1. operating hours h h 0 4 29 10 s 1s 0 67 us 0 1 u Table 4 1 Measurement accuracy of the Sunny Boy SB2500U 11 NE 43 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual 5 Troubleshooting Our quality management strategy includes a constant quality improvement of our prod ucts We always are concerned to avoid all failures and malfunctions of our products The product you purchased was shipped after successfully passing numerous tests con cerning the operation behavior and the disconnection devices as well as long term heavy duty tests We recommend to conduct the following steps in case your PV plant does not operate correctly e check the connection to the grid and to the PV panels pay attention to all safety measures listed in chapter 2 Installation e check the blinking code on the lid of the Sunny Boy and compare the code with the blinking codes in chapter 4 Follow the countermeasures listed there if necessary contact the installer e check the Mode and Error messages in the monitoring system if present e contact the Sunny Boy service if the system malfunction persists The address is listed in the appendix In order to let your PV plant operate again as soon as possible it is essential to provide the following information SB2500U 11 NE 44 E SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual Information concerning the Sunny Boy e se
2. x Se i 7 SAVE THESE INSTRUCTIONS SB2500U 11 NE 3 B SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual IMPORTANT SAFETY INSTRUCTIONS e All electrical installations shall be done in accordance with the local and national electrical codes ANSI NFPA 70 e The Sunny Boy contains no user serviceable parts Please return the unit to an SMA authorized Service Center see page 56 for maintenance e Before installing or using the Sunny Boy please read all instructions and cautionary markings in the technical description and on the Sunny Boy and the PV array e Connecting the Sunny Boy to the electrical utility grid must only be done after receiving prior approval from the utility company and performed only by qualified personnel e Completely cover the surface of all PV arrays with opaque dark material before wiring them PV arrays produce electrical energy when exposed to light and could create a hazardous condition e On top of the device you can find the heat sink of the Sunny Boy with potential temperatures of over 175 F 80 C To reduce the risk of burns do not touch SAVE THESE INSTRUCTIONS SB2500U 11 NE 3 4 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual Table of Contents 1 IMrOdOCON ERE rere ste Retr Renee TUUM 6 2 HASTA UGH NETT ET 7 2 1 What Must Be Done in Case of Transport Damages seessssss 7 2 2 Placement of the Sunny
3. Torque wires with torque of 35 in lb e Ensure all connections are correctly wired and properly torqued s 4 Go sj uU be E pn o nnn E E 5 s Ay 81 E wi gt DENN UM Positive plug Negative plug k jd g p DC conduit and wiring Fig 2 9 DC connection socket SB2500U 11 NE 19 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual 3 Commissioning Safety Notice ILZ NOTE Make sure that nothing is on top of the heat sink of the Sunny Boy when it is running WARNING The heat sink can get very hot i e over 175 F 80 C eS NOTE Make sure that all fittings are sealed and all openings on the bottom are closed with the seals e When putting the lid on make sure the seal in the inner side of the lid is placed correctly When screwing the inner screws make sure that the thread in the Sunny Boy case is not damaged by tilted screws Under certain conditions the enclosure type NEMA 4X cannot be guaranteed any more When mounting the Sunny Boy outside moisture can get into the device and damage the electronics WARNING Make sure that the lid is closed before applying power to the Sunny Boy e Ensure that all C and DC wiring is correct SB2500U 11 NE 20 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual First switching on Please follow the order described when commissioning the device Fig 3 1 Diagram of commissioning provides a sequenc
4. 2 The yellow LED Failure indicates an internal or external failure that keeps the in verter from feeding the grid The specific causes for this and how to avoid them are described in chapter 4 3 Failure Indication The red and yellow LED combined indicate that the internal Ground Fault Detector and Interupter GFDI has detected a ground fault in the PV panel A description of this situation and what has to be done in that case is given in chapter 4 2 SB2500U 11 NE 24 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual LMT Betrieb Operation Erdschlu SWR 2500 Earth Fault Photovoltaik Stringwechselrichter St rung gt Photovoltaic string inverter Failure Fig 4 1 Front view of Sunny Boy 2500U Description of the symbols used in the following section LED off LED on once per second LED on three times per second LED on with short interruptions 75 on 25 off LED on Not important OL E KI SB2500U 11 NE 25 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual tor amp standby night input voltage lt 120 V 8 8 initialization input voltage 120 V 240 V changing operating condition or manually initi ated condition waiting starting conditions are being checked checking grid feeding grid normal operation MPP or constant voltage mode Reduction of power fed to the grid due to in creased temperature of the heat sink insulat
5. Boy ccceceeeeeeeeeeesseeceeeeeeeeeeeesseaaeeeaeeeeeeeeeeeeenaeaaes 8 2 3 Electric CONE LOL ooo DLE 12 2 3 1 Preparation of the electric connection seeeeeeeesesesseseeeeeeee 14 2 3 2 Connection to Electrical Utility Grid esssesesseeeeeeee 16 SEMEE Pe eoo 20 4 Operation and Failure Indication LEDS eeeeeeeeeeseseseeseeeee eere 24 4 1 Opsratlon AGIAN secessus Co Ei Eg FORD Ee Ee EC Fei FORE CERERE EE 27 4 2 Kround EabldltdmdiGalOE to sius odorum tota t dote ain Met ces ee sal ret ate 30 4 3 FEalltire IndioatOfiz 3 iuuat Mata S dut cc ao e does As 31 4 4 Opening and closing of the Sunny Boy ssssssssee 36 4 5 Upgrading or modification of the Sunny Boy interface 39 4 6 Measuring Channels and Messages ssessseseeeennnn 41 4 7 Measurement PICCISION ousdesdaciedei dnb oed danadana daidan 43 Troubleshooting iriigh a au au e u tutt cost E EPI E ECL 44 Warranty Regulations and Liability eee 46 Technical DAA T P 48 7 1 4 Minimum MPP voltage of the PV panel eese 49 8 PDD IIGIK qae VM Ma prc 56 SB2500U 11 NE E 5 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual 1 Introduction The SMA Sunny Boy is a string inverter for grid tied operation With this manual the Sunny Boy can be installed a
6. Service e eMail mailto info SMA de e Internet http www SMA de Appendix drilling template SB2500U 11 NE 60 SMA Regelsysteme GmbH
