APC 1500 VA Power Supply User Manual

image

Contents

1. Page 15 4 0 Installation 4 5 Connect UPS to service and enable continued E 220 230 240 Vac versions The 600VA and 900VA UPSis not furnished with an input line cord Instead two output cords are supplied However in most installations it will not be necessary to purchase a UPS input power cord Simply swap the line cords from your equipment with the furnished outputcords Plugin the UPS using one of the swapped out equipment cords The UPS s input cord must be three conductor each 1 0 mm rated to 10 Amps In the event your equipment does not have a removable line cord the pro vided rewireable plug may be installed on the line cord Additional output cords and adapter plugs are available from your dealer and from the factory The 2000VA model UPS is furnished with an input line cord terminated with a continental European plug Where this plug is improper one of the supplied plug adapters is used Where none of the adapters are appropriate a three conductor 16Amp line cord terminated with an IEC 320 C19 coupler must be purchased contact you dealer The UPS may be configured to operate where 240 Vac 50 Hz service is provided When Option switch 2 is set to the on position the UPS s transfer and on battery output voltages are adjusted for proper operation on 240 Vac service See section 5 6 4 5 2 Enable UPS Move the UPS Enable switch to the on I position When shipped this switch
2. Systems for which interface kits are offered include Novell LAN Manager LAN Server LANtastic Banyan VINES and IBM AS 400 6 3 PowerChute Software PowerChute software provides complete data protection for most operating systems This software is a background process that monitors the UPS through a RS 232 serial port on the host PowerChute offers user notification of impending shutdown power event logging auto restart upon power return and UPS battery conservation features For selected operating systems PowerChute offers sophisticated power diagnostic and network power management features These include interactive battery testing sched uled server shutdowns reboots and battery testing detailed power quality logging and a remote real time graphical power status display showing UPS loading and battery conditions PowerChute is available for many platforms including Novell OS 2 AppleShare XENIX most UNIX based operating systems and DEC VAX VMS Caution Use only factory supplied or authorized UPS monitoring cables Page 26 6 0 UPS Monitoring 6 4 Computer interface port Thecomputerinterface portis diagramed below for your reference Those with technical abilities wishing to use this portin a special application should be aware of the following limitations and capabilities of the interface E Outputs at pins 3 5 and 6 are actually open collector outputs which must be pulled up to a common referenced supply no greater th
3. standby pushbutton See section 15Amp circuit Option UPS enable Site wiring breaker protects side interface port See section See section See section Computer switches switch fault light receptacles See section 6 0 5 6 4 5 4 7 poo 15Amp circuit breaker protects center receptacles NEMA 5 1 5 15R receptacles Battery pack coupler and UPS locking plate See section 4 4 Cooling fan Do not block NEMA 5 20P plug Page 10 Front view NEMA 5 15P L5 30P rewireable plugs supplied as alternate Rear view 3 0 Presentation 3 4 2000VA model 120 Vac version options The 1 2 and 4 wiring device options for the 120 Vac version 2000VA model UPS are shown below for reference These options allow simple plug in installation of the UPS where special service or load wiring devices are used Note There is no Option 3 Note Due to the difference in available capacity of the UPS and the maximum usable current ratings of the wiring devices UPSs furnished with 1 and 2 wiring device options are derated to 1500 VA o g MIME A Option 1 Option 2 Option 4 3 4 1 Option 1 UPSs have the following wiring devices 1 NEMA L5 20R twist lock receptacle 2 NEMA 5 15R duplex receptacles 1 NEM
4. 9 during an extended utility failure If the UPS illuminates the Replace Battery indicator perform the following procedures to be sure that the batteries need replacing 7 2 1 Use the UPS s Line voltage bar graph to check that the utility voltage is within a normalrange The UPS will charge the batteries ata slower rate when operated from very low input voltages Where low line voltages and frequent disturbances are common set the UPS s Option switch 1 to the on 1 position see section 5 0 7 2 2 Allow the UPS to charge the batteries for at least 16 hours following an extended utility failure 7 2 3 Recheck the UPS s batteries by conducting a battery test Press the I Test button to initiate the battery test 7 2 4 If the Replace Battery indicator does not illuminate following the battery test the batteries do not require replacement Extended storage without recharge or successive power outages can cause false indications 7 2 5 If the Replace Battery is illuminated following the battery test the batteries are worn and need to be replaced 7 2 6 Call the Customer Service phone number given on the cover of this manual to obtain information about battery replacement service or battery replacement kits Note Please see the battery cautions at the beginning of this section Page 33 7 0 Difficulty 7 3 Obtaining Service The troubleshooting chart in section 7 1 covers most of the difficulties that a user may encounter
5. Fairgrounds Road 4 rue Ste Claire Deville PO Box 278 Zac du Mandinet B timent Espace West Kingston Rhode Island LOGNES 02892 USA 77447 MARNE LA VALLEE C dex 2 FRANCE Note The troubleshooting chart in section 7 0 offers solutions for most of the difficulties you may encounter with this UPS Before calling the customer service number please have available your UPS s serial number see the label at the rear of the UPS Serial number Entire contents copyright O 1993 American Power Conversion All rights reserved reproduction in whole or in part without permission is prohibited Smart UPS PowerDoctor and PowerChute are registered trademarks of APC SNMP Adapter and SmartBoost are trademarks of APC All other trademarks are the property of their respective owners 990 7004 A 2 10 93
6. Wes WS VA OSE Jouu Y DA M 99 beduroO 14 T TF 402E UST MUSST TH IUC6I MPP 486 UTI WEST VA 00 1OJUOW VOA A G 98 beduroS tq yg Auger LSC MSCS ATE TNE JA YIU 4FL wee VA OSZ 1OJIUOUI VDA MXSGG7 SINAI TUISS MUZE IU6H MILT UTE WER WLM ULSI ce WEP VA 00Z JOJUOU VDA A 0C SdINgI 48 T Z 14 99 ICE WETS UP MOLE MIE METE MP7 WSS VA OSI AUOMPOUOU M 0 Z SA NAT TU TOOT T06 T08 0004 14009 00 2000 MODE UIST WSL VA 001 08 35 SOUDEN tu LL Y 0601 14696 M878 UZT USO JIP UE TIES 1496 VASL Puu IIDSV IeOIdAL u OEST AU Z ZET FTZ MUZOL UST6 FA MTI MESH JOE JOEL VA OS Zo 01 9 0 lle3id Q rd sduny yoN peo soynd uos jes dAL peo 21ndwoy peo p 1 1 JO 0S TU IST j i i UI abseupay ou 2B1eupsip Juanbasqns Spey Aa pede Jo 06 0 abueyras 4 L JO 49qUINN sj9pou yA006 VA009 Lee D m OI peo Sns19A aun uni pue au 9B1ey2al eoid L 6 6 D SAY G G GO GO G O OF UDY 4210245 Aqwoidhy s poo mf 10 149 s s sm sof awg uns aux Say TIS pe P O PZA F un seat 031d A1 s1 au asavyoas 344 pa vsu1 240 syovd K ayjvg ET uayM 2 duvx3 OT Jo 10101 v 200qu p2 0 su1 youd 127309 yova sof umnjo9 OL 21J1 Ul U9018 San va ay 07 UMN 09 Aappo snjd OT AY U1 U9018 sanjva y PPV j Z DoST 10 091d 1 240 sau uny FON si9atos o1dut s s beduro p 14 so 1407 149g TUTE az yez ayg qq I OT 490 470 VA 0002 uow VDA A XSGG Z Sd WAI 8 14 9 0 UTS ayzr dq ayge ayo
