Home
Vermont Casting 2465 Indoor Fireplace User Manual
Contents
1. 3 2 a c D gt o fo Q fe x at De 2a 3 8 25 cs 3 x8 C GS 2a ts Do gt O gej 2 n oO oO 2 High Elevations Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4 500 feet 1 370m above sea level For elevations above 4 500 feet 1 370m in USA installations must be in accordance with the current ANSI Z223 1 NFPA 54 and or local codes having jurisdiction In Canada please consult provincial and or local authorities having jurisdiction for installations at elevations above 4 500 feet 1 370m SCF NW HR ADH OO WARNING Improper installation adjustment alteration service or maintenance can cause in jury or property damage Refer to this manual for correct installation and operational procedures For assistance or additional information consult a qualified installer service agency or the gas supplier ble Venting uratio o n WORT DN OO 12 3 4 5 6 7 8 9 10 11 12 13 14 15 8 19 20 Horizontal Run in feet ST134a Fig 7 Horizontal vent termination window 30001935 7 Dutchwest Direct Vent Natural Vent Gas Heater Vertical Termination Direct Vent ONLY A vertical vent system must terminate no less t
2. Trim Collar Wall Plate Fig 26 Install the horizontal pipe and wall plate parts 10 For both CFM and DuraVent Systems Install the vent terminal Fig 27 Apply high temperature seal ant one inch from the ends of the inner and outer collars Guide the inner and outer vent termination collars into the adjacent pipes Double check that the vent pipes overlap the collars by 2 Fasten the termination to the wall with the screws provided and caulk the joint with weatherproof sealant 11 For CFM only Install Charcoal Gray Pipe Rings 7FSDRG or Polished Brass Pipe Rings 7FS DRP at pipe joints if desired Seal Both Terminal Ends Caulk Plate Joint with Weatherproof Sealant Fig 27 Install the vent terminal 30001935 Vent Termination Below Grade Install Snorkel Kit 7FSDVSKS when it is not possible to meet the required vent termination clearances of 12 305mm above grade level The snorkel kit will allow installation depth of down to 7 178mm below grade level The seven inches is measured from the center of the horizontal vent pipe as it penetrates the wall If the venting system is installed below grade a window well must be installed with adequate and proper drainage Fig 28 NOTE Be sure to maintain side wall clearances and vent run restrictions Refer to Figures 3 4 7 and 8 1 Establi
3. Direct Vent ONLY Approved Vent System Components The Dutchwest Heater must be vented to the outdoors through an adjacent exterior wall or through the roof The venting system must be comprised of the appropriate listed venting components specified on this page These parts are available from DuraVent Corporation or your CFM Corporation Dealer Refer to Figure 4 for dimensions relevant to the standard minimum vent kits Simpson DuraVent Components Minimum Horizontal Vent Kit 2792 Starter Pipe Assembly incl inner amp outer sections 2768 90 Elbow BIk 990B 45 Elbow Gal 945 6 Straight Blk 908B 9 Straight Blk 907B 11 14B Adjustable Straight Section 911B 12 Straight 906 24 Straight 904B 36 Straight 903B 48 Straight 902 Horizontal Vent Cap 984 Wall Plate 940 Vinyl Siding Shield 950 Snorkel Termination 14 982 Snorkel Termination 36 981 Wall Strap 988 Cathedral Ceiling Support Box 941 Storm Collar 953 Firestop Spacer 963 Flashing 0 12 6 12 943 Flashing 6 12 12 12 943S Steel Chimney Kit A 931 Kit B 932 Kit C 933 Masonry Chimney Kit 934 Vertical Termination Cap High Wind 991 Vertical Termination Cap Low Profile 980 Included in Minimum Horizontal Vent Kit 2792 All DuraVent Straight vent pipe sections have a net length 11 37mm less than the nominal dimension i e a 6 152mm Straight pipe section has an effective length of 41 2 115mm CFM
4. GAS VALVES Gas valves are covered for a period of one year ELECTRONIC AND MECHANICAL COMPONENTS Electronic and mechanical components of the burner assembly are covered for one year All steel tube burners are warranted for one year ACCESSORIES Unless otherwise noted all components and CFM Corporation company supplied accessories are covered for a period of one year CONDITIONS AND LIMITATIONS e This new Dutchwest product must be installed by a competent authorized service contractor A licensed technician as prescribed by the local jurisdiction must perform any installation service work It must be installed and operated at all times in accordance with the Installation and Operating instructions furnished with the product Any alteration willful abuse accident or misuse of the product shall nullify this warranty e This warranty is non transferable and is made to the original owner provided that the purchase was made through an authorized supplier of the Company e The customer must pay for any Authorized Dealer in home travel fees or service charges for in home repair work It is the dealers op tion whether the repair work will be done in the customer s home or in the dealer s shop e If upon inspection the damage is found to be the fault of the manu facturer repairs will be authorized at no charge to the customer parts and or labor 30001935 Any part and or component replaced under the provisions of this
5. 1 Contact your supplier Make sure you have your warranty your sales receipt and the model serial number of your CFM Corpo ration product 2 DO NOT ATTEMPT TO DO ANY SERVICE WORK YOURSELF 35 ENER UIDE Look for the EnerGuide Gas Fireplace Energy Efficiency Rating in this brochure Based on CSA P 4 1 02 Efficiency Ratings Model EnerGuide Ratings Fireplace Efficiency 2465 2466 NATIONAL We recommend that our gas FIREPLACE INSTITUTE hearth products be installed NFI and serviced by profes sionals who are certified in the U S by the National Fireplace Institute NFI as CERTIFIED NFI Gas Specialists www nficertified org CFM Corporation 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com
6. 7533113 19 Electrode Ignitor w Cable SIT24 10001297 20 Nut Electrode SIT 0 974 144 57886 21 Tubing Pilot w Fittings 1 8 x 24 10001296 22 Burner Housing Assembly NG LP 20002214 23 Grate Burner JDV 20002167 24 _Ashdoor Handle Assy E V WSI 5004241 25 Handle Damper Maple Wood Blk 1600664 26 Switch ON OFF RN RP Models 30000874 27 Wiring Harness FSDV32 RN JDV 10002582 28 Right Log Bracket 20005259 29 Left Log Bracket 20005258 30 Nut Hex Jam 3 8 16 TOPLK Z 1203290 31 Gasket Base Pan JDV 20002282 32 Gasket Base Pan Inner 20002566 33 Furnace Cement 1206150 34 Gasket HE Door 1203687 35 Sensor 2450 CMG 8184 0032 10002013 36 Pan Hd SL 1 4 20 x 3 Z 1201310 37a Valve Nova SIT820 662 RN Serial s starting with 6414 20010563 37b Valve Nova SIT820 653 RP Serial s starting with 6414 20010645 38 _Ignitor Piezo w Nut SIT 52464 39 Bracket Piezo Ignitor not shown 20010876 When converting to SIT valve must order RP275 When converting to SIT valve must order RP269 Fuel Conversion Kits Conversion Kit NG to LP 2465 Kit 000 5022 Conversion Kit LP to NG 2466 Kit 000 5021 30001935 33 Dutchwest Direct Vent Natural Vent Gas Heater Optional Accessories FK26 Fan The FK26 fan helps distribute heated air from within the firebox out into the room The fan is controlled by a snapstat that turns power on and off as the firebox tem perature rises above and falls below a preset tempera t
7. Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand do not try to repair it call a qualified service technician Applying force or any attempted repair may result in a fire or explosion Do not use this fireplace if any part has been under water Immediately call a qualified service techni cian to inspect the heater and to replace any part of the control system and any gas control which has been under water Lighting Instructions STOP Read the safety information above Turn off all electrical power to the fireplace For MN MP TN TP appliances ONLY go on to Step 4 For RN RP appliances turn the ON OFF switch to OFF position or set thermostat to lowest level Open control access panel Push in gas control knob slightly and turn clock wise to OFF Euro SIT SIT NOVA Honeywell Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety infor mation above If you do not smell gas go to the next step Remove glass door before lighting pilot See Glass Frame Removal section Visibly locate pilot by the main burner Turn knob on gas control counterclockwise sT to PILOT 10 Push the control knob all the way in and hold Immediately light the pilot by repeatedly depress ing the piezo spark ignitor until a flame appears Continue to
8. Wall Plate 1219 Fig 29 Use extension brackets to mount snorkel against recessed wall Vertical Through the Roof Vent Assembly Note that all vertically terminated installations must in clude the restrictor plate included with the stove Refer to Figure 8 Page 8 Make certain the vent system conforms to all other requirements for vertical termination as specified on Page 8 This installation will require you to first determine the roof pitch and use the appropriate vent components Refer to Figures 8 and 9 on Pages 8 and 10 1 Locate the final position of the stove observing all clearances for both the vent and the stove 2 Plumb to the center of the inner 4 flue collar from the ceiling above and mark that location 3 Cut the opening CFM System 9 x 9 240mm x 240mm DuraVent System 10 x 10 254mm x 254mm 4 Plumb any additional opening through the roof or other construction that may be needed In all cases the opening must provide a minimum of 1 25mm clearance to the vent pipe 5 Place the stove in its final position 6 Install firestop s 7DVFS and Attic Insulation Shield 7DVAIS as needed Fig 30 If there is a room above ceiling level a firestop must be installed on both the bottom and top sides of the ceiling joists If an attic is above ceiling level an attic insulation shield must be installed 7 Install the appropriate roof support and flashing making
9. the wallpaper to shrink or may adversely affect the binders in the wallpaper adhesive 30001935 Direct Vent System Only D Cross Corner E Flat on wall A Flat on corner wall B Room Divider C Island Sh Fig 2 Possible stove locations Clearance Requirements Minimum Clearances to Combustible Materials Measure side clearances as shown in Figures 5 and 6 from the outer edge of the cast iron stove top Measure rear clearances from the outermost surface of the steel rear skirt The Dutchwest heater is approved for installation into an alcove constructed of combustible materials to the dimensions and clearances shown on the next page The same clearances apply in a standard parallel instal lation Warning Always maintain required clear ances air spaces to nearby combustibles to prevent fire hazard Do not fill air spaces with insulation All venting components must maintain a 1 25mm clearance to combustible materials Maintain a 6 150mm clearance when using a single wall pipe The gas appliance and vent system must be vent ed directly to the outside of the building and never be attached to a chimney serving a separate solid fuel or gas burning appliance Each direct vent appliance must use its own separate vent system Common vents are prohibited Refer to the manufacturer s instructions included with the venting system for complete installation procedures Dutchwest Direct Ven
