Home
        Bryant SYSTXBBUIZ01 Thermostat User Manual
         Contents
1.                                         A04017  Fig  5   Thin Decorative Backplate  NN  ES    r      Recessed terminal  block in wall 11 2     wide by 2 1 8    high    Lo    ep  E N  lt  Recessed Mount  Ih S    m Ser Interlocking Tabs  4   py  A03190  LT  000  O Surface Mount  lo  Backplate to wall  IH     5 S al  IF      Interlocking Tabs  4   A03191    Fig  7   Surface Mount Assembly  c  Discard or recycle old control     NOTE  Mercury is a hazardous waste  if existing control contains  any mercury  it MUST be disposed of properly     3     Select Evolution Zone Control    mounting plastic  recess  mount or surface mount and decorative backplate if de   sired        Route wires through large hole in mounting plastic  Level    rear plastic against wall  for aesthetic value only   Evolution  Zone Control    need not be level to operate properly  and  mark wall through two mounting holes       Drill two 3 16 inch mounting holes in wall where marked     Secure mounting plastic to wall using two screws and    anchors provided       Adjust length and routing of each wire to reach each wire    entry on the connector backplate  Strip 1   4 inch of insulation  from each wire     A03188    Fig  8   Large Decorative Backplate          A03192    Fig  9   Decorative Backplate Assembly    8  Match and connect thermostat wires to proper terminals on  User Interface backplate  See wiring diagram Fig  12  13   and 14   A     Green   Data A  B     Yellow   Data B  C     White   24VAC  Com   
2.    2  Make sure all colors match for every terminal   3  Check for 24VAC between the C and D terminal connector  of outdoor unit    I made a mistake on the start up screens  and hit the right side  button to get to the run mode  How do I get back to start up   1  Press the ADVANCED button for at least 10 seconds    2  Install Service menu will appear   3  Scroll down to the INSTALL selection   4  Press the right side button  the screen will prompt you to  press the right side again to re install the system   Control does not see zones 5 through 8   1  Make sure zone module 5   8 has the DIP switches set to the  right   2  Recheck wiring to the ABCD connectors   Control says I have zones 5   8 but not 1   4   1  Make sure zone module 1   4 has the DIP switches set to the  left   2  Recheck wiring to the ABCD connectors     Some zones in my zoned system do not provide enough  comfort   A noticeable difference exists between the actual  room temperature and operating set point  yet the equipment  does not turn on      1  The zone airflow limit may be set too low  Perform the  Zone Airflow Limit Checkout procedure  raise airflow limit  setting  if possible    Some zones provide too much airflow and are noisy     1  The zone airflow limit may be set too high  Perform the  Zone Airflow Limit Checkout procedure  lower airflow  limit setting if possible    CRITICAL MALFUNCTION SCREEN   The following errors will cause a Critical Malfunction screen to  pop up  Heat and Cool LEDs will a
3.    DECORATIVE BACKPLATE     Supplied is a thin decorative  backplate  see Fig  5   to hide any marks screw holes left from the  previous thermostat  This decorative backplate  or beauty ring  can  be used in either the recess or surface mount installation by  snapping it onto back of recessed mount backplate or surface  mount backplate before securing to wall  See Fig  8 and 9 for a  larger decorative backplate P N SYSTXXOLBPO1  5 75    wide X  6    tall   which can be ordered separately                                      LI                      Fig  2   Evolution Zone Control     gt    A   000                                                                    ac d                                                                 Fig  4   Surface Mount Backplate    C  Step 3     Installing Evolution Zone Control       WARNING  ELECTRICAL SHOCK HAZARD    A03185    A03186    A03187    Failure to follow this warning could result in personal    injury or death     Before installing Evolution Zone Control     turn off all    power to equipment  There may be more than one power  source to disconnect        1  Turn off all power to equipment     2  If an existing User Interface or control is being replaced     a  Remove existing control from wall     b  Disconnect wires from existing control     pac aoe                                                                                                                                                                                       
4.    lt  BACK CONTINUE  gt   lt  BACK CONTINUE  gt   AIR FILTER MEDIA TYPE HUMIDIFIER INSTALLED  U V  LIGHTS INSTALLED   A03198    Fig  18   Accessories     UV Lights    whether UV lights are installed on the system  select YES or NO   then press right side button to continue     EG     E  Section 5     Zoning          ZONING ZONING  ZONE 1 Ul  SEARCHING FOR ZONE 3 RS  ZONE EQUIPMENT ZONE 4 RS    WORKING    UI USER INTERFACE  RS REMOTE SENSOR  SS SMART SENSOR    lt BACK CONTINUE  gt                 Fig  18a     Zoning  A04084       SEARCHING FOR ZONE EQUIPMENT will appear on the  screen to identify the number of zones detected  This screen will  show Zone 1  Zone 2  etc  and indicate all zones having either a  remote room sensor  or smart sensors associated with them  If the  system contains smart sensors  they must be assigned a zone  number before continuing  See Smart Sensor Installation Instruc   tions on how to assign Smart Sensors to their respective zones   When finished  press right side button to continue  See Fig  18a     F  Section 6     Equipment Summary          EQUIPMENT SUMMARY  FURNACE 355MAV0420 SETUP  AC 598BNX024 COMPLETE   FILTER EAC  HUMIDIFIER YES  UV LIGHTS YES  ZONES 12345678 SAVE   ALL SELECTIONS     lt  NO YES gt   lt NO YES  gt                    A04109    Fig  19   Equipment Summary    The    EQUIPMENT SUMMARY    screen will appear after Ac   cessories and Zoning have been selected  This screen will give a  summary of all equipment automatically foun
5.  be  displayed    HUMIDIFY WITH FAN    e NO  default    e YES    If YES  the humidifier will run with Continuous Fan operation if  there is a humidify demand     VENTILATOR    NOTE  Only appears if ventilator is installed   CLEAN INTERVAL    e 60 to 180 days of actual operation  default 90     Interval at which the Clean Ventilator Pre filter notification will  turn on     UV LIGHTS INSTALLED      NO   e YES   If YES  indicates to the system whether UV lights are installed   CHANGE INTERVAL      6 to 48 months operation time  default 12 months    Interval at which the Change UV Lights notification will be  displayed    Setup   SYSTEM MAINTENANCE   REMIND OWNER OF ROUTINE MAINTENANCE EVERY     This setup is used to adjust the timer interval in which the normal  System Maintenance notification is turned on for the homeowner       Range  OFF  6 to 24 months   default 12 months     CHECKOUT MENUS  The Checkout menu will show the equipment installed in the  system  A sample checkout menu is shown in Fig  24     CHECKOUT       FURNACE   HEAT PUMP HEATING  HEAT PUMP COOLING  HUMIDIFIER   ZONING   VENTILATOR           lt  BACK SELECT gt     A03204  Fig  24     CHECKOUT MENUS  Checkout   FURNACE    Make sure the furnace is properly installed before continuing      LOW HEAT RUNTIME  5 min     HIGH HEAT RUNTIME  5 min     This menu item allows the furnace to be exercised  First  a low  heat runtime and high heat runtime are selected  Range   5   120  min     If only the low heat is to b
