Emerson 7000 SERIES 7ADTB Switch User Manual
Contents
1. The ATS should still be bypassed and isolated Both normal and emergency sources must be available and the emergency source generator if used must be capable of being started put engine starting control in automatic position The Transfer Switch Connected to Normal light and the Normal Source Accepted light should be on 1 Turn the Isolation Handle clockwise approximately 7 turns until the window shows TEST position NOTE The engine generator may be signalled to start while turning the Isolation Handle If emergency source is available the ATS may operate to the emergency position If it does operate Retransfer Delay Bypass switch 2 Perform steps 1 5 at right Observe the status lights E Black square means light is on O White square means light is off 3 Turn the Isolation Handle clockwise approximately 16 turns to the CONN connected position 4 Push in the Bypass Handle and turn it counterclock wise until the OPEN indicator shows green This completes the Functional Test of the ADTB Turn and hold Transfer Control switch clockwise to Transfer Test until the engine starts and runs within 15 sec The Emergency Source Accepted light should come on Transfer switch CN opens and the Transfer Switch Connected to Normal light should go off and the Load Disconnect Active light should come on Both CN amp CE contacts are now open After the delay transition time delay the CE Transfer switch
2. will operate to the Emergency position The Transfer Switch Connected To Emergency light should come on and Load Dis connect Active light goes off Transfer switch will operate back to Normal position after Feature 3A time delay For im mediate retransfer turn Transfer Control counterclockwise to Retransfer Delay Bypass The Transfer Switch Connected To Normal light should come on Transfer Switch Connected to Emergency light should go off The engine generator will stop after the Feature 2E time delay unloaded running engine cool down The Emergency Source Accepted light should go off SECTION 2 TESTING amp SERVICE TRANSFER TEST Test the Automatic Delayed Transition Transfer Switch portion of the 7000 Series ADTB at least once a month This procedure checks the electrical operation of the Transfer Switch and Controller Turn the Engine Control switch to Auto and put the engine generator starting con trol at the engine generator set in automatic mode In the following test the generator will start the load will be transferred to the Emergency source then back to the Normal source An interruption to the load will occur unless the the Transfer Switch contacts are bypassed be fore the test See pages 3 1 and 3 2 for bypassing amp iso lating instructions if no interruption of load is required Be sure to close the enclosure door before proceeding to prevent personal injury in
3. case of electrical system fault Perform the four step Electrical Operation Transfer Test procedure on page 1 4 PREVENTIVE MAINTENANCE Reasonable care in preventive maintenance will insure high reliability and long life for the 7000 Series ADTB An annual preventive maintenance program is recom mended ASCO Services Inc ASI is Automatic Switch Company s national service organization ASI can be contacted at 800 800 2726 for information on preventive maintenance agreements Checklist for Yearly Inspection A Hazardous voltage capable of causing shock burns or death is used in this switch Deenergize both Normal Emergency power sources before performing inspections DANGER Clean the ATS enclosure Brush and vacuum away any excessive dust accumulation Remove any mois ture with a clean cloth Check the transfer switch contacts Remove transfer switch barriers and check the condition of the contacts Replace contacts when pitted or worn excessively Reinstall the barriers carefully Maintain transfer switch lubrication If switch is subjected to severe dust or abnormal operating con ditions renew factory lubrication on all movements and linkages Relubricate solenoid operator if TS coil is replaced Don t use oil order lubrication kit 75 100 Check all cable connections amp retighten them REPLACEMENT PARTS Replacement parts are available in kit form When or dering parts provid
