Home
        Carrier 50VS Heat Pump User Manual
         Contents
1.                                                                                                            DIMENSIONAL DATA    16  14 8  14  12 7  12  10 6  10x8 5       NOTES                       N    Single deflection grilles include adjustable vertical blades for controlling horizontal path of discharge    Double deflection grilles include adjustable vertical and horizontal blades for controlling horizontal and vertical path of  discharge air  recommended     Dimensions are in inches    All dimensions are   1 4 inch    Discharge grilles are shipped loose for field installation    Construction is roll formed aluminum frame and blades    Standard finish is powder coated and will be the same color as the return grille    Installation of grille on adjacent unit sides may require a duct extension to prevent air bypass around discharge grilles   Mounting hardware included     Fig  2     Single and Double Deflection Aluminum Discharge Grille                   3 1 8             DIMENSIONAL DATA    16  14 47 5  14  12       12  10       10  8        NOTES      The opposed blade damper allows control of air volume  cfm  and path of discharge air  Recommended for applica    tions requiring unequal airflow or side discharge grille s  with additional top discharge air opening    Dimensions are in inches    All dimensions are   1 4 inch    Discharge grilles are shipped loose for field installation    Construction is roll formed aluminum frame and blades    Standard finish is powder coa
2.     off        Table 10     Heat Pump Control Board  PCB   PROTOCOL    Modbus    1   Test Normal_   ON   ON   ON         2     FP1 15 F 32 F                  3     Tstat Comm     DIP SWITCH  NUMBER       24 vac Gre  4     RV Cooling          0          5           2       1 OFF  6     Com2 Modbus   Address                      2 Modbus   Address Cre  8     Com2 Modbus   Address OFF   LEGEND   DIP     Dual In Line Package  PC     Personal Computer    PCB     Printed Circuit Board  Table 11     BacNet    Control Board  PCB     DIP SWITCH NUMBER POSITION OFF ON    1 ON  2 OFF  3 OFF  4 OFF  5 OFF  6 OFF  7 OFF  8 OFF  LEGEND           Dual In Line Package    PCB     Printed Circuit Board    DIP Switch Settings and Operation  DIP SWITCH 1  Test Mode   Off Normal Mode   On     Test Mode     Test mode is used to speed up the operation  sequence of the unit  therefore creating a more timely trouble   shooting technique  All time delays are shorted by 10 times  with the exception of the high pressure lockout which is  instantaneous regardless of which mode the switch is posi   tioned  DIP switch 1 must be placed into the Normal mode to  resume proper operation of the unit     DIP SWITCH 2  FP 1 at 15 F   Off FP 1 at 32 F   On     Water Side Freeze Protection Setting     DIP switch 2 is used  to determine the loop freeze protection setting  Depending on  the brine concentration of the liquid source  the temperature  can be set at 15 F or 32     The switch MUST be set to the    On     
3.    25F  Methanol    100  USP Food Grade            Ethanol      Must not be denatured with any petroleum based product     OPEN   LOOP GROUND WATER SYSTEMS     Shut off  valves should be included for ease of servicing  Boiler drains or  other valves should be    tee   d       into the lines to allow acid flush   ing of the heat exchanger  P T plugs should be used so that  pressure drop and temperature can be measured  Piping materi   als should be limited to copper or PVC SCH80     NOTE  Due to the pressure and temperature extremes  PVC  SCH40 is not recommended     Water quantity should be plentiful and of good quality  Con   sult Table 3 for water quality guidelines and recommendations   Copper is recommended for closed loop systems and open loop  ground water systems that are not high in mineral content or  corrosiveness  In ground water situations where scaling could  be heavy or where biological growth such as iron bacteria will  be present  an open loop system is not recommended  Heat ex   changer coils may over time lose heat exchange capabilities  due to build up of mineral deposits  Heat exchangers must only  be serviced by a qualified technician  as acid cleaning agents  and special pumping equipment are required     15         In areas with extremely hard water  the owner should be in   formed that the heat exchanger may require additional system  maintenance and occasional acid flushing     Water Supply and Quality     Check water supply  Water sup   ply should be
4.   04   0 45      0 5    ene    LOW               oe    LOW  Black   HI Bre    50VSE F 540 390    HI                  476    50   86        LOW  Orange   HI       50VSI J 820    HI                 LOW  LOW Blue      VSM N 122      HRe    850    NOTE  Operation not recommended in shaded area     13    311    Optional  Disconnect  Switch          Unit       Power Supply Capacitoy         208 230 60 1  5   1 Black Blue    ed                                              Note 4    2                                                  Compressor    BLOWER SPEED WIRING    50VSA B  50VSC D  50VSE F  50VSG H  50VSI J  50VSK L  50VSM N                                                                                                                                                                                                                                                                                                                                                                                                                                                                                1 See Chart    Above                    SW1              882     1                          2 O       1 15    32          3       Tstat Commi24vac  1 4 O   RV Cooling OFF ON    5                     1         6           2 modbus address               2 modbus address  Typical 24 VAC Field Installed      Com2 modbus address           2 Stage Tstat Wiri                                             g   ii B
5.  TIGHT   Y N     HAVE WATER CONNECTIONS BEEN MADE AND IS FLUID AVAILABLE AT HEAT EXCHANGER    Y N  ____    HAS PUMP BEEN TURNED ON AND ARE ISOLATION VALVES OPEN          HAS CONDENSATE CONNECTION BEEN MADE AND IS A TRAP INSTALLED   Y N   IS AN AIR FILTER INSTALLED   Y N     START UP  IS FAN OPERATING WHEN COMPRESSOR OPERATES   Y N     IF 3 PHASE SCROLL COMPRESSOR IS PRESENT  VERIFY PROPER ROTATION PER INSTRUCTIONS   YN        UNIT VOLTAGE     COOLING OPERATION    PHASE AB VOLTS PHASE BC VOLTS PHASE CA VOLTS   if 3 phase   if 3 phase    PHASE AB AMPS PHASE BC AMPS PHASE CA AMPS   if 3 phase   if 3 phase    CONTROL VOLTAGE    IS CONTROL VOLTAGE ABOVE 21 6 VOLTS   Y N     IF NOT  CHECK FOR PROPER TRANSFORMER CONNECTION     TEMPERATURES  FILL IN THE ANALYSIS CHART ATTACHED     COAXIAL HEAT COOLING CYCLE     EXCHANGER FLUID IN F FLUID OUT F PSI FLOW  HEATING CYCLE   FLUID IN F FLUID OUT F PSI FLOW  AIR COIL COOLING CYCLE   AIR IN    AIR OUT F  HEATING CYCLE   AIR IN    AIR OUT F    CL 1    HEATING CYCLE ANALYSIS                               PSI SAT  4  SUCTION    F  COMPRESSOR  EXPANSION  VALVE DISCHARGE       4  bA     4  LIQUID LINE oF oF  PSI PSI  WATER IN WATER OUT  COOLING CYCLE ANALYSIS  PSI SAT               SUCTION    F  COMPRESSOR  EXPANSION  VALVE DISCHARGE                T W       F  LIQUID LINE oF oF        LF   lt     L_              PSI PSI  WATER IN WATER OUT       HEAT OF EXTRACTION  ABSORPTION  OR HEAT OF REJECTION      FLOW RATE  GPM  x TEMP  DIFF   DEG  F  x FL
6.  and lower it into the riser  from the floor below     NOTE  The top of each riser is equipped with a 3 in  deep  swaged connection  There is sufficient extension at the  bottom to allow insertion of approximately 2 in  of the  riser into the swaged top of the riser below     3  Center risers in the pipe chase and shim the cabinet level   Plumb risers in two planes to assure proper unit operation  and condensate drainage     4  Attach the cabinet assembly to the floor and the building  structure on at least two sides using sheet metal angles   field provided   A field provided base vibration dampen   ing pad can be used to help eliminate transfer of any vi   bration to the structure  If vibration dampening pads are    Fig  8     Friction Loss of Risers       111111 111 11 111111   1111111111 1 11111   Pt  11 1 11 1 11111              SJT      Ne TIT        IN TN TEE TT     BEA  Gk     100   4 4 4 1 1 1 NTR LET     1 1                                       1    11   used some rough in dimensional changes will need to be 1111111111             considered before installation due to style and thickness Pett tt tT EE TT  of the pads  Additional anchorage can be provided by in  gL ie EL       stalling brackets at the top of the cabinet  field provided                   120 140       Riser Length for 1 in  and 1 1 2 in  Expansion   Ft       Water Temperature Difference   F    Fig  9     Allowable Riser Lengths Between  System Expansion Loops    5  DO NOT attach drywall studs to the 
7.  in the            position     DIP Switch 5  Com2   Off BacNet    or LonWorks      Com1   On Communicating Thermostat    Com2 modbus address    DIP Switch 7  Com2 modbus address    DIP Switch 8  Com2 modbus address     Standard 24 vac Sequence of Operation    RANDOM START DELAY     When the unit is first pow   ered    On    the control microprocessor will generate a random  number to determine the start delay of the compressor opera   tion  3 to 5 minutes   This delay is used to prevent multiple  units from cycling    On    at the same time  The purpose is to  prevent a large power load on the building electrical system af   ter a power outage  After the number  or delay time  is generat   ed the microprocessor will use this time to determine the mini   mum amount of time that must be delayed before the compres   sor 15 cycled            after a demand is received from the  thermostat     ANTI SHORT CYCLING DELAY     After the random  start delay is generated the microprocessor will use this time to  determine the minimum amount of time that must be delayed  before the compressor is cycled    On    after a demand is  received from the thermostat  This allows the refrigerant sys   tem to equalize in pressure and prevents short cycling of the  compressor     MINIMUM COMPRESSOR RUNTIME     The minimum  compressor runtime of each cycle  heating or cooling  is  60 seconds  Once the compressor is energized it will not de   energize  even if the thermostat input is removed  until t
