1.   For further information regarding the individual steps  see the page indicated    Commissioning steps    Inspection steps    Di Maintenance steps Page    1  Starting the heating system    11  2  Shutting down the system    12  3  Removing the burner  if required     13  4  Opening the cleaning 0400    5  13  5  Opening the clean out cover and combustion  chamber door    14  6  Extracting  if installed  and cleaning the  turbulators       arras nio 14  7  Cleaning the heating surface  the flue outlet and  flue pipers ai ie 15  8  Checking all seals gaskets and packing cords on  the flue gas side  9  Checking the thermal insulation parts                   15  10  Inserting turbulators  if appropriate  and closing  the cleaning doors    16  11  Securing the clean out cover and the combustion  chamber door    16  12  Installing the burner               17  13  Checking all connections on the water and steam  side for leaks  14  Checking the inspection ports for leaks                17  15  Check the function of all safety equipment in  accordance with the log for steam boiler systems  categorvIV      et a ee 18  16  Cleaning the sight glass in the combustion  chamber doors    19  17  Checking the water quality    19  18  Checking the installation room ventilation    Commissioning  inspection  maintenance    Steps   commissioning  inspection and     cont      Commissioning steps    Inspection steps      Maintenance steps Page    Q Q 19  Checking the flue pipe for soundness  Q Q 
2.   sioning service report  These values  must be confirmed by the expert and  the system user    According to the Pressure Equipment  Directive 97 23 EC  hot water boilers  category IV may only be operated   supervised and maintained by a  trained boilerman     Operational checks    A    Danger   Boiler components that are not  thermally insulated can be sub   ject to high temperatures that  can result in burns    Take care with hot surfaces     Subject to the safety equipment fitted  and the details in the permit certifi   cate  either monitor the correct boiler  operation constantly  every 24 hours  or every 72 hours     Operating information    The relevant authority may grant   upon application  permission to oper   ate the boiler without permanent  supervision  subject to it being  equipped in accordance with EN  12953 part 6    In systems comprising several boi   lers  of which one is constantly used  as standby boiler  only change the  operation over in longer intervals  e g   during the annual inspection of the  total system    We would recommend that you oper   ate the boiler constantly at the  required operating pressure and tem   perature    The continued boiler operation is still  advantageous  even if no heat is  drawn off for a longer period of time     Determine the extent of checks   required in accordance with TRD 601    sh  1  section 7  or local regulations     Test the chemical composition of the   boiler water and feedwater constantly   in accordance with 
3.  Further details regarding the individual steps  cont      ie or Eat    i 1      ef                                              6 o                                                            Check the function of all safety equipment in accordance  with the log for steam boiler systems category IV     Check the safety valves plus the tem   perature and pressure limiters in  accordance with manufacturer s  details     18    5592 548 GB    5592 548 GB       Commissioning  inspection  maintenance  Further details regarding the individual steps  cont      Cleaning the sight glass in the combustion chamber doors    Check the sight glass with gaskets  4   for leaks and clean     Checking the water quality    For standard values  see page 20   Adjusting the burner    By the burner manufacturer or  authorised heating contractor     19    Additional information  Standard values for water quality    According to the EN 12953 part 10  and the VdTUV datasheet 1466  regarding the water quality for hot  water boilers in heating systems  the  following details apply to heating sys   tems operated with flow temperatures  in excess of 100   C     Operation with circulating water with low salt content    Only use water with a low salt content Systems using mixed condensate   as fill or top up water  such as desali  generally create water with low salt   nated water  permeate or condensate  content if no boiler water is fed into  the system for putrefaction by alka     lies     Operation with 