7. range There is a fixed ratio between the minimum MPP voltage V min the Sunny Boy loads onto the PV panel and the grid voltage V as shown in Fig 7 1 Depending on the current grid voltage the minimum DC voltage is assessed and fixed This flexible MPP voltage range lets the user make optimum use of the specific device characteristics while the energy yield is increased 270 256 Volt DC 260 250 240 234 Volt DC N Co eo N eo 207 Volt DC eo VMWpp min V N N 200 190 180 170 211Vot AC 240 VoIt AC 264 Volt AC 160 T T T T 200 205 210 215 220 225 230 235 240 245 250 255 260 265 Vac V Fig 7 1 Minimal MPP voltage as a function of grid voltage SB2500U 11 NE 49 SMA Regelsysteme GmbH Sunny Boy 2500U Input Values of the Sunny Boy DC side Input voltage MPP range depending on Yey Max open circuit voltage under all conditions Max input current Max DC power Recommended PV panel power Voltage ripple All pole disconnection on DC side Pole confusion protection Ground fault protection ev ACnom SB2500U 11 NE 50 Installation and Operator s Manual 234 V 550 V DC Vaos 600 V DC 13A DC Pas 2710 W DC upto 3000 W V 10 6 optional external DC breaker PP short circuit diode ground fault detection I gt 1000 mA Dif SMA Regelsysteme GmbH Sunny Boy 2500U I
8. reduce the risk of electric shock do not perform any sevicing other than specified in this technical description unless you are qualified to do so When working on the Sunny Boy follow the instructions below 1 Separate the Sunny Boy from the grid by opening the 240 Volt AC circuit breaker in the main fusebox WARNING Make sure the main 240V breaker in the main utility breaker box is switched OFF 2 Switch the DC breaker in the DC disconnect enclosure OFF WARNING Wait for approx 5 minutes until internal voltage has dis charged after shutting down the DC voltage on the Sunny Boy SB2500U 11 NE F 36 gt SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual 3 Take off the lid by removing screws 1 4 see Fig 2 6 on the lid M5 You now have the opened Sunny Boy in front of you see Fig 2 7 and can see the posi tion of components and clamps relevant for you You will find e The internal grid fuse WARNING For continued protection against risk of fire replace only with same types and rating of fuse The type is Littelfuse 314015 15AMP 250 V AC e The control system board with the socket for the piggy back board for the communica tion To install the new communication components read chapter 4 5 SB2500U 11 NE 37 B SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual Closing of the Sunny Boy e When putting the lid on make sure the seal in the inner side
9. times The code is sent three times If the failure persists the indication is repeated The input voltage is too high The PV panels are generating a voltage higher than the permissible specified voltage WARNING Disconnect the PV Panels from the Sunny Boy immediately Too high input voltage can destroy the Sunny Boy Have the circuits of your PV panels checked SB2500U 11 NE 34 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual Blinking code 5 Device failure Operation X e amp Earth Fault Q Q Q Failure D 69 9 The yellow failure indication LED is activated for 5 seconds is out for 3 seconds and then blinks five times The code is sent three times If the failure persists the indication is repeated The Sunny Boy is in a condition that makes it impossible to return to normal operation and is most likely defective NOTE The Sunny Boy has to be checked by a qualified technician SB2500U 11 NE 5 35 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual 4 4 Opening and closing of the Sunny Boy Normally the Sunny Boy operates fully automatically and maintenance free Should the device nonetheless be opened e g for e upgrading or modification of the Sunny Boy interface e control of internal AC fuse follow the instructions given below Opening of the Sunny Boy WARNING These servicing instructions are for use by qualified personnel only To
10. 175 feet 57 m cable with a cross section of AWG 10 The total impedance of the grid plus the interconnecting ac cables should be less than 1 25 Ohm SB2500U 11 NE S 1 6 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual oe E H hy gt x a NIC as AA WP bare e ERE uL iii CD MR yee Ae ci nm y ram m t k one d a AN se BA net tne ve Crees eime ie o TUM d ec pa Pd wpe cea dew emi end e eeneves t hice rud as ILI Fig 2 8 AC connection socket e Connect the main 240 Volt AC breaker box to the Sunny Boy by a 1 2 conduit e Insert the conduit fitting in the very right opening of the Sunny Boy Fasten the fitting on the inside of the Sunny Boy with the nut e Pull the wires through the conduit into the interior of the Sunny Boy e Connect the wire L1 to the terminal labeled L in the Sunny Boy see Fig 2 8 e Connect the wire L2 to the terminal labeled N in the Sunny Boy e Connect the equipment grounding conductor to the terminal labeled PE in the Sunny Boy e Torque wires with torque of 35 in Ib e Ensure all connections are correctly wired and properly torqued SB2500U 11 NE 17 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual Connection of the PV panels to the DC disconnect enclosure WARNING Completely cover the surface of all PV arrays with opaque dark material before wiring them PV arrays produce
11. 26 mm are ac cepted by the AC and DC terminals on the printed circuit board WARNING The connection of the Sunny Boy to the DC voltage from the PV string and the AC voltage of the utility must be done in the order de scribed here This ensures that the disconnecting of contacts as well as hazardous voltages during the installation are avoided e Connect the Sunny Boy to the electricity grid e Connect the PV strings to the DC disconnect enclosure e Connect the DC disconnect enclosure to the Sunny Boy e Connect the utility by switching all breakers ON To disconnect the Sunny Boy from the system first turn all breakers and switches OFF Then disconnect the various conductors in the reverse order listed above SB2500U 11 NE P 1 3 i SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual 2 3 1 Preparation of the electric connection Remove all screws 1 4 size M5 see Fig 2 6 and take off the lid When removing these screws be sure to save the special lock washers and reinstall them to properly ground the front panel Sunn Boy SWR 2500 3 Fig 2 6 Front view of the Sunny Boy 2500U You now have the opened Sunny Boy in front of you see Fig 2 7 and can see the position of components and clamps relevant for you You will find e The internal grid fuse WARNING A defective grid fuse has to be replaced only with same types and rating of fuse in order for continued protection against risk o
12. 500 3000 63 50 mm distance between the holes on the top 217 50 mm position of the holes on the top for 6 mm screws Total width of the Sunny Boy 434 50 mm A Please note mount the Sunny Boy Never mount the tilted to the back or Sunny Boy tilted vertical to the front hA XX bottom hole 6 mm diam Ses Total height of the Sunny Boy 295 50 mm E o 19 o N A o 2 o o z c o E a o e E xm v ni S E Fig 2 2 Picture of drilling template original template in appendix SB2500U 11 NE T 1 0 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual Preparing the Mounting The Sunny Boy is mounted on its back side with the 3 metal straps For that 3 screws and 3 according dowels wall anchors are necessary The screws and dowels are not included We recommend 6 mm screws and 8 mm dowels EY NOTE For outside mounting use stainless steel screws Use a plastic washer in order to avoid scratching the paint LULU Fig 2 3 Side view of the mounting to wall Metal straps for mounting The top straps take the load the bottom is screwed down in order to prevent the tilting off the wall Mounting to wall Mark the holes with the drilling template e Drill the holes and put in the wall anchors put in the screws of both top holes and screw them in until ca 4 mm
