1. FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 19 of 62 6 2 5 Map Descriptor Example 1 Explicit Configuration using Network Management Polls The Map Descriptor pollTemp_p shows the use of SNVT_Units for Scaling when polling temperature The Map Descriptor pollSwitch shows the use of SNVT_Option for Selective data scanning This only brings in the State portion of SNVT_Switch Map_Descriptors Map_Descriptor Name Data_Array Name _ Data_Array Offset Lon_Function Function Node_ Name SNVT_Index SNVT_Type SNVT_Units SNVT_Option Scan_Interval pollTemp_p DA_Explicit 1 NMFETCHC Rdbc Remote_Node_ 0 SNVT_temp_p Deg_F fa 1 0s pollSwitch DA_Explicit 2 NMFETCHC Rdbc Remote_Node_ 1 SNVT_switch V State 1 0s This field determines the Map Explicitly Addressed Client Map Descriptors use For Non Throttled Descriptor s this field to point to their relevant Server Map Client Map function See Descriptors Descriptors the Section 6 1 2 Scan_Interval for more determines the information update rate 6 2 6 Map Descriptor Example 2 Polling UNVT s Map_Descriptors Map_Descriptor_Name Data_Array_Name Data_Array_Offset Lon_Function Function Node_Name SNVT_Index SNVT_Type UNVT_Byte Length S
2. 163 840 163 830 Type 163 835 32 767 Ox7FFF 1 Suggested Data Array Formats Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value Illumination Lux Data Length 0 65 535 N A Suggested Data Array Formats Data Length 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Mass Grams 0 6 553 5 N A FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 47 of 62 Data Length 1 Suggested Data Array Formats Float SNVT_mass_f Data Item 1 Measurement Units Values Range Invalid Value Mass Grams 0 3 40282E38 N A SNVT_mass_kilo SNVT_mass_mega SNVT_mass_mil SNVT_motor_state Data Length 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Mass Data Length Kilograms kg 0 6 553 5 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Mass Data Length Metric Tons Tonne 0 6 553 5 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value
3. Devices 25 Device_1 Device_1 lt gt Device_2 Neuronid 01 00 82 8E 4F 00 Programid 90 00 35 47 1 02 04 91 E Routers Self doc LonwoiksTestServer Device state On Line a Last reset cause External Firmware 7 Model number Q 1 Da all your bindings first Last error No Error 0 with NL220 NEWRON NEWRON SYSTEM General pil pepe Huga 2 Set the devices to gt Advanced FRANCE S ere ee 1 Amit errors crc O Transaction timeout 0 Now Click Configured in 33 05 hone 1845 NLUtil tool to commit the Lost messages Q Transactions full O bindi to the device 433 TE 16 44 dls Layer2 received 1533 Transmit retries O Web Layer3 received 891 Backlog overflows U ere corn Layer3 transmitted 884 Late acknowledgements 0 Soft key dissed messages 0 Collisions O Upgrade dongle Eepromlocks Q J NLSuite family r Tools LonWorks LNS and MIP i s software suite Online Configured PM Autotest eee i eee Hard offline Freq 1 100 s isual offices designer LNS plugin Bak Offline Application less fi 00 Windows API L LonWorks expertise Help Consultancy and training Appendix B 3 Honeywell Care This system uses unacknowledged service as default This protocol driver requires acknowledged service to operate correctly Appendix B 4 Tridium JACE This system uses unacknowledged service as default This protocol driver requires acknowledged
4. NV_Max_Value Network Variable updates with values higher than specified in this field will be ignored See Appendix A 2 NV_Delta_Value Network Variable updates where the value s delta change is less than specified in this field will be ignored unless the Max_Scan_Time Condition has been met Compulsory for Throttling Lon Functions only Not used on other Lon Functions See Appendix A 2 NV_Selfdoc_Text The Self Documenting String for this Network Variable Normal Text up to a length of 40 characters 6 3 5 Timing Parameters Column Title Function Legal Values 0 32000 Scan_Interval Seconds per scan gt s Minimum Scan Time in seconds Compulsory for Throttling Lon Functions See Appendix Min_Scan_Time only Not used on other Lon Functions A 3 Maximum Scan Time in seconds Compulsory for Throttling Lon Functions See Appendix Max_Scan_Time only Not used on other Lon Functions A 3 FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 23 of 62 6 3 6 Map Descriptor Example Server Side Map Descriptors Map_Descriptors Map_Descriptor_Name Data_Array_Name Data_Array_Offset Lon_Function Function Node_Name SNVT_Index Nv_Delta_Value SNVT_Type Nv_Min_Val
5. 16 N A Data Length bits in word 31 Suggested Data Array Formats Byte Uint16 Float Data Item 1 31 ascii00 ascii01 ascii30 Measurement Units Values Range Invalid Value Character String Data Length N A 0 255 N A 16 Suggested Data Array Formats Uint16 Float Data Item 1 char_set Measurement Units Values Range Invalid Value Locale Code N A 0 255 N A Data Item 2 16 wide_char00 wide_char14 Measurement Values Range Invalid Value Wide character string with NULL terminator Data Length 0 65 535 N A 2 Suggested Data Array Formats Float Data Item 1 Value Measurement Units Values Range Invalid Value Value Percentage of full scale 0 100 0 N A Data Item 2 State Measurement Units Values Range Invalid Value State Data Length N A 0 1 1 1 Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value telcom_states_t Data Length N A 0 20 255 OxFF TEL_NUL 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Temperature Degrees Celsius 274 0 6 279 5 N A Data Length 1 Suggested Data Array Formats Floa
6. Data Item 2 reg_val_unit Measurement Units Values Range Invalid Value reg_val_unit_t N A 0 43 255 OxFF RVU_NUL Data Item 3 reg_val_decimals Measurement Units Values Range Invalid Value Decimal Place Digits to Right of Decimal Point 0 7 N A Data Length 9 Suggested Data Array Formats Sint32 Data Item 1 reg _val_ts_raw Measurement Units Values Range Invalid Value Raw Value 2 147 483 648 N A 2 147 483 647 Data Item 2 reg val_ts_unit Measurement Units Values Range Invalid Value reg_val_unit_t N A 0 43 255 OxFF RVU_NUL Data Item 3 reg_val_ts bits Measurement Units Values Range Invalid Value See SNVT tables See SNVT tables 0 255 N A Data Item 4 reg_val_ts year Measurement Units Values Range Invalid Value Year Year 0 300 N A SNVT_reg_val_ts Data Item 5 reg_val_ts month Measurement Units Values Range Invalid Value Month Month of Year 0 12 N A Data Item 6 reg val_ts day Measurement Units Values Range Invalid Value Day Day of Month 0 31 N A Data Item 7 reg _val_ts_ hour Measurement Units Values Range Invalid Value Hour Hour of day 0 23 N A Data Item 8 reg_val_ts_min Measurement Units Values Range Invalid Value Minutes Minute of Hour 0 59 N A Data Item 9 reg_val_ts_secs Measurement Units Values Range Invalid Value Minutes Minute of Ho
7. FS 8700 21 LonWorks Manual Page 16 of 62 Example 2 Setting the Domain and Subnet from the configuration file FieldServer System_Station_Address Title node_id D Domain_ID S Subnet_ID Title continued The Title field must start with D followed by the Domain_ID in hexadecimal notation followed by S followed by the Subnet_ID in hexadecimal notation and enclosed by The domain length is automatically determined by the number of digits in the Domain_ID field Since 2 hexadecimal digits constitute 1 byte D123456 for example would have a length of 3 Once the domain table has been set the Dxx Sxx part of the Title field will be removed Now the Title field will be left with Title continued which may be the Node self documentation string or any title lon ini file contents The file may contain any values or be removed from the FieldServer FieldServer configuration file contents config csv FieldServer System_Station_Address Title 12 D48 S01 TESTING Specifying the Domain and Subnet in the configuration file will override the settings from the lon ini file 6 1 5 Network Management The NVPIEXC command generally used for polling has the limitation that data can only move in one direction Server to Client The added functionality of a Write through was added to the network management fetch command NMFETCHC to provide movement of data bac
8. Mass Data Length Milligrams mg 0 6 553 5 N A 1 Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value motor_state_t Data Length N A 0 7 255 OxFF MOTOR_NUL 2 Suggested Data Array Formats Uint16 Float Data Item 1 Multiplier A Measurement Units Values Range Invalid Value SNVT_mul_div E Hs Multiplier N A 0 65 535 N A Data Item 2 Divisor Measurement Units Values Range Invalid Value Divisor N A 1 65 535 0 Data Length 1 Suggested Data Array Formats Float SNVT_multiplier Data Item 1 Measurement Units Values Range Invalid Value Multiplier N A 0 32 7675 N A FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com 2 147 483 647 FS 8700 21 LonWorks Manual Page 48 of 62 Data Length 15 Suggested Data Array Formats Byte Uint16 Float Data Item 1 8 nv_type_pid0 nv_type_pid7 Measurement Units Values Range Invalid Value Program ID N A 0 255 N A Data Item 9 nv_type_scope Measurement Units Values Range Invalid Value Scope N A 0 6 N A Data Item 10 nv_type_index Measurement Units Values Range Invalid Value Type index
9. SNVT_btu_mega Data item 4 Measurement Units Values Range Invalid Value Thermal Energy Mega British Thermal 0 65 535 N A SNVT_char_ascii Data Length Units 1 Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value Character 8 bit ASCII Character 0 255 N A Data Length 3 Suggested Data Array Formats Byte Uint16 Float Data Item 1 chlr_run_mode Measurement Units Values Range Invalid Value Byte Uint16 Float 8 bit ASCII Character 0 255 N A SNVT_chir_status Data Item 2 chlr_op_mode Measurement Units Values Range Invalid Value hvac_t N A 0 17 255 OxFF HVAC_NUL Data Item 3 chir_state Measurement Units Values Range Invalid Value N A 0 255 N A Data Length 3 Suggested Data Array Formats Float Data Item 1 L_star Measurement Units Values Range Invalid Value Lightness Lightness 0 0 100 0 N A SNVT_color Data Item 2 a_star Measurement Units Values Range Invalid Value Redness Greenness Redness Greenness 200 0 200 0 N A Data Item 3 b_star Measurement Units Values Range Invalid Value Yellowness Blueness Yellowness Blueness 200 0 200 0 N A Data Length 1 SNVT_config_src SNVT_count SNVT_count_f SNVT_count_inc Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement
10. Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 25 of 62 Appendix A 5 Configuration Properties Configuration Properties are implemented on the FieldServer using configuration Network Variables Configuration Network Variables take the form of update inputs in order to be updated or read by a network management tool Each Configuration Network Variable will have its own Map Descriptor Since the data carried by a Network Variable is intended as a configuration property for other already declared non configuration Network Variable s no Data Array needs to be assigned to its Map Descriptor Configuration Properties can be declared to belong to the entire Node to an Object s or to a Network Variable s This declaration defines the scope of the Configuration Property Configuration Properties that belong to an Object are declared as a part of the Object Configuration Properties associated with a Network Variable s are declared as belonging to the Network Variable s etc A Configuration Property s Type and Responsible Map Descriptor s are declared by the Configuration Network Variable s self documentation string as follows For linking to the entire node amp 0 0 x80 SCPT Index Example amp 0 0 x80 20 For linking to object s amp 1 Object Index s 0 x80 SCPT Index Example amp 1 0 2 3 0 x80 23 For linking to ne
11. characterize the behavior of a device in the system Network installation tools realize this attribute and provide database storage to support maintenance operations If a device fails and needs to be replaced the configuration property data stored in the database is downloaded into the replacement device to restore the behavior of the replaced device in the system Configuration properties are implemented on the FieldServer through configuration network variables User defined configuration property types are not supported Appendix A 5 provides a list of standard configuration property types that are supported The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 6 of 62 3 DRIVER SCOPE OF SUPPLY 3 1 Supplied by FieldServer Technologies for this driver FieldServer Technologies Part Description FS 8700 21 Driver Manual 3 2 Provided by the Supplier of ae Party Equipment Part Description N A LonMaker Integration Tool from Echelon Corporation Optional Network Management Software N A LonWatcher from Distech Controls Inc Optional Network Management Software N A C
12. z z Measurement Units Values Range Invalid Value Flow volume Milliliters Second 0 65 535 N A ml s FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 44 of 62 Data Length 1 Suggested Data Array Formats Float SNVT_flow_p Data Item 1 Measurement Units Values Range Invalid Value Flow volume Cubic metres per hour 0 655 34 Raw 65 535 OxFFFF Type 655 35 Data Length 1 Suggested Data Array Formats Float SNVT_freq_f Data Item 1 Measurement Units Values Range Invalid Value Frequency Hertz 0 3 40282E38 N A SNVT_freq_hz SNVT_freq_kilohz SNVT_freq_milhz SNVT_fire_init Data Length 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Frequency Data Length Hertz 0 6 553 5 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Frequency Data Length Kilohertz 0 6 553 5 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Frequency Data Length Hertz 0 6 5535 N A 1 Suggested Data Array For