8.  low speed  blower when a  G  input has been received at the 24 vac ther   mostat input connection  When the input is removed the blow   er will deenergize immediately     START UP    1  Turn on the line power to all heat pumps     2  Turn the thermostat fan position to    ON     Blower should  start     3  Balance airflow at registers     4  Adjust all valves to their full open positions  Room  temperature should be within the minimum maximum  ranges of Table 9  During start up checks  loop water  temperature entering the heat pump should be between  60 and 95        5  Two factors determine the operating limits of the 50VS  heat pumps  supply water temperature and the return air  temperature  When any one of these factors is at a mini   mum or maximum level  the other factor must be at a nor   mal level to ensure proper unit operation     a  Adjust the unit thermostat to the warmest setting   Place the thermostat mode switch in the    COOL     position  Slowly reduce thermostat setting until the  compressor activates     b  Check for cool air delivery at the unit grille within  a few minutes after the unit has begun to operate   NOTE  Units have a 3 to 5 minute time delay in  the control circuit that can be eliminated on the  microprocessor control board  See test mode  described in the DIP Switch Settings and Opera   tion section     c  Check the elevation and cleanliness of the conden   sate lines  Dripping may be a sign of a blocked  line  Check that the condensate trap 
9.  ob   tain maximum performance  Check once a year under normal  operating conditions and  if dirty  brush or vacuum clean  Care  must be taken not to damage the aluminum fins while cleaning        CAUTION    Use caution when cleaning the coil fins as the fin edges are  extremely sharp  Failure to heed this warning could result  in personal injury        Cabinet     The cabinet can be cleaned using a mild  detergent  Do not allow water to stay in contact with the cabi   net for long periods of time to prevent corrosion of the cabinet  sheet metal     Refrigerant System     To maintain sealed circuit integ   rity  do not install service gages unless unit operation appears  abnormal  Verify that air and water flow rates are at proper lev   els before servicing the refrigerant circuit     TROUBLESHOOTING    Lockout Modes     If the microprocessor board is flash   ing a system warning and the unit is locked out and not run   ning  the lockout can be cleared from the microprocessor by a  momentary shutdown of incoming line voltage  208 vac or  230 vac   A lockout that still occurs after line voltage shudown  means that the fault still exists and needs to be repaired     HIGH PRESSURE LOCKOUT  HP      The high pressure  lockout will occur if the discharge pressure of the compressor  exceeds 600 psi  The lockout is immediate and has no delay  from the time the high pressure switch opens to the lockout   Upon lockout the compressor will be deenergized immediately   The blower will be 
10.  of the contactor     208 230 VAC OPERATION     All commercial 208 230 v  units are factory wired for 208 v single phase operation  For  230 v single phase operation the primary voltage to the trans   former must be changed  Remove the red lead from the com   pressor contactor capping it with a wire nut and connecting the  orange 230 vac lead wire from the transformer to the compres   sor contactor     NOTE  Failure to change the primary voltage lead when using    240 vac line voltage may result in electrical component dam   age and intermittent system failure           Table 4     Cabinet Electrical Data     50VS Unit  UNIT VOLTAGE VOLTAGE MAX FUSE SIZE  A   V Hz Ph V Hz Ph  50VSA B 15  50VSC D 15  50VSE F   208230460   2082201860                   ons   25  50VSG H 25  50VSI J 25  50VSK L 35  50VSM N 40  LEGEND  FLA     Full Load Amps  Table 5     Chassis Electrical Data     50VS Unit             E  V Hz Ph AMP  A   A   A   A   A   50VSA B 4 60  50VSC D 6 25  SOVSE F   208230160  133   25                          5    7o   8 80  50VSG H_  208230160  136           4          6   01 1765      75    9 00  50   8     208230160  151   25                 862          89 20   1170  50VSK L 14 10  50VSM N 16 50  LEGEND  LRA     Locked Rotor Amps  RLA     Rated Load Amps    Table 6     50VS Unit Blower Performance and Speed Wiring    UNIT FAN SPEED  RATED  MIN  AND WIRING CFM    LOW        EXTERNAL STATIC PRESSURE  in  wg     crm   o  oor   0 05          015   02   025          035 
11.  of the unit  This sensor is for  monitoring purposes only     DISCHARGE AIR TEMPERATURE SENSOR FAILURE   DAT      If the discharge temperature thermistor fails it will  not affect the operation of the unit  This sensor is for monitor   ing purposes only    FREEZE PROTECTION 1 TEMPERATURE SENSOR  FAILURE  FP1      If the freeze protection 1 thermistor fails  for 30 continuous seconds             lockout will occur  The  compressor will then be deenergized and the blower will deen   ergize 15 seconds after the compressor is deenergized  The sen   sor must be replaced if this lockout occurs     FREEZE PROTECTION 2 TEMPERATURE SENSOR  FAILURE  FP2      If the freeze protection 2 thermistor fails  for 30 continuous seconds an FP2 lockout will occur  The  compressor will then be deenergized and the blower will  deenergize 15 seconds after the compressor is deenergized  The  sensor must be replaced if this lockout occurs     SERVICE    A  WARNING    Electrical shock can cause personal injury or death  When  installing or servicing system  always turn off main power  to system  There may be more than one disconnect switch     A  WARNING    The installation and servicing of air conditioning equip   ment can be hazardous due to system pressure and electri        cal components  Only trained and qualified service  personnel should install  repair  or service air conditioning  equipment     Water Coil Maintenance    CLOSED LOOP SYSTEM       Other Water Loop Applica   tions      Generall
12.  okay to  lt 0 5 ppm      lt 0 5 ppm  Maximum allowable at maximum water temperature   50 F  10 C  Br  240  100     38       lt 20               lt 150                        lt 400 ppm  lt 250 ppm  lt 150 ppm   lt 1000 ppm  lt 550 ppm  lt 375 ppm   gt 1000 ppm  gt 550 ppm  gt 375 ppm     lt 10 ppm   lt 1 ppm    sandfree    for reinjection  of particles and a maxi   mum velocity of 6 fps  Filtered for maximum 800 micron size  Any par   ticulate that is not removed can potentially clog components     Use cupronickel heat exchanger when concentrations of calcium or  sodium chloride are greater than 125 ppm are present   Seawater is  approximately 25 000 ppm      ttlf the concentration of these corrosives exceeds the maximum  allowable level  then the potential for serious corrosion problems  exists   Sulfides in the water quickly oxidize when exposed to air  requir   ing that no agitation occur as the sample is taken  Unless tested  immediately at the site  the sample will require stabilization with a  few drops of one Molar zinc acetate solution  allowing accurate  sulfide determination up to 24 hours after sampling  A low pH and  high alkalinity cause system problems  even when both values  are within ranges shown  The term pH refers to the acidity  basic   ity  or neutrality of the water supply  Below 7 0  the water is con   sidered to be acidic  Above 7 0  water is considered to be basic   Neutral water contains a pH of 7 0   To convert ppm to grains per gallon  divide by 1
13.  plentiful and of good quality  See Table 3 for wa   ter quality guidelines        IMPORTANT  Failure to comply with the above required  water quality and quantity limitations and the closed   system application design requirements may cause damage    to the tube in tube heat exchanger  This damage is not the  responsibility of the manufacturer        In all applications  the quality of the water circulated  through the heat exchanger must fall within the ranges listed in  the Water Quality Guidelines table  Consult a local water treat   ment firm  independent testing facility  or local water authority  for specific recommendations to maintain water quality within  the published limits     Table 3     Water Quality Guidelines    HX CLOSED  CONDITION MATERIAL  RECIRCULATINGt    Scaling Potential     Primary Measurement    OPEN LOOP AND RECIRCULATING WELL      Above the given limits  scaling is likely to occur  Scaling indexes should be calculated using the limits below     pH Calcium  Hardness Method All N A    pH  lt  7 5 and Ca Hardness   lt 100 ppm    Index Limits for Probable Scaling Situations  Operation outside these limits is not recommended    Scaling indexes should be calculated at 150 F for direct use and HWG applications  and at 90 F for indirect HX use  A monitoring plan should be    implemented     Ryznar Stability Index    Langelier Saturation Index    Iron Fouling             Fe2   Ferrous    Bacterial          Potential     Iron Fouling    Corrosion Preventiont
14.  tain 2 hoses  one balancing valve with shutoff  one shut   off  and 2 hose adaptors     4  Locate the valves inside the unit cabinet marked WATER  IN and WATER OUT  Attach the hoses to the water  valve  Always use a back up wrench when tightening the  hose to the valve     5  Ifthe valves are removed to attach the hoses  be sure the  O ring is in the valve before attaching to the union in the  cabinet    NOTE  The valve union is to be hand tight plus an addi   tional 1 4 of a turn  always use back up wrench on the fit   tings being tightened    6  Attach flex hoses  Let the universal ends of the hoses  hang inside the cabinet  See Table 8 for bend allowances   NOTE  Be sure the valve handles and P T ports are in a  position that enables them to be opened and closed and  used for system readings  Check the swivel ends of the  hoses  Gaskets must be in the hose for proper seal                          BALL VALVE       SUPPLY    PRESSURE TEMP TEST PLUG       VALVE DETAIL VIEW          1 2 in  FLEX HOSE  50VSC VSH UNITS   3 4 in  FLEX HOSE  50VSI VSN UNITS     RETURN    BALANCING VALVE    PRESSURE TEMP TEST PLUG    Fig  11     Hose Kit Installation    Table 8     Braided Water Hose Bend Allowances    HOSE DIAMETER         BEND ALLOWANCE  in    1 5 25 8  3 4 475       NOTE  Do not allow hoses to rest against sharp edges or structural  building components  Compressor vibration may cause hose failure  and vibration transmission through the hoses to the structure  caus   ing noise c
15. 08 x 6 69 9 21 x 9 99  Airflow  cfm  20   40   540   640 80   1120   1300  Static Pressure  in  wg  0  WATER CONDENSATE SIDE DATA  Flow Rate  gpm  26   32 45   52   65   85   9 5  Water Connection Size  FPT   in   1 2 3 4  Water Side Pressure Drop  psi  58   58 15         8   48   72   102  Condensate Connection Size  in   3 4  AIR COIL DATA  Total Face Area  sq ft  148   1 411   144   14   481    1     Tube Size  in   3 8  Fin Spacing  FPI  12 14 10  Number of Rows 2 3 2 3  CABINET DATA  Depth  in   18 24  Height  in   88 88  Width  in   18 24  Standard Filter    1 in  Washable 14 1 4 x 18 1 2 14 1 4 x 22 1 2 19 x 28 3 4  LEGEND            Fins Per Inch  PSC     Permanent Split Capacitor                  CONNECTION  i SIZE  FPT            SIZE  in    50VSAB      509865 T  50          A  50VSG H A  5098     50951  A  S0VSMN A          SUPPLY GRILLE    OPTIONAL 24V  THERMOSTAT  LOCATION       CONTROL BOX    CONTROL BOX  ACCESS           MOTOR  BLOWER           OPTIONAL AUTO FLOW   FILTER 1040S REGULATOR LOCATION  FACTORY INSTALLED  SUPPLY AND RETURN  FEEDERS WITH BALL  VALVES       AIR COIL    HOSE KITS          RETURN  AIR OPENING                 PUMP CHASSIS    AIR COIL  DRAIN PAN       CONDENSATE DRAIN PAN       ACOUSTICAL  INSULATION          FACTORY  INSTALLED  P TRAP                Fig  1     50VS Unit Dimensional Data                                                                                                                                                           