13. Failure Operation amp Earth Fault amp Failure The yellow failure LED is permanently on This is a failure of the utility monitoring or the automatic disconnection device MSD The Sunny Boy has detected a failure in the disconnection device and has suppressed the utility interaction on startup The Sunny Boy must be checked by service personnel and can only be put back to operation after a thorough checkup SB2500U 11 NE 31 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual Blinking code 2 Grid Failure Operation X Q Q Q Earth Fault 5 Q 69 Q Failure gt 29 9 9 gt Bg 3s is 1s i The yellow failure indication LED is on for 5 seconds is out for 3 seconds and then blinks twice The code is sent three times If the failure persists the indication blinking code is repeated The Sunny Boy is indicating a failure which has one of the following reasons e Low grid voltage V see table 9 2 AC min e X High grid voltage gt Vicma see table 9 2 e Low grid frequency lt f see table 9 2 e High grid frequency gt f see table 9 2 AC max e Drastic grid frequency change Check the utility check the function of other electric consumers and check the fuse of the mains connector to the Sunny Boy NOTE Have the grid connection to the Sunny Boy checked by a qualified electrician Check the correct connection and the fuse in the Sunn
14. Only a qualified elec trician may work on the device especially open it While upgrading the Sunny Boy interface the operator can get into touch both with elec tronic components and components carrying lethal voltage Faulty upgrading can lead to damage at the device and danger to people by electric voltage Therefore the device may only be upgraded by qualified personnel or the SMA service WARNING Only work on the Sunny Boy when it is disconnected from the grid and is sufficiently discharged Follow ESD protection countermeasures when modifying the Sunny Boy Electronic components are sensitive to electrostatic discharge To protect them you have to be on the same electric potential Discharge the electrostatic charge by touching the grounded case before touching an electronic component otherwise you run a great risk in destroying your electronics SB2500U 11 NE Fj 39 E SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual Open the device as described in chapter 4 4 Remove the piggy back that is installed on the system control board Only for installation of an RS232 or RS485 board Remove the light blue resistors see Fig 2 7 on the system control board by cutting them out with a wire cutter Only for installation of a board for Powerline Communication Please make sure that the light blue resistors see Fig 2 7 are plugged onto the system control board If not wires corresponding
15. Sunny Boy SWR 2500U Installation and Operator s Manual Issue 1 2 Grid Tied String Inverter for Photovoltaic Systems SB2500U 11 NE3801 Sunny Boy 2500U Installation and Operator s Manual Document Issue Comments Number and Alteration SB2500U Review 11 EE4900 11 NE3801 A Changes due to faulty documents or improvement of the documentation B Changes maintaining full or upward compatibility C Changes limiting or excluding compatibility es D 03 on Basler SB2500U 11 NE 2 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual IMPORTANT SAFETY INSTRUCTIONS This manual contains important instructions that shall be followed during in stallation and maintenance of the Sunny Boy To reduce the risk of electrical shock and to ensure the safe installation and operation of the Sunny Boy the following safety symbols have been placed throughout this technical description to indicate dangerous conditions and im portant safety instructions WARNING This indicates a fact or feature very important for the safety of gt the user and or which can cause a serious hardware defect if not applied appropriately Use extreme caution when performing this task NOTE This indicates a feature that is important either for optimal and a comfortable usage or optimal operation of the system Follow instructions closely EXAMPLE This indicates an example ES s y A
16. ad all instructions and cau tionary markings in the technical description and on the Sunny Boy and the photovoltaic array WARNING All electrical installations shall be done in accordance with all local electrical codes and the National Electrical Code NEC ANSI NFPA 70 WARNING Connecting the Sunny Boy to the electrical utility grid must only be done after receiving prior approval from the utility company and gt performed only by qualified personnel 2 1 What Must Be Done in Case of Transport Damages The Sunny Boy inverters are thoroughly checked before they are shipped Even though they are delivered in a sturdy packaging which can be recycled the inverters can be damaged which is the forwarding company s fault in most cases Please inspect your inverter thoroughly after it is delivered If any damages can be detected on the packaging that could lead to the conclusion that the contents is dam aged or if you detect that the inverter is damaged please immediately notify the for warding company SMA or your local supplier can help you in this matter In any case the declaration of transport damage must be made within 6 days upon receipt of the product and must be stated in writing directly to the forwarding agent If it is necessary to return the in verter to the manufacturer please use the packaging the inverter was sent in SB2500U 11 NE 7 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Oper
17. again so that the Sunny Boy is supplied with the DC voltage SB2500U 11 NE 21 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual e The Sunny Boy switches to fully automatic normal operation The green LED is blinking Should the red LED still be on the GFDI fuse is defective and has to be replaced You will find a description of the correct type in chapter 4 2 Remove Switch DC ON and GFDI Fuse wait 20 seconds Switch DC OFF and Remove the wait 5 minutes ground fault Switch DC OFF and wait 180 seconds Insert GFDI Fuse Switch DC ON and wait 30 seconds Switch DC OFF and changing wait 5 minutes defective GFDI Fuse Green LED blinking Normal operation grid feeding after 5 minutes Fig 3 1 Diagram of commissioning SB2500U 11 NE 3 22 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual If the input voltage is high enough the Sunny Boy should start to feed inverted PV power fully automatically to the grid once enough power is coming from the PV modules The design of the Sunny Boy makes sure that its internal consumption is as low as possible The Sunny Boy requires a maximum 7 W internal consumption which it takes from the PV panel If you measure the voltage of the PV modules you must keep in mind the inverter s internal consumption that will have an effect on your measurement with lower solar radiation The open circuit voltage of the PV pa