6.  exterior door  window or in a  closet   The remote sensor can be wired to the terminal block  connectors labeled S1 and S2 at the User Interface backplate  or  the OS1 and OSIC connection at the Damper Control Module  In  either case  the Evolution Zone Control will automatically detect  the remote room sensor and ignore its internal temperature sensor   It is also important to note the humidity sensor cannot be remotely  located  so do not locate the Evolution Zone Control in an area  where humidity sensing may not be accurate     NOTE  S1  amp  S2 connection on UI backplate is now used for  Remote Room Sensor  NOT for OAT Sensor hookup     In addition  the Remote Room Sensor is a temperature sensor only   having no additional user inputs  This sensor is typically connected  to the Damper Control Module and used to sense and control  temperature in each zone    SMART SENSOR     Any zone may use a Smart Sensor  It  provides a temperature display and buttons to adjust the desired  temperature in that zone only  It also displays outdoor temperature  and indoor humidity  If a Smart Sensor is used in a zone  a Remote  Room Sensor may also be used in the same zone  The Remote  Room Sensor has priority over the Smart Sensor    WIRING CONSIDERATIONS     Ordinary thermostat wire is  recommended  Use or larger for normal wiring applica   tions  Continuous wire lengths over 100 ft  should use 20 AWG or  larger    NOTE  ABCD bus wiring only requires a four wire connection   however  it
7.  is good practice to run thermostat cable having more  than four wires in the event of a damaged or broken wire during  installation            Each communicating device in the Evolution Zone System has a  four pin connector labeled ABCD  It is recommended that the  following color code be used when wiring each device     A     Green   Data A   B     Yellow   Data B   C     White   24VAC  Com   D     Red   24VAC  Hot     It is not mandatory that the above color code be used  but each  ABCD connector in the system MUST be wired consistently     LOCATING DAMPER CONTROL MODULE     All wiring is  run back to the Damper Control Module  Select a location near the  furnace or fan coil where wiring from the User Interface  each  Remote Room Sensor or Smart Sensor  each damper actuator  and  the equipment itself can come together easily     The Damper Control Module is approved for indoor use only and  should never be installed with any of its components exposed to  the elements  The Damper Control Module  and zone dampers   may be installed in any area where the temperature remains  between  4  F  to 158   F    20  C to 70  C   and there is no  condensation  The cover must be installed to prevent damage from  other sources  Do not locate where it will be accessible to children   It may be mounted in either vertical or horizontal position   Remember that wiring access is likely the most important consid   eration     CAUTION  ELECTRICAL OPERATION HAZARD  Failure to follow this caution
8.  may result in equipment  A damage or improper operation     To prevent possible damage to the Damper Control  Module  DO NOT mount on plenum  ductwork  or flush  against furnace or fan coil        MOUNTING EVOLUTION    ZONE CONTROL     There are  two options for mounting the Evolution Zone Control    to the  wall  First  become familiar with all plastic assembly pieces shown  in Fig  2 through 9  The User Interface will snap together with  either the Recess Mount or the Surface Mount backplate     RECESS MOUNT     This provides the thinnest mounting con   figuration  See Fig  3   The backplate containing the recessed  terminal block can be mounted directly to the wall by cutting a  hole 1 2    wide by 2 1 8    high  Mark location and cut hole in wall     NOTE  Always ensure the Evolution Zone Control    location is  acceptable before cutting any holes in wall     SURFACE MOUNT     This provides surface mounting configu   ration  which allows use of a small hole in the wall  A surface  mount backplate is supplied  See Fig  4   Attach backplate as  shown in Fig  7  and the assembly will mount directly to the wall  requiring only a small hole in the wall allowing a four wire  connection to pass through     NOTE  Once Evolution Zone Control    is secured to wall with  the backplate assembly  snapped together   care must be taken not  to bend or break the interlocking tabs when removing  Gently  remove Evolution Zone Control by rocking up down until inter   locking tabs release  
9.  system  or the system is transitioned from Off to Cool or Heat modes  The  blower will run at a medium airflow for one minute   Unoccupied    Pressing the HOLD button for 3 sec  will set the selected zone to  unoccupied status     All Zones    Pressing the zone button for 3 sec  will gray out the entire display  and put the User Interface into All Zones mode  indicated by All  Zones in upper left of the display   Any changes to set temperature   fan  or Hold status will occur in all zones when the screen is exited   Press the Zone button to exit All Zones mode     TROUBLESHOOTING  Evolution Zone Control    does not power up     1  Recheck wiring to ABCD on all devices   2  Make sure all colors match for every terminal     3  Make sure power is applied to the indoor unit  and the  amber LED is lit on indoor control circuit board     4  Check for 24VAC between the C and D terminals at  Evolution Zone Control    terminal connector and Damper  Control Module    5  Check fuse on indoor unit   s circuit board     Display says    Indoor Unit Not Found      1  Recheck wiring to ABCD on all devices    2  Make sure all colors match for every terminal   3  Press left side button to try again   4      If display still reads    Indoor Unit Not Found     disconnect  all devices from ABCD and connect User Interface directly  to indoor unit     Display says    Outdoor Unit Not Found     and I have a two   speed communicating outdoor unit   1  Recheck wiring to ABCD connector on outdoor unit
10. 2 speed heat pump or AC  unit  a low cool runtime and a high cool runtime are independently  selectable to exercise  The display will change to show the heat  pump or AC operating status  Default time   Fixed 5 min   minimum  range   5   120 min     Checkout   HUMIDIFIER     OFF      ON   The humidifier can be exercised On and Off with this menu option   Checkout   VENTILATOR       SPEED     OFF    LOW  e HIGH    The ventilator can be exercised through all of its operating speeds  with this menu option     Checkout   ZONING  DUCT ASSESSMENT  This is the same Duct Assessment that runs on first start up     Measures duct capacity for each zone  The Duct Assessment will  perform an airflow measurement on each zone and determine the  relative size of each zone along with damper leakage  This  assessment will require approximately 1 minute for each zone in  the system     NOTE  A Duct Assessment will automatically occur every 24  hours at 1 00 p m  to check system static and calibrate dampers     SENSOR DAMPER CHECK     The Sensor Damper Check allows the installer to check each zone  damper for operation  as well as insure the zone sensor corre   sponds to that particular zone     When first initiated  the Zone 1 damper will fully OPEN  and all  other zones will CLOSE  Using the scroll button  the installer can  select each zone and verify the damper is fully open while all other  dampers remain closed     After proper damper operation has been verified  the installer can  now che