13. 1 Raw unadjusted data Occupied_cool Deg C 1 Degrees Celsius C Deg F 1 Degrees Fahrenheit F Raw 1 Raw unadjusted data Standby_cool Deg C 1 Degrees Celsius C Deg F 1 Degrees Fahrenheit F Raw 1 Raw unadjusted data SNVT_temp_setptlUnoccupied_cool Deg C 1 Degrees Celsius C Deg F 1 Degrees Fahrenheit F Raw 1 Raw unadjusted data Occupied_heat Deg C 1 Degrees Celsius C Deg F 1 Degrees Fahrenheit F Raw 1 Raw unadjusted data Standby_heat Deg C 1 Degrees Celsius C Deg_F 1 Degrees Fahrenheit F Raw 1 Raw unadjusted data Unoccupied_ heatDeg_C 1 Degrees Celsius C Deg_F 1 Degrees Fahrenheit F Page 29 of 62 FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 30 of 62 Appendix B Vendor Information Appendix B 1 Echelon LonMaker Appendix B 1 1 Using LonMaker to commission the FieldServer e Ensure that the correct firmware and latest configuration is loaded on the FieldServer Each change in the FieldServer requires re commissioning of the FieldServer in LonMaker e Ensure that the FieldServer and the LonMaker machine are on the same network e Open the existing Network in LonMaker or create a new Network e Click on Create New Network and follow the network wizard making the following selections e Ne
14. 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 42 of 62 Data Length 5 Suggested Data Array Formats Uint16 Float Data Item 1 etm_day Measurement Units Values Range Invalid Value Days Days 0 65 534 65 535 OxFFFF Data Item 2 etm_hour Measurement Units Values Range Invalid Value Hours Hours 0 23 N A SNVT_elapsed_tm Data Item 3 etm_minute Measurement Units Values Range Invalid Value Minutes Minutes 0 59 N A Data Item 4 etm_second Measurement Units Values Range Invalid Value Seconds Seconds 0 59 N A Data Item 5 etm_millisecond Measurement Units Values Range Invalid Value Milliseconds Milliseconds 0 999 N A Data Length 1 Suggested Data Array Formats Uint16 Float SNVT_elec_kwh Data Item 1 Measurement Units Values Range Invalid Value Electrical energy Kilowatt hours 0 65 535 N A SNVT_elec_kwh_l SNVT_elec_whr SNVT_elec_whr_f Data Length 1 Suggested Data Array Formats Sint32 Data Item 1 Measurement Units Values Range Invalid Value Electricity Data Length Kilowatt hour 214 748 364 8 214 748 364 6 214 748 364 7 Ox7FFFFFFF 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Electric energy Data Length Watt hours 0
15. 6 553 5 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Electric Energy Watt hour 0 3 40282E38 N A Data Length 1 Suggested Data Array Formats Float SNVT_enthalpy Dataitem 1 Measurement Units Values Range Invalid Value Enthalpy KiloJoules per Kilogram 327 68 327 66 Raw 32 767 0x7FFF kJ kg Type 327 67 Data Length 1 SNVT_evap_state Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value evap_t N A 0 2 255 OxFF EVAP_NUL FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 43 of 62 SNVT_ex_control SNVT_file_pos SNVT_file_req only raw data supported SNVT_file_status only raw data supported SNVT_fire_test Data Length 10 Suggested Data Array Formats Byte Uint16 Float Data Item 1 ex_ctrl_status Measurement Units Values Range Invalid Value ex_control_t N A 0 2 255 OxFF EX_CONTROL_NUL Data Item 2 7 ex_ctrl_domid_0 ex_ctrl_domid_5 Measurement Units Values Range Invalid Value Domain ID Byte 0 255 N A Data Item 8 ex_ctrl_domid_len Measureme
16. 62 SNVT_pumpset_mn Data Length 8 Suggested Data Array Formats Byte Uint16 Float Data Item 1 pset_main_pump Measurement Units Values Range Invalid Value motor_state_t N A 0 7 255 OxFF MOTOR_NUL Data Item 2 pset_booster_pump Measurement Units Values Range Invalid Value motor_state_t N A 0 7 255 OxFF MOTOR_NUL Data Item 3 pset_prio_level Measurement Units Values Range Invalid Value priority_level_t N A 0 11 255 OxFF PR_NUL Data Item 4 pset_process_ready Measurement Units Values Range Invalid Value Boolean_t Bit 0 1 255 OxFF BOOL_NUL Data Item 5 pset_emerg_stop Measurement Units Values Range Invalid Value Boolean_t Bit 0 1 255 OxFF BOOL_NUL Data Item 6 pset_main_pumpd_ena Measurement Units Values Range Invalid Value Boolean_t Bit 0 1 255 OxFF BOOL_NUL Data Item 7 pset_boost_pumpd_ena Measurement Units Values Range Invalid Value Boolean_t Bit 0 1 255 OxFF BOOL_NUL Data Item 8 pset_maint_req Measurement Units Values Range Invalid Value Boolean_t Bit 0 1 255 OxFF BOOL_NUL FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS
17. 8700 21 LonWorks Manual Page 54 of 62 Data Length 14 Suggested Data Array Formats Float Data Item 1 pset_sn_dil_flow Measurement Units Values Range Invalid Value Total Dilution Flow Milliliters per second 0 65 534 N A Volume Data Item 2 pset_sn_exh_temp Measurement Units Values Range Invalid Value Exhaust Temperature Degrees Celcius 274 0 6 279 4 N A Data Item 3 pset_sn_exh_press Measurement Units Values Range Invalid Value Exhaust Pressure Kilo pascals 3 276 8 N A 3 276 6 Data Item 4 pset_sn_seal_press Measurement Units Values Range Invalid Value Shaft seal purge Kilo pascals 3 276 8 N A pressure 3 276 6 Data Item 5 pset_sn_inlet_vacuum Measurement Units Values Range Invalid Value Inlet vacuum pressure Kilo pascals 3 40282E38 N A 3 40282E38 Data Item 6 pset_sn_supply_volts Measurement Units Values Range Invalid Value Supply voltage Volts 3 276 8 N A SNVT_pumpset_mn 3 276 6 Data Item 7 pset_sn_cool_flow Measurement Units Values Range Invalid Value Total coolant flow Milliliters per second 0 65 534 N A Data Item 8 pset_sn_cool_fl_low Measurement Units Values Range Invalid Value Boolean Bit 0 1 255 OxFF BOOL_NUL Data Item 9 pset_sn_dil_active Measurement Units Values Range Invalid Value Boolean Bit 0 1 255 OxFF BOOL_NUL Data Item 10 pset_sn_bal_dil_act Measurement Units Values Range Invalid Value Boolean Bit 0 1 255 OxFF BOOL_NUL Data Item 11 pset_sn_inl_p_dil_act Measurement Units Values Range Invalid Value B
18. Array Formats Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value Electric Voltage Volts Alternating Current VAC 0 65 534 65 535 OxFFFF Data Length 1 Suggested Data Array Formats Float SNVT_volt_dbmv Datailvernt Measurement Units Values Range Invalid Value Electric Voltage Decibels milliVolts 3 276 8 N A Direct Current 3 276 7 Data Length 1 Suggested Data Array Formats Float SNVT volt f Data Item 1 A Measurement Units Values Range Invalid Value Electric Voltage Volts 3 40282E38 N A 3 40282E38 FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 62 of 62 SNVT_volt_kilo SNVT_volt_mil SNVT_zerospan Data Length 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Electric Voltage Kilovolts 3 276 8 N A 3 276 7 Data Length 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Electric Voltage Data Length Millivolts 3 276 8 3 276 7 N A 2 Suggested Data Array Formats Float Data Item 1 zero Measurement Units Values Range Invalid Value Ze
19. Function Legal Values Protocol Specify protocol used LonWorks Specify Network Management Primarily used for Circon_Sl refer LonMaker LonWatcher Connection_Type h to Appendix C 5 Circon_SI None Example Client Side Connections Connections Adapter Protocol LonWorks LonWorks FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 11 of 62 5 2 2 Node Parameters Section Title Nodes Column Title Function Legal Values Node_Name Provide name for Node Up to 32 alphanumeric characters Protocol Specify protocol used LonWorks Example Client Side Nodes Nodes Node_Name Protocol LON_1 LonWorks 5 2 3 FieldServer Related Map Descriptor Parameters Column Title Function Legal Values Name of this Map Descriptor Network Variable Map_Descriptor_Name Up to 16 alphanumeric characters Name Name of Data Array where data is to be stored or One of the Data Array names from Data Data_Array_Name i fetched from in the FieldServer Array section above O to maximum specified in Data Array Data_Array_Offset Starting location in Data Array K section above See Section 5 1 2 for a list of valid entries for Lon_Function Detailed Fu
20. Location array element 8 bit unsigned byte 0 255 N A Data Item 7 Object_ID Measurement Units Values Range Invalid Value Object ID object index 0 65 535 N A Data Item 8 Alarm_type Measurement Units Values Range Invalid Value alarm_type_t N A 0 254 255 OxFF AL_NUL Data Item 9 Priority_level Measurement Units Values Range Invalid Value Priority_level_t N A 0 11 255 OXFF PR_NUL Data Item 10 Index_to_SNVT Measurement Units Values Range Invalid Value Index to NV index of NV Causine 65535 N A alarm Alm_Value00 Data Item 11 14 _Alm_Value03 Measurement Units Values Range Invalid Value Value array element specific to NVT 0 255 N A Data Item 15 Year Measurement Units Values Range Invalid Value Year year 0 3000 N A Data Item 16 Month Measurement Units Values Range Invalid Value Month month of year 0 12 N A Data Item 17 Day Measurement Units Values Range Invalid Value Day day of month 0 31 N A Data Item 18 Hour Measurement Units Values Range Invalid Value Hour Hour of day 0 23 N A Data Item 19 Minute Measurement Units Values Range Invalid Value Minute Minutes 0 59 N A Data Item 20 Second Measurement Units Values Range Invalid Value Second Seconds 0 59 N A Data Item 21 Millisecond Measurement Units Values Range Invalid Value Millisecond Milliseconds 0 999 N A Data Item 22 25 Alm_limit00 Alm_limit03 Measurement Units Values Range Invalid Value Alarm limit array coe to NVT 0 255 N A element Data Length 1 Suggest
21. N A 1 65 535 0 Data Item 11 nv_type_cat SNVT_nv_type Measurement Units Values Range Invalid Value nv_type_category_t N A 1 14 255 OxFF NVT_CAT_NUL Data Item 12 nv_type_length Measurement Units Values Range Invalid Value Type length Bytes 1 31 0 Data Item 13 nv_type_scale_a Measurement Units Values Range Invalid Value Scaling multiplier N A 32 768 32 766 32 767 Data Item 14 nv_type_scale_b Measurement Units Values Range Invalid Value Scaling exponent N A 32 768 32 766 32 767 Data Item 15 nv_type_scale_c Measurement Units Values Range Invalid Value Scaling offset N A 32 768 32 766 32 767 Data Length 2 Suggested Data Array Formats Uint16 Float Data Item 1 obj_request_id Measurement Units Values Range Invalid Value SNVT_obj_request obj_request_id File Byte Address 0 N A Data Item 2 obj_request Measurement Units Values Range Invalid Value object_request_t N A 0 17 255 OxFF RQ_NUL Data Length 2 Suggested Data Array Formats Uint32 Data Item 1 obj_status_id Measurement Units Values Range Invalid Value SNVT_obj_status Functional Block ID N A 0 65 535 N A Data Item 2 obj_status_bits Measurement Units Values Range Invalid Value object_status_bits Bits 0 N A SNVT_occupancy Data Length 4 294 967 295 1 Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value 0 3 SNVT_ov
22. Range Invalid Value Phase Rotation Radians Data Length 3 40282E38 3 40282E38 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Angular velocity Radians second Data Length 3 276 8 3 276 7 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Angular Velocity Radians Second Data Length 3 40282E38 3 40282E38 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Area Square meters m 0 13 1068 Type 13 107 OxFFFF 65 535 Data Length 1 Suggested Data Array Formats Float SNVT_btu_f Data Item 1 Measurement Units Values Range Invalid Value Thermal Energy British Thermal Units 0 3 40282E38 N A Data Length 1 Suggested Data Array Formats Uint16 Float SNVT_btu_kilo Detailers aes Measurement Units Values Range Invalid Value Thermal Energy Kilo British Thermal 0 65 535 N A Units FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 39 of 62 Data Length 1 Suggested Data Array Formats Uint16 Float
23. Sensor Client Side Map Descriptors Map_Descriptors Map_Descriptor_Name Data_Array_Name Data_Array_Offset Lon_Function Function Node_Name SNVT_Index SNVT_Type Nv_Min_Value Nv_Max_Value Nv_Selfdoc_text nvoTemp DA_FI_01 0 NVUOIMC Wrbc LON_1 y SNVT_Temp_f V 0 1 WaterTemp NviTempMin V V CFG_NVUI Server LON_1 V SNVT_Temp_f 10 v amp 200 x8023 NviTempMax V V CFG_NVUI Server LON_1 v SNVT_Temp_f 300 amp 200 x8020 The Node Self Documentation String These two configuration network variables will be linked to the first Map Descriptor declared The NV_Min_Value and NV_Max_Value fields define the defaults for these CP s These defaults are loaded by the FieldServer after a restart only when re commissioning is required The object index is O and this Map Descriptor defines the 1 Network Variable of the object defines one LonMark object of type 1 Open Loop Sensor LonMark Config file Example 2 Water Heating Element Actuator Client Side Map Descriptors Map_Descriptors Map_Descriptor_Name Data_Array_Name Data_Array_Offset Lon_Function Function Node_Name SNVT_Index SNVT_Type Nv_Min_Value Nv_Max_Value Nv_Selfdoc_text nvoTemp DA_FI_01 0 NVUOIMC Wrbc LON_1 y SNVT_Temp_f V 0 1 WaterTemp NviTempMin V K CFG_NVUI Server LON_1 y SNVT_Temp_f 10 V amp 200 x8023 NviTempMax r V CFG
24. Units Values Range Invalid Value Config_source_t N A 0 1 255 OxFF CFG_NUL Data Length 1 Suggested Data Array Formats Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value Event Count Count 0 65 535 N A Data Length 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Event Count Count 0 3 40282E38 N A Data Length 1 Suggested Data Array Formats Sint16 Float Data Item 1 Measurement Units Values Range Invalid Value Incremental Count Count 32 768 32 767 N A FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 40 of 62 Data Length 1 Suggested Data Array Formats Float SNVT_count_inc Data tem 1 i Measurement Units Values Range Invalid Value Incremental Count Count 3 40282E38 N A 3 40282E38 Data Length 3 Suggested Data Array Formats Uint16 Float Data Item 1 ctl_req_revr_id Measurement Units Values Range Invalid Value Receiver ID ID number 1 65 535 0 SNVT_color Data Item 2 ctl_req_sndr_id Measurement Units Values Range Invalid Value Sender ID ID number 1 65 534 65 535 OxFFFF Data Item 3 ctl
25. Wrbc LON_1 SNVT_Temp_f 10 5 20 V TempOut2 DA_FO_01 A NVUOIMX Wrbc LON_1 SNVT_Temp_f V V r TempOut3 DA_FO_01 2 NVUOIMC Wrbc LON_1 SNVT_Temp_f V V 20 Templn DA_FI_01 0 gt NVPIIMT Rdbc LON_1 SNVT_Temp_f_ r p This field determines the Map Descriptor s The Data Array will be sampled and evaluated for bol Non Throttled delta change once every Client Map Descriptors the Required for Throttling Mode This field specifies the Min scan Lime seconds Scan Interval eras a minimum change needed for a Network Variable s ee determines the EM value to invoke an NV Update If found during Min_Scan_Time for more sampling Throttling Mode that information Max_Scan_Time has elapsed since the last NV Update a new NV Update will be transmitted update rate FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 14 of 62 6 EXPLICIT CONFIGURATIONS 6 1 Special considerations With Explicit configuration the FieldServer communicates directly with other devices by specifying the remote device address in the FieldServer configuration All the Servers and their Clients need to be on the same domain to be able to communicate If the LonWorks device s Node ID is not known it
