Home

Life is good 55LM660S-ZA Flat Panel Television User Manual

image

Contents

1. BUTTON OPERATION DISPLAY COMMENTS This example shows how to access parameter 12 boiler pump delay The first display shown is at the beginning of the menu listings after entering the installer access code 7 Beginning of menu listings A General The caret symbol gt highlights i B Temp Settings the selectable line v DOWN Press 1 time to highlight second listing Sigman HE CAET SYMDO 2 TUS B Temp Settings the selectable line Vv DOWN Press 1 time to toggle menu listing gt C Data Logging The menu toggles to the next two D Functions menu options vy DOWN Press 2 times to toggle menu listing gt E DHW Settings The menu toggles to the next two F Heat Curve menu options vyv DOWN Press 2 times to toggle menu listing gt G Anti Cycling The menu toggles to the next two H Control Modes menu options v DOWN Press 2times totogi ment iA gt I Circulation Pumps The menu toggles to the next two gg g PAE ENEE EEI EE Menu options ENTER RES Press 1 time to list parameters eee cE eae 11 Will fash Sees Pump A UP Press 1 time to change parameter DO Atta t meko Gi l2 wi ash im Pump amp ENTER RES Press 1 time to select parameter Ewe we BAe es 12 will OD en parameter P Pump 0 50 minutes value will appear A UP Press to increase or decrease value I2 Postrun Time SH Parameter will increase or decrease or DOWN Pump 0 67 minutes depending on button pressed ENTER RES Press 1 time to save SH OFF Display will change to normal
2. 2 Check settings of external limit controls if any and adjust if necessary Perform start up and checks 1 Start boiler and perform checks and tests specified in Section 10 Start up of the Knight Wall Mount Installation and Operation Manual 2 Verify cold fill pressure is correct and that operating pressure does not go too high 26 Service Manual Check burner flame 1 Inspect flame through observation window 2 Ifthe flame is unsatisfactory at either high fire or low fire turn off boiler and allow boiler to cool down Remove the burner and clean it thoroughly using a vacuum cleaner or compressed air Do not use compressed air to clean burner if performed inside a building 3 Remove the burner reference FIG 2 2 below 4 When replacing the burner ensure gasket is in good condition and positioned correctly FIG 2 2 Figure 2 2 Burner Assembly AIR GAS ARM x SCREWS QTY 5 2 Maintenance continued Check flame signal 1 At high fire the flame signal shown on the display should be at least 10 microamps 2 A lower flame signal may indicate a fouled or damaged flame sense electrode If cleaning the flame sense electrode does not improve ground wiring is in good condition and ground continuity is satisfactory replace the flame sense electrode 3 See Section 3 Troubleshooting in this manual for other procedures to deal with low flame signal Review with owner 1 Review the Knight Wal
3. 31 WHAT IS IN THIS MANUAL 20 0000s 5 Table 3F Troubleshooting Chart Fault Messages 32 39 1 SERVICE Combustion Analysis Procedure 40 Near Boiler Piping 0000c00eceeeee 6 Table 3G Troubleshooting Chart Combustion Levels 40 The Knight Wall Mount Display 0 7 Table 3H Flue Products sia noires iata ndadari 40 Control INpuls sereen oa Kod Sein Geek Po ee keel 8 Gas Valve Adjustment Procedure 41 Control Outputs rira t inaia vn Lea reed wees 9 Revision Notes 2020000 Back Cover General Operation 200000 000s 10 Sequence of Operation 0 00000005 11 12 Display Panel Menu Access 0000 00 13 Display Panel Parameter Access 14 Parameter lable 2 cteeacaehaea a tact dee eee Bae aes 15 16 Viewable and Changeable Control Parameters 17 22 Hazard definitions The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product A DANGER DANGER indicates an imminently hazardous situation which if not avoided will result in death or serious injury G WARNING indicates a potentially hazardous situation which if not avoided could result in death or serious injury A WARNIN CAUTION indicates a potentially hazardous situation which if
4. D S 2 Service Mode Delay 18 No No Yes Yes Le 1 DHW Boiler Set Point 18 Yes Yes Yes Yes E 2 SH DHW Switching Time 18 Yes Yes Yes Yes 1 Minimum Air Temperature 18 No No Yes Yes m 2 Maximum Air Temperature 18 No No Yes Yes 3 Maximum SH Set Point 19 No No Yes Yes w amp 4 Minimum SH Set Point 19 No No Yes Yes 4 a F 5 Outdoor Air Shutdown 19 Yes Yes Yes Yes 6 ou oor A i Suen 19 Yes Yes Yes Yes Differential 7 Shift Air Reset 19 No No Yes Yes 3 8 Boost Temperature 20 Yes Yes Yes Yes 9 Boost Time 20 Yes Yes Yes Yes 15 GHT Service Manual WALL MOUNT BOILER 1 Service Parameter table continued Table 1D continued from previous page This table lists SMART SYSTEM control module parameters and where to access them f2 SEE USER ACCESS INSTALLER ACCESS zZ MENU SUB ITEM DESCRIPTION PAGE DISPLAY MODIFY DISPLAY MODIFY ce gt 1 Anti cycling Time 20 No No Yes Yes S at G 2 Return Temperature Differential for 20 No No v wae Ending Anti Cycling Z d 3 Ramp Delay On Off 20 No No Yes Yes a Outlet Syetom IIED i No No Yes Yes o 2 ee Thermostat BMS and 21 No No Wes Wes Fa o 3 Boiler Cascade Address 21 No No Yes Yes H 4 Max Cascade Set Point 21 No No Yes Yes 5 Cascade Offset 22 No No Yes Yes 6 Cascade Differential 22 No No Yes Yes o 1
5. Freeze protection fluids e NEVER use automotive antifreeze Use only inhibited propylene glycol solutions which are specifically formulated for hydronic systems Ethylene glycol is toxic and can attack gaskets and seals used in hydronic systems What is in this manual Service Near boiler piping Typical system components The Knight wall mount boiler display Display panel readout buttons and their functions Control module inputs Control module inputs and options Control module outputs Control module outputs and options General How the boiler operates e How the control module operates e Access modes user and installer Sequence of operation Domestic Hot Water DHW space heating Control panel menu access Accessing programming mode and locating menus See separate guide covering the PC interface Control panel parameter access Accessing and changing parameters from the display panel Quick start information parameter table An index of available adjustments and readouts where to access them and where to find detailed information Knight wall mount boiler operation A General B Temperature Setting eC Data Logging D Functions E DHW Settings F Outdoor Air Reset Curve e G Anti cycling H Control Modes I Circulation Pumps e J Service Notification Service Manual Maintenance Service and maintenance schedules Address reported problems
6. This parameter can be changed by the installer by accessing parameter El The temperature range of this parameter is 50 F to 190 F The default value is 180 F SH DHW switching time The SH DHW switching time parameter sets the length of time the control will stay in DHW Mode when a SH call has been received After this time period has expired the control will revert to SH Mode If a DHW call is still active the timer will reset After the time period has expired the control will revert back to DHW Mode This will continue until one of the demands has been satisfied This parameter can be changed by the installer by accessing parameter E2 The time range of this parameter is 10 minutes to 240 minutes The default value is 30 minutes F Outdoor air reset Outdoor air reset operation When the outdoor air sensor is installed the control will calculate the water temperature set point based on the outdoor air temperature As the outdoor air temperature drops the water temperature set point increases This feature allows the boiler to be more efficient in periods of mild weather see FIG 1 1 on page 19 Minimum air temperature When the outdoor air temperature drops to or below this point the water temperature will be at its maximum setting FIG 1 1 However if the user set point is set lower the water temperature will be limited by the user set point instead This parameter can be changed by the installer by accessing parameter F
7. and time The control uses an internal clock for the night setback feature and for logging of events For these features to work correctly the clock must be set when the boiler is first installed or anytime the boiler has been powered off for more than 30 days To set the clock parameter A3 must be accessed The date and time are displayed as YY MM DD W hh mm YY year MM month DD date W day 1 Sunday 2 Monday etc hh hour 24 hour time 2 00 PM 14 00 mm minutes The internal clock does not adjust for NOTICE Daylight Savings Time and therefore will require a manual adjustment Software version The software version allows the user to view the software version in use by the control This software controls the operation of the boiler When a new software version becomes available the existing control can be replaced with a new control to update the software Temperature units The control can be configured to display temperature in either C or F This parameter can be changed by the user or the installer by accessing parameter A5 The default is F Night setback temperature Once the internal clock has been set correctly the night setback feature can be used to program a lower water temperature set point for space heating This parameter can be changed by the user or the installer by accessing parameter A6 The temperature range for this parameter is 32 F to 140 F The feature is turned off wit
8. fashion and that the boiler and system pump are running on a call for heat Air in the piping system e Properly purge all air from the piping system Low system water pressure e Verify system pressure is a minimum of 12 psi No Pump Operation Boiler Pump Blown fuse ni habits Pump e Replace fuse F5 on the control board see page 28 of this manual Note Make sure pump amperage does not exceed 1 8 amps DHW Pum PE Faulty pump e Replace pump Internal fault on control board Replace main control board System pressure exceeds relief valve setting Relief Valve Opening e Lower the system pressure below the 30 psi rating of the supplied relief valve or replace the standard relief valve with a higher rated valve up to the maximum pressure of the heat exchanger e Improperly sized expansion tank 37 GHT Service Manual WALL MOUNT BOILER 3 Troubleshooting Table 3F Troubleshooting Chart Fault Messages Displayed on Boiler Interface FAULT DESCRIPTION CORRECTIVE ACTION Either the optional flow switch or the optional Check boiler pump operation on a call for heat low water cutoff is not making Flow e Check for closed valves or obstructions in the boiler i piping Switch LWCO will require a manual e Verify system is full of water and all air has been reset once condition has purged from the system been corrected Press A A 7 a ERE PEDO ON e Check for loose or misplaced jump
