Home

Graco 1759162 Baby Swing User Manual

image

Contents

1. STEP 2 Place the metal grate on top of the burner Position the legs of the grate into the for ward set of indentations in the burner top sliding the grate forward See Figure 14 8 STEP 3 Log 1 NG SRV2101 085 Log 1 LP SRV2101 087 Log 1 is the left burning log The air shut ter in the end of the burner tube goes over the left brass orifice located behind the main burner The left end of the log goes tight against the left refractory wall See Figures 14 9 and 14 10 2101 910 54 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 9 SEigure 14 119Eront View i s E hne rr oor PC eenegen Ae eg STEP A Log 2 NG SRV2101 086 Log 2 LP SRV2101 088 Log 2 is the right burning log The air shutter in the end of the burner tube goes over the right brass orifice located behind the main burner The right end of the log goes tight against the right refractory wall RISE K d SE T m I KE ris ACUOLAR SIE A ecd Is STEP 5 Log 3 SRV2101 197 Place log 3 on top of the burner surface in front of the hump Slide it back against the hump and the V notch in the bottom of the log rests into the second grate tine from the left PA Figure 14 15 Front Viewsne LLL A L 9 rires V i STEP 6 Log 4 SRV386 716 Place log 4 on top of the left side of log 2 The bottom of this log has a slot in it that goes over the tab molded into the top of log 2 The other
2. WAL Heat 3 in 76 mm Shield top clearance Heat Shield 1 in 25 mm Wall clearance Shield bottom amp sides Firestop WALL When using SLP or SL D pipe minimum clearances from the vent pipe to combus tible materials at inside wall firestops are Top 2 1 2 in 64 mm Bottom 1 2 in 13 mm Sides 1 in 25 mm Figure 8 1 Horizontal Venting Clearances To Combustible Materials B Wall Penetration Framing Combustible Wall Penetration Whenever a combustible wall is penetrated you must frame a hole for the wall shield firestop s The wall shield firestop maintains minimum clearances and prevents cold air infiltration The opening must be framed on all four sides using the same size framing materials as those used in the wall construction SLP pipe A wall shield firestop must be placed on each side of an interior wall A minimum 1 1 2 in 38 mm overlap of attached heat shields must be maintained DVP pipe A wall shield firestop is required on one side only on interior walls If your local inspector requires a wall shield firestop on both sides then both wall shield firestops must have a heat shield refer to Section 16 B attached to them See Section 10 M for information for regarding the in stallation of a horizontal termination cap Non Combustible Wall Penetration If the hole being penetrated is surrounded by noncom bustible materials s
3. Figure 14 3 52 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 STEP 4 Refer to the details in Figure 14 5 to position Optional Refractory Standoff Bracket Note If fireplace is rear vented and has no elbows in the vent run adjusting the refractory standoff bracket is allowed If any elbows are used in the vent run DO NOT adjust the refractory standoff bracket Remove screw shown in Detail A Bend down back flap along the two 2 perforations to break back flap from refractory standoff bracket See Detail B Rotate the separated piece and bend the back flap as shown in Detail C to enable the tabs to fit into the two 2 holes on the left and right of the refractory standoffs indicated in Detail D Verify that the back flap rests on top of left and right refractory standoff tabs noted in Detail E LA L Standoff Bracket DETAIL A DETAIL B DETAIL C DETAIL D DETAIL E Figure 14 4 STEP 5 Hold the top refractory with the brick pattern facing down Bring the back edge into the firebox slightly higher than the front edge Bring the back edge all the way to the metal back wall of the fireplace Raise the front edge up until it clears the side refractory pieces Drop the back edge down and nest the sides and back into the groove around the edges of the top piece of refractory Figure 14 5 F Ember Placement WARNING Risk of Exp
4. 11 7 8 in 302 mm 5 in 4 127 mm N L s o SN DVP BEK2 DVP HPC Cap Brick Extension 146 mm COOL ADD Cap Shield 13 7 8 in L 352 mm 9 1 2 in 241 mm lt a gt j 14 in 356 mm Go DRC RADIUS Cap Shield Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 63 B Vent Components Diagrams continued 7 3 8 in 187 mm 1 1 2 in 17 3 4 in ue in l 451 mm mm 12 in lt 305 mm DVP TB1 BasementVent Cap DVP TVHW VerticalTermination Cap Highwind IT L 12 in 305 mm 7 1 8 in 12 1 8 in 181 mm 314 mm 7 1 LZ x in 3 8 in 10 mm 222 mm 1 in 25 mm SX 7 3 4 to 10 3 8 in 197 to 264 mm DVP FBHT DVP HPC J FireBrickTermination Cap High Performance Cap Figure 16 5 DVP vent components 64 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 B Vent Components Diagrams continued Effective Length 5 3 4 to 8 3 8 in 5 1 2 in 146 to 213 mm 10 1 2 in 267 mm 10 7 8 in A WARNING Fire Risk When using DVP HRC SS and DVP HRC ZC SS termination caps on top vented fireplaces a 6 inch minimum vertical vent section is required before installing first elbow DVP HRC SS DVP HR
5. 12 08 7 Vent Information and Diagrams A Approved Pe 23 B Vent Table Key e R R R RR RRR R RRR RR 23 C Use of Elbows 23 D Measuring Standards sese eee eee 23 E Vent Diagrams xii cits g Ske bison E EUR Run y eds 24 8 Vent Clearances and Framing A Pipe Clearances to Combustibles u naauauu 33 B Wall Penetration Framing llle 33 C Install the Ceiling Firestop lille 34 D Install Attic Insulation Shield naa anaana 35 E Installing the Optional Heat Zone Gas Kit 35 9 Appliance Preparation A Choosing the Top or Rear Vent nananana aana 36 B Bear Vert s nieee lr eue RR 3rd el 37 C Installing the Non combustible Board 37 D Securing and Leveling the Appliance 37 10 Installing Vent Pipe DVP and SLP Pipe A Assemble Vent Sections DVP Pipe Only 38 B Assemble Vent Sections SLP Pipe Only 39 C Assemble Slip Sections nananana aa 39 D Secure the Vent Sections elles 40 E Disassemble Vent Sections lisi isusun 40 F Install Decorative Ceiling Components SLP only 41 G Install Metal Roof Flasbing 42 H Assemble and Install Storm Collar Ls 42 L Install DEA 43 J Install Vertical Termination Cap 44 K Install Decorative Wall Components SLP only 44 L Heat Shield Requirements for Horizontal Termination 44 M Install Horizontal Termination Cap DVP and SLP Pi
6. Approved Minimum De Gaz Acceptable 0 0inw c Po Col d eau Maximum Pressure Pression 0 0inw c Po Col d eau Maximum Manifold Pressure Pression 0 0 in w c Po Col d eau Minimum Manifold Pressure Pression 0 0 in w c Po Col d eau Model Number Total Electrical Requirements 000Vac 00Hz less than 00 Amperes MADE IN USA INCANADA sai ALTITUDE 0 0000 FT 0000 0000FT Modele XXXXXXXX MAX INPUTBTUH 00 000 00 000 Serial Number MIN INPUTBTUH 00 000 00 000 Sariai ORIFICE SIZE NNN ON Serie XXXXXXXX 2 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 A Safety Alert Key e DANGER Indicates a hazardous situation which if not avoided will result in death or serious injury e WARNING Indicates a hazardous situation which if not avoided could result in death or serious injury e CAUTION Indicates a hazardous situation which if not avoided could result in minor or moderate injury e NOTICE Used to address practices not related to personal injury Table of Contents A Congratulations 2 B Limited Lifetime Warranty ss e x x e x e x e eee 5 1 Listing and Code Approvals A Appliance Certification 0 0 0 0 ce eee eee 7 B Glass Specifications lille esses 7 C BTU Specifications iu a dr EE ERR RS 7 D High Altitude Installations llle esses 7 E Non Combustible Materials Specification 7
7. C Optional Accessories Requirements This appliance may be used with a wall switch wall mounted thermostat and or a remote control Wiring for optional Hearth amp Home Technologies approved accessories should be done now to avoid reconstruction Follow instructions that come with those accessories Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 47 INTERMITTENT PILOT IPI MODULE M e i As 2 i BATTERY PACK CONNECT TO ORIFICE SOLENOID RED WIRE TO RED WIRE BLACK WIRE TO BLACK WIRE SWITCH BACK VIEW e f H DEXEN IPI VALVE GRN NOT CONNECTED F O L CAPACITOR PART IS ENCLOSED IN SHRINK TUBING CONTROL MODULE J BOX 110V CORD ASSEMBLY 2 9V TRANSFORMER SOLENOID jo ACCENT LIGHTING NOTE WIRE TYPE 80 C Note Appliance will not operate unless properly grounded Figure 12 1 Intellifire Pilot Ignition IPI Wiring Diagram D Electrical Service and Repair WARNING Risk of Shock Replace damaged wire with WARNING Risk of Shock Label all wires prior to dis e connection when servicing
8. F Combustible Materials Specification 7 G Electrical Codes 1 0 0 0 tsart RE LER eee 7 H Requirements for the Commonwealth of Massachusetts 8 User Guide 2 Operating Instructions A Gas Fireplace Gate 9 B Your Fireplace sois sett Te eae Ae gare 9 G Fan Kit optional sae o iens 10 D Clear Space sessio verre er e deeg 10 E Decorative Doors and Fronts 10 F Fixed Glass Assembly lessen 10 G Remote Controls Wall Controls and Wall Switches 10 H Before Lighting Fireplace sse e e e e Ke 10 Lighting Instructions Pi 11 d After Fireplace is Lit ccc ewe eevee ceded Re 12 K Frequently Asked Questions anuanua 12 3 Maintenance and Service A Maintenance Tasks Homeowner lusu 13 B Maintenance Tasks Qualified Service Technician 14 Installer Guide 4 Getting Started A Typical Appliance System liiis eee ee eee 16 B Design and Installation Considerations 17 C Tools and Supplies Needed nnna 17 D Inspect Appliance and Components 17 5 Framing and Clearances A Selecting Appliance Location sanansa nann 18 B Constructing the Appliance Chase 19 C Cearances llle eee 19 D Mantel and Wall Projections 20 6 Termination Locations A Vent Termination Minimum Clearances 21 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S
9. I terminal on module Place ON OFF rocker switch or wall switch in ON position If there is no spark at I terminal module must be replaced If there is a spark at I terminal module is fine Inspect pilot assembly for shorted sparker wire or cracked insulator around electrode Replace pilot if necessary 2 Pilot won t light A No power or transformer installed Verify that transformer is installed and plugged into module Check there is no noise or incorrectly voltage of transformer under load at spade connection on module spark with ON OFF switch in ON position Acceptable readings of a good transformer are between 3 2 and 2 8 volts AC B Ashorted or loose connection in Remove and reinstall the wiring harness that plugs into module wiring configuration or wiring har Verify there is a tight fit Verify pilot assembly wiring to module Re ness move and verify continuity of each wire in wiring harness Replace any damaged components C Improper wall switch wiring Verify that 110 VAC power is ON to junction box D Module not grounded Verify black ground wire from module wire harness is grounded to metal chassis of appliance E Module Turn ON OFF rocker switch or wall switch to OFF position Remove ignitor wire I from module Place ON OFF rocker switch or wall switch in ON position If there is no spark at I terminal module must be replaced If there is a spark at I terminal module is fine Inspect pilo
10. Not Required To Be Vented in the most current edition of NFPA 54 as adopted by the Board and Product Approved side wall horizontally vented gas fu eled equipment installed in a room or structure separate from the dwelling building or structure used in whole or in part for residential purposes MANUFACTURER REQUIREMENTS Gas Equipment Venting System Provided When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment the instructions provided by the manufacturer for installation of the equipment and the venting system shall include Detailed instructions for the installation of the venting system design or the venting system components and A complete parts list for the venting system design or venting system Gas Equipment Venting System NOT Provided When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not pro vide the parts for venting the flue gases but identifies special venting systems the following requirements shall be satisfied by the manufacturer The referenced special venting system instructions shall be included with the appliance or equipment in stallation instructions and The special venting systems shall be Product Ap proved by the Board and the instructions for that sys tem shall include a parts list and detailed installation instruction
11. materials beyond the minimum clearances Comply with all minimum clearances to combustibles as specified in this manual Overlapping materials could ignite and will interfere with proper operation of doors and louvers NON COMBUSTIBLE ZONE Shaded areas E a 41 in gt pel MEASUREMENTS FROM TOP EDGE OF THE OPENING Note Measurement is taken from top of the opening NOT the top of the fireplace Figure 13 1 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles Combustible Mantel Legs or Wall Projections INTERIOR WALL TOP VIEW A B FIREPLACE OPENING f is MANTEL LEG OR WALL PROJECTIONS Figure 13 3 Noncombustible Facing Diagram If A minimum is then B maximum ls DE Prom 1 2 3 3 T5 fo femmes 26 5r 76 oz 327 oo Figure 13 2 Combustible Mantel Leg or Wall Projections Acceptable on both sides of opening 50 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 C Doors Only doors certified for use with this appliance model may be used Contact your dealer for a list of doors that may be used Once you have determined what kind of door and finishing material is going to be used on the fireplace you may use the table below which shows the door mod els and the finishing material thickness allowed For an inside fit there is an available template to as
12. 12 08 51 1 Appliance Setup A Remove Fixed Glass Assembly See Section 14 H B Remove the Shipping Materials Remove shipping materials from inside or underneath the firebox C Clean the Appliance Clean vacuum any sawdust that may have accumulated inside the firebox or underneath in the control cavity D Accessories Install approved accessories per instructions included with accessories Contact your dealer for a list of ap proved accessories WARNING Risk of Fire and Electric Shock Use ONLY Hearth amp Home Technologies approved optional acces sories with this appliance Using non listed accessories could result in a safety hazard and will void the warranty E Install the Refractory Note The red refractory will naturally darken when the firebox heats up The red color will return when the firebox cools STEP 1 Place the back piece of refractory in back of the firebox The small indentation on one side goes down Lean the refractory slightly so it doesn t tip over Figure 14 1 STEP 2 Place the left side refractory onto the left side of the burner Push the back refractory against the back wall Place the bumps on the bottom of the left refractory into the grooves on the burner surface Push to top gently against the side of the fireplace Once in place push it back so the bevel cuts sit against each other and the seam is minimized Figure 14 2 STEP 3 Repeat step 2 for the right side