4.  after the supply    boiler has been completely de    pressurised  4  Close all valves     5592 548 GB    12    5592 548 GB    Commissioning  inspection  maintenance  Further details regarding the individual steps  cont    Removing the burner  if required   1  Remove the fuel supply line     2  Undo screws  A  and remove burn   er with burner plate  6      Undo screws  A  at cleaning door s   and open the cleaning door s         13    Commissioning  inspection  maintenance  Further details regarding the individual steps  cont      Opening the clean out cover and combustion chamber door  1  Remove clean out cover  6      2  Open combustion chamber door    Extracting  if installed  and cleaning the turbulators    For this  use the turbulator extractor       14    Remove turbulators  A  without force     that is part of the cleaning equipment     5592 548 GB    5592 548 GB       Commissioning  inspection  maintenance  Further details regarding the individual steps  cont      Cleaning the heating surface  the flue outlet and flue pipe    1  Clean flues     combustion cham   ber and reversing chamber with  the brush and remove combustion  residues     2  Remove combustion residues from  the flue pipe and the flue outlet     Checking the thermal insulation parts    1  Checking the thermal insulation  parts of combustion chamber door          2  Check the thermal insulation parts  on the clean out doors  the com     ae bustion chamber entry  the clean   out cover and check inside th
5.  gradually  open the boiler return valve and  possibly the feedwater valve as  well as the boiler flow valve     Only then enable the full burner  load     When heating the system from  cold  also when restarting after  maintenance and cleaning work    prevent all heat transfer to consu   mers  to clear the dew point range  as quickly as possible     After the operating temperature  has been reached  sequentially  switch on the heat consumers and  change over to automatic mode     11    Commissioning  inspection  maintenance  Further details regarding the individual steps  cont      17  Check the fittings for leaks priorto 18  Check the boiler door s  and    and during the heat up phase and clean out cover after approx  50  retighten  where required  hours for leaks and retighten all  Retighten all fittings at max  per  screws     missible operating pressure  Tor   que values under cold and hot                conditions    Closure Dimen  Torque  sions   Hand hole  100 x 150    100 Nm  M16   Head hole  220 x 320    200 Nm  M20   Manhole 320 x 420    350 Nm  M24             Shutting down the system    Danger 1  Close the shut off valves in the oil  Opening the boiler connections lines  at the oil tank and filter  or  and openings whilst the boiler the gas shut off valve    is under pressure can lead to a   high risk of severe injury  2  Switch OFF the burner    Only open the connections on   the water and steam side and 3  Isolate the system from the power  inspection apertures
6.  serious injury    m Never smoke  Prevent naked  flames and sparks  Never  switch lights or electrical  appliances ON or OFF    m Close the gas shut off valve    m Open windows and doors    m Remove all people from the  danger zone      Notify your gas or electricity  supplier from outside the  building      Shut off the electricity supply  to the building from a safe  place  outside the building      If you smell flue gas  A Danger  Flue gas can lead to life threa   tening poisoning   m Shut down the heating sys   tem   m Ventilate the boiler room   m Close all doors leading to the  living space     5592 548 GB    5592 548 GB    Safety instructions  cont      Working on the system    m When using gas as fuel  also close  the main gas shut off valve and  safeguard against unauthorised  reopening    m Isolate the system from the power  supply and check that it is no longer   live   e g  by removing a separate  fuse or by means of a main isolator    m Safeguard the system against  unauthorised reconnection     I Please note     Electronic modules can be  damaged by electro static dis   charges   Touch earthed objects  such as  heating or water pipes  to dis   charge static loads     Safety instructions    Repair work    Please note   Repairing components which  fulfil a safety function can com   promise the safe operation of  your heating system    Replace faulty components  only with original Viessmann  spare parts     Ancillary components  spare and  wearing parts    Please n
7. 20  Adjusting the burner    10    5592 548 GB    5592 548 GB    Commissioning  inspection  maintenance    Further details regarding the individual steps    Starting the heating system    R      Check that the turbulators  if    10     Details provided by the burner  manufacturer and regarding  accessories    installed  are fully pushed into the  hot gas flues  open the cleaning  door s         Check that the installation room    ventilation is open       Check the function of the water    treatment system       Fill the boiler with water and venti     late it     Note   The water in hot water boilers  must comply with EN 12953 part  10  see also  Standard values for  water quality  on page 20       Check all fitted components  such    as pipework  valves  regulators   pumps etc  for function and leaks       Check the system pressure       Check the fuel oil level or the gas    supply pressure       Open the flue gas damper  if    installed        Check that the cleaning aperture     s  on the flue outlet is are closed     Open the gas or oil supply line  shut off valves     11     12     13     14     15     16     Switch ON the main isolator  the  switch for the boiler drives and  the burner control switch in this  order  observe the burner manu   facturer   s operating instructions      Start the boiler at a low output   max  30   and gradually heat up  to a temperature of approx  30 K  below operating temperature     After the required flow tempera   ture has been reached 