9. shut off as the starting point If the temperature drops below the temperature parameter the control will abort anti cycling and allow the boiler to fire This parameter can be changed by the installer by accessing parameter G2 The temperature range of this parameter is 0 F to 86 F The default value is 10 F Ramp delay on off When the ramp delay on off parameter is active the ramp delay limits the boiler firing rate when a SH cycle has started There are six 6 limiting steps used to limit temperature overshoot and short cycles see FIG 1 2 on page 21 of this manual This feature can be turned on or off depending on the installation This parameter can be changed by the installer by accessing parameter G3 The control range of this parameter is 0 Off 1 Ramp Up Only and 2 Ramp Up and Ramp Down The default value is 0 When ramp delay is active additional parameters for ramp delay operation will have to be adjusted These can only be accessed by the optional PC software See the Knight Wall Mount Smart System PC Program Instructions Manual for additional ramp delay parameter information 1 Service continued Figure 1 2 Ramp Delay Interval RATE A RAMP 6 RAMP 5 RAMP 4 RAMP 3 RAMP 2 RAMP 1 1 Service Manual CALL TIME FOR 1 HEAT gt H Control modes SH controlling sensor The SH controlling sensor parameter selects the sensor the cont
10. the resistance of the sensor does not closely match its corresponding table replace the sensor Table 3B Inlet Outlet System Sensor Resistance vs Temperature Table 3C Flue Temperature Sensor Resistance vs Temperature CE OE D a a a E Table 3D Outdoor Air Sensor Resistance vs Temperature 30 Bhool 3 Troubleshooting continued Table 3E Troubleshooting Chart Noisy System Supply gas problem Natural gas pressures should be between 4 inches w c and 14 inches w c LP gas pressures should be between 8 inches w c and 14 inches w c Gas air mixture problem Noisy Dirty damaged burner Operation Low water flow through the heat exchanger Service Manual CORRECTIVE ACTION e Refer to Section 7 Gas Connections of the Knight Wall Mount Installation and Operation Manual for detailed information concerning the gas supply e Refer to the Gas Valve Adjustment Procedure on page 41 of this manual for the proper gas valve setting Verify that the vent air intake lengths do not exceed the maximum listed in the General Venting section of the Knight Wall Mount Installation and Operation Manual e Refer to page 26 in this manual for the burner removal and inspection procedure Clean or replace the burner as necessary e Refer to Section 6 Hydronic Piping of the Knight Wall Mount Installation and Operation Manual for minimum flow rates Verify that the boiler is piped in a primary secondary
11. to inspect for the above conditions and have them repaired can result in severe personal injury or death Check water system 1 Verify all system components are correctly installed and operational 2 Check the cold fill pressure for the system Verify it is correct must be a minimum of 12 psi 3 Watch the system pressure as the boiler heats up during testing to ensure pressure does not rise too high Excessive pressure rise indicates expansion tank sizing or performance problem 4 Inspect automatic air vents and air separators Remove air vent caps and briefly press push valve to flush vent Replace caps Make sure vents do not leak Replace any leaking vents Check expansion tank 1 Expansion tanks provide space for water to move in and out as the heating system water expands due to temperature increase or contracts as the water cools Tanks may be open closed or diaphragm or bladder type See Section 6 Hydronic Piping of the Knight Wall Mount Installation and Operation Manual for suggested best location of expansion tanks and air eliminators Check boiler relief valve 1 Inspect the relief valve and lift the lever to verify flow Before operating any relief valve ensure that it is piped with its discharge in a safe area to avoid severe scald potential Read Section 6 Hydronic Piping of the Knight Wall Mount Installation and Operation Manual before proceeding further hou Service Manual Safety relief valves
12. 28 of this manual E 35 GHT Service Manual WALL MOUNT BOILER 3 Troubleshooting Table 3F continued from previous page Troubleshooting Chart Fault Messages Displayed on Boiler Interface FAULT DESCRIPTION CORRECTIVE ACTION The actual fan RPM is 30 higher than what e Vent air intake lengths exceed the maximum allowed is being called for lengths Refer to Section 3 General Venting of the Knight Wall Mount Installation and Operation Manual for proper lengths Fan High OR e Check for obstruction or blockage in the vent air Fan Speed High intake pipes or at terminations will require a manual reset once the condition e Check the wiring connections at the fan and at the has been corrected Press main control board the RESET button on the SMART SYSTEM display e Replace the fan to reset e Replace the main control board Either the inlet water or outlet water Check the sensors and their associated wiring Sensor Open temperature sensor has been disconnected Repair or replace the sensor or wiring if damaged will require a manual i reset once the condition e Measure the resistance of the sensors and compare has been corrected Press the resistance to the tables on page 30 of this the RESET button on the manual SMART SYSTEM display wra e Replace the sensor if necessary Either the inlet water or outlet water Check the sensors and their associated wiring IA T E A temperature sensor has be
13. 293 will be held to a series of increasing limits after the burner has lit If the space heating call for heat is active and the DHW thermostat closes the control will turn on the DHW pump wait DHW 85 RATE 2 seconds and then turn off the boiler pump This will divert 177 8 180 the hot water away from the heating zone s and send it to the i DHW tank instead The control will then modulate to maintain the outlet temperature to the DHW boiler set point Kuscer Service Manual 1 Service Sequence of operation continued Table 1A continued from previous page Sequence of operation space heating and DHW OPERATION DISPLAY If the DHW thermostat remains on for more than 30 minutes and the space heating call for heat is also on then the control will turn on the boiler pump turn off the DHW pump after 2 SH 41 RATE seconds and resume modulating based on the space heating 7 set point As long as both the space heating and DHW calls for 123 0F 129 heat remain active the control will switch back and forth between the two modes until one of them is satisfied Once both calls for heat are satisfied the control will turn off the burner The blower will remain on for the 10 second postpurge POSTPURGE cycle Any pumps that are running will continue to run for their 127 4F 129 respective pump delay times then turn off Standby 124 7F 129 11 System pump off Standby 122 9F 129 10 Boiler pum
14. 3 15 AMP FUSE GAS VALVE F5 5 AMP FUSE PUMPS F2 3 15 AMP FUSE 24V SUPPLY 5 The boiler is shipped with three 3 spare fuses in a plastic bag provided with the unit 6 If necessary replace open fuse F3 is 1 25 amps F2 and F4 are 3 15 amps and F5 is 5 amps Note Fuses F2 F5 are all slow blow fuses Do not jumper fuse or replace with any fuse except as specified Failure to comply could result in severe personal injury death or substantial property damage 7 Install control module cover and top access cover after fuse inspection 8 Restore power to the boiler at the external line switch and verify boiler operation Section 10 Start up in the Knight Boiler Installation and Operation Manual after completing boiler service Khel Service Manual 3 Troubleshooting continues Table 3A Troubleshooting Chart No Display CORRECTIVE ACTION No 120 vac supplied to unit Check external line switch fuse or breaker Check position of ON OFF switch Turn switch to the ON position Check 120 vac through the ON OFF switch Check wiring harness connection between display board and main control board Connect harness at both points No Display No voltage through the switch e Replace switch Bad display board e Replace board Bad main control board e Replace the main control board Blown fuse e Replace fuse F3 on the main control board see page 28 of this manual Main contr
15. Inspect boiler area and boiler interior Clean condensate trap Check all piping for leaks e Check air openings Flue vent system and air piping e Check water system Check expansion tank e Check boiler relief valve Inspect ignition electrode e Check ignition ground wiring e Check all boiler wiring e Check control settings Perform start up and checks Check burner flame Check flame signal e Check flue gas temperature General maintenance Review with owner Cleaning boiler heat exchanger Oiled bearing circulators Troubleshooting Troubleshooting table No display e Checking temperature sensors Sensor tables Troubleshooting table Fault messages displayed on boiler interface Combustion analysis procedure Gas valve adjustment procedure Kuscer Service Manual 1 Service Near boiler piping This piping reference is included to specify the Near Boiler Piping specific to the Knight wall mount boiler This piping scheme is important for proper operation of the SMART SYSTEM control See the Knight Wall Mount Installation and Operation Manual for more detailed piping diagrams AIR cI VENT FQ DOMESTIC HOT WATER PUMP om INDIRECT 3 DOMESTIC HOT WATER 40 TANK TO FLOOR DRAIN TO sp SYSTEM BOILER PUMP R Es SYSTEM ae poe FROM SYSTEM 6 howl Service Manual 1 Service continued The Knight wall mount display e Press to turn boiler