13. 2SL or DVP SLP24 adapter to the starting collar of the appliance Lock the vent components into place by sliding the pipe section onto the collar Align the seam of the pipe and seam of collar to allow engagement Rotate the vent component to lock into place Use this procedure for all vent components See Figure 10 5 Slide the gasket over the first vent section and place it flush to the appliance This will prevent cold air infiltration High temperature caulk may be used to hold the part in place Continue adding vent components locking each succeeding component into place Ensure that each succeeding vent component is securely fitted and locked into the preceding component Commercial Multi family Multi level exceeding two sto ries or High Rise Applications For Installation into a commercial multi family multi level exceeding two stories or high rise applications All outer pipe joints must be sealed with high temperature silicone including the slip section that connects directly to the hori zontal termination cap Apply a bead of silicone sealant inside the female outer pipe joint prior to joining sections See Figure 10 1 Only outer pipes need to be sealed All unit collar pipe slip section elbow and cap outer flues shall be sealed in this manner unless otherwise stated WARNING Risk of Fire or Explosion DO NOT break silicone seals on slip sections Use care when remov ing termination cap from sli
14. 4 hours of initial burning to remove deposits left by oils from the manufacturing process A non abrasive cleaner such as gas fireplace glass cleaner may be necessary See your dealer Noise is caused by metal expanding and contracting as it heats up and cools down similar to Metallic noise the sound produced by a furnace or heating duct This noise does not affect the operation or longevity of the appliance Is it normal to see the pilot flame burn In an Intellifire ignition system it is normal to see the pilot flame but it should turn off when continually ON OFF is turned off 12 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 Maintenance and Service Any safety screen or guard removed for servicing must be replaced prior to operating the fireplace When properly maintained your fireplace will give you many years of trouble free service We recommend an nual service by a qualified service technician A Maintenance Tasks Homeowner Installation and repair should be done by a qualified service technician only The fireplace should be inspected before use and at least annually by a professional service person The following tasks may be performed annually by the homeowner If you are uncomfortable performing any of the listed tasks please call your dealer for a service ap pointment More frequent cleaning may be required due to lint from carpeting or other factors Control compartme
15. ROOF FLASHING MAINTAINS MINIMUM CLEARANCE AROUND PIPE SECTION 10 G STORM COLLAR SECTION 10 H G VENT PIPE PENETRATES ROOF PREFERABLY WITHOUT AFFECTING ROOF RAFTERS SECTION 8 C ATTIC INSULATION SHIELD NOT SHOWN MUST BE USED HERE TO KEEP INSULATION AWAY FROM A VENT PIPE IF ATTIC IS INSULATED SECTIONS 8 C AND 8 D CEILING FIRESTOP ON FLOOR OF ATTIC SECTION 8 C FRAMING HEADER SECTION 5 B FRAMING HEADED OFF IN CEILING JOISTS SECTION 8 C OPTIONAL WALL SWITCH MANTEL AND MANTEL LEG SECTION 5 D SURROUND HEARTH EXTENSION GAS LINE SECTION 11 16 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 B Design and Installation Considerations Heat amp Glo direct vent gas appliances are designed to operate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside No additional outside air source is required Installation MUST comply with local regional state and national codes and regulations Consult insurance carrier local building inspector fire officials or authorities having jurisdiction over restrictions installation inspection and permits Before installing determine the following Where the appliance is to be installed The vent system configuration to be used Gas supply piping requirements Electrical wiring requirements Framing and finishing details Wheth
16. Vent Depth Depth Depth Depth 2 3 4 in to 3 1 8 in to 4 7 8 in to 5 1 4 in to 4 7 8 in 5 1 4 in 9 in 9 3 8 in DVP TRAP1 can adjust 1 1 2 in 3 1 8 to 4 5 8 in DVP TRAP2 can adjust 4 in 5 3 8 to 9 3 8 DVP HPC1 can adjust 2 1 8 in 4 1 4 to 6 3 8 DVP HPC2 can adjust 4 1 8 in 6 3 8 to 10 1 2 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 45 1 Gas Information A Fuel Conversion Make sure the appliance is compatible with available gas types Conversions must be made by a qualified service technician using Hearth amp Home Technologies specified and approved parts B Gas Pressure Optimum appliance performance requires proper input pressures Gas line sizing requirements will be determined in ANSI Z223 1 National Fuel Gas Code in the USA and CAN CGA B149 in Canada Pressure requirements are Gas Pressure Natural Gas Propane WARNING Risk of Fire or Explosion High pressure will damage valve Low pressure may cause explosion Verify inlet pressures Verify minimum pressures when other household gas appliances are operating Install regulator upstream of valve if line pressure is greater than 1 2 psig A WARNING Fire Risk Explosion Hazard High pressure will damage valve Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1 2 psig Close the manual shutoff valve BEFORE pressure testing ga
17. bw E AA 68 D Contact Information ss sste irnir weri aroei tya eee 72 gt Contains updated information 4 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 B Limited Lifetime Warranty Hearth amp Home Technologies LIMITED WARRANTY Hearth amp Home Technologies HHT and its respective brands extends the following warranty for HHT gas wood pellet and electric appliances purchased from an authorized HHT dealer and installed in the United States of America or Canada Warranty starts with date of purchase by the original owner End User except as noted for replacement parts Warranty Period HHT Manufactured Appliances and Venting EPA Components Covered Parts Labor Gas Wood Pellet Wood Electric Venting All Parts and Material Except as 1 Year X X X X X X covered by Conditions Exclusion and Limitations listed Igniters Electronic Components and Glass Blowers mm umm rri 2 years Aen x Feos 5years 3years x x Castings amp Baffles Firebox HHT Chimney 7 years 3 years X X X Termination amp Heat Exchanger LERNEN EE ER eee Limited i se O D LI T T H See Conditions Exclusions and limitations 9 01 08 CONDITIONS EXCLUSIONS amp LIMITATION OF LIABILITY This warranty applies to the original owner and is transferable up to two years from date of purchase to the new homeowner provided the purchase was mad
18. controls Wiring errors can insulation cause improper and dangerous operation Verify proper operation after servicing 48 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 E Junction Box Installation If the box is being wired from the INSIDE of the appliance Remove the screw attaching the junction box receptacle to the outer shell rotate the junction box inward to disengage it from the outer shell see Figure 12 2 Pull the electrical wires from outside the appliance through the opening into the valve compartment and secure wires with a Romex connector See Figure 12 2 Make all necessary wire connections to the junction box receptacle and reattach the junction box receptacle to the outer shell F Wall Switch Installation for Fan Optional If the box is being wired to a wall mounted switch for use with a fan See Figure 12 3 The power supply for the appliance must be brought into a switch box The power can then be supplied from the switch box to the appliance using a minimum of 14 3 with ground wire At the switch box connect the black hot wire and red switch leg wire to the wall switch as shown At the appliance connect the black hot white neutral and green ground wires to the junction box as shown Add a 1 4 in insulated female connector to the red switch leg wire route it through the knockout in the face of the junction box and connect to the top fan switch co
19. eA Da ss 8 0 8 foot minimum in snow regions Figure 10 14 Minimum Height From Roof To Lowest Discharge Opening NOTICE Failure to properly caulk the roof flashing could cause water entry Caulk the gap between the roof flashing and the outside diameter of the pipe Caulk the perimeter of the flashing where it contacts the roof surface See Figure 10 15 Figure10 15 H Assemble and Install Storm Collar CAUTION Risk of Cuts Abrasions or Flying Debris Wear protective gloves and safety glasses during instal lation Sheet metal edges are sharp Connect both halves of the storm collar with two screws see Figure 10 16 Wrap the storm collar around the exposed pipe section closest to the roof and align brackets Insert a bolt provided through the brackets and tighten the nut to complete the storm collar assembly Make sure the collar is tight against the pipe section Slide the assembled storm collar down the pipe section until it rests on the roof flashing see Figure 10 17 Caulk around the top of the storm collar See Figure 10 23 rii IC Tak TG S TTS TU ae n e l ETp e EIgUure 10 SZ Ss Tar be Storm Collart Around ur 42 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 Install RF4 8 The RF4 8 may be used in place of the roof flashing and storm collar Sections 10 G and 10 H Pipe must be supported within 12 inches of the roofline using plumbers strapping o
20. may cause overheating and fire HORIZONTAL OVERHANG Termination Cap 20 INCHES MIN VERTICAL WALL LOWEST DISCHARGE OPENING GAS DIRECT VENT TERMINATION CAP f using decorative cap cover s this distance may need to be increased Refer to the installation instructions supplied with the decorative cap cover ROOF PITCH IS X 12 H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING In a staggered installation with both gas and wood terminations the wood termination cap must be higher than the gas termination cap Figure 6 2 Staggered Termination Caps Roof Pitch H Min Ft SE T dite siete 1 0 Over 6 12 to 7 12 i ene ens 1 25 Over 7 12 to 8 12 Over 8 12 to 9 12 Over 9 12 to 10 12 2 Over 10 12 to 11 12 cone Over 11 12 t0 e 5 reet eerie j Over 12 12 to 14 12 Over 14 12 to 16 12 Over 16 12 to 18 12 BA Over 18 12 t0 20 12 ro one 7 5 Over 20 12 to 211 8 0 8 foot minimum in snow regions Figure 6 1 Minimum Height From Roof To Lowest Discharge Opening Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 21 See Note 2 Measure vertical clearances from this surface X AIR SUPPLY INLET VENT TERMINAL 12 inches Se
21. of the following patents Nos produits sont couverts par un ou plusieurs des brevets suivants United States 4593510 4686807 4766876 4793322 4811534 5000162 5016609 5076254 5113843 5191877 5218953 5263471 5328356 5341794 5347983 5429495 5452708 5542407 5601073 5613487 5647340 5688568 5762062 5775408 5890485 5931661 5941237 5947112 5996575 6006743 6019099 6048195 6053165 6145502 6170481 6237588 6296474 6374822 6413079 6439226 6484712 6543698 6550687 6601579 6672860 6688302B2 671572482 6729551 6736133 6748940 6748942 D320652 D445174 D462436 Canada 1297749 2195264 2225408 or other U S and foreign patents pending ou autres brevets americains et etrangers en attente GAS FI RED H E AT G LO Heat amp Glo a brand of Hearth amp Home Technologies Inc C US 3 Type of Gas No one builds a better fire 7571 215th Street West Lakeville MN 55044 Not for use with solid fuel Ne doit pas entre utilise avec un combustible solide LISTED Type of Gas Sorte De Gaz This appliance must be installed in accordance with local codes if any if not follow ANSI 2223 1 inthe USA or CAN CGA B149 installation codes Installer l appareil selon les codes ou reglements NATURAL G AS locaux ou en l absence de tels reglements selon les codes d installation CAN CGA B149 l ANSI Z21XX XXXX CSA 2 XX MXX UL307B Gas and Electric Information Minimum Permissible Gas Supply for Purposes of Input Adjustment
22. to be performed 593 913F Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 11 J After Fireplace is Lit Initial Break in Procedure The fireplace should be run three to four hours continuously on high Turn the fireplace off and allow it to completely cool Remove fixed glass assembly See Section 14 H Clean fixed glass assembly See Section 3 Replace the fixed glass assembly and run continuously on high an additional 12 hours This cures the materials used to manufacture the fire place NOTICE Open windows for air circulation during fire place break in e Some people may be sensitive to smoke and odors e Smoke detectors may activate K Frequently Asked Questions This is a result of gas combustion and temperature variations As the appliance warms this condensation will disappear This is a result of normal operation and the flames will begin to yellow as the appliance is al Blue flames lowed to burn for 20 to 40 minutes When first operated this appliance may release an odor for the first several hours This is caused Odor from appliance by the curing of the paint and the burning off of any oils remaining from manufacturing Odor may also be released from finishing materials and adhesives used around the appliance Condensation on the glass This is a normal result of the curing process of the paint and logs Glass should be cleaned Film on the glass within 3 to
23. up may be installed on the next adjacent floor level In the event that the requirements of this subdivision can not be met at the time of completion of installation the owner shall have a period of thirty 30 days to comply with the above requirements provided however that dur ing said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed Approved Carbon Monoxide Detectors Each carbon monoxide detector as required in accor dance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified Signage A metal or plastic identification plate shall be permanent ly mounted to the exterior of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizon tally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector ob serves carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5 08 2 a 1 through 4 Exemptions The following equipment is exempt from 248 CMR 5 08 2 a 1 through 4 The equipment listed in Chapter 10 entitled Equipment
