1.    holes    01006323    TOSHIBA 6F 9EO090    6  Adjustments  6 1 Current setting     1  When detected current is in a range of 0 5   54   After confirming that the current value under normal load  condition is in a range of 0 5   54  set the current  adjusting knob to the desired detecting value     2  When detected current is above 54   Using an external CT  current transformer   properly suited  for the detected Current value  connect the secondary side of  the CT to the input terminal of the relay  Calculate the  secondary current corresponding to the detected current  value  based on the CT ratio  Then set the current adjusting  Knob to this calculated value     6 2 Setting the detection delay time    Setting time varies depending upon each individual application   Adjust the detection delay time according to the following      1  Hotor load   TO avoid detection during start up  set the delay tire to  approximately 120  of starting time    Transformer load         N        If the inrush current  inrush time varies depending upon  capacity  is large  set the delay time to approximately  120  of this inrush time  Genenrally  1f the capacity 15  small  inrush time is short and therefore  even when the  adjusting knob is set at the minimum position  there should  not be any nuisance tripping      12     01005323    asini a 6F 9E 0090    6 3 Setting the Response delay time  Adjust the set time according to the purpose of detection  l e   overcurrent or undercurrent   The set t
2.   10006323    TOSHIBA    I NSTRUCTI ON MANUAL    CURRENT RELAY    RC803A  HP 1    TOSHIBA CORPORATION    6F9E0090                   1 1 292                         1L 4           01009324    TOSHIBA    1   2  2 1  2 2   3   4   4 1  4 2  b 3  4 4  4 5       6  6 1  6 2  6 3       8    6  9  0090  CONTENTS   General Description                                     Check Before Using                                              External Appearance                                           Specifications                                               3  Descriptiono f  Operatioa                       P   5  Applications                                                              6  Overcurrent Detection on Hotors   e 6  Undercurrent Detection on Motors                        8  Limiting Starting Current of Rotors                     9  Transformers                                                  10  Heaters  Lampe and Other Circuits                       10  Mounting                                                        10  Adjustaents                                                  12  Current Setting                                           12  Setting the Detection Delay Time                        12  Setting the Response Delay Time                         3  Operationallest                                             13  Cover Removal    aus s Lu arroces 17    01005494    TOSHIBA 6F 9E0090       Please thoroughly read this instruction manual before using the  RC803A Curr
3.  current  this relay can automatically advance the  starting resistance on the secondary side of the motor  in this  case  the knob of the detection delay timar and that of the    response delay timer should be kept at the minimum settings      01005393    01009324    TOSHIBA 6F9EO0090    4 4 Transformers  To use this current relay for detecting overcurrent on  transformers  it is necessary to set the detection delay timer  with the inrush current of transformer taken into consideration     4 5 Heaters  Lamps and other Circuits   This relay can be used to detect the disconnection of  circuits by sensing the existence of current flow   n other  words  if disconnection occurs  current does not flow and an  undercurrent condition is detected by the relay  For example   this relay can be used to detect the disconnection of heater  circuits on constant temperature ovens or heatar circuits for  insulators on transmission and distribution facilities In    extremely cold regions     5  Hount ing  See Fig  4 for uounting dieensions  Be careful not to use this  relay in the following conditions      1  Locations in aebient temperatures outside  10    50        2  Locations subject to high temperature  steam or dripping water     3  Dusty dirty locations     4  Locations subject to vibration  total amplitude 2 5mm or more   20 times sec  or more  and shock  above 15G in 3 directions      01009323    TOSHIBA    6  9  0090       128    Hountino    Fig  4 Dimensions      11     3   7 Hole 
