounted filter holder     gt     Air filter 20  x 16  x 1  cardboard                 side plate       Cold air ducting support    Cold air return box    Side plate                       1 4    20  x 1  hex bolt
58. rmostats use a dry contact  hook up the main thermostat   wood  to the WOOD MECH port on the PC board and the option   s thermostat to the USER MECH port  If the  thermostats send a 24 volt signal to the appliance  hook up the main thermostat  wood  to the WOOD 24V port on  the PC board and the option   s thermostat to the USER 24V port  For more information regarding the wiring  connections  refer to the diagrams in section 7     3 13 3 Trio furnace  wood oil electric or wood electric oil      The trio model also uses two thermostats which must be located at the same height from the floor  When the main  thermostat  wood  calls for heat and the demand cannot be satisfied by the furnace with wood as a combustible  the  first option will take over and maintain the house at the temperature programmed on the second thermostat  option    Should the first option be unable to satisfy the call for heat  the second option will take over and maintain the house  at the temperature programmed on the second thermostat  option   If the thermostats use a dry contact  hook up the  main thermostat  wood  to the WOOD MECH port on the PC board and the option   s thermostat to the USER MECH  port  If the thermostats send a 24 volt signal to the appliance  hook up the main thermostat  wood  to the WOOD  24V port on the PC board and the option   s thermostat to the USER 24V port  For more information regarding the  wiring connections  refer to the diagrams in section 7     3 14 INSTALLATION OF A 
59. s to normal residential use only  Damages caused by misuse  abuse  improper  installation  lack of maintenance  over firing  negligence or accident during transportation  power  failures  downdrafts  or venting problems are not covered by this warranty     This warranty does not cover any scratch  corrosion  distortion  or discoloration  Any defect or damage caused by the  use of unauthorized parts or others than original parts void this warranty  An authorized qualified technician must  perform the installation in accordance with the instructions supplied with this product and all local and national  building codes  Any service call related to an improper installation is not covered by this warranty     The manufacturer may require that defective products be returned or that digital pictures be provided to support the  claim  Returned products are to be shipped prepaid to the manufacturer for investigation  If a product is found to be  defective  the manufacturer will repair or replace such defect  Transportation fees to ship the product back to the  purchaser will be paid by the manufacturer  Repair work covered by the warranty  executed at the purchaser   s domicile  by an authorized qualified technician requires the prior approval of the manufacturer  Labour cost and repair work to  the account of the manufacturer are based on predetermined rate schedule and must not exceed the wholesale price of  the replacement part  All parts and labour costs covered by this warranty a
60. stalled on the RIGHT side of the furnace    CONTROL PCB ACCESS PANEL   10 X 1 2       TYPE METAL SCREW       CONTROL PCB     10 X 1 27      TYPE METAL SCREW    mL 28                     Control PCB installed      the LEFT side of the furnace    CONTROL PCB     10 A 1 2      TYPE METAL SCREW CONTROL PCB ACCESS PANEL     10    1 2  A  TYPE METAL SCREW    14    Now  it is time to make the connection between the control PCB and the blower  Since the control PCB may be  installed on either side of the furnace  refer to the drawings below to run the wire properly     Control PCB installed on the RIGHT side of the furnace    THE COLD AIR DUCTING SUPPORT HAS BEEN  HIDDEN ON THIS VIEW TO SHOW THE    ELECTRIC WIRE LOCATION              14 6 electric wire           Control PCB installed on the LEFT side of the furnace    BX 14 6 electric wire    15    34 RTD SUPPORT BRACKET INSTALLATION AND CONNECTION   resistance temperature detector     Your Max Caddy furnace is equipped with a RTD probe  resistance temperature detector   This RTD probe must be  installed on the RTD support bracket  The RTD support bracket may be installed on left side or on the right side of  the furnace  To install it  all you need to do is to screw it in place in the two pre drilled holes as shown below     RTD support bracket installed on the RIGHT side of the furnace        10 X 1 2       type metal screw        RTD support bracket             RTD probe  Le 7s                P j      y  PNE  DETAIL D       RTD su
61. temperature in your house will go below the value at which your wall thermostat is programmed  a signal  will be sent to your furnace through the PC board  activating the motorized damper located in front of the furnace  and allowing more oxygen to the fire  The         temperature sensor   located in the hot air plenum of your furnace   will read the plenum temperature  When the temperature reaches the start up value selected by the user  KIP   the  blower will start functioning at the speed selected by the user  If the temperature exceeds the limit determined by the  manufacturer  the blower will automatically select the maximal speed and the front air damper will close in order to  slow down combustion  When the temperature returns to a safe level  the blower will return to the speed selected by  the user     Programming    Make sure that your wall thermostat is well connected to the PC board  Make sure that the right port has been  selected based on the type of thermostat  e g  24VAC or Millivolt      In the MODE menu  select MANU by pushing the SELECT button  Then  using the arrows buttons  choose from the  different selections  KIP  TEMP  UNIT  or FAN  Consult the    Selections    section in order to obtain a compete  definition of the terms KIP  TEMP  UNIT  and FAN     When your choice is made  press SELECT  Then  use the arrows to make the appropriate adjustment  Press  SELECT to memorize your adjustment  To change the selection   KIP  TEMP  UNIT  or FAN  push an arro
