Home

American Power Conversion 100 VAC Power Supply User Manual

image

Contents

1. Facing the front of the UPS locate the battery cable in the S center of the unit and remove the tape to expose the cable dd o Lala connector O 00 2 Locate the UPS battery connector O which is to the right of the battery tray O and recessed Connect the battery cable connector to the UPS connector Press firmly to ensure that the connection is tight You will hear a snap when the connector is properly seated Also as a visual indication the back of the connector should be recessed 0 64 cm from the sheet metal 990 7096 Rev 2 6 on the front of the unit You may see small sparks when connecting the battery 3 Tuck the white battery cable cord into the space above the UPS connector Unpack the front panel bezel and hold it with the cutout section on the right Align the tabs on the side of the bezel with the slots on the front of the UPS 6 and firmly snap it into place Connect Power and Equipment to the UPS Use an APC supplied cable to connect to the Computer Interface Port DO NOT use a standard serial interface cable since it is incompatible with the UPS connector e Plug the UPS into a standard receptacle e Plug the equipment into the back of the UPS e Do not plug laser printers into a UPS of 1000 VA or less due to the large increase in power consumption when printing e Turn on all connected equipment the equipment will not be powe
2. in the maximum load defined in the Specifications at the APC web site the overload LED comes on and the UPS emits a sustained tone The alarm remains on until the overload is removed The UPS continues to supply power as long as it is on line and the breaker does not trip but it will not provide power from batteries in the event of a utility voltage interruption Disconnect nonessential equipment from the UPS to eliminate the overload Ifa continuous overload occurs while the UPS is on battery the UPS will turn off its output in order to protect itself from possible damage Replace Battery If the battery fails a self test the UPS emits short beeps for one minute and the replace battery LED illuminates If the LED flashes the battery is disconnected The UPS repeats the alarm every five hours Perform the self test procedure after the battery has charged for 24 hours to confirm the replace battery condition The alarm will stop if the battery passes the self test Low Battery When the UPS is operating on battery and the energy reserve of the battery runs low the UPS beeps continuously by default until the UPS shuts down from battery exhaustion or returns to on line operation The low battery warning interval can be changed through optional software Shutdown Mode via optional software or an accessory In shutdown mode the UPS stops supplying power to the connected equipment waiting for the return of utility power If there is no uti
3. information on replacement battery kits 990 7096 Rev 2 2 CHAPTER 2 BASICS About APC American Power Conversion Corporation APC is the leading national and international manufacturer of state of the art uninterruptible power supplies redundant switches power management software and related equipment APC products protect hardware software and data from the threat of power disturbances in business and government offices throughout the world About Your New UPS This APC Uninterruptible Power Supply UPS is designed to prevent blackouts brownouts sags and surges from reaching your computer and other valuable electronic equipment This UPS also filters out small utility line fluctuations and isolates your equipment from large disturbances by internally disconnecting from the utility line while supplying power from its internal batteries until the utility line returns to safe levels The UPS is ready to be mounted in a 46 5 cm 19 inch wide EIA IEC rack cabinet How to Contact APC Internet http www apcc com support contact 3 990 7096 Rev 2 CHAPTER 3 INSTALLATION Unpacking APC has taken care to design robust packaging for your product However accidents and damage may occur during shipment Inspection Inspect the UPS upon receipt Notify the carrier and dealer if there is damage The packaging is recyclable save it for reuse or dispose of it properly Contents The shipping package conta
4. DED ABOVE IN NO EVENT WILL APC BE LIABLE FOR DIRECT INDIRECT SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE Specifically APC is not liable for any costs such as lost profits or revenue loss of equipment loss of use of equipment loss of software loss of data costs of substitutes claims by third parties or otherwise Entire contents copyright O 2001 by American Power Conversion Corporation All rights reserved Reproduction in whole or in part without permission is prohibited APC Smart UPS and PowerChute are registered trademarks of American Power Conversion Corporation All other trademarks are the property of their respective owners 21 990 7096 Rev 2