24. venting there is no insulation in the outer vent pipe Figure 9 7 To attach the first section of vent pipe make sure to use the fiberglass gasket in the manual bag to seal between the first vent component and the outer fireplace wrap Use 2 self tapping screws to secure the gasket to the outer wrap Secure the first section of venting to the fireplace by screw ing through the two straps left over from cutting the seal cap strap in step 2 C Installing the Non combustible Board The factory supplied non combustible board spans the distance from the top of the fireplace to the center of the framing header This board must be used See Figure 9 8 Figure 9 8 Non combustible Board D Securing and Leveling the Appliance WARNING Risk of Fire Prevent contact with e Sagging or loose insulation e Insulation backing or plastic e Framing and other combustible materials Block openings into the chase to prevent entry of blown in insulation Make sure insulation and other materials are secured DO NOT notch the framing around the appliance standoffs Failure to maintain air space clearance may cause overheating and fire The diagram shows how to properly position and secure the appliance see Figure 9 9 Nailing tabs are provided to secure the appliance to the framing members Bend out nailing tabs on each side Place the appliance into position Keep nailing tabs flush with the framing Level the appliance
25. 000GLX IPILP S R 2101 900 Rev S 12 08 19 D Mantel and Wall Projections WARNING Risk of Fire Comply with all minimum clear ances as specified Framing or finishing material closer than the minimums listed must be constructed entirely of noncom bustible materials i e steel studs concrete board etc Combustible Mantels TO CEILING MEASUREMENTS FROM TOP EDGE OF THE OPENING Note All measurements in inches Note Measurement is taken from top of the opening NOT the top of the fireplace Figure 5 3 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles Combustible Mantel Legs or Wall Projections INTERIOR WALL TOP VIEW A B FIREPLACE OPENING MANTEL LEG OR WALL PROJECTIONS If A minimum is then B maximum is DE me 1 2 3 4 5 K 25 51 76 102 127 co Figure 5 4 Clearances to Mantel Legs or Wall Projections Acceptable on both sides of opening 20 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 Termination Locations A Vent Termination Minimum Clearances A WARNING Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials 6 in minimum up to 20 in 18 in minimum 152 mm 508 mm 457 mm 20 in and over Gas Wood or Fuel Oil Termination Cap N Failure to keep insulation or other materials away from vent pipe
26. 00GLX IPILP S R 2101 900 Rev S 12 08 39 D Secure the Vent Sections Vertical runs of DVP pipe must be supported every 8 ft 2 44 m after the 25 ft 7 62 m maximum unsupported rise Vertical runs of SLP pipe must be supported every 8 ft 2 44 m Horizontal sections must be supported every 5 feet 1 52 m Vent supports or plumbers strap spaced 120 apart may be used to support vent sections See Figures 10 8 and 10 9 Wall shield firestops may be used to provide horizontal support vent sections SLP ceiling firestops have tabs that may be used to provide vertical support WARNING Risk of Fire Explosion or Asphyxiation Improper support may allow vent to sag and separate Use vent run supports and connect vent sections per in stallation instructions DO NOT allow vent to sag below connection point to appliance Figure 10 8 Securing Vertical Pipe Sections Figure 10 9 Securing Horizontal Pipe Sections E Disassemble Vent Sections Rotate either section see Figure 10 10 so the seams on both pipe sections are aligned as shown in Figure 10 11 Pull carefully to separate the pieces of pipe Figure 10 10 Rotate Seams for Disassembly Figure 10 11 Align and Disassemble Vent Sections 40 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 F Install Decorative Ceiling Components SLP only EENES A decorative ceiling t
27. 2 installation which does not comply with local building codes 3 shipping improper handling improper operation abuse misuse accident or unworkmanlike repairs 4 environmental conditions inadequate ventilation or drafting caused by tight sealing construction of the structure or handling devices such as exhaust fans or forced air furnaces or other such causes 5 use of fuels other than those specified in the operating instructions 6 installation or use of components not supplied with the appliance or any other components not expressly authorized and approved by HHT and or 7 modification of the appliance not expressly authorized and approved by HHT in writing This warranty does not apply to non HHT venting components hearth components or other accessories used in conjunction with the installation of this product This warranty is void if the appliance has been over fired or operated in atmospheres contaminated by chlorine fluorine or other damaging chemicals the appliance is subject to prolonged periods of dampness or condensation or there is any damage to the appliance or other components due to water or weather damage which is the result of but not limited to improper chimney or venting installation HHT s liability under this warranty is limited to the replacement and repair of defective components or workmanship during the applicable period HHT may fully discharge all of its obligations under such warranties by repairing the def
28. 2 mm section of straight pipe may Elbow only need to be attached to the appliance 6in 152 mm before a 90 elbow to allow the vent 305 mm pipe to clear the top standoffs Ton 914mm V H H 40 ft 12 2 m Maximum H H 20 ft 6 1 m Maximum Two Elbows INSTALLED HORIZONTALLY Figure 7 4 24 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 Top Vent Horizontal Termination continued Three Elbows vm Ing vw JI ne sm Uess at oramm cin D ss zu 610mm H H 20 ft 6 1 m Maximum V V H H 40 ft 12 2 m Maximum Figure 7 5 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 25 Top Vent Vertical Termination Flue Restrictor Instructions 1 Remove the top piece of refractory if already installed No Elbow See Figure 7 7 V 40 ft Max 12 4 m TOP FLUE V 2 3 ft Min 914 mm REFRACTORY RESTRICTOR Note If installing a vertical vent termination off the top of the ap pliance the flue restrictor should be used Figure 7 7 2 Break the flue restrictor into two pieces Do this by bending the part back and forth until it breaks see Figure 7 8 Figure 7 6 Figure 7 8 Flue Restrictor 26 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 Top Vent Vertical Termination continued 4 Center the Flue Restrictor on vent and se
29. 2101 900 Rev S 12 08 57 1 Troubleshooting With proper installation operation and maintenance your gas appliance will provide years of trouble free service If you do experience a problem this troubleshooting guide will assist a qualified service technician in the diagnosis of a problem and the corrective action to be taken This troubleshooting guide can only be used by a qualified service technician Contact your dealer to arrange a service call by a qualified service technician A Intellifire Ignition System Symptom Possible Cause Corrective Action 1 Pilot won t light A Incorrect wiring Verify S wire white for sensor and I wire orange for ignitor are The ignitor module connected to correct terminals on module and pilot assembly makes noise but no f E f t aT Spark B Loose connections or electrical Verify no loose connections or electrical shorts in wiring from mod shorts in the wiring ule to pilot assembly Verify connections underneath pilot assem bly are tight also verify connections are not grounding out to metal chassis pilot burner pilot enclosure mesh screen if present or any other metal object C Ignitor gap is too large Verify gap of igniter to right side of pilot hood The gap should be approximately 17 in or 1 8 in 3 mm D Module Turn ON OFF rocker switch or wall switch to OFF position Remove ignitor wire I from module Place a grounded wire about 3 16 in 5 mm away from
30. 68 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 Service Parts List 6000GLX IPI IMPORTANT THIS IS DATED INFORMATION When requesting service or replacement parts for your appliance please provide model number and serial number All parts listed in this manual may be ordered from an authorized dealer TEM DESCRIPTION COMMENTS Log Assembly NG Log Assembly LP Log 1 Flame Out of Log Left NG Log 1 Flame Out of Log Left LP Log 2 Flame Out of Log Right NG Log 2 Flame Out of Log Right LP og 3 og 4 og 5 og 6 og 7 Refractory Red R 4 pieces Stocked at Depot PART NUMBER LOGS 6000GLX LOGS 6000GLXLP SRV2101 085 SRV2101 087 SRV2101 086 RV2101 088 RV2101 197 RV386 716 SRV2101 195 SRV2101 196 SRV530 703 BRICK 6GLX R BRICK 6GLX S SRV2101 572 SRV2101 472 SRV2101 570 RV2101 470 RV2101 573 SRV2101 473 SRV2101 571 SRV2101 471 2101 043 2101 312 2101 260 LA 6GLX SRV2101 008 SRV2101 007 Wal Refractory Stratford Tan S 4 pieces Stratford Right Refractory R Right Refractory S Back Refractory R Back Refractory S Top Refractory R Walt Top Refractory S Left Refractory R Left Refractory S rate Assembly Q on combustible board LD urround Q Q lass Assembly Burner Assembly Red R Burner Assembly Stratford Tan S Flue Restrictor N O 8 olo irs oo FK 160A 85 128 C Gasket Assembly Contains Ve
31. C ZC SS HORIZONTAL TERMINATION CAP Figure 16 6 DVP vent components Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 65 B Vent Components Diagrams continued 6 1 2 in 165 mm M 6 5 8 in 168 mm a SLP45 6 5 8 in 45 Elbow Tea mm 9 7 8 In 251 mm SLP 90ST 90 Elbow Effective Height Length C C ipe ames le Effective sm o9 om Height Length i DVP SLP24 Adapter SLP PIPE e SLP HVS RF4 8 Horizontal Pipe Roof Flashing Ceiling Firestop Wall Shield Firestop Support Figure 16 7 SLP Series Vent Components 66 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 B Vent Components Diagrams continued m ae SLP SNKD Snorkel Termination Cap SLP CCS BK SLP TVHW Cathedral Ceiling Vertical Support Box Black Termination Cap SLP TRAP1 SLP TRAP2 Horizontal Horizontal Termination Cap Termination Cap DVP 2SL DVP HSM B Extended Heat Shield SLP DCF BK SLP WT BK Ceiling Firestop Wall Thimble Black Black Figure 16 8 SLP Series Vent Components Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 67 H EAT GLO C Service Parts 6000G LX IPI No one builds a better fire Service Parts Diagram Beginning Manufacturing Date May 2006 Ending Manufacturing Date Part number list on following page
32. H 8 ft 2 4 m Maximum a NV e den ei INSTALLED E Figure 7 20 HORIZONTALLY 32 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 Vent Clearances and Framing A Pipe Clearances to Combustibles WARNING Risk of Fire Maintain air space clearance to vent DO NOT pack insulation or other combustibles Between ceiling firestops Between wall shield firestops e Around vent system Failure to keep insulation or other material away from vent pipe may cause over heating and fire Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm DVP heat shield designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in a DVP HSM B will be required SLP heat shield designed to be used on a wall 4 3 8 in to 7 5 8 in 111 mm to 194 mm thick If wall thickness is less than 4 3 8 the existing heat shields must be field trimmed If wall thickness is greater than 7 5 8 in a DVP HSM B will be required DVP SLP Pipe Shown ax Heat 3 in 76 mm 3 in 76 mm Shield top ipic i top clearance j F gt eat T Shield 7 NI 1 in 25 mm clearance around S Il WI vertical sections U gt 4 1 in 25 mm Wall clearance Shield bottom amp sides Firestop
33. HEAT GLO No one builds a better fire Owner s Manual Installation and Operation Models GAS FIRED 6000GLX IPI S 6000GLX IPI R 6000GLX IPILP S C UL US 6000GLX IPILP R LISTED NOTICE DO NOT DISCARD THIS MANUAL Important operating Read understand andfollow Leave this manual with and maintenance these instructions for safe party responsible for use instructions included installation and operation and operation A WARNING If the information in these A WARNING instructions is not followed exactly a fire m HOT SURFACES or explosion may result causing property Glass and other surfaces are hot during As tion AND cool down damage personal injury or death UN Hot glass will cause burns DO NOT store or use gasoline or other flam DO NOT touch glass until it is cooled mable vapors and liquids in the vicinity of this TE ETT touch glass or any other appliance S SES euer ey y PP CAREFULLY SUPERVISE children in same room as e What to do if you smell gas fireplace DO NOT try to light any appliance Alert children and adults to hazards of high temperatures l e High temperatures may ignite clothing or other flammable DO NOT touch any electrical switch DO materials NOT use any phone in your building e Keep clothing furniture draperies and other flammable materials away Immediately call your gas supplier from a neighbor s phone Follow the gas suppli This appli
34. L ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYSTEM 3 FASTENERS PER SIDE CEILING FIRESTOP INSTALLED BELOW CEILING CEILING FIRESTOP INSTALLED ABOVE CEILING Figure 8 4 Installing the Attic Shield 34 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 D Install Attic Insulation Shield WARNING Fire Risk DO NOT allow loose materials or insulation to touch vent Hearth amp Home Technologies Inc requires the use of an attic shield The National Fuel Gas Code ANSI Z223 1 and NFPA 54 requires an attic shield constructed of 26 gauge minimum metal that extends at least 2 in 51 mm above insulation Attic shields must meet specified clearance and be se cured in place Flat Ceiling Installation Remove one shield from box NOTICE Cut previously installed batt insulation to make room for the attic insulation shield Wrap shield around pipe if pipe is already installed in area to be insulated Match the three holes in each side and fasten with three screws to form a tube Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling firestop Bend the remaining bottom tabs inward 90 to maintain the air space between the pipe and the shield Set the shield on the ceiling firestop and attach to the firestop Bend all tabs inward 90 around the top of the shield These tabs must be used to prevent blown insulation from getting between the shie
