Eaton Electrical -66103 Network Card User Manual
Contents
1. 6 34003906EN AE ACCESS TO SUPERVISION To check whether the Network Management Card amp Modbus Jbus 66103 is operational after installation and configuration proceed as follows e Runa browser Enter in the address bar http IP address e g http 172 16 1 82 e The home page is displayed Network Management Card amp ModBus JBus ups UPS Properties Help UPS Properties UPS Control Pulsar M 2200 Weekly Schedule Computer Room Shutdown Parameters Logs and Hotification Measuremernts Event Log System Log Email Notification AC Power Settings Network BEE 0 System on Notified Applications si Output crop on Access Control is oop On Firmware Upload Battery Battery load level ModBus JBus serial al Settings Remanng backup tme 4h33mn30s Battery status oK ModBusABus port Not used Last update 2008 05 29 11 10 07 e Set the time by clicking the Time command e Continue configuration via the sections in the Settings menu USER MANUAL This manual provides all the information required to install and configure the Network Management Card amp Modbus Jbus 66103 For more information on the supervision control and configuration functions offered by the Network Management Card amp Modbus Jbus 66103 see the user manual on the Solution Pac 2 CD ROM or in the Products Power Management section of the www eaton com powerquality site 34003906EN AE 7 SENSOR CONNECTION option
2. Configuration Jbus configuration Sensor configuration Exit go 0IAIANwWN e Press the 5 key Jbus configuration The Jbus configuration menu is displayed Jbus settings 1 Display Jbus settings Modify Jbus settings Display Jbus diagnostics Reset Jbus diagnostics Return to Jbus Default Configuration Display Jbus frames Exit ooo KRW ND 12 34003906EN AE Press the 2 key Modifiy Jbus settings O Press Return key to modify the Jbus settings Setting Jbus configutration Set Slave number 0x1 Set the Baud Rate 1 38400 2 19200 3 9600 4 4800 5 2400 6 1200 3 Set data format 1 8 bits 2 7 bits 1 Set stop bit 1 1 bits 2 2 bits 1 Set parity 1 None 2 Even 3 Odd 1 Wait during the new setting is saved TLS Slave JBUS initialized The Jbus configuration is now updated Hex format e Press the 0 key Exit e Press the 0 key Exit Through a web browser e Runa browser e Enter in the address bar http IP address e g http 172 16 1 82 The home page is displayed e Select the setting menu Network Management Card amp ModBus JBus ups ModBus JBus Settings Help UPS Properties Pulsar M 2200 Computer Room UPS Control Weekly Schedule Shutdown Parameters ee ce Serial speed 3500 Logs and Hotification fi M sgun gt Data format fe Event Log Stop bit Fa System Log Emai Notification Party None S
3. The Environment sensor is a Network Management Card amp Modbus Jbus option It is available from EATON cat no 66846 The sensor remotely monitors the UPS environment by regularly measuring the temperature and humidity and checking the states of two external contacts It can also send alarms e mail SNMP trap tripped by pre set thresholds Connection is made via the Service port Settings Sensor on the Network Management Card amp Modbus Jbus The sensor is detected automatically Configuration and supervision use a menu that may be accessed directly from the home page For more information see the user manual of the Network Management Card amp Modbus Jbus ETHERNET Network Management Card amp ModBus JBus ups Environment Status Help UPS Properties Pulsar M 2200 Computer Room UPS Control emper e Weekly Schede Shutdown Parameters o 22 7 C 70 Logs and Notification Min 22 1 recorded on 2008 05 29 13 59 39 Measurements Evert Log Max 22 7 recorded on 2008 05 29 140316 System Log Rami iini PERE Configure thresholds on Environment Settings Emad Notification scusi on Settings Humidity ines 0 488 100 System Noted Appcetions TT TTT TT Access Control Min 46 7 recorded on 2008 0529 13 59 19 m Macc 51 4 recorded on 200805129 14 0248 Firmware Upload Configure thresholds on Reset MnMax Colbrate me Input 1 2008105129 14 01 43 Input 2 open Input 2 2008 05 29 140316 Input 82 closed 8
4. 04 Pulsar MX Frame 15 20 kVA 01 e If the technical level of the UPS is lower than that indicated in the table contact EATON 34003906EN AE 3 OVERVIEW MAC address 209100829000 INDICATIONS Jbus modbus port ETHERNET 10 100BT port Service port Settings Sensor Orange LED RS232 activity Green LED communication with the UPS Catalogue number Orange LED 10 100M Green LED connection activity ETHERNET port LED Colour Status Description ACT Green O OFF Card not connected to network ON Card connected to network but no activity O Port is sending receiving O Flashing 100M Orange O OFF O Port operating at 10 Mbits s ON O Port operating at 100 Mbits s Service port Settings Sensor LED Colour Status Description UPS Data Green O OFF O Card starting ON O Communicating with UPS O Flashing O Normal operation Communication with UPS is operational RS232 Orange OFF Configuration menu activated ON Normal operation Configuration menu not activated O Flashing Communication with Environment Sensor option 4 34003906EN AE The Network Management Card amp Modbus Jbus 66103 can be hot plugged on all UPSs from EATON equipped with a Minislot It is not necessary to shutdown the UPS disconnect the load or restart the UPS Remove the plastic cover of the Minislot Note the MAC address of the card before in