4. retransfer to the normal source to time out Wait for Feature 2E time delay Starting control must be in the automatic position These are factory settings Refer to Controller User s Guide If the problem is isolated to circuits on the controller or the transfer switch call ASI or your local ASCO Power Technolo gies sales office Furnish the Serial No Catalog No amp BOM No from the transfer switch nameplate MANUAL LOAD TRANSFER This procedure manually transfers load to other source if the Transfer Switch or Control Panel are out of service Close enclosure doors to prevent personal injury in case of electrical system fault 1 Besure that the Bypass Handle is CLOSED on either Emergency or Normal see page 3 1 Be sure that the Isolation Handle is in the TEST or ISOLATE position see page 3 2 3 Turn the Bypass Handle counterclockwise to OPEN the Bypass Switch Then Bypass to the other source see page 3 1 MAINTENANCE HANDLE DANGER Bypass and isolate the Transfer Switch before using the maintenance handle See pages 3 1 and 3 2 Remove the hub and handle after using them and store on frame A Turn counterclockwise to OPEN contacts Turn clockwise to CLOSE contacts handle slide hub insert firmly onto shaft __ enue amp insert pin IMO NOIE Push in shaft to operate Normal contacts Pull out shaft to operate Emergency contacts SECTION 3 BYPASSI
5. ASCO 7000 Series 7ADTB Operator s Manual Automatic Delayed Transition Transfer amp Bypass lsolation Switches G design 1000 through 3000 amp sizes A DANGER DANGER is used in this manual to warn of high voltages capable of causing shock burns or death WARNING is used in this manual to warn of possible personal injury CAUTION is used in this manual to warn of possible equipment damage TABLE OF CONTENTS section page Refer to the outline and wiring drawings provided with your 7000 Series ADTB for all installation and connection details and accessories Refer to Group 5 Controller User s Guide 381333 126 for ATS status display messages time delays pickup amp dropout settings and adjustments An experienced licensed electrician must install the 7ADTB Rating Label Each 7000 Series 7ADTB contains a rating label to define the load and fault circuit withstand closing ratings Refer to the label on the Transfer Switch for specific values INSTALLATION Mounting da slei A E na sti ioe eae 1 1 Do not exceed the values on the rating label Power Connections 005 1 2 Exceeding the rating can cause personal injury Engine Starting amp Auxiliary Circuits 1 2 or serious equipment damage Functional Test 0 1 3 1 4 TESTING amp SERVICE __ Nameplate Transfer Test amp Preven
6. B switch Connecting Power Conductors A Wiring Diagram is furnished with the ADTB All wiring must be made in accordance with the local codes After the power cables have been tested connect them to the appropriate terminal lugs on the Bypass Switch as shown on the wiring diagram provided with this ADTB Make sure that the lugs provided are suitable for use with the cables being installed Standard terminal lugs are solderless screw type and will accept the wire sizes listed on the drawings provided with the ADTB Be careful when stripping insulation from conductors avoid nicking or ringing the conductor Remove surface oxides from conductors by cleaning with a wire brush Follow conductor manufacturer s instructions when aluminum conductor is used Apply joint compound to conductor then carefully wipe away excess compound Tighten the cable lugs to the torque specified on the rating label Be sure that the Normal and Emergency power connections are in proper phase rotation Bus Connections If bus connection is used use SAE grade 5 hardware to connect bus to appropriate terminal plates on bypass switching device Wipe off bus surfaces before they are joined If bus is dirty gently clean surfaces with a non flammable solvent Avoid touching cleaned surfaces Do not breathe cleaning solvent vapors Use SAE grade 5 hardware and tighten the bolted joints to the torque specified in Table A The reliability o