26. is made available in Data Arrays For example SNVT_temp_f is always transported across the LonWorks network as degrees Celsius but by setting the SNVT_Units field to Deg_F the measurement units of the Map Descriptor s data will be set to degrees Fahrenheit The following table shows which SNVT s currently have SNVT_Units capabilities SNVT_Type SNVT_Option SNVT_UnitslLength Measurement Units SNVT_press f N A Inch_H20 1 Inches of water SNVT_press p N A Inch_H20 1 Inches of water Raw 1 Raw unadjusted data SNVT_temp N A Deg_C 1 Degrees Celsius C Deg_F 1 Degrees Fahrenheit F SNVT temp f N A Deg_C 1 Degrees Celsius Co Deg F 1 Degrees Fahrenheit F Raw 1 Raw unadjusted data SNVT_temp_p N A Deg_C 1 Degrees Celsius C Deg_F 1 Degrees Fahrenheit F All Raw 2 Raw unadjusted data ee Raw 1 Raw unadjusted data SNVT_switch Value Percent 1 Percent State Raw 1 Raw unadjusted data See Also Appendix A 8 FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual SNVT_Type SNVT_Option SNVT_UnitslLength Measurement Units Raw 12 Raw unadjusted data All Deg_C 6 Degrees Celsius C Deg_F 6 Degrees Fahrenheit F Raw
27. run different configurations one of these devices may fail to commission properly The following configuration can be used to force the SPID Connections Adapter Protocol SPID Lonworks Lonworks 80 00 95 48 50 02 04 01 FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 5 of 62 2 3 Clients Servers The FieldServer functions as a Client when polling or sending updates on the LonWorks network and as a Server when being polled or receiving updates The FieldServer can be bound to a maximum number of 15 LonWorks Nodes The FieldServer recommended point limit is 1000 points for the FS B2011 Series and 4096 points for the FS B30 and FS B4011 2 4 Explicit Implicit Clients can address Servers using explicit or implicit addressing Clients using explicit addressing obtain their data transfer parameters directly from the FieldServer configuration file Implicit addressing is used when a Network Management Tool such as LonMaker is used to connect a FieldServer to other LonWorks Nodes the FieldServer is assigned its data transfer binding parameters by the Network Management Tool 2 5 XIF Files At start up the FieldServer creates an external interface file XIF called fserver xif based on the configuration file The FieldServer differs from most oth
28. stored in a Floating point Data Array 3 bytes will go to waste A SNVT with more than one data item may require a float Data Array format to prevent loss of resolution Since FieldServer Map Descriptors can only work with one type of Data Array format for all the data items in a SNVT it is sometimes necessary to use a Float Data Array element for all data items of which some may only have required a Byte Fortunately all SNVT s are short in length and RAM is adequately provided for on the FieldServer If a loss in resolution can be tolerated any Data Array format may be used The range of FieldServer Data Arrays formats are Data Array Format Description Values Range BIT 1 bit 0 1 BYTE 8 bit Byte 0 255 SINT16 16 bit Signed Integer 32 768 32 767 UINT16 16 bit Unsigned Integer 0 65 535 SINT32 32 bit Signed Integer 2 147 483 647 2 147 483 647 UINT32 32 bit Unsigned Integer 0 4 294 967 295 FLOAT 32 bit Float 3 40282E38 3 40282E38 Values Range These are the only values that will be allowed for the SNVT e g a value of 101 will not be processed in a read or write on SNVT_Switch s Value data item Invalid Value The Invalid value is used to force the data item s value should a value outside the value range be encountered in a read or write Should the invalid value be N A Not Applicable the data item s value will be bounded by the indicated values range e g an i
29. support fieldserver com FS 8700 21 LonWorks Manual Page 45 of 62 Data Length 1 Suggested Data Array Formats Byte Uint16 Float SNVT_hvac_mode Data Item 1 Measurement Units Values Range Invalid Value Hvac_t N A 0 17 255 OxFF HVAC_NUL Data Length 3 Suggested Data Array Formats Float Data Item 1 hvac_ord_state Measurement Units Values Range Invalid Value hvac_overid_t N A 0 48 255 OxFF HVO_NUL Data Item 2 hvac_ord_percent a oa Measurement Units Values Range Invalid Value Percent Percent of Full Scale 163 840 Type 163 835 Raw 163 830 32 767 Ox7FFF Data Item 3 hvac_ord_flow Measurement Units Values Range Invalid Value Flow Liters per Second 0 65 534 65 535 OxFFF Data Length 7 Suggested Data Array Formats Float SNVT_hvac_status SNVT_hvac_type Data Item 1 hvac_sts_mode Measurement Units Values Range Invalid Value hvac_t N A 0 17 255 OxFF HV_NUL Data Item 2 hvac_heat_out_pri Measurement Units Values Range Invalid Value Primary Heat Output Percent of Full Scale 163 840 Type 163 835 Raw 163 830 32 767 Ox7FFF Data Item 3 hvac_heat_out_sec Measurement Units Values Range Invalid Value Secondary Heat Percent of Full Scale 163 840 Type 163 835 Raw Output 163 830 32 767 Ox7FFF Data Item 4 hvac_cool_out Measurement Units Values Range Invalid Value Cooling Output Percent of Fu
30. 0 6 553 5 N A Data Length 1 Suggested Data Array Formats Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value Concentration Parts per Million ppm 0 65 535 N A Data Length 1 Suggested Data Array Formats Uint16 Float SNVT_ppm_f Data Item 1 Measurement Units Values Range Invalid Value Concentration Parts per Million 0 3 40282E38 N A Data Length 11 Suggested Data Array Formats Uint16 Float Data Item 1 preset_learn Measurement Units Values Range Invalid Value learn_mode_t N A 0 3 255 OxFF LN_NUL Data Item 2 preset_selector Measurement Units Values Range Invalid Value Selector N A 0 65 535 N A Darien preset_value00 preset_value03 Measurement Units Values Range Invalid Value Value Specific to SNVT 0 255 N A Data Item 7 preset_day SNVT_preset Measurement Units Values Range Invalid Value Days Days 0 65 534 65 535 OxFFFF Data Item 8 preset_hour Measurement Units Values Range Invalid Value Hours Hour 0 23 N A Data Item 9 preset_minute Measurement Units Values Range Invalid Value Minutes Minutes 0 59 N A Data Item 10 preset_second Measurement Units Values Range Invalid Value Seconds Seconds 0 59 N A Data Item 11 preset_millisec Measurement Units Values Range Invalid Value Milliseconds Milliseconds 0 999 N A D
31. 30 Appendix B 1 1 Using LonMaker to commission the FieldServer ixaaaiiiiaaananssssnnnnnnnnnnnnnnnnnnnnnnnnnnnannnnnaaa 30 Appendix B 1 2 Removing Previous FieldServer Device Templates in LonMaker ooooccccccnnnooonacnnncnononaaannnnnnos 30 Appendix B 2 Neuron Systems Appendix B 3 Honeywell Care Appendix AA al ka kr Appendix B 5 TTF nNG R Ver2 1sk sna coeeseds Jans a kra r aa yaa Appendix C Troubleshooting Tips aaaaaaaaaaaaaaanannnnnnnnnnnnnnnnnennnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn 33 Appendix C 1 Debugging a LonWorks connection Hints and tips aiaaaaiaiaaaa assiaaaasananasaaannannnanaaannnnnnanannanaai 33 Appendix C2 O NT 33 Appendix C 2 1 Error Message Lonlive C 121 uaaaaaaiiinaannnnsnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnaa 33 Appendix C 3 Exposing Operation Statistics s es a ea aa da a aa ea Aaa a ra Aa AAEREN is 34 Appendix C 4 Illegal Characters in Network Variable Names cccccnocoooncnnnconnonononcnononcnononononononcnnnnnnnononnncnnnnnnnns 35 Appendix CO CirconuSiLimitatlons AAA li 35 Appendix C 6 Service types currently supported for network variable messages cccccnnnoooonnnoncnononaannnnnncnnnnnnnns 35 Appendix C 7 Combining Explicit and Implicit oooooccccconoconanacononononooonnnnnonononononononnnconnnonnnnnnnncnnnnnnnnnnnnncnnnnnnnns 35 Appendix D SNVT Type wncsccecscesec
32. A A i R AAA A A A ADA 21 6 3 3 FieldServer Related Map Descriptor Parameters ssssccccccsesessssccscecsesssessaasesccesseenssueesecesseesssasesseesens 6 3 4 Driver Related Map Descriptor Parameters 6 3 5 Timing OLMOS A A E AAA A A AS AA 6 3 6 Map Destript rExXampleis s dduda sSosbubselu uudaa ususatd kkabunid d da alkukvinkati Appendix A Useful Features acicicscscccvcosssccsesecscccvenssedsvscsvedsvenstecscsesvedscsedeecdescdcectescdeecseedcecdeccdeecesssases eesuessdeeasess 24 Append rA T Using UN TS a aid iii 24 Appendix A 2 Using NV_Min NV_Max Ct ooooooccncnccnnnooonnnnnnncnonononononnncncnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnncnnnnnnons 24 Appendix A 3 Throttling Mode evi AA ole wae AE A ELEN EA eae akhir a a a kili AppendiA 4 XIFGeneratioN cerdito iaa a a aaae aana a aee ar aaraa e ava kaaa aiota irae Appendix A 5 Configuration Properties Appendix A 6 LonMark Object Creation Appendix A 7 Node Status Operation aaaaztaataaaaa snsaaanann nnnnnnnnnnnnnnnnnnnnnnunnnnnnnnnnnnnnnnnnunnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnna Appendix A 8 Working with Binary Data Appendix A 9 Filtering SNVT Variables Appendix A 9 1 SNVT_Option Field Appendix A 9 2 SNVT_UniES Field iii A E Aa E bakka Appendix B Vendor Information scce eeaeee asas S daa Esaa ene Enea er seses tne Esda iniciando Easier REEE 30 Appendix B 1 EcheloniLonMaker ena a a a kad Jas loan A EEEE Ola k a aaa spada a IEEE Hak a SEA
33. FieldServer Technologies A Sierra Monitor Company Driver Manual Supplement to the FieldServer Instruction Manual FS 8700 21 LonWorks APPLICABILITY amp EFFECTIVITY Effective for all systems manufactured after April 2009 Driver Version 1 25 Document Revision 6 FS8700 21 LonWorks Manual Table of Contents TABLE OF CONTENTS 1 2 Description 30d cece NN 4 A su ddadeassgeadussasbadestesse 4 2 1 NV Updates Poll ii Sink iin enhanc RR em A A oS Aah Bless ean 4 2 2 Network Management ETE caridad svn Rea dha a sana ea og asia assets E di aasdan aes atando bess 4 2 2 1 LonWorks Program ID Calculation SPID 4 2 3 CIENTS SOPV EIS so 3 oss ede ccecoe E E A EE E EA TAEA asst ecb utes EEA AE uMteste state stele 5 2 4 Explicit I ripoliG tts ses iss a dash 5 2 5 A O RN 5 2 6 Device ResQurcE Flema cocoa ca ai a kt a Dakar i aa k a a ars 5 2 7 E a a OO 5 2 8 Configuration Properties oia a ds tandas eii discal Etc 5 Driver Scope of SUPPLY lt iccccccciscecccdicccscccleccccceievescccsccecescssuescecsetesscesacecacecdcecdccescecuceudcececessceducecdcectsesdsecdcesdesctees 6 3 1 Supplied by FieldServer Technologies for this driver 3 2 Provided by the Supplier of 3 Patty EQUIPO aI ASAE E E ES AA E E A a EE E A E 3 3 Additional files required for the DriVer occccnncooooonnnncnnnnanonnnnnnnncnnanannnnnnnncnnnnnnnnnnnnncnnnnnnnnnnnnncnnnnnnnnnnnnnccn ns 6 Hardware Connections ciciccciccccccec
34. Item 1 Measurement Units Values Range Invalid Value days_of_week_t N A 0 6 255 OxFF Data Length 1 SNVT_defr_mode Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value defrost_t N A 0 2 255 OxFF DEM_MODE_NUL FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 41 of 62 SNVT_defr_state SNVT_defr_term SNVT_density SNVT_density_f SNVT_dev_c_mode SNVT_earth_pos Data Length 1 Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value defrost_state_t Data Length N A 0 4 255 OxFF DFS_NUL 1 Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value defrost_term_t Data Length N A 0 100 255 OxFF DFT_NUL 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Density Data Length Kg m3 kilograms per cubic meter 0 32 767 5 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Den
35. LonWorks FieldServer Performance No Desciption Min Typ Max Units FieldServer startup time with 4096 network variables 6 5 Minutes 2 Time to commission FieldServer with 4096 network variables 40 Minutes 3 Time to complete a network variable updFieldServersbetween two 16 I Milli FieldServers acknowledged service seconds 4 Time to complete a networFieldServersoll message between two els Milli FieldServers request response service seconds 3 Time to complete a network manageFieldServers variable fetch message F Milli between two FieldServers request response service seconds FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 36 of 62 Appendix D SNVT_Type The following section describes each SNVT as implemented on the FieldServer LonWorks driver Data Length The number of Data Array elements required when specifying a Data Array name under a Map Descriptor Suggested Data Array Formats This field suggests FieldServer Data Array formats in ascending order of storage space required while ensuring data integrity It is not recommended to store a byte value in a bit Data Array since only the values O and 1 will be retained from the byte value resulting in a loss of resolution If a byte value is
36. Raw Ox7FFF Data Item 2 Standby_cool Measurement Units Values Range Invalid Value Standby Setpoint Cooling Degrees Celsius 273 17 327 66 Type 327 67 Raw Ox7FFF Data Item 3 Unoccupied_cool Measurement Units Values Range Invalid Value Unoccupied Setpoint Cooling Degrees Celsius 273 17 327 66 Type 327 67 Raw Ox7FFF Data Item 4 Occupied_heat Measurement Units Values Range Invalid Value Occupied Setpoint Heating Degrees Celsius 273 17 327 66 Type 327 67 Raw Ox7FFF Data Item 5 Standby_heat Measurement Units Values Range Invalid Value Standby Setpoint Heating Degrees Celsius 273 17 327 66 Type 327 67 Raw Ox7FFF Data Item 6 Unoccupied_heat Measurement Units Values Range Invalid Value Unoccupied Setpoint Data Length Heating Degrees Celsius 273 17 327 66 Type 327 67 Raw Ox7FFF 1 Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value therm_mode_t Data Length N A 0 2 255 OxFF THERM_NUL 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Elapsed Time Seconds 3 40282E38 N A 3 40282E38 FieldServer Technologies 1991 Tarob Court Milp