62. that you never exceed the maximum blower motor full load amperage     4 5 3 HEAT Mode  automatic heating     Operation    When the temperature in your house is below the value at which your wall thermostat is programmed  a signal is  sent to your furnace through the PC board  activating the motorized damper located in front of the furnace and thus  allowing more oxygen to the fire  The RTD temperature probe  located inside the hot air plenum of your furnace   reads the plenum temperature continuously  When the temperature reaches the start up value selected by the user   KIP     Kick in Point   the distribution blower starts functioning at the minimum speed  Thereafter  the blower  increments its speed until it reaches the best efficiency point  BEP  determined by the manufacturer  If the  temperature inside the hot air plenum exceeds the limit determined by the manufacturer  the blower automatically  selects the maximal speed and the motorized damper closes in order to slow down combustion  When the  temperature returns to a safe level  the blower speed gradually returns to the speed required to maintain the BEP     Programming    Make sure that your wall thermostat is well connected to the PC board  Make sure that the right port has been  selected based on the type of thermostat  e g  24VAC or Millivolt      In the MODE menu  select HEAT by pushing the SELECT button  Then  using the arrows buttons  choose from the  different selections  KIP  TEMP  or UNIT  Consult the  Sele
63. ugh an authorized PSG dealer     If you want to enjoy the best service on the market and substantial savings on heating costs  there    is really only one choice  an Authorized PSG Dealer     por             60                WARRANTY    a    REGULAR             PSG LIMITED LIFETIME WARRANTY  REGULAR     The warranty of the manufacturer extends only to the original consumer purchaser and is not transferable  This  warranty covers brand new products only  which have not been altered  modified nor repaired since shipment from  factory  Proof of purchase  dated bill of sale   model name and serial number must be supplied when making any  warranty claim to your PSG dealer     This warranty applies to normal residential use only  Damages caused by misuse  abuse  improper  installation  lack of maintenance  over firing  negligence or accident during transportation  power  failures  downdrafts  or venting problems are not covered by this warranty     This warranty does not cover any scratch  corrosion  distortion  or discoloration  Any defect or damage caused by the  use of unauthorized parts or others than original parts void this warranty  An authorized qualified technician must  perform the installation in accordance with the instructions supplied with this product and all local and national  building codes  Any service call related to an improper installation is not covered by this warranty     The manufacturer may require that defective products be returned or that digital pict
64. ures be provided to support the  claim  Returned products are to be shipped prepaid to the manufacturer for investigation  If a product is found to be  defective  the manufacturer will repair or replace such defect  Transportation fees to ship the product back to the  purchaser will be paid by the manufacturer  All parts costs covered by this warranty are limited according to the table  below     The manufacturer at its discretion may decide to repair or replace any part or unit after inspection and investigation of  the defect  The manufacturer may  at its discretion  fully discharge all obligations with respect to this warranty by  refunding the wholesale price of any warranted but defective parts  The manufacturer shall in no event be responsible  for any special  indirect  consequential damages of any nature  which are in excess of the original purchase price of the  product  A one time replacement limit applies to all parts benefiting from a lifetime coverage  This warranty applies to  products purchased after April 1st  2013     WARRANTY APPLICATION  PARTS LABOUR    DESCRIPTION       Castings  combustion chamber  welds only   castings  and heat exchanger   Lifeti     ifetime    welds only       Stainless steel firebox components  secondary air tubes   surrounds and   heat shields  ash drawer  and plating   defective manufacture     Carbon steel firebox components  glass retainers  handle assembly  C Cast   baffle   and vermiculite baffle     Oil burner  electrical eleme
65. w  button  To go back to the main menu  HEAT  COOL  CIRC  MANU   push on the MODE button  After two minutes  of inactivity on the keyboard  the display will shut itself off     4 5 7 The Selections    KIP  Kick in Point   start up temperature of the furnace blower     Using the arrows  increase or decrease the temperature at which the furnace distribution blower will start  functioning  You can adjust the temperature between 107  F  42  C     132 F  56  C    After two minutes of inactivity  on the keyboard  the display will shut itself off  The KIP must be programmed if the furnace is operated under the  HEAT or MANU modes     TEMP  Temperature     By pushing the arrows  you will see the current temperature inside the main hot air plenum of your furnace  After two  minutes of inactivity on the keyboard  the display will shut itself off  The TEMP selection has no impact on the  operation of the furnace  It is offered as a practical way for an installer or a technician to quickly obtain the  temperature inside the hot air plenum under the HEAT or MANU modes if a problem arises and the temperature  must be known in order to trouble shoot the furnace     UNIT  measuring unit    By pushing the arrows  you will select the measuring unit that you wish to use  Fahrenheit or Celsius   Thereafter   temperatures will be displayed according to your selection  After two minutes of inactivity on the keyboard  the  display will shut itself off  The UNIT selection has no impact on the operat
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
NEW TECHNOLOGY CATALOG.indd    Sony CFD-S20CP User's Manual  取扱説明書 - 測定器レンタル 株式会社メジャー  MYTHO-EASY - Tablazat.hu  OASIS3-MCT User Guide OASIS3-MCT 1.0  Darci USB Setup - WesTest Engineering  Jura Capresso LP 850 User's Manual  USER MANUAL - Harris Communications  Catálogo PDF - Motos Marin    Copyright © All rights reserved. 
   Failed to retrieve file