8. EN 12953 part 10   and VdTUV datasheet 1466  or local   regulations     Carry out the following checks daily   or every 72 hours  subject to boiler   version and the manufacturer s speci    fication  see also TRD 601  sh  1       Blow down the boiler  only for boi   lers without automatic facility   briefly open the valve two or three  times at operating pressure       Check the water level limiter    m Check the feed and boiler water     Operating information  Operational checks  cont      Carry out the following checks   monthly    m Check the function of the safety  valve    m Check the function of all control and  safety equipment    m Check all connections and closures  for leaks    m Check the installation room ventila   tion     Shutdown    Have someone carry out the following   checks every six months  in accor    dance with TRD 602 and 604     m Check the safety equipment    m Check the burner    m Check the thermal insulation on the  hot gas side  i e  on lids and doors    Record the results of the daily    monthly and biannual checks in a log     To prevent corrosion setting in during idle periods  when the boiler is not pres   surised  conserve the boiler surfaces on the flue gas and water sides  subject to  the length of the period during which the boiler is taken out of use  There is a dif   ferentiation between wet conservation  during which exposure to oxygen is to  be avoided  and dry conservation  during which moisture levels are to be mini     mised      Br
9. Operating and service VIE2MANN  instructions    for contractors    Vitomax 200 HW   Type M238   Oil gas fired high pressure hot water boiler  Combustion output 4 0 to 18 2 MW       VITOMAX 200 HW       5592 548 GB 06 2007 Please keep safe     Safety instructions    Safety instructions    Please follow these safety instructions closely to prevent accidents and    material losses     Safety instructions explained  A Danger   This symbol warns against the  risk of injury     Please note   This symbol warns against the  risk of material losses and  environmental pollution     Note  Details identified by the word  Note   contain additional information     Target group    These instructions are exclusively   designed for qualified personnel      Work on gas equipment must only  be carried out by a qualified gas fit   ter    m Work on electrical equipment must  only be carried out by a qualified  electrician    m The system must be commissioned  by the system installer or a qualified  person authorised by the installer     Regulations    Observe the following when working   on this system   m all legal instructions regarding the  prevention of accidents    m all legal instructions regarding  environmental protection     m the Code of Practice of relevant  trade associations    m all current safety regulations as  defined by DIN  EN  DVGW  TRGI   TRF  VDE and all locally applicable  standards     If you smell gas    Danger   Escaping gas can lead to   explosions which may result in  
10. e  reversing chamber     15    Commissioning  inspection  maintenance  Further details regarding the individual steps  cont      Inserting turbulators  if appropriate  and closing the clean   ing doors    1  Insert turbulators  only in the  3rd flue      as far as they will go     2  Close the clean out doors   3  Tighten the screws on the clean     w out doors  A  evenly and diagon   ally        Securing the clean out cover and the combustion chamber  door    1  Tighten down both clean out cov   ers  8  so they seal     2  Close combustion chamber door    Q    and tighten it down so it seals     16    5592 548 GB    5592 548 GB    Commissioning  inspection  maintenance  Further details regarding the individual steps  cont      Installing the burner    1  Secure burner plate  8  with  screws  A  to burner flange        2  For pressure jet gas burner   Fit the gas supply pipe     Danger     gt   xj  ae Escaping gas leads to a risk   a    of explosion     E Test the soundness of all  A    gas connections     Checking the inspection ports for leaks    Danger Note  Boiler components that are not Replace the gaskets every time a con   thermally insulated can be sub  nection has been opened     ject to high temperatures that Insert only gaskets approved in accor   can result in burns  dance with TRD 401  appendix 1   Take care with hot surfaces  VdTUV  or local regulations      Installation instructions of the  gasket manufacturer     17    Commissioning  inspection  maintenance   