16. KNIGHT WALL MOUNT BOILER Service Manual Models 50 210 D n Ki OUNT I WALL M OC UP DOWN _ PREVIOUS NEXT A WARNING This manual must only be used by a qualified heating installer service technician Read all instructions z J including this manual and the Onur Knight Wall Mount Installation and Operation ENERGY STAR Manual before installing Perform steps in the order given Failure to comply r could result in severe personal t Lo chinvar injury death or substantial property damage Y High Efficiency Water Heaters Boilers and Pool Heaters A 2 G CERTIFIED Save this manual for future reference CONTENTS cote Sreec cen csnche ete ear eee et 2 2 MAINTENANCE Hazard Definitions naana naana cee ee eee 2 Maintenance and Annual Startup 0005 23 27 PLEASE READ BEFORE PROCEEDING 3 3 TROUBLESHOOTING Handling Ceramic Fiber Materials 3 Before Troubleshooting 5222 000 28 When servicing boiler 0 000 e eee eee 4 Check Control Module Fuses 28 Boiler operation 00 0 cece eee eee 4 Table 3A Troubleshooting Chart No Display 29 Boiler water 0 00 0c cece cece eeeeeeeeeeeee 4 Checking Temperature Sensors 30 Freeze protection fluids 0 00 4 Table 3E Troubleshooting Chart Noisy System
17. Replace the main control board 3 Troubleshooting continued GHT Service Manual WALL MOUNT BOILER Table 3F continued from previous page Troubleshooting Chart Fault Messages Displayed on Boiler Interface FAULT DESCRIPTION CORRECTIVE ACTION Anti cycling No Flame Ign will require a manual reset once the condition has been corrected Press the RESET button on the SMART SYSTEM display to reset The main control board has received a call for heat too quickly after the previous call for heat has ended The unit has failed to prove main burner ignition after four 4 attempts The control board will release the call for heat after a set time period The control board will release the call for heat if the outlet temperature drops too quickly Inspect spark electrode and associated wiring for damage and connection Reference page 26 of this manual for removal and cleaning procedures Replace if necessary Check for proper electrical grounding of the unit Check incoming supply gas pressure Natural gas pressures should be between 4 14 inches w c and LP gas pressures should be between 8 14 inches w c Refer to Section 7 Gas Connections of the Knight Wall Mount Installation and Operation Manual for detailed information concerning the gas supply Verify that the plastic hose from the gas valve to the air inlet is connected and is not damaged Verify that the vent air intake pipes are installed co
18. SCRIPTION The unit was running and lost the flame signal This condition occurred four 4 straight times No Flame Running will require a manual reset once the condition has been corrected Press the RESET button on the SMART SYSTEM display to reset E 34 CORRECTIVE ACTION e Inspect spark electrode and associated wiring for damage and connection Reference page 26 of this manual for removal and cleaning procedures Replace if necessary Check for proper electrical grounding of unit Check incoming supply gas pressure Natural gas pressures should be between 4 14 inches w c and LP gas pressures should be between 8 14 inches w c Refer to Section 7 Gas Connections of the Knight Boiler Installation and Operation Manual for detailed information concerning the gas supply Verify that the plastic hose from the gas valve to the air inlet is connected and is not damaged Verify that the vent air intake pipes are installed correctly and there are no obstructions Check for 24 vac to the gas valve at the 2 pin connection on the side of the main control board during the ignition attempt If no voltage is present replace the main control board If 24 vac is present at the main control board check the wiring between the main control board and the gas valve Replace the wiring if necessary Do not disconnect the wiring from the gas valve and attempt to measure voltage at that point The main control board can detec
19. System Pump Delay 22 No No Yes Yes Os q 5 2 SH Pump Delay 22 No No Yes Yes 22 9 Bs 3 DHW Pump Delay 22 No No Yes Yes a 2 Z 7 ESE m e 1 Service Notification in Month 22 No No Yes Yes a 2 k 2 Service Notification Running Hours 22 No No Yes Yes 2 J L 3 Service Notification Boiler Cycles 22 No No Yes Yes Of o 4 Reset Service Notification Counter 22 No No Yes Yes 2 NOTICE The parameters for Building Management System operation are not listed in this table They are only accessible using the PC interface software See separate documentation for access information See page 21 of this manual for a brief discussion 16 1 Service Service Manual Viewable and changeable control parameters CAUTION Before changing parameters note the settings so that the unit can be returned to its original operating parameters A General Boiler model The control will display Knight Boiler as the model number because the same control is used on several models This will be displayed when parameter A1 has been accessed This parameter is not changeable User code The User Code allows the user to access and change a limited number of control parameters The access code can be changed by the user or the installer to a code of their choosing To change the code parameter A2 must be accessed The default code is 0704 The code can be changed one digit at a time by using the arrow keys on the display Date
20. Y RUN TIME CONTACTS SEQUENCER BUILDING MANAGMENT SYSTEM BOILER PUMP SYSTEM PUMP DHW PUMP IGNITOR BLOWER GAS VALVE DISPLAY PANEL PC INTERFACE 9 1 Service General Operation How the boiler operates The Knight wall mount boiler uses an advanced stainless steel heat exchanger and an electronic control module that allows fully condensing operation The blower pulls in gas and air and pushes flue products out of the boiler through the heat exchanger and flue piping The control module regulates blower speed to control boiler firing rate The gas valve senses the amount of air flowing into the boiler and allows only the right amount of gas to flow How the control module operates The Knight wall mount control module receives input from boiler sensors The control module activates and controls the blower and gas valve to regulate heat input and switches boiler DHW and system pumps on and off as needed The user installer programs the module to meet system needs by adjusting control parameters These parameters set operating temperatures and boiler operating modes Boiler operation can be based on boiler outlet water temperature boiler return water temperature or system supply temperature depending on the parameter setting Sequence of operation Table 1 shows control module normal sequences of operation for space heating and DHW operation The combined operation sequence is for a typical application progr
21. act with skin and eyes Use NIOSH certified dust respirator N95 Service Manual When calling or writing about the boiler Please have the boiler model and serial number from the boiler rating plate Consider piping and installation when determining boiler location see the Knight Wall Mount Installation and Operation Manual Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written Other types of respirators may be needed depending on the job site conditions Current NIOSH recommendations can be found on the NIOSH website at http www cdc gov niosh homepage html NIOSH approved respirators manufacturers and phone numbers are also listed on this website e Wear long sleeved loose fitting clothing gloves and eye protection thoroughly NIOSH stated First Aid E Eye Irrigate immediately E Breathing Fresh air Wash potentially contaminated clothes separately from other clothing Apply enough water to the combustion chamber lining to prevent airborne dust Remove the combustion chamber lining from the boiler and place it in a plastic bag for disposal Rinse clothes washer Kou Service Manual Please read before proceeding When servicing boiler e To avoid electric shock disconnect electrical supply before perfor
22. ally only by a qualified service technician In addition the maintenance and care of the boiler designated in Table 2A and explained on the following pages must be performed to assure Electrical shock hazard Turn off power to the boiler before any service operation on the boiler except as noted A WARNING Aa aves otherwise in this instruction manual Failure to turn off electrical power could result in electrical shock causing severe personal injury or death Address reported problems Figure 2 1 Condensate Trap 1 Inspect any problems reported by the owner and correct before proceeding Inspect boiler area 1 Verify that boiler area is free of any combustible materials 2 Verify that air intake area is free of any of the contaminants listed in Section 1 of the Knight Wall Mount Installation and Operation Manual If any of these are present in the boiler intake air vicinity they must be removed If they cannot be removed reinstall the air and vent lines per this manual and the Knight Wall Mount Installation and Operation Manual Inspect boiler interior 1 Remove the front access cover and inspect the interior of ee CONDENSATE FROM gasoline and other flammable vapors and liquids HEAT EXCHANGER 2 PVC CAP WITH BLOCKED DRAIN SWITCH RETAINING SCREW CONDENSATE DRAIN e REMOVABLE CAP TO CLEAN OUT TRAP the boiler A WARNING The condensate trap must be filled with 2 Vacuum any sediment from in
23. ammed to provide DHW priority 10 Service Manual Access modes User The user can adjust space heating set point using the UP and DOWN buttons at any time during normal operation By entering the USER code 0704 the user can also change temperature units time and date and night setback settings In user mode the following parameters can be viewed but not changed Boiler outlet water temperature in DHW mode boiler model number software version total operating hours and total cycles Installer Most parameters are available only to the installer accessible only by entering the installer access code 5309 Saving parameters To save parameters Press the ENTER RESET button To keep parameter settings only for a current operating cycle Press the MENU EXIT button 1 time to return to the parameter listings press again to return to the menu listings howl Service Manual 1 Service continued Sequence of operation Table 1A Sequence of operation space heating and DHW OPERATION DISPLAY Upon a call for heat the control turns on the appropriate pumps BLR Standby system and boiler pumps for space heating call DHW pump Kojoj uhi Ac RE a Ae for DHW call The control connects 120 vac to the blower The blower does not run at this time e If the unit is equipped with a flow switch or low water cutoff it must close before the control powers up the blower e If the unit is equipped with a manual res
