Series 90-30, Programmable Coprocessor Module
Contents
1. PCM RAM including the RAM Disk the RAM device is automatically cleared on the first power up after the PCM PROM is changed If RAM disk files must be preserved they must be stored to an attached personal computer PC using TERMF or PCOP before upgrading the PCM firmware and loaded to the PCM after the upgrade Power up Delay The first COMMREQ sent to a PCM after a power cycle needs to be delayed until the PCM has finished power up initialization See the Programmable Coprocessor Module and Support Software User s Manual for example PLC programs which delay before sending CCM and MegaBasic COMMREQs Problems Resolved by this Upgrade 1 PLC Reference Table Access by CCM CCM now queries the PLC CPU to determine the valid ranges for register YR discrete input I and discrete output Q references In previous firmware releases CCM would sometimes prevent access to valid references CCM Target ID Check Incompatible with Previous Versions In PCM firmware versions 2 51 and earlier the target ID fields in received CCM message headers are not checked to ensure they match the target ID of the most recent ENQuiry sequence This check was added in versions 2 52 through 3 02 Consequently a few existing CCM applications that generate messages with incorrect target ID values fail with those versions although they function correctly with earlier PCM firmware The CCM specification states that target ID fields in message headers must m
2. application is started by a PCMEXEC BAT file the PCM uses a default task number for MegaBasic unless PCMEXEC BAT explicitly specifies a task In this PCM firmware release as well as release 2 51 and all earlier releases the default task number for MegaBasic is seven 7 In release 3 00 the default MegaBasic task number is 15 When the MegaBasic application controls a PCM light emitting diode LED indicator the LED must be configured for control by MegaBasic The MegaBasic task number must be specified ina PCMEXEC BAT command If the task number for PCM firmware release 2 51 or earlier is assumed and MegaBasic runs as the default task number then the application will not be able to control the LED when running in a release 3 00 PCM This problem has been corrected in this release CCM Q N Enquiry Partial N or Q enquiry sequences no longer disrupt detection of valid N or Q enquiry sequences Any valid enquiry sequence will now be responded to regardless of prior transmissions Multidrop Enquiry In multidrop configurations switching from one slave to the next sometimes required a retransmission of the enquiry sequence A retransmission is no longer required Restrictions and Significant Open Problems 1 Invalid MegaBasic COMMREQ May Not Cause PLC Fault When a MegaBasic COMMREQ message is sent to the PCM and MegaBasic is not executing the expected fault message may occasionally not appear in the PLC fault table CCM Timeout
3. EQ plus the longer of the two COMMREQ timeout values is less than the PLC CPU watchdog timer setting If two or more WAIT mode COMMREQs can be sent during the same PLC sweep the total of the timeouts for all the COMMREQs must be considered See the Programmable Coprocessor Module and Support Software User s Manual Extra Fault When a WAIT mode COMMREQ which specifies an invalid PCM TASK ID is executed two Bad task id faults are posted to the PLC fault table NOWAIT I O and CTRL C If a MegaBasic program performs NOWAIT read and NOWAIT write operations simultaneously on the same serial port and the program is aborted with CTRL C or a MegaBasic STOP statement the PCM may hang if the program is restarted before the I O operations complete Additional Restrictions When Using a Release 1 0x Model 331 CPU 1 Multiple PCMs and or ADCs When two or more PCMs and or Access 90 Display Coprocessor modules ADCs which do not have identical catalog numbers are installed in a PLC system the PCM ADC modules may not function normally particularly after a short power cycle warm boot Loss of module faults may be posted to the PLC fault table MegaBasic Data Length If a MegaBasic program attempts to write more than 512 bytes of data to the PLC CPU ina single request the CPU watchdog timer will expire turning off the CPU OK LED Lost COMMREQ When two or more PCMs are present a COMMREOQ to either PCM may never complete If a ladde
4. February 16 1994 GFK 0494T IMPORTANT PRODUCT INFORMATION READ THIS INFORMATION FIRST Product Programmable Coprocessor Module Version 3 03 Catalog Number Hardware Identification EPROM Label IC693PCM300K PC3A1 388 020N3 03 U34 388 021K3 03 U35 1C693PCM301H PC3A2 395 020K3 03 1C693PCM311H J PC3C1 395 020K3 03 U39 Suffix change due to the following to add UL Class I Div 2 approval and C UL approval No hardware or software changes were required This is release 3 03 of the Programmable Coprocessor Module PCM It corrects several minor software errors in CCM communication The PCM supports application programming in the MegaBasic and C languages The module also communicates using the Communications Control Module CCM protocol Functional Compatibility PCM firmware version 3 03 is compatible with release 1 00 or later of PCM support software TERME IC641SWP063A and IC641SWP023A and release 2 04 or later of PCM development software PCOP IC641SWP061B and IC641SWP021A To develop MegaBasic applications you must use either TERMF or PCOP PCM firmware version 3 03 is compatible with release 1 03 of the Model 331 CPU IC693CPU331C or later However it is strongly recommended that all release 1 0x users upgrade to CPU release 2 04 IC693CPU331J or later This upgrade is available at no charge See Additional Restrictions When Using a Release 1 0x CPU 331 later in this document for a list of restrictions which ap