5. PS beeps occasionally e Normal UPS operation None The UPS is protecting the connected equipment UPS does not provide expected backup time e The UPS s battery is weak due to a recent outage or is near the end of its service life e The UPS is overloaded Charge the battery Batteries require recharging after extended outages Also they wear faster when put into service often or when operated at elevated temperatures If the battery is near the end of its service life consider replacing the battery even if the replace battery indicator is not yet lit Check the UPS s load bar display Unplug less needed equipment such as printers Front panel indicators the six in the center light sequentially e The UPS has been shut down by remote control e The UPS has been put into sleep mode by remote control None The UPS will restart automatically when utility power returns The indicators illuminate from top to bottom then bottom to top None The UPS will restart automatically when the sleep timer expires The indicators illuminate from top to bottom then back to the top 17 990 7096 Rev 2 UPS is plugged into wall outlet and only the battery charge bar graph is lit None The UPS will return to normal operation when the power is restored and the battery has a sufficient charge e The UPS is shut down and the battery is discharged from an extended outage Replace battery light is lit and th
6. ace hot swappable battery tray Battery replacement is a safe procedure isolated from electrical hazards You may leave the UPS and the protected equipment on for the following procedure See your dealer or APC refer to How to Contact APC page 3 for information on replacement battery cartridges Smart UPS Model Replacement Battery Cartridge SU1400RMJ2U RBC24 J 1 The battery tray is accessible from the front of the UPS 2 Be careful removing the battery tray it is heavy 3 This procedure requires a Phillips head screwdriver 4 Small sparks at the battery connectors are normal during re connection 15 990 7096 Rev 2 O 00 g i 990 7096 Rev 2 10 11 12 13 14 Face the front of the UPS and using both hands insert each index finger behind the lip of the curved section of the front panel bezel and pull towards you The front panel bezel will unsnap Set the bezel aside Take out the white cord which is tucked into the space above the battery connector O Grasp the cord and pull firmly towards you to disconnect the battery Use a Phillips head screwdriver to remove the four 4 screws O that secure the battery tray Set the screws aside Use the battery tray handle to slide the tray out halfway Then hold the tray f
7. ate of Last Battery Replacement Minimum Capacity Before Return from Shutdown Sensitivity Duration of Low Battery Warning Alarm Delay After Line Fail Shutdown Delay Synchronized Turn on Delay High Transfer Point Low Transfer Point 990 7096 Rev 2 Every 14 days 336 hours UPS_IDEN Manufacture Date 0 percent 5 second delay 108 Vac Every 7 days 168 hours On Startup Only No Self Test Up to eight characters to define the UPS Date of Battery Replacement 15 25 35 50 60 75 90 percent Reduced Low 5 7 10 12 15 18 20 minutes 30 second delay At Low Battery Condition No 0 60 120 240 480 720 960 seconds 20 60 120 240 480 720 960 seconds 110 112 114 Vac 86 88 90 Vac Sets the interval at which the UPS will execute a self test Refer to your software manual for details Use this field to uniquely identify the UPS for network management purposes Reset this date when you replace the battery tray The UPS will charge its batteries to the specified percentage before return from a shutdown Set lower than normal sensitivity to avoid lowered battery capacity and service life in situations where the connected equipment can tolerate minor power disturbances Sets the time before shutdown at which the UPS issues a low battery warning Set it higher than the default if the OS needs more time for a graceful shutdown To avoid alarms for min
8. ck mount brackets ears and cleats installed and mounting rails for rack mounting included The rails support the UPS and allow adequate air flow There are two steps to install the UPS in a rack This section describes each in detail 1 Install the mounting rails in the rack required for four post racks only 2 Load the UPS into the rack QD Check the rack to make sure it will not tip after moving the mounting brackets Install the Mounting Rails in the Rack Four Post Rack Installation Only Install the mounting rails in the rack Directions are included with the rail kit Load the UPS into the Rack Due to the weight of the UPS two people are required to install it in the rack To lighten the UPS you may remove the batteries while you mount it in the rack Refer to Replacing the Battery page 16 for instructions on how to remove the batteries Four Post Racks 1 Supporting the UPS from both sides carefully align the unit with the rails 2 Each side of the UPS has a cleat O that must slide into the groove on the rail Insert each cleat into its groove and slide the UPS into position 3 Insert the four 4 ornamental screws supplied with the UPS through the mounting brackets and into the top and bottom holes in the U space A 0975 5 2 5090599 EC 7 5 990 7096 Rev 2 Two Post Racks S 1 Ifthe rack holes are not 10 32 D threaded first attach the backi