37. Time period If the value differs by an amount greater than or equal to that specified by the NV_Delta_Value field from the previously transmitted value the NV update will be transmitted Otherwise an NV update will be only sent if the time since the last update is greater than or equal to the Max_Scan_Time field value Refer to the examples in Sections 5 2 6 and 6 3 6 This functionality applies only to SNVT s of either Floating point or Integer formats Appendix A 4 XIF Generation After start up the FieldServer creates a XIF version 4 0 according to the configuration loaded This file is called fServer xif and can be uploaded from the FieldServer using the RuiNet utility The FieldServer s XIF file is internally generated by the LonWorks driver using the information contained in the FieldServer s configuration file CONFIG CSV It is not possible to download an externally created XIF file using NodeUtil or LonMaker It is also not possible to download any type of externally created network variables default values file The FieldServer s configuration can be changed by uploading and editing the CONFIG CSV file and therefore the XIF file must be obtained by uploading it from the FieldServer Remember that this XIF file will change whenever the configuration file has been changed downloaded and the FieldServer restarted FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com
38. _NVUI Server LON_1 y SNVT_Temp_f 300 amp 200 x8020 The Node Self These two configuration network variables will be linked to the first Map Descriptor declared The Documentation String NV_Min_Value and NV_Max_Value fields define the defines one LonMark object of type 3 Open Loop Actuator The object index is O and defaults for these CP s These defaults are loaded by the FieldServer after a restart only when re commissioning is required this Map Descriptor defines the 1 Network Variable of the object FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 5091970 email support fieldserver com FS 8700 21 LonWorks Manual Page 27 of 62 Appendix A 7 Node Status Operation When binding network variables on the FieldServer the node status will be on line before binding as well as after un binding network variables A Node will go off line only when a bound network variable of that node goes off line e g is disconnected When using a network tool to commission the FieldServer implicit addressing the FieldServer LonWorks Node must be placed ONLINE on the LonWorks network before it will pass data with other bound network variables The following messages may appear on the driver screen when using Ruinet which indicates that the FieldServer has not been put into the ONLINE sta
39. _req_sndr_pri Measurement Units Values Range Invalid Value Sender priority Priority value 0 200 N A Data Length 5 Suggested Data Array Formats Uint16 Float Data Item 1 ctl_rsp_status Measurement Units Values Range Invalid Value control_resp_t N A 0 5 255 OxFF CTRLR_NUL Data Item 2 ctl_rsp_snd_id Measurement Units Values Range Invalid Value Sender ID ID number 1 65 534 65 535 OxFFFF SNVT_ctrl_resp Data Item 3 ctl_rsp_snd_rlower Measurement Units Values Range Invalid Value Sender Range Lower ID ID number 1 65 534 65 535 OxFFFF Data Item 4 ctl_rsp_snd_rupper Measurement Units Values Range Invalid Value ctl_rsp_snd_rupper ID number 1 65 534 65 535 OxFFFF Data Item 5 ctl_rsp_cntrl_id Measurement Units Values Range Invalid Value Controller ID ID number 1 65 534 65 535 OxFFFF SNVT_currency Data Length 3 Suggested Data Array Formats Sint32 Data Item 1 Currency Measurement Units Values Range Invalid Value Currency_t N A 0 56 255 OxFF CU_NUL Data Item 2 Power_of_10 Measurement Units Values Range Invalid Value Magnitude Power of 10 128 127 N A Data Item 3 Currency_Value Measurement Units Values Range Invalid Value Value Data Length Currency Value 2 147 483 648 2 147 483 647 N A 1 Suggested Data Array Formats Byte Uint16 Float SNVT_count_inc Data
40. ariable Update Input PASSIVE 5 1 3 SNVT_Index For implicitly addressed Client Map Descriptors and all Server side Map Descriptors the driver will assign an index to each one starting from O and incrementing to 4095 in the order they appear in the configuration file 5 1 4 Address Table Limit It is important to note the limitation within LonWorks Implicit addressing that the Address Table used for storing the addresses of all active connections made with the FieldServer is limited to 16 Device Addresses including that of the FieldServer This is a LonWorks limitation not a FieldServer limitation and it means that the FieldServer can only make active implicit connections to 15 other devices If active connections to more than 15 devices are required then it is necessary to use Explicit Configuration NMFETCHC is recommended Devices that write to passive Map Descriptors in the FieldServer only are not placed in this table and therefore this limitation does not apply A Passive Map Descriptor is recognized by the Passive Parameter in the Function Field FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 10 of 62 5 1 5 Network Management Capability When commissioning an implicitly configured FieldServer using the Traditional binding method the
41. aring the Map Descriptor functions as WRBC or WRBX can do this See Section 5 1 2 for more information e Ifthe domain and Subnet ID are defined in the configuration file of the FieldServer these values will be used when power is cycled to the FieldServer If the values set here are different to what the Network Manager has set up for the FieldServer for clients using implicit addressing the FieldServer will stop communicating In this case change these settings or remove them from the configuration file completely and recommission the FieldServer Appendix C 2 Error Messages Message Description LON 03 FYI Standard driver build This is normal This message is informational and can be safely ignored Appendix C 2 1 Error Message Lonlive c 121 If the following error message is returned DRIVER gt LON Error timeout while waiting for Lon I F to reset Configuration Error It is possible that the FieldServer hardware in use may not support LonWorks or the firmware loaded contains LonWorks but is the wrong firmware for the application Remove LonWorks from the configuration or get new firmware hardware FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 34 of 62 Appendix C 3 Exposing Operation Statistics If
42. asurement Units Values Range Invalid Value ptz_pan_dir Direction 0 255 N A Data Item 2 ptz_pan_speed Measurement Units Values Range Invalid Value Pan speed Percent of full level 0 0 100 0 N A Data Item 3 ptz_tilt_dir Measurement Units Values Range Invalid Value tilt_dir_t N A 0 2 255 OxFF TILT_NUL Data Item 4 ptz_tilt_speed Measurement Units Values Range Invalid Value Tilt speed Percent of full level 0 0 100 0 N A Data Item 5 ptz_zoom Measurement Units Values Range Invalid Value zoom_t N A 0 2 255 OxFF ZOOM_NUL Data Item 6 ptz_zoom_speed Measurement Units Values Range Invalid Value ptz_zoom_speed Meters m 3 40282E38 N A 3 40282E38 FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 52 of 62 Data Length 13 Suggested Data Array Formats Float Data Item 1 pump_sn_rot_speed Measurement Units Values Range Invalid Value Frequency Hertz 0 6 553 4 N A Data Item 2 pump_sn_body_temp Measurement Units Values Range Invalid Value Body temperature Degrees celcius 274 0 6 279 4 N A Data Item 3 pump_sn_mot_ext_temp Measurement Units Values Range Invalid Value Motor external Degrees celcius 274 0 6 279 4 N A temperat
43. ata Length 1 Suggested Data Array Formats Float SNVT_press Data Item 1 Measurement Units Values Range Invalid Value Pressure gauge KiloPascals 3 276 8 Type 3 276 7 Raw 3 276 6 32 767 Ox7FFF Data Length 1 Suggested Data Array Formats Float SNVT_press_f Data Item 1 Measurement Units Values Range Invalid Value Pressure gauge Pascals 3 40282E38 N A 3 40282E38 FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 51 of 62 Data Length 1 Suggested Data Array Formats Sint16 Float SNVT_press_p Data Item 1 Measurement Units Values Range Invalid Value Pressure gauge Pascals 32 768 32 766 32 767 Ox7FFF SNVT_privacyzone SNVT_ptz Data Length 3 Suggested Data Array Formats Uint16 Float Data Item 1 priv_zn_action Measurement Units Values Range Invalid Value privacyzone_t N A 0 5 255 OxFF PZ_NUL Data Item 2 priv_zn_number Measurement Units Values Range Invalid Value Zone number Privacy zone number 1 255 0 Data Item 3 priv_zn_camera_id Measurement Units Values Range Invalid Value Camera ID ID number 1 65 535 0 Data Length 6 Suggested Data Array Formats Float Data Item 1 ptz_pan_dir Me
44. can_Interval pollUNVT DA_Explicit 101 NMFETCHC Rdbc Remote_Node 2 UNVT 31 1 0s UNVT Byte length must be specified for correct operation FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 20 of 62 6 2 7 Using Neuron ID to Address Devices Client Drivers only It is possible to poll remote LonWorks devices using their Neuron ID s instead of the traditional Network Manager method The Neuron ID is the 12 Digit Hex identifier of the associated LonWorks Device An example configuration follows Note that Neuron ID addressing is considered explicit addressing so the station address domain ID and subnet ID must be set as described in Section 6 1 4 Bridge System_Station_Address _ Title 110 D01 S01 Neuron ID Example On the Client side Nodes add a new field as shown below Nodes Node_Name Node_ID Protocol Neuron_ID Lon_Srv_11 11 Lonworks F912AB440100 Create a Map Descriptor as Follows Map_Descriptors Map_Descriptor_ Name Data_Array_Name _ Data_Array_Offset Lon_Function Function Node_Name SNVT_Index SNVT_Type Scan_Interval InviAmp1 DA_001 0 NMFETCHC RDBC Lon_Srv_11 _ 000 SNVT_amp Os FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fi
45. cceccsiscseccevactecceusececcevscteccevecdeccesecstecececevecestentesecusetesestenteesseentessevestessteesicests 7 4 1 A O NN 7 4 2 Neuro TDi A A EE oe eeu hav deena tes bos 8 4 3 Lon i DEE E lla R A aa 8 4 4 The LonWorks Adapter Card FS X40 Only cccccccsssecccssscecesssseccessseeccesseecesssseceessseeceesaeeeeessseeceesseseessaeeeesea 8 4 4 1 Port Address Witivi 8 Implicit Configurations 5 5 foc cesicccccciscecscovecevscedscececevscevecedededecevscedecedesecececuesdesecehedecstaesdeessesedecstersdesssensteestarsieeste 9 5 1 Special CONSI ANS ii A a A A dad 9 5 1 1 Map Descriptor Names Network Variable Names wd 5 1 2 IMPICIELON FUNCTIONS A A a k daa k 9 BABA SNYE Id A a r e e O Saat 9 5 1 4 Address Table LME A e dadas 5 1 5 Network Management Capability 5 1 6 dient VS SErVEr MAPPING scsi Ai r ESA AAA iaa 5 2 Client Side Map Ping iia dai ia dae 5 2 1 CONNECTION Para Mete ii A A atla a laka 5 2 2 Node Para meters inicia a acens AARS Da rado 11 5 2 3 FieldServer Related Map Descriptor Parameters ccooooococonnncconononaonnnnnnnnnnnnnanononononnnnnnnnnnnncnnnnnnnnnnnnccnnnns 11 5 2 4 Driver Related Map Descriptor Parameters aaxaiiiianaannnnssnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnni 12 5 2 5 TIMING Parameterssaadisai Kasa corrio ERI AEAEE AAEE r a kana Kada Lea ara nk aa Ta Raka a 12 5 2 6 Client Side Map Descriptor EXQMple uu ccccccssssscccccsseessnscccccccesesessaseccccesseenseaeeeccesseenssseeee
46. cesecsscsssscsesscvessessensssessevessecsecsssessecsensdesedesadescsessdededessdescsessdenedesalesssessdesedersvesesens 36 FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 5091970 email support fieldserver com FS 8700 21 LonWorks Manual Page 4 of 62 1 DESCRIPTION The LonWorks driver allows the FieldServer to transfer data to and from devices using LonWorks protocol The FieldServer can emulate either a Server or Client The FS B4011 FieldServer is supplied with a LonWorks Card while the FS B2011 and FS B30 Series FieldServers have a built in LonWorks Interface A Fieldbus connection is available on the FieldServer The FS B30 and FS B4011 can handle up to 4096 Network Variables and the FS B2011 up to 1000 which can be of the Standard Network Variable Types SNVT and or User defined Network Variable Types UNVT 2 DEFINITIONS 2 1 NV Updates Polls On LonWorks networks information is transferred using Network Variable Updates and Network Variable Polls The Client requests Network Variables from the Server using Network Variable Polls and Network Variable Updates occur when a Client sends Network Variables to a Server 2 2 Network Management The FieldServer is able to set its own Domain Subnet and Node ID at start up using the FieldServer configuration file Alternatively the FieldServer is capable of being commissioned and bo
47. configuration parameters below are all that is needed to achieve this purpose For hints and tips on how to commission the FieldServer using the various Vendor devices that do this see Appendix B It is possible to set the FieldServer Online and Offline using the Network Management Tools This is a LonWorks function and is different from the traditional Online and Offline Status discussed in other FieldServer documentation When the FieldServer is set offline using this LonWorks feature it will not communicate with other LonWorks devices 5 1 6 Client vs Server Mapping Distinguishing Client from Server in the LonWorks Environment is more difficult due to the Peer to Peer nature of LonWorks design Clients and Servers can be identified in this environment as follows e Clients will write Setpoints and have status written to them so expect Setpoints and Control Points on the Output side and Status and Alarms on the Input side e Servers will have the opposite structure with Setpoints and Control Points on the Input Side and Staus and Alarms on the Output side Distinguishing Client from Server is important to ensure correct matching with other protocols being used on a FieldServer For example it would not be useful to map an Output to a BACnet Al point as both points will be expecting to push data out of the FieldServer 5 2 Client Side Mapping 5 2 1 Connection Parameters Section Title Connections Column Title