18. are sticking out e Hang the inverter into the two top screws Fasten the bottom screw This will prevent lifting of the inverter case Check the mounting of the inverter SB2500U 11 NE 1 1 2x SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual 2 3 Electric Connection The electric connection of the Sunny Boy can be done once the device is correctly mounted in its position 600V DC 240 Volts AC 60Hz System Note When three strings of modules are used overcurrent protection may be required in each string to comply with UL Standard 1703 and the markings on the back of each PV module Fig 2 4 Simplified electrical wiring diagram of the PV system GFDI Fuse GFDI FUSE 1A 600 V DC AC ms 60 Hz Communication DC Connection undecHon AC Connection oc Fig 2 5 Underside view of the Sunny Boy SB2500U 11 NE E 1 2 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual WARNING All electrical installations shall be done in accordance with all local electrical codes and the National Electrical Code NEC ANSI NFPA 70 Use no 14 AWG minimum 90 C 194 F copper wire for all connec tions with the Sunny Boy Voltage drop and other considerations may dic tate that larger wire sizes be used The AC grid and the input from the DC disconnect enclosure are connected to the inverter inside the case Cables with wire sizes up to 10 AWG 5
19. ator s Manual 2 2 Placement of the Sunny Boy The Sunny Boy is a sophisticated electronic device and is therefore sensitive to hu midity within the case IS NOTE If the Sunny Boy is placed outside the humidity during the installa tion should be as low as possible pay special attention that it does not rain If moisture is enclosed in the case it will eventually condense within the device which could damage the electronics A suitable position must be found for the inverter while the PV plant is designed In the following you will find a summary of the most important criteria Criteria for device mounting e Due to the high protection class NEMA 4X of the enclosure the installation is possible indoors as well as outdoors e If possible do not expose the inverter to rain despite NEMA 4X e Keep the DC cabling from the solar panel to the inverter as short as possible e X Avoid installation in the living area because a slight noise emission is possible e Avoid mounting on resonant parts e g thin wooden panels plaster panels etc The Sunny Boy tends to slightly vibrate when under load e Provide accessibility for installation and later service e Installation in eye height allows to easily read the operating LEDs or the Sunny Display SB2500U 11 NE 8 m SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual A CAUTION Please note the following points in any case The mounting backgr
20. e chart for commissioning D NOTE Following this procedure you will make sure that the PV panel is iso lated from earth and the GFDl fuse is not defective without using any addi tional measuring instrument e Remove the GFDI fuse from the Sunny Boy see Fig 2 5 e Connect the grid voltage by switching ON the main 240 V AC circuit breaker of the supply lead e Uncover the PV panel At sufficient insolation the PV panel produces the re quired output power for supplying the Sunny Boy e Switch ON the DC circuit breaker in the DC disconnect enclosure Now the Sunny Boy is supplied with the DC voltage and starts to operate e If the PV panel is isolated from earth first the yellow and red LEDs and after approx 20 seconds only the red LED is on at the Sunny Boy If you have communication equipment you will be displayed the GFDI Fuse open failure Should both the red and the yellow LEDs still be on there is a ground fault of the PV panel If you have communication equipment you will be displayed the EarthCurrentMax failure The ground fault has to be removed Then the com missioning procedure described above has to be repeated until only the red LED is on e When you have made sure the PV panel is isolated from earth only red LED on switch the DC breaker OFF e Wait until the LEDs at the device have turned off max 5 minutes e Screw the GFDl fuse into the fuse holder at the Sunny Boy again e Switch the DC breaker ON
21. electrical energy when ex posed to light and could create a hazardous condition Depending on the type of PV module used it is possible to connect one single string or several parallel strings Therefore there are three connections for both the and the pole Within the device these connections are connected in parallel each WARNING Before connecting the connectors of the PV panel to the DC disconnect enclosure check the correct polarity and admissible PV panel voltage between the and the cable connectors of the PV panel The PV panel open circuit voltage must be below or at most equal to 600 V DC V x 600 V DC under all conditions Please read chapter 7 1 1 SB2500U 11 NE 1 8 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual Connection of the Sunny Boy to the DC disconnect enclosure e Install the DC conduit from the DC disconnect enclosure to the Sunny Boy e Insert the conduit fitting in the very left opening of the Sunny Boy Fasten the fitting on the inside of the Sunny Boy with the nut Do the same at the DC dis connect enclosure e Ensure all circuit breakers in the DC disconnect enclosure are in the OFF position Route the wires from the DC disconnect enclosure through the conduit and into the Sunny Boy Connect the positive wire to the terminal block labeled with see Fig 2 9 Connect the negative wire to the terminal block labeled with see Fig 2 9
22. er fed to grid Zac grid impedance Vpv PE PV voltage to earth Ipv current from PV panels E Total energy yield h Total total operation hours Power On total system start ups Serial Number Mode Error Mode Messages Sunny Boy serial number operating mode failure description for mode disturbance Stop manual system stop Offset offset calibration of the electronics Waiting grid switching on conditions are not fulfilled yet Grid monitoring MPP Search MPP SB2500U 11 NE checking grid grid impedance PV voltage is determined and set Sunny Boy is in MPP mode 41 SMA Regelsysteme GmbH Sunny Boy 2500U V Const Derating Disturbance Error messages F Bfr Srr F EEPROM F EEPROM dBh F Fac Bfr F Fac Srr F dZac Bfr F dZac Srr F Imax F Shut Down F MSD UAC F MSD FAC F MSD Meas F K1 Close F K1 Open F EarthCurMax S F EarthCurMax B F MSD ZAC F Offset F MSD Timeout F Vac Bfr F Vac Srr F VpvMax F Zac Bfr F Zac Srr F Watchdog F GFDI Fuse Ope F ROM SB2500U 11 NE Installation and Operator s Manual Sunny Boy is in constant voltage MPP mode reduction of the grid feeding power failure communication between micro controllers is failing EEPROM cannot be read or written on EEPROM cannot be read or written on BFR frequency measurement value out of tolerable range SSR frequency measurement value out of tolerable range BFR impedance measurement value out of tolerable range SSR impedance measure