10. Corporation reserves the right to make changes in design materials specifications prices and discontinue colors and products at any time without notice Dutchwest Direct Vent Natural Vent Gas Heater Models 2465 2466 Ref Description Dutchwest 1 Gas Log Assembly SDV30 20003458 1a Rear Log 20003459 1b Right Log 20003460 1c Left Log 20003461 2 Small Lava Rock Package 57897 3 Top DV DW Gas 30001925 4 Front DW Gas 30001928 5 Door DW Gas 30001929 6 End Rt DW Gas 30001927 7 End Lt DW Gas 30001926 8 Leg DW Gas 30001930 9 Manifold Assembly 20003739 32 30001935 Dutchwest Direct Vent Natural Vent Gas Heater Dutchwest Direct Vent Natural Vent Gas Heater Models 2465 2466 continued Ref Description Dutchwest 10 Glass DV25 1601691 11 __Glass Frame Assembly SDV30 30000127 12 Gasket Glass Med Knit RDV40 1203702 13a Valve RN Honeywell VS8420E 2038 Serial s up to 6413 10001782 13b Valve RP Honeywell VS8420E 2020 Serial s up to 6413 10001759 14 Pilot Top Convertible 10002266 15a Pilot Assembly 3Way N DV RN 0 199 706 10002264 Pilot Assembly 3Way N DV RP 0 199 703 10002265 15b Pilot PSE NA175 20001115 Pilot PSE LP175 20001116 16a Orifice Hood 69 Front LP 30000513 16b Orifice Hood 54 Front NG 20000130 16c Orifice Hood 54 Rear LP 20000130 16d Orifice Hood 44 Rear NG 30000334 17 Thermocouple 24 53373 7531137 18 Thermopile 18 RS 51827
11. If pilot lights turn off pilot trode at the pilot and push the ignitor button again If pilot will not light check gap at electrode and pilot it should be 1 8 to have a strong spark B Defective ignitor push button Push piezo ignitor button Check for spark at elec trode and pilot If there is no spark at the pilot and electrode wire is properly connected replace ignitor A Defective pilot generator ther Check pilot flame It must impinge on the thermo Pilot will not stay lit mocouple couple or thermopile NOTE This pilot burner as after carefully fol sembly uses both a thermocouple and a thermopile lowing the lighting The thermocouple operates the pilot flame Tighten instructions the thermocouple The thermopile operates the main valve ON and OFF Clean and or adjust pilot for maximum flame impingement on thermocouple and thermopile B Defective automatic valve op Turn valve knob to Pilot Maintain flow to pilot mil erator livolt meter should read greater than 10mV If the reading is okay and the pilot does not stay on re place the gas valve NOTE An interrupter block not supplied must be used to conduct this test Pilot lights no gas to A Remote switch or wires defec Check rocker switch and wires for proper connection burner valve knob Use jumper wires across terminals at rocker switch ON remote switch If burner lights replace rocker switch If okay use rocker switch ON jumper wires acr
12. ON OFF Switch The switch assembly parts are found in the parts bag 1 Attach switch assembly to left rear side of stove shroud when facing shroud using two screws and existing holes in shroud Fig 41 Run wires down back of stove under bottom of rear shroud to valve Attach wires to valve terminals Fig 42 N wo Switch Assembly Existing Holes Fig 42 Attach switch wires to valve 21 Dutchwest Direct Vent Natural Vent Gas Heater Thermostat Connection optional Use only a thermostat rated for 500 millivolts Check the table below for the appropriate gauge ther mostat wire to use for the length of lead required in your installation Thermostat Wire Gauge Maximum Run 18 20 feet 16 20 40 feet 14 up to 60 feet Install the wall thermostat in the desired location and run the wires to the stove location Terminate these leads with 1 4 female connectors Connect the thermostat wires to the valve Fig 42 Install the Stove Front Insert the handle stub into the hole in the front casting Fasten in place witht he 3 8 locking nut provided Fig 43 The front attaches to the stove by four steel tabs that engage with corresponding cast ribs onto the sides and bottom of the stove body Position the front about 3 down from stove top and lift the plate to engage the upper tabs behind the adjacent ribs on the sides Fig 44 Then
13. Termination It is imperative the vent termination be located observ ing the minimum clearances as shown on this page Dutchwest Direct Vent Natural Vent Gas Heater General Venting Information Termination Location INSIDE CORNER DETAIL VENT TERMINATION AIR SUPPLY INLET AREA WHERE TERMINAL IS NOT PERMITTED Canadian Installations US Installations A Clearance above grade veranda porch 2 30cm 2 30cm deck or balcony 1 1 B Clearance to window or door that may be 6 15cm for appliances 6 15cm for appliances opened lt 10 000Btuh 3kW 12 30cm lt 10 000 Btuh 3kW 9 for appliances gt 10 000 Btuh 3kW and 23cm for appliances gt 10 000 lt 100 000 Btuh 30kW 36 91cm Btuh 3kW and lt 50 000 Btuh for appliances gt 100 000 Btuh 30kW 15kW 12 30cm for appliances gt 50 000 Btuh 15kW C Clearance to permanently closed window 12 305mm recommended to 12 305mm recommended to prevent window condensation prevent window condensation D Vertical clearance to ventilated soffit located above the terminal within a horizontal 18 458mm 18 458mm distance of 2 feet 610mm from the center line of the terminal E Clearance to unventilated soffit 12 305mm 12 305mm F Clearance to outside corner G Clearance to inside corner see next page H Clearance to each inside of center line 3 91cm within a heigh
14. Vent Components The following kits are available to meet the needs of most installations All pipe has a 7 outer diameter and includes a 4 diameter inner section A CG designation indicates the part is finished in Charcoal Gray paint Consult your dealer about other vent parts that may be appropriate to complete the installation Min Through the Wall Vent Kit 1 90 Degree Elbow CG 1 24 Straight pipe CG 1 36 Straight pipe CG 1 Side Wall Termination 1 Firestop 1 Zero clearance sleeve 1 Hardware package 12 7TFSMSK Ye rye re wv wv wH 1 Finishing plate CG 1 Finishing collar CG 4 Polished Brass flue pipe rings Through the Wall Vent Kit 90 Degree Elbow CG 24 Straight pipe CG 48 Straight pipe CG Side Wall Termination 1 1 1 1 1 Firestop 1 1 1 1 7TFSDVSK Zero clearance sleeve Hardware package Finishing plate CG Finishing collar CG 4 Polished Brass flue pipe rings Through the Wall Vent Kit for Below Grade Termination Includes all of the above parts plus 1 Snorkel Termination Vertical Termination Kit 1 12 6 12 Pitch 1 Combination Horizontal Offset Roof Support 1 Vertical Termination Storm Collar 1 12 6 12 Flashing Finishing Plate CG 7TFSDVSKS 7TDVSKVA Finishing Collar CG Polished Brass Flue Pipe Ring Hardware Package Vertical Termination Kit 7 12 12 12 Pitch 1 7 12 12 12 Flashing and all o
15. Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Proposition 65 Warning Fuels used in gas woodburn ing or oil fired appliances and the products of combustion of such fuels contain chemicals known to the State of Cali fornia to cause cancer birth defects and other reproductive harm California Health amp Safety Code Sec 25249 6 Aftermarket Completion of sale nor for purpose of resale from the manufacturer Dutchwest Direct Vent Natural Vent Gas Heater Dutchwest Direct Vent Natural Vent Dimensions Refer to Page 6 for Flue Collar Centerline Dimensions Valve 43 Inlet 111mm T R E 318mm 17 419mm Fig 1 Dutchwest dimensions Attention The Dutchwest stove is shipped from the factory as a Direct Vent Gas Heater This heater may be convert ed into a Natural Vent unit in the field If a Natural Vent heater is desired the Z31D00 FSDHAG Draft Hood must be directly installed to the top of the unit according to the installation instructions The Draft Hood Adapter is available in the 7FSDHASK stove kit or as a separate item When the Dutchwest stove is converted to Natural Vent it uses 4 vent pipe For aesthetic purposes the CFM direct vent system may be used up to the ceiling 4 30001935 Dutchwest Direct Vent Natural Vent Gas Heater Installation Requirements The install
16. hearth There are no other hearth requirements 30001935 Dutchwest Direct Vent Natural Vent Gas Heater Gas Specifications Horizontal Termination Max Min Direct Vent ONLY Input Input The vent must rise vertically a minimum of 24 610mm Gas Control BTU h BTU h off the top of the unit before the first elbow The hori 2465 Millivolt 28 000 20 000 zontal run may extend up to 20 6m and include a 2466 Millivolt 28 000 19 000 vertical rise of up to 40 12m Fig 7 Horizontal termination must also meet the criteria shown in Figures Weight Fully assembled 202 Ibs 9 through 11 Gas Inlet and Manifold Pressures e Approved vent systems must terminate above and including the heavy line in Figure 7 PO Natural LP Propane e Two 45 elbows may be substituted for each single Inlet Minimum 90 elbow Inlet Maximum e With arise between 2 5 one 90 or two 45 el Manifold Pressure 3 5 W C 10 0 w c bows may be used Certified to ANSI Z21 88 2005 CSA 2 33 2005 Vented Gas Fireplace Heaters The installation of your Dutchwest stove must conform with local codes or in the absence of lo cal codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition or CSA B149 1 Installation code EXCEPTION Do not derate this appliance for altitude up to 4 500 feet 1 370m Maintain the manifold pressure at 3 5 w c for Natural Gas and 10 0 w c for LP Gas
17. hold the control knob in for about one 1 minute after the pilot is lit Release knob and it will pop back up Pilot should remain lit If it goes out repeat steps 5 through 8 If knob does not pop up when released stop and immediately call your service technician or gas supplier If after several tries the pilot will not stay lit turn the gas control knob to OFF and call your service technician or gas supplier 11 Replace glass door 12 Turn gas control knob to ON position 13 For RN RP appliances turn the ON OFF switch to ON position or set thermostat to desired setting 14 Turn on all electrical power to the fireplace To Turn Off Gas To Heater Turn the ON OFF switch to Off position or set the thermostat to lowest setting Turn off all electric power to the fireplace if service is to be performed 24 Open control access panel Push in gas control knob slightly and turn clock wise to OFF Do not force Close control access panel 30001935 Dutchwest Direct Vent Natural Vent Gas Heater Troubleshooting Honeywell 8420 Gas Control System NOTE Before troubleshooting the gas control system be sure the external gas shutoff is in the ON position WARNING REMOVE THE GLASS PANEL BEFORE PERFORMING ANY GAS CONTROL SERVICE WORK SYMPTOM POSSIBLE CAUSES CORRECTIVE ACTION 1 Spark ignitor will not A Defective or misaligned elec Using a match light pilot