11. 25   4 MINUTES ARE REQUIRED ZONE 4 20   TO COMPLETE PROGRESS  ES DAMPER LEAKAGE 10  PRESS START TO BEGIN a     lt  QUIT START  gt   lt  STOP  gt   lt  QUIT START  gt                          Fig  19a     Duct Assessment  A04085    QUICK START    For first time installers  Quick Start will allow a quick start up of  the Evolution Zone System before learning all the details of system  operation  However  for the best possible comfort and operation  refer to the Evolution Zone Control    Owner   s Manual     A  Set Day  Time 8  Desired Humidity    1  Flip down the door at the base of the Evolution Zone  Control    and press the BASIC button     2  Adjust the highlighted HOUR setting using the TIME        button     Press SCROLL button  down  to highlight MINUTE   Adjust the MINUTE setting using the TIME       button   Press SCROLL button  down  to highlight DAY     Adjust the current DAY setting using the TIME        button     Press SCROLL button  down  to highlight HUMIDITY   8  Press the red HEAT button to select heating humidity     DAGA ee NA         9  Adjust desired heating humidity level using either        button     10  Press the blue COOL button to select cooling humidity     11  Adjust the desired  either     button     cooling humidity level using    12  To exit press BASIC button or close door     13  If changes are made  you will be asked to    SAVE  CHANGES  YES NO        B  Override Heating Schedule    1  Press the red HEAT button  Heating mode is confirmed  whe
12. ATIONS WITH EQUIPMENT  PLEASE WAIT     The User Interface will automatically continue  by    SEARCHING FOR INDOOR EQUIPMENT     followed by   SEARCHING FOR OUTDOOR EQUIPMENT     See Fig  15    Once the indoor and outdoor equipment has been found  the  Installer will be asked to select Accessories  Proceed to Section 4   Selecting Accessories    NOTE  If the variable speed indoor equipment  furnace or fan  coil  cannot be found  the User Interface will display    CANNOT  COMMUNICATE WITH INDOOR UNIT     This MUST be  corrected before the initial power up sequence can continue  If  indoor unit is found  but outdoor unit is not found     OUTDOOR  UNIT NOT IDENTIFIED    will appear  Proceed to the next section  for Outdoor Unit Identification     B  Section 2     Selecting Outdoor Unit       OUTDOOR UNIT    NOT IDENTIFIED    OUTDOOR UNIT    OUTDOOR UNIT       SELECT TYPE   NONE  AC  HP    ENTER HEAT PUMP  SIZE    18000 TO 60000 BTU    HEAT PUMP    ENTER NUMBER OF  SPEEDS  1 or 2     PRESS     TO MAKE PRESS     TO MAKE PRESS     TO MAKE                         SELECTION SELECTION SELECTION  CONTINUE gt   lt  BACK CONTINUE  gt   lt  BACK CONTINUE  gt   A03196    Fig  16   Selecting Outdoor Unit    If there is no communicating outdoor unit  the screen  shown in  Fig  16  will appear  Press either Time or Temp     buttons to  select AC  air conditioner   HP  heat pump   or None  no unit  installed   Press right side button to continue to next screen    If either AC or HP has been sel
13. D     Red   24VAC  Hot   NOTE  It is not mandatory that the above color code be used  but  each ABCD connection in the system MUST be wired consis   tently  A separate ABCD Connector comes inside packaging and  should be used when connecting to furnace  or fan coil   Ensure  connector is inserted properly into circuit board   See Fig  10           Fig  10   4   Wire ABCD Connector    CAUTION  ELECTRICAL OPERATION HAZARD  Failure to follow this caution may result in equipment  damage or improper operation    Improper wiring of the ABCD connector will cause the    Evolution Zone System to operate improperly  Check to  make sure all wiring is correct before proceeding with  installation or turning on power        9  Push any excess wire into the wall  Seal hole in wall to  prevent any air leaks  Leaks can affect operation     10  Attach Evolution Zone Control    to the mounting plastic by  lining up the plastic guides on the back of the control with  the opening on the mounting plastic and push on     11  Perform installation of all other system equipment  i e  zone  sensors  dampers  humidifier  ventilator  UV lights  etc      12  Turn on power to equipment     fr N                                                             Zone ___y  zove E e o     lt           Fan Button  Button   lt  Display Screen   LCD   le  gt     lt        Right Side  II IA A A Button  Time        u  lt           Heat Button  Hold  Button             Cool Button  Temperature        Button     SCROLL sys
14. FORT is a  decreased airflow used to improve humidity control  EFFI   CIENCY is the airflow used to meet specified ratings  MAXI   MUM is a fixed airflow speed of 400 CFM ton based on the  outdoor unit size     DEHUM AIRFLOW   e NORMAL  default     HIGH    Normal airflow adjustment used during dehumidifying  If duct  sweating is an issue  selecting HIGH will increase the dehumidi   fying airflow speed and reduce the sweating     HEATER SIZE   e  choices dependent upon fan coil model     This will show the heater size entered during the start up process   This value can be changed to another value  limited by the model  number of the fan coil   If the electric heater is self identifying   this value is not shown     Setup   HEAT PUMP   AC   COOLING LOCKOUT   e NONE  default        45   F     50   F   s 33  F     Outside temperature below which cooling will not be provided     ENTERED SIZE   e  dependent on indoor unit model     Size of the outdoor unit entered during the start up process  If the  outdoor unit is a communicating model  this value will not be  shown  This size can be changed here but is limited to sizes that the  indoor unit can handle     DEFROST INTERVAL       30 minutes     60 minutes      90 minutes   e 120 minutes  default    Time interval at which defrost cycles can occur on a heat pump   ELECT HEAT LOCKOUT   LOCKOUT TEMP      NONE  default    e  5 to 55 deg  F    Outside temperature above which the electric heat will not operate   In dual fuel application
15. ICIENCY  e COMFORT  default   e MAXIMUM    Selects the airflow of the furnace when cooling  COMFORT is a  decreased airflow used to improve humidity control  EFFI   CIENCY is the airflow used to meet specified ratings  MAXI   MUM is a fixed airflow of 400 CFM ton based on the outdoor unit  size    DEHUM AIRFLOW      NORMAL  default       HIGH          NORMAL airflow adjustment is used during dehumidifying  If  duct sweating is an issue  selecting HIGH will increase the  dehumidifying airflow and reduce the sweating     LOW HEAT RISE     ON    OFF  default     Set this to ON if the system contains a bypass humidifier  The ON  setting will increase the furnace low heat airflow     STAGING   e SYSTEM  default   e LOW    HIGH    Controls the staging of the furnace  SYSTEM setting will allow  the Evolution Zone Control    to determine furnace staging  LOW  will only run the low stage of furnace heat  HIGH will only run the  high stage of furnace heat     OFF DELAY    e 90 seconds   e 120 seconds  default   e 150 seconds   e 180 seconds    Amount of time the blower will continue to run after heating has  shut off     LOCKOUT TEMP     NONE  default   e  5 to 55 deg F    Appears on dual fuel systems only  furnace with heat pump    Outside temperature above which the furnace will NOT run     Setup   FAN COIL   HP AC AIRFLOW      EFFICIENCY     COMFORT  default     MAXIMUM    Selects the airflow of the fan coil when heating or cooling with a  heat pump  or cooling with an AC unit   COM
16. Installation and Start Up Instructions    Evolution  Zone Control  SYSTXBBUIZO1                      Evolution    Zone Control  SYSTXBBUIZ01  A04031    NOTE  Read the entire instruction manual before starting the  installation     This symbol     indicates a change since the last issue     TABLE OF CONTENTS          SAFETY CONSIDERATIONS            uuneesssssnennensennennennenne 1  INTRODUCTION     INSTALLATION AND START UP OVERVIEW    1  INSTALLATION   cocinada 1  INITIAL POWER UE aE 288 E S E N N 5  QUICK STAR Tsun a 7  INSTALL   SERVICE MENUS a   OPERATIONAL INFORMATION  ccoccoccnccnconcnncnninncancnncanonacnnannos 12  TROUBLESHOOTING mept e E 13    SAFETY CONSIDERATIONS    Read and follow manufacturer instructions carefully  Follow all  local electrical codes during installation  All wiring must conform  to local and national electrical codes  Improper wiring or installa   tion may damage the Evolution    Zone System  Recognize safety  information  This is the safety alert symbol A    When you see this  symbol on the equipment and in the instruction manual  be alert to  the potential for personal injury  Understand the signal words  DANGER  WARNING  and CAUTION  These words are used  with the safety alert symbol  DANGER identifies the most serious  hazards  which will result in severe personal injury or death       pE    Cancels  New II UIZO1 0 1    03 04    WARNING signifies a hazard  which could result in personal  injury or death  CAUTION is used to identify unsafe pra