24. call for heat If voltage is not present check the wiring back to the main control board Replace the main control board if necessary If 120 vac is present on a call for heat and the boiler pump is not operating replace the pump Verify that the boiler pump is set to the proper speed or that the boiler pump is the proper size Reference Section 6 Hydronic Piping of the Knight Boiler Installation and Operation Manual for boiler pump specifications 120 vac input to the main control board has Check 120 vac supply to the transformer dropped below 80 vac Check wiring connections at the low voltage terminal Low 24 vac strip Check the wire size length to remote devices Replace the transformer The main control board has detected Replace the main control board MEV Col Lele dela internal fault The main control board has detected Replace the main control board SS internal fault 7 The main control board has detected Replace the main control board ey L ETET TSAN internal fault The main control board has detected Replace the main control board eE TETT A internal fault 1I 39 mE Khel Service Manual 3 Troubleshooting Combustion Analysis Procedure 1 Turn the main power off to the boiler by placing the On Off switch in the OFF position Table 3H Flue Products 2 Remove the flue temperature sensor from the flue pipe NaturalGas Propane connection Note Combustion measurements will be made at
25. display will alternate the standard boiler display text with the message SERVICE DUE every 5 seconds This parameter is adjustable by the installer by accessing parameter J3 The range for this parameter is 0 cycles to 100 000 cycles The default is 10 000 cycles Reset service notification counter Once servicing has been completed the service notification counter should be reset This parameter can be reset by the installer by accessing parameter J4 Once accessed press the RESET key to reset the service notification counter Bhool Service Manual 2 Maintenance Maintenance and annual startup Table 2A Service and Maintenance Schedules Owner maintenance see the Knight Wall Mount User s Information Manual for instructions Service technician see the following pages for instructions General e Address reported problems e Inspect interior clean and vacuum if e Check boiler area necessary E e Check pressure temperature e Clean condensate trap and fill with fresh gauge water eCheck for leaks water gas flue condensate e Verify flue and air lines in good condition and sealed tight e Check vent piping eCheck system water pressure system piping expansion tank e Check air piping e Check control settings oe aaa e Check air and vent termination e Check ignition and flame sense screens electrodes sand off any deposits clean and reposition Monthly e Check wiring and connections Perform start
26. door temperature rises above this point the control will block all SH demands DHW demands will still be active This parameter can be changed by the user or the installer by accessing parameter F5 The temperature range of this parameter is 0 F to 120 F The default value is 80 F Outdoor air shutdown differential The outdoor air shutdown differential parameter is the number of degrees below parameter F5 the outdoor air temperature must go before the boiler will respond to a SH demand This parameter can be changed by the user or the installer by accessing parameter F6 The temperature range of this parameter is 0 F to 90 F The default value is 10 F Shift reset curve The shift reset curve parameter shifts the actual set point above the calculated set point the number of degrees in this parameter This parameter can be changed by the installer by accessing parameter F7 The temperature range of this parameter is 27 F to 27 F The default value is 0 F This feature will be active if this parameter is set to anything other than 0 F 19 1 Service Boost temperature If a SH demand lasts longer than the programmed time delay setting F9 and there have been no DHW demands the control will increase the water temperature set point by the amount in this parameter If the SH demand continues through another time period the set point will be increased again This will continue until either the SH demand ends a maximum of 20
27. e The CO levels should be less than property damage 150 ppm for a properly installed unit If the combustion is not within the specified range reference the chart below for possible causes and corrective actions Table 3G Troubleshooting Chart Combustion Levels POSSIBLE CAUSE CORRECTIVE ACTION e Refer to Section 3 General Venting of the Knight Wall Mount Installation and Operation Vent Air Intake Length Manual for the proper venting and air intake methods for the Knight wall mount boiler or Obstruction Check for obstructions at the vent air intake terminals Gas Supply Pressure Refer to Section 7 Gas Connections of the Knight Wall Mount Installation and Operation Manual for the proper gas supply for the Knight wall mount boiler 3 Refer to page 26 of this manual for burner removal and cleaning procedures Dirty Damaged Burner i Replace burner if necessary Gas Valve Adjustment Refer to page 41 of this manual for the gas valve adjustment procedure 40 GHT Service Manual ALL MOUNT BOILER 3 Troubleshooting continued Gas valve adjustment procedure If adjustment of the gas valve is deemed necessary use the following procedures Locate the throttle adjustment screw on the side of the venturi valve FIG 3 2 Using a screwdriver turn the screw a 1 4 turn clockwise to increase CO levels or a 1 4 turn counterclockwise to decrease CO levels After performing one adjustment on the valve follow the Comb
28. e designated Leader boiler determines the total output needed from the group based on the set point and controlling sensor reading It assigns portions of this output to itself Leader and the Member boilers When Cascade is selected each boiler in the group requires a unique address see below The default control is Thermostat Boiler cascade address The boiler designated as the Leader needs to be programmed with address 0 All the Member boilers require addresses from 1 to 7 and the addresses must be different for each Member The addresses can be in any order regardless of the order in which the units are wired together This parameter is adjustable by the installer by accessing parameter H3 The outdoor air if used and system supply sensor must be connected to the Leader boiler The default address is 1 Max cascade set point This parameter determines the set point used by the individual boilers in a Cascade When a boiler is commanded to fire by the Leader boiler it will attempt to achieve this temperature at its outlet The Leader boiler will limit the modulation of the last boiler to fire in order to hold the temperature at the system supply sensor to the user set point If any of the boiler outlet temperatures reach the max cascade set point the boiler will then modulate down on its own in order to keep its outlet temperature within the max cascade set point Therefore this parameter can be used to limit the outlet tempe
29. ections to switch Wires should be connected to the common and normally closed terminals Air intake lengths exceed the maximum allowed lengths Refer to Section 3 General Venting of the Knight Wall Mount Installation and Operation Manual for proper lengths Check for obstruction or blockage in the air intake pipes or at terminations Check reference hoses connected to the air pressure switch for blockage or obstruction Inspect the burner Reference page 26 of this manual for removal and cleaning procedures Replace if necessary Inspect the heat exchanger Reference page 27 of this manual for removal and cleaning procedures Replace if necessary e Faulty air pressure switch Replace switch howl Service Manual 3 Troubleshooting continued Table 3F continued from previous page Troubleshooting Chart Fault Messages Displayed on Boiler Interface FAUT DESCRIPTION CORRECTIVE ACTION While the unit is in Service Mode the outlet Establish a heating load to remove the heat from the temperature has exceeded 185 F boiler loop e Verify that the system is full of water and that all air has been properly purged from the system e Verify that the boiler is piped properly into the heating system Refer to Section 6 Hydronic Piping of the Knight Wall Mount Installation and Operation Manual for the proper piping methods for the Knight Service Bik wall mount boiler Check 120 vac to the boiler pump motor on a
30. en shorted Repair or replace the sensor or wiring if damaged will require a manual nese once ihe cordiam e Measure the resistance of the sensors and compare ihas haan cormueciail Pes the resistance to the tables on page 30 of this the RESET button on the manual SMART SYSTEM display ee e Replace the sensor if necessary Aux Proving An optional remote proving switch is not Check function of remote devices CUS En EnNEE making reset once the condition e Check for loose or misplaced jumper if auxiliary has been corrected Press proving switch is not installed the RESET button on the SMART SYSTEM display to reset m 36 E howl Service Manual 3 Troubleshooting continued Table 3F continued from previous page Troubleshooting Chart Fault Messages Displayed on Boiler Interface FAULT DESCRIPTION CORRECTIVE ACTION The stack temperature has exceeded the set Inspect the heat exchanger Reference page 27 of parameters for the boiler this manual for the procedure on how to clean the flue side of the heat exchanger Inspect the flue sensor and associated wiring Measure the resistance of the flue sensor and compare to Table 3C on page 30 of this manual Replace the sensor if necessary Verify that the vent air intake pipes are properly installed and that there are no obstructions Replace the main control board The temperature rise across the heat exchanger has exceeded the set parameters for the boi
31. ers if flow switch or the SMART SYSTEM LWCO is not installed display to reset Blown fuse e Replace fuse F2 on the control board see page 28 of this manual The blocked drain switch has detected Check condensate tube from unit to floor drain for Pete IEAn Excessive condensate build up inside the proper installation and obstructions will require a manual unit reset once condition has been corrected Press the RESET button on e Check for loose wiring connection at wire harness the SMART SYSTEM plug display to reset e Inspect condensate trap for blockage Clean if necessary e Bad blocked drain switch Replace switch Flame The flame detector circuit is seeing a flame Check supply voltage for proper polarity Sequence signal while no flame is present will require a manual reset once the condition e Check the flame rod and make sure it is clean has been corrected Press the RESET button e Check the internal wiring for bad connections on the SMART SYSTEM display to reset e Check external wiring for voltage feedback e Replace main control board CAES The main control board did not detect the gas Check wiring harness connection at the gas valve and Fail valve at the main control board will require a manual reset once the condition has been corrected Press the RESET button e Replace the gas valve on the SMART SYSTEM display to reset e Replace the gas valve wire harness e
