1.       A WARNING    FIRE HAZARD  Do not exceed the specified voltage   Replace existing control with exact model and  dash number   Protect the control from direct contact with water   dripping  spraying  rain  etc     Label all wires before disconnection when servic   ing controls  Wiring errors can cause improper  and dangerous operation      Route and secure wiring away from flame     SHOCK HAZARD    Disconnect electric power before servicing     Ensure proper earth grounding of appliance     Ensure proper connection of line neutral and line  hot wires     EXPLOSION HAZARD    Shut off main gas to appliance until installation is  complete     CAUTION    Do not short out terminals on gas valve or primary  control  Short or incorrect wiring may damage the  thermostat        INSTALLATION  MOUNTING AND WIRING    All wiring should be installed according to local and national  electrical codes and ordinances     The control must be secured to an area that will experience a  minimum of vibration and remain below the maximum ambient  temperature rating of 175 F  The control is approved for mini   mum ambient temperatures of  40 F     When mounting the control  any orientation is acceptable   Choose a location that will not damage  obstruct or place stress  on the control s terminations  system wiring harness or system  components  After finding a suitable location  drill four  4  s   holes for mounting control  To ensure proper mounting hole  locations  there is a mounting hole temp
2.  remains locked     In the event of two successive retry attempts  the warm up time  will be unlocked and setto 21 seconds  If flame is then achieved   the warm up time will begin adapting again with the next call for  heat  If  however  this third attempt fails to achieve flame  the  control will go into system lockout     At the end of the ignitor warm up time  both valves in the 36E  manifold gas valve are opened  Flame must be detected within  4 seconds  If flame is detected  the delay to fan on period  begins  After the delay to fan on period ends  the circulator fan  is energized at heat speed  If there is an optional electronic air  cleaner on the system  the electronic air cleaner is also ener   gized  When the thermostat is satisfied  the gas valve is de   energized  After proof of flame loss  the delay to fan off period  begins and the inducer blower remains energized to purge the       System for 5 seconds  When the purge is complete  the inducer  blower and humidifier are de energized  After the delay to fan   off period ends  the circulator fan and electronic air cleaner are  de energized  If flame is not detected  both valves are de   energized  the ignitor is turned off  and the 50A55 control goes  into the    retry    sequence     The  retry  sequence provides a 60 second wait following an  unsuccessful ignition attempt  flame not detected   After this  wait  the ignition sequence is restarted with 2 seconds of ignitor  warm up time  If this ignition attempt i
3.  sense signal    7 flashes  then pause  8 flashes  then pause    The LED will also flash once at power up     MOUNTING HOLE TEMPLATE    MOUNTING HOLE TEMPLATE  FOR MOUNTING HOLE LOCATIONS    4 172    007   2 ples         6 402    010   2 ples      Refer to page 3 of the installation instructions for proper installation     
4. FIER    ELECTRONIC  AIR CLEANER    COMPRESSOR  CONTACTOR    QQ  HIGH L  MIT AUX  HIGH   N  C   LIMIT  N  C      Low Voltage  24 VAC    Line Voltage  120 VAC   N  C    Normally closed switch  N  O    Normally open switch       TYPICAL SYSTEM WIRING TABLE    TERMINAL TYPE CONNECTION  low voltage thermostat W terminal  or equivalent   Terminal low voltage thermostat G terminal  or equivalent   block with low voltage thermostat R terminal  or equivalent     captive low voltage thermostat Y terminal  or equivalent   screws  2nd wire from Y terminal goes to 24 VAC HOT side of    compressor contactor coil   24 VAC COMMON side of compressor contactor coil  MV  2 terminals  gas valve  both gas solenoids are connected in parallel   TR 24 VAC transformer  low voltage COMMON side   TH 24 VAC transformer  low voltage HIGH side   FP 12 pin flame sensor probe   PS connector pressure switch INPUT  HLI  amp  harness high limit INPUT  HLO high limit OUTPUT  GND MUST BE RELIABLY GROUNDED TO CHASSIS   3 unused terminals   inducer HOT side  4 pin ignitor HOT side  connector   inducer NEUTRAL side   amp  harness n    ignitor NEUTRAL side    input voltage  120 VAC  HOT side  circulator blower NEUTRAL terminal  input voltage  120 VAC  NEUTRAL side  electronic air cleaner NEUTRAL side      maximum recommended flame probe wire length is 36 inches        OPERATION  OPTION SWITCHES    The option switches on the 50A55 438 control are used to  determine the length of the cool delay to fan off and heat del
