Home
Extinguishant Control Panel User Manual
Contents
1. a Man 1091SHQU_Quaestor SZE_01 Page 9 of 10 Display Enable first stage relay Flashing dot indicates first output step 1 stage relay output disabled Mode Press mode button till dP is displayed Enable first stage relay output step 2 Dot stops flashing to indicate first stage relay output enabled Enter Press button Disable second stage relay output step 1 Mode Press mode button till dA is displayed Dot flashes to indicate second stage relay output is disabled Disable second stage relay output step 2 Enter Press button Enable second stage relay output step 1 Flashing dot indicates second stage relay output disabled Mode Press mode button till dP is displayed Enable second stage relay output step 2 Dot stops flashing to indicate second stage relay output enabled Enter Press button Disable first stage sounders step 1 Mode Press mode button till db is displayed Disable first stage sounders Dot flashes to indicate first step 1 stage sounders are disabled LL LL LULL CELL L Enter Press button Enable first stage sounders Flashing dot indicates first step 1 stage sounders disabled Mode Press mode button till db is displayed Enable first stage sounders Dot stops flashing to indicate step 2 i first stage sounders enabled Enter Press button Man 1091SHQU Quaestor SZE 01 Page 10 of 10
2. in Zone 1 2 3 Enter Press button Q Q Q Zone Fault Test Disablement Dot stops flashing when enabled Zone fault LED off Exit test mode step 1 i l L Mode Press button First display Exit test mode step 2 Zones in test mode will have i flashing dot Select a Press to scroll zones Jone 2 Exit test mode step 3 Fire in Zone a e Enter O O O Press button Zone Fault Test Disablement Dot stops flashing when test mode exited Zone 1 fault LED off Man 1091SHQU Quaestor SZE 01 Page 7 of 10 Display Automatic Manual Automatic Manual and manual only Change from Manual only to and manual only Automatic and Manual and vice versa Start Extract fan Insert key and turn Press Mode button till Ac appears in display Enter Press button Press Enter button again to Dot flashes to indicate extract turn extract fan on active Press Enter button again to Dot stops flashing to indicate turn extract fan off Enter extractive inactive Press button Extinguishant will release after time displayed in Manually release the seconds on the countdown extinguishant timer CAUTION Pull down flap and press button to release extinguishant Disable extinguishant control step 1 Press mode button till dE is displayed Disable extinguishant Dot flashes to indicate control step 2 extinguishant control is disabled Enter Press button Enable extinguishant control
3. Flashing dot indicates step 1 extinguishant control disabled Mode Press mode buiton till dE is displayed Enable extinguishant control Dot stops flashing to indicate step 2 extinguishant control enabled Enter Press button Man 1091SHQU Quaestor SZE 01 Page 8 of 10 Disable manual release step 1 Display e Mode Press mode button till dt is displayed Dot flashes to indicate Manual release is disabled Disable manual release step 1 Enter Press button Flashing dot indicates Manual release disabled Enable Manual release step 1 Mode Press mode button till dt is displayed Dot stops flashing to indicate Manual release enabled Enable Manual release step 2 Enter Press button Disable extract fan step 1 Mode Press mode button till dc is displayed Dot flashes to indicate Extract fan is disabled Disable extract fan step 2 Enter Press button Flashing dot indicates extract fan disabled Enable extract fan step 1 Mode Press mode button till dc is displayed Dot stops flashing to indicate Extract fan enabled Enable extract fan step 2 Enter Press button Disable first stage relay output step 1 Mode Press mode button till dP is displayed Dot flashes to indicate first stage relay output is disabled Disable first stage relay output step 2 Enter Press button LL OL LULL LL LL LL