16. 1     Freeze Protection Water Side         Capacitor 5  Accessory relays 24 vac maximum  activated        compressor  FP2     Freeze Protection Air Side output           HP    High Pressure Switch o   High Pressure Switch 6  For 230 v operation  remove the red wire and replace with the                Pressure Switch F   Beto 50      6080    BacNet    or LonWorks   card  connect com  LWT     Leaving Water Temperature   i ae                RV    Reversing Male        Low Pressure Switch municating thermostat  then short J1  2 3   If adding terminating  Factory Low Voltage Wiring   resistance  short J1  1 2    Factory High Voltage Wiring        Temperature Thermistor            Field Low Voltage Wiring              Field Line Voltage Wiring 22 Condensate Switch      Optional Block              Internal PCB Connection    Ho    Relay Contacts    Fig  10     Typical 50VS Unit Control Wiring    14    Step 7     Wire Field Control Connections  STANDARD 24 V THERMOSTAT CONNECTIONS      The thermostat should be wired directly to the microprocessor  board terminals labeled      to the corresponding terminals   R C Y1 Y2 0 G     Installation of Optional Wall Mounted Thermostat     The  unit can be controlled with a remote 24 volt surface mounted  thermostat such as the Honeywell TH5320U1001 or  TH6320U1000 series thermostat  Refer to instructions pro   vided with remote thermostat for wiring instructions using  2 stages of heating and 2 stages of cooling for a heat pump  system    Below 
17. 17 18  System Checkout                                     18  FIELD SELECTABLE INPUTS                     18 19  DIP Switch Settings and Operation                  18  Standard 24 vac Sequence of Operation             19  5                                                                    19 20  Operating Limits                                      20  Lockout Mode                                        20  SERVICE 32 33 te                 21  Water Coil Maintenance                              21  Filter S                          ao ad 21  Condensate Drain                                    21                                                               21  Fan     1                                               21  Evaporator                                             21  Cabinet                                            21  Refrigerant 5   516   1                                     21                                                              21 22  Lockout                                                 21  START UP CHECKLIST                         CL1 CL2       SAFETY CONSIDERATIONS    Installation and servicing of air conditioning equipment can  be hazardous due to system pressure and electrical    components  Only trained and qualified service personnel  should install  repair  or service air conditioning equipment    Untrained personnel can perform basic maintenance func   tions such as cleaning coils and filters and replacing filters  All  other operations 
18. 7  Hardness in  mg l is equivalent to ppm      gt     Step 6  Connections    Wire Field Power    A WARNING    Supply    Electrical shock can cause personal injury or death  When  installing or servicing system  always turn off main power  to system  There may be more than one disconnect switch        ELECTRICAL LINE VOLTAGE          field installed wir   ing  including electrical ground  must comply with the National  Electrical Code  NEC  as well as all applicable local codes  Re   fer to Tables 4 and 5 for fuse sizes  Refer to Table 6 for blower  speed wiring  See Fig  10 for field connections or the electrical  diagram located on the back of the electrical compartment front  panel  All electrical connections must be made by the installing   or electrical  contractor  All final electrical connections must  be made with a length of flexible conduit to minimize vibration  and sound transmission to the building     General Line Voltage Wiring     Be sure the available  power is the same voltage and phase shown on the unit             serial plate  Line and low voltage wiring must be done in  accordance with local codes or the NEC  whichever is appli   cable     POWER CONNECTION    Units Equipped with Disconnect     Connect incoming line  voltage to the disconnect switch and ground wire to the ground  lug provided inside the electrical compartment     Units without Disconnect     Line voltage connection is made  by connecting the incoming line voltage wires to the line  side s 
19. AQUAZONE     50VS    Vertical Stack Water Source Heat Pump  with PURON    R 410A  Refrigerant       Installation  Start Up  and Service Instructions    CONTENTS   Page  SAFETY CONSIDERATIONS                           1  65                                                              1                                      0                                       2 17  Step 1     Check    0      5         6                               2  Step 2     Check                                           8  e STORAGE     PROTECTION      INSPECT UNIT  Step 3     Locate                                          8  Step 4     Install Drywall                               8  Step 5     Install Cabinet and Riser                    8        SYSTEM PIPING ARRANGEMENTS   RISER MATERIAL  SIZING  AND INSTALLATION  RISER EXPANSION   RISER CONNECTIONS   COMMERCIAL WATER LOOP APPLICATION  GROUND LOOP HEAT PUMP APPLICATION  OPEN LOOP GROUND WATER SYSTEMS   Step 6     Wire Field Power Supply Connections     13  e ELECTRICAL LINE VOLTAGE     POWER CONNECTION       208 230 VOLT OPERATION    Step 7     Wire Field Control Connections            15  Step 8     Clean and Flush                                15  Step 9     Install Hose                                      15  Step 10     Install Chassis into the Cabinet           16  Step 11     Install Return Panel                       16  Step 12     Install Supply Grille                       17                                                            
20. ARI Standard 110   e Determination of operating limits is dependent primarily  upon three factors   a  Ambient temperature  b  Return air temperature    c  Water temperature      When any one of these factors is at minimum or maximum  levels  the other two factors should be at normal levels to  ensure proper unit operation     20    Extreme variations in temperature and humidity and or cor   rosive water or air will adversely affect unit performance  reli   ability  and service life     Lockout Mode     If the microprocessor board is flashing  a system warning and the unit is locked out and not running   the lockout can be cleared from the microprocessor by a mo   mentary shutdown of incoming line voltage  208 vac or  230 vac   A lockout that still occurs after line voltage shut   down means that the fault still exists and needs to be repaired     HIGH PRESSURE LOCKOUT            The high pressure  lockout will occur if the discharge pressure of the compressor  exceeds 600 psi  The lockout is immediate and has no delay  from the time the high pressure switch opens to the lockout   Upon lockout the compressor will be deenergized immediately   The blower will be deenergized 15 seconds after the compres   sor is deenergized     LOW PRESSURE LOCKOUT  LP      The low pressure  lockout will occur if the suction pressure falls below 40 psi for  30 continuous seconds  The compressor will then be de   energized and the blower will deenergize 15 seconds after the  compressor is deenerg
21. Do not  allow the weight of the ductwork to rest on the unit     6  Provide adequate clearance for filter replacement and  drain pan cleaning  Do not allow piping  conduit  etc  to  block filter access     7  Provide sufficient access to allow maintenance and  servicing of the fan and fan motor  compressor and coils   Removal of the entire unit from the closet should not be  necessary     8  Provide an unobstructed path to the unit within the closet  or mechanical room  Space should be sufficient to allow  removal of unit if necessary     9  Provide ready access to water valves and fittings  and  screwdriver access to unit side panels  discharge collar   and all electrical connections     10  Where access to side panels is limited  pre removal of the  control box side mounting screws may be necessary for  future servicing     STORAGE     If the equipment is not needed immediately at  the jobsite  it should be left in its shipping carton and stored in a  clean  dry area of the building or in a warehouse  Units must be  stored in an upright position at all times  If carton stacking is  necessary  stack units a maximum of 3 cartons high  Do not re   move any equipment from its shipping package until it is need   ed for installation     PROTECTION     Once the units are properly positioned on  the jobsite  cover them with either a shipping carton  vinyl film   or an equivalent protective covering  Cap open ends of pipes  stored on the jobsite  This precaution is especially import
22. IRST STAGE  Y1      When the microproces   sor receives  Y 1  at the 24 vac thermostat input connection the  unit will proceed with the cooling first stage sequence  The mi   croprocessor must receive these signals for 2 continuous sec   onds before it recognizes the inputs as valid  Once the input  signals are determined to be valid the reversing valve will  energize deenergize after 5 seconds  The microprocessor will  then verify that the anti short cycling delay has been satisfied   Once the anti short cycling delay has been satisfied the com   pressor and will cycle    On     The blower will cycle    On    in low  speed 15 seconds after the compressor is cycled    On        HEATING SECOND STAGE        Y2      When the micro   processor receives  Y1  Y2  at the 24 vac thermostat input  connection the unit will proceed with the heating second stage  sequence  The microprocessor must receive these signals for  2 continuous seconds before it recognizes the inputs as valid   Once the input signals are determined to be valid the reversing  valve will energize deenergize after 5 seconds     The microprocessor will then verify that the anti short cy   cling delay has been satisfied  Once the anti short cycling delay  has been satisfied the compressor and will cycle    On     The  blower will cycle    On    in high speed 15 seconds after the com   pressor is cycled    On        FAN ONLY MODE  G      The fan only mode can be used  only with a 24 vac thermostat and will energize the