5. WHITE RODGERS    50A55 438    Integrated Furnace Control    INSTALLATION INSTRUCTIONS       Operator  Save these instructions for future use     FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE  INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL  INJURY AND OR PROPERTY DAMAGE     The 50A55 438 is an automatic gas interrupted ignition control  that employs a microprocessor to continually monitor  analyze   and control the proper operation of the gas burner  inducer  and  fan     Signals interpreted during continual surveillance of the thermo   stat and flame sensing element initiate automatic ignition of the  burner  sensing of the flame  and system shut off during normal  operation     DESCRIPTION    These controls incorporate system fault analysis for quick gas  flow shut off  coupled with automatic ignition retry upon sensing  a fault correction           Installation should be done by a qualified heating and air  conditioning contractor or licensed electrician     If in doubt about whether your wiring is millivolt  line  or low  voltage  have it inspected by a qualified heating and air condi   tioning contractor or licensed electrician     Do not exceed the specification ratings     All wiring must conform to local and national electrical codes and  ordinances     This control is a precision instrument  and should be handled  carefully  Rough handling or distorting components could cause  the control to malfunction     Following installation or replaceme
6. ay   to fan off periods  The following tables show the time periods  that will result from the various switch positions     OPTION SWITCH POSITIONS    COOL delay   to fan off     0 sec   80 sec     Set switch  to fan off   2  3  60 sec   100 sec   140 sec     180 sec        HEAT MODE    In a typical system  a call for heat is initiated by closing the  thermostat contacts  This starts the 50A55 control   s heating  sequence  The inducer blower and optional humidifier are  energized and the ignitor is powered within one second     These controls have an adaptive algorithm that adjusts the  duration of the ignitor warm up for the purpose of extending  ignitor life  Upon initial application of power  the warm up time is  17 seconds  The ignitor on time will then be increased or  decreased depending on whether or not flame is achieved  The  warm up time is limited to a maximum of 21 seconds  During the  first 64 warm up periods following power up  the warm up time  may not be less than 17 seconds     Upon a call for heat  if the warm up time has not been locked  it  willbe decreased by one second  This reduction of the ignitor on   time will continue until flame fails to be achieved  resulting in a  retry      In the event of a retry  the warm up time will be increased by two  seconds and locked at that duration  Once the warm up time is  locked  it remains fixed until another call for heat results in a  retry  in which case  the warm up time is again increased by two  seconds and
7. e 24 VAC power at the control for at least one  second  You may also need to reset the flame rollout sensor  switch     3  After one hour in lockout  the control will automatically reset  itself     DIAGNOSTIC FEATURES    The 50A55 control continuously monitors its own operation and  the operation of the system  The LED light on the control will  flash slowly  one flash per second  if there are no failures and no  call for heat  If there is a call for heat  the LED will flash quickly   one flash per half second   If a failure occurs  the LED will  indicate a failure code as shown below  If the failure is internal  to the control  the light will stay on continuously  In this  case  the entire control should be replaced  as the control  is not field repairable  