9. d delivers power to the connected equipment If your system is experiencing excessive periods of high or low voltage have a certified electrician check your facility for electrical problems If the problem continues contact the utility company for further assistance On line Indicator The on line indicator illuminates when the UPS is supplying utility power to the connected equipment Ifthe indicator is not lit the UPS is supplying battery power and the UPS will sound an alarm four beeps every 30 seconds Utility Voltage Bar Graph This UPS has a diagnostic feature that displays the utility voltage With the UPS plugged into the normal utility power press and hold the on button to see the utility voltage bar graph display After a few seconds the 5 LED display on the right of the front panel shows the utility input voltage Refer to the figure to the left for the voltage reading values are not listed on the UPS The display indicates that the voltage is between the highest LED lit and the next higher value For example with three LEDs lit the input voltage is between 91 and 109 Vac If no LEDs come on and the UPS is plugged into a working AC power outlet the line voltage is extremely low If all five LEDs come on the line voltage is extremely high and should be checked by an electrician voltage display A The UPS starts a self test as part of this procedure The self test does not affect the Voltage Trim F This LED comes
10. e UPS beeps for one minute every five hours Charge the batteries for 24 hours and perform self test see e Weak batteries e Bad or expired battery Self Test page 9 to see if it clears Replace the batteries Refer to Replacing the Battery page 15 Replace battery light flashes battery charge bar graph is off and the UPS beeps continuously Check that the battery connector is fully engaged e Battery not connected properly Some or all front panel indicators are flashing Do not attempt to use the UPS Turn the UPS off and have it e Internal UPS fault or battery charger failure serviced immediately With the warning interval setting shown above the battery graph flashes and the UPS operates normally when the battery capacity is insufficient to give the full warning time that the unit is set for The table bellow shows all conditions that could be interpreted as flashing Condition Display Beeper Low battery load still powered Q bit 6 set One or more LEDs flashing on the battery capacity bar graph with either the on line LED or on battery LED on Continuous beeping user settable Low battery shut down 8 bit O set Q Only battery capacity bar graph LEDs on None bit 6 set if flashing or flashing Standby enable bit 7 set Q bit 6 set Only battery capacity bar graph LEDs on None if flashing or flashing Boost or trim relay fault bit 6 set Ce
11. elephone and network line protectors Refer to Connect Power and Equipment to the UPS page 7 for information Voltage Sensitivity The UPS detects line voltage distortions such as spikes notches dips and swells as well as distortions caused by operation with inexpensive fuel powered generators By default the UPS reacts to distortions by transferring to on battery operation to protect the connected equipment In areas where power quality is poor the UPS may frequently transfer to on battery operation If the connected equipment can operate normally under such conditions reduce the sensitivity setting to conserve battery capacity and service life To reduce UPS sensitivity press the Sensitivity button on the rear panel Use a pointed object such as a pen to press the button Press it once to set the UPS s sensitivity to reduced Press it again to set the sensitivity to low Press the button a third time to reset normal sensitivity The Sensitivity can also be changed through software XX normal Normal When the UPS is set to normal sensitivity the LED is brightly lit O reduced Reduced When it is set to reduced sensitivity the LED is dimly lit O low Low When it is set to low sensitivity the LED is off 990 7096 Rev 2 12 Low Battery Warning Level By default the low battery warning occurs when there are approximately two minutes of on battery run time remaining This may not be enough time to gracefully shut down some protec