4. e Power Supply    OA  M    Start PB  it  xz 13        PB  j    H 23 l4        ME       Til T2  T3     121               z   aire                      4    Current relay    Note  The RC803 s output  contacts are shown  with Dower source    applied     Fig  2 Application Example using An External CT    01005393    ibn 6  9   0090    further  when this relay is used in    motor circuit  the  detection delay tiger should be set longer than the startinv  time  about 120   so that this relay is not actuated by inrush  current  If current flowinp in the main circuit becomes abnormal  after the time Deriod of the detection delay timer has elapsed   the relay is actuated when the set time of the response delay  timer is over     4 2 Undercurrent Detection on Motors  To utilize the undercurrent detection function  the relay  is used in a motor circuit with a fixed load  to detect livht  or no load conditions  For example       the case of a pump motor   this relay is used to detect undercurrent when the volume Of  water supplied in a water pipe is low  or in case of a thread  winding rachine  when the tension of the thread drops        Tom 6F9E 0090    AC3 Phase Power Supply        Statrt PB         Current relay    Note  The RC803 s output  contacts are shown  with Dower source    applied     Fig  3 Application Example    4 3 Limiting Startino current of Motors  Many motors of medium and large capacity use a method to  start by limiting starting current  By detectino the main  circuit
5. ent Sensing Relay     1  General Description   This current relay is designed to detect current in AC circuits  with a wide range of applications  e t   detection of abnoraai  current of various electrical equipment due to overloads or broken  circuits  e 9   heater circuits   detection of starting current to  autoaaticaiiy advance the secondary resistance on induction wound  rotor motor controllers    During starting  excessive current such as inrush current  may  exceed rated current flow in motor or transforaer circuits  this  current relay has an adjustable delay circuit to prevent it from  operating during start up    Further  this current relay is fail safe  The relay operates  at the same time control Dower is applied  and the relay is de   energized when the input signal exceeds the preset level or control  Dower is removed     2  Check Before Using  Before using this relay  check the following Doints  If any  defects are found  contact the dealer from which you purchased this  relay   2 1 External Appearance  Check the relay for any missing Darts and for damage  dirt     rust  and loosened screws caused during transportation     01006323    TOSHIBA    2 2 Specifications    6F9E0090    Rated Current  Range of current    sensing    Input circuit  voltage    Type of Current    Response delay  time adjustable  range    Detection delay    tile adjustable  range    Operating volt     Accuracv             v    SPECIFICATIDHS  5A  continuous     0 5   5A  For current above t
6. his range  use a  CT  current transforrer  and connect the  relay to its secondary side     low voltage circuit  below AC 600V    To detect current in high voltage circuits   use a CT  and connect the relay to its  secondary side    Undercurrent    Overcurrent     0 1   35    0 1   30s    a5   132VAC  170   250VAC  50 60  2     10     TOSHIBA    ITEM  Ambient temp     range    Temp error    Dielectric with     stand voltage    Impulse with     stand voltage    Insulation    resistance    Vibration   Oscillation     Impulse    Overcurrent    intensity    Output contact  rating   250VAC max          6F9E0090    SPECIFICATIONS     10    50     10 a t 330     Between terminals and ground  2000VACf or 1 min     Between terminals and ground  1 X 40us at 4500V  standard waveform     Between terminals and ground 100M Ohms or  more when measured with a 500VDC aegger     Amplitude 2 5mm  20Hz  2G   156    40 times of max  continuous current  54    for 1sec   appliedtwice  in accordance with  FECIA     Over Current  SPDT  Under Current  SPDT    TOSHIBA 6F9E0090    Inductive load    Voltage Continuous  120  MS AC  p  f   0  4   Rating  Designation  oe                             0 34  0 154  L R 15ms   0 14       ITEH SPECIFICATIONS    Hysteresis Approx  10X of operating value     Power consumption   o Operating Power 3 5VA  o Input Circuit 0  1VA  when 5A is applied     Height  75kg  1 7 Ib        3  Description of Operation   When the detected current exceeds the detection circuit  ope
7. ing lamp lights at the same time the relay operates                0100 324    TOSHIBA    6F 9E0090        b  When undercurrent or disconnection is detected    Caution     At the same time the main circuit switch is turned ON  the  starting current and rated current flows  and the relay is  picked Up  If current drops below the undercurrent set point   the undercurrent State is detected and the relay drops out    Refer to Fig  5    If input signal to this current relay is zero  When stopped    it is not possible to judge if it is undercurrent or in a  disconnected state  In this case  it is recommended to   have a circuit connecting a normally open auxiliary con   tact of the main circuit switch in series with the alara