7. and 00 VA models en 8 AN A aE A de do donne 10 4 0 Installation ME 13 340 Operation suscita 18 6 0 UPS MONITOTING nn 26 7 9 DIIHEUNY une 28 Diner EE 29 Schwierigkeit Deutsch een ee a 30 Dificultad Espa ol ae een 31 8 0 Storing TNE UPS ann 35 9 0 SPECITICALIONS ssciviarirircica dude ebe Ne KENNEN Ge g Nee 36 Typical tute versus 1000 areas 38 Page 1 1 0 Introduction 1 1 Overview This equipment is a high performance line interactive uninterruptible power source UPS designed to provide clean reliable AC power to computer loads The UPS s line interactive circuit topology illustrated below offers excellent efficiency on line voltage regulation and fast utility fault response The UPS s DC to AC inverter is always connected to the output and when operating on line a portion of the inverter circuitry is put to work in reverse to continuously maintain optimum float charge on the battery The inverter circuitry also acts to protect the load from surges and EMI RFInoiseas partofanadvancedhybridsurge suppression and filtering network Aunique mode of operation named SmartBoost serves to regulate the load voltage by compensating for brownouts or sags This is accomplished without the need to draw power from the UPS s battery In anticipation of utility failure the UPS continuously monitors the line and prepares the inverter frequency for synchronous transfer of the load Upon occurrence of utility voltage failure such
8. asa blackout severe brownoutor an overvoltage condition the UPS transfers the load to power derived from the battery Transfer to the on battery mode of operation takes place typically within 2 milliseconds The inverter s output voltage waveshape is a low distortion sine wave Resynchronization and retransfer to on line operation is automatic upon recovery of the line voltage to within normal limits Transfer Surge amp Noise x Protection Switch Battery Charging normal O LJ Discharging power fail av N Output Line interactive UPS block diagram Ee Inverter Battery Charger Page 2 1 0 Introduction 1 2 SmartBoost SmartBoost allows continuous on line operation during extended brownouts or low line voltage conditions The UPS compensates for the reduced line voltage by boosting the load voltage to a value 12 above the input Reliability is enhanced because the limited battery capacity is saved for complete utility failures 1 3 Battery replacement indicators and test The UPS provides both visual and audible Replace Battery indications The indications are based on the result of an actual load test on the battery By exercising the UPS s battery during a startup test the UPS is able to detect a weak battery before it is put into service In applications where the UPS is not turned off daily or where the UPS is purposely left operating unattended the UPS automatically conducts this self
9. is in the off position to prevent accidental activation of the UPS The batteries will not appreciably discharge if this switch is left on Q Allow the UPS tocharge its battery for at least 16 hours before use The UPS recharges its battery whenever the utility voltage is normal and UPS Enable switch is on While the UPS was shipped from the factory with the batteries in a fully charged state the batteries may lose some charge during shipping and storage You may use the UPSimmediately without charging but the Low Battery indicator may illuminate and the UPS may have reduced backup time until the battery has had an opportunity to charge Page 16 4 0 Installation 4 6 Plug loads into UPS Plug all loads to be protected into the UPS Do not exceed the UPS s capacity as given in section 9 0 Once switched on the UPS will monitor and display the magnitude of the applied load Note Do not plug laser printers into this UPS Laser printers draw a considerable amount of power This will reduce the available backup time and in some cases will cause the UPS to signal an overload 4 7 Check Site Wiring Fault indicator 120 Vac versions Once loads are connected to the UPS and the UPS is turned on the Site Wiring Fault indicator at the UPS s rear panel should be checked It will illuminate when the UPS is plugged into an improperly wired wa
10. limits for on line operation 50 or 60 Hz 5 Lower input voltage limit for on line operation 90 Vac 173 Vac when set for operation at the nominal 240 Vac line the lower input voltage limit is increased to 180 Vac Upper input voltage limit for on line operation 132 Vac 253 Vac when set for operation at the nominal 240 Vac line the upper input voltage limit is increased to 264 Vac SmartBoost operation input voltage range 90 to 103 Vac 173 to 196 Vac when set for operation at the nominal 240 Vac line the SmartBoost input voltage range is increased to 180 to 204 Vac Transfer time 2 ms typical 4ms maximum Note that 1 ms is 0 001 seconds 9 3 Output characteristics Maximum load 600VA model 600 VA or 400 W 0 67 power factor Maximum load 900VA model 900 VA or 630 W 0 7 power factor Maximum load 2000VA model 120 Vac version 2000 VA or 1500 W 0 75 power factor with supplied NEMA L5 30P installed 1000 VA or 1000 W with supplied NEMA 5 15P installed 1500VA or 1500 W as supplied See section3 0 for maximum load ratings of models with wiring device options Maximum load 2000VA model 220 230 240 Vac versions 2000 VA or 1500 W 0 75 power factor On battery output voltage 115 Vac 225 Vac 5 The 220 230 240 Vac version may be set to provide a nominal 240 Vac see section 5 0 On battery frequency 50 or 60 Hz 0 1 Hz unless synchronized to mains frequency during utility brownout On battery waveshape
11. low distortion sinewave Protection overcurrent and short circuit protected latching shutdown upon overload Page 36 9 0 Specifications TAF Noise and surge suppression Surge energy rating one time 10 1000 us waveform 480 J Surge current capability one time 8 20 us waveform 6500 Amp peak maximum Surge response time 0 ns instantaneous normal mode lt 5 ns common mode Surge voltage let through lt 0 3 lt 2 of applied ANSI C62 41 Category A 6 kV test waveform Noise filter normal and common mode EMI RFI suppression 100 kHz to 10 MHz 9 5 Battery and charger Battery type spill proof maintenance free sealed lead calcium Typical battery life 3 to 6 years depends on number of discharge cycles and ambient temperature Typical recharge time see tables in section 9 9 9 6 Environment Operating temperature 0 C to 40 C 32 F to 104 F Storage temperature 15 C to 45 C 5 F to 113 F Operating and storage relative humidity 0 to 95 non condensing Operating elevation 0 to 3 000 m 10 000 ft Storage elevation 0 to 15 000 m 50 000 ft Electromagnetic immunity IEC 801 2 801 3 801 4 801 5 severity levels III or IV Audible noise 600VA 900VA models lt 50 dBA at 1 m 3 ft Audible noise 2000VA models lt 60 dBA at 1 m 3 ft 9 7 Physical Size 600VA 900 VA models Electronics and Battery pack enclosures each 9 1 Hx6 9 W x 17 8 D 23 1 x 17 5 x 45 2 cm Size 2000VA mo
12. set to react to such line voltage distortions by transferring the load immediately to on battery operation This affords maximum protection for all load types Where power quality is poor due to local cyclic heavy load switching or use of inexpensive fuel generators the UPS may be caused to transfer to on battery operation very often If the UPS is powering loads that are known to operate normally under such conditions such behavior is undesirable as battery capacity is being spent unnecessarily The user may set Option switch 1 to the on position in order to desensitize the UPS to rapid low amplitude line voltage fluctuations When this is done the UPS s upper transfer voltage is also increased by 3 for a total of 13 above the nominal input voltage This allows the UPS s battery charger to maintain maximum possible battery capacity saving it for gross utility failures Page 21 5 0 Operation 5 6 Option switches continued 5 6 2 Option switch 2 Option switch 2 controls different functions depending upon the UPS version type E 120 Vac version The UPS s factory setinput voltage limits for on line and SmartBoost operation are given in section 9 0 and are centered on the nominal input voltage of 120 Vac When Option switch 2 is set to the on position the upper and lower transfer voltages are lowered by 4 and are centered on a nominal input of 115 Vac This option is useful where the nominal input voltage is 110 to 115 V