12. et website www apcc com e Note the model number of the UPS the serial number and the date purchased A technician will ask you to describe the problem and try to solve it over the phone 1f possible If this is not possible the technician will issue a Returned Material Authorization Number RMA e Ifthe UPS is under warranty repairs are free If not there is a repair charge 4 Pack the UPS in its original packaging If the original packing is not available ask customer service about obtaining a new set Pack the UPS properly to avoid damage in transit Never use Styrofoam beads for packaging Damage sustained in transit is not covered under warranty 5 Mark the RMA on the outside of the package 6 Return the UPS by insured prepaid carrier to the address given to you by Customer Service damage during transport U S Federal Regulation requires that batteries be disconnected during shipment The batteries may remain in the UPS they do not have to be removed QD Always DISCONNECT THE BATTERIES before shipping the UPS to avoid This requirement applies whether the UPS is moved indoors or out alone or installed in an equipment rack or system 19 990 7096 Rev 2 Regulatory Agency Approvals LISTED 42C2 E95463 This is a Class A product based on the standard of the Voluntary Control Council for Interference by Information Technology Equipment VCCI If this equipment is used in a domestic environment radio d
13. harged e The UPS includes a protective earth conductor which carries the leakage current from the load devices computer equipment Total leakage current must not exceed 3 5 mA e Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly effect its safety or effectiveness is not recommended Battery Safety e This equipment contains potentially hazardous voltages Do not attempt to disassemble the unit The only exception is for battery replacement using the procedures below Except for the battery the unit contains no user serviceable parts Repairs are performed only by factory trained service personnel e Do not dispose of batteries in a fire The batteries may explode e Do not open or mutilate batteries They contain an electrolyte which is toxic and harmful to the skin and eyes e To avoid personal injury due to energy hazard remove wrist watches and jewelry such as rings when replacing the batteries Use tools with insulated handles e Replace batteries with the same number and type of batteries as originally installed in the equipment Recycling of Batteries Return the battery tray to APC using the package in which your replacement tray shipped See How to Contact APC page 3 for details The battery replacement kit includes a new battery tray See your dealer or Replacing the Battery page 16 for
14. ins the UPS its front panel bezel disconnected from the unit mounting rails and a literature kit containing mounting hardware and product documentation Placement AS a eS Install the UPS in a protected area that 1s free of mm E num excessive dust and has adequate air flow Do not m Y Sf d x x x operate the UPS where the temperature and humidity are outside the specified limits 22 Y Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the warranty How to Install Your Smart UPS To install the UPS follow these steps 1 Mount the UPS in the rack Connect the battery and attach the front panel bezel Connect power and the equipment to the UPS Turn on the UPS pm me us Install optional PowerChute software sold separately This section describes each step in detail 990 7096 Rev 2 4 Mount the UPS in the Rack QD Select a location with adequate air flow that is free from excessive dust Ensure that the air vents on the front and rear of the UPS are not blocked Allow at least 2 54 cm 1 inch of space on both sides A The UPS requires two people to install due to its weight To lighten the UPS you may remove the batteries while you mount the unit in the rack Refer to Replacing the Battery page 15 for instructions on removing the batteries The UPS comes with standard 46 5 cm 19 inch ra
15. isturbance may occur in which case the user may be required to take corrective actions On Battery Run Time N UPS battery life differs based on usage and environment Load Load Run Time E A may mu 990 7096 Rev 2 20 Limited Warranty American Power Conversion APC warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase Its obligation under this warranty is limited to repairing or replacing at its own sole option any such defective products To obtain service under warranty you must obtain a Returned Material Authorization RMA number from customer support Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase This warranty does not apply to equipment that has been damaged by accident negligence or misapplication or has been altered or modified in any way This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase EXCEPT AS PROVIDED HEREIN AMERICAN POWER CONVERSION MAKES NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Some states do not permit limitation or exclusion of implied warranties therefore the aforesaid limitation s or exclusion s may not apply to the purchaser EXCEPT AS PROVI