23. LASH  a 6 6 POSSIBLE FAULT CAUSE     COMMTSTAT  LED1   LED2   LED3   LED4   LED1   LED2   LED3   LED4  High Pressure Lockout Low Airflow  Heating   Low  ON    Water Temperature  lt  35 F  or  lt  15 F  Heating     Condensate Overflow Clogged Drain Line    Over Under Low Voltage  Protection  18 vac  gt  Er 11 OFF  FLASH FLASH  OFF OFF ON ON OFF   Loss of Power  Brown Out  voltage  30 vac    LWT Sensor Failure  Low    Water Temperature                         FLASH     OFF             Resistance Above  or Below Specification    DAT Sensor Failure   Discharge Air Er 14 FLASH  OFF   OFF  FLASH      ADONG  Temperature  or Below Specification    FP1 Sensor Failure   gris     gris     Freeze Protection      FLASH     OFF   FLASH     OFF      OFF Sensor Resistance Above  or Below Specification    FP2 Sensor Failure Sensor Resistance Above    LEGEND  LED     Light Emitting Diode    NOTE  Warning LEDs and error codes are found on the system con   trol board     Copyright 2008 Carrier Corporation    Manufacturer reserves the right to discontinue  or change at any time  specifications or designs without notice and without incurring obligations     Catalog No  04 53500046 01 Printed in U S A     Form 50VS 1SI    Pg 22 311 11 08 Replaces  New    START UP CHECKLIST    CUSTOMER  JOB NAME   MODEL NO   SERIAL NO   DATE                 PRE START UP  DOES THE UNIT VOLTAGE CORRESPOND WITH THE SUPPLY VOLTAGE AVAILABLE   Y N     HAVE THE POWER AND CONTROL WIRING CONNECTIONS BEEN MADE AND TERMINALS 
24. P APPLICATION    NOTE  In most commercial building applications using a  frame style or plate style heat exchanger should be used to iso   late the water source heat pump units from the ground water  loop increasing system performance  equipment longevity     Pre Installation     Prior to installation  locate and mark all ex   isting underground utilities  piping  etc  Install loops for new  construction before sidewalks  patios  driveways  and other  construction has begun  During construction  accurately mark  all ground loop piping on the plot plan as an aid in avoiding po   tential future damage to the installation     11    Piping Installation     All earth loop piping materials should  be limited to polyethylene fusion only for in ground sections of  the loop  Galvanized or steel fittings should not be used at any  time due to their tendency to corrode  All plastic to metal  threaded fittings should be avoided due to their potential to leak  in earth coupled applications  A flanged fitting should be sub   stituted  P T plugs should be used so that flow can be measured  using the pressure drop of the unit heat exchanger     Earth loop temperatures can range between 25 and 110      Flow rates between 2 25 and 3 0 gpm per ton of cooling capac   ity is recommended in these applications     Test individual horizontal loop circuits before backfilling   Test vertical U bends and pond loop assemblies prior to  installation     Pressures of at least 100 psi should be used when t
25. UID FACTOR      Btu hr   SUPERHEAT   SUCTION TEMPERATURE    SUCTION SATURATION TEMPERATURE     DEG      SUBCOOLING   DISCHARGE SATURATION TEMPERATURE    LIQUID LINE TEMPERATURE     DEG F      Use 500 for water  485 for antifreeze     Copyright 2008 Carrier Corporation    Manufacturer reserves the right to discontinue  or change at any time  specifications or designs without notice and without incurring obligations   Catalog No  04 53500046 01 Printed in U S A  Form 50VS 1SI Pg CL 2 311 11 08 Replaces  New    CUT ALONG DOTTED LINE          CUTALONGDOTTEDLINE           0          
26. ally  riser copper type  size  length and insulation thickness are  determined by the location of the water source heat pump unit  in the building  Chilled water and hot water risers are available  in Type M  Type L copper  varying diameters from 3 4 to  21 2 in   and with either no insulation    5 or 3 4 in  thick closed  cell foam insulation  Condensate risers are available in Type M  copper  varying diameters from 3 4 to 11 4 in   and with no  insulation    2 or 3 4 in  thick closed cell foam insulation  All  factory supplied risers and riser extensions are insulated for the  full length of the riser  eliminating the need for field insulation   Insulation is not required on loop water piping except where  the piping runs through unheated areas  outside the building or  when the loop water temperature is below the minimum  expected dew point of the pipe ambient conditions  Insulation  is required if loop water temperature drops below the dew  point  insulation is required for the ground loop applications in  most climates      Riser sizing is generally based on the water flow require   ments of each unit and the units on higher and lower floors that  tie into the same riser column depending on the piping system  chosen  Water piping is often designed at approximately 5 ft s   Keeping this in mind  risers can be reduced in size as the water  flow decreases from floor to floor  For low rise buildings  riser  sizes can be of a single diameter     The reduced material handling 
27. ame Dimensions     50VSI VSN Units                                                             NOTE  All dimensions are in inches     Step 2     Check Unit     Upon receipt of shipment at  the jobsite  carefully check the shipment against the bill of  lading  Make sure all units have been received  Inspect the car   ton or crating of each unit  and inspect each unit for damage   Ensure the shipping company makes proper notation of any  shortages or damage on all copies of the freight bill  Concealed  damage not discovered during unloading must be reported to  the shipping company within 15 days of receipt of shipment     NOTE  It is the responsibility of the purchaser to file all  necessary claims with the shipping company     1  Be sure that the location chosen for unit installation pro   vides ambient temperatures maintained above freezing   Well water applications are especially susceptible to  freezing    2  Be sure the installation location is isolated from sleeping  areas  private offices and other acoustically sensitive  spaces     NOTE  A sound control accessory package may be used  to help eliminate sound in sensitive spaces     3  Check local codes to be sure a secondary drain pan is not  required under the unit     4  Be sure unit is mounted at a height sufficient to provide  an adequate slope of the condensate lines  If an appropri   ate slope cannot be achieved  a field supplied condensate  pump may be required    5  Provide sufficient space for duct connection  
28. ant in  areas where painting  plastering  or spraying of fireproof mate   rial  etc  is not yet complete  Foreign material that accumulates  within the units can prevent proper start up and necessitate  costly clean up operations    Before installing any of the system components  be sure to  examine each pipe  fitting  and valve  and remove any dirt or  foreign material found in or on these components        CAUTION    DO NOT store or install units in corrosive environments or  in locations subject to temperature or humidity extremes     e g   attics  garages  rooftops  etc    Corrosive conditions  and high temperature or humidity can significantly reduce  performance  reliability  and service life  Always move  units in an upright position  Tilting units on their sides may  cause equipment damage        INSPECT UNIT     To prepare the unit for installation  com   plete the procedures listed below     1  Compare the electrical data on the unit nameplate with  ordering and shipping information to verify that the  correct unit has been shipped     2  Do not remove the packaging until the unit is ready for  installation     3  Verify that the unit   s refrigerant tubing is free of kinks or  dents  and that it does not touch other unit components     4  Inspect all electrical connections  Be sure connections are  clean and tight at their terminations     5  Remove any blower support cardboard from inlet of the  blower     6  Locate and verify any accessory kit located in compress
29. are not recommended for 50VSA VSD units   arge Cabine       Fig  12     50VS Unit Airflow Arrangements    17    Table 9     Limits of Operation    Cooling  F  Heating  F     0       85   Rated Ambient Air 68   Rated Entering Air  db wb  68   Entering Air Maximum  db wb  80  30    Air Limits  Ambient Air Maximum  Ambient Air Minimum    Entering Water Minimum    0   20  Entering Water  Normal  50 110 30 70  Entering Water Maximum 90  LEGEND  db     Dry Bulb    wb     Wet Bulb     Requires additional insulation when operating below the dew point     4  Unit fan  Manually rotate fan to verify free rotation and  ensure that blower wheel is secured to the motor shaft  Be  sure to remove any shipping supports if needed  DO NOT  oil motors upon start up  Fan motors are pre oiled at the  factory  Check unit fan speed selection and compare to  design requirements     5  Condensate line  Verify that condensate line is open and  properly pitched toward drain     6  Water flow balancing  Record inlet and outlet water tem   peratures for each heat pump upon start up  This check  can eliminate nuisance trip outs and high velocity water  flow that could erode heat exchangers     7  Unit controls  Verify that the microprocessor DIP  dual  in line package  switches are set for proper operation and  system configuration     System Checkout    1  System water temperature  Check water temperature for  proper range and also verify heating and cooling set  points for proper operation     2  System 
30. are typical thermostat connections and color codes    Re Power  Red    R___R Rc joined by factory jumper wire  Red    Y Compressor Contactor  Stage 1   Yellow    Y2 Compressor Contactor  Stage 2   Blue       24        Common  White    O Reversing Valve  Orange    G Fan Relay  Green     NOTE  The terminal block on the microprocessor board is  removable for ease of thermostat wiring installation     Low voltage wiring between the unit and the wall thermo   stat must comply with all applicable electrical codes  1      NEC  and local codes   and be completed before the unit is  installed  Use of six wire  color coded  low voltage cable is  recommended    Table 7 lists recommended wire sizes and lengths to install  the thermostat  The total resistance of low voltage wiring must  not exceed 1 ohm  Any resistance in excess of 1 ohm may  cause the control to malfunction because of high voltage drop     Table 7     Recommended Wire Gage     Low  Voltage Thermostat    MAXIMUM RUN  UNIT TO       WIRE SIZE  gage     THERMOSTAT   ft   22 30  20 50  18 75  16 125  14 200       Step 8     Clean and Flush System     Cleaning  and flushing the unit is the most important step to ensure  proper start up and continued efficient operation of the system   Follow the instructions below to properly clean and flush the  system     1  Verify that electrical power to the unit is off     2  Verify that supply and return riser service valves are  closed at each unit     3  Fill the system with water  lea