7. NG amp ISOLATING BYPASSING THE ATS This procedure explains how to Bypass the closed automatic transfer switch contacts Bypassing is required before the ATS can be tested or isolated The Bypass Handle must be in the OPEN position green indicator and the Isolation Handle must be in the CLOSED position window See Figures 3 1 3 2 and 3 3 BYPASS Indicator shows green OPEN when the ATS is not bypassed To Bypass Normal push in handle all the way amp turn it clockwise BYPASS SWITCH HANDLE J EMERGENCY You can only bypass to the same source that the Transfer Switch is connected Solenoid interlock prevents incorrect operation 1 Observe which Transfer Switch Connected To light is on Normal or Emergency on the door This is the position of the automatic transfer switch 2 Bypass to the same source as connected to transfer switch as follows select Normal or Emergency Indicator shows yellow EMERGENCY CLOSED when ATS is bypassed to Emergency or yellow NORMAL CLOSED when ATS is bypassed to Normal Source To Bypass Emergency pull out han dle all the way amp turn it clockwise Figure 3 1 Bypass Handle and position indicators To Bypass Normal Source Load connected to Normal Source The Transfer Switch Connected To Normal light is on and Transfer Switch Connected To Emergency light is off Push in the Bypass Handle all the way then turn it clockwise u
8. e control features that are provided and review their operation before proceeding After installing the ADTB check the following Bypass Handle should be in the OPEN position Isolation Handle should be in the CLOSED position CN transfer switch should be CLOSED CE transfer switch should be OPEN If handles are not in correct positions follow instructions for Bypassing and Isolating the automatic transfer switch in Section 3 Do not force the handles Electrical interlocks prevent a wrong sequence of operation 1 Voltage Checks First check nameplate on transfer switch rated voltage must be the same as normal and emergency line voltages A DANGER Use extreme caution when using a meter to measure voltages Do not touch power terminals shock burns or death could result Perform steps 1 6 at the right Observe the status lights See Figure 1 3 E Black square means light is on O White square means light is off Tf necessary adjust voltage regulator on generator per the manufacturer s recommendations The ADTB will respond only to rated voltage specified on the nameplate Now continue to 2 Electrical Operation on next page Close the normal source circuit breaker The Transfer Switch Connected To Normal and the Normal Source Accepted lights should come on Use an accurate voltmeter to check phase to phase and phase to neutral voltages pres ent at the transfer switch no
9. e the Serial No Bill of Material No BOM and Catalog No from the transfer switch name plate For service call ASCO Services at 1 800 800 2726 you will be put in contact with your local ASI office DISCONNECTING THE CONTROLLER The harness disconnect plugs are furnished for repair purposes only and should not have to be unplugged If the controller must be isolated follow these steps A DANGER Bypass lIsolation Switch is energized Do not touch isolation contact fingers shock burns or death could result Disconnecting the Plugs 1 Bypass and Isolate the Automatic Transfer Switch 2 Open the upper enclosure door 3 Separate the two quick disconnect plugs by squeez ing the latches Do not pull on the harness wires Reconnecting the Plugs 1 The ATS should be still bypassed and isolated 2 The two harness plugs and sockets are keyed Care fully align the plugs with the sockets and press straight in until the latches click 3 Close the enclosure doors 4 Follow Return to Service instructions on page 3 3 TESTING amp SERVICE continued TROUBLE SHOOTING Note any optional accessories that may be furnished on the ADTB and review their operation Refer to any A DANGER separate drawings and or instructions that may be packed Hazardous voltage capable of causing shock with the ADTB burns or death is used in this switch Do not touch the power or load terminals of the bypass swi