16. lity power present external devices e g servers connected to the computer interface or the accessory slot can command the UPS to shut down This is normally done to preserve battery capacity after the graceful shutdown of protected servers The UPS will scroll the front panel indicators sequentially in shutdown mode 11 990 7096 Rev 2 Rear Panel The rear panel has the input and output connectors computer interface port and manual settings for the low battery warning level and voltage sensitivity indicator o OVERLOAD PROTECTOR ES G UNINTERRUPTIBLE POWER SUPPLY SEE TOP COVERTOR ADDITIONAL CAUTION INGS H OUTPUT 120V 50 60 Hz MODEL oova 450W MODEL 1000VA B70W gt MODEL 1400va esow S7 O SZ S p WIRING ETE im Computer Interface Port Optional power management software and interface kits can be used with this UPS Use only interface kits supplied or approved by APC If used connect the interface cable to the 9 pin computer inter face port on the back panel of the UPS Secure the connector s screws to complete the connection QD Use an APC supplied cable to connect to the Computer Interface Port DO NOT use a standard serial interface cable since it is incompatible with the UPS connector TVSS Screw e The UPS features a transient voltage surge suppression TVSS screw for connecting the ground lead on surge suppression devices such as t
17. ng plate E l supplied 870 1148 O to the rack L 2 Support the UPS from the front and e back Insert the four 4 ornamental A li gr sl a screws supplied with the UPS or ll e through the mounting brackets and 5 O L A into the top and bottom holes in the oa E as U space as shown for the Four Post M o D o Rack Screw them into the threaded A holes of the backing plate Removing the UPS from the Rack i Due to the weight of the UPS two people are required to remove it from the rack Remove the front panel bezel Face the front of the UPS and using both hands insert each index finger behind the lip of the curved section of the front panel bezel and pull towards you 2 Unscrew the four ornamental screws two screws on each mounting bracket 3 Position one person in front of the rack and the second person either behind or on one side of the UPS for additional support 4 Using the battery tray handle to support the front of the unit slide the UPS partially out of the rack 5 Supporting the UPS from the bottom or rear of the unit slide the UPS fully out of the rack Connect the Battery and Attach the Front Panel Bezel is packaged separately within the main box You must connect the battery and install A The UPS is shipped without its battery connected and the front panel bezel installed it the plastic front panel bezel before the installation is complete 1
18. nter 6 LEDs flashing in unison None Sleep 1 e delayed wake up 8 bit 3 Center 6 LEDs boost overload on line None set on battery trim replace battery scrolling down vertically then back to top Shut down till power returns 8 bit 4 Center 6 LEDs boost overload on line None set on battery trim replace battery scrolling up down vertically Battery overvoltage i e charger failure 8 bit 5 set Center 6 LEDs flashing in unison with on line boost trim and or on battery LEDs staying on and with both bar graphs functioning normally Continuous beeping DC imbalance bit 4 set Left half of LEDs power bar graph boost on line trim flashing in unison None Battery disconnected bit 5 set Replace battery LED flashing and battery capacity bar graph off all other LEDs unaffected Continuous beeping Output overvoltage bit 7 set Right half of LEDs battery capacity bar graph overload on battery replace battery flashing in unison None 990 7096 Rev 2 18 Service and Transport If the UPS requires service do not return it to the dealer Follow these steps 1 Review the problems discussed in Troubleshooting page 17 to eliminate common problems 2 Verify that no circuit breakers are tripped this is the most common UPS problem 3 Ifthe problem persists call customer service refer to How to Contact APC page 3 or visit the APC Intern
19. on to indicate that the UPS is compensating for a high utility voltage Voltage Boost This LED comes on to indicate that the UPS is compensating for a low utility voltage 990 7096 Rev 2 10 Battery Power O 96 O 72 O 48 O 24 O 0 If the utility power fails the UPS can provide power to the connected equipment from its internal battery for a finite period The UPS sounds an alarm four beeps every 30 seconds while operating on battery power The alarm stops when the UPS returns to on line operation On Battery Power Indicator When the on battery power indicator is lit the UPS is supplying battery power to the connected equipment Refer to On Battery Operation page 13 for details Battery Charge Bar Graph The 5 LED display on the right of the front panel shows the present charge of the UPS s battery as a percentage of the battery s capacity When all five LEDs are lit the battery is fully charged The LEDs extinguish from top to bottom as the battery capacity diminishes The battery capacity threshold is shown in the figure to the left 1t is not listed on the front panel display As a low battery warning any LEDs illuminated for the given capacity will flash The low battery warning setting can be changed from the rear panel see Low Battery Warning Level page 13 or through the optional PowerChute software Overload When the UPS is overloaded when the connected equipment exceeds the maximum specified