13. test every 14 days 1 4 Remote interfaces The UPS provides a remote computer interface capable of full bidirectional RS 232 communications When combined with PowerDoctor UPS monitoring software and a serially connected local DOS PC power quality related events can be logged Power Chute plus offers all the features of PowerDoctor plus the ability to control orderly and unattended network or multi user computer system shutdown during an extended power outage Also available for the UPS is the SNMP Simple Network Management Protocol Adapter to provide load type independent remote monitoring and manage mentacross Ethernet or Token Ring based LANs or WANS capable of routing IP messages Using any standard Network Management System NMS and the SNMP Adapter the UPS becomes manageable through a single familiar interface from across your building to across the world 1 5 Extended capabilities Via the UPS s remote interface the user can access advanced monitoring power manage ment and operation customizing functions Monitored parameters include line voltage line frequency output power output voltage battery capacity battery voltage and internal temperature Power management functions include scheduled shutdown power failure simulation and remote turn off UPS functions that can be customized include the automatic self test and low battery warning intervals shut down turn off and turn on delay intervals transfer voltage utility fau
14. your RMA on the outside of the package The factory cannot accept any package without this marking M Return your UPS via insured prepaid carrier to the address on the rear of this booklet Page 34 8 0 Storing the UPS 8 1 Storage conditions The UPS should be covered and stored uprightina cool dry location The UPSshouldbe stored with its Battery packs in a fully charged state That is the indicated battery capacity should be 100 before the UPS is switched off for storage Once charged disconnect the Battery packs from each other and from the UPS 8 2 Extended storage To achieve expected run time following extended storage the UPS should be allowed to refresh its batteries every 6 months in environments where the ambient temperature is 15C to 30 C 5 F to 86 F For extended storage in environments where the ambient temperature is 30 to 45 C 86 F to 113 F the UPS should be allowed to refresh its batteries every 3 months Page 35 9 0 Specifications Note Where specifications ratings differ values for the 220 230 240 Vac versions are given in brackets 9 1 Input Nominal input voltage single phase 120 Vac 220 230 240 Vac Nominal input frequency 50 or 60 Hz internally selected by microprocessor Input protection 600VA 900VA model 14 Amp 12 Amp resettable circuit breaker Input protection 2000VA model 15 Amp resettable circuit breaker 9 2 Transfer characteristics Frequency
15. A L5 20P twist lock input plug 3 4 2 Option 2 UPSs have the following wiring devices 1 5 20R duplex receptacle 2 NEMA 5 15R duplex receptacles 1 NEMA 5 20P input plug 3 4 3 Option 4 UPSs have the following wiring devices 1 NEMA L5 30R twist lock receptacle 2 NEMA 5 15R duplex receptacles 1 NEMA L5 30P twist lock input plug Page 11 3 0 Presentation 3 5 2000VA model 220 230 240 Vac version Note 2000VA model Battery pack not shown Use only factory supplied or authorized Battery packs On Test Alarm UPS enable Computer Option disable pushbutton switch interface port switches Circuit See section 5 1 See section 4 5 See section 6 0 See section 5 6 breaker Display features See section ESS EE 16 Amp 5 0 IEC 320 inlet Power standby pushbutton IEC 320 See section output 5 1 couplers All couplers are protected by the UPS Battery pack coupler and UPS locking plate See section 4 4 Cooling fan Do not block J Front view Rear view Page 12 4 0 Installation 4 1 Receiving inspection Once the UPS has been removed from its shipping container it should be inspected for damage that may have occurred while in transit Immediately notify the carrier and place of purchase if any damage is found The packing materials are made from recyclable materials and sh
16. Arc AMERICAN POWER CONVERSION Smart UPS Models 600XL 900XL and 2000XL Le elle User s Manual Important safety instructions Please read this manual Veuillez lire ce manuel Bitte lesen Sie dieses Anleitungshandbuch Se ruega leer este manual de instrucciones This manual provides safety installation and operating instructions that will help you derive the fullest performance and service life that the UPS has to offer PLEASESAVE THIS MANUAL Itincludes important instructions for the safe use of this UPS and for obtaining factory service should the proper operation of the UPS come into question Down the road service or storage issues may arise and require reference to this manual CONSERVER CES INSTRUCTIONS Cette notice contient des instructions importantes concernant la s curit Radio Frequency Interference WARNING Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment NOTE This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can ra
17. UPS and operation of UPS monitoring software may be altered or amended without notice 5 7 1 Status reporting General When queried the UPS reports its electronics serial number version number date of manufacture and date of last battery replacement Operating status When queried the UPS reports its current operating status Reported modes includes on line on battery Smart Boost overloaded output low battery shut down and internal fault Test results When queried the UPS reports the stored results of the last automatic or manually initiated battery test The user may also test the operation of the UPS s visual and audible indicators 5 7 2 Monitoring O Line voltage and frequency The UPS continuously monitors the rms line voltage and the line frequency Transients lasting less than 0 5 seconds are not reported This information canbe logged using UPS monitoring software plotted using any spreadsheet application and used to identify transient power quality problems over extended peri ods Minimum and maximum line voltage The minimum and maximum line voltage is recorded to provide a snapshot of power quality over a user specified interval Transients lasting less than 0 5 seconds are not recorded Output power The UPS continuously monitors the power consumed by the load The value given is a percentage of the full load rating of the UPS This information can be logged using UPS monitoring software plotted usi
18. ac m 220 230 240 Vac version The UPS s factory set on battery output voltage and input voltage limits for on line and SmartBoost operation are appropriate for use in regions where the nominal line voltage is 220 to 230 Vac When Option switch 2 is set to the on l position the upper and lower transfer voltages are raised by 4 and are centered on a nominal input of 240 Vac In addition the on battery output voltage is increased to 240 Vac 5 6 3 Option switch 3 When Option switch 3 is set to the on I position the UPS s audible alarm is disabled for the first 30 seconds of an extended utility fault This function is useful where brief power interruptions are frequent and cause the alarm to become annoying 5 6 4 Option switch 4 When Option switch 4is set to the on position the UPS s low battery warning interval before shutdown due to battery capacity exhaustion is extended This function is useful where the UPS is protecting a computer system that requires a longer warning interval before power loss to perform a graceful shutdown Page 22 5 0 Operation 5 7 Extended capabilities The following sections briefly describe the UPS s extended capabilities These advanced functions are accessed by acomputer running optional PowerDoctor or PowerChute plus UPS monitoring software See the UPS monitoring software literature for more informa tion on the application of these functions Note The extended capabilities of the
19. an 40 Vdc The transistors are capable of a maximum non inductive load of 25 mAdc Use only Pin 4 as the common E The output at Pin 2 will generate a LO to HI RS 232 level upon transfer of the output load to power derived from the UPS s battery The pin is normally at a LO RS 232 level E The UPS will shut down when a HI RS 232 level sustained for 4 5 s is applied to Pin 1 The UPSresponds to this signal following a delay only during mains failures load is operating from the UPS s internal power source M An unregulated 24 Vdc appears at Pin 8 of the interface port whenever the UPS is powered The supply is limited to 40 mAdc maximum Normally Open Line Fail Signal Normally Open Low Battery Signal Normally Closed Line Fail Signal DB 9F pin out 6789 Common RS 232 Shut Down Input RS 232 Line Fail Output 12345 Unregulated 24 Vde Output Chassis Page 27 7 0 Difficulty Caution CAUTION E This Uninterruptible Power Source contains potentially hazardous voltages Do not attempt to disassemble the unit The unitcontains no user serviceable parts Repairs are performed only by factory trained service personnel M This Uninterruptible Power Source uses batteries The batteries will eventually become too weak to provide rated autonomous operation To obtain battery replacement or repair service please call the Customer Service telephone number written on the cover of this manual for infor