18. of the glass frame all around the perimeter Place the flat gasketed side of the glass panel back into the steel frame Pinch the rounded inside facing gasket material to bulk it up 5 Replace the glass frame and front panel as previ ously described Fig 60 Wrap the gasket material around the outside edge of the glass Inspect the Vent System Annually Have the vent system inspected annually by a qualified technician Shut off the main gas supply before inspect ing the system Both the inner exhaust pipe and the out er combustion supply pipe must be checked to confirm that they are unblocked and in good condition 30 Check the Gas Flame Regularly To ensure that the stove is operating properly check the flames periodically to confirms they match Figure 61 The flames will be blue during the first 15 20 minutes of operation and will gradually turn to yellow after that Do not use your stove if the flame pattern differs from that shown here Contact your dealer or a qualified technician for help Fig 61 Correct flame pattern Stove Disassembly If there is ever a need to remove the firebox assem bly from the stove shell support the firebox with solid stands about 6 150mm tall under the left and right outer edges of the firebox base Do not set the firebox assembly directly on the floor this can damage the control valve and or the gas lines from the valve to the firebox Before removing the firebox from
19. should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition Young children should be carefully supervised when they are in the same room as the appliance Clothing or other flammable materials should not be placed on or near the appliance Any safety screen glass or guard removed for servic ing an appliance must be replaced prior to operating the appliance The appliance area must be kept clear and free from combustible materials gasoline and other flammable vapors and liquids The flow of combustion and ventilation air must not be obstructed The installation must include adequate accessibility and clearance for servicing and proper operation WARNING Do not operate the Room Heater with the glass panel removed cracked or broken Replacement of the panel should be done by a licensed or qualified service person Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water Do not burn wood trash or any other material for which this appliance was not designed This appliance is designed to burn either natural gas or propane only This gas appliance must not be connected to a chim ney flue serving a separate solid fuel burning appliance CAUTION Label all wires prior to disconnection when servicing controls
20. the restrictor plate is needed If so put the restrictor plate in place within the inner flue collar as shown in Figure 16 Fig 16 Install the restrictor plate only if required for the vent ing configuration Refer to Page 8 2 Attach Inner Starter Pipe found in with the logset to the next section of inner pipe e Run a bead of sealant about 1 2 from the upper end of the Inner starter pipe and join the two sec tions together e Drill three pilot holes into the Inner Starter and secure the assembly with three sheet metal screws Fig 17 3 Dry fit the Outer pipe assembly to the stove for the purpose of determining the center line of the pipe on the wall e Side Wall Terminations Dry fit the outer elbow with the vertical outer vent and confirm the centerline alignment with the wall thimble opening Remove the pipes and elbows before continuing with Step 4 4 Attach the Inner Vent Assembly to the stove e Run a bead of sealant around the bottom end of the starter pipe and attach the assembly to the stove using three 1 4 20 x 3 8 Phillips screws provided in the parts bag Fig 18 14 5 Install the Outer Adapter Pipe Apply a 1 4 bead of cement around the inside wall of the pipe about 1 from the end Insert the pipe over the stove flue collar keeping the vertical seam oriented to the back of the stove Also be sure to align holes on the pipe with the holes on the flue collar of the firebox Faste
21. the shell disconnect the on off switch wires from the valve If the assembly includes the optional fan disconnect the fan rheostat If the installation includes a wall thermostat disconnect the thermostat leads from valve Disconnection and reconnection to the gas line should only be done by a qualified gas service technician Upon reinstallation the vent system must be sealed to the firebox as shown in the installation section Page 16 Also be sure the logs are placed in the firebox cor rectly as shown in Figures 34 amp 35 Page 20 30001935 Wiring Diagrams On Off Switch Wiring ae rd iy Thermopile i ST124b Optional Thermostat Thermostat a Optional Wiring Thermopile i ST124c Fig 62 On Off switch and optional thermostat circuit NOTE IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH TYPE SF 2 200 WIRE OR ITS EQUIVALENT Safety Limit Switch hermocouple T E Fig 63 Draft hood adapter wiring 30001935 Dutchwest Direct Vent Natural Vent Gas Heater Chassis Ground FAN JUNCTION BOX Strain Relief ON OFF Rheostat Schematic Diagram SNAPSTAT ON OFF RHEOSTAT Fig 64 Fan circuit 31 Dutchwest Direct Vent Natural Vent Gas Heater CFM
22. warranty is covered for six months or the remainder of the original warranty whichever is longest e This warranty is limited to the repair of or replacement of part s found to be defective in material or workmanship provided that such part s have been subjected to normal conditions of use and service after said defect is confirmed by the Company s inspection e The company may at its discretion fully discharge all obligations with respect to this warranty by refunding the wholesale price of the defective part s Any installation labor construction transportation or other related costs expenses arising from defective part s repair replacement or otherwise of same will not be covered by this warranty nor shall the Company assume responsibility for same Further the Company will not be responsible for any incidental indirect or consequential dam ages except as provided by law SOME STATES DO NOT ALLOW FOR THE EXCLUSION OR LIMI TATIONS OF INCIDENTAL AND CONSEQUENTIAL DAMAGES OR LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOUR CIR CUMSTANCES THIS WARRANTY GIVES YOU SPECIFIC RIGHTS AND YOU MAY HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE All other warranties expressed or implied with respect to the product its components and accessories or any obligations liabilities on the part of the Company are hereby expressly excluded The Company neither assumes n
23. EST 1974 INSTALLER CONSUMER SAFETY INFORMATION PLEASE READ THIS MANUAL BEFORE INSTALLING AND USING APPLIANCE WARNING Direct Vent Natu ral IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY A FIRE OR EXPLO Ve nt G as H eate r SION MAY RESULT CAUSING a PROPERTY DAMAGE PER Models 2465 2466 SONAL INJURY OR LOSS OF LIFE DUTCHWEST BY VERMONT CASTINGS FOR YOUR SAFETY Installation and service must be performed by a qualified installer service agency or the gas supplier WHAT TO DO IF YOU SMELL GAS e Do not try to light any appliance e Do not touch any electric switch do not use any phone in your building e Immediately call your gas supplier from your neighbor s phone Follow the gas suppliers instructions Homeowner s Installation e If you cannot reach your gas supplier call the fire department and Operating Manual DO NOT STORE OR USE GASOLINE OR OTHER FLAM MABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE This appliance may be installed in an after market permanently located manufactured mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certified kit is used 30001935 1 07 Rev 11 Dutchwest Direct Vent Natural Vent Gas Heater Ble Meym Clo EL PLEASE READ THE INSTALLA
24. FM Corporation approved parts Refer to Page 32 for Replacement Parts Refer to Figure 58 and previous instructions for removal of the damaged glass frame ST771a Fig 59 Release the latches to release the glass frame 29 Dutchwest Direct Vent Natural Vent Gas Heater Gasket Replacement The Dutchwest Gas Heater uses a tadpole type gasket to seal between the glass panel and the frame In time this gasket can become brittle and compressed and should be replaced New gasket is available from your dealer Shut off the gas supply and allow the stove to cool Wear safety goggles and a dust mask 1 Remove the Front Glass Frame and Glass Panel Figs 56 amp 57 Remove the old gasket Use a razor blade to separate the glass and gasket from the frame and to clean the glass of any remaining cement or bits of gasket Use a cold chisel if neces sary 2 Determine the correct length of gasket by laying it out around the edge of the glass Allow an extra 1 2 25 50 mm Mark the spot to be cut Use a utility knife 3 Starting on a long edge remove about 6 of the pro tective paper strip and apply the flat adhesive face of the gasket around the outside facing edge of the panel Continue around the panel applying a bout 6 at a time and being careful to not stretch the mate rial Do not overlap the gasket ends Fig 60 4 Apply a thin bead of high temperature silicone rubber sealant along the inside corner
25. Regularly 0 c cccceeceeeceeeeeeeeeeeeeeeeeeceeeeeeeeeceeeeeeeeeseneeeeeeneees 30 Stove DiSaSSeMDIy sis iedesceidees hs cach eon aa a aaa an ae ene AEE aE PA E SEER 30 Wirmo Diagram en e E e E E EE ES 31 Replacement Parts irinin ere eae oe eir ia aaeei aiai ees bie dan Saara Nesie 32 Optional Accessories cece ccccceeesetstceeeeceeeeeeeeeeeeeeeeeeesseseceeeeeeessaeasaaeeeeaeeeeeeeeeeeeeeeseeeeees 34 Warranty scenen ertean nane tka tet des aaa aan aar aad a arra aean aeaea Eea eae as 35 E erguid sAn ie a A OA A A eee 36 2 30001935 Dutchwest Direct Vent Natural Vent Gas Heater General Information The Dutchwest Direct Vent Natural Vent Room Heater Model Nos 3070 3071 3072 and 3073 is a vented gas appliance listed to the ANSI standard Z21 88b 2001 and CSA 2 33b 2001 for Vented Room Heaters and CSA 2 17 M91 Gas Fired Appliances For Use at High Altitudes The installation of the Dutchwest Direct Vent Natural Vent Room Heater must conform with local codes or in the absence of local codes with National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition and CSA B 149 1 Instal lation Code EXCEPTION Do not derate this appliance for altitude Maintain the manifold pressure at 3 5 w c for Natural Gas and 10 0 w c for LP gas at maximum input This appliance is only for use with the type of gas indicat ed on the rating plate This appliance is not convertible for use with other gases unless