23. f fire The type is Littelfuse 314015 15 AMP 250V AC The control system board with the socket for the Piggy Back board for the communication E Terminal for the AC connection e Terminals for the DC connection SB2500U 11 NE 14 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual hb 4 AC Connection d Grid Fuse HJ TA Fig 2 7 Interior of the Sunny Boy 2500U SMA Regelsysteme GmbH SB2500U 11 NE 15 Sunny Boy 2500U Installation and Operators Manual 2 3 2 Connection to Electrical Utility Grid The Sunny Boy must be connected to the grid with 3 cables e with two phases L1 and L2 and one equipment grounding conduc tor Protective earth PE WARNING Make sure the main 240 V breaker in the main utility breaker box is switched OFF before you connect the AC terminal block The grid impedance value at the connection point should be as low as possible to avoid an increase of the AC voltage to non permissible values while the Sunny Boy feeds to the grid This also results in a higher system efficiency EXAMPLE The impedance is the sum of the electricity grid impedance at CE A i E house distribution and all impedance values of cables and clamping IN OE points NB Impedance values are e ca 0 44 Q for a 70 feet 16 4 m cable with a cross section of AWG 14 e ca 0 40 Q for a 100 feet 33 m cable with a cross section of AWG 12 e ca 0 43 Q for a
24. he cells is at its lowest point Therefore it has to take into account the lowest possible ambient temperature of the PV panel when planning the PV plant Based on this temperature and knowing the type of PV modules used you can then determine the maximum open circuit voltage of the PV panel You can enter these data into our EXCEL tool GenAu and check whether the maximum ad missible input voltage of the Sunny Boy is not exceeded under any possible operating conditions You will find this tool in the Internet for download at http www SMA de ftp energietechnik sunnyboy GenAu GenAu exe WARNING The MPP voltage of the connected PV modules may not fall below the specified range at 158 F 70 C V gt min input voltage range NOTE The Sunny Boy can tolerate a current higher than the specified icy current as long as the voltage is within the specified range SB2500U 11 NE 48 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual 7 1 1 Minimum MPP voltage of the PV panel Often a fixed lower MPP voltage limit of the inverter is not useful when the cells of the PV panel have very high temperatures This means the MPP voltage of the PV panel de creases and the inverter cannot feed the maximum power from the PV panel to the low voltage grid The inverter remains at the lower limit of input voltage and cannot follow the MPP of the PV panel Therefore the Sunny Boy has a flexible MPP voltage
25. he right to refuse warranty services Conditions The device will be repaired at SMA s discretion in its works without invoicing material and work or a replacement resp compensation device will be delivered The rejected device is to be sent back to SMA in the original packing or in a transport pack ing of equal quality The customer has to grant SMA the necessary time and opportunity to repair the defects SB2500U 11 NE 46 5 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual Exclusion of Liability Excluded are any warranty claims and liabilities for direct or consequential damages due to e transportation damages e improper installation or commissioning improper alterations modification or repairing attempts inappropriate use or operation e insufficient air supply to the device e any installation and operation beyond the scope covered by according relevant safety regulations VDE UL1741 NEC etc e or force majeure lightning surge voltage storm fire NOTE We cannot guarantee the proper function of the data transmission EJ via mains lead Powerline modem in case it is carried out in electric grids with high harmonic distortion resp high frequency line distortions like e g industrial power supply grids or in the neighborhood of irregular consumers unshielded motors switching power supplies converters etc Further more the simultaneous operation of babyphone
26. icity grid either in MPP or in Constant Volt age operation Additionally it is in the derating mode due to increased temperature of the heat sink SB2500U 11 NE E 29 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual 4 2 Ground Fault Indicator Isolation failure Green LED off Red LEDon Yellow LED on This is the result of a ground fault of the PV panel The inverter then has to indicate this condition and disconnect from the grid The inverter has to be reset manually it cannot restart automatically CAUTION The PV array must be inspected for ground faults Please have a look at chapter 3 First switching on If the ground fault of the PV panel is removed the inverter switches from permanent de vice disable to GFDI Fuse open failure and the yellow LED is off The red LED is still on Now the following must be done Defective GFDI fuse GreenLED off Red LED on Yellow LED off The failure GFDI Fuse open is displayed If an intact fuse is then installed the inverter restarts operation The GFDI Fuse open failure persists in case the fuse is defective WARNING For continued protection against risk of fire replace only with same types and rating of fuse The type is Littelfuse KLKD 1 AMP 600 V AC DC SB2500U 11 NE 30 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual 4 3 Failure Indication Consistent
27. ion failure ground fault of the PV panels see chapter 4 2 failure GFDI fuse is defective see chapter 4 2 failure internal or external failure exact description depending on blink code see chapter 4 3 e Consistent Failure A failure of the utility has occurred Table 4 1 Operation indication overview SB2500U 11 NE E 26 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual 4 1 Operation Indicator Standby night C9 GO all LEDs are off Q The Sunny Boy is in Standby mode The input voltage is too low V 120 V for supplying the Sunny Boy control system with enough power Initialization all LEDs are on The Sunny Boy control system is initializing The string voltage to the inverter is between approx 120 V and 240 V The supply is suf ficient for the system control and not quite sufficient for feeding to the grid Data trans mission is not possible NOTE In some seldom cases bad weather low solar radiation the LEDs 3 can go on all at once and off again This blinking results from the fact that the incoming radiation is not high enough for the Sunny Boy to keep it stable Note This is not a malfunction SB2500U 11 NE 27 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual Stop 69 Green LED blinks 3 times per second C9 Red LED off G9 Yellow LED off The inverter has stopped operation among other tasks the measure