20. closure Battery pack k O SI w Front view Rear view Page 8 Site wiring fault light See section 4 7 Circuit breaker 10 Amp IEC 320 inlet NEMA 5 15R receptacles Battery pack coupler and UPS locking plate See section 4 4 Battery pack coupler and locking plate See section 4 4 Battery cables 2 0 Presentation 3 2 600VA and 900VA models 220 230 240 Vac version Note Use only factory supplied or authorized Battery packs On Test Alarm UPS enable Computer Option disable pushbutton switch interface port switches Circuit See section 5 1 See section 4 5 See section 6 0 See section 5 6 breaker Display features See section 5 0 10 Amp Power e 920 standby B Inlet pushbutton o O See section IEC 320 5 1 E C 8 E output couplers All couplers are Electronics protected by enclosure the UPS Battery pack coupler and Battery locking plate pack See section 4 4 Battery pack coupler and locking plate FAA See section 4 4 Battery O cables Front view Rear view Page 9 2 0 Presentation 3 3 2000VA model 120 Vac version Note 2000VA model Battery pack not shown Use only factory supplied or authorized Battery packs On Test Alarm disable pushbutton See section 5 1 Display features See section 5 0 Power
21. d alimentation permanente UPS Ne pas placer de r cipients contenant un liquide sur cet appareil ni proximit de celui ci M Pour viter une surchauffe de la source d alimentation permanente UPS conservez la l abri du soleil Ne pas installer proximit d appareils d gageant de la chaleur tels que radiateurs ou appareils de chauffage Page 5 2 0 Sicherheit Vorsicht VORSICHT BB Um die Gefahr eines elektrischen Schlages auf ein Minimum zu reduzieren die unterbrechungsfreie Stromversorgung vom Stromnetz trennen bevor ggf ein Com puter Schnittstellensignalkabel angeschlossen wird Das Netzkabel erstnach Herstellung aller Signalverbindungen wieder einstecken E Die unterbrechungsfreie Stromversorgung an eine geerdete zweipolige Dreiphasen Netzsteckdose anschlie en Die Steckdose mu mit einem geeigneten Abzweigschutz Sicherung oder Leistungsschalter verbunden sein Der Anschlu der unterbrechungsfreien Stromversorgung an einen anderen Steckdosentyp kann zu Stromschl gen f hren und gegen die rtlichen Vorschriften versto en M Diese unterbrechungsfreie Stromversorgung besitzt eine interne Energiequelle Batterie die vom Benutzer nicht abgeschaltet werden kann Der Ausgang kann eingeschaltet werden wenn das Ger t nicht an das Stromnetz angeschlossen ist E Umdieunterbrechungsfreie Stromversorgungim Notfall ordnungsgemafs abzuschalten den O Schalter an der R ckseite auf O Aus stellen und
22. das Netzkabel aus der Steckdose ziehen M Die unterbrechungsfreie Stromversorgung nicht an einem Ort aufstellen an dem sie mit Wasser oder berm ig hoher Luftfeuchtigkeit in Ber hrung kommen k nnte M Darauf achten da weder Wasser noch Fremdk rper in das Innere der unterbrechungsfreien Stromversorgung eindringen Keine Objekte die Fl ssigkeit enthalten auf oder neben die unterbrechungsfreie Stromversorgung stellen E Um ein Uberhitzen der unterbrechungsfreien Stromversorgung zu verhindern das Ger t vor direkter Sonneneinstrahlung fernhalten und nicht in der N he von w rmeabstrahlenden Haushaltsger ten z B Heizger t oder Herd aufstellen Page 6 2 0 Seguridad Atencion ATENCION M Para reducir el riesgo de descarga el ctrica desconecte de la red la Fuente de energ a ininterrumpible antes de instalar el cable de se alizaci n de interfaz de la computadora si se usa Vuelva a conectar el conductor flexible de alimentaci n solamente una vez efectuadas todas las interconexiones de se alizaci n E Conecte la Fuente de energ a ininterrumpible a un tomacorriente bipolar y trifilar con neutro de puesta a tierra El tomacorriente debe estar conectado a la protecci n de derivaci n apropiada ya sea un fusible o un disyuntor La conexi n a cualquier otro tipo de tomacorriente puede constituir peligro de descarga el ctrica y violar los c digos el ctricos locales E Esta Fuente de energ a in
23. del Electronics enclosures is 18 0 H x 6 9 W x 17 8 D 45 7 x 17 5 x 45 2 cm The Battery pack is 9 1 H x 6 9 W x 17 8 D 23 1 x 17 5 x 45 2 cm Weight 600VA 900VA models Electronics enclosure is 32 lbs 14 5 kg shipping weight is 37 lbs 16 8 kg The Battery pack is 62 lbs 28 1 kg shipping weightis 67 lbs 30 4 kg Weight 2000 VA model Electronics enclosure is 61 lbs 27 7 kg shipping weightis 68 lbs 30 8 kg The Battery pack is 64 lbs 29 0 kg shipping weight is 69 lbs 31 3 kg 9 8 Approvals Safety approvals UL per 1778 CSA per C22 2 TUV per IEC 950 EMC verification FCC DOC Class A verified EN55022 Class A verified Page 37 402 DoS7 10 paidh 240 sang uny luo potu VA006 241 4of 240 2d 1 pjog HI uaa d S n 00 am uns 031d 12 0N CUNA NA DNA eR Luut LO O TTL I be bes bes bey ca ua Lut Trou VI UUU J ynduucoruru za 00F SV WAI AU EL WLT U00L 8 MEL M6S Ip ME EC 1460 VA 008 SIOAIS AY G6 Z SA WAI DIT WTH MOTU ATO eg MOL MPs M0 IST MIT VA 002 siopuou M CC gge beduuoO 2 14007 FZ MOS MPT HTO Cs MPO WLP WOE WPT VA 009 sIoquou M agz gge beduo MEZZ 14961 USO MIEL MEI T6 MTL ITS Wee IST VA 0SS As O1duuas s beduuo5 mme OZ THOSE MOO MET HTO MeL WLS WLE WTI VA 00S sopuow 6I ME g 98p beduroO tq tree uer WOT MTL Merl STL W468 F9 NIP WET VA 0St 1Joltuour 61 ME 98 bedwoD tu STE Aur Ste MOT UELI Met OO MEL Mr UTT VA 00t OATS Y G6 Sd INgI 4 ZSE TUTE gg Mer AMC OO MSIL MPs
24. diate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interfer ence to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Shielded signaling cables must be used with this unit to ensure compliance with the Class A FCC limits This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications Le pr sent appareil num rique n emet pas de bruits radio lectriques d passant les limites applicables aux appareils num riques de la Class A prescrites dans le R glement sur le brouillage radio lectrique dicte par le minist re des Communications du Canada Hiermit wird bescheinigt dass der Smart UPS 600XL 900XL 2000XL Ununterbrechbare Stromversorgungs Ger t in Unereinstimmung mit den Bestimmungen der Vfg 1046 1984 funk entstort ist Der Deutschen Bundespost wurde das Inverkehrbringen diese Gerates angezeigt und die Berechtigung zur Uberprufung der Serie auf Einhaltung der Bestimmungen eingeraumt Table of contents 1 0 INTFOQUCIO Marcio 2 2 0 MOYA AA iaaa das di 4 e Ee esmers eaer EE E E E NE ERES 5 SIcHerheilli Denise its 6 segtiidad Espa ol nennen 7 3 0 Presentation ui aida 8 600VA
25. e UT M6 1 MET 1480 UC VA 0091 uow VDA A 98 bedwod p 19 8 0 EZ uso me mer auzr qqpg qz qq 61 mer men VA 0021 s194198 oxdur ls s beduro z 14 oT 1406 1908 OZ 1409 rs yzr qee qyz MUST 1490 WAOOOL XPAODIN Odd TOL 406 1464 1489 14 z s yzr ULE Ze Aq Zl aq Z0 yayndurostutur 07Q 00F SV WAI ayg l Dot 1468 14 2 1469 ICS TH MOS 461 1480 SIOAIOS AH Op Z Sd WAI 7 US EL AYUS IL UTOL 1488 1474 1409 Zh USE TZ 1460 s opuou M 98 beduroO 7 I4 991 MY SPL UST IUTOL 1428 UTZ USS 1407 1497 q TI 194198 o1duas s beduro Y E07 IZZI u ZSI ygz ayeor UPS 1499 Ugh MIE PT IOJUOUI el M 98 beduroo YY EST MU ezel UTS 14 Tol au L ET IU LOL 1408 1489 Ze YLT 19AJOS OIL G6 Z Sd NAI TY 87 14 T SZ au g 1Z IU FSI 14 0 S1 AU ZIT 1468 1499 ZP 1461 zopuow YODA M 98 beduro I4 LTS IY S8Z UST ayz zlayrz laygerlayrtor yez yzr aq ZZ 1OJJUOUI VOA M 9G 98 beduroo ay 8 S MUZE 14987 MY HZ 14 CSOT AUTOT USIT UPS WES SZ IOJUOUW YODA M XSGG Sd WAI MTP 14 OZE I4 67 1887 14 THT UT 6L Zo 01 9 0 lIP3Id Q rd sduwvy 110 1 peo7 s1ndwoy peo s1ndwos jes dA 2b1ey y olu 2B1eupsip yuanbasqns sappe sped 191189 Amede jo 06 01 2B1ey3a1 Isn d oi ol 6 8 Z 9 S t 4 L JO 19qUINN SISPOUI yA0007Z Z 6 6 peo sns1an aun uni pue aun 9bB1eya