26. TION amp OPERATING INSTRUCTIONS BEFORE USING APPLIANCE Thank you and congratulations on your purchase of a Dutchwest stove IMPORTANT Read all instructions and warnings carefully before starting installation Failure to follow these instructions may result in a possible fire hazard and will void the warranty Installation amp Operating Instructions 0 ccccccccc cece eeeeee cece eteceeeeeeeeeceaaeeeeeeetaaeeeeeeteneneees 3 STOVE DIMENSIONS is d heise sicesae ccshn dente sceennedesadsieQedsacenedsoneasadhaeaieccadansaceelssiedeseeqeersieereunsensed 4 Installation Requirement ccccccccceeeeeeeeeeeeeeeeeeeeeeeeseeceeeeeeeeeeaaeeeeesseeeeeeeeeeeneeneees 5 Locating th StoVe isise inaia e Nia OE aaa EVSEN aa a AiE 5 Clearance Requirements sieneen i i r E Ea 5 Parallel amp Corner Installation c2 c c ecceiedege cseesenedatiesscnecenscceedednoeeaaeseenedeenessenecsceceenietes 6 Wall and Ceiling Clearances c ccccecececceeeeeeeeceeeeeeeeeecaeeeeeeseecneeeeeeeseneaeeeeeeseeneneeeeess 6 Hearth REQUIREMENTS 3 sse inaina aaea aana dedee a aar a aa aa Rea a ideata 6 Gas Specification Senine e E E E EN a E 7 Gas Inlet and Manifold PreSSures 00 ciecceeeeseeteeeeeeeeteeeeeneeeteneeeeeeeeeeeneeeteneeenneeeeea 7 FIGHHEIGVALONS siesscehe czycecerieedssattccctavaadeadinashcacet a eaa E E O ERKA EERE 7 Horizontal Termination Direct Vent ONLY cccceeeeeeeeeeeneeeeeteeeeneeeteneeeeseateesnaees 7 Verti
27. a 90 angle to firebox base after conversion Pilot Orifice CO106b Fig 56 Remove pilot orifice 27 Dutchwest Direct Vent Natural Vent Gas Heater 21 Replace burner Slide the burner in at an angle with left side lower than the right side Slide the left side onto the injectors making sure the burner leg remains at a 90 angle to the base Lower the right hand side down in to place Make sure the burner is as far left as possible and the injector shoulders are inside the burner Left Burner Leg Injector Shoulder NOTE It is very critical to keep the left burner leg which holds the injectors at a 90 angle to the base Fig 57 This keeps the orifices aligned with the tubes inside burner Failure to do so could affect the Fig 57 Be sure to maintain 90 angle at left burner leg flame appearance and performance of the unit 22 Place conversion label on valve 23 Reinstall the right and left log bracket assembly 24 Reinstall the rear log bracket 25 Replace logs 26 Replace glass and stove front Conversion is complete Table 2 Injector Orifice Size Matrix a Ss to Natural Gas Input BTU h Part Rear Part Minimum Maximum eS 5021 54 055 30000514 44 086 30000334 19 000 28 000 aT a ee to LP Input BTU h Part Rear Part Minimum Maximum e 5022 69 029 30000513 54 055 30000514 20 000 28 000 28 30001935 Dutchw
28. a certified kit is used Installation and replacement of gas piping gas utiliza tion equipment or accessories and repair and servicing of equipment shall be performed only by a qualified agency The term qualified agency means any individ ual firm corporation or company that either in person or through a representative is engaged in and is respon sible for a installation or replacement of gas piping or b the connection installation repair or servicing of equipment who is experienced in such work familiar with all precautions required and has complied with all the requirements of the authority having jurisdiction The Dutchwest Direct Vent Natural Vent Room Heater should be inspected before use and at least annually by a qualified service agency It is imperative that control compartments burners and circulating air passage ways of the appliance be kept clean The Dutchwest Direct Vent Natural Vent Room Heater and its individual shut off valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1 2 psig 3 5 kPa The Dutchwest Direct Vent Natural Vent Room Heater must be isolated from the gas supply piping system by clos ing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig Direct Vent describes a sealed combustion system in which incoming outsid
29. arances When planning the installation consider the location of the vent terminal and clearances Some of the most common clearances to keep in mind are shown in Fig ure 10 Important All vent clearances must be maintained Check your vent termination clearances against Figures 9 through 11 The vent should be placed so that people cannot be burned by accidentally touching the vent surfaces when the stove is operating The vent termination should be located where it cannot be damaged by such things as automobile doors lawn mowers or snowblowers and it should be located away from areas where it could become blocked by snow etc Some considerations are e Obstructions or impediments to venting e Nearby combustible materials that could come into contact with combustion exhaust gases e Other nearby openings within 12 305mm through which exhaust gas could reenter the building e All vegetation within 3 76mm that may interfere with the draft Other factors that influence where the installation will be sited include the location of outside walls where additional heat may be desired in the home where the family members gather most regularly and perhaps most importantly the distance limitations of the venting system A IMPORTANT Direct Vent Only The horizontal termination must not be recessed into the exterior wall or siding Horizontal vent runs must be level toward the vent termination Clearances ar
30. ation must conform with local codes or in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition EXCEP TION Do not derate this appliance for altitude Main tain the manifold pressure at 3 5 w c for Natural Gas and 10 w c for Propane In Canada installation must be in accordance with the current CSA B 149 1 Installation Codes and or local codes The installation should be done by a qualified ser vice person who is familiar with the building codes and installation techniques appropriate for your area to accomplish a safe and effective installation Your dealer or your local gas supplier will be able to refer a qualified service person WARNING Due to high temperatures the HEATER should be located out of traffic and away from fur niture and draperies The surface of the Heater Is hot when it is in use Young children should be watched carefully when they are in the same room when the Heater is in use and they should be taught to avoid the hot surface Keep any objects that can burn well away from the Heater and observe the recommended clearances that follow Locating the Stove In choosing a location for the stove consider e The location of outside walls e Where additional heat is needed e Where family members gather most often e The vent system requirements NOTE We do not recommend the use of wallpaper next to this stove Over time radiant heat may cause
31. cal Termination Direct Vent ONLY pecs isn srn aria a 8 Vent Termination ClearanCes iecccscscecnccdeeseisceeisye cans i qenaedees seseeadea ia d a ria 8 General Venting Information Termination Location cceceeeeeeeeeeeeeeeeeeeeeeeeeee 10 Termination ClearanCes uiscci agiep arara a aa i 11 Venting Requirements Natural Vent ONLY cceeeeceeeeeeeeeeeeeeeeeeeeeeeneeeeeeeeeneneees 11 Venting Requirements and Options Direct Vent ONLY ssssssssssrsnsssssrrnssrerrnnessrerrnne 12 Install the Optional Fan srice a a E aS 13 Venting System Assembly Direct Vent cccceccceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeenneees 14 Install Vent Adapter Pipe CFM Vent Components cccceeeeeeeeeeeeeteeeeeeteeneeees 14 Install Vent Adapter Pipe Simpson Dura Vent Components eeceeeeeeeteeeeeee 15 Side Wall Termination Assembly cceccceceeeeeceeeeeeeeeeeeeeeeeeeeaeeeeeeeeeeceeeeeeseeneeeeeeess 15 Vent Termination Below Grade sisien sasoina neea 17 Vertical Through the Roof Vent Assembly cccceeeeeeceeeeeeeeeeeeeeeeeeeeeteeeeeeeeeneneees 17 Venting System Assembly Natural Vento ee eeeeeeneeeeeeeeeeeneeeeeneeeetneeeteeeeenaaes 18 Install the Vent Pipe isimi iesene iinne eee asa aini iae e i aaaea 18 Install the Log Setiana aaae aE ened E E a EEEa AREEN 19 Connect Gas Supply LING nerusne n ree ie EEN a EEE asi ks 19 Burner MTOnmMation si asanes a a 20 Air Shutter Adj
32. certain that the upper flange of the flashing base is below the shingles Fig 31 17 Dutchwest Direct Vent Natural Vent Gas Heater 8 Install appropriate pipe sections until the vent run reaches above the flashing The enlarged ends of the vent sections always face downward 9 Install the storm collar and seal around the joints Fig 31 10 Add additional vent lengths to achieve the proper overall height 11 Apply cement to the inner and outer termination col lars and install the terminal cap 7DVAIS Attic Insulation Shield 7DVFS Firestop In Upper Floor Use Four 8d 7DVFS Firestop in Ceiling Fig 30 Install firestops and attic insulation shield Sealant Storm Collar Upper edge of flange goes under upper shingles Flashing 7DVSKV A B of F Roof Support Fig 31 Roof support and flashing 18 Venting System Assembly Natural Vent General Information The Dutchwest Heater is shipped from the factory as a Direct Vent Heater It may be converted to a Natural Vent heater by installing the Model Z31D00 FSDHAG Draft Hood Adapter The Dutchwest Heater is approved for installation as a Natural Vent CFM Direct Vent pipe could be used directly after the Draft Hood Adapter up to the ceiling then B vent pipe must be used Do not mix types of B vent pipe use components from one maker or the other Follow the vent component maker s instruct
33. e Blower Assembly mounts to the bottom rear of the stove and the Rheostat mounts to the valve cov erplate The assembly includes a snapstat which automatically turns the fan On or Off above or below approximately 109 The Rheostat also pro vides a range of fan speed settings from Off which overrides the snapstat function to High Unpack and inspect the Blower assembly Confirm that the fan spins freely WARNING This appliance is equipped with a three prong grounded plug for your protection against shock hazard and should be plugged directly into a prop erly grounded three prong receptacle Do not cut or remove the grounding prong from this plug Not Used on RF Models Snapstat Bracket Snapstat Extension Assembly Rheostat S G Connect to PC Board on RF Models Only Fig 12 Fan kit components 2 Remove the rear skirt insert panel at the bottom of the Rear Skirt Fig 13 and fasten the blower as sembly to the firebox back with the two Phillips pan head bolts originally installed in the firebox back 1 Fig 14 3 Attach the snapstat assembly to the snapstat brack et with two sheet metal screws 2 Fig 14 Attach the snapstat bracket to the stove with a hex head bolt passing through the bracket and into the stove base 3 Fig 14 4 The rheostat control switch attaches to the left side of the valve bracket at the front of the stove 30001935 Dutchwest Direct Ven