10. ed now without load interruption see page 2 1 Bypass Switch Turn crank counter clockwise until window shows TEST position window ISOLATION HANDLE CONN TEST ISOLATE TO CONNECT TO ISOLATE TRANSFER TRANSFER WITCH TURN CLOCKWISE unfold crank N counterclockwise draws out transfer switching device Figure 3 6 Isolation Handle NOTE In the TEST position the transfer switching device solenoid operator circuit is energized through secondary disconnects A DANGER Hazardous voltage capable of causing electrical shock burns or death do not touch any control circuit terminals Automatic Transfer Switch Figure 3 4 CONNECTED to TEST position 3 Continue turning Isolation Handle counterclockwise approx 7 turns until the window shows ISOLATE Bypass Switch Turn crank counter clockwise until window o shows ISOLATE Automatic Transfer Switch Figure 3 5 TEST to ISOLATE position 4 Open the lower enclosure door Pull out the side rail carriage then roll out the transfer switch It can be safely inspected in this position The transfer switch can also be removed for easier maintenance opera tions Figure 3 7 Transfer switching device isolated and pulled out for inspection See page 2 2 for maintenance handle use A lifting yoke kit 607064 is available to facilitate lifting by using an overhead crane or similar equipment Transfer Switch w
11. eighs 350 450 Ibs Use lifting device 607064 or other device capable of lifting this weight to avoid personal injury or equipment damage BYPASSING amp ISOLATING continued RETURN TO SERVICE This procedure explains how to return the automatic transfer switch ATS to service after inspection and maintenance Observe the Bypass Switch Position indica Solenoid interlock prevents you from closing the isolation contacts until the ATS is in the same position as the Bypass Switch tor and lights Refer to Figures 3 7 3 8 3 9 and 3 10 1 Slide the transfer switch ATS into the enclosure isolation contacts facing inward until its crank pins engage the latch plates on both sides Next push in side rail carriage Then close enclosure door Close the enclosure door to prevent personal injury in case of electrical system fault 3 Observe which Bypass Switch Position indicator is black NORMAL or EMERGENCY at the Bypass Switch Handle This indicates the source connected to the load 4 Observe which Transfer Switch Connected To light is on Normal or Emergency on the door This is the position of the Transfer Switch If itis not in the same position as the Bypass Handle change the position of the Transfer Switch as follows To change the position of transfer switch Operate to NORMAL OperatetoOEMERGENCY Align position indicator Do not leave the handle in an intermediate position Turn T
12. f the connection depends on how clean and how tight the joint is Table A Tightening torque values for bolted joints Bolt Diameter Recommended Grade 5 hardware Tightening Torque in inches in foot pounds 5 16 12 3 8 20 1 2 50 5 8 95 Harnesses All internal connections are made at the factory The bypass switch transfer switch and control panel are joined together by an interconnecting wire harness The disconnect plugs are already engaged on enclosed switches For opentype switches the plugs must be engaged after installation is completed Align harness plugs with sockets in the control and push them together until they are secure Engine Starting Contacts and Auxiliary Circuits The engine control contact signal connections and auxiliary circuits are located on terminal block TB as shown on the Wiring Diagram provided with the ADTB Connect the signal wires to the appropriate terminals INSTALLATION continued asco 7000 SERIES an Power Transfer amp Bypass Switch Network Power Transfer Transfer Switch Transfer Switch Control Connected Connected Retransfer Transfer To To Delay t Normal Emergency Bypass tarcos j 7 oe observe Normal Emergency Source Source Disconnect th ese lig hts Accepted Accepted Active GREEN AMBER Figure 1 3 Standard controls and indicators Functional Test Read all instructions on the Wiring Diagrams and labels affixed to the ADTB Note th
13. hipping Angles from the Transfer Switch Open the lower front door The Transfer Switch carriage is secured to the frame for shipment Remove the three shipping angle 1 upper left 1 upper right 1 lower right To prevent serious damage remove three shipping angles from the Transfer Switch carriage Do not turn the Isolation Handle until they are removed INSTALLATION Figure 1 1 Typical enclosure remove 3 shipping L angles from transfer switch Figure 1 2 Remove three shipping L angles INSTALLATION continued A DANGER De energize the conductors before making any line or auxiliary circuitry connections Be sure that Normal and Emergency line connections are in proper