17. Owner   s Manual     To enter INSTALL   SERVICE menus  press and hold the  ADVANCED button for at least ten seconds  The following menu  will appear  See Fig  20      NOTE  The INSTALL   SERVICE menu will automatically exit  after 60 minutes of no push button activity     EQUIPMENT SUMMARY  Shows all equipment recognized by  and attached to the system     INSTALL  Used when adding  changing out  or uninstalling  equipment     SETUP  Used to view or modify equipment settings   CHECKOUT  Allows testing of equipment operation       SERVICE  Used to view operation and fault history of equipment  and enter dealer name phone number for display     EQUIPMENT SUMMARY MENU          EQUIPMENT SUMMARY  FURNACE 355MAV0420  AC 598BNX024  FILTER EAC  HUMIDIFIER YES  UV LIGHTS YES  ZONES 1234   lt  BACK          A04108  Fig  21     EQUIPMENT SUMMARY    An example screen is shown in Fig  21     This screen shows indoor unit type and model number  outdoor  unit type  and model number if a 2 speed unit   filter type  any  accessories that are installed  and how many zones are recognized     INSTALL MENU       INSTALL       TO ADD  UNINSTALL OR  RE INSTALL EQUIPMENT   PRESS RIGHT SIDE  BUTTON           lt  BACK INSTALL  gt        A03202  Fig  22     INSTALL    This menu item will perform start up process in order to learn all  equipment in system  Press right side button to initiate the process   See Fig  22     SETUP MENU  This menu has several layers  allowing modification of equipment  setti
18. before routing control wiring        All wiring must comply with national  local  and state codes     EVOLUTION    ZONE CONTROL LOCATION    The Evolu   tion Zone Control    User Interface is the command center for the  Evolution Zone System and is typically located in Zone 1 to sense  and control temperature in this zone  It should be located where it  is easily accessible and visible to the adult homeowner or end user   For accurate temperature measurement  the following guidelines  should be followed     The Evolution    Zone Control and Room Sensors should be  mounted       Approximately 5 feet  1 5 meters  from the floor     e Close to or in a frequently used room  preferably on an inside  partitioning wall     e Ona section of wall without pipes or ductwork    The Evolution    Zone Control and Room Sensors should NOT be   mounted    e Close to a window  on an outside wall  or next to a door leading  to the outside     e Exposed to direct light or heat from a lamp  sun  fireplace  or  other temperature radiating objects which could cause a false  reading    e Close to or in direct airflow from supply registers     e In areas with poor air circulation  such as behind a door or in  an alcove     REMOTE ROOM SENSOR OPTION     A remote room sensor  can be used with the Evolution    Zone Control to take the place of  the User Interface internal temperature sensor  This allows the  Evolution    Zone Control to be mounted in areas with less than  optimal airflow  such as near an
19. ck and verify that each remote room sensor corresponds to  the proper zone damper in the same zone  Start from the top and  highlight zone 1 to open damper  Temporarily disconnect any  other zone remote room sensor  at sensor location   That zone  damper will now OPEN  while the Zone 1 damper will close   EXAMPLE  If the Zone 2 remote room sensor is disconnected  the  Zone 2 damper will now open as indicated on the User Interface    display  The word    FAIL    will also be displayed instead of the  actual temperature for Zone 2  Reconnect Zone 2 sensor and try all  remaining sensors one at a time in the system  Smart Sensors may  also be checked  see Smart Sensor Installation Instructions for  procedure     AIRFLOW LIMITS   e Low     Medium      High  default    e Maximum    Because there is no bypass damper  the Zone Airflow Limit check  will allow the installer to assess the airflow noise generated by the  system providing the maximum amount of airflow to each zone   Select 9 ZONE  then select AIRFLOW LIMIT  Low  Medium   High  default   or Maximum  When Start is pressed  right side  button   the selected zone   s damper will fully open  all others will  close  and the indoor unit will provide the maximum airflow for  that zone  as selected in Setup   ZONING  Airflow Limits   If the  airflow noise is objectionable  the installer can select a lower  airflow noise limit  If the noise is not objectionable  the installer  should leave High selected  or even Maximum     NOTE  S
20. ctices   which may result in minor personal injury or product and property  damage  NOTE is used to highlight suggestions which may result  in enhanced installation  reliability  or operation     INTRODUCTION   The Evolution Zone System consists of several intelligent com   municating components which includes the Evolution Zone Con   trol  or User Interface   Smart Sensors  Damper Control Module   variable  speed furnace or FE fan coil  2 speed AC or HP  which  continually communicate with each other via a four wire connec   tion called the ABCD bus  Commands  operating conditions  and  other data are passed continually between components over the  ABCD bus  The result is a new level of comfort  versatility  and  simplicity    All furnaces or fan coils are variable speed and multi stage for  maximum flexibility  efficiency  and comfort  They support con   trolled ventilation  humidification  dehumidification  and air qual   ity control  Either a dual capacity  communicating   or a standard  24 vac controlled outdoor unit may be used     When using conventional outdoor units  the variable speed furnace  or fan coil provides the 24 volt signals needed to control them   Also  the Evolution    Damper Control Module  P N  SYSTXBB4ZC01  allows connection of a conventional HRV or  ERV without the need for a separate wall control     All system components are controlled through the wall mounted  Evolution    Zone Control  which replaces the conventional ther   mostat and provides th
21. d  1 1   1 1 I 1 is ce ee ga un BD  ul ss   D  a FL O DEP E  A   B  C  D  A B  ol D    9  GO _  Humidifier HUM  NAS Connection   9  Damper com  Control 2e a  module    Sensor  e  Optional              Fig  12     Communicating Indoor Unit w 2 Speed Pu   ron    Communicating Outdoor Unit                                                                                              A04018  Indoor  Zone Control Unit  User Interface  amp   Smart Sensor s  ________ Green  l Yellow  A   B  C   D E EA  1 4 4 1 l l White  l I i I i lona  roto IO ee    l 1 1 l l l I  AA  A B  C  D  A B      0  1 Spd AC  Humidifier 4  Ne  of Connection  Y   gt  e    24V  Damper           e  Control vive Y  module el     gt     a  el              OAT  Sensor    Fig  13     Connection Diagram for Furnace or FE Fan  Coil with 1 Speed AC                                                                                                       A04019  Zone Control Variable Speed  User Interface  amp  Fan Coil  Smart Sensor s  Green  r                4  A  Yellow  AlB CID 1022 22 22       L  1 4 4 4 i l White  1 1 non 1 1 A a Be    na a Red  a ee  ilk a  ee sess ST  D      1 OR L I  allele       a  s  c  o 2  alee 1 Spd  HP  Humidifier HUM  A roo ie e   Y ta a e   Damper   A ERE Y   o  Control NR an ci ee On   module y         ey  e     gt     gt   el                 OAT  Sensor    Fig  14     Connection Diagram for FE Fan Coil with  1 Speed HP  A04020    isolation relay coil to furnace or fan coil HUM and COM term