34. e Place the assembly out of the way on a flat padded surface such as a coun ter protected by a towel Remove the logset from the firebox Remove the rear log bracket by unfastening the screw Fig 49 Remove the right and left log bracket assembly by unfastening the two screws which hold the burner in place Fig 49 N oO of O Remove Screws Rear Log Bracket Left amp Right Log Bracket Assembly ST768 Fig 49 Remove rear log bracket and left and right log bracket assembly 7 Hold the burner at the right hand side and lift to clear the right burner leg Then pull to the right to clear the injectors on the left hand side 8 Remove injector orifices from left burner leg using 1 2 wrench Fig 55 9 Install conversion orifices Refer to Table 2 Honeywell Valve 1 Remove cap from Hi Lo knob This can be accom plished by lifting the plastic cap off the screw Fig 50 2 Remove the screw from center of Hi Lo knob with small screwdriver turning counterclockwise Fig 50 3 Insert blue painted screw when converting to natural gas and red painted screw when converting to LP 4 Tighten screw do not over tighten replace cap Center Screw Fig 50 Remove center screw from Hi Lo knob SIT 820 Valve 1 Using TORX T20 bit remove and discard the three 3 pressure regulator mounting screws A pressure regulator tower B and the spring and diaphragm assembly C Fig 51 2 I
35. e air for combustion and outgoing exhaust enter and exit through two separate concentric passages within the same sealed vent system The system does not use room air to support combustion The Direct Vent system permits the gas appliance to be vented directly to the outside atmosphere through the side of the house or vertically through the roof Conventional venting systems Natural Vent take air from the room for combustion and vent the exhaust vertically through the roof to the atmo sphere This appliance is approved for bedroom installations in the U S and Canada This appliance may be installed in an aftermarket manu factured mobile home where not prohibited by state or local codes 30001935 WARNING Operation of this heater when not con nected to a properly installed and maintained venting system can result in carbon monoxide CO poisoning and possible death The Dutchwest Direct Vent Natural Vent Room Heater when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 latest edition or of the current Canadian Electrical Code C22 1 Due to high temperatures this appliance should be located out of traffic and away from furniture and drap eries WARNING This appliance is hot while in operation Keep children clothing and furniture away Contact may cause burns or ignition of combustible materials Children and adults
36. enting system used on Direct Vent appliances are certified as part of the appliance with clearances tested and approved by the listing agency 3 CFM Corporation assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements Fig 9 Vent termination clearances 10 30001935 Dutchwest Direct Vent Natural Vent Gas Heater Termination Clearances Termination clearances for buildings with combustible and noncombustible exteriors Inside Corner Outside Corner Alcove Applications F G Combustible Combustible 6 152 mm 6 152 mm Noncombustible 2 51 mm Noncombustible 2 51 mm Balcony Balcony with no side wall with perpendicular side wall E Min 6 152 mm for non vinyl sidewalls Min 12 305 mm for vinyl sidewalls O 8 2 4 m Min FT 6 1 8 m M Combustible amp 9 2 7 M 2 3 x Dyauay Combustible amp ee 12 3 7 m 1 2 x Dy ua Noncombustible M 24 610 mm 20 Dyin Of Termination caps x 3 12 305 mm P 20 508 mm Ce 2 termination caps x Dy i NOTE Termination in an alcove space spaces open only on one side and with an overhang is permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be a 3 914 m
37. est Direct Vent Natural Vent Gas Heater Maintenance Your Dutchwest Gas Heater will provide years of ser vice with minimal upkeep The following procedures will help ensure that your stove continues to function properly Annual System Inspection Have the entire heater and venting system inspected annually by a qualified gas technician Replace any worn or broken parts Logset and Burner Cleaning and Inspection Cleanliness is critical to the proper function of the heater The logset and burner must all be kept free of dust and unobstructed by debris Inspect these areas before each use and clean as necessary 1 Turn the burner OFF and let the heater cool com pletely before cleaning Lift the Stove Front up and then swing the bottom out to disengage it from the heater shell Fig 56 Carefully remove the glass and frame assembly and place it out of the way on a flat padded surface such as a counter protected by a towel Carefully inspect the Logs for damage Contact your local dealer if any damage is evident DO NOT OP ERATE THE HEATER WITH DAMAGED LOGS Use a soft bristled brush to sweep dust or debris from the Logs Pilot and Burner Use care as the logs are fragile and susceptible to damage DO NOT USE A VACUUM TO CLEAN THE LOGS OR BURNER Replace the glass panel and frame assembly Replace the Stove Front N on gt oO N O Care of Cast iron An occasional dusting with a dry rag will he
38. f the other Vertical Termination parts Vertical Termination Flat Roof 1 Flat Flashing and all of the other Vertical Termination parts Twist Lock 24 Straight Pipe CG 1 24 Non adjustable Pipe 1 Polished Brass Flue Pipe Ring Twist Lock 48 Straight Pipe CG 1 48 Nonadjustable Pipe 1 Polished Brass Flue Pipe Ring Twist Lock 45 Degree Elbow CG for vertical offsets 1 45 degree Elbow 1 Polished Brass Flue Pipe Ring Draft Hood Adapter NV Stove Kit 1 7 Diameter Polished Brass Trim Ring 1 48 Nonadjustable Pipe CG 24 Nonadjustable Pipe CG Finishing Plate Finishing Collar CG 1 90 Degree Elbow CG Stove Kit 7FSDHASK Includes all parts in the 7FSSK plus the Draft Hood Adapter FSDHAG 1 1 1 1 1 1 7TDVSKVB 7DVSKVF 7TFSDVP24 7TFSDVP48 7TFSDVT45 FSDHAG 7FSSK Yr re wH 1 1 1 Combination Offset Roof Support 7DVCS Attic Insulation Shield 7DVAIS 7 Charcoal Gray Pipe Rings 4 7FSDRG 7 Polished Brass Pipe Rings 4 7FSDRP Wall Thimble 942G NOTE Direct vent pipe may be used on the Natural Vent sys tem from the top of the draft hood adapter to the ceiling 30001935 Install the Optional Fan If you are installing the optional convection Fan Kit 2767 FK26 continue here If you are not installing a Fan Kit go to Page 14 Venting System Assembly 1 The fan kit includes a Blower Assembly and a Rheo stat Assembly connected by a cable Fig 12 Th
39. flat padded surface such as a counter protected by a towel 4 Take the logset out of the firebox if previously in stalled 5 Remove the rear log bracket by unfastening the screw Fig 37 6 Remove the right and left log bracket assembly by unfastening the two screws which hold the burner in place Fig 37 7 Hold the burner at the right hand side and lift to clear the right burner leg Then pull to the right to clear the injectors on the left hand side Remove Screws Rear Log Bracket Left amp Right Log Bracket Assembly ST768 Fig 37 Remove rear log bracket and left and right log bracket assembly 4 30001935 8 The air shutter is located on the bottom of the burner to the left Fig 37 Unfasten the two nuts holding the shutter in place The shutter may be adjusted between the factory adjusted 1 2 to fully open Reassemble the shutter to allow the rear injector air inlet to close from the minimum 1 2 opening to fully open Fig 39 You may have to try more than once to find the correct air shutter opening for best results depending on your altitude Air Shutter Original Position Burner See Table 1 Fig 38 Air shutter in original from the factory position Front Injector Air Inlet Air Shutter May be adjusted up to fully open Burner Rear Injector Air Inlet Fig 39 Air shutter adjusted 9 Refasten the two nuts and assemble the burner into the unit by sliding the burner in at an angle wit
40. gth of the individual venting sections and the lengths of the decorative pipe if installed you may need to slip the decorative pipe over the venting sections before attaching upper sections to lower ones The sections of decorative pipe should be oriented with their seams if any toward the wall sections usually do not need to be fastened at each joint other than slip sections If the layout includes a slip section this should be the last section of pipe visible in the room at the ceiling Complete the venting according to the vent maker s instructions Left Log Decorative Grate LG141 Fig 34 Install the back left and right logs Connect the Gas Supply Line Check the Rating Plate attached by a steel cable to the firebox to confirm that you have the appropriate firebox for the type of fuel to be used The Dutchwest may be converted from one gas to another using the appropri ate Fuel Conversion Kit listed on Page 34 Fig 33 Install draft hood adapter Install the Log Set 1 Remove the logs from their packaging and inspect each piece for damage DO NOT INSTALL DAM AGED LOGS 2 Install the rear log centering it side to side on the sheet metal shelf at the back of the firebox Fig 34 The log will touch both sides and the back wall of the firebox 3 Install the right log by engaging hole on bottom with pin on the rear log Fig 34 Then set right bottom side on the burner so the edge of the log to
41. h the left side lower than the right side Slide the left side onto the injectors Lower the right hand side down into place Make sure the burner is as far left as pos sible and the injector shoulders are inside the burner NOTE It is very critical to keep the left burner leg which holds the injectors at a 90 angle to the base Fig 40 This keeps the orifices aligned with tubes on the inside of the burner Failure to do so could affect the flame appearance and performance of the unit 10 Refasten the right and left log bracket assembly 11 Refasten the rear log bracket 12 Replace logs 13 Replace glass and stove front Follow lighting instructions on Page 25 Check flame color appearance NOTE Allow stove to burn for at least 1 2 hour to establish full flame color 30001935 Dutchwest Direct Vent Natural Vent Gas Heater Should color need further adjustment repeat steps 1 12 for air shutter adjustment Left Burner Leg A Injector Shoulder Fig 40 Be sure to maintain 90 angle at left burner leg Complete the Assembly e Open the swiveling latches cams on the top left and right corners of the glass frame e Position the glass and frame against the firebox by placing the bottom edge on the brackets on the bot tom face of the firebox e Swing the assembly against the firebox and close the latches firmly against the pins protruding from the firebox top Install