26. ed Indicators on front panel flash UPS has been shut down by in a marquee fashion All indicators are illuminated and UPS emits constant tone Site wiring fault light is illuminated UPS operates normally Low battery light is iluminated and on line light is extinguished Replace battery light is illuminated computer software Internal UPS fault Building wiring error such as missing ground or hot neutral reversal UPS is shut down and battery is discharged due to extended power failure Weak battery loads 2 Reduce the UPS s load by unplugging equipment and reset the circuit breaker press button on rear panel 3 Check outlet with a table lamp If very dim have utility voltage checked by an electrician 1 Reduce the UPS s load by unplugging equipment and reset the circuit breaker press button on rear panel 2 Test the input voltage with UPS s Line voltage bar graph see section 5 0 Inexpensive fuel powered generators can cause distorted line voltages set Option switch 1 to the on 1 position The UPS is protecting your computer equipment from momentary sags or swells Set Option switches 1 and 2 to match input voltage range Alternatively set Option switc 3 to the on position see section 5 0 1 The UPS s batteries require recharging following an extended outage The batteries will wear faster when put into service often and when operating at elevated temperat
27. he Replace Battery indicator means that the automatic battery test has found that the battery is weak and requires replacement The indicator is extinguished following a successful battery test Page 18 5 0 Operation 5 2 Battery capacity bar graph 100 80 60 40 20 Low battery when blinking The battery capacity bar graph continuously displays the state of battery charge In the above example the display shows that 100 of rated battery capacity is available Where power quality is fair the UPS will be able to maintain the battery at 100 of rated capacity In the event of an extended utility failure the capacity shown will decrease at a rate dependent on the load drawn from the UPS Large computer loads will cause the battery capacity indication to fall at a faster rate When low battery conditions are reached the bottom most bar will blink Once normal line voltages are restored the UPS will recharge the battery and the capacity bar graph will show an increasing number of illuminated bars 5 3 Output power bar graph Overload 85 67 50 33 17 The output power bar graph displays the power drawn from the UPS as a percentage of the UPS s full rated capacity This example shows that the load equipment is drawing between 67 and 85 of the UPS s rated capacity If this were a 1250VA UPS running a computer load then the above would correspond to between 840 VA and 1060 VA 590 Watts and 740 Watts at 0 7 powe
28. hes must beset to the on position Functionality of the option switches is not lost as all such functions are duplicated by the UPS monitoring software Once any of the Option switches are returned to the off position functionality governed by the position of all Option switches is also restored Battery test operation The battery test can be customized to automatically run upon startup upon startup and once every 7 days thereafter upon startup and once every 14 days thereafter or never The UPS s battery test operation default setting is upon start and every 14 days thereafter O Transfer voltage The UPS s upper and lower transfer voltages can be customized over a wide range Default settings are given in section 9 0 O On battery output voltage 220 230 240 Vac versions only The UPS s on battery Page 24 5 0 Operation 5 7 Extended capabilities continued output voltage may be setto a nominal 220 225 230 or 240 Vac The UPS s default setting is 225 Vac O Utility failure sensitivity The UPS s sensitivity to line voltage distortions may be customized to allow use of the UPS in noisy electrical environments or with fuel powered generators High medium and low sensitivity settings may be chosen The high setting provides the best protection from all utility voltage vagaries The medium setting is selected where rapid low amplitude line voltage fluctuations occur frequently as the result of motor load switch
29. ing in air conditioners elevators etc The low setting is selected when the UPS is operated from an inexpensive fuel powered generator The UPS s utility failure sensitivity default setting is high O Audible alarm operation The UPS s audible alarm beeps four times every 30 seconds in response to failed utility conditions The alarm beeps continuously when low battery conditions are reached This is the default operation Audible alarm operation may be customized such that an indication in response to utility failure is delayed by 30 seconds silenced until low battery conditions are reached or muted during both utility failure and low battery conditions Minimum battery capacity to restart The UPS may be customized so that it will not restart upon restoration of the utility until the battery has been recharged to within 0 10 25 or 90 of full capacity This function eliminates unexpectedly short run times when repetitive utility failures occur The UPS s minimum battery capacity to restart default setting is 0 Shut down turn off delay The UPS s shut down or turn off delay interval may be customized to 20 180 300 or 600 seconds The UPS s shut down delay default setting is 20 seconds Extension of the shut delay is useful where the time between issuance of the UPS shut down command and actual completion of the operating system shutdown routine is longer than 20 seconds O Turn on delay The UPS s turn on delay may be c
30. interrumpible tiene una fuente de energ a interna la bater a queno puedeser desactivada por el usuario La salida puede tener corriente aun cuando la unidad no se encuentre conectada al suministro de red M Para desactivar correctamente la Fuente de energ a ininterrumpible en una situaci n de emergencia coloque el interruptor I O del panel posterior en la posici n O Off desconectado y desconecte de la red el conductor flexible de alimentaci n M No instale la Fuente de energ a ininterrumpible en lugares donde haya agua o humedad excesiva M No deje que en la Fuente de energ a ininterrumpible entre agua ni ning n objeto extra o No ponga objetos con l quidos encima de la unidad ni cerca de ella M Parareducirelriesgo de sobrecalentamiento no exponga la unidad alos rayos directos del sol ni la instale cerca de artefactos que emiten calor como estufas o cocinas Page 7 2 0 Presentation 3 1 600VA and 900VA models 120 Vac version Note Llse only factory supplied or authorized Battery packs Option UPS enable On Test Alarm Computer switches switch disable pushbutton interface port See section See section See section 5 1 See section 6 0 5 6 4 5 Display features See section Ed res e 5 0 Power standby S pushbutton See section ES 2 d 200 Electronics 1 Gu 1 O D o en
31. ions doivent tre effectu es par du personnel qualifi et agr par le constructeur E Cette source d alimentation permanente UPS contient des accumulateurs Ces accumulateurs deviendrontun jour trop faibles pour pouvoir assurer un fonctionnement autonome correct Pour toute r paration ou remplacement des accumulateurs composez le num ro du Service la client le inscrit sur la couverture de ce manuel afin d obtenir les coordonn es du Centre de Service le plus proche IN oY M Les accumulateurs contenus dans cette source d alimentation sont recyclables L elimination des batteries est reglement e Consulter les codes locaux cet effet Ils contiennent du plomb et repr sentent donc un risque pour l homme et pour l environnement si les r gles de mise au rebut ne sont pas respect es Veuillez retournez l unite un Centre de Service agr lorsque vous d sirerez remplacer ou vous d barrasser des accumulateurs usag s M ATTENTION Pour le remplacement utiliser le m me nombre de batteries du mod le suivant accumulateur au plomb M ATTENTION Une batterie peut pr senter un risque de choc electrique de br lure par transfert d nergie Suivre les pr cautions qui s imposent Page 29 7 0 Schwierigkeit Vorsicht VORSICHT M Im Inneren dieser unterbrechungsfreien Stromversorgung herrschen potentiell gef hrliche Spannungen Nicht versuchen das Ger t zu ffnen Es enth lt keine vom Benut