20. or power glitches set the alarm delay Sets the interval between when the UPS receives a shutdown command and when shutdown occurs The UPS will wait the specified time after the return of utility power before turn on for example to avoid branch circuit overload To avoid unnecessary battery usage set the High Transfer Point higher if the utility voltage is chronically high and the connected equipment is known to work under this condition Set the Low Transfer Point lower if the utility voltage is chronically low and the connected equipment can tolerate this condition CHAPTER 5 MAINTENANCE AND TROUBLESHOOTING Storage This section describes how to store the UPS while it is not in use To remove the UPS from the rack see Removing the UPS from the Rack page 6 Storage Conditions Store the UPS covered and flat rack mount orientation in a cool dry location with its battery fully charged Disconnect any cables connected to the computer interface port to avoid unnecessarily draining the battery Extended Storage At 15 to 30 C 5 to 86 F charge the UPS s battery every six months At 30 to 45 C 86 to 113 F charge the UPS s battery every three months Replacing the Battery Please read Chapter 1 Safety Information page 1 before replacing the battery tray Once the battery is disconnected the connected equipment is not protected from power outages This UPS has an easy to repl
21. red until the UPS is turned on e Add any optional accessories See the literature accompanying the accessory for details e Connect ground leads to the TVSS screw optional The transient voltage surge suppression TVSS screw provides grounding through the UPS s power cord ground conductor See Rear Panel page 13 for the location of the screw To make the connection loosen the screw and connect the surge suppression device s ground lead Tighten the screw to secure the lead Turn on the UPS Make sure the battery is connected before turning on the UPS e Press the UPS s on button located on the front panel to power up your UPS This will power up connected equipment 7 990 7096 Rev 2 charges fully during the first four hours of normal operation Do not expect full run A The UPS charges its battery whenever it is connected to utility power The battery time during this initial charge period e The unit performs a self test automatically when turned on and every two weeks thereafter by default Install Optional PowerChute Software sold separately and Accessories For additional computer system security install PowerChute UPS monitoring software PowerChute is sold separately It provides automatic unattended shutdown capabilities on most major network operating systems This UPS is equipped with an accessory slot See the APC website apcc com for available accessories If a standard accessory is in
22. rom the sides and slide it out to the maximum extended position A stop tab O on the bottom of the tray will prevent the tray from coming out completely Carefully lift the tray up so that the stop tab O clears the ledge on the unit Return the battery tray to APC using the package in which your replacement tray shipped See How to Contact APC page 3 for details The battery replacement kit includes a new battery tray Hold the new tray on the sides and align it with the opening Raise the back of the tray up slightly to position the stop tab on the inside of the opening Then level the tray and push it in completely Remove the tape on the new battery tray connector to expose the cable connector Locate the UPS battery connector O which is to the right of the battery tray and recessed Connect the battery cable connector to the UPS connector Press firmly to ensure that the connection is tight You will hear a snap when the connector is properly seated Replace the four 4 screws removed in step 4 Tuck the white battery cable cord neatly into the space above the UPS connector Hold the front panel bezel with the cutout section on the right Align the tabs on the side of the bezel with the slots on the front of the UPS 6 and firmly snap it into place 16 Troubleshooting Use the chart below to solve minor UPS installation problems Contact APC Technical Support Staff see How to Contact APC page 3 for assis