If the LED is continuously off  there may  be no power to the control  the fuse on the control may be open   or there may be a failure in the control     If the sensed failure is in the system  external to the control   the  LED will flash in the following flash pause sequences to indicate  failure status  each flash will last approximately 0 25 seconds   and each pause will last approximately 2 seconds      2 flashes  then pause  3 flashes  then pause  4 flashes  then pause  5 flashes  then pause  6 flashes  then pause    System lockout  no flame   Pressure switch problem   Thermal protection device open  Flame sensed with gas valve off  115 Volt AC power reversed im   proper ground   Gas valve circuit error   Low flame
8. for cool is initiated by closing the  thermostat contacts  This energizes the 50A55 control  The  compressor and optional electronic air cleaner are energized   and the circulator fan is energized at cool speed  After the  thermostat is satisfied  the compressor is de energized and the   optional  cool mode delay to fan off period begins  After the  optional delay to fan off period ends  the circulator fan and  electronic air cleaner  optional  are de energized     MANUAL FAN ON MODE    If the thermostat fan switch is moved to the ON position  the  circulatorfan  heat speed  and optional electronic air cleaner are  energized  When the fan switch is returned to the AUTO posi   tion  the circulator fan and electronic air cleaner  optional  are  de energized     SYSTEM LOCKOUT AND  DIAGNOSTIC FEATURES    SYSTEM LOCKOUT FEATURES    When system lockout occurs  the gas valve is de energized  the  circulator blower is energized at heat speed  and  if flame is  sensed  the inducer blower is energized  The diagnostic indica   tor light will flash or glow continuously to indicate system status    System lockout will never override any precautionary  features      To reset the control after system lockout  do one of the  following     1  Interruptthe call for heat or cool at the thermostat for atleast  one second but less than 20 seconds  if flame is sensed  with the gas valve de energized  interrupting the call for  heat at the thermostat will not reset the control      2  Interrupt th
9. late on page 8 of this  instruction sheet  Detach the page with the template from the  instruction sheet and apply it to the mounting location  When  drilling the holes  take care so that the transformer  wiring  harness or other system components are not damaged  Four  4    8 sheet metal screws are provided to complete the installation     Refer to the wiring diagram and wiring table when connecting  the 50A55 control to other components of the system     UL approved  105  C rated 18 gauge  stranded   4    thick insula   tion wire is recommended for all low voltage safety circuit  connections  Refer to 50A55 specification sheet for recom   mended terminals to mate with those on the control     UL approved  105  C rated 16 gauge min   stranded   4    thick  insulation wire is recommended for all line voltage connections   Refer to 50A55 specification sheet for recommended terminals  to mate with those on the control     The 50A55 has only one serviceable part an automotive type  fuse  which protects the low voltage transformer from damage  if its output is short circuited  If the fuse has opened up  remove  whatever caused the short circuit and replace the fuse with only  a 3 Amp automotive type fuse  If the fuse is not the cause of the  control s problem  replace the entire 50A55 control  There are  no other user serviceable parts     TYPICAL SYSTEM WIRING DIAGRAM    HOT NEUTRAL    LINE LINE      120 VAC l l    24 VAC CLASS II  TRANSFORMER    TH    INDUCER  IGNITOR    HUMIDI