4. QUAESTOR SZE Extinguishant Control Panel SHC70002 SHC70003 User Manual Man 1091SHQU Issue 01 March 2013 General System Status Fire In Zone Disablements Extinguishant Status Extinguishant tou LJ Fire ai Power Fatt LI LI a Ki Extingwrvhent maripa ans Sounder Fault Manual Release e Power On Disablement 2 3 Release imminent Autot Minua Manusi nly n r Ist Stage tat Stage J pelay on General fou e LA Contact Activated Zone Fault fest Ind Stage told Activated LI Test Mode On System Fault y Disablement Contact i Alarm Fault Extract mues Warning mh Chtablement Silanced Flosd ng Lone favit Silence Sound Akarm Fautt Reset Lamp Test Mode Select Enter System Mode Enable Control Warning Silence 100 310 an Alarm a SAFETY HI TECH ETM owa asye Vin Cavor 96 6708 Avezzann AQ Kay Ted A ONGAAONIO Fa re Wa 24 www god tyinitech com Brngulshant Cornero Saran K1 109142 SHC70002 y mam mend 2009 ss A Fire alarm condition General fire indicator lights and zonal fire indicators flash Buzzer sounds urgently Carry out fire procedure Fault condition General fault indicator lights and specific fault indicators flash Buzzer sounds continuously Call maintenance engineer Man 1091SHQU Quaestor SZE 01 Page 2 of 10 Disabled condition General disablement indicator and specific fault indicator lit continuously Maintain vigilance during disablement conditions Test
5. condition Test indicator and specific fault indicator lit continuously Ensure system is returned to normal when testing is finished Man 1091SHQU Quaestor SZE 01 Page 3 of 10 Manual only mode Manual only indicator lit di 0 0 2 3 60 0 Fauit Tout 090000 z i iR E 4 Extinguishant will not be released by automatic detection Automatic and Manual mode Automatic and Manual indicator lit Extinguishant will be released by automatic detection Man 1091SHQU Quaestor SZE 01 Page 4 of 10 1 Stage activated Normally accompanied by a zonal fire indicator If no zonal fire indicator and Release imminent indicator is lit then a manual release button has been activated Al TOR BZE som Y 1 stage of automatic release of extinguishant has Started Release Imminent Always accompanied by 1 stage activated indicator Normally accompanied by more than one zonal fire indicator Countdown timer to extinguishant release has started Time remaining before release indicated in seconds on seven segment display If no zone fire LEDs lit then release is by manual unit a a Di Extinguishant will be released when timer reaches zero display will show EEE during extinguishant release Man 1091SHQU Quaestor SZE 01 Page 5 of 10 How To Do This Display Comments Buzzer sounds whilst button L is pressed Test lamps Lamp test e e Press button All lamps on O Alarm Fault Silence b
6. uzzer Ce warning silenced Alarm Fault warning silence Press button Enable control Buzzer beeps twice every Enable buttons n seven seconds mn Alarm Fault Buzzer Silenced Insert key and turn Silence alarms Silence Sound Alarm Press button Buzzer beeps urgently Sound alarms Silence Sound Alarm Press button All fault indicators Resets fire detection system flash for 3 seconds Extinguishant system will reset only after the extinguishant has been Reset released Press button Mode Press button till d1 First display displayed Disable a zone step 1 Disable a zone step 2 Select Press button to scroll zones Disable a zone step 3 Fire in Zone e General e A O Disablement 1 2 3 Enter O Oo O Press button Zone Fault Test LI L Disablement Dot flashes when disabled Zone 2 fault LED lit Do This Display Man 1091SHQU Quaestor SZE 01 Page 6 of 10 Put a zone into test mode step 1 Mode Press button till t1 displayed Put a zone into test mode step 2 Select Press button to scroll zones Put a zone into test mode Test mode on step 3 Enter Press button Zone Fault Test Disablement Dot flashes when disabled Zone 2 fault LED lit Enable a zone step 1 Mode Press button till d1 displayed Enable a zone step 2 Disabled zones will have flashing dot Select Press button to scroll zones Enable a zone step 3 Fire