35. Manifold Assembly Solenoid Orifice NG 53C Orifice LP 68C olenoid Capacitor Assembly Wal skl zeck Jl a o o A 1251 k 2V Transformer Wall Switch Wire Bracket Bulb box Bulb Bracket Glass apton Lens ech N lass Bracket Battery Pack Cord Assembly 2101 252 2101182 p NEN p a Conversion Kit NG Conversion KIT LP Pilot Orifice NG Pilot Orifice LP Regulator NG Regulator LP Mi VM LI kad L 87 e les ana 302 320A 2088 136 2101 041 750 500 750 501 82 839 82 854 93 592 2101 293 93 590A 2101 071 582 853 582 868 2101 072 2101 290 2095 550 2101 120 2101 164 2101 252 2101 132 91 593 594A 2101 084 NGK 6GLX IPI LPK 6GLX IPI 93 528 93 527 NGK DXV LPK DXV o Gn Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 71 D Contact Information HEAT GLO No one builds a better fire gt Heat amp Glo a brand of Hearth amp Home Technologies Inc 7571 215 Street West Lakeville MN 55044 www heatnglo com Please contact your Heat amp Glo dealer with any questions or concerns For the location of your nearest Heat amp Glo dealer please visit www heatnglo com NOTES NOTICE DO NOT DISCARD THIS MANUAL Important operating Read understand and follow Leave this manual with and maintenance these instructions for safe party responsible for use instructions included installation
36. Protective gloves sandpaper steel wool cloths mineral spirits primer and touch up paint Inspect for paint condition warped surfaces corrosion or perforation Sand and repaint as necessary Replace fireplace if firebox has been perforated Control Compartment and Firebox Top Frequency Annually By Qualified Service Technician Tools needed Protective gloves vacuum cleaner dust cloths Vacuum and wipe out dust cobwebs debris or pet hair Use caution when cleaning these areas Screw tips that have penetrated the sheet metal are sharp and should be avoided Remove all foreign objects Verify unobstructed air circulation Burner Ignition and Operation Frequency Annually By Qualified Service Technician Tools needed Protective gloves vacuum cleaner whisk broom flashlight voltmeter indexed drill bit set and a manometer Verify burner is properly secured and aligned with pilot or igniter Clean off burner top inspect for plugged ports corrosion or deterioration Replace burner if necessary Replace Glowing embers with new dime size pieces DO NOT block ports or obstruct lighting paths Refer to Section 14 for proper ember placement Verify batteries have been removed from battery back up IPI systems to prevent premature battery failure or leaking Check for smooth lighting and ignition carryover to all ports Verify that there is no ignition delay Inspect for lifting or other flame problem
37. Requirements for the Commonwealth of Massachusetts For all side wall horizontally vented gas fueled equipment installed in every dwelling building or structure used in whole or in part for residential purposes including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven 7 feet above finished grade in the area of the venting in cluding but not limited to decks and porches the following requirements shall be satisfied Installation of Carbon Monoxide Detectors At the time of installation of the side wall horizontal vented gas fueled equipment the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back up is installed on the floor level where the gas equipment is to be installed In addi tion the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detec tor with an alarm is installed on each additional level of the dwelling building or structure served by the side wall horizontal vented gas fueled equipment It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors In the event that the side wall horizontally vented gas fu eled equipment is installed in a crawl space or an attic the hard wired carbon monoxide detector with alarm and battery back
38. T place combustible objects in front of the fireplace or block louvers High temperatures may start a fire See Figure 2 2 Avoid placing candles and other heat sensitive objects on mantel or hearth Heat may damage these objects Figure 2 2 Clear Space E Decorative Doors and Fronts WARNING Risk of Fire Install ONLY doors or fronts approved by Hearth amp Home Technologies Unapproved doors or fronts may cause fireplace to overheat This fireplace has been supplied with an integral barrier to prevent direct contact with the fixed glass panel DO NOT operate the fireplace with the barrier removed Contact your dealer or Hearth amp Home Technologies if the barrier is not present or help is needed to properly install one For more information refer to the instructions supplied with your decorative door or front F Fixed Glass Assembly See Section 14 H G Remote Controls Wall Controls and Wall Switches Follow the instructions supplied with the control installed to operate your fireplace For safety Install a switch lock or a wall remote control with child protection lockout feature Keep remote controls out of reach of children See your dealer if you have questions H Before Lighting Fireplace Before operating this fireplace for the first time have a qualified service technician Verify all shipping materials have been removed from inside and or underneath the firebox Review proper p
39. ance has been supplied with an integral barrier er s instructions to prevent direct contact with the fixed glass panel DO s NOT operate the appliance with the barrier removed f you cannot reach your gas supplier call E cu ue E the fire department ontact your dealer or Heart ome Technologies if the barrier is not present or help is needed to properly install one nstallation and service must be performed by a qualified installer service agency or the gas supplier In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter See Table of Contents for location of additional Commonwealth This appliance may be installed as an OEM installation in of Massachusetts requirements manufactured home USA only or mobile home and must be installed in accordance with the manufacturer s instructions and the manufactured home construction and safety standard Title 24 CFR Part 3280 or Standard for Installation in Mobile performed by qualified personnel Hearth amp Home Homes CAN CSA Z240MH in Canada Technologies suggests NFI certified or factory trained This appliance is only for use with the type s of gas indicated professionals or technicians supervised by an NFI on the rating plate Gaul certified professional Installation and service of this appliance should be Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 1 Read this manual before installing o
40. and operation and operation This product may be covered by one or more of the following patents United States 4593510 4686807 4766876 4793322 4811534 5000162 5016609 5076254 5113843 5191877 5218953 5263471 5328356 5341794 5347983 5429495 5452708 5542407 5601073 5613487 5647340 5688568 5762062 5775408 5890485 5931661 5941237 5947112 5996575 6006743 6019099 6048195 6053165 6145502 6170481 6237588 6296474 6374822 6413079 6439226 6484712 6543698 6550687 6601579 6672860 6688302B2 6715724B2 6729551 6736133 6748940 6748942 6769426 6774802 6796302 6840261 6848441 6863064 6866205 6869278 6875012 6880275 6908039 6919884 D320652 D445174 D462436 Canada 1297749 2195264 2225408 2313972 Australia 780250 780403 1418504 or other U S and foreign patents pending Printed in U S A Copyright 2008 72 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08
41. be sealed in this manner unless otherwise stated WARNING Risk of Fire or Explosion DO NOT break silicone seals on slip sections Use care when remov ing termination cap from slip pipe If slip section seals are broken during removal of the termination cap vent may leak Figure 10 2 Figure 10 3 Assemble Pipe Sections Per Figure 10 2 Start the inner pipe on the lanced end of section A into the flared end of section B Note Make sure that the seams are not aligned to prevent unintentional disconnection Start the outer pipe of section A over the outer pipe of section B Once both vents sections are started push firmly until all lanced tabs lock into place Lightly tug on the pipe to confirm the tabs have locked It is acceptable to use screws no longer than 1 2 in 13 mm to hold outer pipe sections together If predrilling holes DO NOT penetrate inner pipe For 90 and 45 elbows that are changing the vent direction from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating Use screws no longer than 1 2 in 13 mm If predrilling screw holes DO NOT penetrate inner pipe Figure 10 4 Seams INCORRECT 38 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 B Assemble Vent Sections SLP Pipe Only To attach the first vent component to the starting collars of the appliance Attach a DVP
42. cles and Gas Fired Appliances for Use at High Altitudes NOTICE This installation must conform with local codes In the absence of local codes you must comply with the National Fuel Gas Code ANSI Z223 1 latest edition in the U S A and the CAN CGA B149 Installation Codes in Canada NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE This appliance is tested and approved as either supplemen tal room heat or as a decorative appliance It should not be factored as primary heat in residential heating calculations B Glass Specifications This appliance is equipped with 5 mm ceramic glass Re place glass only with 5 mm ceramic glass Please contact your dealer for replacement glass C BTU Specifications Maxi Mini Orifi Models ST H U S 0 2000 FT or Canada 2000 4500 FT BTUH BTUH DMS 39 US 40 000 18 700 ege mn ne mz Lamm 18700 leie 6000GDX IPI S NG canana 36 000 16 830 70 54 2 54 36 000 16 500 o8 2 CANADA 32 400 14 850 Di 69 2 D High Altitude Installations NOTICE If the heating value of the gas has been reduced these rules do not apply Check with your local gas utility or authorities having jurisdiction 6000GLX IPILP R 6000GLX IPILP S When installing above 2000 feet elevation In the USA Reduce input rate 4 for each 1000 feet above 2000 feet In CANADA Reduce input rate 10 for elevations between 2000 feet and 4500 feet Above 4500 feet consult local gas
43. cratched Heplace as a complete assembly Removing Fixed Glass Assembly Pull the four glass assembly latches out of the groove on the glass frame Remove glass door from the appliance see Figure 14 23 Replacing Fixed Glass Assembly Replace the glass door on the appliance Pull out and latch the four glass assembly latches into the groove on the glass frame LATCHES BOTH BOTTOM AND TOP GLASS P ASSEMBLY Figure 14 23 Fixed Glass Assembly l Install the Mesh Screen mesh is supplied with the optional doors J Install Trim and or Surround Install optional trim kits and or surrounds using the instructions included with the accessory Use non combustible materials to cover the gap between the sheet rock and the appliance when applicable to the model K Air Shutter Setting Air shutter settings should be adjusted by a qualified ser vice technician at the time of installation The air shutter is set at the factory for minimum vertical vent run Adjust air shutter for longer vertical runs See Figure 14 24 Loosen the wing nut e Push the air handle in to close the air shutter Pull the air handle out to open the air shutter Tighten the wing nut NOTICE If sooting occurs provide more air by opening the air shutter AIR SHUTTER WING NUT Lett Log WA Right Log WA Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R
44. creen if present or any other metal object With fixed glass assembly in place verify that flame is en gulfing flame sensing rod on left side of pilot hood Flame sensing rod should glow shortly after ignition Verify cor rect pilot orifice is installed and gas inlet is set to pressure specifications Clean flame sensing rod with emery cloth to remove any contaminants that may have accumulated on flame sensing rod Verify module is securely grounded to metal chassis of ap pliance Verify that wire harness is firmly connected to the module Verify that ceramic insulator around the flame sensing rod is not cracked damaged or loose Verify connection from flame sensing rod to white sensor wire Clean flame sensing rod with emery cloth to remove any contaminants that may have accumulated on flame sensing rod Verify continuity with a multimeter with ohms set at lowest range Replace pilot if any damage is detected Turn ON OFF rocker switch or wall switch to OFF position Remove ignitor wire I from module Place ON OFF rocker SIS switch or wall switch in ON position If there is no spark at terminal module must be replaced If there is a spark at terminal module is fine N N Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 59 1 Reference Materials A Appliance Dimension Diagram Dimensions are actual appliance dimensions Use for reference only For framing dimensions and clearances ref
45. cure in place by using two self tapping screws see Figure 7 10 3 Match the amount of vertical you have in the system 5 Reinstall the Exhaust Shield with the chart to find the appropriate position to set the Flue Restrictor see Figure 7 9 TOP all REAR VENT Vertical Up NG LP NG ES No No Restrictor Restrictor Restrictor No Restrictor SETTING Figure 7 10 Figure 7 9 gt Note If the DVP 2SL or DVP SLP24 adapter is used with SLP pipe you MUST subtract one number from the table above Example Top vent 40 ft vertical with DVP pipe 5 4 Top vent 40 ft vertical with SLP pipe 4 3 Emwow TS Tang TT en RE 3 RTT Fan som Daun TTT Tan sum Dan 49m Pan 12m os eim 17 1 V V H 50 ft 15 2 m Maximum No specific restrictions on this value EXCEPT V V H cannot exceed 50 ft 15 2 m Two Elbows Figure 7 11 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 27 Top Vent Vertical Termination continued iesus H H 20 ft 6 1 m Maximum V V H H 40 ft 12 2 m Maximum INSTALLED HORIZONTALLY Figure 7 12 28 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 Rear Vent Horizontal Termination NoElbw LT II H 16 in 406 mm Maximum Figure 7 13 One 45 Elbow Do not use a 45 elbow in corner installations Use two 90 elbows in
46. d with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below the termination cap 3 All gravity air intakes within 3 feet of a termination cap must be a minimum of 1 foot below the termination cap Figure 6 3 Minimum Clearances for Termination Measure horizontal clearances from this surface AREA WHERE TERMINAL IS NOT PERMITTED EE clearance above paved See Note 1 sidewalk or a paved driveway located on public property clearance from sides of electri cal service clearance above electrical service 6 inches See Note 5 12inches See Note 5 Covered Alcove Applications M 18 inches clearance under veranda porch deck balcony or overhang 42 inches 6 inches vinyl non vinyl sidewalls 12 inches vinyl sidewalls 18 inches 42 inches 8 ft non vinyl soffit and overhang vinyl soffit and overhang 4 caps 12 feet 1 2 x Q actua Quin termination caps X 3 Huss 2 termination caps x Gcr Note 3 Local codes or regulations may require different clearances Note 4 Termination caps may be hot Consider their proximity to doors or other traffic areas Note 5 Location of the vent termination must not interfere with access to the electrical service In the U S and Canada Vent system termina