28. isting Mark only at the factory under UL s Conformity Assessment Service Program to the above products which are constructed as described below Identical to the subject model which was submitted to UL for this investigation the UL records covering the product will be in the Conformity Assessment Services Inspection Procedure File E210376 Volume 1 based on the completion of the Initial Production Inspection IPI that was performed on May 4 2001 To provide the manufacturer with the intended authorization to use the UL Mark the addressee must send a copy of this Notice and all attached material to each manufacturing location as currently authorized in the appropriate UL File Procedure This authorization is effective for 90 days only from the date of this Notice and only for products at the indicated manufacturing locations Records covering the product are now being prepared and will be sent to the indicated manufacturing locations in the near future Please note that Conformity Assessment Services Procedures are sent to the manufacturers only unless the Applicant specifically requests this document E Please note Within Canada there are federal and local statutes and regulations requiring the use of bilingual product markings It is the responsibility of the manufacturer lor distributor to comply with this law As such the markings provided in the UL Conformity Assessment Service Procedure may include only the English version Please co
29. ment value out of tolerable range internal over current internal over current continuous different values between BFR and SRR for grid voltage different values between BFR and SRR for grid frequency different values between BFR and SRR for dl Fac Vac or Zac Relay test failed Relay test failed SRR earth current between PV and GND is out of tolerable range BFR earth current between PV and GND is out of tolerable range different values between BFR and SRR for grid impedance Offset check for grid voltage failed BFR or SSR controller failure BFR grid voltage measurement value out of tolerable range SSR grid voltage measurement value out of tolerable range PV input voltage out of tolerable range BFR grid impedance measurement value out of tolerable range SSR grid impedance measurement value out of tolerable range Watchdog for operation control triggered The GFDI Fuse is defective Failure of Read only memory test 42 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual 4 7 Measurement Precision Any kind of measurement always depends on the accuracy The reproducibility of the measurement values is conceived for an ambient temperature of 77 F 25 C Other temperatures must be evaluated with respect to the inaccuracy resulting from these dif ferent temperatures Range Resolution Maximal fail ure Display Measurement O 77 F energy yield E kWh 0 4 29 10 Wmin 1 Wmin 20 Wmin 3
30. ment electronics is calibrated Subsequent condition is Waiting Stop condition can be initiated by the user with the Sunny Boy Control or the program Sunny Data The Sunny Boy remains in this condition until set to MPP Operation or Constant Voltage Operation Waiting Grid Monitoring Q Green LED blinks once per second C9 Red LED off G9 Yellow LED off The Sunny Boy is checking the utility concerning its suitability for feeding electricity start ing voltage starting time and begins to monitoring iss NOTE If the Sunny Boy fails to connect to the utility 3 times in a row it will wait for 10 minutes before the next attempt SB2500U 11 NE 28 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual Operation Green LED on G9 Red LED off G9 Yellow LED off all LEDs are off The Sunny Boy is feeding the local electricity grid either in MPP or in Constant Volt age operation MPP operation default setting The Sunny Boy pushes the voltage from the PV modules to the voltage with the maximum output power e Constant Voltage operation The voltage from the PV modules can be set to a fixed value This value is transmit ted to the Sunny Boy with the Sunny Boy Control or with the Sunny Data software The parameter is V Konst Derating Green LED blinks 75 ON 25 OFF G9 Red LED off G9 Yellow LED off The Sunny Boy is feeding the local electr
31. nd operated in a safe way This installer s guide is used as reference for the commissioning and as guideline on how to use all functions of the inverter optimally and how you can extend your existing PV plant Supplementary grid feeding includes the conversion of the DC voltage from the PV panel to grid compatible AC voltage with so called inverters and the subsequent connection to the electricity grid in the house distribution Here the electricity from the PV modules provides all consumers with electric power household devices lights etc In case that not enough power is produced the addi tionally necessary power is obtained from the grid In case that there is a surplus of power this surplus is fed into the local grid and is therefore available for other con sumers This way every single kilowatt hour is utilized and the electricity company s power systems are relieved In the most simple case a PV plant therefore consists of two basic components the PV panel and the inverter Va Gy lt i Photovoltaic Sunny Boy Modules String Inverter MT Electrical Grid Fig 1 1 Grid tied string inverter application For a more detailed technical description of the Sunny Boy and its functionality please read Sunny Boy 2500U Technical Description SB2500U 11 NE 6 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual 2 Installation WARNING Before installing the Sunny Boy re
32. nel will therefore not be displayed The internal consumption is negligible for the voltage measurement with higher solar radiation The operating state of the Sunny Boy will be indicated with three LEDs integrated into the lid The meaning of the LEDs will be explained in chapter 4 Operation and Failure Indication LEDs SB2500U 11 NE 23 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual 4 Operation and Failure Indication LEDs The inverter normally operates automatically without user interaction and without any maintenance The inverter automatically turns itself off when a grid feeding is not possible e g at night The Sunny Boy automatically starts its grid feeding the next day once the solar radia tion is high enough The inverter goes to standby mode if the radiation and the result ing electric input energy is too low and is therefore always ready for operation Each time the Sunny Boy starts up it runs a number of self test and safety proce dures which the user does not notice The user can obtain the inverter s operating status from the 3 integrated LEDs on the lid see Table 4 1 Operation indication overview The green LED Operation describes the current operation of the Sunny Boy see chapter 4 1 Operation Indicator The red LED warns the user that the GFDl fuse is defective A description of this situation and what has to be done in that case is given in chapter 4