22. d or manually  selected  If a wrong selection was made  press left side button   BACK selection  to go back to that particular screen and make  changes  When everything is OK  press right side button again to  continue   See Fig  19     The    SETUP COMPLETE  SAVE ALL SELECTIONS      screen will appear after Equipment Summary  To Save All  Selections press  YES  right side button  Pressing the left side  button  NO selection  will return to the Equipment Summary  screen where changes can be performed to any of the equipment  selection screens  After selecting YES  the initial power up  sequence of the new Evolution Zone    Control is complete  The  User Interface screen will now display normal operating mode     G  Section 7     Duct Assessment    The following screen will appear after Setup is exited  Press  right side button to start Duct Assessment  Duct Assessment will  measure the relative size of the ductwork  including damper  leakage  These measurements are used to control the correct  amount of airflow in the zoned system  Status messages will  appear on the screen to indicate what the system is doing  The  process will take approximately one minute per zone  At the end of  the process  the display will show the relative size of each zone  duct  See Fig  19a           DUCT ASSESSMENT DUCT ASSESSMENT DUCT ASSESSMENT  MEASURE DUCT ASSESSMENT ACTIVE   CAPACITY FOR EACH PLEASE WAIT ZONE CAPACITY   ZONE  OPENING ALL ZONES ZONE1 25   AIRFLOW STABILIZING ZONE 2 20   ZONE 3 
23. default 3   This adjusts sensitivity to zone  temperature changes  1   most sensitive  9   least sensitive     PROGRAMMING   e On or Off  default On   e Periods Per Day   2 or 4  default 4     e Programmable Fan On Off  default Off   If ON is selected  fan  can be set to Auto  Low  Med  or High independently in each  zone     SMART RECOVERY   e On or Off   default On     Applies to programmable operation only  Will start recovery 90  minutes prior to schedule change in both heating and cooling  mode     ENGLISH METRIC DISPLAY        F or   C   default     F   RESET FACTORY DEFAULTS   Program Schedule         e Yes No to reset back to Energy Star default Time and Temp  schedules     User Settings     e Yes No to reset the user settings in the Advanced Setup to  factory default settings     Install Settings     e Yes No to reset install settings in Install Service menus to  factory default settings     Last 10 Faults     Yes No to reset last 10 faults under Service Info menu   Setup   FURNACE     Upon a first time start up of the Evolution Zone Control     the  furnace DIP switch settings will be copied to the furnace setup  menu  Any changes can then be made from the Evolution Zone  Contro         AIRFLOW   e COMFORT  default     EFFICIENCY    Selects the airflow of the furnace when heating  EFFICIENCY is  the airflow used to meet specified ratings  COMFORT is a  decreased airflow used to increase the output air temperature and  provide increased comfort     AC AIRFLOW     EFF
24. e exercised     The furnace will execute its ignition start up sequence  This  sequence will be displayed on the Evolution Zone Control screen   After the gas valve and blower motor turn on  the screen will  automatically change to    FURNACE CHECK    and show the  current operating status of the furnace     Checkout   FAN COIL  ELECTRIC HEAT CHECK      ELECTRIC HEAT RUNTIME  5 min   Default time   5 min    Range  0   120 min     If you have a fan coil with electric heaters  this menu item will  allow the heaters to be exercised        10       With self identifying electric heaters  three stages of electric heat  are available to be exercised in any combination  Non identifying  heaters will only provide one stage of heat     Enter the run time  in minutes  of each stage of heat to be  exercised then press START  right side button   The display will  change to show the fan coil s operating status     Checkout   HEAT PUMP HEATING    HIGH HEAT RUNTIME  5 min    e LOW HEAT RUNTIME  5 min      DEFROST  NO    The heat pump heating mode can be exercised with this menu  option  With a 2 speed heat pump  a low heat runtime and a high  heat runtime are independently selectable to exercise  A defrost  cycle is also selectable  Default time   Fixed 5 min  minimum   range   5   120 min    Checkout   HEAT PUMP COOLING OR AC COOLING     HIGH COOL RUNTIME  5 min      LOW COOL RUNTIME  5 min     The heat pump cooling mode  or AC cooling mode  can be  exercised with this menu option  With a 
25. e homeowner with a single wall control for  all features of the system     INSTALLATION AND START UP OVERVIEW  This instruction covers installation of the Evolution    Zone  Control only  Physical installation instructions for the indoor and  outdoor equipment  Damper Control Module  and accessories are  provided with each unit     Setup  commissioning  operation  and troubleshooting of the  Evolution Zone System is covered only in this installation instruc   tion  It is the guide to connecting the system components and  commissioning the system once all physical components are  installed  Special screen prompts and start up capabilities are  provided in the Evolution System to simplify and automate the  initial commissioning of the system      Install Evolution    Zone Control according to this instruction       Install indoor unit  outdoor unit  and accessories according to  their instructions     e Wire complete system according to this instruction     e Setup  commission  and operate system according to this  instruction to assure a smooth and trouble free start up     INSTALLATION  A  Step 1     Check Equipment and Job Site    INSPECT EQUIPMENT     File claim with shipping company   prior to installation  if shipment is damaged or incomplete     B  Step 2     Evolution Zone Control    Location and  Wiring Considerations    WARNING  ELECTRICAL SHOCK HAZARD  A Failure to follow this warning could result in personal    injury or possible equipment damage   Disconnect Power 
26. ected as the outdoor unit type  the  middle screen will appear  See Fig  16   Press either Time or Temp      buttons to select appropriate Btu size of outdoor unit  then press  right side button to continue  If a NIM  Network Interface Module   is applied for non communicating two speed outdoor equipment   select 1 or 2 speed compressor operation   and press right side  button to continue     NOTE  Range of outdoor unit Btu selection is limited by model  number of indoor unit installed  The Evolution Zone Control     will not allow an outdoor unit size that is not supported by the  installed indoor unit     NOTE  On new system installations  the model and serial number  will be recognized and displayed  On any indoor outdoor board  replacements  the equipment will be recognized but the exact  model serial number will not be displayed     C  Section 3     Selecting Electric Heater  ELECTRIC HEATER  NOT IDENTIFIED    ENTER SIZE   5 Kw   KW  NONE  5 10 15 KW    PRESS     TO MAKE  SELECTION     lt  BACK CONTINUE  gt           A03197  Fig  17   Selecting Electric Heater    If indoor unit is a fan coil and the electric heater is not  self identifying     ELECTRIC HEATER NOT IDENTIFIED    will  appear  See Fig  17   Press either Time or Temp     buttons to  select appropriate size of electric heater installed  then press  right side button to continue     NOTE  Range of electric heaters available is limited by model  number of the fan coil installed  The Evolution Zone Control     w