42. han 8 2 44m and no more than 40 12m above the appli ance flue collar A 2 restrictor plate supplied must be used where specified in all vertically terminated vent systems Fig 8 NOTE The restrictor plate supplied with the vertical termination should be discarded Install restrictor plate supplied with stove directly at stove outlet A vertically terminated vent system must also conform to the following criteria No more than three 90 elbows may be used Two 45 elbows may be substituted for one 90 elbow No more than six elbows may be used e Vent must rise a minimum of 2 feet before offset is used e Termination height must conform to roof clearance as specified in Figure 9 All Vertical Termina tions in this area Require use of the 2 Restrictor Plate lar to the top of the vent pipe n feet lue coll lt F Ci T B E gt oO ec S oa a S S p N fo Unacceptable Configura one n OF TDN amp 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Horizontal Run in feet ST132a Fig 8 Vertical vent termination window The Restrictor Plate is used on Direct Vent Installations Only 8 Vent Termination Cle
43. imited lifetime coverage on the ceramic burner plaque Warrantees are made to the original owner subject to proof of purchase and the conditions and limitations listed on this Warranty Document COMPONENT WARRANTY CAST IRON All external and internal cast iron parts are warranted for a period of three years Note On porcelain enamel finished external parts and accessories The Company offers no Warranty on chipping of enamel surfaces Inspect all product prior to accepting it for any damage to the enamel The salt air environment of coastal areas or a high humidity environ ment can be corrosive to the porcelain enamel finish These condi tions can cause rusting of the cast iron beneath the porcelain enamel finish which will cause the finish to flake off Dye lot variations with replacement parts and or accessories can oc cur and are not covered by warranty GLASS DOORS Glass doors are covered for a period of one year Glass doors are not warranted for breakage due to misuse or accident Glass doors are not covered for discoloration or burned in stains due to environmental issues or improper cleaning and maintenance BRASS PLATED PARTS AND ACCESSORIES Brass parts should be cleaned with Lemon oil only Brass cleaners cannot be used Mortar mix and masonry cleaners may corrode the brass finish The Company will not be responsible for nor will it warrant any brass parts which are damaged by external chemicals or down draft conditions
44. ions exactly The heater will also accept standard or enam elled 7 150mm diameter pipe around the Type B venting for decorative purposes only Fig 32 NOTE The restrictor plate supplied with the stove is not used for Natural Vent applications Decorative 7 Pipe CFM Direct Vent System may be used Draft Hood 4 B vent up up to the ceiling Pipe Draft Hood Adapter Fig 32 Decorative 7 pipe may be fitted around the B vent pipe The Dutchwest stove when installed as a Natural vent heater includes a vent safety switch Fig 60 Page 32 Operating the stove when it is not connected to a properly installed and maintained venting system or tampering with or disconnecting the vent safety switch can result in carbon monoxide CO poisoning and pos sible death For U S installations The venting system must con form with local codes and or the current National Fuel Gas Code ANSI 222 1 For Canadian installations The venting system must conform to the current CSA B149 1 installation code Install the Vent Pipe Apply a bead of sealant around bottom end of inner starter pipe found in bag with logset and attach to stove Apply a bead of sealant around top of inner starter pipe and install the Z31D00 FSDHAG Draft Hood according to Draft Hood instructions Fig 33 30001935 Dutchwest Direct Vent Natural Vent Gas Heater Attach the first section of venting to the draft hood De pending on the len
45. lower the front into position so the lower tabs engage with the corresponding ribs at the bottom N When properly installed the bottom of the stove front cannot be pulled away from the sides without also lifting it 3 8 Locking Nut Fig 43 Insert handle stub into hole in front Secure with 3 8 locking nut Engage steel tabs behind the cast iron bosses Bottom tabs engage notch in the leg Fig 44 Install the front plate 30001935 Dutchwest Direct Vent Natural Vent Gas Heater Operation Your First Fire Read these instructions carefully and familiarize your self with the burner controls Locate the pilot assembly Figure 45 Follow the lighting instructions on Page 25 exactly During the first fire it is not unusual to smell some odor associated with new logs paint and metal being heated Odors should dissipate within an hour or so however you can open a window to provide fresh air to alleviate the condition Pilot and Burner Inspection Each time you light your heater check that the pilot flame and burner flame patterns are as shown in Figure 47 lf flame patterns are incorrect turn the heater off Contact your dealer or a qualified gas technician for as sistance Do not operate the heater until the pilot flame is correct Follow regular maintenance procedures as described on Page 30 Fig 45 Pilot assembly location 30001935 Flame amp Temperature Adjustment For sto
46. lp keep the painted surfaces looking new Use high temperature stove paints available through your local dealer to touch up areas as needed Clean areas to be painted with a wire brush and be sure to cover the logs burner and valve assembly glass and frame assembly Apply the paint sparingly two light coats of paint will give bet ter results than a single heavy coat Clean porcelain enamel surfaces with a soft damp cloth Do not use abrasive cleaning agents If neces sary use only a cleaning agent formulated especially for use on porcelain enamel surfaces 30001935 CAUTION TURN THE PILOT OFF BEFORE PAINTING ALLOW THE HEATER TO COOL COMPLETELY BEFORE PAINTING Cleaning the Glass WARNING Allow the glass cool completely before attempting to clean It will be necessary to clean the glass periodically Dur ing start up condensation which is normal forms on the inside of the glass and causes lint dust and other airborne particles to cling to the glass surface Also initial paint curing may deposit a slight film on the glass It is therefore recommended that the glass be cleaned two or three times with a non ammonia household cleaner and warm water we recommend gas fireplace glass cleaner After that the glass should be cleaned two or three times during each heating season depend ing on the circumstances present Clean glass after first two weeks of operation Glass Replacement Replace glass only with C
47. m minimum between termination caps 2 All mechanical air intakes within 10 1 m of a termination cap must be a minimum of 3 914 mm below the termination cap 3 All gravity air intakes within 3 914 mm of a termination cap must be a minimum of 1 305 mm below the termination cap Fig 10 Termination clearances Venting Requirements Natural Vent Only Venting Runs NOTE When venting staight vertical without any elbow a minimum of 8 ft vertical is required off the top of the stove O Acceptable venting configuration Unacceptable venting configuration A Vertical installations up to 36 feet 12m in height Up to an 18 ft horizontal vent run can be installed within the vent system using a maximum of two 90 degree elbows or four 45 degree elbows B Vertical installations up to 36 feet 12m in height Up to a 24 ft horizontal vent run can be installed within the vent system using a maximum of two 45 degree elbows Ratio 2 3 Hor Vert Vertical Run in feet Measured from top of the unit before any elbow 124 6 8 10 1214 16 18 20 22 24 Horizontal Run in feet FP567b Fig 11 Vent termination window Natural Vent ONLY NOTE When using the FSDHAG the restrictor plate supplied with the stove is not used 30001935 11 Dutchwest Direct Vent Natural Vent Gas Heater Venting Requirements and Options
48. ment of 5 5 W C In order to connect Propane use a fitting with 3 8 NPT nipple on the valve side and 1 2 propane gas supply line with an input of 28 000 BTUs at a manifold pressure of 10 0 and minimum inlet supply for adjust ment of 11 0 w c Air Shutter Adjustment The Dutchwest is shipped from the factory with the air shutter adjusted to the minimum allowed opening Refer to Table 1 Based on the altitude where the stove is located a shutter adjustment is acceptable to provide a mixed balance of flame color glow To adjust the shutter opening follow the steps below NOTE The air shutter may only be adjusted to a more open position The factory setting is the minimum allow able air shutter opening Figs 38 amp 39 Table 1 Air Shutter Adjustment Minimum rear injector inlet openings Model Natural Gas Direct Vent 1 2 Natural Vent 1 2 Air Shutter Adjustment Instructions To adjust the air shutter the following procedures should be followed 1 Remove stove front Lift stove front up and then swing bottom out and away to disengage from the stove body Fig 36 2 Swing open the swiveling latches at the top left and right corners of the glass frame Fig 57 Page 31 ST771a Fig 36 Remove stove front 3 Pull the top edge of the glass and frame assembly away from the firebox and lift it off its supports on the bottom of the firebox face Place the assembly out of the way on a
49. n the pipe to the holes in the flue collar with the 12 x 1 2 sheet metal screws provided Fig 19 First Section of Vent Pipe 8 x 1 2 Sheet Metal Screws 4 Inner Starter Pipe Fig 17 Connect the inner starter with the next section of in ner vent pipe ST760 Fig 18 Attach inner assembly to flue collar Fig 19 Fasten outer pipe with 12 x 1 2 sheet metal screw 30001935 Dutchwest Direct Vent Natural Vent Gas Heater Install the Vent Adapter Pipe Side Wall Termination Assembly Simpson Dura Vent Components 1 Locate the vent opening on the wall Refer to Fig 1 Install the Restrictor Plate Consult the Vent Run Specifications on Page 8 to determine whether the restrictor plate is needed If so put the restrictor plate in place within the inner flue collar Fig 16 Discard the inner starter pipe shipped with the log set Using the starter pipe assembly listed on Page 7 slide the inner section out to allow access e Run a bead of sealant around the bottom end of the starter pipe and attach the assembly to the stove using three 1 4 20 x 3 8 Phillips screws provided in the parts bag Fig 20 Install the Outer Adapter Pipe Apply a 1 4 bead of cement around the outside surface about one inch from the crimped end Fig 21 Orient the verti cal seam to the rear and insert the crimped end of the outer pipe into the flue collar Fasten with three sheet metal