33. nstallation and Operator s Manual Output values of the Sunny Boy utility side Nominal output power Maximal output power Operating range utility voltage Operating range utility frequency Total Harmonic Distortion THD Phase shift ref fundamental Utility monitoring Islanding protection Ground Fault Protection All pole disconnection utility Short circuit protection Overvoltage classification Testing voltage 50 Hz Testing voltage for surge 1 2 50 us External Interfaces Data transmission via Powerline Data transmission via separate cable SB2500U 11 NE 51 ae 2200 W AC B 2500 W AC ACmax Ve 211 264 V AC f 59 3 60 5 Hz AC THD 4 96 with Kr 2 Pac gt 0 5 Pa nom Q 0 V f in accordance with UL 1741 AC AC l in accordance with UL1741 independent disconnection MSD redundant design double current controlled III 2 88 kV 1 s 4 kV serial interface 6 kV optional optional electrically separated RS232 RS485 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual Power Consumption Internal consumption during operation Internal consumption during stand by Efficiency Maximum efficiency Ambient Conditions Tolerable ambient temperature Rel humidity Size amp Weight Enclosure type Size w x h x d Weight Certifications EMI Utility interaction Utility monitoring L
34. ntact us if you necd assistance with translations or in determining which markings are appropriate for your product Products produced which bear the UL Mark shall be identical to those evaluated by UL and found to comply with UL s requirements If changes in construction are discovered orn icd authorization to use the UL Mark may be withdrawn and products that bear the UL Mark may have to be revised in the field or at the manufacturer s facility to bring them into compliance with UL s requirements Respectfully Reviewed by r ee ims Lipson Stephen T Gardner Ext 41576 Timothy P Zgonena Ext 43051 Sr Project Engineer Sr Project Engineer Conformity Assessment Services 3013MNBK Conformity Assessment Services 3013MNBK E mail Stephen T Gardner us ul cam E mail Timothy P Zqonena us ul com A not for profit organization dedicated to public safety an enrmmittad ta malty service Sunny Boy 2500U Installation and Operator s Manual Information about SMA Further literature about the Sunny Boy inverter family e User Manual Sunny Boy 700 850 e User Manual Sunny Boy 1100E e User Manual Sunny Boy 1700E e User Manual Sunny Boy 2000 e User Manual Sunny Boy 2500U e User Manual Sunny Boy 3000 e User Manual Sunny Data e User Manual Sunny Data Control e User Manual Sunny Boy Control e User Manual SWR COM Socket Powerline Modem e Sunny Boy Info periodical newsletter with up to date information e SMA CD produc
35. of the lid is placed cor rectly When screwing the inner screws make sure that the thread in the Sunny Boy case is not damaged by tilted screws Under certain conditions the enclosure type NEMA 4X cannot be guaranteed any more When mounting the Sunny Boy outside moisture can get into the device and damage the electronics WARNING Make sure that the lid of the Sunny Boy is screwed tightly to the case before you start operating the Sunny Boy e Connect the PV panel by switching ON the DC breaker in the DC disconnect enclo sure e Connect the grid by switching ON the main 240 Volt breaker With sufficient power from the PV panel the Sunny Boy should now start automatically feeding the grid SB2500U 11 NE n 38 E SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual 4 5 Upgrading or modification of the Sunny Boy interface The Sunny Boy is prepared for data transmission By simply plugging on a piggy back module it supports transmission via Powerline RS232 or RS485 interfaces In order to install a new interface in the Sunny Boy a corresponding piggy back module has to be installed on the system control board WARNING Follow all relevant instructions in chapters 2 3 Electric Con nection 3 Commissioning 4 4 Opening and closing of the Sunny Boy in the Sunny Boy manual WARNING The Sunny Boy works with high voltages externally and inter nally which can cause considerable harm to people
36. ound must be firm e The ambient temperature must be between 13 F and 140 F e The National Electrical Code NEC requires that the inverter be connected to a dedicated circuit and no other outlets or device may be connected to this circuit See NEC Section 690 64 b 1 The NEC also impose limitations on the size of the inverter and the man ner in with it is connected to the utility grid See NEC Section 690 64 b 2 e Do not expose the string inverter to direct sunlight if necessary in stall a shading roof A minimum distance of 8 inch 200 mm must be clear above the in verter for ventilation i e no cupboards ceiling etc e Free air circulation around the case must not be obstructed If you are installing the Sunny Boy in a cabinet or closet etc the air circulation must be sufficient for heat dissipation provide external ventilation e The heat sink can reach a temperature of more than 175 F Check existing electrical installations or plumbing prior to drilling holes into the wall Provide a correct position of the inverter see below Hio Lp UUW mount straight or tilted to the back never mount tilted to front Fig 2 1 How to mount the Sunny Boy SB2500U 11 NE 9 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operators Manual The Sunny Boy inverter is mounted on the back side with the three metal straps Drilling Template for the Sunny Boy 2000 2
37. ow voltage regulation SB2500U 11 NE 52 7W lt 0 25 W max gt 94 13 F 140 F 25 C 60 C 0 100 class 3K6 NEMA 4X 17 08 x 11 61 x 8 42inch 434 x 295 x 214 mm 70 Ib 32 kg in compliance with FCC regulations DIN EN 50081 Part 1 EN 55014 EN 60555 Part 2 EN 55011 group 1 class B DIN EN 50082 part 1 in compliance with UL1741 EN 61000 3 2 in compliance with UL1741 optional MSD VDEW E DIN VDE 0126 10 97 DIN EN 50178 4 98 VDE 0160 DIN EN 60146 part 1 1 3 94 VDE 0558 part 11 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual 8 0 aan meen 6 0 TR lA l d d o o pM 77 250 300 350 400 450 500 550 600 U A Fig 7 2 Maximal Input Current of the Sunny Boy 2500U 3000 2500 2000 1500 Pac W 1000 500 250 300 350 400 450 500 550 600 U V Fig 7 3 Output Power of the Sunny Boy 2500U SB2500U 11 NE 53 E SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual 0 9 0 8 0 7 0 6 0 5 0 4 efficiency P Pyc 0 3 0 2 0 1 0 00 0 25 0 50 0 75 1 00 1 25 1 50 1 75 2 00 2 25 2 50 Pac kW Fig 7 4 Efficiency of the Sunny Boy 2500U SB2500U 11 NE 54 SMA Regelsysteme GmbH S
38. rial number of the inverter e Sunny Boy type e short failure description number of the blinking code chapter 4 if Sunny Boy Control or a PC with Sunny Data is present What failure is indi cated Can you reproduce the failure How can you reproduce it Has this failure always occurred What were the ambient conditions as the failure occurred Information concerning the PV modules e Supplier type of modules e number of modules in string e output power e open circuit voltage Use the original box the Sunny Boy was delivered in if it is necessary to send the Sunny Boy to the manufacturer SB2500U 11 NE 45 E SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual 6 Warranty Regulations and Liability Warranty The warranty period is 24 months from the date of purchasing the device by the end user It ends at the latest 30 months after the delivery date from SMA and includes all defects caused by material or manufacturing faults The guaranty period for warranty repairs or compensation deliveries ends 12 months after delivery but runs at least until the expiration of the original warranty period for the delivered item Evidence SMA will only render warranty services if the rejected device is sent back to SMA together with a copy of the account the distributor has issued for the consumer The type plate at the device must be legible In case of non fulfillment SMA reserves t