32. et high limit it must be closed before the control powers up the blower BLR Standby e If the unit is equipped with a solenoid valve and or a vent s valve they will be energized along with the blower OUT 123 8F 129 e If the unit is equipped with a gas pressure switch it must close at this time e If there is an auxiliary device connected to the unit the unit will then provide 24 vac to its enable relay If the auxiliary device has a proving switch it must close before the sequence continues The control then starts a 10 second prepurge cycle PREPURGE 123 9F 129 Once the prepurge cycle is complete and the blocked drain IGNITION switch and auto reset high limit are closed the control starts S the 5 second trial for ignition by sending spark voltage to the 123 9F 129 spark electrode and opening the gas valve If the control does not detect flame by the end of the trial for ignition the control performs a 10 second postpurge another POSTPURGE PREPURGE prepurge and tries to light the burner again If the burner does 123 9F 129 not light after 4 trials the control locks out for 1 hour and then tries another set of 4 trials If the control detects a flame before the trial for ignition ends it begins to modulate the burner in order to maintain the set point SH 20 RATE If the boiler lights due to a space heating call for heat and the 3 ramp delay function is active default is off the modulation 124 8F 1
33. g methods for the Knight wall mount Check 120 vac to boiler pump motor on a call for heat If voltage is not present check wiring back to the main control board Replace the main control board if necessary If 120 vac is present on a call for heat and the boiler Auto Reset pump is not operating replace the pump High Limit If the system pump is a variable speed pump ensure that the system flow is not less than the boiler flow If operating on something other than an outlet sensor check temperature setting of the main control board If the optional manual reset high limit has tripped check setting of the device Check resistance of water sensors and compare to Table 3B on page 30 of this manual Replace sensor if necessary Replace high limit The actual fan RPM is 30 lower than what Vent air intake lengths exceed the maximum allowed is being called for lengths Refer to Section 3 General Venting of the Knight Wall Mount Installation and Operation Manual OR for proper lengths Fan Low Fan Speed Low will require a manual reset once the condition has been corrected Press the RESET button on the SMART SYSTEM display to reset e Replace the fan Check for obstruction or blockage in the vent air intake pipes or at terminations Check the wiring connections at the fan and at the main control board e Replace the main control board Blown fuse e Replace fuse F4 on the control board see page
34. h a setting of 32 F The default value is 32 F Night setback times If parameter A6 is set to anything other than 32 F the night setback feature becomes active This will require start and stop times to be programmed for the days that reduced temperatures are required These times can be changed by the user or the installer by accessing parameter A7 Each day of the week Sunday through Saturday will have an on and off time Example Monday ON 22 30 Tuesday OFF 6 45 If you wish to skip a day and have no night setback leave the on and off times the same The default times for each day will be 00 00 midnight B Temperature settings SH set point user The SH set point user sets the water temperature set point for fixed operation or the maximum temperature set point when the outdoor air sensor is used This parameter can be changed by the user or the installer by accessing parameter B1 The temperature range of this parameter is 50 F to 190 F The default value is 125 F SH minimum set point The SH minimum set point sets the minimum water temperature set point that can be used for space heating operation The user or installer will not be able to program the control with a lower SH set point This parameter can only be changed by the installer by accessing parameter B2 The temperature range of this parameter is 32 F to 190 F The default value is 70 F SH Maximum set point The SH maximum set point sets the maximu
35. increases has occurred or the maximum set point has been reached Once the SH demand has been satisfied the set point will revert back to its calculated setting The boost temperature can be changed by the installer by accessing parameter F8 The temperature range of this parameter is 0 F to 45 F The default value is 0 F This feature will be active if this parameter is set to anything other than O F Boost time The boost time parameter sets the amount of time that must elapse with a SH demand before the water temperature set point will be increased This parameter can be changed by the installer by accessing parameter F9 The time range for this parameter is 1 minute to 60 minutes The default value is 20 minutes 20 Service Manual G Anti cycling Anti cycling time Once a SH demand has been satisfied a set amount of time must elapse before the control will respond to a new SH demand The control will block the new heat demand and anti cycling will be shown in the display until the time has elapsed or the water temperature drops below parameter G2 This parameter can be changed by the installer by accessing parameter G1 The time range for this parameter is 0 minutes to 40 minutes The default value is 1 minute Inlet temperature differential for ending anti cycling The control will bypass the anti cycling time if the water temperature drops too quickly The control will use the water temperature the boiler was at when it
36. l The temperature range of this parameter is 30 F to 90 F The default value is 25 F Maximum air temperature When the outdoor air temperature rises to or above this point the water temperature will be at its minimum setting FIG 1 1 This parameter can be changed by the installer by accessing parameter F2 The temperature range of this parameter is 30 F to 90 F The default value is 70 F 1 Service continued Figure 1 1 Outdoor Air Reset Curve WATER TEMPERATURE SET POINT MAXIMUM RESET Default 180 F USER SET POINT Default 125 F MINIMUM RESET Default 70 F Default 25 F Default 70 F OUTDOOR AIR Service Manual OUTDOOR OUTDOOR AIR TEMPERATURE AT MINIMUM RESET AT MAXIMUM RESET Maximum SH set point When the outdoor temperature drops to or below its minimum setting F1 the water temperature will be at this point if the SH set point is set higher FIG 1 1 This parameter can be changed by the installer by accessing parameter F3 The temperature range of this parameter is 0 F to 190 F The default value is 180 F Minimum SH set point When the outdoor temperature rises to or above its maximum setting F2 the water temperature will be at this point FIG 1 1 This parameter can be changed by the installer by accessing parameter F4 The temperature range of this parameter is 0 F to 190 F The default value is 70 F Outdoor air shutdown When the out
37. l Mount User s Information Manual with the owner 2 Emphasize the need to perform the maintenance schedule specified in the Knight Wall Mount User s Information Manual and in this manual as well 3 Remind the owner of the need to call a licensed contractor should the boiler or system exhibit any unusual behavior 4 Remind the owner to follow the proper shutdown procedure and to schedule an annual start up at the beginning of the next heating season Cleaning boiler heat exchanger 1 Shut down boiler Follow the To Turn Off Gas to Appliance instructions for the boiler in the Knight Wall Mount Installation and Operation Manual Do not drain the boiler unless it will be exposed to freezing temperatures If using freeze prevention fluid in system do not drain 2 Allow time for the boiler to cool to room temperature if it has been firing 3 Remove the blower assembly gas air arm from the heat exchanger access cover Set bolts aside 4 Remove the nuts securing the heat exchanger access cover to the heat exchanger and set aside howl Service Manual 5 Remove the heat exchanger access cover cover gasket s and chamber insulation assembly A WARNING The boiler contains ceramic fiber materials Use care when handling these 10 ll 12 13 materials per instructions on page 3 of this manual Failure to comply could result in severe personal injury Use a vacuum cleaner to remove any acc
38. l number of times the boiler has attempted to fire This parameter can be viewed by the user and the installer by accessing parameter C3 Show last 10 errors The control will log the 10 most current errors with the date and time the error occurred This parameter can be viewed by the user and the installer by accessing parameter C4 D Functions Reset last 10 errors The reset last 10 errors parameter allows the error counter to be reset to 0 This parameter can only be cleared by the installer by accessing parameter D1 Once accessed press the RESET key to clear the counter Service mode delay By pressing the pin button on the front of the display for five 5 seconds the control will be placed in Service Mode This will override all other heat demands The Service Mode allows the installer to set the unit to either maximum firing rate or minimum firing rate for the purpose of combustion analysis The delay sets the length of time the boiler will stay in the Service Mode if no keys have been pressed before going back to its original state This parameter can only be changed by the installer by accessing parameter D2 The time range of this parameter is 0 to 40 minutes The default value is 20 minutes 18 Service Manual E DHW settings DHW boiler set point When a DHW call for heat becomes active the control will use the DHW boiler set point to determine the firing rate of the boiler based on the actual water temperature