23. stalled on this UPS follow the installation instructions included with the accessory 990 7096 Rev 2 8 CHAPTER 4 OPERATION Front Panel This rack mount UPS has the power control and operating indicators located on the front panel IN i Ze DN t A W d fSmartus f 0 2 Y E i E 0 o 0 t f i 8 Jj t 315490 g i o e M f gt Z i i Y Operation The ON and OFF buttons control the power to the outlets on the UPS They can be used as a master On Off switch for the connected equipment The charger and communication circuits of the UPS remain operational as long as it is plugged into an acceptable utility power outlet Power On Press and release the large upper button labeled TEST to supply power to the connected equipment The equipment is immediately powered while the UPS performs a self test Power Off Press and release the small lower button labeled 0 to turn off power to the connected equipment battery charge Whenever the UPS is plugged in and utility voltage is present the charger maintains Load Bar Graph Bo The 5 LED display on the left of the front panel shows the percentage of available power being Qs used by the connected equipment load The display shows the
24. tance with complex UPS problems Problem and Possible Cause Solution UPS will not turn on e ON button not pushed e UPS not connected to AC power supply e UPS s input circuit breaker tripped e Very low or no utility voltage e Battery not connected properly Press the ON button once to power the UPS and the connected equipment Check that the power cable from the UPS to the utility power supply is securely connected Reduce the load on the UPS by unplugging equipment and reset the circuit breaker on back of UPS by pressing the plunger back in Check the AC power supply to the UPS with a table lamp If very dim have the utility voltage checked Check that the battery connector is fully engaged UPS will not turn off e Internal UPS fault Do not attempt to use the UPS Unplug the UPS and have it serviced immediately UPS operates on battery although normal line voltage exists e UPS s input circuit breaker tripped e Very high low or distorted line voltage Inexpensive fuel powered generators can distort the voltage Reduce the load on the UPS by unplugging equipment and reset the circuit breaker on back of UPS by pressing the plunger back in Move the UPS to a different outlet on a different circuit Test the input voltage with the utility voltage display If acceptable to the connected equipment reduce the UPS s sensitivity See Voltage Sensitivity page 12 for procedures U
25. ted computer systems To change the warning interval press the rear panel Sensitivity button while pressing and holding the front panel on button O 2 min Brightly lit The low battery warning interval is approximately two minutes O 5min Dimly lit The low battery warning interval is approximately five minutes 7min Off The low battery warning interval is approximately seven minutes On Battery Operation The Smart UPS will switch to battery operation automatically should the utility power fail While running on battery an internal alarm will sound periodic beeps Press the on button on the front panel to silence the UPS alarm for the current alarm only The optional PowerChute software allows you to change the audible indicator If the utility power does not return the UPS will continue supplying power to the connected equipment until exhausted A continuous beeping will sound approximately two minutes before the UPS s final low battery shutdown If using a computer you must manually save your files and power down before the UPS turns itself off unless you are using optional PowerChute interface software that provides automatic unattended shutdown Refer to On Battery Run Time page 20 for approximate run time data 13 990 7096 Rev 2 User Configuration Items Note Setting these items requires software or optional hardware Function Factory User Selectable Description Default Choices Automatic Self Test D
26. ttery POWT ee leema EET 11 Rear Paneline E 12 On Battery Operati oi iceri iiir iea o e tenere eere oe E cheek tailed red n ne eere 13 User Configuration Items ooooonincninnononcnonnconncnnnoconccon nono nono noconnconn cnn n non on n aran rra nnne nnne nnne nnne 14 990 7096 Revision 2 Chapter 5 Maintenance and Troubleshooting 15 Niere 15 Storage Conditions teet eo ase c ean a ir D eerte Iud 15 Extended MALA ttee tete t DR celestia one dead E a a 15 Replacing the Battery aee terae a ada 15 A eter tait a teet te oett darte edite Mee NO 17 SetVICe i uei dep ende re a pter ee lr He P ane eter tabe Heb Re eed pe innt 19 Regulatory Agency Approvals ssesseseeseeeeeeeenen nennen enne enne nnne nenne nnne nnn nnne 20 Or Battery Rum Time uo on teet eee ehe era teetedes see E Redes t 20 CHAPTER 1 SAFETY INFORMATION This Safety Guide contains important instructions that should be followed during installation and maintenance of the APC equipment and batteries It is intended for APC customers who setup install relocate or maintain APC equipment Conventions Used in this Manual This section defines the symbols used throughout this manual Carefully read all information boxes and abide by the instructions procedure practice condition or the like which if not correctly A The WARNING sign denotes a serious hazard It calls attention to a performed or adhered to could result in injur