39. s may lead to short time data transmission disturbances or interruptions In case of disturbed data transmission via mains lead we offer alternatively a communication via separate data line as option RS232 or R8485 We do not guarantee that the software is completely free of failures In case of a fault an instruction how to avoid the effects of the fault is also considered as sufficient repair Only the customer is responsible for the correct selection orderly use supervision and the re sults of the use of software We reserve the right to make alterations serving the improvement of the device Further or other claims for direct or indirect damages especially including claims for damages from positive contract violation are excluded insofar as not otherwise compelling stated by law SB2500U 11 NE 47 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual 7 Technical Data Input PV panel Maximum open circuit voltage of the PV panel WARNING It is essential to comply with the respective input voltage range which varies depending on the type and number of PV modules used WARNING The maximum open circuit voltage of the PV panel may not ex ceed the specified maximum input voltage of the Sunny Boy The open circuit voltage of the PV panel depends on the temperature of its cells and on the respective solar radiation The highest open circuit voltage of the PV panel oc curs when the temperature of t
40. to O Ohm resistors have to be soldered in there Plug the desired piggy back module onto the required slot When plugging on the piggy back please make sure no socket of the piggy back plug in contacts remains open Connect the cables for RS232 or RS485 No cabling is necessary for Powerline commu nication Data cables are lead outside through the free opening at the bottom of the Sunny Boy Please insert the PG16 screws into this opening and fasten them Push the communication cable through the contact unit of the PG cable fitting Connect the terminal cables to the terminal strip of the system control board and check whether they are firmly fastened Fasten the cable seal of the PG16 cable fitting If you have installed RS232 cabling please close the opening in the bottom with the seal included in the packing list Close the device as described in chapter 4 4 SB2500U 11 NE 40 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual 4 6 Measuring Channels and Messages The communication supports a number of measuring channels and messages from the Sunny Boy inverters The following abbreviations are used BFR SRR BetriebsfUhrungsrechner Sequential Control System Stromregelungsrechner Current Control System Measuring Channels Vpv Vpv Setpoint PV input voltage PV desired input voltage of the Vpv control lac current to the grid Vac grid voltage Fac grid frequency Pac pow
41. ts technical documentation driver Manual Improved Powerline Communication with the Sunny Boy Family Sunny Boy in the Internet All documentation and software concerning the Sunny Boy products is available on the Internet http www SMA de This literature can be ordered from SMA for a small fee most of this although is available free of charge for download from www SMA de SB2500U 11 NE x 58 m SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual Our Sunny Boy Homepage is updated daily and offers e the newest information concerning the Sunny Boy inverter family e the newest software e help concerning problems with your PV plant e and of course all you might want to know about SMA Regelsysteme Those who want to know more about SMA Regelsysteme GmbH and its products are very welcome to visit us on our homepage SB2500U 11 NE z 59 Ej SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual SMA in the USA e Address SMA America Inc 20830 Red Dog Road Grass Valley CA 95945 e Telephone 530 273 4895 Telefax 530 274 7271 e eMail info sma america com e Internet http www sma america com SMA in Europe Address SMA Regelsysteme GmbH Hannoversche StraBe 1 5 D 34266 Niestetal e Telephone 0049 561 9522 0 operator 0049 561 9522 499 Sunny Boy Service e Telefax 0049 561 9522 100 main fax 0049 561 9522 4699 Sunny Boy
42. unny Boy 2500U Installation and Operator s Manual Parameter List Sunny Boy 2500U All parameters are transmitted to Sunny Data or to the Sunny Boy Control when the Sunny Boy is configured The following table shows the available parameters No Name Unt Range Default Change by o dme O wvSat v 29 eo 300 Installer Tsat s 5 80 300 Installer 29 300 262 Installer Installer Table 7 2 Parameter list Sunny Boy 2500U SB2500U 11 NE z 55 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual 8 Appendix Certificate for Sunny Boy 2500U e Underwriters Laboratories Listing Document dated 8 May 2001 SB2500U 11 NE E 56 ES SMA Regelsysteme GmbH 333 Pfingsten Road Northbrook flinois 60062 2096 United States Country Code 1 847 272 8800 FAX No 847 272 8129 http Avww ul com W Underwriters Laboratories Inc e NOTICE OF AUTHORIZATION TO APPLY THE UL MARK Northbrook Office May 8 2001 Sma Regelsysteme Gmbh Attn Mr Sven Bremicker Hannoversche Str 1 5 34266 Neistetal Germany Our Reference File E210376 Project 00NK8603A Subject Sunny Boy SWR 2500U Dear Mr Bremicker We have completed our engineering investigation under the above Project number and find the Products comply witn the applicable requirements This letter temporarily supplements the UL Conformity Assessment Services Inspection Procedure and serves as authorization to apply the UL and C UL L
43. y Boy WARNING Do not forget to disconnect the Sunny Boy from the grid Be fore opening the device read chapter 4 4 SB2500U 11 NE 5 32 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual Blinking Code 3 Grid impedance too high if the optional Grid Impedance Meas urement is active Operation amp C9 Earth Fault 5 GO amp Failure The yellow failure LED is activated for 5 seconds remains dark for 3 seconds and then blinks three times The code is sent three times If the failure persists the indication begins once again The Sunny Boy has detected a failure based on the utility impedance values The criteria for the grid impedance is described in the section Islanding protection in the technical description of the Sunny Boy A too high utility impedance can be the reason should this failure occur very often The impedance can be checked with the Sunny Boy Control or Sunny Data This failure can normally be avoided by increasing the cross section of the AC cabling SB2500U 11 NE 5 33 SMA Regelsysteme GmbH Sunny Boy 2500U Installation and Operator s Manual Blinking code 4 Input voltage PV panel too high Operation 9 6 690 00 09 amp Earth Fault 59 6 690 00 09 9 aue 6 9 O 0 0 O 5s 3s 1s 1s 1s 1s E Tales umocim Ce ee ee The yellow failure indication LED is activated for 5 seconds is out for 3 seconds and then blinks four