Home
Manual - Potter Electric Signal Company, LLC
Contents
1. i C P Link EDENN NaN aN annann cion 3 Sesso E bd E a S1 O i A j O Dip Switches DWG 608 21 Fire Communications Bridge Installation FCB 1000 This panel supports one 1 Fire Communications Bridge accessory This module provides an optional remote IP connection for IP reporting functionality The FCB 1000 is controlled over the 4 wire P Link connection This then can be mounted inside the AE 8 or AE 14 accessory cabinets or the optional rack mount kit FCB 1000RM The FCB 1000RM includes a standard 19 inch rack mount enclosure which can then be installed directly into the IT equipment rack Note The Ethernet IP connection is limited to same room installation This connection shall be limited to 20 feet and enclosed in conduit or equivalently protected against mechanical injury Figure 41 FCB 1000 Bridge FCB 1000RM Showing Rack Mount DWG 608 13 DWG 608 14 Figure 42 FCB 1000 Wiring to Control Panel Example Example Powered by control panel P Link A B DWG 608 26 P Link
2. Potter Q Job Details Remote Access Password Potter Q General Options L _ O zs Te O Points estivi Email Reporting v The Transfer window displays all completed transfers Lan settings A Time Medium URI Phone Filename F gt History Complete 7 21 2011 11 18 IP 10 0 5 18 C Documents and Settings denise Download Complete 7 21 2011 11 15 IP 10 0 5 18 C Documents and Settings denise v rn al Panna bo ina mms 44 4m TM anaran aala mmmn Note Double click anywhere on the transfer record to view details 5 47 PFC 6030 5403595 REV C 2 13 Uploading from Panel to Computer The Upload Configuration File to Computer transfer icon a is used to upload the configuration file from the panel to the computer once the LEARN function is completed or whenever devices are added or removed from the panel To upload programming changes to computer 1 Click the Upload Configuration File to Computer icon or right click from Transfers region as shown below Figure 60 Example of Transfer Shortcut Menu Transfers 7 A IX Status Time Medium URI Phone Filename History Complete e l 11 18 41 AM 1P 10 0 5 18 Download Complete f 111 15 22aM 1P 10 05 18 Download Complete Delete 01 11 10 23 AM IP 10 0 5 18 Upload Complete Redo 111 04 46AM TP 10 0 5 18 Right click anywhere in the transfer window to display the
3. DWG 593 20 3 18 PFC 6030 5403595 e REV C 2 13 Single Action Dual Action Pull Station APS SA APS DA The APS SA DA addressable pull stations are non coded that provide an addressable point to the panel The APS pull stations have terminals that allow the SLC to be wired directly to the device and then exit to the next device in the loop Refer to the wiring example shown below Figure 21 Example of Addressable Pull Station Wiring From FACP or Previous Module Addressable Pull To Next Module Station Single Action O Dual Action Model No APS SA DA FACTORY WIRED CONTACTS DWG 593 36 PFC 6030 5403595 REV C 2 13 Addressing SLC Devices Before devices can be programmed they must be assigned a unique address There are two 2 methods to address devices 1 You may use a hand held address setting device or 2 Use the panel s System Tools SLC Addr Prog option Only authorized system users may access the System Tools options You may sequentially address individual devices or groups of devices and assign different numerical ranges i e 10 and 15 25 as necessary To address devices via a hand held address device 1 Connect the device to the base on the hand held address device or to the terminals with a pair of wires to connect modules 2 Use the buttons on the device to set the address an
4. The Add Multiple Zones dialog box displays Figure 99 Examples of Adding Multiple Zones Dialog Box MM Add Multiple Zones Number of Zones Starting Zone Number 2 3 In Number of Zones field enter the number of zones to create Note You may enter up to 99 zones 4 In Starting Zone Number field enter the zone number to begin numbering zones if different from default 5 Click OK or Cancel to exit dialog box The Zones window lists all new zones Figure 100 Zones Window a d Zone 3 6 Goto the Zone Configuration window to view all available zones Figure 101 Example of Configuring Two 2 Zones Alarm Silence Night Heat Fixed ROR Name Style ee able Latching Local Output Pattern Day Sens Sens cenz Heat Sens Zone 2 1 e e Constant 3 5 2 5 135 135 Zone 3 Alarm 1 we se E Constant 3 5 2 5 135 135 5 74 PFC 6030 5403595 REV C 2 13 Configuring Zones The next step is to customize a zone s attributes which includes changing the name selecting type of zone and other characteristics 1 e constant double time output pattern latching or non latching silenceable auto silence timer etc To configure a zone 1 Double click in the Zone s Name field to modify default name 66 Note Up to 16 alphanumeric characters may be entered For example Main Lobby or Server Room 2 Click in Style field Click the drop down arrow