39. ler Verify that the system is full of water and that all air has been properly purged from the system Verify that the boiler is piped properly into the heating system Refer to Section 6 Hydronic Piping of the Knight Wall Mount Installation and Operation Manual for the proper piping methods for the Knight wall mount boiler Check for 120 vac to the boiler pump motor on a call Temp O Shoot for heat If voltage is not present check the wiring back to the main control board Replace the main control board if necessary If 120 vac is present on a call for heat and the boiler pump is not operating replace the pump Verify that the boiler pump is set to the proper speed or that the pump is the proper size Reference Section 6 Hydronic Piping of the Knight Wall Mount Installation and Operation Manual for boiler pump specifications Outlet water temperature has exceeded the Verify that the system is full of water and that all air maximum outlet water temperature has been properly purged from the system Verify that the boiler is piped properly into the heating system Refer to Section 6 Hydronic Piping of the Knight Wall Mount Installation and Operation Manual for the proper piping methods for the Knight wall mount boiler Check for 120 vac to the boiler pump motor on a call for heat If voltage is not present check wiring back to the main control board Replace the main control board if necessary e If 120 vac is pre
40. m water temperature set point that can be used for space heating The user or installer will not be able to program the control with a higher SH set point This parameter can only be changed by the installer by accessing parameter B3 The temperature range of this parameter is 32 F to 190 F The default value is 190 F SH Offset The SH offset sets how many degrees above set point the temperature has to go before the boiler will shut off This parameter can only be changed by the installer by accessing parameter B4 The temperature range of this parameter is 0 F to 86 F The default value is 10 F 17 1 Service SH Differential The SH differential sets how many degrees below the turn off temperature the temperature has to go before the boiler will turn on This parameter can only be changed by the installer by accessing parameter B5 The temperature range of this parameter is 0 F to 86 F The default value is 20 F C Data logging Hours running SH The hours running SH parameter shows the total number of hours the boiler has been in the SH firing position This parameter can be viewed by the user and the installer by accessing parameter Cl Hours running DHW The hours running DHW parameter shows the total number of hours the boiler has been in the DHW firing position This parameter can be viewed by the user and the installer by accessing parameter C2 Ignition attempts The ignition attempts parameter shows the tota
41. ming maintenance e To avoid severe burns allow boiler to cool before performing maintenance Boiler operation Do not block flow of combustion or ventilation air to the boiler Should overheating occur or gas supply fail to shut off do not turn off or disconnect electrical supply to circulator Instead shut off the gas supply at a location external to the appliance Do not use this boiler if any part has been under water The possible damage to a flooded appliance can be extensive and present numerous safety hazards Any appliance that has been under water must be replaced Boiler water Thoroughly flush the system without boiler connected to remove sediment The high efficiency heat exchanger can be damaged by build up or corrosion due to sediment Do not use petroleum based cleaning or sealing compounds in the boiler system Gaskets and seals in the system may be damaged This can result in substantial property damage Do not use homemade cures or boiler patent medicines Serious damage to the boiler personnel and or property may result Continual fresh make up water will reduce boiler life Mineral buildup in the heat exchanger reduces heat transfer overheats the stainless steel heat exchanger and causes failure Addition of oxygen carried in by makeup water can cause internal corrosion Leaks in boiler piping must be repaired at once to prevent the introduction of makeup water
42. not avoided may result in minor or moderate A CAUTION a CAUTION CAUTION used without the safety alert symbol indicates a potentially hazardous situation which if not avoided may result in property damage NOTICE indicates special instructions on installation operation or maintenance that are important but not related to personal injury or property damage NOTICE Please read before proceeding Installer Read all instructions including this manual and the Knight Wall Mount Installation and Operation Manual before installing Perform steps in the order given User This manual is for use only by a qualified heating installer service technician Refer to the Knight Wall Mount User s Information Manual for your reference Have this boiler serviced inspected by a qualified service technician at least annually Failure to comply with the above could result in severe personal injury death or substantial property damage Handling ceramic fiber materials REMOVAL OF COMBUSTION CHAMBER LINING A WARNING The combustion chamber door insulation in this product contains ceramic fiber material Ceramic fibers can be converted to cristobalite in very high temperature applications The International Agency for Research on Cancer IARC has concluded Crystalline silica inhaled in the form of quartz or cristobalite from occupational sources is carcinogenic to humans Group 1 NOTICE HM Avoid breathing dust and cont
43. off or Hold 5 seconds to enter code back on Input Mode Menu Mode e Press to select a menu item Press to move up one level e Press after parameter programming in Menu Mode or to exit to store parameter data Menu Mode e Press to exit Service Mode MENU EXIT ENTER RESET mJ DISPLAY SCREEN EJ T p MENU EXIT ENTER RESET SERVICE O BUTTON PC CONNECTION PREVIOUS NEXT PORT lt D gt PREVIOUS NEXT UP DOWN e Press to change boiler water Press to toggle display during normal temperature set point during operation to show outlet and return normal operation temperatures fan speed and flame e Press to change displayed data signal i values in Menu Mode Press to toggle between digits when e Press to navigate through menu entering access code or between hour listing in Menu Mode minutes etc when entering date and time GHT Service Manual 1 Service Control inputs GAS PRESSURE SWITCH DHW THERMOSTAT ROOM THERMOSTAT ZONE CONTROL LOW VOLTAGE FLOW SWITCH CONNECTION BOARD SYSTEM SENSOR OUTDOOR SENSOR SEQUENCER BUILDING MANAGMENT SYSTEM LOW WATER CUTOFF INLET TEMPERATURE SENSOR OUTLET TEMPERATURE HIGH LIMIT SENSOR FLUE GAS SENSOR ox SMART CONTROL MODULE 1 Service continued Control outputs LOW VOLTAGE CONNECTION BOARD 7 i I SMART CONTROL MODULE Service Manual ALARM BELL AUX DEVICE RELA
44. ol board temperature set point Review temperature setting satisfied Remote thermostat satisfied e Review remote thermostat setting Outside air temperature above Warm Check location of outside air sensor Check Weather Shutdown WWSD set point for resistance of outdoor air sensor and compare to Table main control board 3D on page 30 of this manual No Burner Operation Unit locked out on fault Consult display for specific fault Refer to fault descriptions on page 32 of this manual for corrective actions Ramp delay active Check ramp delay parameter settings Optional PC software required Turn ramp delay feature off See page 20 of this manual for instructions on how to turn this feature off Check BMS parameter settings Optional PC software required Unit Does Not Modulate Above 50 Flue sensor open e Verify that the flue sensor is located in the flue outlet Boiler controlled by BMS e Check wiring connections at the flue sensor e Check the resistance of the flue sensor and compare to Table 3C on page 30 of this manual 29 Bho Service Manual 3 Troubleshooting Checking temperature sensors The boiler temperature sensors inlet water outlet water system water flue and outdoor air are all resistance type devices The following tables show the correct values for the sensors at various temperatures Use an ohmmeter to read the resistance of the sensor at a known temperature If
45. or press MENU EXIT to continue OUT 123 7 F display as you exit menu mode ENTER RES Press 1 time to return to normal SH Pre Purge This display example assumes operation OUT 123 7 F a call for space heating is present 14 GHT Service Manual WALL MOUNT BOILER 1 Service continued Parameter table Table 1D This table lists SMART SYSTEM control module parameters and where to access them SEE USER ACCESS INSTALLER ACCESS MENU SUB ITEM DESCRIPTION PAGE DISPLAY MODIFY DISPLAY MODIFY 1 Boiler Model 17 Yes No Yes No s 2 User Code re Yes Yes Yes Yes u 3 Date and Time 17 Yes Yes Yes Yes W 6 A 4 Software Version 1 Yes No Yes No 5 Temperature Units 17 Yes Yes Yes Yes 6 Night Setback Temperature 17 Yes Yes Yes Yes 7 Night Setback Times 17 Yes Yes Yes Yes W 1 SH Set Point User id Yes Yes Yes Yes pa 2 SH Minimum Set Point 17 No No Yes Yes zZ E B 3 SH Maximum Set Point 17 No No Yes Yes w S a 4 SH Offset 17 No No Yes Yes u 5 SH Differential 18 No No Yes Yes 1 Hours Running SH 18 Yes No Yes No oO dZ 2 Hours Running DHW 18 Yes No Yes No E C qo m a 3 Ignition Attempts 18 Yes No Yes No e 4 Show Last 10 Errors 18 Yes No Yes No w Z Q 1 Reset Last 10 Errors 18 No No Yes Yes Fe
46. own the boiler until a new relief valve has been installed After following the above warning directions if the relief valve weeps or will not seat properly replace the relief valve Ensure that the reason for relief valve weeping is the valve and not over pressurization of the system due to expansion tank waterlogging or undersizing 25 2 Maintenance Inspect ignition and flame sense electrodes 1 Remove the ignition and flame sense electrodes from the boiler heat exchanger access cover 2 Remove any deposits accumulated on the ignition flame sense electrode using sandpaper If the electrodes cannot be cleaned satisfactorily replace with new ones 3 Replace ignition flame sense electrode making sure gasket is in good condition and correctly positioned Check ignition ground wiring 1 Inspect boiler ground wire from the heat exchanger access cover to ground terminal strip 2 Verify all wiring is in good condition and securely attached 3 Check ground continuity of wiring using continuity meter 4 Replace ground wires if ground continuity is not satisfactory Check all boiler wiring 1 Inspect all boiler wiring making sure wires are in good condition and securely attached Check control settings 1 Set the SMART SYSTEM control module display to Parameter Mode and check all settings See Section 1 of this manual Adjust settings if necessary See Section 1 of this manual for adjustment procedures