32. l eoid L 6 6 DECLARATION OF CONFORMITY Application of Council Directive s 89 336 EEC Standard s to which Conformity is Declared EN55022 EN50082 1 Manufacturer s Name AMERICAN POWER CONVERSION Manufacturer s Address 132 FAIRGROUNDS ROAD WEST KINGSTON RI 02892 USA Importer s Name Importer s Address Type of Equipment UNINTERRUPTIBLE POWER SOURCE Model No SMART UPS 600XL 900XL 2000XL INCLUDING OPTIONS 1 2 3 4 Serial Number 5930100001 5931299999 S940100001 S941299999 Year of Manufacture 1993 1994 I the undersigned hereby declare that the equipment specified above conforms to the above Directives s Place BILLERICA MA USA Signature Date 11 1 93 Joseph Pomata Full name Regulatory Compliance Engineer Position Page 40 Limited Warranty American Power Conversion APC warrants its products to be free from defects in materials and workmanship for a period oftwo years from the date of purchase Its obligation under this warranty is limited to repairing or replacing at its own sole option any such defective products To obtain service under warranty you must obtain a Returned Material Authoriza tion RMA number from APC or an APC service center Products must be returned to APC or an APC service center with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase This warranty doe
33. ll outlet Wiring faults detected include missing ground hot neutral polarity reversal and overloaded neutral circuit lt SITE m WIRING IN FAUL Note If the UPS indicates a site wiring fault a qualified electrician should be summoned to correct the building wiring 4 8 Switch on load equipment If load equipment switches are left on the UPS sl Testpushbutton can be used as master system on off switch 4 9 Switch on the UPS The UPS and your loads will become energized when the l Test pushbutton is held pressed for a second Once powered the UPS will initiate a battery test During the test the UPS will operate the load from power derived from the battery This test function ensures that the UPS is working properly and that its battery does not require replacement In the event the batteries are too weak to support the load during the test the UPS will immediately return to on line operation the load will not be affected The test is completed when the On Line indicator ceases to blink Note If the red Load indicator is illuminated the UPS is overloaded Unplug equipment that does not require backing up such as a printer and restart the UPS If the Replace Battery indicator illuminates recharge the UPS overnight and retest Page 17 5 0 Operation 5 1 Display features On Battery On Test Alarm SmartBoost On Line indicator disable pushbutton indicator Replace dE Battery indicator Sado indicator Po
34. lt sensitivity and activation of the audible alarm Page 3 2 0 Safety Caution CAUTION M To reducethe risk of electric shock disconnect the Uninterruptible Power Source from the mains before installing computer interface signal cable when used Reconnect the power cord only after all signalling interconnections have been made E Connect the Uninterruptible Power Source toa two pole three wire grounding mains receptacle The receptacle must be connected to appropriate branch protection fuse or circuit breaker Connection to any other type of receptacle may result in a shock hazard and may violate local electrical codes M This Uninterruptible Power Source has an internal energy source the battery that cannot be de energized by the user The output may be energized when the unit is not connected to a mains supply E To properly deenergize the Uninterruptible Power Source in an emergency move the rear panel I O switch to the O off position and disconnect the power cord from the mains E Avoid installing the Uninterruptible Power Source in locations where there is water or excessive humidity M Do not allow water or any foreign object to get inside the Uninterruptible Power Source Do not put objects containing liquid on or near the unit M Toreduce the risk of overheating the Uninterruptible PowerSource avoid exposing the unit to the direct rays of the sun Avoid installing the unit near heat emitting appliance
35. mation on the Service Center nearest you IN CS M The batteries used by this Uninterruptible Power Source are recyclable Proper disposal of the batteries is required The batteries contain lead and pose a hazard to the environment and human health if not disposed of properly Please refer to local codes for proper disposal requirements or return the unit to a factory authorized Service Center for battery replacement or disposal E Battery replacement should be performed or supervised by personnel familiar with the danger of batteries and the required precautions Keep unauthorized personnel away from batteries When replacing batteries use the same number and type of sealed lead acid batteries as were originally contained in your UPS M CAUTION Do not dispose of batteries in a fire The batteries may explode M CAUTION Do not open or mutilate batteries They contain an electrolyte which is toxic and harmful to the skin and eyes M CAUTION A battery can present a risk of electrical shock and high short circuit current When replacing batteries wrist watches and jewelry such as rings should be removed Use tools with insulated handles Page 28 7 0 Difficult Attention ATTENTIONI M Cette source d alimentation permanente UPS contient des circuits haute tension pr sentant un danger Ne jamais essayer de le d monter Il n y a aucun composant qui puisse tre r par par l utilisateur Toutes les r parat
36. mplazo de bater as o servicio de reparaciones se ruega llamar al n mero telef nico deAtenci n a los Clientes indicado en la tapa de este manual y averiguar el Centro de Servicio m s cercano IN oY M Las bater as que se encuentran en esta Fuente de energ a ininterrumpible son reciclables Las baterias contienen plomo y constituyen un peligro para el medio ambiente y para la salud de las personas si no se las desechan como corresponde Se ruega devolver la unidad a un Centro de Servicio autorizado por la fabrica para el reemplazo o la eliminaci n de las bater as Page 31 7 0 Difficulty 7 1 Troubleshooting chart PROBLEM UPS will not turn on UPS operates on battery even though normal line voltage is thought to exist UPS beeps occasionally UPS beeps more than once or twice an hour UPS does not provide expected back up time POSSIBLE CAUSE ACTION TO TAKE 1 UPS Enable switch is in the off 1 Turn on the rear panel UPS Enable switch position or front panel switch notPress front panel switch to power UPS and pressed 2 UPS s input circuit breaker is tripped button is extended 3 Very low utility voltage or dead outlet 1 UPS s input circuit breaker is tripped button is extended 2 Very high low or badly distorted line voltage This is normal Chronically high or distorted line voltage 1 UPS s battery is weak due to recent utility outage or wear 2 UPS is overload
37. ng any spreadsheet application and used to determine load usage over extended periods Page 23 5 0 Operation 5 7 Extended capabilities continued O Output voltage internal temperature battery voltage battery capacity The UPS continuously monitors the rms output voltage internal temperature in degrees Celsius battery voltage and the remaining battery capacity as a percentage of the fully charged condition This information is valuable for troubleshooting purposes 5 7 3 Power management O Shut down While operating on battery the UPS may be directed to shut down following a user set delay Controlled shut down of the UPS conserves battery capacity and extends battery life because the UPS is not allowed to run until all battery capacity isexhausted O Shut down with delayed restart The UPS may be directed to shut down in any mode following a user set delay then restart after another user set delay The restart delay may be used to stagger power up multiple network servers protected by multiple UPSs O Simulate power failure The UPS may be directed to simulate a power failure by briefly operating on battery This function is useful for test purposes O Turn off The UPS may be directed to turn offimmediately or following a user settable delay 5 7 4 Operation customizing Alteration of many UPS operations is possible to suit specific applications In order to use the customizing features of the UPS all Option switc