11. ief interruption of operation  1 to 2 days     Water side    Recommendation  Maintain the boiler  pressure and temperature  Where that  is not possible and the boiler should  be depressurised for several days  we  would recommend the following     Flue gas side  Keep the heating surfaces dry     Remove severe contamination as it  binds moisture     To prevent oxygen corrosion  add an  oxygen binder with twice to three  times the standard dose to the feed   water from approx  one hour before  the boiler is shut down     5592 548 GB    5592 548 GB    Shutdown  cont      Operating information    Longer interruptions of operation    Water side    Wet conservation  as long as there is no risk of frost    1  Fill the boiler up to the highest pos   sible level with treated feedwater   To prevent oxygen corrosion  add    an oxygen binder to the boiler water     e g  sodium sulphite  in accor   dance with the manufacturer s  instructions  For this  ensure good  admixing with the boiler water   thermal or mechanical agitation     2  If  in multi boiler systems  only  some boilers must be conserved   these can be filled with desalinated  boiler water from the boilers that  remain in use  which will also main   tain the temperature    3  Maintaining pressure in a fully filled  boiler using nitrogen  preferably  nitrogen 5 0  of 0 1 to 0 2 bar can  prevent corrosion     Dry conservation in case there is a risk of frost or in case of longer idle    periods    Drain the boiler at a temperat
12. nt                                                                                 Tu    i       A e     T                   Boiler type                     amp   ES    VIE     Ki        1E   g 8     lt   10  e E   e B                     Q                                  5592 548 GB    Keyword index    B   Burner installation                         17  Burner  removal                             13  C   Cleaning door  opening                  13  Clean out cover  opening               14  Clean out cover  securing              16  Combustion chamber door  opening     ae ee pad E Cei a     14  F   Fill and top up water                     20  Flue outlet and flue pipe  cleaning  15  Flue supply line                          0        13  M   Maintenance information                 8    Keyword index    O   Operational checks                         5  S   Safety valve  checking                    6  Saline water                                  20  Shutdown               eee 6  12  Sight glass  cleaning                     19  Starting the heating system            11  T   Thermal insulation parts  checking 15  Turbulators  extracting                  14  Turbulators  inserting                    16  Ww   Water quality    20  Water with a low salt content          20    27    28    Viessmann Werke GmbH amp Co KG  D 35107 Allendorf   Telephone   49 6452 70 0   Fax   49 6452 70 2780  www viessmann com    Viessmann Limited   Hortonwood 30  Telford  Shropshire  TF1 7YP  GB  Tele
13. ote   Spare and wearing parts which  have not been tested together  with the heating system can  compromise its function  Instal   ling non authorised compo   nents and non approved  modifications conversion can  compromise safety and may  invalidate our warranty    For replacements  use only ori   ginal spare parts from  Viessmann or those which are  approved by Viessmann     Index  Index    Operating information       Operating tips  cast sie dati alia a lin deeds ana aio 5  Operational checks 5  Shutdown  ae riali riali iatale ada EL Alpi al 6  Maintenance information                  eens 8  Commissioning  inspection  maintenance   Steps   commissioning  inspection and maintenance                         9  Further details regarding the individual steps                     11  Additional information   Standard values for water quality                       20  Commissioning service reports                       cece eee eeeeeeeeeeeaaeeeeeeeaaneeees 22  Keyword iNdeX sicir ies RIO ante IAA AEREE 27    5592 548 GB    5592 548 GB    Operating tips    According to the Pressure Equipment  Directive 97 23 EC  a steam boiler  category IV may only be taken into  use when the relevant authority has  granted permission for the installation  of the system  and an authorised  expert has tested the system    The system must be commissioned by  the system installer or a qualified per   son authorised by the installer as well  the relevant expert    Record all actual values in a commis 
14. phone   44 1952 675000  Fax   44 1952 675040   E mail  info uk viessmann com    Subject to technical modifications     5592 548 GB    Printed on environmentally friendly   chlorine free bleached paper    M    