31. ation  operation and ical room  Be sure to allow adequate space around the unit for  maintenance instructions are provided with each unit  Before servicing  See Fig  1 5 for unit dimensions   unit start up  read all manuals and become familiar with the    unit and its operation  Thoroughly check out the system before A CAUTION  operation  Complete the inspections and instructions listed  below to prepare a unit for installation  See Table 1 for unit    hvsical dat To avoid equipment damage  do not use units as a source of  physical data     heating or cooling during the construction process  The  mechanical components and filters used in these units  quickly becomes clogged with construction dirt and debris  which may cause system damage     IMPORTANT  This equipment is designed for indoor  installation ONLY  Extreme variations in temperature        humidity and corrosive water or air will adversely affect  the unit performance  reliability and service life        Table 1     Physical Data     50VS Unit    UNIT 50VSM N  COOLING CAPACITY  Btuh 32 700  HEATING CAPACITY  Btuh 45 000  CABINET WEIGHT  Ib     ees eT 170  CHASSIS WEIGHT  Ib         15   19   12   187   158    205  COMPRESSOR  1 each  Rotary Scroll  High Side Pressure  psig         Low Side Pressure  psig     FACTORY REFRIGERANT CHARGE R 410A  oz  eet eer Se               ee                    61 8                           Fan Motor Type Speeds PSC 2 speed  Blower Wheel Size  Depth x Width   in    Std High Static 7 
32. deenergized 15 seconds after the compres   sor is deenergized     LOW PRESSURE LOCKOUT  LP      The low pressure  lockout will occur if the suction pressure falls below 40 psi for  30 continuous seconds  The compressor will then be deener   gized and the blower will deenergize 15 seconds after the com   pressor is deenergized     FREEZE PROTECTION 1 LOCKOUT     The freeze pro   tection 1 lockout will occur if the liquid line temperature falls  below the set point  15 F or 30 F  for 30 continuous seconds   See DIP switch 2 description in the DIP Switch Settings and  Operation section  The compressor will then be deenergized  and the blower will deenergize 15 seconds after the compressor  is deenergized     FREEZE PROTECTION 2 LOCKOUT     The freeze pro   tection 2 lockout will occur if the air coil temperature falls be   low the set point  32 F  for 30 continuous seconds  See DIP  switch 2 description in the DIP Switch Settings and Operation  section  The compressor will then be deenergized and the  blower will deenergize 15 seconds after the compressor is  deenergized     CONDENSATE OVERFLOW 1 LOCKOUT  CO1       The unit contains one condensate overflow sensor located in  the chassis drain pan below the air coil  A condensate lockout  will occur if the sensor senses condensate for 30 continuous  seconds  The compressor will then be deenergized and the  blower will deenergize 15 seconds after the compressor is  deenergized    OVER UNDER VOLTAGE PROTECTION     If the unit  cont
33. equipment cabinet     10    2 0    6  When all units on a riser are anchored into place  com   plete riser joints as follows     a  Verify that all riser joints are vertically aligned and  that risers penetrate at least 1 in  into the swaged  joint of the riser below  DO NOT let riser joint bot   tom out     b  Braze riser joints with a high temperature alloy  using proper Phos copper of Silfos  Soft solder 50   50  60 40  85 15  or 95 5 or low temperature alloys  are not suitable riser weld materials     c  Anchor built in risers to the building structure with  at least one contact point  To accommodate vertical  expansion and contraction DO NOT fasten risers  rigidly within the unit    d  Verify that unit shut off valves are closed  DO  NOT OPEN VALVES until the system has been  cleaned and flushed     e  Flush system  refer to System Cleaning and Flush   ing section for more information     f  Install vents in piping loop as required to bleed the  system of air accumulated during installation     7  Install supply duct extension s  provided with the cabinet  by folding the tabs down to secure extension s  to  cabinet     COMMERCIAL WATER LOOP APPLICATION     Com   mercial systems typically include a number of units connected  to a common piping system  Any unit plumbing maintenance  work can introduce air into the piping system  therefore  air  elimination equipment is a major portion of the mechanical  room plumbing  In piping systems expected to utilize water  temperatur
34. es below 50          in  closed cell insulation is re   quired on all piping surfaces to eliminate condensation  Metal  to plastic threaded joints should never be used due to their ten   dency to leak over time     Teflon tape thread sealant is recommended for use in system  piping to minimize internal fouling of the heat exchanger  Do  not over tighten connections and route piping so as not to inter   fere with service or maintenance access  Hose kits include shut  off valves  pressure temperature  P T  plugs for performance  measurement  high pressure stainless steel braided hose  and  hose adaptors     Balancing valves and variable speed pumping systems my  also be used     The piping system should be flushed to remove dirt  pipe  shavings  chips  and other foreign material prior to operation   See System Cleaning and Flushing section  The flow rate is  usually set between 2 25 and 3 5 gpm per ton for most  applications of water loop heat pumps  To ensure proper main   tenance and servicing  P T ports are imperative for temperature  and flow verification  as well as performance checks     Water loop heat pump  cooling tower boiler  systems typi   cally utilize a common loop  maintained between 60 to 90 F   The use of a closed circuit evaporate cooling tower with a sec   ondary heat exchanger between the tower and the water loop is  recommended  If an open type cooling tower is used continu   ously  chemical treatment and filtering will be necessary     GROUND LOOP HEAT PUM
35. esting   Do not exceed the pipe pressure rating  Test entire system  when all loops are assembled     Flushing the Earth Loop     Upon completion of system in   stallation and testing  flush the system to remove all foreign ob   jects and purge to remove all air     Antifreeze     In areas when minimum entering loop tempera   tures drop below 40 F or where piping will be routed through  areas subject to freezing  antifreeze is required  Alcohols and  glycols are commonly used as antifreeze  however your local  Carrier distributor should be consulted for the antifreeze best  suited to your area  Freeze protection should be maintained to  15 F below the lowest expected entering loop temperature  For  example  if 30 F is the minimum expected entering loop tem   perature  the leaving loop temperature would be 25 to 22 F and  freeze protection should be at 15     Calculation as follows     30     15    15       All alcohols should be premixed and pumped from a reser   voir outside of the building when possible or introduced under  the water level to prevent fumes  Calculate the total volume of  fluid in the piping system  Then use the percentage by volume  shown in Table 2 for the amount of antifreeze needed  Anti   freeze concentration should be checked from a well mixed  sample using a hydrometer to measure specific gravity           Table 2     Antifreeze Percentages by Volume  MINIMUM TEMPERATURE FOR LOW                        TYPE TEMPERATURE PROTECTION    10      15      20F
36. ety alert  symbol        When this symbol is displayed on the unit and in  instructions or manuals  be alert to the potential for personal  injury     A  WARNING    Electrical shock can cause personal injury or death  Before    installing or servicing system  always turn off main power  to system  There may be more than one disconnect switch   Turn off accessory heater power if applicable        GENERAL    This installation and start up instructions literature is for  Aquazone    water source heat pump systems     The SOVS water source heat pump  WSHP  is a vertically  stacked unit with electronic controls designed for year round  cooling and heating     IMPORTANT  The installation of water source heat pump  units and all associated components  parts  and accessories  which make up the installation shall be in accordance with  the regulations of ALL authorities having jurisdiction and    MUST conform to all applicable codes  It is the responsi   bility of the installing contractor to determine and comply  with ALL applicable codes and regulations        Manufacturer reserves the right to discontinue  or change at any time  specifications or designs without notice and without incurring obligations     Catalog No  04 53500046 01 Printed in U S A     Form 50VS 1SI    Pg 1 311 10 08 Replaces  New    INSTALLATION The 50    8 units are designed for indoor installations  Units  are typically installed in a floor level closet or a small mechan     Step 1     Check Jobsite     Install
37. g  Verify that voltage is within an  acceptable range for the unit and wiring and fuses break   ers are properly sized  Verify that low voltage wiring is  complete     3  Entering water and air  Ensure that entering water and  air temperatures are within operating limits of Table 9     DOUBLE SUPPLY       t SUPPLY AIR TO ROOM    RETURN AIR FROM ROOM  Field supplied and installed piping    Cross hoses in slave cabinet   36 in  hoses required in slave unit               Single   Double   Triple   He  LEGEND  58 1 Cabinet    1412 10x8                      Small Cabinet  Dimension to suit local codes     Gondensate Vrain  50VSC D   44x12   10x8   10x8 and installer     copay   Small Cabinet      50VSE F   Small Cabinet    14  12 ia NOTES   50VSG H   14  12 108   1  Refer to the table and the airfl ts above to determine grill     14  12   10x8 10  8   Refer to the table and the airflow arrangements above to determine grille   Small Cabinet              size and location based on the type and size of the unit cabinet chassis  50VSI J combination    Large Cabinet  16  14   12  10   12x10 2  The riser          is defined as being the rear of each unit  Supply air  grilles and return air access panel can be any side except rear                    16  14   12  10   12  10 3  Return air location also denotes the control location and servicing access   9 4  Single discharge openings are not recommended for 50VSI VSN units   L            0 16  14   12x10   12x10 Triple discharge openings 