38. ould be saved for reuse or disposed of properly 4 2 Placement The UPS may be installed in any protected environment The location should provide adequate air flow around the unit in an atmosphere free from excessive dust Do not operate the UPS in an environment where the ambient temperature or humidity is outside the limits given in the Specifications section of this manual el 4 3 Install bracket 2000VA models 220 230 240 Vac version The 220 230 240 Vac version 2000VA model UPS is supplied with a bracket that serves to stabilize the UPS and Battery packs other models and versions do not require this bracket To install the bracket follow the instructions listed below 4 3 1 Position the UPS and Battery pack enclosures as shown in the illustration below and remove the enclosure screws indicated 4 3 2 Place bracket between the UPS and Battery pack and attach using the supplied screws 4 0 Installation 4 4 Connect battery pack Follow the instructions listed below to install and lock the battery pack coupler Note Use only factory supplied or authorized battery packs 4 4 1 Remove the battery coupler clamp from the Electronics enclosure 4 4 2 Turn the battery coupler clamp and refasten loosely at one side 4 4 3 Mate the battery pack coupler to the electronics enclosure 4 4 4 Fasten remaining side of batter
39. r factor This is a typical installation When the UPS is loaded such that five bars are illuminated thoroughly test your complete system to be sure the UPS will not become overloaded A thorough test includes running backup tape drives disk drives etc If the UPS becomes overloaded the overload bar will illuminate and the UPS will sound an alarm Page 19 5 0 Operation 5 4 Line voltage bar graph Bar increments versus version type 220 230 120 Vac 208 Vac 240 Vac 130 237 260 123 225 246 116 212 232 110 200 220 104 187 208 98 175 196 The line voltage bar graph displays the UPS s input voltage in discrete steps Line voltage is displayed when thel Test pushbutton is pressed and held The example above shows that the UPS s input line voltage is between 116 and 123 Vac 120 Vac version UPS see table for values for other versions Ifno bars are illuminated and the UPS is plugged into a known working wall outlet the line voltage is extremely low Low input voltage could be a result of an overloaded branch circuit a misadjusted service pole transformer or intentional local service brownout The UPS will compensate for this problem by boosting the load voltage supplied to your computer equipment If all six bars are illuminated the line voltage is high and should be checked by a qualified electrician 5 5 Audible alarm The UPS contains a beeper that emits sound through the ventilation openings E
40. s APC does not recommend the use of any of its products in direct patient care APC will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to APC that a the risks of injury or damage have been minimized b the customer assumes all such risks and c the liability of American Power Conversion is adequately protected under the circumstances Examples of devices considered to be life support devices are neonatal oxygen analyzers nerve stimulators whether used for anesthesia pain relief or other purposes autotransfusion devices blood pumps defibrillators arrhythmia detectors and alarms pacemakers hemodialysis systems peritoneal dialysis systems neonatal ventilator incubators ventilators for both adults and infants anesthesia ventilators and infusion pumps as well as any other devices designated as critical by the U S FDA Hospital grade wiring devices and leakage current may be ordered as options on many APC UPS systems APC does not claim that units with this modification are certified or listed as Hospital Grade by APC or any other organization Therefore these units do not meet the requirements for use in direct patient care AMERICAN POWER CONVERSION ZS PHONE Z PHONE 800 800 4272 in USA Canada 33 1 64 62 59 00 in Europe 401 789 5735 world wide 401 789 5735 world wide 2 MAILING DT MAILING American Power Conversion American Power Conversion 132
41. s such as a room heater or stove Page 4 2 0 S curit Attention ATTENTION M Pour r duire le risque d lectrocution d branchez la prise principale de la source d alimentation permanente Uninterruptible Power Source avant d installer le c ble d interface allantal ordinateur si utilis Nerebranchez le bloc d alimentation ou apres avoir effectu toutes les connections M Branchez la source d alimentation permanente UPS dans une prise de courant 3 d rivations deux p les et la terre Cette prise doit tre munie d une protection ad quate fusible ou coupe circuit Le branchement dans tout autre genre de prise pourrait entra ner un risque d lectrocution et peut constituer une infraction la r glementation locale concernant les installations lectriques E Cette source d alimentation permanente UPS est munie d une source d nergie interne accumulateur quine peut pas tre d sactiv e par l utilisateur La prise de sortie peut donc tre sous tension m me lorsque l appareil n est pas branch M En cas d urgence pour d sactiver correctement la source d alimentation permanente UPS poussez l interrupteur du panneau arri re sur la positionO Off et d branchez le cordon d alimentation principal E Ne pas installer la source d alimentation permanente UPS dans un endroit o il y a de l eau ou une humidit excessive E Nepaslaisser de l eau ou tout objet p n trer dans la source
42. s not apply to equipment which has been damaged by accident negligence or mis application or has been altered or modified in any way This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase EXCEPT AS PROVIDED HEREIN AMERICAN POWER CONVERSION MAKES NO WAR RANTIES EXPRESS OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Some states do not permit limitation or exclusion of implied warranties therefore the aforesaid limitation s or exclusion s may not apply to the purchaser EXCEPT AS PROVIDED ABOVE IN NO EVENT WILL APC BE LIABLE FOR DIRECT INDIRECT SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAM AGE Specifically APC is not liable for any costs such as lost profits or revenue loss of equipment loss of use of equipment loss of software loss of data costs of substitutes claims by third parties or otherwise This warranty gives you specific legal rights and you may also have other rights which vary from state to state Life support policy As a general policy American Power Conversion APC does not recommend the use of any of its products in life support applications where failure or malfunction of the APC product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or effectivenes
43. under conditions other than a failure of the UPS itself For problems not covered in the chart the procedures outlined below should be followed If your UPS should require service M See the troubleshooting chart and eliminate the obvious A tripped UPS circuit breaker is the most common problem encountered and is user resettable once exces sive loads are unplugged from the UPS E If the circuit breaker is OK note your UPS model serial number and date of purchase Contact the Customer Service Department at the phone number given on the cover of this booklet E Be prepared to provide a description of the problem A technician will help you solve the problem over the phone if possible or will give you a Return MaterialAuthorization Number RMA E If the UPS is within the warranty period repairs will be performed free of charge If it is not within the warranty period there will be a charge for repair M Pack the UPS in its original packaging If you no longer have the original shipping materials ask the technician about obtaining a new set Itis very important that you pack the UPS properly to avoid damage in transit Never use styrofoam beads for packaging the UPS because it will settle through beads and become damaged Damages sustained in transit are not covered under warranty Enclose a letter in the package with your name RMA address copy of sales receipt description of trouble phone number and check if necessary E Mark