5. 34003906EN AE J BUS MODBUS RS232 link configuration and connection Received data input Not connected Transmitted data output Not connected Signal ground SG Txd Rxd RS485 link configuration and connection For proper operation the polarity of EIA RS485 2 wire and 4 wire lines must be set at only one point and the lines terminated at the end Polarity Normally the master of the network sets the polarity of the line The receiver inputs have a true failsafe feature wich eliminates the need for external bias resistors and ensures a logic high output level when the inputs are open or shorted This guarantees that the receiver outputs are in a known state before communication begins and when communication ceases Termination Termination is used to match impedance of a node to the impedance of the transmission line being used When impedance are mismatched the transmitted signal is not completely absorbed by the load anda portion is reflected back into the transmission line The termination line is not necessary if the speed on the line is much less than 115Kbauds T RS485 RD B 1 R ov 9V The default setting of the RS485 is a 4 wires configuration without polarity and without termination SA1 switch
6. es are used to make the termination and the topology of the line 2 or 4 wires The termination resistance value is 166 Q SA1 description reserved reserved link termination between T to R 2 wires configuration if set to ON connection T to R 2 wires configuration if set to ON connection T to R 2 wires configuration if set to ON reserved reserved link termination between R and R if set to ON ONO OAWN 34003906EN AE 9 2 wires connection JOI polarity if end of the li Ra if end of the li polarity connection o connection ne ne L transmit receive data Master unit transmit receive data Card of an intermediate cubicle Card settings of an intermediate cubicle 10 34003906EN AE Link with termination Link without polarity and without termination 3V3 Ra termination SA1 3 transmit receive data Card of an end of line cubicle 4 wires connection T5V master Rp transmitt A ace transmit data L OV 5V Rp slave receiver connection if end of
7. ettings Save modified settings Save Network gs System Notified Applications Reset Factory Access Control Time Firmware Upload ModBus JBus serial Serge e Set the parameters e Select the Save button to save the new parameters 34003906EN AE 13 TECHNICAL CHARACTERISTICS Physical characteristics Dimensions W x D x H 132 x 66 x 42 mm Weight 709 RoHS 100 compatible Storage Storage temperature range 10 C to 70 C Ambient conditions Operating temperature range 0 C to 40 C Relative humidity 90 RH max without condensation Card performance Supply voltage 5V 5 Supply current all LEDs ON and Environment Sensor connected 300 mA max Functions Web supervision 5 browsers max http 3 browsers max https Languages English French German Italian Spanish Alarms E mail SNMP TRAP Web page Log 400 measurements or events Server protection Up to 100 servers protected Network Fast ETHERNET 10 100 Mbits auto negotiation HTTP 1 1 SNMP V1 NTP TFTP SMTP BOOTP DHCP Identification User name and password Security SSL 3 0 TLS 1 0 Browsers Microsoft Internet Explorer 6 x or higher NMS Enterprise Power Manager EPM Management Pac 2 MIB MIB Il standard UPS EATON MIB V1 7 Settings default values IP network BOOTP DHCP enabled IP address 172 17 16 16 manual configuratio
8. n Subnet mask 255 255 0 0 Gateway 0 0 0 0 NTP server pool ntp org Web page access control User name EATON Password EATON Service port menu access control Password EATON or eaton not modifiable Date and time Synchronise with an NTP server GMT Service port 9600 bits s 8 bits 1 bit stop no parity RS485 port Slave nb 0x01 9600 bits s 8 bits 1 bit stop no parity 14 34003906EN AE ELECTROMAGNETIC COMPATIBILITY When correctly installed and used in accordance with manufacturer instructions the card complies with the following standards e ITE Information Technology Equipment safety IEC EN 60950 1 2002 e EMC EN 61000 6 2 2002 EN 61000 6 3 2002 IEC EN 62040 2 2002 In compliance with European directives Low voltage 73 23 EEC and 93 68 EEC e EMC 89 336 EEC and 93 68 EEC Federal Communication Commission FCC statement This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment The information presented in this manual is also available in other languages in the download section of the EATON site www eaton com powerquality 34003906EN AE 15 www eaton com 34003906EN AE