47. p off system pump continues its delay if longer 12 howl Service Manual 1 Service continued Display panel menu access Table 1B Use this procedure to access menus from the display panel BUTTON OPERATION DISPLAY COMMENTS RREA p Himei i ti B O Boiler turns off this ensures ress Ume N Rorma operation PMP O uninterrupted programming l Enter Menu Code Digit shown underlined at left will MENU EXIT Hold for 5 seconds display will change flash A uP Press 9 times to change last digit Enter Menu Code Digit shown underlined at left will in readout to 9 0009 flash lt q PREVIOUS Press 2 times to move to the second Enter Menu Code Digit shown underlined at left will digit 0009 flash A UP Press 3 times to change second digit Enter Menu Code Digit shown underlined at left will in readout to 3 0309 flash lt q PREVIOUS Press 1 time to change to the first Enter Menu Code Digit shown underlined at left will digit 0309 flash A ue Press 5 times to change first digit Enter Menu Code Digit shown underlined at left will in readout to 5 5309 flash If you enter a digit incorrectly you can move to the digit by using the NEXT and PREVIOUS buttons as needed until the digit you want is flashing Then use UP and or DOWN buttons to change the value Enter Menu Code The words INSTALLER CODE O ENTER RES Press to enter the code will flash while dis
48. played z After 2 seconds display shows menus gt A General The caret symbol gt highlights press ENTER RESET to select a menu B Temp Settings the selectable line If the code is entered incorrectly the display will return to its previous mode You will have to start over at step 1 to enter the code A General The caret symbol gt highlights gt B Temp Settings the selectable line gt C Data Logging The menu toggles to the next two D Functions menu options gt E DHW Settings The menu toggles to the next two F Outdoor Reset menu options gt G Anti cycling The menu toggles to the next two H Control Modes menu options Ww DOWN Press 1 time to highlight second listing Ww DOWN Press 1 time to toggle menu listing Ww DOWN Press 2 times to toggle menu listing y DOWN Press 2 times to toggle menu listing wv DOWN Press 2 times to toggle menu listing V H ie H W ie H w t H e B ue 0 The menu toggles to the next two nE AEREE ENU Options To select a highlighted menu press the ENTER RESET button one time The display will change to the first parameter under that menu with the first characters flashing 13 1 Service Display panel parameter access GHT Service Manual WALL MOUNT BOILER Table 1C This is a typical example of accessing a parameter shown for parameter 12 boiler pump delay
49. r is 0 minutes to 40 minutes The default time is 30 seconds DHW pump delay The DHW pump delay parameter sets the length of time the DHW pump if connected will run after a DHW demand has been satisfied Setting the delay time to 0 will disable the pump This parameter is adjustable by the installer by accessing parameter I3 The time range for this parameter is 0 minutes to 40 minutes The default time is 30 seconds J Service Notification Service notification in months When the boiler control determines that a scheduled service is due based on days of installation the boiler display will alternate the standard boiler display text with the message SERVICE DUE every 5 seconds This parameter is adjustable by the installer by accessing parameter J1 The time range for this parameter is 0 months to 36 months The default time is 12 months 22 Service Manual Service notification running hours When the boiler control determines that a scheduled service is due based on the hours of actual operation the boiler display will alternate the standard boiler display text with the message SERVICE DUE every 5 seconds This parameter is adjustable by the installer by accessing parameter J2 The time range for this parameter is 0 hours to 100 000 hours The default time is 10 000 hours Service notification boiler cycles When the boiler control determines that a scheduled service is due based on the number of boiler cycles the boiler
50. ratures of all the boilers in a Cascade Note that this parameter does not apply when the boiler is heating an indirect DHW tank This parameter is adjustable by the installer by accessing parameter H4 The default max cascade set point is 185 F 21 1 Service Cascade offset This parameter determines how much the temperature must go above set point before the lead boiler will turn off This parameter can be adjusted by the installer by accessing parameter H5 The default value is 9 9 F Cascade off on differential This parameter determines how much the temperature must go below the turn off temperature Set point Offset before the lead boiler turns on This parameter can be adjusted by the installer by accessing parameter H6 The default value is 19 8 F I Circulation pumps System pump delay The system pump delay parameter sets the length of time the system pump if connected will run after a SH demand has been satisfied Setting the delay time to 0 will disable the pump This parameter is adjustable by the installer by accessing parameter I1 The time range for this parameter is 0 minutes to 40 minutes The default time is 30 seconds SH pump delay The SH pump delay parameter sets the length of time the boiler pump will run after a SH demand has been satisfied Setting the delay time to 0 will disable the pump This parameter is adjustable by the installer by accessing parameter I2 The time range for this paramete
51. rol will use to regulate the boiler firing rate This parameter is adjustable by the installer by accessing parameter H1 The sensor selections are as follows The outlet sensor regulates the firing rate based on the outlet water temperature of the boiler and the inlet sensor regulates the firing rate based on the inlet water temperature of the boiler If the outlet sensor is selected and the optional system supply sensor is connected the control will regulate the firing rate based on the system supply sensor temperature The default sensor is the Outlet Sensor SH source The SH source parameter selects the method used to control the modulation of the boiler This parameter is adjustable by the installer by accessing parameter H2 The control methods are as follows 1 Thermostat The control modulates the boiler based on the user set point and the temperature of the selected controlling sensor 2 BMS Building Management System The control modulates the boiler based on the 0 10 vdc signal delivered to the appropriate terminals on the connection board When BMS is selected additional parameters for BMS operation may need to be adjusted These can only be accessed by the optional PC software See the Knight Wall Mount Smart System PC Program Instructions Manual for additional BMS parameter information TIME TIME MINUTES TIME 3 TIME 5 TIME 2 4 6 3 Cascade The boiler is part of a group of boilers sequenced together Th
52. rrectly and that there are no obstructions Check for 24 vac to the gas valve at the 2 pin connection on the side of the main control board during the ignition attempt If no voltage is present replace the main control board If 24 vac is present at the main control board check the wiring between the main control board and the gas valve Replace the wiring if necessary Do not disconnect the wiring from the gas valve and attempt to measure voltage at that point The main control board can detect if the gas valve is not connected and will display the Gas Valve or Gas Valve Fail fault If 24 vac is present check the outlet of the valve to ensure the valve is flowing gas With a manometer connected to the outlet tap of the gas valve when the unit is in the prepurge period there should be a negative pressure present When the valve is energized a change in pressure should occur If the pressure change does not occur the gas valve is not opening Replace the gas valve Inspect flame sensor and associated wiring Reference page 26 of this manual for removal and cleaning procedures Replace if necessary Inspect the burner Reference page 26 of this manual for removal and cleaning procedures Replace if necessary Replace the main control board 33 3 Troubleshooting GHT Service Manual WALL MOUNT BOILER Table 3F continued from previous page Troubleshooting Chart Fault Messages Displayed on Boiler Interface DE
53. sent on a call for heat and the boiler pump is not operating replace the pump 37 3 Troubleshooting Service Manual Table 3F continued from previous page Troubleshooting Chart Fault Messages Displayed on Boiler Interface FAULT DESCRIPTION CORRECTIVE ACTION Temp O Shoot continued will require a manual ECA No Outlet water temperature has exceeded the Web ycomesercatemiuresy Maximum outlet water temperature the RESET button on the SMART SYSTEM display to reset Rem Ctrl Fit External control is cycling too often Parameters Progr will require a manual After downloading parameters from a laptop SSeS SIUC the main control board must be reset has been corrected Press the RESET button on the SMART SYSTEM display to reset APS Open will require a manual reset once the condition has been corrected Press the RESET button on the SMART SYSTEM display to reset Air pressure switch contacts are open 35 E e Verify that the boiler pump is set to the proper speed or that the boiler pump is the proper size Reference Section 6 Hydronic Piping of the Knight Wall Mount Installation and Operation Manual for boiler pump specifications Replace the main control board Check set point of the external control Check the wiring between the external control and the unit Replace the control Press the ENTER RESET button on the SMART SYSTEM display panel Check the wiring conn