phase rotation Place engine gen erator starting control in the OFF position Make sure engine generator is not in operation Testing Power Conductors Do not connect the power conductors to the ADTB until they are tested Installing power cables in conduit cable troughs and ceiling suspended hangers often requires considerable force The pulling of cables can damage insulation and stretch or break the conductor s strands For this reason after the cables are pulled into position and before they are connected they should be tested to verify that they are not defective or have been damaged during installation Protect the switch from construction grit and metal chips to prevent malfunction or shortened life of the ADT
14. ings see Controller User s Guide Copyright ASCO Power Technologies L P 2007
15. ncy generator 2 2 functional test 1 3 1 4 H harness 1 2 disconnect plugs 2 1 HELP customercare asco com 800 800 ASCO Printed in U S A INDEX inspection 3 1 installation 1 1 isolating the ATS 3 2 L lights 1 3 1 4 load connected to emergency 1 5 load connected to normal 1 4 Load Disconnect Active light 1 4 lubrication 2 1 M maintenance preventive 2 1 maintenance handle 2 2 warning 2 2 manual load transfer 2 2 warning 2 2 N nameplate cover Normal Source Accepted light 1 3 O operation electrical 1 4 manual 2 2 warning 2 2 P parts 2 1 phase rotation check 1 3 preventive maintenance 2 1 problem 2 2 R rating label cover removal of shipping angles 1 1 removal of shipping skid 1 1 replacement parts 2 1 return to service 3 3 S service ASCO Services Inc ASI 2 1 settings see Controller User s Guide shipping angles 1 1 warning 1 1 shipping skid 1 1 T test functional 1 3 14 testing power cables 1 2 time delays 2 1 see Controller User s Guide Transfer Control selector switch Retransfer Delay Bypass 1 4 Transfer Test 14 Transfer Switch Connected To Emergency light 1 4 Transfer Switch Connected To Normal light 1 4 transfer test 1 4 2 1 transfer to emergency 1 4 2 1 transfer to normal 1 4 2 1 troubleshooting 2 2 V voltage checks 1 3 voltage pickup and dropout sett
16. ntil Bypass Switch Position shows CLOSED on NORMAL yellow indicator The red light Unit Not In Automatic will flash Bypass Switch Push in Bypass Handle amp turn it clockwise Figure 3 2 Bypass to Normal To Bypass Emergency Source Load connected to Emergency Source The Transfer Switch Connected To Emergency light is on and Transfer Switch Connected To Normal light is off Pull out the Bypass Handle all the way then turn it clockwise until Bypass Switch Position shows CLOSED on EMERGENCY yellow indicator The red light Unit Not In Automatic will flash Bypass Switch Pull out Bypass Handle amp turn it clockwise Figure 3 3 Bypass to Emergency The automatic transfer switch can now be put in the TEST or OPEN position See ISOLATING on page 3 2 NOTE When Accessory 66A reversed Normal amp Emergency connections is specified the handle push pull operation is reversed Follow instructions on the door 3 1 BYPASSING amp ISOLATING continued ISOLATING THE ATS Isolating is required before any service work can be performed on the automatic transfer switch ATS Refer to Figures 3 4 3 5 3 6 and 3 7 1 Bypass the closed automatic transfer switch contacts See BYPASSING on page 3 1 Align position indicator Do not leave the handle in an intermediate position 2 Turn the Isolation Handle counterclockwise approx 16 turns until window shows TEST The ATS can be test
17. o Emergency light is off Push in the Bypass Handle then turn it counterclockwise until Bypass Switch Position shows OPEN green indica tor The Unit Not in Automatic light should be off Bypass Switch Push in Bypass Handle amp turn it D counter clockwise Figure 3 12 Un Bypass Normal To Un Bypass Emergency Source Load connected to Emergency Source The Transfer Switch Connected To Emergency light is on and Transfer Switch Connected To Normal light is off Pull out the Bypass Handle then turn it counterclock wise until Bypass Switch Position shows OPEN green indicator The Unit Not in Automatic light should be off Bypass Switch Pull out Bypass Handle amp turn it counter clockwise Figure 3 13 Un Bypass Emergency The Automatic Delayed Transition Transfer amp Bypass Isolation Switch should be left in this position NOTE When Accessory 66A reversed Normal amp Emergency connections is specified the handle push pull operation is reversed Follow instructions on the door 3 4 A auxiliary circuits 1 2 B bus connections 1 2 bypassing the ATS 3 1 C catalog number cover cleaning 2 1 connections line 1 1 controller disconnecting 2 1 see Controller User s Guide E electrical operation 1 4 Emergency Source Accepted light 1 3 Engine Control selector switch Auto position 2 1 engine starting contacts 1 2 F foundation 1 1 freque