48. e in the right hand byte STATE portion LonMark guidelines for this SNVT stipulate that the VALUE portion has a range from 0 100 and that the STATE portion can assume a value of 1 or 0 However since the raw data type for these two values is byte a value ranging from 0 255 care needs to be taken when transferring values into this SNVT to make sure the source values are within the legal range If a value is placed into one of these bytes that is deemed out of range then a 1 value will be sent on the LonWorks network to indicate out of range Also note that when sending binary status in a SNVT Switch some devices expect the VALUE portion to change when the STATUS portion changes so an analog value that changes in sympathy with the binary state may be necessary FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 28 of 62 Appendix A 9 Filtering SNVT Variables Appendix A 9 1 SNVT_Option Field This field can be used to isolate a specific record within a complex SNVT Appendix D shows which SNVTs are currently attributed with SNVT_Option capabilities Appendix A 9 2 SNVT_Units Field The measurement units of a SNVT is fixed as far as it is transported across the LonWorks network but by the setting of the SNVT_Units field it is possible to specify how the data
49. e set e Set the DSN using a Network manager by commissioning the FieldServer into the Network Manager Project When doing it this way it is extremely important that the DSN is not forced in the FieldServer Configuration as the Configuration address will override the Network Manager Address every time the FieldServer is restarted e Set the DSN from the Lon ini file Using this option provides a default DSN if the FieldServer does not have a DSN assigned If a Network Manager or the FieldServer Configuration provides a DSN then the Lon ini DSN will be ignored e Set the DSN in the FieldServer configuration This option takes precedence over the 2 other addressing options and should therefore not be used when commissioning a FieldServer into a Network with a Network Manager Example 1 Setting the Domain and Subnet from the lon ini file The Domain Table and Subnet IDs can be set from a lon ini file on the FieldServer The FieldServer s LonWorks Node ID will be set from the System_Station_Address field in the configuration file if specified otherwise a default value will be used lon ini file contents D50 S01 FieldServer configuration file contents config csv FieldServer System_Station_Address Title 12 Your title FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com
50. ection Title Nodes Column Title Function Legal Values K Up to 32 alphanumeric Node_Name Provide name for Node characters Server destination Node s Subnet ID of an explicitly addressed Subnet_ID 1 255 message Node_ID Server destination Node s Node ID of an explicitly addressed message 1 127 Protocol Specify protocol used LonWorks Adapter Specify port Adapter used LonWorks Example Client Side Nodes Nodes Node_Name Subnet_ID Node_ID Protocol Adapter LON_1 Pal pal LonWorks LonWorks FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 18 of 62 6 2 3 Driver Related Map Descriptor Parameters Column Title Function Legal Values _ One of the node names Name of Node to fetch data from or send data to Needed for Explicit epee Node_Name j specified in Client Node Addressing Descriptors above SNVT_Index Server Network Variable Index 0 4095 SNVT_Type Standard network variable type of the data See Appendix D SNVT_Option Specifies which record out of a complex SNVT we are after See Appendix A 9 1 SNVT_Units Specifies the measurement units if something other than Metric is required See Appendix A 9 2 UNVT_Byte_Length Specifies the length in bytes of an UNVT Th
51. ed Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Electric current Amperes 3 276 8 N A 3 276 7 FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 38 of 62 Data Length 1 Suggested Data Array Formats Uint16 Float SNVT_amp_ac Data Item 1 H Measurement Units Values Range Invalid Value Alternating electric Amperes 0 65 534 65 535 OxFFFF current SNVT_amp_f Data Length 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Electric current Amperes 3 40282E38 3 40282E38 N A SNVT_angle Data Length 1 Suggested Data Array Formats Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value Phase Rotation Radians 0 65 535 N A SNVT_angle_deg SNVT_angle_f SNVT_angle_vel SNVT_angle_vel_f SNVT_area Data Length 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Angular distance degrees Data Length 359 98 360 00 Type 655 34 Raw 32 767 Ox7FFF 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values
52. eldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 21 of 62 6 3 Server Side Configuration 6 3 1 Connections Section Title Connections Column Title Function Legal Values Adapter Adapter Name LonWorks Protocol Specify protocol used LonWorks Example Server Side Connections Connections Adapter Protocol LonWorks LonWorks 6 3 2 Nodes Section Title Nodes Column Title Function Legal Values Node_Name Provide name for Node Up to 32 alphanumeric characters Protocol Specify protocol used LonWorks Example Server Side Nodes Nodes Node_Name Protocol LON_1 LonWorks 6 3 3 FieldServer Related Map Descriptor Parameters Column Title Function Legal Values Up to 16 alphanumeric characters Map_Descriptor_Name Name of this Map Descriptor 7 See Section 6 1 1 0 Name of Data Array where data is to be stored One of the Data Array names from Data_Array_Name or fetched from in the FieldServer Data Array section above X O to maximum specified in Data Data_Array_Offset Starting location in Data Array V K Array section above R See Section 6 1 2 for a list of valid Lon_Function Detailed Function of Client Map Descriptor entries f See Section 6 1 2 for a list of valid Function Funct
53. ement Units Values Range Invalid Value Turbidity Nephelometric 0 65 534 65 535 OxFFFF SNVT_turbidity_f SNVT_valve_mode SNVT_vol SNVT_vol_f SNVT_vol_kilo SNVT_vol_mil SNVT_volt_ac Data Length Turbidity Units NTU 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Turbidity Data Length Nephelometric Turbidity Units NTU 0 3 40282E38 N A 1 Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value valve_mode_t Data Length N A 0 7 255 OxFF VALVE_NUL 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Volume Data Length Liters 0 6 553 5 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Volume Data Length Liters 0 3 40282E38 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Volume Data Length Kiloliters kl 0 6 553 5 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Volume Data Length Milliliters 0 6 553 5 N A 1 Suggested Data
54. ent Units Values Range Invalid Value Speed Meters per Second 3 40282E38 3 40282E38 N A Data Length 1 Suggested Data Array Formats Float SNVT_speed_mil Data Item 1 Measurement Units Values Range Invalid Value Linear Velocity Millimeters per Second 0 65 535 N A Data Length 1 Suggested Data Array Formats Uint16 Float SNVT_state Data Item 1 Measurement Units Values Range Invalid Value 16 state bits Bits 0 65 535 N A FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 58 of 62 SNVT_state_64 SNVT_str_asc SNVT_str_int SNVT_scene SNVT_telcom SNVT_temp SNVT_temp_diff_p Data Length 4 Suggested Data Array Formats Packed_Bit Uint16 Float Data Item 1 state_64_wordO Measurement Units Values Range Invalid Value Boolean Bit 0 1 per bit 16 N A bits in word Data Item 2 state_64_word1 Measurement Units Values Range Invalid Value Boolean Bit 0 1 per bit 16 N A bits in word Data Item 3 state_64_word2 Measurement Units Values Range Invalid Value Boolean Bit O 1 per bit 16 N A bits in word Data Item 4 state_64_word3 Measurement Units Values Range Invalid Value Boolean Bit 0 1 per bit
55. er LonWorks drivers in that it is configurable and therefore its XIF is not fixed for all applications The list of points available to the network will vary depending on the other networks connected to the FieldServer and the requirements of the particular application The recommended procedure for obtaining the XIF file for the FieldServer is to upload it Refer to Appendix A 4 for details 2 6 Device Resource Files The STANDARD device resource file covers FieldServer data type support All Standard Network Variable Types SNVTs in this file are available to the user These SNVTs are listed in Section 5 1 3 Please note that due to the sophisticated nature of LonWorks variables it may not always be possible to typecast the full information supplied in a LonWorks variable to a simple Data Type contained in another protocol The FieldServer supports Move and Logic functions which would allow the LonWorks variable to be split up and passed to separate simple data types thus preventing information loss The FieldServer supports the sending and receiving of User defined Network Variable Types UNVTs on the LonWorks Network An UNVT is simply implemented as an array of bytes of user defined length 2 7 NV Aliases The FieldServer currently supports a default of 63 network variable aliases to avoid network variable connection constraints This number may be increased to a maximum of 4096 2 8 Configuration Properties Configuration Properties CP s
56. er saves the properties of that device as a device template It is important to remove all previous device templates from LonMaker when moving onto your next FieldServer product as some parameters might transfer to your new device To remove the device templates open your LonMaker workspace as you would normally do Then choose the LonMaker toolbar and choose the Device Templates option This will bring up a list of all device templates Highlight and then remove all device templates that do not contain Echelon or LNS This will ensure a fresh commission of your FieldServer product FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 31 of 62 Appendix B 2 Neuron Systems Newron Systems may produce the following Error message bindings lost after power cycle The solution to this is to place the FieldServer in the Configured state which will cause the bindings to be committed to the Neuron and they will remain after a power cycle Procedure 1 Make the bindings in NL220 2 Place devices in ONLINE mode or state 3 Refer to the following Screencap for assistance in placing the FieldServer in the Configured state File Views Localinterface Network Selection Browser Options Dom mA v a ek ole BEB 0 e x MO wise lA E Local interface H Grid
57. er to the FTT 10A Free Topology Transceiver User s Guide from Echelon Corporation for recommended wiring practices if necessary The connection diagram below shows how the FieldServer FS B2011 FS B30 and FS B4011 are connected to a LonWorks network To other LonWorks Nodes To other LonWorks Nodes To other LonWorks Nodes DB 9 Connector FieldBus Connector To other LonWorks Nodes Configure the remote LonWorks devices according to manufacturer s instructions 4 1 Service Pin The service pin is used to commission the FieldServer onto the network using a LonWorks Network Management tool On FS B2011 and FS B4011 FieldServers the node s unique Neuron ID will be displayed on the Error Screen of the Ruinet utility with every service pin press FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 8 of 62 4 2 Neuron ID The driver prints the Neuron ID on the Driver Message Screen as its starts On FS B2011 and FS B4011 FieldServers it is possible to print the Neuron ID on the Error Screen at any time by pushing the Service Button on the side of the FieldServer On all platforms the driver can store the Neuron ID in a Data Array so that it can be read by a Client node Refer also to Appendix C 3 4 3 LonLED s The location of the Lon LED va
58. erride Occup_t Data Length N A 255 OxFF OC_NUL 1 Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value override_t N A 0 2 255 OxFF OV_NUL FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 49 of 62 Data Length 1 Suggested Data Array Formats Float SNVT_pH Data Item 1 Measurement Units Values Range Invalid Value Acidity pH 32 768 32 767 N A Data Length 1 Suggested Data Array Formats Float SNVT_pH_f Data Item 1 Measurement Units Values Range Invalid Value Acidity pH 3 40282E38 N A 3 40282E38 Data Length 9 Suggested Data Array Formats Float Data Item 1 pos_ctrl_rcvr_id Measurement Units Values Range Invalid Value Receiver ID ID number 1 65 535 0 Data Item 2 pos_ctrl_cntrl_id Measurement Units Values Range Invalid Value Controller ID ID number 1 65 534 65 535 OXFFFF Data Item 3 pos_ctrl_cntrl_prio Measurement Units Values Range Invalid Value Controller priority Priority value 0 200 N A Data Item 4 pos_ctrl_function Measurement Units Values Range Invalid Value cam_func_t N A 0 2 255 OxFF CMF_NUL Data Item 5 po
59. eters km 0 6 553 5 N A SNVT_length_micr SNVT_length_mil SNVT_length_cont SNVT_length_cont_f SNVT_length_disc SNVT_length_percent SNVT_lux SNVT_magcard only raw data supported SNVT_mass Data Length 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Length Data Length Micrometers Microns 0 6 553 5 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Length Millimeters mm Data Length 0 6 553 5 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Continuous Level Percent of Full Level Data Length 0 100 0 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Continuous Level Percent of Full Scale Data Length 0 100 N A 1 Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value Discrete_levels_t N A Data Length 0 4 255 OxFF ST_NUL 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Percent of Full Scale or Parts per Million ppm Percentage Level Data Length