27. electing a lower airflow noise limit may decrease the  homeowner   s comfort in that zone     SERVICE MENUS    The Service Info menu will only show the equipment installed in  the system  Below is a sample using a furnace and a heat pump   dual fuel   A sample service menu is shown in Fig  25     SERVICE INFO    FURNACE STATUS   HEAT PUMP STATUS  ZONING STATUS   LAST 10 SYSTEM FAULTS  RUN FAULT HISTORY  TODAY S DATE  MODEL SERIAL NUMBER       SERVICE PHONE NUMBER        lt  BACK SELECT  gt     A04092  Fig  25     SERVICE INFO MENUS    Service   FURNACE STATUS    The Status screens will show all of the current operating param   eters of each installed piece of equipment     HEAT STAGE       OFF  LOW  HIGH   Displays stage of heat that the furnace is currently delivering   AIRFLOW CFM    e  furnace model dependent    Cubic Feet per Minute of air the blower is currently delivering   LEAVING AIR TEMP     This sensor is NOT required  However  if LAT sensor is  connected to the Damper Control Module  the sensor will read  leaving air temperature of the furnace     COIL TEMP     This sensor is NOT required  However  if HPT sensor is  connected to the Damper Control Module  the sensor will read  temperature at that location  i e  if placed in return air  will read  return air temperature      INDUCER RPM  90  furnaces only       Inducer motor RPM value   BLOWER RPM       Blower motor RPM value     STATIC PRESS     e Inches of water  Displays static pressure that the furnace is  curre
28. en the error code is  cleared or disappears  furnace heating will resume     TWO SPEED OUTDOOR UNIT   Code 85   VC voltage at standby   Code 86   High capacity compressor lockout   USER INTERFACE   Temp Sensor Failed     NO SENSOR DATA    shown in place of  actual temp    Outdoor Unit communication fault    Network Interface Module  NIM  communication fault   Defrost Error  defrost signal on for more than 15 minutes     The user can press the right side button to dismiss the notice  The  regular run mode screen will then appear except    SYSTEM  MALFUNCTION    will appear in place of the day time  If the error  has not disappeared within 24 hours  the above display will return   If the error code disappears     SYSTEM MALFUNCTION    will  disappear and the day time will reappear     14    15    O 2004 Bryant Heating 8 Cooling Systems 7310 W  Morris St  Indianapolis  IN 46231    16    Printed in U S A  iiuizO1 0 1 Catalog No  809 60024    
29. ill not allow an electric heater size that is not supported by the  installed fan coil     D  Section 4     Selecting Accessories    Once the indoor and outdoor equipment have been found or  entered  the following screens will appear allowing the Installer to  select the AIR FILTER TYPE  HUMIDIFIER INSTALLED  and  UV LIGHTS INSTALLED     See Fig  18   Use either Time or  Temp     buttons to make appropriate selections in the highlighted  area on the display screen  Press right side button to continue  or  advance  to the next screen    AIR FILTER TYPE    This accessory screen will appear first   The installer will need to enter the type of filter  MEDIA  EAC  or  both   See Table 1 and make a selection using Time or Temp      button  then press right side button to continue     Table 1     Filter Selection                INSTALLED FILTER MENU SELECTION  1 Inch to 4 inch media MEDIA  High voltage EAC EAC  High voltage EAC   1 to 4 inch media MEDIA   EAC    HUMIDIFIER INSTALLED     This will appear after the Air  Filter Type screen  Select whether a humidifier is installed on the  system  YES or NO  then press right side button to continue     UV LIGHTS INSTALLED    This screen will appear to select       ACCESSORIES    ACCESSORIES    HUMIDIFIER  INSTALLED  YES    ACCESSORIES    U V  LIGHTS  INSTALLED  YES       AIR FILTER TYPE   EAC    MEDIA  MEDIA   EAC    PRESS     TO MAKE PRESS     TO MAKE PRESS     TO MAKE                         SELECTION SELECTION SELECTION  CONTINUE  gt
30. inals  will allow the Evolution Zone Control to automatically energize  the HUM output during a call for humidification  The N O  relay  contacts will be used to energize the humidifier  See fan powered  humidifier installation instructions for more details     BE    WARNING  FIRE OR EQUIPMENT HAZARD  Failure to follow this warning could result in equipment  damage or fire     Do not apply 24vac fan powered humidifier  with internal  power supply  direct to indoor unit HUM and COM  terminals        INITIAL POWER UP  NOTE  Refer to Functional Overview  Fig  11  to become  familiar with key function buttons such as    System On Off         Zone        Fan        Left Side    and    Right Side    buttons  etc  These  function buttons will be used frequently during setup     A  Section 1     Power Up Sequence    INDOOR UNIT    SEARCHING FOR  INDOOR EQUIPMENT    OUTDOOR UNIT    SEARCHING FOR  OUTDOOR EQUIPMENT    ESTABLISHING  COMMUNICATIONS  WITH EQUIPMENT   PLEASE WAIT    WORKING WORKING    SOFTWARE  VERSION       Fig  15     Power Up Sequence    This section addresses initial power up  or commissioning  of a  new Evolution Zone Control     The User Interface will commu   nicate and identify all Evolution components in the system  The  following is a typical example for a communicating Variable   Speed Furnace   Fan Coil with a 2 spd  Air Conditioner   Heat  Pump  including Dual Fuel     The User Interface display will light up and indicate that it is now   ESTABLISHING COMMUNIC
31. iring diagram Fig  14 for connecting an FE fan coil with a  1 speed heat pump  non communicating outdoor unit   When OAT  is applied  the Evolution system will provide enhanced system  features and benefits     NOTE  For other applications not listed  refer to the Network  Interface Module  NIM  Installation Instructions     HUMIDIFIER CONNECTION     A 24vac bypass or fan  powered humidifier may be installed     NOTE  Do Not Use a traditional humidistat to control humidifier  operation  If a humidifier is installed  let the Evolution    Zone  Control operate humidifier     Bypass Humidifiers     A bypass humidifier should be wired  directly to the furnace or fan coil HUM and 24vac COM terminals   The Evolution Zone Control will automatically energize the HUM  output during a call for humidification     Fan Powered Humidifiers     Most fan powered humidifiers  produce internal 24vac in order to energize upon a switch or  contact closure  For this application  a 24vac N O  Isolation Relay   DPST  MUST be used to prevent mixing the internal humidifier  power with the indoor equipment transformer  Applying 24vac    Indoor                                                                                                                                                             Zone Control Unit 2 Spd AC or HP  User Interface  amp   Smart Sensor s  e Green   lb A  l Yellow  A   B  C  D iii    B        B  4 1 4 1 l l White  1 1 1 1 1 Lo  1 CI         Cc  l I l l l l l  1 bode 1 ot Re
32. lternately flash at a 1 second  rate  This appears when system cannot deliver any conditioning at  all     FAN COIL  Code 16   Communication Fault    PEE   o EEE       OUTSIDE  942   FAN  AUTO           ALERT      HVAC SERVICE  1 800 555 1212    CRITICAL MALFUNCTION  CALL TECHNICIAN    Fig  26     Critical Malfunction Screen             A04027    Code 44   Blower Communication Fault   Code 41   Blower Motor Fault   FURNACE   Code 15   Blower Motor Lockout   Code 22   Abnormal Flame Proving Signal  not dual fuel   Code 41   Blower Motor Fault   USER INTERFACE   No communication with indoor unit   SYSTEM MALFUNCTION SCREEN    This screen appears when system cannot completely deliver  conditioning  The following errors will cause a System Malfunc   tion Screen to pop up           OUTSIDE  94     FAN  AUTO      1    HVAC SERVICE  1 800 555 1212    SYSTEM MALFUNCTION  CALL TECHNICIAN  DISMISS  NOTICE  gt     Fig  27     System Malfunction Screen                A04028    FAN COIL   Code 37   Heater output sensed ON when not energized  FURNACE   Code 13   Limit Circuit Lockout   Code 14   Ignition Lockout   Code 21   Gas Heating Lockout   Code 22   Abnormal Flame Proving Signal  dual fuel only   Code 23   Pressure Switch Did Not Open   Code 24   Secondary Voltage Fuse Open   Code 33   Limit Circuit Fault AND High Heat Only is active  Code 45   Control Circuitry Lockout    NOTE  For all the above furnace error codes  the system will use  heat pump heating exclusively if available  Wh