47. down to the roof line and fold the resulting flaps to the roof See Figure 10 13 Nail the flaps to the roof AFTER running a bead of non hardening sealant between the flaps and the roof WARNING Risk of Fire Clean out ALL materials from inside the support box and complete the vertical vent run and termination Figure 10 13 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 41 G Install Metal Roof Flashing Note Skip this section if using the RF4 8 See minimum vent heights for various pitched roofs Figure 10 14 to determine the length of pipe to extend through the roof Slide the roof flashing over the pipe sections extending through the roof as shown in Figure 10 15 HORIZONTAL OVERHANG 20 INCHES MIN VERTICAL WALL LOWEST DISCHARGE OPENING GAS DIRECT VENT TERMINATION CAP L ROOF PITCH IS X 12 H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING Roof Pitch H Min Ft Flat oer 1 0 Over 6 12 to 7 12 1 25 Over 7 12 to 8 12 sss 1 5 Over 8 12 t0 9 12 iun 2 0 Over 9 12 to 10 12 ees 2 5 Over 10 12 to 11 12 3 25 Over 11 12 to 12 12 4 0 Over 12 12 to 14 12 5 0 Over 14 12 to 16 12 6 0 Over 16 12 to 18 12 7 0 Over 18 12 to 20 12 7 5 Over 20 12 to
48. e Note 1 clearances above grade veranda porch deck or balcony clearances to window or door that may be opened or to perma nently closed window Glass vertical clearance to unventilated soffit or to ventilated soffit located above the terminal for vinyl clad soffits and below electrical service 12 inches 18 inches 30 inches 9 inches clearance to outside corner clearance to inside corner not to be installed above a gas meter regulator assembly within 3 feet 90 cm horizontally from the center line of the regulator clearance to gas service regulator vent outlet 6 inches 3 ft Canada 9 inches U S A 12 inches Canada clearance to non mechanical See Note 2 air supply inlet to building or the combustion air inlet to any other appliance 3 ft U S A 6 ft Canada See Note 2 clearance to a mechanical pow ered air supply inlet a vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings ee only permitted if veranda porch deck or balcony is fully open on a minimum of 2 sides beneath the floor or meets Note 2 Note 1 On private property where termination is less than 7 feet above a sidewalk driveway deck porch veranda or balcony use of a listed cap shield is suggested See vents components page Note 2 Termination in a covered alcove space spaces open only on one side an
49. e through an authorized dealer or distributor of HHT and the appliance remains in its original place of installation The maximum amount recoverable under this warranty is limited to the purchase price of the product n no event shall HHT be liable for any incidental or consequential damages caused by defects in the product Adjustments regular maintenance cleaning and temporary repairs or the failure to duplicate the problem in the home is not covered under this warranty Page 1 of 2 4021 645A 09 01 08 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 5 B Limited Lifetime Warranty continued This limited warranty does not extend to or include surface finish on the appliance or terminations door gasketing glass gasketing glass discoloration firebrick pellet logs kaowool or other ceramic insulating materials Rust and or corrosion on any of the metal surfaces cast iron components baffles firepots doors or firebox area are not covered by this warranty Noise resulting from minor expansion contraction or movement of certain parts is normal and complaints related to this noise are not covered by this warranty HHT s obligation under this warranty does not extend to damages resulting from 1 installation operation or maintenance of the appliance not in accordance with the installation instructions operating instructions and the listing agent identification label furnished with the appliance
50. ective component s at HHT s discretion Shipping costs are not covered under this warranty Some states do not allow exclusions or limitation of incidental or consequential damages so those limitations may not apply to you This warranty gives you specific rights you may also have other rights which vary from state to state EXCEPT TO THE EXTENT PROVIDED BY LAW HHT MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY SPECIFIED HEREIN THE DURATION OF ANY IMPLIED WARRANTY IS LIMITED TO DURATION OF THE WARRANTY SPECIFIED ABOVE This Limited Warranty is effective on all HHT appliances sold after September 01 2008 and supersedes any and all warranties currently in existence If warranty service is needed you should contact your installing dealer If the installing dealer is unable to provide necessary parts or components contact the nearest authorized HHT dealer or supplier Page 2 of 2 4021 645A 09 01 08 6 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 Listing and Code Approvals A Appliance Certification MODELS 6000GLX IPI R 6000GLX IPI S 6000GLX IPILP R 6000GLX IPILP S LABORATORY Underwriters Laboratories Inc UL TYPE Direct Vent Gas Appliance Heater STANDARD ANSI Z21 88 2000 CSA2 33 M98 UL307B This product is listed to ANSI standards for Vented Gas Appliance Heaters and applicable sections of Gas Burn ing Heating Appliances for Manufactured Homes and Recreational Vehi
51. end of the log rests in the flat area on top of log 3 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 55 a 57 Figure 4 7 Front View y E Figure14 18 Top View STEP 7 Log 5 SRV2101 195 Place log 5 on top of log 1 and log 4 The bottom of this log has two slots in it that both go over the two tabs molded in the top of log 1 Ws gt Se OO E a NE OE A a GMAT S d T HE2 Figure 14 19 Erop Views abe w a lie Figure 14 20 Top View STEP 8 Log 6 SRV2101 196 Place log 6 on top of log 2 and the grate There is a slot in the bottom of this log Place the slot over the tab on top of the right end of log 2 The end of this log has a square notch in it that rests into the second tine from the right on the grate Note May be necessary to tilt grate forward to interlock bottom notch in log Figure 14 21 Front View i T Pn las DIG LST View STEP 9 Log 7 SRV530 703 Place log 7 on top of log 1 and the grate The lower right end of the log rests against the second tine from the left on the grate Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 H Fixed Glass Assembly WARNING Risk of Asphyxiation Handle fixed glass assembly with care Inspect the gasket to ensure it is undamaged and inspect the glass for cracks chips or scratches DO NOT strike slam or scratch glass DO NOT operate fireplace with glass removed cracked broken or s
52. er optional accessories devices such as a fan wall switch or remote control are desired Improper installation adjustment alteration service or maintenance can cause injury or property damage For assistance or additional information consult a qualified service technician service agency or your dealer C Tools and Supplies Needed Before beginning the installation be sure that the following tools and building supplies are available Tape measure Framing material Pliers High temperature caulking material Hammer Phillips screwdriver Gloves Framing square Voltmeter Electric drill and bits 1 4 in Plumb line Safety glasses Level Reciprocating saw Manometer Flat blade screwdriver Non corrosive leak check solution 1 2 3 4 in length 6 or 8 Self drilling screws One 1 4 in female connection for optional fan D Inspect Appliance and Components Carefully remove the appliance and components from the packaging The vent system components and decorative doors and fronts may be shipped in separate packages If packaged separately the log set and appliance grate must be installed Report to your dealer any parts damaged in shipment particularly the condition of the glass Read all of the instructions before starting the instal lation Follow these instructions carefully during the installation to ensure maximum safety and benefit WARNING Risk of Fire or Explosion Damaged parts could impair safe o
53. er to Section 5 ELECTRICAL ACCESS GAS LINE ACCESS LEFT SIDE FRONT VIEW RIGHT SIDE Location inches itimeters La f ion i Oo pp 9 E m NE P E LL Figure 16 1 Appliance Dimensions 60 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 B Vent Components Diagrams Effective DVP4 102 267 mm Height Length 152 DVP12 305 4 12 4 7 8 in DVP24 24 610 276 mm 36 48 Effective Length Inches Millimeters 10 172 in als le 10 7 8 in DVP Pipe see chart 1219 fem 3to6 76to 152 DVP45 45 Elbow 310 12 76 to 305 310 12 76 to 305 3to 24 76 to 610 11 3 8 in 289 mm EN LW 10 in 254 mm NES A 7 3 8 in 187 mm e E 7 i 1 1 4 in 32 mm 10 in 254 mm 9 1 4 in 1 o gt 235mm 4 2 in TYP e 13 1 4 in gt 3 mm 337 mm DVP AS Attic Shield DVP FS Ceiling Firestop DVP90ST 90 Elbow 12 in 305 mm E x 10 in 1 1 2 in eg 254 mm gt 38 mm UP i 5 in 12 in 127 mm 305 mm DVP HVS Vent Support DVP WS Wall Shield Firestop Figure 16 2 DVP vent components Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 61 B Vent Components Diagrams co
54. ess Due to high temperatures the appliance should be locat ed out of traffic and away from furniture and draperies AL E INSTALLATION E S d TOP VENT ONE 90 ELBOW REAR VENT REAR VENT HORIZONTAL TERMINATION ONE ELBOW TWO ELBOWS REAR VENT NO ELBOWS pate R STR waa e Figure 5 1 Appliance Locations 18 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 B Constructing the Appliance Chase A chase is a vertical box like structure built to enclose the gas appliance and or its vent system In cooler climates the vent should be enclosed inside the chase NOTICE Treatment of ceiling firestops and wall shield firestops and construction of the chase may vary with the type of building These instructions are not substitutes for the requirements of local building codes Therefore you MUST check local building codes to determine the requirements to these steps Chases should be constructed in the manner of all out side walls of the home to prevent cold air drafting prob lems The chase should not break the outside building envelope in any manner Walls ceiling base plate and cantilever floor of the chase should be insulated Vapor and air infiltration barriers should be installed in the chase as per regional codes for the rest of the home Additionally in regions where cold air infiltration may be an issue the inside surfaces may be sheetrocked and taped fo
55. from side to side and front to back Shim the appliance as necessary It is acceptable to use wood shims underneath the appliance Secure the appliance to the framing by using nails or screws through the nailing tabs Secure the appliance to the floor by inserting two screws through the pilot holes at the bottom of the appliance NAILING TABS BOTH SIDES PILOT HOLES Figure 9 9 Proper Positioning and Securing of an Appliance Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 37 10 Installing Vent Pipe DVP and SLP Pipe A Assemble Vent Sections DVP Pipe Only Attach Vent to the Firebox Assembly Note The end of the pipe sections with the lanced tabs will face toward the appliance Attach the first pipe section to the starting collar Lanced pipe end to the starting collar Inner pipe over inner collar Push the pipe section until all lanced tabs snap in place Lightly tug on pipe to confirm it has locked Commercial Multi family Multi level exceeding two sto ries or High Rise Applications All outer pipe joints must be sealed with high temperature silicone including the slip section that connects directly to the horizontal termination cap Apply a bead of silicone sealant inside the female outer pipe joint prior to joining sections See Figure 10 1 Only outer pipes need to be sealed All unit collar pipe slip section elbow and cap outer flues shall
56. g and firestop systems Install wall shield and ceiling firestops as speci fied Note The 6000 series fireplaces can adapt to SLP series vent pipe if desired When venting off the top of the unit use a DVP 2SL adapter and a minimum 48 inch vertical section of SLP series vent pipe A DVP SLP24 adapter may also be used with a 24 inch vertical section of SLP series vent pipe After the 48 inch vertical section the venting table rules must be i l Failure to keep insulation or other material away followed The first 48 inch vertical section is NOT counted as part of the vertical components in the table It is still counted as part of the overall maximum run All venting table rules for the vent run must still be followed from vent pipe may cause fire Example DVP pipe 3 ft min vertical 11 ft max horizontal SLP pipe 7 ft min vertical 11 ft max horizontal Fire Risk When using DVP HRC SS and DVP HRC ZC SS termination caps on top vented fireplaces a 6 inch minimum vertical vent section is required before installing first elbow Top Vent Horizontal Termination V H 40 ft 12 2 m Maximum 1 H 20 ft 6 1 m Maximum Note For corner installations A 6 inch 152 mm section of straight pipe may need to be attached to the appliance before a 90 elbow to allow the vent pipe to clear the top standoffs Figure 7 3 V Minimum H H Maximum Note For corner installations A 6 inch 15
57. glasses Inspect venting and termination cap for blockage or obstruction such plants bird nests leaves snow debris etc Verify termination cap clearance to subsequent construc tion building additions decks fences or sheds See Section 6 Inspect for corrosion or separation Verify weather stripping sealing and flashing remains intact Inspect draft shield to verify it is not damaged or missing B Maintenance Tasks Qualified Service Technician The following tasks must be performed by a qualified ser vice technician Gasket Seal and Glass Assembly Inspection Frequency Annually By Qualified Service Technician Tools needed Protective gloves drop cloth and a stable work surface Inspect gasket seal and its condition Inspect fixed glass assembly for scratches and nicks that can lead to breakage when exposed to heat Confirm there is no damage to glass or glass frame Replace as necessary Verify that fixed glass assembly is properly retained and attachment components are intact and not damaged Replace as necessary Logs Frequency Annually By Qualified Service Technician Tools needed Protective gloves Inspect for damaged or missing logs Replace as neces sary Refer to Section 14 for log placement instructions Verify correct log placement and no flame impingement causing sooting Correct as necessary Firebox Frequency Annually By Qualified Service Technician Tools needed