or  lamp circuit  this will Drevent the relay fror signalling a  fault condition during a normal shutdown       15     01006323    TOGHIRA 6F9E0090        6  If the relay does not operate in the above test  check if  the current setting is correct or if the input signal is  above the set detection value   f the input signal is  correct  check the operation of the relay by gradually  reducing the setting of the current adjusting knob  If the  relay still does not operate  it is defective   n this case   please contact the dealer from which you purchased the relay  or Toshiba              Power Source        12 Overcurrent    Undercurrant  Detected current    Overcurrent  detect ion  Undercurrant et 73  detect ion        7     dd   unns    T1  Detection delay ti
8. ire for the response  delay varies ger application  Host applications may not need  any delay time  It is mainly used to prevent nuisance tripping   ride through  by ignoring momentary load gliches     7  Operational lest     1  Check both the control and detection circuits to confirm there  is no mis wiring     2  Check if the current dedtction time delay  and response  time delay settings are correct     3  If the wiring ard settings are correct  energize the control  circuit and check if it is the proper voltage                TOSHIBA 6F9E0090     4  When the Dower source is applied  the relay is excited and the  output contact   s states are reversed  The relationship between  the input signal end the output contacts are shown in Table 2   Check this relationship during the test     Output Contact Statis    Power signal   Overcurrent   Undercurrent    source   operating Between NM Between   Between  level 5 and 7   6 and 7   8 and 10   9 and 10       Table 2   5  If no problem is found when the Dower source is applied  turn    the rain circuit switch ON and perform the following checks      a  In the case of a motor load  If the set start up time delay is too short  the relay may  be actuated       such a case  reset the detection delay time  adjusting knob accordingly  After the start up time delay  has expired  apply current above the set detection value  to confirm that the relay functions  after the response  delay time   In addition  check that the detection  indicat
9. rating level  the detection delay timer is actuated  If over   current is continuously detected for more then the detection delay  time set value  the overcurrent response delay timer is actuated   Then  if overcurrent is detected when the response delay timer has  elapsed  the overcurrent relay is actuated    If current drops below the undercurrent detection set value   the response delay timer is actuated  and after the set tile has  expired  the undercurrent detection relay is actuated  In the case  of undercurrent detection  the detection delay timer is not actuated     01006323    TOSHIBA 222 6950090    Detection delay  time                Overcurrent    detecting Operation delay time       Hysteresis width    Return point   Relay OFF                       Current  2 Hysteresis H i  4     __y Hysteresis               A ES   3 width  1 Detection delay      circuit operati Undercurrent detecting Operation     leve  03 0  454    elay Time  N Undercurrent detecting  Fig  1 Characteristics  4  Application  4 1 Overcurrent Detection on Hotors  An application example Is shown in Fig  2  In this circuit   an excessive load is detected by detecting the overcurrent of a  motor and the main circuit is opend to Protect     5    01009424    TOSHIBA 6  9  0090    the motor from being damaged  If the detected current is above  54  and in case of a high voltage circuit  use an external CT and    connect the secondary side of CT to the relay as shown in the  following figure     AC3 Phas
10. re  T2  Overcurrent detecting resgonse delay timer  T3  Undercurrent detecting resgonse delay timer    Fig  5 Relay Operation       16     01005303         6F9E0090    8  Cover Removal  To adjust the current and time settings the cover must be raaoved   Remove the cover by applying a force in the direction of the arrow  as shown below  To replace the cover  place the projection of the  cover in the slip out oreventive hole and then insert the bosses  of the cover into the 2 holes at the upper left and right          Cover  Slip out  preventive  projection  Slip out  preventive  hole         17      11006393    TOSHIBA CORPORATION    
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
MANUAL DE INSTRUCCIONES USO, MANUTENCIÌN Y MONTAJE  Samsung Gear Manual de utilizare  SCOPE quick start guide  NEOi 809 Quick Reference for MMS / GPRS / Wap  Pfister GT341PC0 Installation Guide  ISO-TECH IPM6300 Wechselstrom-Leistungsqualitäts  Agilent E4418B パワー・メー タ  Guide pour la pratique de l`éducation thérapeutique  Sony DSC-W220/L Marketing Specifications    Copyright © All rights reserved. 