18. on Switch ADTB consists of an upper bypass isolation switch a transfer switch a monitoring and transfer control panel and door mounted controls The ADTB is factory wired and tested Installation requires removal of the shipping skid then securing the enclosure to the supporting founda tion Remove the Shipping Skid Open the front lower door and remove the two front lag screws securing the enclosure to the wood skid Next remove the rear lower panel and remove the two rear lag screws securing the enclosure to the wood skid Supporting foundation and mounting The supporting foundation for the enclosure must be level and straight Allow at least 35 inches in front of the enclosure for draw out of the Transfer Switch Refer to the enclosure outline drawing included with the 7000 Series ADTB for all mounting details including door Opening space If bottom cable entry is used the foundation must be prepared so that the conduit stubs are located correctly Refer to the appropriate enclosure outline drawing for specified cable entrance area and location Provide cable bending space and clearance to live metal parts Whena concrete floor is poured use interlocking conduit spacer caps or a wood or metal template to maintain proper conduit alignment Mounting Refer to the enclosure outline drawing furnished with this switch and mount the 7000 Series ADTB according to the details and instructions shown on the drawing Remove three S
19. ransfer Control Turn Transfer Control switch to Retransfer switch to Transfer Test Delay Bypass hold 15 seconds position ISOLATION HANDLE Connected To Normal Connected To Emergency light should come on light should comes on window ISOLATE TO CONNECT SFER OWITCH TURN CLOCKWISE TO ISOLATI TRANSFI unfold crank clockwise draws in the Transfer Switch If Feature 2B time delay is used there will be a delay before transfer to Emergency NOTE With Normal available the automatic transfer switch will not stay in the emergency position unless Feature 3A time delay is used at least 30 seconds Do not close the isolation contacts unless the Transfer Switch ATS and Bypass Switch are in the same position Figure 3 8 Isolation Handle 2 Turn the Isolation Handle clockwise approx 7 turns until the window shows TEST The ATS can be tested now without load interruption see page 2 1 Bypass Switch 5 When the transfer switch is in the same position as the Bypass Switch handle continue turning the Isolation Handle clockwise about 16 turns until the window shows CONN connected Bypass Switch Turn crank clockwise Cy until Turn crank window clockwise shows until window TEST shows CONN connected ATS Figure 3 10 TEST to CONNECTED position Now continue to the next page for instructions on how to Figure 3 9 ISOLATE to TEST position
20. return the Bypass Handle to the OPEN postition 3 3 BYPASSING amp ISOLATING continued RETURN TO SERVICE continued This procedure explains how to return the Bypass Switch Handle to the OPEN position The Bypass Handle must be in the CLOSED position yellow indicator on NOR MAL or EMERGENCY and the Isolation Handle must be in the TEST position window If the handles are not in these positions refer to Return to Service on page 3 3 See Figures 3 11 3 12 and 3 13 Indicator shows green OPEN when the ATS is not bypassed To un Bypass Normal push in handle all the way amp turn it counterclockwise You can only bypass to the same source that the ATS is connected Solenoid interlock prevents incorrect operation 1 Observe which Bypass Switch Position indicator is yellow VORMAL or EMERGENCY at the Bypass Switch Handle This indicates the source connected to the load Un Bypass to same source as the Bypass Switch Position as follows select Normal or Emergency Indicator shows yellow EMERGENCY CLOSED when ATS is bypassed to Emergency or yellow NORMAL when ATS is bypassed to Normal Source To un Bypass Emergency pull out handle all the way amp turn it counterclockwise Figure 3 11 Bypass Handle and position indicators To Un Bypass Normal Source Load connected to Normal Source The Transfer Switch Connected To Normal light is on and Transfer Switch Connected T