50. nsure the rubber gasket D is properly positioned and install the new HI LO pressure regulator assem bly to the valve using the new screws E supplied with the kit Tighten the screws securely Ref torque 25 in lb Fig 52 3 Install the enclosed conversion label F to the valve body where it can easily be seen Fig 52 30001935 Fig 52 Replace regulator Pilot Orifice Conversion 1 Locate pilot Fig 49 2 Replace pilot orifice Pilot Type 1 e Remove pilot hood by lifting up Fig 53 Do not remove snap ring to remove pilot hood NOTE It is not necessary to remove the pilot tube for conver sion e Remove pilot orifice with allen wrench Fig 54 e Install the conversion orifice e Reinstall pilot hood Be sure to align hood with index tab Pilot type 2 e Loosen pilot hood turning counterclockwise using a 7 16 wrench Fig 55 NOTE You may use pen etrating oil to prevent pilot hood threads from seizing up 30001935 Dutchwest Direct Vent Natural Vent Gas Heater Pilot Hood Index Tap Snap Ring Fig 55 Remove pilot hood Your pilot may have a different appearance e Remove pilot orifice with needlenose pliers Fig 56 NOTE Use a wrench to hold pilot tube in place while removing the orifice e Install the conversion orifice e Reinstall pilot hood and tighten until mark on pilot hood aligns with mark on pilot bracket NOTE Be sure burner leg remains at
51. nversion Instructions WARNING This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes and requirements of the authority having jurisdiction If the information in these instruc tions is not followed exactly a fire explosion or production of carbon monoxide may result causing property damage personal injury or loss of life The qualified service agency is respon sible for the proper installation of this kit The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer s instructions supplied with the kit CAUTION The gas supply shall be shut off prior to disconnecting the electrical power before pro ceeding with the conversion Ema Main Gas Gas Supply Inlet Line Fig 48 Attach the gas line to the left side of the valve Conversion Precautions Before proceeding turn control knob on valve to OFF and turn gas supply OFF Turn OFF any electricity that may be going to the appliance Conversion Procedure Remove stove front Lift stove front up and then swing bottom out and away to disengage from the stove body Fig 58 Page 29 Swing open the swiveling latches at the top left and right corners of the glass frame Fig 59 Page 29 Pull the top edge of the glass and frame assembly away from the firebox fac
52. or authorizes any third party to as sume on its behalf any other liabilities with respect to the sale of this CFM Corporation product The warranties as outlined within this document do not apply to chim ney components or other non CFM Corporation accessories used in conjunction with the installation of this product Damage to the unit while in transit is not covered by this warranty but is subject to claim against the common carrier Contact the dealer from whom you purchased your fireplace stove do not operate the appliance as this might negate the ability to process the claim with the carrier The Company will not be responsible for a Down drafts or spillage caused by environmental conditions such as near by trees buildings roof tops hills or mountains b Inadequate ventilation or negative air pressure caused by me chanical systems such as furnaces fans clothes dryers etc e This warranty is void if a The fireplace has been operated in atmospheres contaminated by chlorine fluorine or other damaging chemicals b The fireplace has been subjected to prolonged periods of damp ness or condensation c Any damages to the fireplace combustion chamber heat exchanger or other components due to water or weather damage which is the result of but not limited to improper chimney venting installation d Any alteration willful abuse accident or misuse of the product has occurred IF WARRANTY SERVICE IS NEEDED
53. ore e Slide the wall plate over horizontal run before at taching the horizontal run to the elbow Fasten wall plate to wall 4 For CFM Vent Pipe only If necessary measure to determine the vertical length X of pipe required from the adapter pipe to the wall cutout centerline including a 2 51mm overlap at the joint Fig 24 use a hacksaw or tin snips to trim the pipe as needed Fig 24 Determine the vertical pipe length 5 Install first the inner then the outer straight pipe section s trimmed end down to the point of the el bow Drill 3 holes through each joint and fasten with sheet metal screws 6 Seal and install the elbow using 3 sheet metal screws at each joint 7 Measure and cut if needed the appropriate length of pipe section needed to make the connection through the wall Include a 2 overlap i e from the elbow to the outside wall face about 2 or the dis tance required if installing a second 90 elbow Fig 25 8 Slip the wall plate and trim collar over the interior end of the horizontal pipe and install into the wall sleeve Seal the joint inside the wall plate if needed to keep cold air from being drawn into the home 9 Seal the ends and connect the horizontal pipe to the elbow Fasten the wall plate to the pipe with three sheet metal screws Slide the trim collar up against the wall plate to cover the screws Fig 26 16
54. oss rocker switch wires at the valve if burner lights wires are faulty or connections are bad B Thermopile may not generate 1 Be sure wire connections from thermopile at gas sufficient voltage valve terminals are tight and thermopile is fully inserted into pilot bracket One of the rocker switch wires may be grounded Remove rocker switch wires from valve terminals If burner now stays lit trace rocker switch wiring from ground It may be grounded to the appliance or the gas supply line Check the thermopile with a millivolt meter Take reading at thermopile TP and TP TH terminals of gas valve Should read 325 millivolts minimum while holding valve knob depressed in PILOT po sition and with rocker switch OFF Replace faulty thermopile if reading is below specified minimum C Plugged burner orifice Check burner orifices for debris and remove D Defective automatic valve op Turn knob to ON place rocker switch to ON millivolt erator meter should read greater than 10 mV If the read ing is okay and the burner does not light replace the valve 4 Frequent pilot out A Pilot flame may be too low or Clean and or adjust pilot flame for maximum flame age high blowing or lifting caus impingement on thermocouple and thermopile ing the pilot to drop out B Possible blockage of the vent Check the vent terminal for blockage terminal 25 30001935 Dutchwest Direct Vent Natural Vent Gas Heater Fuel Co
55. ound the vent termination must be maintained For installations using Simpson DuraVent pipe parallel installations with minimum wall clearance have restricted access for connecting the Hori zontal Vent Cap straps to the vent pipe See the maker s instructions for recommended installation procedures 30001935 Dutchwest Direct Vent Natural Vent Gas Heater Venting Termination Clearances Your stove is approved to be vented either through the side wall or vertical through the roof e This unit does not require any opening for in spection of vent pipe e Only CFM Corporation and Simpson DuraVent venting components specifically approved and labelled for this stove may be used e Minimum clearances between vent pipes and combustible materials is one 1 inch 25 mm except where stated otherwise e Venting terminals shall not be recessed into a wall or siding e Horizontal venting must be installed on a level plane without an inclining or declining slope 30001935 There must not be any obstruction such as bushes garden sheds fences decks or utility buildings within 24 from the front of the termination hood Do not locate termination hood where excessive snow or ice build up may occur Be sure to check vent termi nation area after snow falls and clear to prevent ac cidental blockage of venting system When using snow blowers make sure snow is not directed towards vent termination area Location of Vent
56. screws provided Inner Adapter 1 4 20 x 3 8 Pipe Phillips Screws g 8 Gon L H it a ST762 Fig 20 Simpson DuraVent install inner adapter pipe Fig 21 Simpson DuraVent install outer adapter pipe 30001935 ure 5 Page 6 to determine the opening centerline It may be necessary to first position the stove and measure to find the hole location Depending on whether the wall is made of combustible materials cut the opening to the size shown in Figure 22 Com bustible wall openings must be framed as shown in Figure 22 Framing Detail 10 T2 250 mm 191 mm 7 Zo l VO584 100 Fig 22 Locate vent opening 2 Measure the wall thickness and cut the wall sleeve sections to proper length MAXIMUM 12 Assemble the sleeve with the 8 sheet metal screws supplied Attach the firestop plate to the sleeve end with the holes Fig 23 NOTE The wall sleeve is required in combustible walls only Install the Wall Firestop Sleeve assembly into the wall cutout and fasten the firestop to the wall cutout framing members Fig 23 12 305 mm Max Length Sleeve ZCS103 Fig 23 Assemble the wall sleeve and firestop 15 Dutchwest Direct Vent Natural Vent Gas Heater For DuraVent pipe only install vent pipe by align ing the locking system together sliding the pipes together and twisting clockwise e Install 90 elbow Twist lock as bef
57. sh the vent hole through the wall 2 Remove soil to a depth of approximately 16 406 mm below the base of the snorkel Install a window well not supplied Refill the hole with 12 305mm of coarse gravel and maintain a clearance of at least 4 102 mm below the snorkel Fig 28 3 Install the vent system as described on Pages 14 17 4 Be sure to make a watertight joint around the vent pipe joint at the inside and outside wall joints 5 Apply high temperature sealant around the inner and outer snorkel collars Join the pipes and fasten the snorkel termination to the wall with the screws provided 6 Level the soil to maintain a 4 clearance below the snorkel Waterproof Seal Snorkel i Around Pipe Termination Firestop Cap av 4 Clearance ERRET Gravel p o Drain Window Well Fig 28 Snorkel kit installation If the foundation is recessed use extension brackets not supplied to fasten the lower portion of the snorkel Fasten the brackets to the wall first and then fasten to the snorkel with self tapping 8 x 1 2 sheet metal screws Extend the vent pipes out as far as the protrud ing wall face Fig 29 30001935 Dutchwest Direct Vent Natural Vent Gas Heater Recessed Wall Firestop Finishing ta Collar Sheet Metal Screws and Bracket Waterproof Seal Aroun o 7 Pipe