58. himble can be installed on a flat ceil ing through which the vent passes The decorative ceiling thimble is used to cover the firestop CATHEDRAL CEILING D D R SUPPORT BOX O Seal the gap between the vent pipe and firestop using high temperature silicone to prevent cold air infiltration Install the decorative ceiling thimble by sliding it up to the ceiling and attaching it using the provided screws 2 in 51 mm MIN BELOW FINISHED CEILING A decorative cathedral ceiling support box can be installed on a cathedral ceiling through which the vent passes CUT HOLE 1 8 in 3 mm Use a plumb bob to mark the center line of the venting GREATER IN SIZE THAN system on the ceiling and drill a small hole through the PATTERN OF SUPPORT gw BOX AS IT IS PROJECTED ceiling and roof at this point Locate the hole and mark ONTO ROOF LINE the outline of the cathedral ceiling support box on the outside roof Remove shingles or other roof covering as necessary Figure 10 12 to cut the rectangular hole for the support box Cut the hole 1 8 in 3 mm larger than the support box outline Lower the support box through the hole in the roof until its bottom is at least 2 in 51 mm below the ceiling Figure 10 12 Level the support box both vertically and horizontally and temporarily tack it in place through the inside walls into the roof sheathing Use tin snips to cut the support box from the top corners
59. horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CAN CGA B149 installation codes and refer to Section 6 of this manual CAUTION Risk of Burns Local codes may require in stallation of a cap shield to prevent anything or anyone from touching the hot cap NOTICE For certain exposures which require superior resistance to wind driven rain penetration a flashing kit and HRC caps are available When penetrating a brick wall a brick extension kit is available for framing the brick Note When using termination caps with factory supplied heat shield attached no additional wall shield firestop is required on the exterior side of a combustible wall HEAT SHIELD OR HEAT SHIELD Rec 1 1 2 IN 38 MM MIN OVERLAP WALL SHIELD FIRESTOP N SLIP SECTION 1 CAN BE EXTENDED INNER VENT OUTER VENT SHEATHING INTERIOR EXTERIOR VENT DEPTH FROM BACK OF APPLIANCE TO OUTSIDE SURFACE OF EXTERIOR WALL gt SEE CHART BELOW Figure 10 25 Venting through the wall Cap Specification Chart depth without using additional pipe sections DVP TRAPK1 DVP TRAP1 DVP TRAPK2 DVP TRAP2 Top Vent Rear Vent Top Vent Rear Vent Depth Depth Depth Depth 2 3 4 in to 3 1 8 in to 5 1 8in to 5 1 2 in to 4 5 8 in 5 in 9 1 8 in 9 1 2 in DVP HPC1 DVP HPC1 DVP HPC2 DVP HPC2 Top Vent Rear Vent Top Vent Rear
60. ipe section while placing the outer collar of the cap over the outer flue of the pipe section Secure the cap by driving three self tapping screws supplied through the pilot holes in the outer collar of the cap into the outer flue of the pipe see Figure 10 23 Figure 10 23 K Install Decorative Wall Components SLP only A decorative wall thimble can be installed on wall through which the vent passes The decorative wall thimble is used to cover the wall shield firestop Slide the decorative wall thimble over the last section of horizontal pipe before connecting the termination cap to the pipe Once the pipe section and the termination cap have been connected slide the wall thimble up to the interior wall surface and attach with screws provided See Figure 10 24 Figure 10 24 Wall Thimble L Heat Shield Requirements for Horizontal Termination WARNING Risk of Fire To prevent overheating and fire heat shields must extend through the entire wall thick ness DO NOT remove the heat shields attached to the wall shield firestop and the horizontal termination cap shown in Figure 10 25 Heat shields must overlap 1 1 2 in 88 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other section is factory attached to the cap See Figure 10 25 If the wall thickness does not allow the required 1 1 2 in 88 mm heat shield overlap when in
61. lacement of logs ember material and or other decorative materials Check the wiring Check the air shutter adjustment Ensure that there are no gas leaks Ensure that the glass is sealed and in the proper position and that the integral barrier is in place WARNING Risk of Fire or Asphyxiation DO NOT op erate fireplace with fixed glass assembly removed 10 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 l Lighting Instructions IPI The IPI system may be operated with two D cell batteries When using batteries unplug the transformer To prolong battery life remove them when using the transformer L FOR YOUR SAFETY L C LIGHTING 1 READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life This appliance is equipped with an intermittent pilot ignition IPI device which automatically lights the burn er DO NOT try to light the burner by hand BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electric switch do not use any phone in your building WARNING DO NOT CONNECT 110 VAC TO THE CONTROL VALVE Improper installation adjustment al teratio
62. ld and vent pipe and to maintain air space clearance Vaulted Ceiling Installation Remove one shield from box NOTICE Cut previously installed batt insulation to make room for the attic insulation shield Cut the attic insulation shield if application is for vaulted ceiling to fit your ceiling pitch Snip cut edge to recreate 1 in bend tabs all the way around the bottom Wrap shield around pipe if pipe is already installed in area to be insulated Match the three holes in each side and fasten with three screws to form a tube Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling firestop Bend the remaining bottom tabs inward 90 to maintain the air space between the pipe and the shield Set the shield on the ceiling firestop and attach to the firestop Bend all tabs inward 90 around the top of the shield These tabs must be used to prevent blown insulation from getting between the shield and vent pipe and to maintain air space clearance BEND ALL TABS INWARD 90 TO MAINTAIN CLEARANCE AND PREVENT INSULATION FROM FALLING INSIDE BEND 3 TABS OUTWARD TO FASTEN TO CEILING FIRESTOP BEND REMAINING TABS INWARD 90 DEGREES TO MAINTAIN CLEARANCE Figure 8 5 Attic Insulation Shield E Installing the Optional Heat Zone Gas Kit Remove the knockout from the fireplace and discard it see Figure 8 6 Center the duct collar around the exposed hole and attach it to the fireplace
63. losion Follow ember placement instructions in manual DO NOT place embers directly over burner ports Replace ember material annually Improperly placed embers interfere with proper burner operation Ember material is shipped with this gas appliance To place the ember material Embers CANNOT be placed directly over ports Care should be taken not to cover the lighting trail of ports from back to front Place dime size pieces of Glowing Embers just in front of the port trail but not on or in between the ports see Figure 14 6 Care should be taken so that the ports are not covered Failure to follow this procedure will likely cause lighting and sooting problems Figure 14 6 Placement of Embers Place Mystic Embers on areas of base refractory away from port holes Use this material to give the appliance a realistic ash bed Save the remaining ember materials for use during appliance servicing The embers provided should be enough for 3 to 5 applications Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 53 G Install the Log Assembly Log Assembly LOGS 6000GLX LOGS 6000GLXLP If the gas logs have been factory installed they should not need to be positioned If the logs have been packaged separately refer to the following instructions STEP 1 CAUTION Logs are fragile Carefully remove the logs grate and supporting cardboard from the inside of the fireplace See Figure 14 7
64. n service or maintenance can cause injury or property damage Re fer to the owner s information manual provided with this appliance This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air If not installed operated and main tained in accordance with the man ufacturer s instructions this product could expose you to substances in fuel or fuel combustion which are known to the State of California to cause can cer birth defects or other reproductive harm Keep burner and control compartment clean See installation and operating instructions accompanying appliance Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions f you cannot reach your gas sup plier call the fire department C DO NOT use this appliance if any part has been under water Imme diately call a qualified service tech nician to inspect the appliance and to replace any part of the control System and any gas control which has been under water CAUTION Hot while in operation DO NOT touch Keep children clothing furniture gaso line and other liquids having flammable vapors away DO NOT operate the appliance with fixed glass assembly removed cracked or broken Replacement of the fixed glass assembly should be done by a licensed or qualified service person NOT FOR USE WITH SOLID FUEL For use with natu
65. nnector 1 4 in male as shown Romex Connector Cover Plate outside firebox Copper GRN wire ground attached inside box to GRN screw with GRN wire NOTICE DO NOT wire 110 VAC to wall switch Figure 12 2 Junction Box Detail Switch Minimum 14 3 AWG with Ground Junction Box Power Supply Wires Switch Box Knockout Figure 12 3 Junction Box Wired to Wall Switch or BC10 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 49 1 Finishing A Mantel and Wall Projections B Facing Material WARNING Risk of Fire Comply with all minimum clear Metal front faces may be covered with non combustible ances as specified Framing closer than the minimums list materials only ed must be constructed entirely of noncombustible materi n Facing and or finishing materials must not interfere with air flow through louvers operation of louvers or doors or access for service als i e steel studs concrete board etc Failure to comply could cause fire Combustible Mantels Facing and or finishing materials must never overhang into the glass opening re Observe all clearances when applying combustible Note All materials measurements in inches L o Seal joints between the finished wall and appliance top and sides using a 300 F minimum sealant Refer to Figure 13 3 WARNING Risk of Fire DO NOT apply combustible
66. nt Seal Cap Burner Neck Shutter 2103 081 Bracket Manifold and Valve Plate Gaskets Glass Latch Assembly Mineral Wool Touch Up Paint Vermiculite Embers Wall Switch Kit Additional service part numbers on following page C 86 122A 50 721 TUP GBK 12 MYSTIC EMBERS WSK300 HNG L L NN 13 E L EE WS L L L Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 69 H EAT GLO Service Parts 6000G LX IPI R S No one builds a better fire Valve Assembly Diagram Parts List Beginning Manufacturing Date May 2006 Ending Manufacturing Date Intermittent Pilot Ignition Valve Assembly Part number list on following page 70 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 Service Parts List 6000GLX IPI R S IMPORTANT THIS IS DATED INFORMATION When requesting service or replacement parts for your appliance please provide model number and serial number All parts listed Stocked in this manual may be ordered from an authorized dealer at Depot ITEM DESCRIPTION COMMENTS PART NUMBER Pilot Assembly NG 2090 012 Y Pilot Assembly LP 2090 013 Y Shutter Sleeve 8026 130 Y 3 Shutter Bracket Assembly e 2026 017 Y lt lt lt Valve Bracket Flex Ball Valve Assembly mber Bulb 20W ulb Socket Assembly Valve NG Valve LP Orifice NG 39C Orifice LP 54C ontrol Module lex 12 ire Assembly rn CH M z
67. nt burner and circulating air passageway of the fireplace must be kept clean CAUTION Risk of Burns The fireplace should be turned off and cooled before servicing Glass Cleaning Frequency Seasonally By Homeowner Tools Needed Protective gloves glass cleaner drop cloth and a stable work surface CAUTION Handle fixed glass assembly with care Glass is breakable Avoid striking scratching or slamming glass Avoid abrasive cleaners DO NOT clean glass while it is hot Prepare a work area large enough to accommodate fixed glass assembly and door frame by placing a drop cloth on a flat stable surface Note Fixed glass assembly and gasketing may have res idue that can stain carpeting or floor surfaces Remove door or decorative front from fireplace and set aside on work surface See Section 14 H for instructions to remove fixed glass assembly Clean glass with a non abrasive commercially available cleaner Light deposits Use a soft cloth with soap and water Heavy deposits Use commercial fireplace glass cleaner consult with your dealer Carefully set fixed glass assembly in place on fireplace Hold glass in place with one hand and secure glass latches with the other hand Reinstall door or decorative front Doors Surrounds Fronts Frequency Annually By Homeowner Tools needed Protective gloves stable work surface Assess condition of screen and replace as necessary Inspect fo
68. ntinued Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required 8in 203 mm Heat Shield Term Ca Minimum Maximum P Effective Length Effective Length Effect Tapi 3 1 8 in 4 5 8 in puede SC om mm Length 79 mm 117 mm DVP TRAP 5 3 8 in 9 3 8 in DVP TRAP1 DVP TRAP2 DVP TRAPK1 DVP TRAPK2 Bal WI DVP HPC1 DVP HPC2 Pog CPC Lr Figure 16 3 DVP vent components 62 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 B Vent Components Diagrams continued 13 1 4 in 367 mm ee 24 5 8 in 27 1 2 in 625 mm nw Que D I mm RF6M Roof Flashing Multi pak lt 13 3 4 in x 349 mm 13 3 4 in 349 mm N BEK Trap Cap Brick Extension 7 1 8 in 181 mm DVP TRAPFL Flashing DVP HSM B Extended Heat Shield Figure 16 4 DVP vent components 31 in 787 mm 24 5 8 in 625 mm 13 1 4 in 67 mm RF12M Roof Flashing Multi pak
69. othing or other g P yig q vacations trips etc flammable materials Keep clothing furniture draperies and other flammable Remove batteries from remote controls materials away y Turn off wall controls This appliance has been supplied with an integral barrier e Unplug 3 volt adapter plug and remove batteries on IPI to prevent direct contact with the fixed glass panel DO models NOT operate the appliance with the barrier removed Contact your dealer or Hearth amp Home Technologies if the B Your Fireplace barrier is not present or help is needed to properly install one WARNING DO NOT operate fireplace before read ing and understanding operating instructions Failure to operate fireplace according to operating instructions could cause fire or injury If you expect that small children or vulnerable adults may come into contact with this fireplace the following precau tions are recommended Install a physical barrier such as Adecorative firescreen Adjustable safety gate DECORATIVE DOORS NOT SHOWN SECTION 2 E FIXED GLASS ASSEMBLY NOT SHOWN SECTION 14 H FAN KIT SECTION 2 C CLEAR SPACE SECTION 2 D d Figure 2 1 General Operating Parts Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 9 C Fan Kit optional If desired a fan kit may be added Contact your dealer to order the correct fan kit D Clear Space WARNING DO NO