5. 4 Click OK to save changes B 1 PFC 6030 5403595 e REV C 2 13 Oo ADDenc am Maintenance and Testina yA Ae Ye gt Hi A A A A h Acceptance Test The control panel is required to be installed in accordance with local and state building codes and NFPA 72 National Fire Alarm Code At the conclusion of each original installation or modification of this system the control panel and related system is required to be inspected and tested in accordance with NFPA 72 to verify compliance with the applicable standards Testing should be conducted by Potter factory trained fire alarm technician s in the presence of a representative of the Authority Having Jurisdiction AHJ and the building owners representative Refer to NFPA 72 National Fire Alarm Code Inspection Testing and Maintenance Periodic Testing and Service Periodic testing and maintenance of the control panel all initiating devices all notification appliances and any other associated equipment is essential to ensure the system will operate as designed in emergency situations Service and test the control panel according to the schedules and procedures outlined in the following documents e NFPA 72 Inspection Testing and Maintenance e Service manuals and instructions for any and all peripheral devices installed in the system It is very important that any and all trouble conditions or faults be corrected immediately Operational Checks During interim peri
6. Expansion Device DWG 602 28 DWG 602 31 Figure 141 P Link Class A Wiring Example PoP epee aaa 00999999010 Expansion Device M NAC 1 NAC 5 NAC 3 a Expansion Device DWG 602 29 DWG 602 32 6 100 PFC 6030 5403595 e REV C 2 13 Municipal Box Connection When the PSN 1000 PSN 1000 E is programmed as a municipal box connection the circuit is power limited and supervised for open and short circuit conditions It also provides a local energy connection Please refer to the figure shown below for a wiring example Configuration Characteristics e NACI NAC6 s trip current is 3 amps e Maximum voltage rating is 24 VDC Notes 1 The panel has ground fault detection on municipal box connection circuits 2 The impedance to ground for ground fault detection is 0 ohms Figure 142 PSN 1000 Configured as Municipal Box Relay Outputs End of line device 5 1k ohm 1 2W Part 3005012 Municipal Box Notes The EOL device shall be installed in the same electrical enclosure as the Municipal Box DWG 602 31 The board has two 2 relay outputs a dedicated Trouble relay and a Low AC relay The dedicated Trouble relay is a failsafe trouble relay that changes position anytime a trouble condition occurs The relays have a contact rating is 24VDC 3 0A 125VAC 3A and a Power Factor of 1 0
7. Figure 12 CIZM 4 Class B From FACP or Previous Module SLC Loop A Select Style B Conventional Detector To Next Module From FACP or Previous Module 5 1KQ 1 2W EOLR ee Conventional Initiating Zone Module Model No CIZM 4 TAREN Mouule Note The resistance of external wiring shall be less that 1000 DWG 593 12 The capacitance of external wiring shall be less than 1 micro farads Miniature Contact Module MCM Refer to the figure shown below for a MCM wiring example Figure 13 MCM Wiring Example Note The resistance of external wiring shall be less that 1000 The capacitance of external wiring shall be less than 1 micro farads 5 1KQ 1 2W EOLR To Next Module SLC Loop Mini Contact Module Model No MCM DWG 593 13 From FACP or Previous Module Note If MCM is located in an electrical box it should be secured using crew tabs or other method to prevent movement Single Contact Module 4 inch Mount SCM 4 Refer to the figure shown below for a SCM 4 wiring example Figure 14 SCM 4 Wiring Example Note The resistance of external wiring shall be less that 1000 The capacitance of external wiring shall be less than 1 micro farads 5 1KQ 1 2W EOLR To Next Module SLC Loop Single Contact Module Model No SCM 4 DWG 1593 14 From FACP or Previous Module 3 16 PFC 6030 5403595 e REV C 2 13 Dual Contact Module 4 inch Moun
8. From the SLC Addr Prog menu press 1 to address a Single device Attach connector wires to SLC PGM terminals if not already done The Connect Device prompt displays Connect device The Found Address xx prompt displays e Modify new address if needed or press ENTER to continue e The Writing Addr XX prompt displays and the system beeps three 3 times when completed When addressing is completed the Found Addr XX New Addr XX prompt displays e Disconnect device and continue with next device e Repeat steps as needed Press ESC when finished For Multiple Devices l From the SLC Addr Prog menu press 2 to address Mult device e The Start Address XX prompt displays e Modify starting address if needed and press ENTER e The prompt Connect Device displays Connect 1 device The Addr XX Next XX Remove prompt displays e Disconnect the device connect next device Addressing is completed when the panel emits a series of three 3 beeps e The Addr XX Next XX Remove prompt displays e Continue with next device following prompts Notes e The prompt Addr XX refers to the current device number and Next XX is the next sequential address number e When configuring a Class B DCM 4 press the UP ARROW to skip the next sequential number The Class B DCM 4 requires 2 addresses if this isn t done the next available address will be assigned to a diff