38. he min   imum runtime is satisfied     COOLING FIRST STAGE  Y1  O      When the micropro   cessor receives  Y1  O  at the 24 vac thermostat input connec   tion the unit will proceed with the cooling first stage sequence   The microprocessor must receive these signals for 2 continu   ous seconds before it recognizes the inputs as valid  Once the  input signals are determined to be valid the reversing valve will  energize deenergize after 5 seconds     The microprocessor will then verify that the anti short cy   cling delay has been satisfied  Once the anti short cycling delay  has been satisfied the compressor and will cycle    On     The  blower will cycle    On    in low speed 15 seconds after the com   pressor is cycled    On        COOLING SECOND STAGE        Y2          When the mi   croprocessor receives  Y1  Y2      at the 24 vac thermostat in   put connection the unit will proceed with the cooling second  stage sequence  The microprocessor must receive these signals  for 2 continuous seconds before it recognizes the inputs as val   id  Once the input signals are determined to be valid the revers   ing valve will energize deenergize after 5 seconds  The micro   processor will then verify that the anti short cycling delay has  been satisfied  Once the anti short cycling delay has been satis   fied the compressor and will cycle    On     The blower will cycle     On    in high speed 15 seconds after the compressor is cycled     On           DIP Switch 6    19    HEATING F
39. inimum flow rate for entering water  temperatures below 50 F is 2 0 gpm per ton     Filters     A clean filter must be used to obtain maximum  performance  Filters should be inspected every month under  normal operating conditions  It is especially important to pro   vide consistent washing of these filters  in the opposite direc   tion of the normal airflow  once per month  Never operate a  unit without a filter  severe system damage can occur     Condensate Drain     In areas where airborne bacteria  may produce an algae build up in the drain pan  it may be nec   essary to remove and treat the drain pan chemically with an al   gaecide approximately every three months to minimize the  problem  The condensate pan may also need to be cleaned peri   odically to ensure indoor air quality  The condensate drain can  pick up lint and dirt  especially with dirty filters  Inspect the  drain twice a year to avoid the possibility of plugging     Compressor     Conduct annual amperage checks to in   sure that amp draw is no more than 10  greater than indicated  on the serial data plate     Fan Motors     All units have lubricated fan motors  Peri   odic maintenance oiling is not recommended  as it will result in  dirt accumulating in the excess oil and cause eventual motor  failure  Conduct annual dry operation check and amperage       21    check to ensure amp draw is no more than 10  greater than in   dicated on serial data plate     Evaporator Coil     The air coil must be cleaned to
40. is filled to pro   vide a water seal     d  Refer to Table 12  Check the temperature of both  entering and leaving water  If temperature is within  range  proceed with the test  If temperature is  outside of the operating range  see Troubleshooting  section    e  Check air temperature drop across the air coil    when compressor is operating  Air temperature  drop should be between 15 and 25 F     f  Turn thermostat to    OFF    position  A hissing noise  indicates proper functioning of the reversing valve     g  Allow 5 minutes between tests for pressure to  equalize before beginning heating test     h  Adjust the thermostat to the lowest setting  Place  the thermostat mode switch in the    HEAT     position    i  Slowly raise the thermostat to a higher temperature  until the compressor activates     j  Check for warm air delivery within a few minutes  after the unit has begun to operate     k  Refer to Table 9  Check the temperature of both  entering and leaving water  If temperature is within  range  proceed with the test  If temperature is out   side of the operating range  check refrigerant  pressures     1  Check air temperature rise across the air coil when  compressor is operating  Air temperature rise  should be between 20 and 30 F     m  Check for vibration  noise  and water leaks     6  If unit fails to operate  perform troubleshooting analysis   see troubleshooting section   If the check described fails  to reveal the problem and the unit still does not operate   c
41. ividual unit riser columns  This riser arrangement allows for  more flexibility in individual unit riser sizing but has the same  general characteristics as the    reverse return    system described  above  It may also be a better fit for the particular structural and  architectural requirements of the building  This piping system  may also be used on 4 pipe systems     Regardless of the system selected  optimum performance  can only be achieved through adjustment to the recommended  water flow at each individual unit  see Table 1 for individual  unit water flow requirements      RISER MATERIAL  SIZING  AND INSULATION      Some of the factors affecting riser application and sizing are  noise  tube erosion and economics  Water source heat pumps  maybe supplied with factory installed risers  the riser material   diameter  length and insulation thickness must be determined  for each unit based on its positioning within the building   Figure 8 displays riser tube diameter sizes as a function of flow   gpm   friction loss and water velocity  For maximum riser  velocity on pressure drop per 100 ft  refer to ASHRAE  Amer   ican Society of Heating  Refrigeration  and Air Conditioning                                                                TO ABOVE FLOOR Fill  SUPPLY  OPENING 1                                              suPPLY OPENING  A  I 11                              88 5 in   D                LI A oe B          Engineers  Fundamentals Handbook for Riser Sizing  Gener   
42. ized     FREEZE PROTECTION 1 LOCKOUT     The freeze pro   tection 1 lockout will occur if the liquid line temperature falls  below the set point  15 F or 30 F  for 30 continuous seconds   See DIP switch 2 description in the DIP Switch Settings and  Operation section  The compressor will then be deenergized  and the blower will deenergize 15 seconds after the compressor  is deenergized     FREEZE PROTECTION 2 LOCKOUT     The freeze pro   tection 1 lockout will occur if the air coil temperature falls be   low the set point 32 F for 30 continuous seconds  See DIP  switch 2  The compressor will then be deenergized and the  blower will deenergize 15 seconds after the compressor is  deenergized     CONDENSATE OVERFLOW 1 LOCKOUT      1       The unit contains one condensate overflow sensor located in  the chassis drain pan below the air coil  A condensate lockout  will occur if the sensor senses condensate for 30 continuous  seconds  The compressor will then be deenergized and the  blower will deenergize 15 seconds after the compressor is  deenergized     OVER UNDER VOLTAGE PROTECTION     If the unit  control voltage is less than 18 vac or greater than 30 vac the  unit will shut down all inputs immediately  Once the voltage  has reached acceptable levels the unit microprocessor will  power            automatically and resume previous operation     LEAVING WATER TEMPERATURE SENSOR FAIL   URE  LWT      If the leaving water temperature thermistor  fails it will not affect the operation
43. lack             532001001        i 8 9   gt          sae   TH6320U1000   00                 qe                R     Note 2 1 i    9        gt    white  Oo 2   ie   102                 A    oly      fi        84  Note 5 Accessory     nor  H SIm    1                    e      Whit wie     J3 i       Hnit         Relay 1     2 Nor a               gt      lige tne            2  Accessory     2           oie             6  Relay 2 com  112          0   4              P3      5       o                  9        gt               Black  HP  Q         Bacnet   Lonworks     com 3 2 1        88 bes     ome  Card  a            oS                       com 2 1    5       fa aa         0 8   08               2 24        Note 7             gt      Orang RV  Connect to  FF                    4 elo  K Bol        Network     O    gt               Note 1      0  Ke      59995     12                  1  LEGEND NOTES        881    Fan Relay Speed 1 ick Connect Terminal 1  Used for optional communicating thermostat   BR2     Fan Relay Sheed 2     QuickConnect Termi 2  Cut JP1 or JP2 for dry contact output accessory relay 1 and 2   CC     Compressor Contactor Q Screw Terminal 3  If a single stage thermostat is used  place a jumper wire between  CO     Condensate Overflow Y1        Y2 at P1 terminal           Compressor Relay      gt    Relay Coil 4  If the disconnect option is not installed  connect the power to the  DAT     Discharge Air Temperature L1 and L2 lugs on the compressor contactor   FP
44. ns necessitated by variations in floor to          ee 38 20 30      RL          floor dimensions including cutting off or extending risers is the  sole responsibility of the installing contractor     Additional expansion compensation must be made in the  riser system in the field where movement is expected to exceed  the factory allowances  Figure 9 displays the expansion charac   teristics of risers compared to water temperature differential   Assuming a minimum water temperature of 20 F and a  maximum water temperature of 120 F  the temperature differ   ence of 100 F indicates 90 feet of riser will expand or contract  1 inch  To eliminate stress  a riser system must be anchored at  least once to the building structure  Technical information on  pipe expansion  contraction and anchoring can be found in the  ASHRAE HVAC Systems and Equipment Handbook and vari   ous other technical publications  Riser expansion and the an   choring of each unit is the responsibility of the design engineer                      Pressure Drop   Ft Water 100 Ft of Riser   gt                             and installing contractor  1 0        RISER CONNECTIONS     Install cabinet with risers as                     follows  Water Flow Rate   GPM    1  Move cabinet into position      CAUTION  Keep risers off the floor while moving the cabinet  Failure  to heed this warning could result in equipment damage   2  Be sure that all the copper fittings are clean and free of    dirt  Raise the cabinet upright
45. o not allow paint or wall texture over spray to contact coil   fan or other unit components  Warranties are void if paint or  other foreign debris is allowed to contaminate internal unit  components     Step 5     Install Cabinet and Riser   SYSTEM PIPING ARRANGEMENTS     Figure 7 shows  some of the common piping layouts for water source heat  pumps  2 pipe systems are depicted but the same methods can  be applied to 4 pipe systems     The direct return system shows the most common piping ar   rangement  This is the most cost effective method of piping to  install since the water is supplied and returned to a riser column  at the same place  at the bottom or top of the building  Howev   er  this type of system requires more effort to individually bal   ance water flow to the units  The risers are normally capped at  the ends opposite the main supply and return piping and may  require a field installed flush and vent loop     The first reverse return system shows a system  which is  commonly used to minimize individual unit water flow balanc   ing and is often referred to as    self balancing     This riser ar   rangement has a natural affinity to balance the flow to each unit  in the riser column  However  individual unit balancing may  still be required  This piping system is used on 2 pipe systems  only and has an individual return for each riser column     The second reverse return system shows a system with a  common reverse return riser installed separately from the  ind