21. rmal source terminals Close the emergency source circuit breaker Start generator if necessary The Transfer Switch Connected To Normal amp Emergency Source Accepted lights should come on Use an accurate voltmeter to check phase to phase and phase to neutral voltages pres ent at the transfer switch emer gency source terminals Use a phase rotation meter to check phase rotation of emer gency source it must be the same as the normal source ABC Shut down the engine genera tor if applicable The Emergen cy Source Accepted light should go off Then put the starting control selector switch on the generator set in the automatic position Close enclosure door INSTALLATION continued ASCO 7000 SERIES i Power Transfer amp Bypass Switch Network Power Transfer Transfer Switch Transfer Switch Control Connected Connected Retransfer Transfer To To Delay t Normal Emergency Bypass Cerone a GREEN RED i lt a operate j FY i FA this switch observe Normal Emergency Load Source Source Disconnect these lights Accepted Accepted Active GREEN AMBER Figure 1 4 Standard controls and indicators 2 Electrical Operation This procedure checks electrical operation of the ATS Be sure to close the enclosure door before proceeding to prevent personal injury in case of electrical system fault Transfer Test
22. tch or transfer switch Table 2 1 Trouble Shooting Checks PROBLEM CHECK IN NUMERICAL SEQUENCE 1 OPERATION 2 3 GEN SET VOLTAGE Engine generator set does not start when the Transfer Control switch is turned and held in Transfer Test position or when normal source fails Hold Transfer Test switch 15 seconds or the outage must be long enough to allow for Feature 1C time delay plus engine cranking and starting Starting control must be in the automatic position Batteries must be charged and connected Check wiring to engine starting contacts Transfer switch does not transfer the load to the emergency source after the Wait for Feature 2B time delay to time out Voltmeter should read at least 90 of nominal phase to phase voltage between Generator output circuit breaker must be closed Generator frequency must be engine generator set starts at least 95 of nominal 57 Hz transfer switch terminals EA for a 60 Hz system and EC or EL1 and EL2 for 2 pole switches Transfer switch does not transfer the load to normal source when normal returns or when the Transfer Control switch is released to time out Wait for Feature 3A time delay Voltmeter should read at least 90 of nominal phase to phase voltage between transfer switch terminals NB and NC NC and NA and NA and NB or NL1 and NL2 for 2 pole switches Engine generator set does not stop after load
23. tive Maintenance 2 1 The Transfer Switch nameplate includes data for each Trouble Shooting 0 00ec eae 2 2 specific 7000 Series 7ADTB Use the switch only BYPASSING amp ISOLATING within the limits shown on this nameplate A typical Catalog Number is shown below with its elements Bypassing the ATS 22 eens 3 1 explained Isolating the ATS eee eee 3 2 oe g Return to Service 3 3 3 4 Catalog Number Identification INDEX aiioe back cover Typical 7000 Series ADTB catalog no for switching neutral 3 pole 1600 amp 480 V in Type 1 enclosure G7ADTB B 3 1600 N 5 C Neutral Phase Poles Amperes Voltage Controller Enclosure A solid 2 single 1000 A 115 J 400 5 standard C type 1 B switching 3 three 1200 B 120 K 415 5X if F type 3R 1600 C 208 L 440 EER G type 4 ordered blank none 2000 D 220 M 460 L type 12 3000 E 230 N 480 blank open type F 240 P 550 G 277 Q 575 H 380 R 600 ASCO Power _ 50 Hanover Road Florham Park New Jersey 07932 1591 USA Technologies For sales or service call 1 800 800 2726 ASCO www ascopower com ASCO POWER TECHNOLOGIES CANADA PO Box 1238 17 Airport Road Brantford Ontario Canada N3T 5T3 telephone 519 758 8450 fax 519 758 0876 for service call 1 888 234 2726 ASCO 381333 140 B amp EMERSON Wwww asco ca SECTION 1 The ASCO 7000 Series Automatic Delayed Transition Transfer amp Bypass Iolati