60. ion of Client Map Descriptor entries FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 22 of 62 6 3 4 Driver Related Map Descriptor Parameters Metric is required Column Title Function Legal Values One of the node names Name of Node to fetch data from or send data to Needed for specified in Client Node_Name a H Explicit Addressing Node Descriptors above SNVT_Index Server Network Variable Index 0 4095 SNVT_Type Standard network variable type of the data See Appendix D SNVT_Option Specifies which record out of a complex SNVT we are after See Appendix A 9 1 Specifies the measurement units if something other than K SNVT_ Units See Appendix A 9 2 Specifies the length in bytes of an UNVT This Parameter is parameter is not used on conjunction with SNVT s _ 1 255 See Appendix UNVT_Byte_Length compulsory when SNVT_Type is set to UNVT the parameter is Al not used on conjunction with SNVT s Specifies the Type Number to apply to this particular UNVT E PET a R 0 146 255 See UNVT_ID This Parameter is optional when SNVT_Type is set to UNVT the Appendix A 1 NV_Min_Value Network Variable updates with values less than specified in this field will be ignored See Appendix A 2
61. ircon System Integrator from Circon Systems Corporation Optional Network Management Software PCC10 PCCard LonWorks Adapter Optional 3 3 Additional files required for the Driver F Auto Created Always Loaded By Conditionally Filename Comments by driver FieldServer Technologies loaded Template loaded if no custom configuration Config csv X ordered otherwise Custom configuration loaded Generated at power up Changes if profile in fserver xif X l configuration changes M Used for providing defaulted DSN Refer to lon ini X Section 6 1 4 lonvars cfg X Maintains commissioning settings If corrupted delete it and reboot FieldServer to create new one FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 7 of 62 4 HARDWARE CONNECTIONS LonWorks devices are available with several different physical interfaces The screw plug supplied with the FieldServer LonWorks interface will connect the FieldServer to the FTT 10 network The 9 pin D connector can also be used to connect to the network FS B4011 only The 2 wire twisted pair connection to the network is polarity insensitive The FTT 10 network is a free topology network which supports star loop and or bus wiring connections Please ref
62. is Parameter is compulsory when SNVT_Type is set to UNVT the parameter is not used on conjunction with SNVT s 1 255 See Appendix A 1 UNVT_ID Specifies the Type Number to apply to this particular UNVT This Parameter is optional when SNVT_Type is set to UNVT The parameter is not used on conjunction with SNVT s 0 146 255 See Appendix A 1 NV_Min_Value Network Variable updates with values less than specified in this field will be ignored See Appendix A 2 NV_Max_Value Network Variable updates with values higher than specified in this field will be ignored See Appendix A 2 NV_Delta_Value Network Variable updates where the value s delta change is less than specified in this field will be ignored unless the Max_Scan_Time Condition has been met Compulsory for Throttling Lon Functions only Not used on other Lon Functions See Appendix A 2 NV_Selfdoc_Text The Self Documenting String for this Network Variable Normal Text up to a length of 40 characters 6 2 4 Timing Parameters Column Title Function Legal Values 0 32000 Scan_Interval Seconds per scan 5 s K Minimum Scan Time in seconds Compulsory for Throttling Lon Functions only Not See Appendix Min_Scan_Time used on other Lon Functions A 3 Maximum Scan Time in seconds Compulsory for Throttling Lon Functions only Not See Appendix Max_Scan_Time used on other Lon Functions A 3
63. itas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 60 of 62 Data Length 1 Suggested Data Array Formats Uint16 Float SNVT_time_hour Data Item 1 Measurement Units Values Range Invalid Value Elapsed Time Hours 0 65 535 N A Data Length 1 Suggested Data Array Formats Float SNVT_time_min Data Item 1 Measurement Units Values Range Invalid Value Elapsed Time Minutes 0 65 535 N A SNVT_time_sec SNVT_time_stamp SNVT_time_zone only raw data supported Data Length 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Elapsed time Data Length Seconds 0 6 553 4 65 535 OxFFFF 6 Suggested Data Array Formats Uint16 Float Data Item 1 ts_year Measurement Units Values Range Invalid Value Year Year 0 3000 65 535 OxFFFF Data Item 2 ts_month Measurement Units Values Range Invalid Value Month Month of Year 0 12 N A Data Item 3 ts_day Measurement Units Values Range Invalid Value Day Day of Month 0 31 N A Data Item 4 ts_hour Measurement Units Values Range Invalid Value Hours Hours of Day 0 23 N A Data Item 5 ts_mi
64. k to the polled node Thus should the data in the Data Array linked to a NMFETCHC Map Descriptor change by another process the data will be propagated to the polled node by means of a network variable update Another useful feature of the NMFETCHC function is that it can perform reads to any other type of Node function NVUI CFG_NVUI NVUOEXX NVPIIMC etc This means that even Client Map Descriptors can be read this way Network management fetch requests received on polled nodes are handled differently from normal NV Poll requests The response to a NV Poll will contain valid data Data is valid if the node that is the source of the data is online and if this data is not too old The data in the response to a network management fetch will not be checked for validity however it will simply respond with the current data in the variable FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 17 of 62 6 2 Client Side Configuration 6 2 1 Connections Section Title Connections Column Title Function Legal Values Adapter Adapter Name LonWorks Protocol Specify protocol used LonWorks Example Client Side Connections Connections Adapter Protocol LonWorks LonWorks 6 2 2 Nodes S
65. le by filling the SNVT_Type field with UNVT The UNVT s size in bytes should also be added to the UNVT_Byte_Length field and the UNVT s type number in the UNVT_ID field Valid UNVT_IDs are O and the range 146 to 255 The UNVT_ID value will be substituted with the default value of O if the field is left empty Refer to the example in Section 6 2 3 Appendix A 2 Using NV_Min NV_Max etc The NV_Min_Value NV_Max_Value functionality were added to stop the propagation of out of bounds network variables across a LonWorks network NV values higher than assigned by the NV_Max_Value field or lower than assigned by NV_Min_Value field will not be sent out on the network or copied to their relevant Data Arrays If one or both of these fields are not assigned values limit checking will not be performed on that particular field This functionality applies only to SNVT s of either Floating point or Integer formats Refer to the examples in Sections 5 2 6 and 6 3 6 One or both of these fields can be linked to a configuration network variable update input in order to create an interoperable configuration property For further information refer to Appendix A 5 Appendix A 3 Throttling Mode When the Lon_Function field specifies a Throttling Mode Client Map Descriptor the NV_Delta_Value Min_Scan_Time and Max_Scan_Time fields all need to be assigned values When operating in Throttling Mode a Network Variable s value will be sampled at the Min_Scan_
66. ll Scale 163 840 Type 163 835 Raw 163 830 32 767 Ox7FFF SNVT_length Data Item 5 hvac_econ_out Measurement Units Values Range Invalid Value Economizer Output Percent of Full Scale 163 840 Type 163 835 Raw 163 830 32 767 Ox7FFF Data Item 6 hvac_fan_out Measurement Units Values Range Invalid Value Fan Output Percent of Full Scale 163 840 Type 163 835 Raw 163 830 32 767 Ox7FFF Data Item 7 hvac_in_alarm Measurement Units Values Range Invalid Value In Alarm State Alarm value 0 1 N A Data Length 1 Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value Hvac_hvt_t N A 0 9 255 OxFF HVT_NUL Data Length 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Length Meters m 0 6 553 5 N A FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 46 of 62 Data Length 1 Suggested Data Array Formats Float SNVT_length_f Data Item 1 Measurement Units Values Range Invalid Value Length Meters 0 3 40282E38 N A Data Length 1 Suggested Data Array Formats Float SNVT_length_kilo Data Item 1 Measurement Units Values Range Invalid Value Length Kilom
67. mats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value fire_initiator_t N A 0 16 255 OXFF FI_NUL SNVT_fire_indcte SNVT_gfci_status SNVT_grammage SNVT_grammage_f SNVT_hvac_emerg Data Length 1 Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value fire_indicator_t Data Length N A 0 8 255 OxFF FN_NUL 1 Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value gfci_status_t Data Length N A 0 5 255 OxFF GFCI_NUL 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Grammage Data Length Grams Square meter 0 6 553 5 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Grammage Data Length Grams Square meter 0 3 40282E38 N A 1 Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value emerg_t N A 0 5 255 OxFF EMERG_NUL FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email
68. may be read using a utility program e g NodeUtil or using a LonWorks Analyzer All the Client Node CSV files need to have their Subnet_ID and Node_ID parameters set to point to their respective Server Subnet and Node ID values Once the FieldServers are restarted the network should function correctly 6 1 1 Map Descriptor Names Network Variable Names As a Server the LonWorks driver provides a table of Network Variables for other Nodes to read These Nodes access the variables according to Index numbers which are automatically assigned by the driver according to the Map Descriptor definition order in the configuration file The driver also creates an identification table for configuration nodes to read the name and types of variables available on the FieldServer Within the LonWorks protocol this table size is limited to 64K bytes If the application requires a large number of Server mappings up to 4096 it will be necessary to limit the variable name length Each Server mapping requires 4 bytes plus the length of the name from this 64K block 6 1 2 Lon functions Explicit Map Descriptors are distinguished from Implicit Map Descriptors by the function used in the Lon_Function field of the Map Descriptor Depending on the nature and direction of Data Transfer needed different explicit functions are available as shown below NOTE e Function field MUST pair up with the Lon_Function field as shown in the table e NMFETCHC is the preferred Lon Functio
69. n for most applications See Section 6 1 5 Lon_Function Description Function Field NVUI Network Variable Update Input NVPO Network Variable Polled Output PYER NVPIEXC Network Variable Polled Input Explicitly addressed Continuously sent RDBC NVUOEXC Network Variable Update Output Explicitly addressed Continuously sent WRBC NVUOEXX Network Variable Update Output Explicitly addressed and sent on Change WRBX NVUOEXT Network Variable Update Output Explicitly addressed sent in Throttling Mode WRBC NMFETCHC Network Management Network Variable Fetch Continuously sent Explicit Addressing only RDBC CFG_NVUI Configuration Network Variable Update Input SERVER 6 1 3 SNVT_Index The SNVT_Index field must be specified for all explicitly addressed Client Map Descriptors These Client Map Descriptors use this field to index their relevant Map Descriptors on the Server side FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 15 of 62 6 1 4 Domain Table Setup To be able to communicate with other nodes on the LonWorks network the FieldServer must have its Domain Subnet and Node ID s set Explicit configuration requires the user to set these parameters There are 3 ways in which the FieldServer DSN Domain Subnet Node address can b
70. ncoming read value of 101 will be stored as 100 for SNVT_Switch s Value data item Note that in some cases both the type and raw values are specified Raw values are not of the same type of the SNVT s measurement type i e they are not scaled Data Item SNVT s containing more than one data item have a name specified for each item This name can be used in the SNVT_Option field of a Map Descriptor to isolate only this one item Data Length 1 Suggested Data Array Formats Float SNVT_abs_humid Dataitemi Measurement Units Values Range Invalid Value Absolute humidity gram kilogram 0 655 34 Raw 65 535 OxFFFF Type 655 35 Data Length 1 Suggested Data Array Formats Uint16 Float SNVT_ address Data Item 1 Measurement Units Values Range Invalid Value Neuron Chip Address 16 bit address value 16 384 64 767 N A FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 37 of 62 Data Length 25 Suggested Data Array Formats Uint16 Float SNVT_alarm SNVT_amp Alm_Location00 Dataiitem 16 Alm_Location05 Measurement Units Values Range Invalid Value
71. nction of Client Map Descriptor R Implicit Connections R See Section 5 1 2 for a list of valid entries Function Function of Client Map Descriptor based on the Lon_Function FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 12 of 62 5 2 4 Driver Related Map Descriptor Parameters a Column Title Function Legal Values _ One of the node names Name of Node to fetch data from or send data to Needed for Explicit E Node_Name i specified in Client Node Addressing Descriptors above SNVT_Type Standard network variable type of the data See Appendix D SNVT_Option Specifies which record out of a complex SNVT we are after See Appendix A 9 1 SNVT_Units Specifies the measurement units e g Metric or English See Appendix A 9 2 UNVT_Byte_Length Specifies the length in bytes of an UNVT This Parameter is compulsory when SNVT_Type is set to UNVT the parameter is not used in conjunction with SNVT s 1 255 See Appendix A 1 UNVT_ID Specifies the Type Number to apply to this particular UNVT This Parameter is optional when SNVT_Type is set to UNVT the parameter is not used on conjunction with SNVT s 0 146 255 See Appendix A 1 NV_Min_Value Network Variable updates with