46. omplaints     7  Slide the chassis part way into the cabinet  Match the  WATER IN hose to the WATER IN tube on the chassis  and the WATER OUT hose to the WATER OUT tube   Tighten the swivel connection keeping the copper tube  parallel to the sides of the chassis  and then tighten the  hose to the copper making sure the hose hangs straight  without twisting or turning     NOTE  The copper union and the hose union is to be  hand tight plus an additional 1 4 of a turn  always use  back up wrench on the fittings being tightened     Step 10     Install Chassis into the Cabinet    1  Open the unit water valves and check piping for leaks     2  Complete electrical connections between cabinet and  chassis by mating the quick connect plugs on the chassis  cable to the plugs located in the bottom surface of the  blower deck  directly under the control box     16    3     Before installing the return panel  perform the following  checks     a  Ensure that fan wheel rotates freely and does not  rub against housing  If rough handling during ship   ping has caused fan wheel to shift  adjust as neces   sary    b  Verify that water piping connections to the chassis  are complete and that unit service valves which  were closed during flushing have been opened     c  Verify that power between the cabinet and chassis  is properly connected     d  After the system has been filled and system pump  is started  all connections should be re checked for  water leaks  Carrier WILL NOT be responsible o
47. on site will often offset the  extra costs associated with the larger risers     RISER EXPANSION     Generally  in medium to high rise  buildings  allowances must be made for pipe expansion  In ap   plications supplemented with factory  or field  supplied be   tween the floor riser extensions  assemble and install exten   sions before installing cabinet     NOTE  Riser assemblies are designed to accommodate a  maximum of 1  g in  expansion and contraction up to a total  movement of 21 4 inches  If the total calculated rise expansion  exceeds 21 4 in   expansion devices must be used  field  provided            DIMENSIONS  in      Pays          1 EXISTING WALL                 p 4 8  MIN      50VS UNIT  SIZE          50VSA VSH  50VSI VSN        647 16                      iy                                        RISERS 4  RETURN Wd        5 MSN     RETURN PANEL                     DRYWALL  TOP VIEW    DRYWALL             EXISTING WA  j  11 16 in  MIN                FRAME  FASTENERS BY OTHERS  RETURN PANEL    STUD       UNIT CABINET  GASKET    DETAIL A    Fig  6     Framing Rough In Detail    DIRECT RETURN REVERSE RETURN REVERSE RETURN  WITH A COMMON REVERSE    Flush Vent Loop Capped Risers RETURN RISER    Roof or hr M Rook       3rd Floor 3rd Floor  2nd Floor 2nd Floor  1st Floor 1st Floor  5     5       Mains  Basement                                                                                           Basement  Fig  7     System Piping Arrangements  All riser modificatio
48. ontact a trained service technician to ensure proper diag   nosis and repair of the equipment     7  When testing is complete  set system to maintain desired  comfort level     NOTE  If performance during any mode appears abnormal  refer to the troubleshooting section of this manual  To obtain  maximum performance  the air coil should be cleaned before  start up  Use a coil cleaner for use on indoor evaporator refrig   eration equipment     Table 12     Temperature Change Through Heat  Exchanger    RISE IN DROP IN  COOLING    F    HEATING    F     WATER FLOW GPM       For Closed Loop  Ground    Source or Closed Loop 4 8  Systems at 3 gpm per ton  For Open Loop  Ground Water 10 17    Systems at 1 5 gpm per ton    Operating Limits  ENVIRONMENT     Units are designed for indoor installa   tion only  Never install units in areas subject to freezing or  where humidity levels could cause cabinet condensation  such  as unconditioned spaces subject to 100  outside air    POWER SUPPLY        voltage variation of   10  of name   plate utilization voltage is acceptable   STARTING CONDITIONS     Starting conditions vary de   pending upon model number and are based upon the following   e Conditions in Table 9 are not normal or continuous operat   ing conditions  Mintmum maximum limits are start up con   ditions to bring the building space up to occupancy  temperatures  Units are not designed to operate under these  conditions on a regular basis   e Voltage utilization range complies with 
49. or  and or blower section     7  Remove any access panel screws that may be difficult to  remove once unit is installed     Step 3     Locate Unit     The following guidelines  should be considered when choosing a location for a WSHP         Units are for indoor use only     e Locate in areas where ambient temperatures are between  39 F and 102 F and relative humidity is no greater than  755     e Provide sufficient space for water  electrical and duct  connections     e Locate unit in an area that allows easy access and removal  of filter and access panels     e Allow enough space for service personnel to perform  maintenance         Return air must be able to freely enter the space if unit needs  to be installed in a confined area such as a closet     Step 4     Install Drywall     All rough in instructions  and drawings are designed for a single layer of  gt  g in  thick dry   wall  Refer to Fig  6  Rough in dimensions will be affected if  drywall thickness is different than 5 5 in   the return panel will  not fit snugly to the wall and form a tight seal  Install drywall  using conventional construction methods  Drywall cannot be  fastened to the studs with adhesive alone  a mechanical fasten   er such as drywall screws must be used     Vacuum all drywall dust and construction debris from coils   drain pans and blower discharge plenum after cutting out sup   ply and return holes for grilles  When installation is complete   cover cabinet supply and return air openings     D
50. pH  Check and adjust water pH if necessary to  maintain a level between 6 and 8 5  Proper pH promotes  longevity of hoses and fittings     3  System flushing  Verify that all hoses are connected end  to end when flushing to ensure that debris bypasses the  unit heat exchanger  water valves and other components   Water used in the system must be potable quality initially  and clean of dirt  piping slag  and strong chemical clean   ing agents  Verify that all air is purged from the system   Air in the system can cause poor operation or system  corrosion     4  Cooling tower boiler  Check equipment for proper set  points and operation     5  Standby pumps  Verify that the standby pump is properly  installed and in operating condition     6  System controls  Verify that system controls function and  operate in the proper sequence     7  Low water temperature cutout  Verify that low water  temperature cutout controls are provided for the outdoor  portion of the loop  Otherwise  operating problems may  occur    8  System control center  Verify that the control center and  alarm panel have appropriate set points and are operating  as designed     FIELD SELECTABLE INPUTS    Jumpers and DIP switches on the control board are used to  customize unit operation and can be configured in the field  See  Tables 10 and 11 for heat pump and BacNet control board DIP  switch settings     18    IMPORTANT  Jumpers and DIP switches should only  be clipped when power to control board has been turned
51. per 150 gallons of  water  Reset the boiler to raise the loop temperature to  about 100 F     6  Circulate the solution for between 8 and 24 hours  At the  end of this period  shut off the circulating pump and drain  the solution  Repeat system cleaning if needed     7  Open the supply and return riser service valves at each  unit  Refill the system and bleed off all air     8  Test the system pH with litmus paper  The system water  should have a pH of 6 to 8 5  Add chemicals as appropri   ate to maintain pH levels     9  When the cleaning process is complete  remove the short   circuited hoses  Reconnect the hoses to the proper supply   and return the connections to each of the units  Refill the  system and bleed off all air     NOTE  DO NOT use    Stop Leak    or similar chemical  agent in this system  Addition of chemicals of this type to  the loop water will foul the heat exchanger and inhibit  unit operation     Step 9     Install Hose Kit    1  Refer to Fig  11 for an illustration of a typical supply   return hose kit assembly     2  Pipe joint compound or Teflon tape is not necessary when  using factory supplied hose kits     NOTE  When anti freeze is used  ensure that it is compat   ible with Teflon tape and pipe joint compound that may  have been applied to other pipe fittings in the system     3  Attach the flex hoses  Unpack and examine hose kit  Re   move all shipping and or packing material such as rubber  bands  plastic caps  and styrofoam  Hose kit should con  
52. position if pure water is used as the source brine  This is nor   mally the case in open loop systems  Set the DIP switch to the     Off    position for closed loop systems that contain a brine con   centration that allows liquid temperatures to fall to  or below   15       DIP SWITCH 3  Tstat at Comm   off tstat at 24 vac   On     Thermostat Selection     DIP switch 3 is used to select the  type of thermostat that will be used to control the unit  A digi   tal communicating thermostat can be purchased with the unit  that will allow all fault signals to be displayed on the  thermostat  This allows for efficient troubleshooting and does  not require that the technician access the electrical control box          to determine the unit error  If a digital communicating thermo   stat is used DIP switch 3 must be set in the          position  1    8  24 vac thermostat is used set DIP switch 3 into the    On     position    DIP SWITCH 4  RV at Cooling   Off RV at Cooling   On     Reversing Valve Operation     DIP switch 4 is used to deter   mine the reversing valve  RV  position in the Cooling mode   deenergized energized   This function is used only when a 24   vac thermostat is used and is determined by the reversing valve  output of the thermostat in the Cooling mode  If the thermostat  deenergizes the reversing valve in the Cooling mode then set  the DIP switch in the             position  If the thermostat ener   gizes the reversing valve in the Cooling mode set the DIP  switch