9. played Network configuration MAC address 00 06 23 00 1C 07 Mode DHCP IP address 172 17 23 18 Subnet mask 255 255 248 0 Gateway 172 17 17 e Note the IP address e Press the 0 key Exit e Press the 0 key Exit You can also use NMC Tool software utility to view the card IP adress Provided on the Solution Pac 2 CD ROM or at www eaton com It must be installed on a network connected PC Your network is not equipped with a BOOTP DHCP server Manual configuration is required To set the network configuration use terminal emulation see above From the main configuration menu e Press the 2 key Network configuration e Press the 2 key Modify Network settings e Follow the instructions and enter the IP parameters 1 Read Network settings 2 Modify Network settings 3 Set ethernet speed O Exit For each of the following questions you can press Return to select the value shown in braces or you can enter a new value Should this target obtain IP settings from the network N N Static IP address 172 17 16 16 172 16 1 82 Subnet mask IP address 255 255 0 0 255 255 255 0 Gateway address IP address 0 0 0 0 172 17 17 1 Done Wait until Done is displayed indicating that the IP parameters have been saved e Press the 0 key Exit e Press the 1 key Reset Press the 2 key Restart The card restarts with the new IP settings after approx one minute
10. serting it Insert and secure the card with the screws Connect the ETHERNET cable Check the ETHERNET port indications O Wait until the UPS Data LED flashes regularly approx two minutes indicating that card start up has terminated correctly Note Connection detection continues until the card has been connected to the network Once connection is made card start up continues IP SETTINGS Once the card has started proceed as indicated below e Connect the serial cable to card s service port and PC s COM port e Use a terminal emulator such as HyperTerminal M with these settings Bits per second Data bits Stop bits Parity Flow control 9600 8 1 none none Echo typed characters locally option disabled e Type EATON or eaton The main configuration menu is displayed EATON NETWORK MANAGEMENT CARD 1 Reset Network configuration Set Login Password to Default Return to Default Configuration Jbus configuration Sensor configuration Exit oon RW ND 34003906EN AE 5 Your network is equipped with a BOOTP DHCP server default The card is configured by default with this service enabled No manual configuration is required The IP parameters are automatically collected by the card From the main configuration menu see above e Press the 2 key Network configuration e Press the 1 key Read Network settings The settings supplied by the server are dis
11. the line connection if end of the line Li Y a receive data Master unit PESA ON SAN LES u OFF ON slave receiver Y receive data slave transmitt transmit data Card of an intermediate cubicle Card settings of an intermediate cubicle Link without polarity and without termination Link with termination At OFF ON al slave receiver termination termination Y receive data slave transmitt transmit data Card of an end of line cubicle 34003906EN AE 11 Configuration of the JBUS MODBUS communication parameters Through settings port ETHERNET Connect the RS232 link to terminal Microsoft O e Use the cord supplied with the card e Connect the card to a computer e Use a terminal emulator such as HyperTerminalTM with these settings Bits per second Data bits Stop bits Parity Flow control 9600 8 1 none none Echo typed characters locally option disabled e Check that UPS power is on e Type EATON or eaton The main configuration menu is displayed EATON NETWORK MANAGEMENT CARD 1 Reset Network configuration Set Login Password to Default Return to Default
12. www eaton com Network Management Card amp Modbus Jbus 66103 Installation manual E T N Powering Business Worldwide 2 34003906EN AE The Network Management Card amp Modbus Jbus 66103 is recommended for central UPSs protecting entire networks or for UPS units backing up critical loads With the card installed the UPS has its own IP address and uses the local computer capabilities to Supply web pages http or https SSL with information on status conditions and measurements settings alarms e Integrate an SNMP based NMS such as HP OpenView IBM Tivoli Netview and Computer Associates Unicenter e Communicate with shutdown modules installed on the protected servers Network Shutdown Module Send e mail and SMS messages Control the ON OFF function of the UPS and the outlets e Monitor the Environment Sensor optional cat no 66846 UNPACKING AND CHECKS e One Network Management Card 8 Modbus Jbus 66103 O One serial cable for configuration 34003918 e One installation manual 34003906 CHECK ON UPS VERSION The Network Management Card amp Modbus Jbus 66103 is compatible with the Pulsar range UPSs available since 2006 Note Important Before installing the card check that the UPS technical level NT is at least A equal to that indicated in the table below UPS Type Technical level NT Pulsar 700 1000 1500 02 Pulsar M 2200 3000 03 Pulsar MX 4000 5000 10000