70. ould ignite Purge should be performed by qualified service technician e Ensure adequate ventilation e Ensure there are no ignition sources such as sparks or open flames Light the appliance It will take a short time for air to purge from lines When purging is complete the appliance will light and operate normally WARNING Risk of Fire Explosion or Asphyxiation Check all fittings and connections with a non corrosive commercially available leak check solution DO NOT use open flame Fittings and connections could have loos ened during shipping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory D High Altitude Installations NOTICE If the heating value of the gas has been reduced these rules do not apply Check with your local gas utility or authorities having jurisdiction When installing above 2000 feet elevation s Inthe USA Reduce burner orifice 4 for each 1000 feet above 2000 feet In CANADA Reduce burner orifice 10 for elevations between 2000 feet and 4500 feet Above 4500 feet consult local gas utility 46 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 1 Electrical Information A Wiring Requirements NOTICE This appliance must be electrically wired and grounded in accordance with local codes or in the absence of local codes with National Electric Code ANSI NFPA 70 latest edition or the Canadian Elect
71. p pipe If slip section seals are broken during removal of the termination cap vent may leak Note Align seams to engage pipe then rotate counterclockwise to lock Figure 10 5 Adding Venting Components C Assemble Slip Sections Slide the inner flue of the slip section into the inner flue of the pipe section and the outer flue of the slip section over the outer flue of the pipe section See Figure 10 6 Slide together to the desired length d P Pilotihole Figure 10 6 Slip Section Pilot Holes Maintain a 1 1 2 in 38 mm overlap between the slip section and the pipe section Secure the pipe and slip section with two screws no longer than 1 2 in 13 mm using the pilot holes in the slip section See Figure 10 7 Figure 10 7 Screws into Slip Section Continue adding pipe as necessary following instructions in Assembling Pipe Sections NOTICE If slip section is too long the inner and outer flues of the slip section can be cut to the desired length NOTICE When installing a vent system with an HRC termination cap all pipe system joints shall be sealed using a high temperature silicone sealant e Apply a bead of silicone sealant inside the female outer pipe joint prior to joining sections e Only outer pipes are sealed sealing the inner flue is not required e All unit collar pipe slip section elbow and cap outer flues shall be sealed Heat amp Glo 6000GLX IPI S R 60
72. pe 45 11 Gas Information A Fuel Conversion 0000 cece eee eee 46 B Gas Pressure issue ee eae eee and wad Geek es 46 C Gas Connection E R cece ase RE de rade dats 46 D High Altitude Installations l l 46 12 Electrical Information A Wiring Requirements llli 47 B Intellifire Ignition System Wiring llle 47 C Optional Accessories Requirements 47 D Electrical Service and PHenar lilius 48 E Junction Box Installation sa saauaaaan aaau 49 F Wall Switch Installation for Fan Optional 49 13 Finishing A Mantel and Wall Projections sse sess 50 B Facing Material Sa a ees R R me 50 Gs DOORS ood e ra tuia eon ae ate 51 14 Appliance Setup A Remove Fixed Glass Assembly n n uananaannnn 52 B Remove the Shipping Materials 52 C Clean the Appliance esee 52 D ACCOSSOFIOS i cb RR R eee E deet 52 E Install the Refractory 52 E Ember Placement secre tx Hee Lev 53 G Install the Log Assembly llis esses 54 H Fixed Glass Assembly esses 57 I Installthe Mesh 0 0 0 0 eee nme 57 J Install Trim and or Surround 00000 ee eee 57 K Air Shutter Geng 57 15 Troubleshooting A Intellifire Ignition System 0 0 eee eee 58 16 Reference Materials A Appliance Dimension Diagram u 60 B Vent Components Diagrams eee ae 61 G Service Parts agina pihet pere tne AE
73. peration DO NOT install damaged in complete or substitute components Keep appliance dry Hearth amp Home Technologies disclaims any responsibility for and the warranty will be voided by the following actions Installation and use of any damaged appliance or vent system component Modification of the appliance or vent system Installation other than as instructed by Hearth amp Home Technologies Improper positioning of the gas logs or the glass door Installation and or use of any component part not approved by Hearth amp Home Technologies Any such action may cause a fire hazard WARNING Risk of Fire Explosion or Electric Shock DO NOT use this appliance if any part has been under water Call a qualified service technician to inspect the appliance and to replace any part of the control system and or gas control which has been under water Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 17 Framing and Clearances A Selecting Appliance Location NOTICE Illustrations reflect typical installations and are spits FOR DESIGN PURPOSES ONLY Illustrations diagrams When selecting a location for the appliance it is important to d eA installati duas consider the required clearances to walls see Figure 5 1 AEO rawn to Stale Acua NStaNatNon may vary Gue es individual design preference WARNING Risk of Fire or Burns Provide adequate clearance around air openings and for service acc
74. r an SLP FS when using the RF4 8 Flashing Refer to Section 10 D Secure Vent Sections Figure 10 19 Trim Rubber Boot Figure 10 18 Secure Pipe with SLP FS Trim the rubber boot using scissors or a utility knife cutting along the marked measurement lines See Figure 10 19 Use the 150 mm line for SLP 210 mm for DVP Lubricate pipe or flue with water and slide the flashing down It may be necessary to trim the top shingles around the base of the rubber boot to ensure a good fit Draw a line around flashing Remove flashing Apply silicone sealant to roof inside the lines Figure 10 20 Lubricate pipe or flue with water and slide flashing down Seat firmly in sealant Nail roof flashing to the roof Apply silicone sealant on the top and sides edges of the flashing See Figure 10 21 Install shingles Apply sealant at the top edge of the rubber boot See Figure 10 22 We recommend that you top coat with conventional acrylic house paint to improve the appearance of your galvanized base flashing lx 5 Figure 10 20 Apply Sealant APPLY SEALANT TOP amp PARTIAL SIDES SILICONE SEALANT TOP OF BOOT A FLASHING O SHINGLES 24 4 Figure 10 22 Installation Complete Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 43 J Install Vertical Termination Cap Attach the vertical termination cap by sliding the inner collar of the cap into the inner flue of the p
75. r maximum air tightness Rough Rough Rough Rough Opening Opening Opening Opening Vent Pipe Height Depth Width Adjust framing dimensions for interior sheathing such as sheetrock C Add 12 inches for rear venting with one 90 elbow Figure 5 2 Clearances to Combustibles Clearance to Ceiling To further prevent drafts the wall shield and ceiling fire stops should be caulked with high temperature caulk to seal gaps Gas line holes and other openings should be caulked with high temperature caulk or stuffed with un faced insulation If the appliance is being installed on a cement surface a layer of plywood may be placed under neath to prevent conducting cold up into the room C Clearances NOTICE Install appliance on hard metal or wood surfaces extending full width and depth DO NOT install directly on carpeting vinyl tile or any combustible material other than wood WARNING Risk of Fire Maintain specified air space clearances to appliance and vent pipe Insulation and other materials must be secured to prevent accidental contact The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fireplace or chimney Failure to maintain airspace may cause overheating and a fire Combustible Combustible Behind Sides of Front of Flooring Appliance Appliance Appliance Heat amp Glo 6000GLX IPI S R 6
76. r operating this appliance Please retain this owner s manual for future reference A Congratulations This owner s manual should be retained for future reference We suggest that you keep it with your other Congratulations on selecting a Heat amp Glo gas fireplace an important documents and product manuals elegant and clean alternative to wood burning fireplaces The Heat amp Glo gas fireplace you have selected is designed The information contained in this owner s manual unless to provide the utmost in safety reliability and efficiency t otherwise applies to all models and gas control Systems As the owner of a new fireplace you ll want to read and e carefully follow all of the instructions contained in this Your new Heat amp Glo gas fireplace will give you years of owner s manual Pay special attention to all cautions and durable use and trouble free enjoyment Welcome to the wamings Heat amp Glo family of fireplace products Homeowner Reference Information We recommend that you record the following pertinent information about your fireplace Model Name Date purchased installed Serial Number Location on fireplace Dealership purchased from Dealer Phone Notes Listing Label Information Location The model information regarding your specific fireplace can be found on the rating plate usually located in the control area of the fireplace This product may be covered by one or more
77. r scratches dents or other damage and repair as necessary Check that louvers are not blocked Vacuum and dust surfaces Remote Control Frequency Seasonally By Homeowner Tools needed Replacement batteries and remote con trol instructions Locate remote control transmitter and receiver Verify operation of remote Refer to remote control operation instructions for proper calibration and setup procedure Place batteries as needed in remote transmitters and battery powered receivers Place remote control out of reach of children If not using your fireplace for an extended period of time summer months vacations trips etc to prevent unin tended operation s Remove batteries from remote controls Unplug 3 volt adapter plug on IPI models Light Bulbs Frequency As needed By Homeowner Tools needed Protective gloves replacement light bulbs Remove the door or front from the fireplace There are two square boxes hanging down behind the gas valve These are separated into two pieces While wearing gloves grasp the sides of the box and slide the front side portion towards you The front will slide free of the rest of the box Remove the bulb by pulling straight out Reverse the steps to replace the bulb into the box Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 13 Venting Frequency Seasonally By Homeowner Tools needed Protective gloves and safety
78. ral gas and propane A conversion kit as supplied by the manufacturer shall be used to convert this appliance to the alternate fuel Also Certified for Installation in a Bedroom or a Bedsitting Room For assistance or additional informa tion consult a qualified installer ser vice agency or the gas supplier For additional information on operating your Hearth amp Home Technologies fireplace please refer to www fireplaces com Final inspection by INSTRUCTIONS IPI Turn off all electric power to the appliance This appliance is equipped with an ignition device which automatically lights the burner DO NOT try to light the burner by hand OW O OO A Q Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the Safety Information located on the left side of this la bel If you do not smell gas go to next step Turn on all electric power to the appliance To light the burner flip the ON OFF switch to the ON position The ON OFF switch may include a wall switch if so equipped If the appliance will not operate follow the in structions To Turn Off Gas to Appliance and call your service technician or gas supplier ITO TURN OFF GAS TO APPLIANCE Turn wall control or ON OFF switch to OFF Turn off all electric power to the appliance if service is
79. ric Code CSA C22 1 Wire the appliance junction box to 110 120 VAC This is required for proper operation of the appliance A 110 120 VAC circuit for this product must be protected with ground fault circuit interrupter protection in compliance with the applicable electrical codes when it is installed in locations such as in bathrooms or near sinks Low voltage and 110 VAC voltage cannot be shared within the same wall box WARNING Risk of Shock or Explosion DO NOT wire 110V to the valve or to the appliance wall switch Incorrect wiring will damage controls B Intellifire Ignition System Wiring Wire the appliance junction box to 110 VAC for proper operation of the appliance WARNING Risk of Shock or Explosion DO NOT wire IPI controlled appliance junction box to a switched circuit Incorrect wiring will override IPI safety lockout Refer to Figure 12 1 Intellifire Pilot Ignition IPI Wiring Diagram This appliance is equipped with an Intellifire control valve which operates on a 3 volt system Plug the 3 volt AC transformer into the appliance junction box to supply power to the unit OR install two D cell batteries not included into the battery pack before use NOTICE Batteries should not be placed in the battery pack while using the transformer Remove batteries before using the transformer and unplug the transformer before installing the batteries Battery polarity must be correct or module damage will occur
80. s A copy of all installation instructions for all Product Ap proved side wall horizontally vented gas fueled equip ment all venting instructions all parts lists for venting instructions and or all venting design instructions shall remain with the appliance or equipment at the completion of the installation See Gas Connection section for additional Common wealth of Massachusetts requirements 8 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 User Guide Operating Instructions A Gas Fireplace Safety Install a switch lock or a wall remote control with child protection lockout feature A WARNING Keep remote controls out of reach of children HOT SURFACES Never leave children alone near a hot fireplace whether Glass and other surfaces are hot during operating or cooling down operation AND cool down e Teach children to NEVER touch the fireplace Hot glass will cause burns E Consider not using the fireplace when children will be DO NOT touch glass until it is cooled 9 P NEVER allow children to touch glass presen Keep children away Contact your dealer for more information or visit www e CAREFULLY SUPERVISE children in same room as hpba org staysafe fireplace d Alert children and adults to hazards of high temperatures To prevent unintended operation when not using your fire place for an extended period of time summer months High temperatures may ignite cl