58. t Natural Vent Gas Heater Parallel Installation Minimum Clearance and Flue Centerline Direct Vent and Natural Vent Stove Clearances A 4 102 mm ST128c B 4 102 mm C 15 395 mm D 9 229 mm Fig 3 Parallel installation minimum back and side clear ances and flue centerlines Pipe Centerlines Corner Installation Minimum Clearance and Flue Centerline Direct Vent and Natural Vent ST129c Wall Centerline from Floor ST131c Effective Minimum Wall Thimble 5712 1461 mm CFM Pipe Centerline 53 1359 mm Simpson DuraVent Pipe Fig 5 Minimum wall thimble centerline Wall and Ceiling Clearances ST101c A Rear Wall B Min Clearance 4 102 mm 4512 1156 mm C Min Alcove Height D Max Alcove Depth 7312 1867 mm 48 1220 mm Stove Clearance Pipe Centerline A 4 102 mm B 14 370 mm Fig 4 Corner installation minimum corner clearances and flue centerline Sidewall Clearance 4 102 mm needed for installing DuraVent Minimum Vent Kit 2792 or CFM Corpora tion Minimum Vent Kit 7TFSDVSK Fig 6 Dimensions and clearances to ceiling or alcove Hearth Requirements The Dutchwest Heater must be installed on rigid floor ing When the heater is installed directly on any com bustible surface other than wood flooring a metal or wood panel extending the full width and depth of the unit must be used as the
59. t Natural Vent Gas Heater e Remove retaining nut from shaft of rheostat if preinstalled e Insert the rheostat through the hole in the back of the left side of the valve bracket aligning the locator pin with the smaller hole in that bracket e Thread the retaining nut onto the shaft of the rheostat tightening with a wrench Do not over tighten e Attach the control knob to the rheostat shaft e Use the wire tie to secure the fan and rheostat wire harnesses together Rear Skirt Sheet Metal Screws Star Washer Sheet Metal Screws Phillips Pan O oe Snapstat ieee o 4 4 20 7 i Hex Bolt Head Bolts Star Washer Snapstat Bracket Rheostat Retaining Collar Rheostat Knob Fig 15 Attach the fan rheostat 13 Dutchwest Direct Vent Natural Vent Gas Heater Venting System Assembly Direct Vent General Information The Dutchwest is approved for installation only with the vent components listed on Page 12 Follow the vent component instructions exactly For U S installations The venting system must con form with local codes and or the current National Fuel Gas Code ANSI Z223 1 NFPA 54 For Canadian installations The venting system must conform to the current CSA B149 1 installation code Install the Vent Adapter Pipe CFM Corporation Vent Components 1 Install the Restrictor Plate Consult the Vent Run Specifications on Page 8 to determine whether
60. t of 15 5m 3 91cm within a height of 15 extended above meter regulator assembly above the meter regulator assembly 5m above the meter regulator assy J Clearance to nonmechanical air supply inlet 6 15cm for appliances lt 10 000 6 15cm for appliances to building or the combustion air inlet to any Btuh 8kW 12 30cm for lt 10 000 Btuh 3kW 9 other appliances appliances gt 10 000 Btuh 3kW and 23cm for appliances gt 10 000 lt 100 000 Btuh 30kW 36 91cm Btuh 3kW and lt 50 000 Btuh for appliances gt 100 000 Btuh 30kW 15kW 12 30cm for appliances gt 50 000 Btuh 15kW 3m horizontally driveway located on public property M Clearance under veranda porch deck or 12 30cm 12 30cm acre ee N Clearance above a roof shall extend a minimum of 24 610mm above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18 450mm 1 In accordance with the current CSA B149 Installation Codes 2 In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Codes t Avent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings only permitted if veranda porch deck or balcony is fully open on a minimum 2 sides beneath the floor NOTE 1 Local codes or regulations may require different clearances 2 The special v
61. uches the right side of the firebox The right log does not use the locator pins on the burner to stay in place 4 Install the left log by engaging hole on bottom with pin on rear log Fig 34 Then set left bottom side on the burner so the edge of the log touches the left side of the firebox 5 Loosely sprinkle the lava rocks directly on top of the burner in front of and between the decorative grate and the right and left logs Use the lava rock to cover brackets on the burner Fig 35 30001935 CAUTION This appliance should only be connected A by a qualified gas technician Test to confirm manifold pressures as specified below The Dutchwest Heater and its individual shutoff valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1 2 psig 3 5 kPa The Dutchwest Heater must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1 2 psig There must be a gas shutoff between the stove and the supply In order to connect Natural Gas use a fitting with 3 8 NPT nipple on the valve side and 1 2 natural gas supply line with an input of 28 000 BTUs ata manifold pressure of 3 5 and minimum inlet sup ply for adjustment of 5 5 w c In order to connect Propane use a fitting with 3 8 NPT nipple on the val
62. ure A rheostat provides for variable fan speeds Specifications 115 Volt 60Hz 75 Amps Maintenance The fan itself does not require regular maintenance however periodic cleaning of the fan and the surround ing area is required Installation Refer to Page 13 for installation instructions Remote Controls The remote control allows you to turn the heater on or off from anywhere in the room Refer to Page 32 for wiring diagrams Model Functions Controlled RC1 ON OFF RC2 ON OFF and Temperature IMTFK Wall mounted thermostat control Decorative Rings 7 brass or charcoal gray rings are available to add a decorative touch to the exposed stove pipe Model Description 7FSDRG 4 7 Charcoal Gray Rings 4 7FSDRP 4 7 Polished Brass Rings 4 30001935 LIMITED LIFETIME WARRANTY PRODUCT COVERED BY THIS WARRANTY All Dutchwest gas stoves equipped with an Insta Flame Ceramic Burner BASIC WARRANTY CFM Corporation Company hereinafter referred to collectively as the Company warrants that your new Dutchwest Gas Fireplace Stove is free from manufacturing and material defects for a period of one year from the date of purchase subject to the following conditions and limitations EXTENDED LIFETIME WARRANTY The heat exchanger where applicable and combustion chamber of every Dutchwest gas product is warranted for life against through wall perforation All appliances equipped with an Insta Flame Ce ramic Burner have l
63. ustment amp INStructiOns ccccccecceceeeeeeeeeceeeeeeeeneeeeeeeeeeeneeeeeeeeeneaeees 20 Complete the Assembly serrie iaaea ae aE aaae aaaea daa Tiaa 21 Install ON OFF SWH E E Alc EEEE 21 Thermostat Connection Optional ccceeceececeeeeeeeeceeeeeeeeeeaeeeeeeeeeeaeeeeeeseeeeaeeeeees 22 Install the Front and Top Plates cccceccccccceceeeeeeceeeeeeeeeceeeeeeeeeeeeeeeseeeseeseeeenenaeees 22 Operation YOUR First FING sises asear ne Aes they N eee hee 23 Pilot and Burner Information isisisi ea eieaa vir i aaa ah 23 Flame amp Temperature Adjustment Flame Characteristics sssennneeeseeenee eeren 23 Lighting and Operating INStrUCtiONS s sisosi kiiensis niaaa airaa iaeaea 24 Troubleshooting Honeywell 8420 Gas Control System sessscsssrerrreerrereer 25 Fuel Conversion Instructions soirceas ps taretare naa Nete ENE AED AEAEE ETEA 26 Maintenance Annual System INSPectiony cic csie eee aaaeeeaa a E aaa EE EEE 29 Logset and Burner Cleaning and Inspection seeseeeeeesiesriierrirssirnerireerirerrinsrrenen 29 Careof Cast WOM css secs ceapecsccvus chet E a E id ee ae ek tah nn 29 Cleaning the Gl SS rrrainis iisen e iieii inian 29 Glass Replacement si 025e scesed sceescec ted dna a r eaa aaie NAA EE YEAP ENE aE ERARE 29 Gasket Replacement aiiin aie EE E E E E REE 30 Inspect the Vent System Annually ec ceeeeeeeeeeeeeeeeneeeeeneeeeeneeeeteeeeenaeeeeseeeeseneeeeegs 30 Check the Gas Flame
64. ve side and 1 2 pro pane gas supply line with an input of 28 000 BTUs at a manifold pressure of 10 0 and minimum inlet supply for adjustment of 11 0 w c 19 Dutchwest Direct Vent Natural Vent Gas Heater In the U S Gas connection should be made in ac cordance with current National Fuel Gas Code ANSI Z2223 1 NFPA 54 Since some municipalities have additional local codes be sure to consult your local authority In Canada consult the local authority and CSA B149 1 installation code Always check for gas leaks with a mild soap and water solution Do not use an open flame for leak testing Light the pilot according to the directions on Page 25 before going to the next step Burner Information The appliance must only use the gas specified on the rating plate unless converted using a Fuel Conver sion Kit To convert from LP to Natural Gas use Kit 000 5021 To convert from Natural Gas to LP use Kit 000 5022 Conversion instructions are provided with each kit and beginning on Page 27 in this manual This appliance should be connected to the gas supply only by a qualified gas service technician Follow all local codes There must be a gas shut off between the stove and the supply In order to connect Natural Gas use a fitting with 3 8 NPT nipple on the valve side and 1 2 natural gas sup ply line with an input of 28 000 BTUs at a manifold pres sure of 3 5 and minimum inlet supply for adjust
65. ves equipped with HI LO valves flame adjust ment is accomplished by rotating the HI LO adjustment knob located near the center of the gas control valve Fig 46 Turn counterclockwise Turn clockwise to increase flame height to decrease flame height Fig 46 Flame adjustment knob for Honeywell valve Flame Characteristics It is important to periodically perform a visual check of the pilot and the burner flames Compare them to Figure 47 If any of the flames appear abnormal call a service person CO106c Fig 47 Correct pilot and burner flame patterns 23 Dutchwest Direct Vent Natural Vent Gas Heater Lighting and Operating Instructions FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life A This heater has a pilot which must be lit manu ally When lighting the pilot follow these instruc tions exactly BEFORE LIGHTING smell all around the heater area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any fireplace Do not touch any electric switch Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions e If you cannot reach your gas supplier call the Fire Department C
Download Pdf Manuals
Related Search
Related Contents
VT-P082-SUM-001-E-02.. Formation plongeur Nitrox Confirmé このたびは通話録音装置 VR-D170/VR-D170AⅡ をお買い Pelco IM10C10-1 surveillance camera Brinkmann Backyard Kitchen Outdoor Gas Grill User's Manual Recommendation Report Measuring Gross Sommaire Minka Lavery 4952-267B Instructions / Assembly Manual Genov Copyright © All rights reserved.
Failed to retrieve file