27. voltage level between the highest D LED lit and the next higher value For example if three LEDs are lit the connected equipment is a drawing between 50 and 67 of the UPS s capacity If all five LEDs are lit the connected equipment is drawing between 85 and 100 of capacity Thoroughly test your complete system to make sure that the UPS will not become overloaded In the graphic to the left the load capacity threshold is listed next to the LED these are not shown on the actual UPS Self Test During the self test the UPS briefly operates the connected equipment on battery If the UPS passes the self test 1t returns to on line operation If the UPS fails the self test it immediately 9 990 7096 Rev 2 returns to on line operation and lights the replace battery LED The connected equipment is not affected by a failed test Recharge the battery for 24 hours and perform another self test If it fails the battery must be replaced See Replacing the Battery page 16 for details Automatic Self Test The UPS performs a self test automatically when turned on and every two weeks thereafter by default Automatic self test eases maintenance requirements by eliminating the need for periodic manual self tests Manual Self Test Press and hold the on button on the front panel for a few seconds before the self test will begin Utility Power Q 119 Q 109 O 100 O 91 O 81 During normal operation the UPS monitors the utility power an
28. www apcc com User s Manual English APC Smart UPS 1400 VA 2U Rack Mount Uninterruptible Power Supply 100 Vac 990 7096 Revision 2 TABLE OF CONTENTS ENGLISH Chapter 1 Safety Information s 1 Conventions Used in this Manual esee nennen nennen nnne nennen 1 Handling Sato atu pet jeta 1 Electrical Safety inma dae 1 Deenereizin ge Dali HE A e ORE et iaa 2 Battery dd ais 2 Recycling Of Ballet iii ere ee e MET n Ei Ie EP ache mtt en iens 2 Chapter 2 Basles s oe oto be aee es 3 Dani uus 3 About Y out New UPS EE A E A 3 Howto Contact AG x3 retro ete onc e aia iaa 3 Chapter 3 Installation t 4 npacking u ice a ie ertet ee ec tere idee ilte rue wh dees ect Pee ea een 4 InspectiOtic orto id Pre oe tenes ede agua 4 eI Pe asias 4 Placement Snnt BRE RR EVE RHEINE 4 How to Install Y our Simart UDS 55 retiro ra terti tr etg ihr d eR OR 4 Mount the PS in the Rack eio ree rt de eei me retire Sesion deen red eie cadens 5 Connect the Battery and Attach the Front Panel Bezel esee 6 Connect Power and Equipment to the UPS sse enne 7 Chapter 4 Operation ttt 9 Front Panel ck lees E nn 9 OPTOMA EA AA AE A AR ok A A E od ea coun ede EE ta 9 SS RR O 9 Utility Powers tia aia lala die 10 Ba
29. y to personnel QD The CAUTION sign denotes a hazard It calls attention to an operating procedure practice or the like which if not correctly performed or adhered to could result in damage to or destruction of all or part of the product The NOTE sign denotes important information It calls attention to a procedure practice condition or the like which is essential to highlight Handling Safety e Becareful Do not lift heavy loads without assistance 18 32 kg 40 70 Ib i e This equipment is intended for installation in a temperature controlled indoor area see the Specifications at the APC web site for exact temperature range free of conductive contaminants Electrical Safety e To reduce the risk of fire connect only to a circuit provided with a 20 A maximum branch circuit overcurrent protection in accordance with the National Electrical Code ANSI NFPA e Do not work alone under hazardous conditions e Check that the power cord s plug s and sockets are in good condition 1 990 7096 Rev 2 Deenergizing Safety e This UPS has an internal energy source the battery the output may be energized when the unit is not connected to an AC power outlet e To deenergize the UPS first press the Off button to switch the outputs off Next disconnect the UPS from the AC power outlet then disconnect the battery and finally press the ON button to ensure that the internal capacitors are disc

Download Pdf Manuals

image

Related Search

Related Contents

Ultrasonic Liposuction Equipment F-218  Dell UPS 5600R Getting Started Guide  Bedienungsanleitung Glanzgradmessgerät PCE  Philips 14PV422 User's Manual  User manual - Agilent Technologies  Use and Care Manual  Manual ELG S5M  Sage mode d`emploi n°1  Manuel utilisateur  NEC AS241W-BK Mechanical Drawings  

Copyright © All rights reserved.
Failed to retrieve file