53. r  liable for damage caused by any water leaks from a  field installed water connection s      4  Re attach the upper electrical access panel  Do not start    the unit with access panel removed  system lockout and  possible equipment damage can occur     Step 11     Install Return Panel    1     Install the provided adhesive backed gasket material on  the outer perimeter of the cabinet to seal the return panel  to the cabinet       Install the cabinet return panel  Refer to Fig  4 and 5     Step 12     Install Supply Grille    Refer to Fig  2  3  and 12 to determine grille size and location  based on the type and size of the unit cabinet chassis combina   tion  Perform the following to install supply grilles over the  cabinet discharge openings     PRE START UP    Check the following before system start up     1  Balancing shutoff valves  Ensure that all isolation valves  are open and water control valves are wired     1  To prevent supply air from short circuiting back into the  return air panel a supply duct extension s  is provided    with each cabinet     2  Insert the grille into the cabinet supply duct extension s    Assure that the grille flange rests against the drywall cov     ering the cabinet     3  Secure the grille to the drywall with the screws provided     NO SUPPLY OPENINGS                         re              SUPPLY RETURN        DRAIN        RISERS    LEFT RIGHT    CABINET       FRONT    Supply Grille Sizes and Arrangements       2  Line voltage and wirin
54. rol voltage is less than 18 vac or greater than 30 vac the  unit will shut down all inputs immediately  Once the voltage    has reached acceptable levels  the unit microprocessor will  power on automatically and resume previous operation     LEAVING WATER TEMPERATURE SENSOR FAIL   URE  LWT      If the leaving water temperature thermistor  fails  it will not affect the operation of the unit  This sensor is  for monitoring purposes only    DISCHARGE AIR TEMPERATURE SENSOR FAILURE   DAT      If the discharge temperature thermistor fails  it will  not affect the operation of the unit  This sensor is for monitor   ing purposes only    FREEZE PROTECTION 1 TEMPERATURE SENSOR  FAILURE  FP1      If the freeze protection 1 thermistor fails  for 30 continuous seconds an        lockout will occur  The    compressor will then be deenergized and the blower will deen   ergize 15 seconds after the compressor is deenergized  The sen   sor must be replaced if this lockout occurs     FREEZE PROTECTION 2 TEMPERATURE SENSOR  FAILURE  FP2      If the freeze protection 2 thermistor fails  for 30 continuous seconds an FP2 lockout will occur  The  compressor will then be deenergized and the blower will deen   ergize 15 seconds after the compressor is deenergized  The sen   sor must be replaced if this lockout occurs     If unit performance during any mode appears abnormal  re   fer to Table 13     Table 13     Troubleshooting    SYSTEM LOCKOUT  STEADY  FAULT DESCRIPTION  ERROR CODE  SYSTEM WARNING  F
55. should be performed by trained service per   sonnel  When working on air conditioning equipment  observe  precautions in the literature  tags and labels attached to the unit   and other safety precautions that may apply    Improper installation  adjustment  alteration  service  main   tenance  or use can cause explosion  fire  electrical shock or  other conditions which may cause personal injury or property  damage  Consult a qualified installer  service agency  or a local  distributor or branch for information or assistance  The  qualified installer or agency must use factory authorized kits or  accessories when modifying this product  Refer to the individ   ual instructions packaged with the kits or accessories when  installing    Follow all safety codes  Wear safety glasses and work  gloves  Use quenching cloth for brazing operations  Have fire  extinguisher available  Read these instructions thoroughly and  follow all warnings or cautions attached to the unit  Consult  local building codes and the National Electrical Code  NEC   for special installation requirements     Understand the signal words     DANGER  WARNING   and CAUTION  DANGER identifies the most serious hazards  which will result in severe personal injury or death   WARNING signifies hazards that could result in personal inju   ry or death  CAUTION is used to identify unsafe practices   which would result in minor personal injury or product and  property damage    Recognize safety information  This is the saf
56. t    6   8 5  pH Monitor treat as needed     iis ol i oe    Ammonia lon as Hydrox   ide  Chloride  Nitrate and  Sulfate Compounds    Copper  CuproNickel  304 SS  316 55  Titanium    Maximum Chloride Levels    Erosion and Clogging     lt 10 ppm of particles and  a maximum velocity of  6 fps  Filtered for maxi   mum 800 micron size     Particulate Size and  Erosion    Brackish    LEGEND  HWG     Hot Water Generator    HX     Heat Exchanger            Design Limits Not Applicable Considering Recirculating  Potable Water   NR     Application Not Recommended   SS     Stainless Steel     Heat exchanger materials considered are copper  cupronickel   304 SS  stainless steel   316 SS  titanium      tClosed recirculating system is identified by a closed pressurized  piping system        Recirculating open wells should observe the open recirculating  design considerations     12                6 0   7 5  If  gt 7 5 minimize steel pipe use    gt 0 5       0 5    If  lt  0 5 minimize steel pipe use   Based upon 150 F HWG and direct well  85 F indirect well HX      lt 0 2 ppm  Ferrous     If Fe2   ferrous   gt 0 2 ppm with pH 6   8  Oo lt 5 ppm check for iron  bacteria      lt 0 5 ppm of Oxygen  Above this level deposition will occur     6   8 5  Minimize steel pipe below 7 and no open tanks with pH  lt 8    lt 0 5 ppm    At   25 gt 0 2 ppm  avoid use of copper and cupronickel piping or HXs     Rotten egg smell appears at 0 5 ppm level     Copper alloy  bronze or brass  cast components are
57. ted and will be the same color as the return grille     Installation of grille on adjacent unit sides may require a duct extension to prevent air bypass around discharge grilles   Mounting hardware included                   A wh    Fig  3     Double Deflection with Opposed Damper Aluminum Discharge Grille    STANDARD PERIMETER BYPASS OPTIONAL PERIMETER OPTIONAL LOUVERED  ALLEN LOCK  REMOVABLE BYPASS ALLEN LOCK OR ALLEN LOCK  REMOVABLE  KEY LOCK  HINGED       26 28 2 95    21 13                  63 15 58 00      55 35                                                 30 38   24   ROUGH IN OPENING PLUS 1 4          STANDARD PERIMETER BYPASS OPTIONAL PERIMETER OPTIONAL LOUVERED  ALLEN LOCK  REMOVABLE BYPASS ALLEN LOCK OR ALLEN LOCK  REMOVABLE  KEY LOCK  HINGED                                                                              NOTE  All dimensions are in inches     Fig  4     Return Panel and Frame Dimensions     50VSA VSH Units          STANDARD PERIMETER BYPASS OPTIONAL PERIMETER OPTIONAL LOUVERED  ALLEN LOCK  REMOVABLE BYPASS ALLEN LOCK OR ALLEN LOCK  REMOVABLE  KEY LOCK  HINGED    3228                2713           H 2 95        30 19                  63 90                                                             A   _     2 38         24 38   _   ROUGH IN OPENING PLUS 1 4        STANDARD PERIMETER BYPASS OPTIONAL PERIMETER OPTIONAL LOUVERED  ALLEN LOCK  REMOVABLE BYPASS ALLEN LOCK OR ALLEN LOCK  REMOVABLE    KEY LOCK  HINGED         Fig  5     Return Panel and Fr
58. ving the air vents open   Bleed all air from the system but do not allow the system  to overflow  Check the system for leaks and make any re   quired repairs     4  Adjust the water and air level in the expansion tank     5  With strainers in place  start the pumps  Systematically  check each vent to ensure that all of the air is bled from  the system     6  Verify that make up water is available and adjusted to  properly replace any space remaining when all air is  purged  Check the system for leaks and make any addi   tional repairs if needed    7  Set the boiler to raise the loop temperature to approxi   mately 85     Open the drain at the lowest point in the  system  Verify that make up water replacement rate    15    equals rate of bleed  Continue to bleed the system until  the water appears clean or for at least three hours which   ever is longer     8  Completely drain the system   Flush risers as follows     1  Close shut off valves at each unit on the riser except the  shut off valve on the top floor     2  Flush solution through supply riser     NOTE  The solution passes through the top floor connec   tion down the return riser     3  When the building has more than 10 floors  connect the  supply and return run outs on the top two floors to divide  the water flow and reduce pressure drop at the pump     4  Repeat flushing procedure for each set of risers in the  building    5  Refill the system and add in a proportion of trisodium  phosphate approximately one pound 
59. y water coil maintenance is not needed for  closed loop systems  However  if the piping is known to have  high dirt or debris content  it is best to establish a periodic  maintenance schedule with the owner so the water coil can be  checked regularly  Dirty installations are typically the result of  deterioration of iron or galvanized piping or components in the  system  Open cooling towers requiring heavy chemical treat   ment and mineral build up through water use can also contrib   ute to higher maintenance  Should periodic coil cleaning be  necessary  use standard coil cleaning procedures  which are  compatible with both the heat exchanger material and copper  water lines  Generally  the more water flowing through the unit   the less chance for scaling  However  flow rates over 3 gpm per  ton can produce water  or debris  velocities that can erode the  heat exchanger wall and ultimately produce leaks     OPEN LOOP SYSTEM  Direct Ground Water      If the  system is installed in an area with a known high mineral con   tent  125 ppm or greater  in the water  it is best to establish a  periodic maintenance schedule with the owner so the coil can  be checked regularly  Should periodic coil cleaning be neces   sary  use standard coil cleaning procedures  which are compati   ble with the heat exchanger material and copper water lines   Generally  the more water flowing through the unit  the less  chance for scaling  Therefore  1 5 gpm per ton is recommended  as a minimum flow  M
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Registered Trademark    StepMill 3  Schmutzwasserpumpe - Grizzly Gartengeräte & Co. KG    Sony PCG-K37 User's Manual  Eye-Fi Center Installation  Shapelets - Caltech Astronomy - California Institute of Technology  Hitachi CP-X400  Spectre Circuit Simulator User Guide    Copyright © All rights reserved. 
   Failed to retrieve file