15. saline water    Where possible  use water with a low  salt content that is at least free from  alkaline earths  softened  as fill or  top up water              with low salt content saline  El  conductivity at 25  C  uS cm   10 to 30  gt  30 to 100  gt  100 to 1  500  General requirements Clear  with  Clear  with  Clear  without  out sedi  out sedi  sediments  ments ments  pH value at 25   C 9 10 9 10 5 9 10 5  pH value according to the  lt 9 5  lt 9 5  lt 9 5  Drinking Water Order   Drinking Water Treat   ment Order  or local reg   ulations   Oxygen  02  mg   lt  0 1  lt  0 05  lt  0 02 1   values for constant op  litre    eration are generally sig   nificantly lower                  1The oxygen concentration in the re circulated water may be up to 0 1 mg litre  if suitable    inorganic corrosion inhibitors are used   20    5592 548 GB    5592 548 GB    Standard values for water quality  cont      Additional information                   with low salt content saline  Alkaline earths  Ca   Mg  mmol    lt  0 02  lt  0 02  lt  0 02  litre  Phosphate  PO4  mg   lt 5  lt 10  lt 15  litre  Phosphate  PO4  accord  mg   lt 7  lt 7  lt 7  ing to the Drinking Water litre  Order Drinking Water  Treatment Order  or local  regulations   Phosphate  PO4  for mg   lt 2 5  lt 5  lt 15  Viessmann hot water boi  litre  lers  When using oxygen bin   ders   Sodium sulphite mg       lt 10   Na2S03  litre     When using other suita    ble products  observe the  respective guidelines is    sued by 
16. the relevant sup   plier                  The VAT  V datasheet 1466 advises  that further oxygen binders are    offered as chemicals that may have    the following active ingredients     m Ascorbic acid    Carbohydrazide    m Diethyl hydroxylamine  DEHA     m Hydroquinone    m Tannic acid  These must be used with care  how   ever  as they can give rise to oxida   tion  cleavage and transformation  products under boiler operating condi   tions  Please refer to the above guide   lines for further information       Methyl ethyl ketoxime  Meko     21    Commissioning service reports    Commissioning service reports                      Commissioning   Service   Service  date   by    Service   Service   Service  date   by    Service   Service   Service  date   by    Service   Service   Service  date   by    Service   Service   Service  date   by     22       5592 548 GB    5592 548 GB       Commissioning service reports    Vitomax 200 HW spare parts    Note   When ordering spare parts  please quote the serial number and the boiler type   see type plate     Tick the required spare parts and state the number required    Obtain standard parts from your local supplier                             Serial number  Boiler type     23    Commissioning service reports    Vitomax 200 HW spare parts  cont                                                                                 0009       Serial number  Boiler type                    24       5592 548 GB    Vitomax 200 HW spare parts  co
17. ure  between 120 and 140   C  then open  the fittings on the water side    Dry the boiler thoroughly and fill with  desiccant  e g  silica gel  in accor   dance with the manufacturer s details     Flue gas side    Thoroughly clean and dry the sur   faces on the flue gas side    Maintain the alkaline balance of the  wash water  pH 8 9  in case of ammo   nia pH 10      Ensure that the desiccant does not  come into contact with the boiler  material  Then close the boiler again   Check in regular intervals whether the  desiccant is still able to absorb moist   ure     After the surfaces have been dried  completely  conserve them with a thin  film of graphite or boiled oil     Operating information  Shutdown  cont      Keep the surfaces dry during the idle  periods  by inserting desiccant  e g   silica gel  or by air changes from a  connected dryer      Further details    For further details  see the operating  instructions for conservation on the  water and hot gas side or the VAT  V  datasheets  no  1465  Oct  1978  and  the VGB  no  R116H  1981   or local  regulations      Maintenance information    The maintenance of a high pressure  hot water boiler is specified by the  TRD  or local  regulations     Danger   Boiler components that are not  thermally insulated can be sub   ject to high temperatures that  can cause burns    Take care with hot surfaces     5592 548 GB    5592 548 GB    Commissioning  inspection  maintenance    Steps   commissioning  inspection and maintenance  
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
télécharger le fichier PDF ici - MRC  USER`S MANUAL - Smith-Root  FICHE GUIDANCE : CREER UN BORNIER AVEC TRACE V2  Bag Boy Nav-C Series Instruction Manual-May08  Gebrauchsanleitung Operating Instructions  OLE DB User's Guide  Slope tHB – Bayer/Ciba Corning 270 & 800 Instruments CD  Modular-X User Guide    Copyright © All rights reserved. 