54. should be re inspected eee AT LEAST ONCE EVERY THREE YEARS by a licensed plumbing contractor or authorized inspection agency to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally Certain naturally occurring conditions may corrode the valve or its components over time rendering the valve inoperative Such conditions are not detectable unless the valve and its components are physically removed and inspected This inspection must only be conducted by a plumbing contractor or authorized inspection agency not by the owner Failure to re inspect the boiler relief valve as directed could result in unsafe pressure buildup which can result in severe personal injury death or substantial property damage Following installation the valve lever A WARNING must be operated AT LEAST ONCE A YEAR to ensure that waterways are clear Certain naturally occurring mineral deposits may adhere to the valve rendering it inoperative When manually operating the lever water will discharge and precautions must be taken to avoid contact with hot water and to avoid water damage Before operating lever check to see that a discharge line is connected to this valve directing the flow of hot water from the valve to a proper place of disposal Otherwise severe personal injury may result If no water flows valve is inoperative Shut d
55. side the boiler and water during all times of boiler operation to components Remove any obstructions Clean condensate trap 1 Remove the clean out cap on the bottom of the trap Let the avoid flue gas emission from the condensate drain line Failure to fill the trap could result in severe personal injury or death condensate and any debris drain out Check all piping for leaks 2 Fill with fresh water until the water begins to pour out of the Eliminate all system or boiler leaks drain A WARNING Continual fresh makeup water will reduce 3 Replace the clean out cap and resume operation N e p 24 boiler life Minerals can build up in sections reducing heat transfer overheating heat exchanger and causing heat exchanger failure Leaking water may also cause severe property damage Inspect all water and gas piping and verify to be leak free Look for signs of leaking lines and correct any problems found Check gas line using the procedure found in Section 7 Gas Connections of the Knight Wall Mount Installation and Operation Manual 2 Maintenance continued Flue vent system and air piping 1 Visually inspect the entire flue gas venting system and air piping for blockage deterioration or leakage Repair any joints that show signs of leakage Verify that air inlet pipe is connected and properly sealed 2 Verify that boiler vent discharge and air intake are clean and free of obstructions A WARNING Failure
56. t if the gas valve is not connected and will display the Gas Valve or Gas Valve Fail fault If 24 vac is present check the outlet of the valve to ensure the valve is flowing gas With a manometer connected to the outlet tap of the gas valve when the unit is in the prepurge period there should be a negative pressure present When the valve is energized a change in pressure should occur If the pressure change does not occur the gas valve is not opening Replace the gas valve Inspect flame sensor and associated wiring Reference page 26 of this manual for removal and cleaning procedures Replace if necessary Inspect the burner Reference page 26 of this manual for removal and cleaning procedures Replace if necessary e Replace the main control board GHT Service Manual WALL MOUNT BOILER 3 Troubleshooting continued Table 3F continued from previous page Troubleshooting Chart Fault Messages Displayed on Boiler Interface FAULT DESCRIPTION CORRECTIVE ACTION The outlet water temperature has exceeded Verify that the system is full of water and that all air the fixed setting of the automatic reset high has been properly purged from the system limit or the setting of an optional manual i iv into the heati reset high limit Verify that the boiler is piped properly into the heating system Refer to Section 6 Hydronic Piping of the Knight Wall Mount Installation and Operation Manual for the proper pipin
57. this point oe co 3 Turn the main power on to the boiler by placing the 8 0 10 3 0 6 5 9 0 11 4 1 6 9 On Off switch in the ON position 8 Once the combustion analysis is complete test the safety 4 Place the boiler into the active position by pressing the shutoff device by turning the manual shutoff valve to the ENTER RESET button on the display board see page 7 OFF position and ensuring that the boiler shuts down until BLR Standby appears in the display window and registers an alarm Open the manual shutoff valve nae reset the control and return to Service Mode 5 Locate the pinhole button above the T in the Knight logo on the display board see page 7 Press the button 9 Turn the main power off to the boiler and replace the flue once and hold for 5 seconds to place the boiler into temperature sensor into the flue pipe connection Service Mode In Service Mode the boiler will fire at ignition speed and will then modulate up to full fire 10 Place the boiler back into normal operation 6 Insert the probe from a combustion analyzer into the hole left by the removal of the flue temperature sensor You must replace the flue a eg eA sensor to prevent flue gas spillage into the 7 Once the boiler has modulated up to full fire measure the room Failure to comply could result in combustion The values should be in the range listed in severe personal injury death or substantial Table 3H abov
58. tlined in the Troubleshooting chart Severe personal injury death or substantial property damage can result Before troubleshooting 1 Have the following items a Voltmeter that can check 120 vac 24 vac and 12 vdc b Continuity checker c Contact thermometer 2 Check for 120 vac minimum 102 vac to maximum 132 vac to boiler 3 Make sure thermostat is calling for heat and contacts including appropriate zone controls are closed Check for 24 vac between thermostat wire nuts and ground 4 Make sure all external limit controls are installed and operating Check the following 1 Wire connectors to control module are securely plugged in at the module and originating control 2 Gas pressures e Maximum 14 inches w c natural and LP with no flow lockup or with boiler on e Minimum 4 inches w c natural 8 inches w c LP with gas flowing verify during boiler startup 28 Service Manual Check control module fuses Notice Always check control module fuses before replacing control module or any major components blower etc If one of these fuses is blown it can prevent the control module or other components from operating 1 Turn OFF the power to the boiler at the external line switch 2 Remove top access cover 3 Remove the control module cover 4 Inspect fuses F2 F3 F4 and F5 see FIG 5 below Figure 3 1 Control Module Fuses F3 1 25 AMP FUSE MAIN BOARD F4
59. umulation on the boiler heating surfaces Do not use any solvent Finish cleaning using a clean cloth dampened with warm water Install access cover gasket chamber insulation assembly and cover Secure nuts on the studs DO NOT overtighten Re install the blower assembly gas air arm using the bolts set aside in Step 3 Close isolation valves on piping to isolate boiler from system Attach a hose to the boiler drain and flush boiler thoroughly with clean water by using purging valves to allow water to flow through the water make up line to the boiler When the boiler has been flushed restore boiler to operation Perform start up and check out procedures in the Knight Wall Mount Installation and Operation Manual Oiled bearing circulators The circulator shipped with the Knight wall mount boiler is water lubricated No oiling is required Check other circulators in the system Oil any circulators requiring oil following circulator manufacturer s instructions Over oiling will damage the circulator Replace the boiler front access cover 27 3 Troubleshooting ZX WARNING Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Always disconnect power to the boiler before servicing Failure to comply could result in severe personal injury death or substantial property damage Never jumper bypass any device except for momentary testing as ou
60. up checkout and e Check condensate drain system performance verification per Section 10 in the Knight Wall Mount Installation and e Check automatic air vents Operation Manual e Check relief valve a 2 lt E no m lt D2 d Z lt x e Flame inspection stable uniform Test low nater citon itus e Flame signal at least 10 microamps at Periodically high fire e Reset button low water cutoff Clean the heat exchanger if flue temperature is more than 54 F above return water temperature e Check boiler piping gas and Eve water for leaks If combustion or performance Ar indicate need Operate relief valve e Clean heat exchanger e Remove and clean burner using compressed air only e Clean the blower wheel End e Shut boiler down unless boiler of season used for domestic hot water months 2 Maintenance Kou Service Manual Follow the Service and maintenance procedures given throughout this manual and in component literature A WARNING f i shipped with the boiler Failure to perform the service and maintenance could result in damage to the boiler or system Failure to follow the directions in this manual and component literature could result in severe personal injury death or substantial property damage maximum boiler efficiency and reliability Failure to service and maintain the boiler and system could result in equipment failure A WARNING The boiler should be inspected annu
61. ustion Analysis Procedure on page 40 of this manual to measure the combustion If combustion is still not within the specified range repeat the procedure This procedure SHOULD NOT be performed more than four 4 times If after four 4 adjustments and the combustion is still not within the specified range revisit the possible causes in Table 3G on page 40 or replace the gas valve Figure 3 2 Gas Valve Adjustment THROTTLE ADJUSTMENT SCREW mm 47 Kho Service Manual 4 Notes 42 Khel Service Manual 4 Notes 43 Revision Notes Revision B ECO C02407 reflects air pressure switch changes removal of references to the pocket pc and changes made to the Circulation Pumps Section page 22 Revision C ECO C02545 reflects the addition of references to periodic cleaning of screens in vent terminations and safety shutoff testing and instructions WB SER Rev C 11 08

Download Pdf Manuals

image

Related Search

Related Contents

Samsung WF1802XEU 用户手册  Zanussi ZOU 481 User's Manual    Brodit 511666 holder  

Copyright © All rights reserved.
Failed to retrieve file