72. ndex numbers which are automatically assigned by the driver according to the Map Descriptor definition order in the configuration file The driver also creates an identification table for configuration nodes to read the name and types of variables available on the FieldServer Within the LonWorks protocol this table size is limited to 64K bytes If the application requires a large number of Server mappings up to 4096 it will be necessary to limit the variable name length Each Server mapping requires 4 bytes plus the length of the name from this 64K block 5 1 2 Implicit Lon functions Implicit Map Descriptors are distinguished from Explicit Map Descriptors by the function used in the Lon_Function field of the Map Descriptor Depending on the nature and direction of Data Transfer needed different implicit functions are available as follows NOTE function field MUST pair up with the Lon_Function field as shown in the table Lon_Function Description Function Field NVUI Network Variable Update Input NVPO Network Variable Polled Output ee NVPIIMC Network Variable Polled Input Implicitly addressed Continuously sent RDBC NVUOIMC Network Variable Update Output Implicitly addressed Continuously sent WRBC NVUOIMX Network Variable Update Output Implicitly addressed and sent on Change WRBX NVUOIMT Network Variable Update Output Implicitly addressed sent in Throttling Mode WRBC See Appendix A 3 CFG_NVUI Configuration Network V
73. nge Invalid Value Scene Number Scene Number 1 255 N A Data Length 7 Suggested Data Array Formats Float Data Item 1 scn_cfg_func Measurement Units Values Range Invalid Value scene_config t N A 0 4 255 OxFF SCF_NUL Data Item 2 scn_cfg_scene Measurement Units Values Range Invalid Value Scene Number Scene Number 1 255 N A Data Item 3 scn_cfg_setting Measurement Units Values Range Invalid Value Scene Setting Level Percent of Full Level 0 100 0 N A Data Item 4 scn_cfg_rotation SNVT_scene_cfg Measurement Units Values Range Invalid Value Scene Rotation Angle Degrees 359 98 360 00 Raw 32 767 Ox7FFF Type 655 34 Data Item 5 scn_cfg_fade_tim Measurement Units Values Range Invalid Value Scene Fade Time Seconds 0 0 to 6 553 4 Raw 65 535 OxFFFF Type 6553 5 Data Item 6 scn_cfg_dly_tim Measurement Units Values Range Invalid Value Scene Delay Time Seconds 0 0 to 6 553 4 Raw 65 535 OxFFFF Type 6553 5 Data Item 7 scn_cfg_scn_proi Measurement Units Values Range Invalid Value Scene Priority Priority Value 0 255 N A FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 57 of 62 Data Length 3 Sugges
74. nt Units Values Range Invalid Value Domain length Number of bytes 0 6 N A Data Item 9 ex_ctrl_subnet Measurement Units Values Range Invalid Value Subnet Subnet number 1 255 N A Data Item 10 ex_ctrl_node Measurement Units Values Range Invalid Value Node Node number 1 127 N A Data Length 2 Suggested Data Array Formats Uint32 Data Item 1 ops_rw_ptr Measurement Units Values Range Invalid Value Read Write Pointer File Byte Address 0 2 147 483 647 N A Data Item 2 ops_rw_len Measurement Units Values Range Invalid Value Read Write Length Number of Bytes 0 65 535 Data Length 12 Suggested Data Array Formats Byte Data Length 27 Suggested Data Array Formats Byte Data Length Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value N A 0 3 fire_test_t 255 OxFF FT_NUL Data Length 1 Suggested Data Array Formats Uint16 Float SNVT_flow Data Item 1 Measurement Units Values Range Invalid Value Flow volume Liters Second 0 65 534 65 535 OxFFFF Data Length 1 Suggested Data Array Formats Float SNVT flow f Data Item 1 Measurement Units Values Range Invalid Value Flow Volume Liters Second 3 40282E38 N A 3 40282E38 Data Length 1 Suggested Data Array Formats Uint16 Float SNVT_flow_mil Datalltemit
75. nute Measurement Units Values Range Invalid Value Minutes Minute of Hour 0 59 N A Data Item 6 ts_second Measurement Units Values Range Invalid Value Second Data Length Second of Minute 0 59 N A Suggested Data Array Formats Data Length 3 Suggested Data Array Formats Uint16 Float Data Item 1 tod_cur_state Measurement Units Values Range Invalid Value occup_t N A 0 3 255 OxFF OC_NUL SNVT_tod_event Data Item 2 tod_nxt_state Measurement Units Values Range Invalid Value occup_t N A 0 3 255 OxFF OC_NUL Data Item 3 tod_tm_to_nxt Measurement Units Values Range Invalid Value Time to Next State Minute of Hour 0 65 535 N A Data Length 8 Suggested Data Array Formats Float Data Item 1 7 tr_point00 tr_point06 Measurement Units Values Range Invalid Value SNVT_trans_table Axis points Array N A 3 40282E38 N A 3 40282E38 Data Item 8 interp_methods Measurement Units Values Range Invalid Value interp_t N A O 65 535 N A FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 61 of 62 Data Length 1 Suggested Data Array Formats Float SNVT_turbidity Data temi Measur
76. oolean Bit 0 1 255 OxFF BOOL_NUL Data Item 12 pset_sn_exh_dil_act Measurement Units Values Range Invalid Value Boolean Bit 0 1 255 OxFF BOOL_NUL Data Item 13 pset_sn_dil_fl_oor Measurement Units Values Range Invalid Value Boolean Bit 0 1 255 OxFF BOOL_NUL Data Item 14 pset_sn_pwr_sup_on Measurement Units Values Range Invalid Value Boolean Bit 0 1 255 OxFF BOOL_NUL SNVT_pwr_fact Data Length 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Power Factor Multiplier 1 00000 N A 1 00000 FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 55 of 62 Data Length 1 Suggested Data Array Formats Float SNVT_pwr_fact_f Data Item 1 Measurement Units Values Range Invalid Value Power Factor N A 1 1 N A SNVT_pwr_fact_f SNVT_reg_val Data Length 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Power Factor Data Length N A 1 1 N A 3 Suggested Data Array Formats Sint32 Data Item 1 reg_val_value Measurement Units Values Range Invalid Value Raw value Defined by unit field 2 147 483 638 2 147 483 647 N A
77. ries between FieldServer s Please consult the Start up guide for the FieldServer in question Lon LED is consistent with the table below for all FieldServers Explicit Implicit Not Commissioned Implicit Commissioned Off Flashing Off 4 4 The LonWorks Adapter Card FS X40 only 4 4 1 Port Address Switch The LonWorks driver has been configured to access the LonWorks card at ISA port address 340 hex This is the default setting for the card and the DIP switches must not be modified The DIP switch setting on the card is as follows Switch Setting ON ON OFF ON OFF OFF OFF OFF CO NI DD Wy BRB WIN e FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 9 of 62 5 IMPLICIT CONFIGURATIONS 5 1 Special considerations Implicit addressing is used when a Network Management Tool such as LonMaker is used to connect a FieldServer to other LonWorks nodes the FieldServer is assigned its data transfer binding parameters by the Network Management Tool 5 1 1 Map Descriptor Names Network Variable Names When using Implicit configuration the LonWorks driver provides a table of Network Variables for other Nodes to read These Nodes access the variables according to I
78. ro term Percent or Parts per Million ppm 163 840 163 835 N A Data Item 2 span Measurement Units Values Range Invalid Value Span factor Percent or Parts per Million ppm 0 32 7675 N A FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com
79. s_ctrl_action SNVT_pos_ctrl Measurement Units Values Range Invalid Value cam_act_t N A 0 2 255 OxFF CMA_NUL Data Item 6 pos_ctrl_number Measurement Units Values Range Invalid Value Action number Action number 1 255 0 Data Item 7 pos_ctrl_pan Measurement Units Values Range Invalid Value Pan position Degrees 359 98 360 00 Raw 32 767 OXx7FFF Type 655 34 Data Item 8 pos_ctrl_tilt Measurement Units Values Range Invalid Value Tilt position Degrees 359 98 360 00 Raw 32 767 OXx7FFF Type 655 34 Data Item 9 pos_ctrl_zoom Measurement Units Values Range Invalid Value Zoom position Percent of full scale or 163 840 Raw 32 767 0x7FFF ppm 163 830 Type 163 835 SNVT_power SNVT_power_f Data Length 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Power Watts W 0 6 553 5 N A Data Length 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Power Watts 3 40282E38 N A 3 40282E38 FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 50 of 62 Data Length 1 Suggested Data Array Formats Float SNVT_power_kilo Data Item 1 Measurement Units Values Range Invalid Value Power KiloWatts
80. service to operate correctly Note that Tridium calls Acknowledged service critical bindings FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 32 of 62 Appendix B 5 Trane Rover Use Trane Rover Service Pack 4 or later when commissioning the FieldServer This does not ship from Trane by default and may have to be requested from the local Trane representative When using Pre Service Pack 4 software you will be able to see the FieldServer in Rover but none of the FieldServer variables will be available for binding even though they are present Service Pack 4 has been tested to ensure that the variables show and the bindings work well FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 33 of 62 Appendix C Troubleshooting Tips Appendix C 1 Debugging a LonWorks connection Hints and tips e To test connections set the configuration tool into a mode that will display service requests and then push the button on the FieldServer A request should appear e In order for variables to appear as outputs they need to be declared as write variables in the FieldServer Decl
81. sesesensaaeeeesesens 13 Explicit Configurations ocicccicccieccseccdecsicccieceicecdeceisccdecessccdecaddecdeceischescdeactescdeschesededabescoensbescdedenescoesshescdedstencdest 14 6 1 SpecialicOnsid erations vz c italia Ka neste aan IDA sas Ti EA A esti Dni 14 6 1 1 Map Descriptor Names Network Variable Names 6 1 2 Lon functions 6 1 3 SNVEAN di A kka kka 6 1 4 Domain Table SU dia ai 15 6 1 5 Network MANQGeMe Nt cssscccccccsseessnsccseccssesnsnscesecessesessseesecsseeesenssaseeeseseeensaaeeeecesseessaeeseseseeeaaseeseeesns 16 6 2 Client Side Configuration clica di ascaseane a a deidad Bid baa ala 17 FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldServer com Tel 408 262 2299 Fax 408 262 2296 Toll_Free 888 509 1970 email support fieldServer com FS 8700 21 LonWorks Manual Table of Contents 6 2 1 GONNOCTIONS A dd 6 2 2 NOE 0 ii A AA banca 6 2 3 Driver Related Map Descriptor Parameters 6 2 4 FUMING AA NN 6 2 5 Map Descriptor Example 1 Explicit Configuration using Network Management Polls 19 6 2 6 Map Descriptor Example 2 Polling UNVT S aaaiiiaaaaaaassssannnsn sssnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnni 19 6 2 7 Using Neuron ID to Address Devices Client Drivers ONly ooooccnocconononaoccnooaannononanoconannnononnnnccnonanos 20 6 3 Server Side CONTISUPATION sasen A a dnd dia dd k 21 6 3 1 CONNECT A a ease 21 6 3 2 NOE
82. sity Data Length Kilograms per Cubic Meter kg m 0 3 40282E38 N A 1 Suggested Data Array Formats Byte Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value device_c_mode_t N A 0 29 255 OxFF DCM_NUL Data Length 6 Suggested Data Array Formats Float Data Item 1 epos_dir_bits Measurement Units Values Range Invalid Value Latitude Longitude Direction 0 255 N A Data Item 2 epos_lat_degs Measurement Units Values Range Invalid Value Latitude degrees Degrees 1 90 255 OxFF Data Item 3 epos_lat_mins Measurement Units Values Range Invalid Value Latitude Minutes Minutes 1 59 999 Raw 65 535 Type 65 535 OxFFFF Data Item 4 epos_long_degs Measurement Units Values Range Invalid Value Longitude Degrees Degrees 1 180 255 OxFF Data Item 5 epos_long_mins Measurement Units Values Range Invalid Value Longitude Minutes Minutes 1 59 999 Raw 65 535 Type 65 535 OXFFFF Data Item 6 epos_htabv_sea Measurement Units Values Range Invalid Value Height Above Sea Level Meters m 3 40282E38 3 40282E38 N A FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262
83. t Data Item 1 Measurement Units Values Range Invalid Value Temperature Degrees Celcius 327 68 327 66 Raw 32 767 OXx7FFF difference Type 655 34 FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 59 of 62 Data Length 1 Suggested Data Array Formats Float Data Item 1 NVT_t f SNV emp Measurement Units Values Range Invalid Value Incremental Count Degrees Celcius 3 40282E38 N A 3 40282E38 SNVT_temp_p SNVT_temp_ror SNVT_temp_setpt SNVT_therm_mode SNVT_time_f Data Length 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Temperature Data Length Degrees celsius 273 17 327 66 Type 327 67 Raw 32 767 Ox7FFF 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Temperature Rate of Change Rise Data Length Degrees Celsius per Minute C min 16 384 0 16 383 0 Raw 32 767 0x7FFF Type 16 383 5 6 Suggested Data Array Formats Float Data Item 1 Occupied_cool Measurement Units Values Range Invalid Value Occupied Setpoint Cooling Degrees Celsius 273 17 327 66 Type 327 67
84. te yet Not sending NV msg for variable name Node OFFLINE To set the FieldServer to ONLINE using LonMaker e Right click on the FieldServer device and select Manage e Onthe Devices Tab click the ONLINE button The FieldServer LonWorks Node is always ONLINE when using explicit addressing Note The FieldServer Node_Status function refer to the Bridge Configuration Manual looks at the Node_ID configured in order to monitor Node status In implicit applications this may not be the real Node_ID since Node_ID is allocated by the network manager Appendix A 8 Working with Binary Data When sending binary data on a LonWorks network there are two SNVT s that are most commonly used namely SNVT_State and SNVT_ Switch SNVT_State is a 16 bit integer that allows the user to send 16 data bits to the remote device To do this the 16 data bits need to be packed into an integer word If this packing is already done when the value is transferred into the FieldServer then the SNVT need only be linked to the relevant Data Array offset for transfer out of the FieldServer However if the FieldServer is picking up 16 separate bits from another network for this variable then the FieldServer Packed_Bit function can be used to achieve the packing See the FieldServer Configuration manual for more details on the Packed_Bit function SNVT_Switch is a two byte value consisting of an analog value in the left hand byte VALUE portion and a binary stat