33. n  it will remain on for a  minimum of three minutes  If the set point is changed  this timer is  automatically cancelled  allowing the equipment to turn off imme   diately when the demand is removed     Heat Cool Set points  Desired Temperatures     A minimum difference of 2    default  is enforced between heating  and cooling desired temperatures  This is done by allowing one  setting to    push    the other to maintain this difference  This  difference is adjustable via the Install Service menu under Ther   mostat Setup    Auto Changeover   When Auto mode is enabled  factory default  a change from heat  to cool  or vice versa  will not occur until an opposite mode  demand has existed for 30 minutes  If the set point is changed  the  30 minute requirement is defeated  This Auto Changeover time is  adjustable via the Install Service menu under Thermostat Setup   Range   5   120 min    Smart Recovery   With Smart Recovery selected  factory default   transition out of  setback begins 1 5 hours before selected recovery time and  gradually adjusts room temperature so desired temperature will be  achieved at selected recovery time  It operates in both heating and  cooling  This only applies to programmable operation    Media Filter    If MEDIA or MEDIA EAC is installed in the indoor unit  the  system will perform a static pressure check of the system every 24  hours at 1 00PM to monitor filter accumulation  TrueSense     Dirty Filter Detection  or whenever power is applied to the
34. n the red LED next to the red HEAT button is lit     2  Use the TEMP       button to select your desired heating  temperature     3  The default time for temporarily overriding the temperature  schedule is 2 00 HRS as indicated by the text on the lower  left     NOTE  Override time will not appear if programming has been  turned off     4  You can change the temporary override time in 15 minute  increments by pressing the TIME       button until the  desired override time is selected  or press the HOLD button  anytime to override the schedule indefinitely     C  Override Cooling Schedule    1  Press the blue COOL button  Cooling mode is confirmed  when the blue LED next to the COOL button is lit     2  Use the TEMP       button to select your desired cooling  temperature     3  The default time for temporarily overriding the temperature  schedule is 2 00 HRS as indicated by the text on the lower  left     NOTE  Override time will not appear if programming has been  turned off     4  You can change the temporary override time in 15 minute  increments by pressing the TIME       button until the  desired override time is selected  or press the HOLD button  anytime to override the schedule indefinitely     PER  ae    D  Quick Program Schedule for All Days    This section will give you a quick program schedule for ALL   DAYS of the week  For more information on how to create  customized schedules for every day  the entire week  or weekend   refer to the Owner   s Manual     1  Fli
35. ngs  No settings will need to be made at equipment  i e  DIP  switches on a furnace   All configuration settings made effective  from this menu will override equipment configuration made by dip  switches  Fig  23 shows all the information that can be found in the  SETUP menu     SETUP       THERMOSTAT  FURNACE   HEAT PUMP   ZONING   ACCESSORIES   SYSTEM MAINTENANCE     lt  BACK SELECT  gt           A04089  Fig  23     SETUP MENU    Setup   THERMOSTAT   AUTO MODE SETUP     Enable Disable Auto Changeover mode  default Enable      e Auto Changeover Time may be adjusted 5 to 120 minutes    default   30 minutes      When Auto mode is enabled  factory default  a change from heat  to cool  or vice versa  will not occur until an opposite mode  demand has existed for 30 minutes  If the set point is changed  the  30 minute timer is deleted    HEAT COOL DEADBAND      0 to 6 degrees   default   2        A minimum difference of 2   is enforced between heating and  cooling desired temperatures  This will allow one setting to    push     the other to maintain this difference     eg    OFFSETS  This option allows calibration  or deliberate miscali   bration  of the temperature and humidity sensors  These offsets are  added to the actual temperature humidity values  defaults   0      e Zone 1 Offset   5 to  5 degrees    e Outside Temp Offset   5 to  5 degrees    e Humidity Offset   10 to  10 percent   CYCLES PER HOUR      Maximum cycles per hour   4  default  or 6     e Anticipator   1 to 9  
36. ntly experiencing     LOCKOUT TIMER     Seconds    If a lockout timer is active  this will show the current time value   See furnace manual for details on lockout timers     Service   FAN COIL STATUS  ELECTRIC HEAT      OFF  LOW  MED  HIGH    Displays stages of electric heat that the fan coil is currently  delivering     AIRFLOW CFM    e  fan coil model number dependent    Cubic Feet per Minute of air the blower is currently delivering   LEAVING AIR TEMP     This sensor is NOT required  However  if LAT sensor is  connected to the Damper Control Module  the sensor will read  leaving air temperature of the fan coil     COIL TEMP     This sensor is NOT required  However  if HPT sensor is  connected to the Damper Control Module  the sensor will read  temperature at that location  i e  if placed down stream from  evaporator coil  and before electric heat  will read coil leaving air  temperature      BLOWER RPM      Blower motor RPM value   STATIC PRESS      Inches of water   Displays static pressure that the fan coil is currently experiencing   Service   HEAT PUMP   AC STATUS   STAGE   HEAT   COOL        OFF  LOW  HIGH    Displays stage of heating or cooling that the Heat Pump AC is  delivering   DEFROST       NO  YES   Displays status of defrost mode if heat pump   AIRFLOW CFM       Indoor unit CFM measurement   LEAVING AIR TEMP     This sensor is NOT required  However  if LAT sensor is  connected to the Damper Control Module  sensor will read leaving  air temperature of the indo
37. on in heating  cooling  and how long  the unit has been powered     Service   TODAY   S DATE      This menu item allows the installer to enter the current date  It  is used for time date stamping of system faults  This should be  entered every time prior to viewing    LAST 10 SYSTEM  FAULTS    section     Service   MODEL   SERIAL NUMBERS    e This menu item allows the installer to view the model number  and serial number  if available  of all communicating pieces of  equipment in the system     Service   SERVICE PHONE NUMBER    This menu item allows the installer to enter a name and phone  number that the homeowner can call for future service of the  system  This name and phone number will appear to the home   owner whenever a service reminder pop up message is displayed   i e  Change Filter  etc      To edit   e Use Temp     button to move cursor left and right     Use Time     button to select numbers and letters     e Use Scroll button to move up and down between NAME and  NUMBER     OPERATIONAL INFORMATION  Zone Selection        Press top left ZONE button to select zones    Continuous Fan Operation   Pressing FAN button will scroll through the following    e AUTO   No fan operation except during equipment operation      LOW   Approximately 50  of High Speed operation      MED   Half way between High and Low speed operation       HIGH   Highest of either High Heating or High Cooling CFM   Five Minute Compressor Timeguard    This timer prevents compressor from starting unle