44. ures 2 Check load using UPS s Output power bar graph see section 5 0 Unplug non critical equipment such as printers UPS will restart when AC power retums Do not attempt to use UPS Turn off UPS and have it serviced immediately A qualified electrician should be summoned to correct the building wiring UPS will return to normal operation when power is restored and battery has charged sufficiently Allow the batteries to recharge for at least 16 hours If the problem persists after recharging the batteries should be replaced 7 0 Difficulty 7 2 Battery replacement check You can expect to receive 3 to 6 years of service life from the UPS s Battery packs when installed in a cool dry location Battery life is shortened when operated in an environ ment where the ambient temperature is normally above 30C 86 P The UPS automatically performs a battery test upon start up and if left operating every 14 days thereafter This test actually loads the battery for a brief time and will detect a weak battery before it is put into service during a power failure If the battery is too weak to support the load during this test the UPS will instantly return to on line operation The UPS will illuminate the Replace Battery indicator when it is detected that the battery packs can no longer sustain sufficient charge This means that the UPS would be unable to provide power for longer than half the normal interval see section 9
45. ustomized to 0 60 180 or 300 seconds The UPS s turn on delay default setting is 0 seconds Page 25 6 0 UPS Monitoring 6 1 Overview AUPSsystem alone provides excellent protection from brief power problems However during an extended power outage an unattended computer system will eventually shut down dueto battery capacity exhaustion To prevent data corruption when the UPS shuts down the computer must be informed by the UPS of impending shut down and take appropriate file saving measures This important function is called UPS monitoring The UPS s computer interface port is the means by which your UPS communicates with acomputer system Some computer operating systems have built in UPS monitoring These systems require various hardware interfaces Interface kits for all operating systems that support UPS monitoring are available from your dealer In addition your dealer also offers Power Chute software which enhances such built in UPS monitoring Versions of PowerChute are available which add the UPS monitoring function to the many operating systems which do not inherently provide UPS monitoring 6 2 Interface Kits A series of interface kits is available for operating systems that provide UPS monitoring Each interface kit includes the special interface cable required to convert status signals from the UPS into signals which individual operating systems recognize Each kit includes all necessary installation instructions
46. vents that cause the beeper to sound are listed below 5 5 1 On battery operation The UPS emits four short beeps every 30 seconds following failure of the utility The audible alarm is silenced until the next utility failure when the I Test pushbutton is pressed 5 5 2 Low battery During an extended utility failure the UPS will eventually emit continuous beeps to indicate that the UPS will soon shut down due to battery capacity exhaustion The low battery warning cannot be muted Page 20 5 0 Operation 5 5 3 Replace battery SSS In the event the UPS s battery fails a battery test the UPS will emit chirps for a period of 1 minute If the UPS is left operating while in this condition the UPS will emits chirps once every 5 hours until a successful battery test is completed 5 5 4 Overload The UPS will emita loud sustained tone when overloaded When an overload is applied while on line the alarm will sound until the overload is removed If the overload is applied while on battery the alarm will sound until the UPS Enable control is switched off 5 6 Option switches A W TN En on factory settings shown Se Note Option switches may be thrown at any time and take effect immediately O off 5 6 1 Option switch 1 The UPS contains utility fault detection circuitry that is extremely sensitive to line voltage distortions including spikes notches sudden dips and swells The UPS is factory
47. wer bar graph y capacity amp line voltage bar graph Power standby pushbutton 5 1 1 On Test Alarm disable pushbutton The On Test Alarm disable pushbutton is used to control activation of the UPS and to energize the load Once the UPS is energized pressing the button will initiate a battery test This will force the UPS to operate on battery for a brief time during which the UPS determines the strength of the battery When the UPS is on battery this button may be pressed to silence the utility failure audible warning 5 1 2 Power standby pushbutton When held pressed for a second this control will deenergize the UPS and all protected loads However operation of the UPS s battery charger is unaffected by this control 5 1 3 On Line indicator Illumination of the On Line indicator means that the load is being supplied conditioned power derived from the utility service The indicator blinks during the battery test 5 1 4 On Battery indicator Illumination of the On Battery indicator means that load has been transferred to power derived from the UPS s battery and that utility voltage is not within normal limits 5 1 5 Smart Boost indicator Illumination of SmartBoost indicator means that the SmartBoost circuitry has been engaged to compensate for unacceptably low line voltage The UPS is capable of operating in this mode continuously without draining charge from the battery 5 1 6 Replace Battery indicator Illumination of t
48. y coupler clamp to lock in place Remove clamp Turn clamp Mate couplers Secure clamp LaF gt es 4 4 5 Where more than one Battery pack is to be installed connect additional Battery packs as shown in the following illustrations Do not stack the UPS and Battery packs unless a suitable means of maintaining stability is provided gt 12 gt 1 30 5 cm 2 5 cm Note Leave adequate space for cooling m g om O O ORE OO Typical GOOVA 900VA model multiple Battery pack installation 120 Vac ver sion shown Note 10 pack per UPS limit Page 14 4 0 Installation 4 4 Connect battery pack continued gt 12 gt 1 30 5 cm 2 5 cm Note Leave adequate space for cooling Typical 2000VA model multiple Battery pack installation 120 Vac version shown Note The number of 2000VA model Battery packs that may be connected is limited only by the recharge time desired see section 9 9 4 5 Connect UPS to service and enable 4 5 1 Connect UPS to service E 120 Vac versions Plug the UPS into atwo pole three wire grounding receptacle only Avoid the use of extension cords and adapter plugs
49. zer reparierbaren Teile Reparaturen d rfen nur von ausgebildetem Kundendienstpersonal durchgef hrt werden M Diese unterbrechungsfreie Stromversorgung enth lt Batterien die nach einer bestimmten Zeit so schwach werden da der autonome Nennbetrieb nicht mehr gew hrleistet ist Wenn die Batterien ausgewechselt werden m ssen oder Reparaturen f llig sind die auf der Umschlagseite dieser Gebrauchsanweisung angegebene Kundendienst Telefonnummer anrufen Dort teilt man Ihnen mit welches Kundendienstzentrum f r Sie zust ndig ist IN Ac M Die Batterien in dieser unterbrechungsfreien Stromversorgung sind wiederverwertbar Sie sind bleihaltig und stellen eine Gefahr f r die Umwelt und die Gesundheit dar wenn sie nicht ordnungsgem entsorgt werden Das Ger t an ein vom Werk autorisiertes Kundendienstzentrum einsenden um die Batterien auswechseln oder entsorgen zu lassen Page 30 7 0 Dificultad Cuidado CUIDADO M Esta Fuente de energ a ininterrumpible contiene niveles de voltaje peligrosos en potencia No intente desarmar la unidad pues no contiene piezas que puedan ser reparadas por el usuario Las reparaciones deben efectuarse nicamente por parte del personal de mantenimiento capacitado en la f brica M Esta Fuente de energ a ininterrumpible contiene bater as Con el tiempo las bater as se gastan demasiado para poder sustentar el funcionamiento aut nomo a la capacidad nominal Para solicitar el ree

Download Pdf Manuals

image

Related Search

Related Contents

Retail Tablet XXL 3G User Manual ( 1.75 MB )  Free Molecular Heat Transfer Programs for Setup and Dynamic  Documents Released  User Manual  Sony ICF-CD555TV Marketing Specifications  Hidrosembradora  Trendnet TEW-671BR router  LinkerIIa Manual version 1.27 - Ics  020-102035-01_LIT GUID START CP2208.book  