5. On Large Requests CCM requests for 3000 bytes or more of data may occasionally abort with a serial timeout error Error code 0102H Redirection of MegaBasic STDIN When MegaBasic is run with STDIN redirected from a file on an attached PC and execution of the MegaBasic program terminates for any reason MegaBasic is unable to read input characters from the PC file Redirecting STDIN from a PCM RAM disk file works correctly MegaBasic Serial Data Rate When both PCM serial ports are configured for a data rate higher than 9600 bps and a MegaBasic program transmits and receives characters on both ports at the same time the PCM watchdog timer may expire halting operation and turning off the OK LED CCM Data Rate Recoverable CCM communication errors such as dropped characters may occur when CCM initiates commands on both ports simultaneously at data rates above 9600 bps It is recommended that the data rate on either CCM port not exceed 9600 bps when using both ports as initiators New for this release Important Product Information GFK 0494T WAIT Mode COMMREQ Programming the COMMREQ function block for WAIT mode will degrade PLC sweep time and may halt the PLC CPU turning off its OK LED Do not use WAIT mode COMMREQs unless you have a compelling reason If WAIT mode is used it is absolutely essential that no COMMREQs are sent until the PCM is ready to receive them and that the sum of the worst case PLC sweep time without sending a COMMR
6. atch the most recent ENQuiry sequence but no harm is caused if they do not The check has been removed in version 3 03 CCM COMMREQ Fails with AI or AQ Status Word Previously when a CCM COMMERQO Status Word location in AI or AQ memory was specified normal CCM access to register YOR memory would sometimes fail In this release CCM operates correctly with status word locations in AI and AQ memory CCM Slave May Begin to EOT All Incoming Headers In previous PCM firmware releases a signal interruption on the Receive Data RD communication line would cause a CCM slave to enter a mode where it timed out while waiting for an incoming message header and then returned an EOT A reset of the module was necessary to recover This problem no longer occurs Important Product Information GFK 0494T Problems Resolved by Version 3 02 1 Critical Section Functions of the VTOS Operating System The VTOS Start_crit_sec and End_crit_sec functions now disable and enable maskable interrupts respectively as expected Previously the code had no effect on interrupts MegaBasic SYSLINK Error with Default String Dimensions Disabled The string argument of the PCM MegaBasic SYSLINK procedure is now explicitly dimensioned Previously turning off default string or array dimensions with PARAM 12 1 or PARAM 13 1 caused a runtime error from SYSLINK Problems Resolved by Version 3 01 1 Controlling PCM LEDs from MegaBasic When a MegaBasic
7. ply only when a PCM is used with a release 1 05 or earlier CPU There are no changes to these PCM publications MegaBasic Programming Language Reference Manual and PCM Development Software PCOP User s Manual for this release However new material will be added to the Programmable Coprocessor Module and Support Software User s Manual at the next revision See Changes and Additions to the User Manuals later in this document for information on these changes Important Product Information GFK 0494T Special Operational Notes 1 MegaBasic Defaults to Task Seven When MegaBasic is started from an R RUN command ina PCMEXEC BAT file and the command does not specify a task number the PCM operating system assigns MegaBasic to task number 7 This behavior applies to PCMEXEC BAT files created by the PCM operating system as well as files created by users and is consistent with PCM firmware version 2 51 and all earlier releases In PCM release 3 00 MegaBasic defaults to task 15 PCM Serial Ports Are not Isolated The two PCM serial ports are not isolated from module ground in either RS 232C or RS 422 RS 485 mode Common mode input signals must be limited to 12 volts or less for RS 422 RS 485 mode An external RS 232C RS 485 converter with common mode isolation is recommended for serial data paths longer than 50 feet Configuration Restriction A Programmable Coprocessor Module PCM may reside only in the main PLC rack PROM Change
8. r program attempts to send WAIT mode COMMREQs the CPU OK LED may go out after several minutes Ladder programs should always use NOWAIT mode COMMREQs To ensure that transactions are completed a time limit should be established for each COMMREQ using a PLC timer function block When a COMMREQ fails to complete before its timer expires the program can send it again PLC Configuration Change When an I O configuration is stored to the PLC or a Hand Held Programmer operation Autoconfig or clear PLC results in a change to PCM configuration data PCMs must be reset before the new configuration takes effect When the PCM configuration is changed to correct a Configuration mismatch PLC fault a PLC power cycle is required before the PCM will function normally Loss of module PLC faults for the PCM will occur between the time the new configuration is stored and the power cycle Changes and Additions to the User s Manual The text from Controlling PCM LEDs from MegaBasic under Problems Resolved by Version 3 01 in this document will be incorporated into the next revision of the Programmable Coprocessor Module and Support Software User s Manual