38. or unit     COIL TEMP  outdoor unit      Degrees F     Temperature of the outdoor unit coil  only available on 2 speed  communicating outdoor units      BLOWER RPM      RPM feedback from indoor motor   STATIC PRESS      Static pressure of indoor unit   Service   ZONING STATUS  ZONE STATUS     This screen will show each zone in the system with the corre   sponding damper position  POS   and CFM being delivered to  each zone  Damper position range from 0 to 15  O closed   15 open      Service   LAST 10 SYSTEM FAULTS    This screen will show last 10 faults that occurred throughout the  system  Each fault has the time and date incident recorded  Service  technician should enter current date in    TODAY   S DATE    menu  section BEFORE checking and logging the last 10 system faults   Each fault has a two letter acronym preceding the fault name to  identify which piece of equipment generated the fault  This fault  history can be cleared under Thermostat Setup  Reset Factory  Defaults       HP   heat pump   e AC   air conditioner     FN   furnace     FC   fan coil   e ZO   zoning   Service   RUN   FAULT HISTORY    The indoor unit and outdoor unit  if communicating  have the  following histories     NOTE  For Critical Fault Screens  see Troubleshooting section in  this document     Resettable Faults    e Fault counters for each piece of equipment that can be reset   Cycle Counters      Number of heat cool power cycles the unit has performed   Run Times     e Lifetime hours of operati
39. p down the door at the bottom of the control     2  Press the SCHEDULE button  which allows you to create  one schedule for the entire home     3  Press either the LEFT or RIGHT side button repeatedly  if  necessary  until    ALLDAYS    is displayed  The WAKE  time period will be highlighted     4  Using the TIME       button  set the start time for this time  period     5  Press the red HEAT button  Heating temperature will begin  flashing     6  Set the heating temperature using the TEMP       button     7  Press the blue COOL button  Cooling temperature will  begin flashing     8  Set the cooling temperature using the TEMP       button     9  Set the remaining periods by using the SCROLL button to  select    DAY        EVENING     and    SLEEP        10  To copy a zone  use SCROLL button to select    COPY      Select YES and copy this zone schedule to other zones  using NO or YES    11  Exit the scheduling mode by either closing the door or  pressing the SCHEDULE button     12  If changes are made  you will be asked to    SAVE  CHANGES YES NO       INSTALL   SERVICE MENUS       INSTALL SERVICE    EQUIPMENT SUMMARY  INSTALL   SETUP   CHECKOUT   SERVICE       SOFTWARE VERSION 1  SELECT gt            lt EXIT       A03200  Fig  20     INSTALL   SERVICE MENUS    The    INSTALL   SERVICE    menus contain a set of vital  information  This information enables the Installer or Service  person to view a summary of what has been installed  etc  This  information is notcovered in the 
40. s  heat pump will not operate below  selected temperature     HIGH COOL LATCH      NONE  default    e 80 110 deg F   Outside temperature above which only the high speed  of a  2 speed outdoor unit  will run when cooling    Setup   ZONING   DISABLE ZONING     No  default    e Yes    If Yes is selected  zoning is disabled and all dampers open  The  system will run unzoned using the Zone 1 sensor     ZONE OFFSETS      Zone Temperature Offsets  defaults   0  Range  5   to  5      This option allows actual temperature offset for each zone   allowing calibration  or deliberate mis calibration  of each sensor     AIRFLOW LIMITS   e Low     Medium      High  default      Maximum    Zone airflow limit  which is selectable for each zone  Low   Medium  and High allows a relative noise airflow relationship in a  zone  i e  comfort vs  noise   Maximum allows unlimited  noise airflow  i e  maximum airflow allowed      Setup   ACCESSORIES   FILTER TYPE      MEDIA  i e  TrueSense       e EAC   e MEDIA EAC  i e  TrueSense        CLEAN INTERVAL  30 to 180 days  of actual blower operation     Default   90     Interval at which the Clean Filter notification will turn on  Applies  to EAC filter selection only     HUMIDIFIER INSTALLED      NO     YES   If YES  indicates to the system whether a humidifier is installed  and enables humidification functions    CHANGE PAD INTERVAL  1 to 24 months of humidifier  operation  default 6 months     Interval at which the Change Humidify Pad notification will
41. ss it has been off  for at least 5 minutes  It can be defeated by simultaneously  pressing the Fan and Temp   buttons     Emergency Heat  for heat pump applications     To activate Emergency Heat  you must press and hold the HEAT  button for 3 seconds to activate     Keypad Lockout    Keypad can be locked by pressing    Fan    and    Zone    buttons at the  same time for 3 seconds  When keys are locked  a lock symbol will  appear in the upper left corner of screen  Follow same procedure  to unlock keypad     Heat and Cool LED    The Heat and Cool LEDs will pulsate during actual equipment  operation     Equipment Cycle Timer  adjustable 4 6 cycles per hour     This timer prevents the start of a heating or cooling cycle until 15   or 10  minutes after the last start of the same cycle  Its function is  to assure that the equipment is not cycled more than the selected  times per hour  This timer is adjustable from 4 to 6 cycles per hour   This timer is defeated for one cycle when the desired temperature  is manually changed  It can also be defeated for one cycle by  simultaneously pressing the Fan and Temp   buttons   Ten Minute Staging Timer   In multistage heating or cooling  this timer prevents any higher  stage from turning on until the preceding stage has been on for 10  minutes  This timer is defeated if temperature error is greater than  5  F  usually due to a large change in desired temperature      Three Minute Minimum On Time    In normal operation  when a stage turns o
42. tem  SCHEDULE VACATION  Schedule  amp  Vacation pre On Off Button  Program Buttons O O O O I lt  Basic  amp  Advanced  PROGRAM Berges Setup Buttons  Up Down q  Scroll Buttons 2                                            O O    Schedule Vacation 2 Basic Advanced A   to program to start end to set time  for all other  lt     Flip Down  temperature vacation humidity settings   schedule I Door       e Scroll  up  amp  down             A04038  Fig  11   Functional Overview  EQUIPMENT WIRING DIAGRAMS     See wiring diagrams Fig  12  13  and 14 for connecting the  Evolution Zone Control and Smart Sensors to the Damper Control  Module  More information regarding Damper Control set up and  wiring can be found in Damper Control Module Installation  Instructions     See wiring diagram Fig  12 which includes a variable speed indoor  communicating furnace or FE fan coil  with a 2 speed Puron     communicating outdoor unit  No additional OAT  outdoor air  temperature  sensor is required because the Evolution Zone  Control will use the temperature sensor inside the 2 speed unit     See wiring diagram Fig  13 for connecting a variable speed indoor  communicating furnace or FE fan coil with a 1 speed air condi   tioning unit  non communicating outdoor   An Outdoor Air Tem   perature  OAT  sensor may be installed  but is not required  at the  indoor furnace or fan coil OAT terminals  When OAT sensor is  applied  the Evolution System will provide enhanced system  features and benefits     See w
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
IMPACT User Manual - EcoMetrix Incorporated  1762-UM002 - Rockwell Automation  MGC900GB(PDF/775K)  MODE D`EMPLOI USER MANUAL  Kindle Paperwhite-Benutzerhandbuch 2. Ausgabe  1&1 WebHosting  En raison de son poids et afin de faciliter son téléchargement, le  TR 92E - TR 111E  M09 - action commercialeTER-TSC      Copyright © All rights reserved. 
   Failed to retrieve file