85. ted Data Array Formats Float Data Item 1 setting function Measurement Units Values Range Invalid Value setting _t N A 0 5 255 OxFF SET_NUL SNVT_setting Data Item 2 s Measurement Units Values Range Invalid Value Scene Setting Level Percent of Full Level 0 100 0 N A Data Item 3 setting rotation Measurement Units Values Range Invalid Value Rotation Angle Degrees 359 98 360 00 Raw Ox7FFF 32 767 Type 655 34 SNVT_smo_obscur SNVT_sound_db SNVT_sound_db_f SNVT_speed SNVT_speed_f Data Length 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Smoke Obscuration Data Length Percent Obscuration 0 000 5 000 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Sound Level Data Length Decibels 327 68 327 67 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Sound Level Data Length Decibels from Sound Pressure Level 3 40282E38 3 40282E38 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Linear Velocity Data Length Meters per Second 0 6 553 5 N A 1 Suggested Data Array Formats Float Data Item 1 Measurem
86. this driver is appropriately configured it can expose operation statistics in a Data Array which can be monitored by a remote device to check that the driver is performing without error The lines from the example below can be cut and pasted into a configuration file to expose these stats Data_Arrays Data_Array_Name Data_Format Data_Array_Length Lonworks stats UINT32 1000 Data Array Offset Description Increments each time Neuron ID is read Used for scripting Overwritten each time Neuron ID is read Contains 1st byte of Neuron ID Overwritten each time Neuron ID is read Contains 2nd byte of Neuron ID Overwritten each time Neuron ID is read Contains 3rd byte of Neuron ID Overwritten each time Neuron ID is read Contains 4th byte of Neuron ID Overwritten each time Neuron ID is read Contains 5th byte of Neuron ID Overwritten each time Neuron ID is read Contains 6th byte of Neuron ID Not Used WO CO N DD Wm a WwW NI PR Not Used Overwritten each time Neuron ID is read Contains 1st nibble of 1st byte of Neuron ID as an ASCII ES char e g if 1st byte 0x12 then the value stored here is 0x32 the ASCII char for the digit 2 11 Overwritten each time Neuron ID is read Contains 2nd nibble of 1st byte of Neuron ID as an ASCII char e g if 1st byte 0x12 then the value stored here is 0x31 the ASCII char for the digit 1 49 Over
87. twork Interface Choose Network Attached e Management Mode Choose Onnet unless you are working offline e Register Plug ins required None e Once Visio is open with the Network showing drag a new device onto the drawing from the toolbox e Follow the Device Network making the following selections e Enter Device Name Choose commission device e Specify Device Template Choose upload from device e Specify Device Channel Choose Auto Detect e Specify Device Properties Leave as is Ping is optional e Identify Device Choose service pin e Device Application Image Leave unchecked e Initial State Leave as is e Press the service pin on the FieldServer when asked to do so and the FieldServer will be commissioned e Drag a new function block onto the drawing from the toolbox Give the function block a name and ensure that itis allocated to the FieldServer device e Once the function block is on the drawing drag input and output variables onto the function block LonMaker will display the variables available for binding Click on the variables you require or use the select all option and they will be commissioned onto the function block e Connect these variables to other devices by dragging connections from the toolbox and connecting the variables Appendix B 1 2 Removing Previous FieldServer Device Templates in LonMaker If you have previously used LonMaker to commission a FieldServer or ProtoCessor onto a LonWorks network LonMak
88. twork variable s amp 2 NV Index s 0 x80 SCPT Index Example amp 2 0 1 2 4 7 0 x80 20 Examples of configuration network variables are presented in Section 6 3 6 Appendix A 6 LonMark Object Creation For more information on filling out the Node Self Documentation String as well as the relevant Network Variable Self Documentation Strings in order to create a LonMark Object please consult the following documentation from the LonMark Interoperability Association at www lonmark org e Understanding LonMark Self Documentation e LonMark Application Layer Interoperability Guidelines The two examples given below will show how LonMark Objects can be assigned in FieldServer configuration files The first example uses the standard Open Loop Sensor Object Type 1 to create a Water Temperature Sensor that will send out its current status via Network Variable Updates A typical recipient of these updates is given by example 2 which uses the LonMark Open Loop Actuator Object Type 3 to create a Water Heating Element object that will interpret the Network Variable it receives and adjust power to its heating element accordingly FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 26 of 62 LonMark Config file Example 1 Open Loop Water Temperature
89. ue Nv_Max_Value Nv_Selfdoc_text NviTemp DA_FI_01 0 NVUI Server LON_1 7 10 SNVT_Temp_f_ 0 R 0 1 WaterTemp NviTemp DA_FO_01 al NVPO Server LON_1 7 V SNVT_Temp_f_ 0 ISO 8 2001x8023 NviTemp 7 V eFG_NVUI Server LON_1 SNVT_Temp_f 150 amp 200 x8020 Server NVUI can be grouped with Explicitly Addressed Client Map If specified for a Floating point or Descriptors use this field to point Integer SNVT then NV Updates Client NV Update types and t teirra tS M ith val higher th ified NMFETCHC Server dd erver Map ee k er va e ie NVPO can be grouped with Client eet ab NV Poll types and NMFETCHC relevant Data Array location If specified for a Floating point or The Self documenting String for a Required for Throttling Mode This field specifies the Integer SNVT then NV Updates Network Variable can be up to 40 minimum change needed for a Network Variable s with values lower than specified characters wide value to invoke an NV Update here will not be written to its relevant Data Array location FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 24 of 62 Appendix A Useful Features Appendix A 1 Using UNVT s UNVT s are User defined Network Variable Types and are defined in the configuration fi
90. und by Network Management Tools such as LonMaker see Appendix B 1 1 for further information 2 2 1 LonWorks Program ID Calculation SPID Network management tools use the Program ID to identify the different applications running on each device Two devices on a network may have the same Program ID only if they have identical application configurations The Program ID for the FieldServer consists of a fixed and a variable field XX in the Program ID below 90 00 95 47 1E 02 04 XX The fixed part does not change for different configuration files or for different LonWorks driver versions The variable part XX which is also defined as the Model or Revision number does however change The variable part is calculated at start up when the configuration is loaded on the FieldServer Certain critical fields in the configuration file are used to calculate this variable part of the Program ID Thus if the configuration file changes significantly critical fields the Program ID will change Also as we add new features and capabilities to the LonWorks driver this variable part of the Program ID may be different between LonWorks driver versions even though the configuration file is the same It is possible though very unlikely that through a change in LonWorks driver and or configuration file the program IDs calculates out identical to another combination of driver and configuration If this is the case with two FieldServers on the same network that
91. ur 0 59 N A FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 56 of 62 Data Length 1 Suggested Data Array Formats Float SNVT_res Data Item 1 Measurement Units Values Range Invalid Value Electrical Resistance Ohms 0 6 553 5 N A Data Length 1 Suggested Data Array Formats Float SNVT_res_f Data Item 1 SNVT_res_kilo SNVT_scene Measurement Values Range Invalid Value Electrical Resistance Data Length 0 3 40282E38 N A 1 Suggested Data Array Formats Float Data Item 1 Measurement Units Values Range Invalid Value Electrical Resistance Data Length KiloOhms 0 6 553 5 N A 1 Suggested Data Array Formats Uint16 Float Data Item 1 Measurement Units Values Range Invalid Value Angular Velocity Data Length Revolutions per Minute RPM 0 65 534 65 535 OxFFFF 2 Suggested Data Array Formats Byte Uint16 Float Data Item 1 Function Measurement Units Values Range Invalid Value Scene_t N A 0 23 255 OxFF SC_NUL Data Item 2 Scene_Number Measurement Units Values Ra
92. ure Data Item 4 pump_sn_mot_int_temp Measurement Units Values Range Invalid Value Motor internal Degrees celcius 274 0 6 279 4 N A temperature Data Item 5 pump_sn_mot_overload Measurement Units Values Range Invalid Value Boolean Bit 0 1 255 OxFF BOOL_NUL Data Item 6 pump_sn_oil_low Measurement Units Values Range Invalid Value o Boolean Bit 0 1 255 OxFF BOOL_NUL Data Item 7 pump_sn_ph_imbal Measurement Units Values Range Invalid Value Boolean Bit 0 1 255 OxFF BOOL_NUL Data Item 8 pump_sn_curr_use Measurement Units Values Range Invalid Value Electric current usage Ampere 3 276 8 N A 3 276 6 Data Item 9 pump_sn_pwr_usage Measurement Units Values Range Invalid Value Power usage Kilowatts 0 6 553 4 N A Data Item 10 pump_sn_temp_ctrl Measurement Units Values Range Invalid Value unit_temp_t N A 0 3 255 OxFF TEMP_NUL Data Item 11 pump_sn_em_brake_act Measurement Units Values Range Invalid Value Boolean Bit 0 1 255 OxFF BOOL_NUL Data Item 12 pump_sn_fric_brk_act Measurement Units Values Range Invalid Value Boolean Bit 0 1 255 OxFF BOOL_NUL Data Item 13 pump_sn_gas_brk_act Measurement Units Values Range Invalid Value Boolean Bit 0 1 255 OxFF BOOL_NUL FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 53 of
93. values less than specified in this field will be ignored See Appendix A 2 NV_Max_Value Network Variable updates with values higher than specified in this field will be ignored See Appendix A 2 NV_Delta_Value Network Variable updates where the value s delta change is less than specified in this field will be ignored unless the Max_Scan_Time Condition has been met Compulsory for Throttling Lon Functions only Not used on other Lon Functions See Appendix A 3 NV_Selfdoc_Text The Self Documenting String for this Network Variable Normal Text up to a length of 40 characters 5 2 5 Timing Parameters moe Column Title Function Legal Values Scan_Interval Seconds per scan 0 32000 Min_Scan_Time Minimum Scan Time in seconds See Appendix A 3 Max_Scan_Time Maximum Scan Time in seconds See Appendix A 3 FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 13 of 62 5 2 6 Client Side Map Descriptor Example Client Side Map Descriptors Map_Descriptors Map_Descriptor_Name Data_Array_Name Data_Array_Offset Lon_Function Function Node_Name SNVT_Type Nv_Delta_Value Min_Scan_Time Max_Scan_Time Scan_Interval TempOut1 DA_FO_01 0 NVUOIMT
94. written each time Neuron ID is read Contains 1st nibble of 2nd byte of Neuron ID as an ASCII char 43 Overwritten each time Neuron ID is read Contains 2nd nibble of 2nd byte of Neuron ID as an ASCII char j Overwritten each time Neuron ID is read Contains 1st nibble of 3rd byte of Neuron ID as an ASCII char de Overwritten each time Neuron ID is read Contains 2nd nibble of 3rd byte of Neuron ID as an ASCII char 46 Overwritten each time Neuron ID is read Contains 1st nibble of 4th byte of Neuron ID as an ASCII char 47 Overwritten each time Neuron ID is read Contains 2nd nibble of 4th byte of Neuron ID as an ASCII char ig Overwritten each time Neuron ID is read Contains 1st nibble of 5th byte of Neuron ID as an ASCII char i Overwritten each time Neuron ID is read Contains 2nd nibble of 5th byte of Neuron ID as an ASCII char 40 Overwritten each time Neuron ID is read Contains 1st nibble of 6th byte of Neuron ID as an ASCII char 3i Overwritten each time Neuron ID is read Contains 2nd nibble of 6th byte of Neuron ID as an ASCII char FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com FS 8700 21 LonWorks Manual Page 35 of 62 Appendix C 4 Illegal Characters in Network Variable Names Spaces Spaces may not be used in Network Variable Names The driver automaticall
95. y replaces all spaces with underscores at start up Brackets Lonmaker truncates a name from where a bracket is used e g a name like nviTest 1 Input shows as nviTest Brackets are therefore not able to be used in Network Variable Names Appendix C 5 Circon_SI Limitations e Circon_SI does not recognize whitespace e The maximum number of Network Variables under Circon_Sl is limited to 255 per node Set the Connection_Type parameter in the configuration file per the following example This will ensure that all illegal characters are replaced with underscores and that the number of Network Variables per Node is limited to 255 in the configuration Example Client Side Connections Connections Adapter Protocol Connection_Type LonWorks LonWorks _ Circon_Sl Appendix C 6 Service types currently supported for network variable messages Currently the service type for network variable update messages is fixed to acknowledged service Request response service is used for network variable poll and network management fetch messages Appendix C 7 Combining Explicit and Implicit To ensure undisturbed communication between the network management tool and the FieldServer during the commissioning binding or monitoring processes the timeouts of the explicitly addressed variables Map Descriptors might need to be set to values lower than the message timeouts used by the network management tool LonMaker for Windows