10. lay  1 5 amp  9 25 VAC  50 60 Hz  0 6 pf  Ignitor Relay  6 0 amp  9420 VAC  50 60 Hz   resistive   Flame Current Requirements     Minimum current to insure flame detection  1 ua DC   Maximum current for non detection  0 1 ua DC   Maximum allowable leakage resistance  100 M ohms   Measured with a DC microammeter in the flame probe lead  OPERATING TEMPERATURE RANGE    40  to 175  F   40  to 80  C   HUMIDITY RANGE   5  to 93  relative humidity  non condensing     MOUNTING   Surface mount multipoise    TIMING SPECS     60 Hz       maximum  Flame Establishing Time  0 8 sec  Flame Failure Response Time  2 0 sec       At 50 Hz  all timing specifications should be increased by  20      Gases Approved  Natural  Manufactured  Mixed  Liquefied  Petroleum  and LP Gas Air Mixtures are all approved for use     TIMING SPECIFICATIONS   All times are in seconds  unless noted otherwise     PRE PURGE    TRIAL FOR IGNITION  PERIOD    IGNITION ACTIVATION    PERIOD  RETRIES    VALVE SEQUENCE  PERIOD    INTERPURGE  POST PURGE  LOCKOUT TIME  DELAY TO HEAT ON    DELAY TO HEAT OFF    DELAY TO COOL ON  DELAY TO COOL OFF    MINIMUM IGNITOR  WARM UP    MAXIMUM IGNITOR  WARM UP    INITIAL IGNITOR WARM     UP  1st 64 attempts   HUMIDIFIER    ELECTRONIC AIR  CLEANER       50A55 438    45  140 180     11  ES      These times will vary depending on option switch position   The control is factory set at 0 sec  delay to cool off and 100  sec  delay to heat off  See OPERATION section for further    information  
11. nt  follow manufacturer s  recommended installation service instructions to ensure proper    CAUTION    Do not short out terminals on gas valve or primary  control  Short or incorrect wiring may damage the  thermostat     CONTENTS    Description  Precautions  Specifications  Installation   Mounting  amp  Wiring  Operation  Mounting Hole Template    WHITE RODGERS DIVISION  EMERSON ELECTRIC CO    9797 REAVIS ROAD   ST  LOUIS  MISSOURI 63123 5398          Printed in U S A     Failure to comply with the following  warnings could result in personal injury  or property damage     FIRE HAZARD     Do not exceed the specified voltage      Replace existing control with exact model and  dash number   Protect the control from direct contact with water   dripping  spraying  rain  etc     If the control has been in direct contact with water   replace the control   Label all wires before disconnection when servic   ing controls  Wiring errors can cause improper  and dangerous operation   Route and secure wiring away from flame     SHOCK HAZARD    Disconnect electric power before servicing     Ensure proper earth grounding of appliance     Ensure proper connection of line neutral and line  hot wires     EXPLOSION HAZARD    Shut off main gas to appliance until installation is  complete        PART NO  37 6102B  Replaces 37 6102A  0009    SPECIFICATIONS    ELECTRICAL RATINGS    77  F  25 C     Input Voltage  25 VAC  50 60 Hz  Max  Input Current   25 VAC  0 45 amp  Relay Load Ratings   Valve Re
12. s unsuccessful  one more  retry will be made before the control goes into system lockout     If flame is detected  then lost  the 50A55 control will repeat the  initial ignition sequence for a total of ten  recycles   After ten  unsuccessful  recycle  attempts  the control will go into system  lockout     If flame is established for more than 10 seconds after ignition   the 50A55 controller will clear the ignition attempt  or retry   counter  If flame is lost after 10 seconds  it will restart the ignition  sequence  This can occur a maximum of 11 times before system  lockout     During burner operation  a momentary loss of power of 50  milliseconds or longer will de energize the main gas valve   When power is restored  the gas valve will remain de energized  and a restart of the ignition sequence will begin immediately     A momentary loss of gas supply  flame blowout  or a shorted or  open condition in the flame probe circuit will be sensed within 2 0  seconds  The gas valve will de energize and the control will  restartthe ignition sequence  A recycle will begin and the burner  will operate normally if the gas supply returns  or the fault  condition is corrected  before the last ignition attempt  Other   wise  the control will go into system lockout     If the control has gone into system lockout  it may be possible to  reset the control by a momentary power interruption of one  second or longer  Refer to SYSTEM LOCKOUT FEATURES     COOL MODE    In a typical system  a call 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Samsung RT29FBRNDSP User Manual  model: dry 800 & 1200 metal wall  Smartek USA ST-1200 iron  NSD Gyroscopic Hand, Wrist, and Forearm  Oxa-Flor  User Manual  WEU WEU AXT RAPID - Tooled    Atlantis Land A04-HM-CV025 video converter  Sitecom Wireless Network Omni Antenna 5dBi    Copyright © All rights reserved. 