81. s Verify air shutter setting is correct See Section 14 for required air shutter setting Verify air shutter is clear of dust and debris Inspect orifice for soot dirt and corrosion Verify orifice size is correct See Service Parts List for proper orifice sizing Verify manifold and inlet pressures Adjust regulator as required Inspect pilot flame pattern and strength See Figure 3 1 for proper pilot flame pattern Clean or replace orifice spud as necessary Inspect thermocouple thermopile or IPI flame sensing rod for soot corrosion and deterioration Clean with emery cloth or replace as required Verify that there is not a short in flame sense circuit by checking continuity between pilot hood and flame sensing rod Replace pilot as necessary 14 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 Figure 3 1 IPI Pilot Flame Patterns Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 15 Getting Started Installer Guide A Typical Appliance System NOTICE Illustrations and photos reflect typical installations and are for design purposes only Illustrations diagrams are not drawn to scale Actual product may vary from pictures in manual HORIZONTAL Note Dual venting configurations M RECON IDA ARE NOT allowed Appliance MUST be vented EITHER vertically OR horizontally VERTICAL TERMINATION CAP SECTION 10 J NON COMBUSTIBLE
82. s line at test pressures equal to or less than 1 2 psig Note Have the gas supply line installed in accordance with local codes if any If not follow ANSI 223 1 Installation should be done by a qualified installer approved and or licensed as required by the locality In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter Note A listed and Commonwealth of Massachusetts ap proved 1 2 in 13 mm T handle manual shut off valve and flexible gas connector are connected to the 1 2 in 13 mm control valve inlet e If substituting for these components please consult local codes for compliance C Gas Connection Refer to Reference Section 16 for location of gas line access in appliance Gas line may be run through knockout s provided The gap between supply piping and gas access hole may be caulked with high temperature caulk or stuffed with non combustible unfaced insulation to prevent cold air infiltration Ensure that gas line does not come in contact with outer wrap of the appliance Follow local codes Pipe incoming gas line into valve compartment Connect incoming gas line to the 1 2 in 13 mm connection on manual shutoff valve WARNING Risk of Fire or Explosion Support control when attaching pipe to prevent bending gas line Asmall amount of air will be in the gas supply lines WARNING Risk of Fire or Explosion Gas build up dur ing line purge c
83. se of Elbows Diagonal runs have both vertical and horizontal vent as pects when calculating the effects Use the rise for the vertical aspect and the run for the horizontal aspect see Figure 7 1 Two 45 elbows may be used in place of one 90 elbow On 45 runs one foot of diagonal is equal to 8 1 2 in 216 mm horizontal run and 8 1 2 in 216 mm vertical run A length of straight pipe is allowed between two 45 elbows see Figure 7 1 Vertical Horizontal Figure 7 1 D Measuring Standards Vertical and horizontal measurements listed in the vent diagrams were made using the following standards Pipe measurements are shown using the effective length of pipe see Figure 7 2 Horizontal terminations are measured to the outside mounting surface flange of termination cap see Figure 6 3 Vertical terminations are measured to bottom of termination cap Horizontal pipe installed level with no rise Effective Length DVP4 pow Lows s 59 _ Ettective vere 12 305 Cla Pas 4 12 Height Length 24 6 48 Cos aa DVP12A Figure 7 2 DVP Pipe Effective Length Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 23 E Vent Diagrams Top Vent Horizontal Termination A WARNING Fire Risk Explosion Risk Do NOT pack insulation or other combustibles between ceiling firestops ALWAYS maintain specified clearances around ventin
84. sist with siz ing the finishing material FINISH MATERIAL DOOR FIT MAXIMUM THICKNESS iiio nside nside ateau alencia alleria FINISHING MATERIAL FINISHING MATERIAL DOOR Stop finishing material flush with opening Figure 13 4 Folio Door 1 in MAX FINISHING MATERIAL TOP EDGE Finishing materials 1 inch maximum thick Stop finishing material flush with opening Figure 13 5 Overlap Fit Door 374AAin induces 1 8in opening each side of door includes 1 8in opening each side of door Finishing materials over 1 inch thick Figure 13 6 Inside fit door 1 2 IN THICK 1 2 IN THICK FINISHING FINISHING MATERIAL l ST MATERIAL IF FINISHING MATERIAL IS THICKER THAN 2 IN DOORS WILL ONLY OPEN AS FAR AS PICTURED 37 1 4 IN Finishing material between 1 and 3 inches thick Figure 13 7 Operable hinge door Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S
85. stalled an extended heat shield must be used If the wall thickness is less than 4 in 102 mm DVP or 4 3 8 in 111 mm SLP the heat shields on the cap and wall shield firestop must be trimmed A minimum 1 1 2 in 38 mm overlap MUST be maintained Use an extended heat shield if the finished wall thickness is greater than 7 1 4 in 184 mm The extended heat shield may need to be cut to length maintaining sufficient length for a 1 1 2 in 38 mm overlap between heat shields Attach the extended heat shield to either of the existing heat shields using the screws supplied with the extended heat shield Refer to vent components diagrams in the back of this manual Rest the small leg on the extended heat shield on top of the pipe section to properly space it from the pipe section Important Notice Heat shields may not be field constructed 44 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 M Install Horizontal Termination Cap DVP and SLP Pipe WARNING Risk of Fire The telescoping flue section of the termination cap MUST be used when connecting vent 1 1 2 38 mm minimum overlap of flue telescoping section is required Failure to maintain overlap may cause overheating and fire Venttermination must not be recessediin the wall Siding may be brought to the edge of the cap base Flash and seal as appropriate for siding material at outside edges of cap When installing a
86. stead Figure 7 14 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 29 Rear Vent Horizontal Termination continued Meum v minimom TR TR Oea Back to Back V H H 40 ft 12 2 m Maximum H 3 ft 914 mm Maximum H H 20 ft 6 1 m Maximum Two Elbows Figure 7 15 Three Elbows GE Cen 1ft 305 mm ack to Back 44 305mm 2ft 610 mm 90 Elbows V H H H 40 ft 12 2 m Maximum H 3 ft 914 mm Maximum H H H 20 ft 6 1 m Maximum Figure 7 16 30 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 Rear Vent Vertical Termination One Elbow Figure 7 17 Two Elbows Figure 7 18 en temm at eto mm V H 40 ft 12 2 m Maximum H 8ft 2 4 m Maximum H H Maximum V Minimum V H 40ft 12 2 m Maximum H H 8 ft 2 4 m Maximum INSTALLED HORIZONTALLY Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 31 Rear Vent Vertical Termination continued V Minimum H H Maximum Three Elbows H 8 ft 2 4 m Max V V H H 40 ft 12 2 m Max H H 20 ft 6 1 m Max Figure 7 19 H EE P er eam ok iam on erm 7e us ES EN Vi H H H 40 ft 12 2 m Maximum No specific restrictions on this value EXCEPT V H H H cannot exceed 40 ft 12 2 m Maximum H H
87. t assembly for shorted sparker wire or cracked insulator around electrode 3 Pilot sparks but A Gas supply Verify that incoming gas line ball valve is open Verify that inlet Pilot will not light pressure reading is within acceptable limits inlet pressure must not exceed 14 in W C B Ignitor gap is too large Verify gap of igniter to right side of pilot hood The gap should be approximately 17 in or 1 8 in 3 mm C Module is not grounded Verify module is securely grounded to metal chassis of appliance D Module voltage output Valve Pilot Verify battery voltage is at least 2 7 volts Replace batteries if volt solenoid ohms readings age is below 2 7 58 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 Intellifire Ignition System continued Symptom Possible Cause Corrective Action 4 Pilot lights but contin ues to spark and main burner will not ignite If the pilot continues to spark after the pilot flame has been lit flame rectification has not occurred A A shorted or loose connection in flame sensing rod Poor flame rectification or contaminated flame sensing rod Module is not grounded Damaged pilot assembly or contami nated flame sensing rod Verify all connections to wiring diagram in manual Verify connections underneath pilot assembly are tight Verify con nections are not grounding out to metal chassis pilot burn er pilot enclosure or s
88. tion is NOT permitted in screened porches Vent system termination is permitted in porch areas with two or more sides open You must follow all side walls overhang and ground clearances as stated in the instructions Heat amp Glo assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements CAUTION IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED 22 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 Vent Information and Diagrams A Approved Pipe This appliance is approved for use with Hearth amp Home Technologies DVP or SLP venting systems Refer to Sec tion 16B for vent component information DO NOT mix pipe fittings or joining methods from differ ent manufacturers The pipe is tested to be run inside an enclosed wall There is no requirement for inspection openings at each joint within the wall WARNING Risk of Fire or Asphyxiation This appli ance requires a separate vent DO NOT vent to a pipe serving a separate solid fuel burning appliance B Vent Table Key The abbreviations listed in this vent table key are used in the vent diagrams First section closest to appliance of vertical length Second section of vertical length n First section closest to appliance of horizontal length n Subsequent sections of horizontal length C U
89. uch as concrete a hole with diameter one inch greater than the pipe is acceptable Whenever a non combustible wall is penetrated the wall shield firestop is only required on one side and no heat shield is necessary L amp c Shows center of vent framing hole for top or rear venting The center of the hole is one 1 in 25 4 mm above the center of the horizontal vent pipe Figure 8 2 Wall Penetration Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 33 C Install the Ceiling Firestop A ceiling firestop MUST be used between floors and attics DVP pipe only Frame an opening 10 in by 10 in 254 mm by 254 mm whenever the vent penetrates a ceiling floor see Figure 8 3 SLP pipe only Frame opening 9 in x 9 in 229 mm x 229 mm whenever the vent penetrates a ceiling floor see Figure 8 3 Frame the area with the same sized lumber as used in ceiling floor joist The ceiling firestop may be installed above or below the ceiling joists when installed with a attic insulation shield It must be under joists between floors that are not insulated Refer to Figure 8 4 Secure with three fasteners on each side WARNING Risk of Fire DO NOT pack insu lation around the vent Insulation must be kept back from the pipe to prevent overheating ATTIC ABOVE 10 in 254 mm 9 in 229 mm Figure 8 3 Installing Ceiling Firestop INSTAL
90. utility Check with your local gas utility to determine proper orifice size E Non Combustible Materials Specification Material which will not ignite and burn Such materials are those consisting entirely of steel iron brick tile concrete slate glass or plasters or any combination thereof Materials that are reported as passing ASTM E 136 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 C and UL763 shall be considered non combustible materials F Combustible Materials Specification Materials made of or surfaced with wood compressed pa per plant fibers plastics or other material that can ignite and burn whether flame proofed or not or plastered or unplastered shall be considered combustible materials G Electrical Codes NOTICE This appliance must be electrically wired and grounded in accordance with local codes or in the absence of local codes with National Electric Code ANSI NFPA 70 latest edition or the Canadian Electric Code CSA C22 1 A 110 120 VAC circuit for this product must be pro tected with ground fault circuit interrupter protection in compliance with the applicable electrical codes when it is installed in locations such as in bathrooms or near sinks Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 7 Note The following requirements reference various Massachusetts and national codes not contained in this document H
91. with 3 screws Note Do this BEFORE final positioning of fireplace Determine the location for the air register fan housing assembly Reference the Heat Zone Gas kit instructions for the remaining installation steps HEAT ZONE GAS ATTACHES HERE Figure 8 6 Heat Zone Cover Plate Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 35 Appliance Preparation A Choosing the Top or Rear Vent CAUTION Risk of Cuts Abrasions or Flying Debris Wear protective gloves and safety glasses during instal lation Sheet metal edges are sharp NOTICE Once appliance is set up for top or rear venting it CANNOT be changed at a later time the elbow heat shield in place Use this heat shield over the first elbow if applicable For rear vent skip this step Figure 9 2 Cut the seal cap strap across the rectangles next to the disk Figure 9 3 Remove the white gasket material covering the seal cap Figure 9 4 Remove the seal cap NOTICE Once the seal cap has been removed it CANNOT be reattached Figure 9 5 Remove the insulation basket and white insu lation from the center vent pipe Proceed to Section 7 C 36 Heat amp Glo 6000GLX IPI S R 6000GLX IPILP S R 2101 900 Rev S 12 08 B Hear Vent NOTICE Once appliance is set up for top or rear venting it CANNOT be changed at a later time Figure 9 6 Remove the insulation from the outer vent pipe For rear

Download Pdf Manuals

image

Related Search

Related Contents

Vivez le Printemps - Bienvenue à la Ferme  MY100-10/14 - Mykay Tronics CC  QX-870 Industrial Raster Scanner User Manual  User`s Manual - Embedded Artists  Samsung SM-T217TMKATMB User's Manual  MEGÔMETRO DIGITAL  Operation Manual  Samsung AR12FC3TAURX User Manual  C-SC100 Ÿa    

Copyright © All rights reserved.
Failed to retrieve file