9. e Icon changes to EI insert window autohide if window is hidden e Click Ell to unhide and dock window Displays if window is hidden available for specific windows only Note Tab name is specific to the hidden window e Point to Tab to display window e Point or click in another window to hide Example of Zone tab N Zones v o B a Style Alarm Silence stching Local Output Patten D gt Zonei Count able Loop PWR Supply PWR Supply PWR Supply PWR Supply Built in SLC Alarm 1 Y Y Constant Built in SLC Built in SLC Built in SLC Built in SLC Built in SLC Built in SLC Function Conv NAC General Purpose Built in SLC Conv NAC General Purpose E Built in SLC Available in Zones and Points windows only e Click the plus sign to expand e Click the minus sign to collapse Example of expand collapse icons in Points window Loop PWR Supply Main Building PWR Supply PFC 6030 5403595 e REV C 2 13 Menu Option Remote Access Code Job Details General Options Zones Cross Zones Points Sensitivity E mail Reporting E mail Reminders Users LAN Settings Dialer IP Reporting Class A Card Annunciators SLC Loop Power Supply DRV 50 LED 16 RLY 5 FCB 1000 SPG 1000 FIB 1000 Table 12 Programming Menu Overview Description Displays remote access User Name and Password Allows site specific information to be ent
10. Output Zone field Select output zone Output tai Zone 4 R amp D Lab Relea 1 Main Building 2 R amp D Lab 5mk 3 R amp D Lab Heat 4 R amp D Lab Releasing Ck 5 83 PFC 6030 5403595 REV C 2 13 Programming Modules This section addresses how to program optional all P Link appliances including the DACT UD 1000 RA 6500 RA 6075 CA 6075 Class A expansion card LED 16 annunciators and others CA 6075 Class A Converter Module The PFC 6030 supports one 1 Class A Expander card To add and configure a Class A module 1 Select Class A Card from the system panel 2 Click the Add Device button The 4dd Device window displays Figure 118 CA 6075 Class A Add Device Window Add Device Type SLC Class PLink Class Class A Card B B Note If you attempt to add more than one 1 Class A card an error dialog box displays as shown below Figure 119 Unable to Add Dialog Box Unable to add an additional Class 4 Card Maximum number in system is 1 3 Double click in the SLC Class field to select class type A or B 4 Double click in the P Link Class field to select class type A or B Remote Annunciators RA 6500 and RA 6075 The PFC 6030 supports up to thirty one 31 remote annunciators in any combination of RA 6500 and RA 6075 Each LCD annunciator may be programmed with a unique name to help identify the location of an off normal condition To add and conf
11. The system s built in on board IP Communicator provides notification to a remote monitoring company when alarms troubles and supervisory conditions occur The IP Communicator is used with an IP capable Sur Guard receiver by means of the Fibro protocol Note The UD 1000 or DACT may also be installed to provide notification to a remote monitoring company via telephone lines Programming options allow you to select accounts for test events and alarm trouble and supervisory conditions You may set up IP parameters such as when and where to send reports by specifying IP addresses and other report output options An example of the Add IP Communicator window is shown below Figure 149 Example of the IP Reporting Window ETE a oe 2 Primary Panel UDP Port O Secondary IP Reporting Accounts E Primary Secondary Account Account Settings Settings A a ca ca a oe eee a 1 Report Report Report Report Alarms Troubles Supervisory By E E E Point gt gt E E E Point gt gt El El El Point 2 gt E E E Point gt gt Notes 1 A daily test can automatically be sent to a remote monitoring location the test time may be programmed through the General Options program window Time to Send Autotest field 2 Ifthe system has been programmed to use the IP Communicator and the UD 1000 the daily test ca
12. 000 0 00 000 3 5 055 3 5 055 n a 0 00 060 1 80 089 Yes 14 PHOTO Point 14 0 00 000 0 00 000 3 5 055 3 5 055 n a 0 00 060 1 80 089 Yes N Hine Training Panel Detector Status CO y O A gt Poranne Panel History cee Notepad M efx Potter Electric signal Training Panel History txt Thu 01 13 2011 8 00 104m Potter North Training Panel History csv Thu 01 13 2011 8 00 10AM Potter North 800 325 3936 tech pottersignal com orders pottersignal com 01 13 2011 01 13 2011 01 12 2011 01 12 2011 01 13 2011 01 12 2011 D0AM D0AM D0AM 2 94M D0AM 26PM system system system system system system Time set Date set Time Set Powerup Auto Test Normal Login User 3 11790 Troy Lane North Maple Grove MN 55369 800 325 3936 tech pottersignal com orders pottersignal com jN 00 01 wjn 7 9 9 7 E 2 01 12 2011 10 07 534mM system Login User 3 01 12 2011 9 14 29AM system Login User 3 01 13 2011 7 59 004M System Time Set 01 12 2011 9 14 004mM Remote Programming Pass 16 01 13 2011 9 46 00AM System Date Set ae a eee epee fob fend cee 17 01 12 2011 9 48 00AM System Time Set 01 12 2011 9 00 12AM system Login User 01 12 2011 7 55 294M System Powerup 01 12 2011 8 43 344mM System Login User 19 01 13 2011 7 00 00AM system Auto Test Normal oe a a ree system Login User 01 12 2011 2 46 26PM System Login User 3 13 44AM System Login User 01 12 201
13. 6 NAC circuits provided on the PSN 1000 PSN 1000 E rated as continuous 3 amps at 24 VDC The NAC circuits may be configured for Class A or Class B Please refer to the Class A and B wiring examples shown in this section The circuits reverse polarity upon activation and are marked accordingly on the board and illustrations NAC Wiring e Outputs are supervised and regulated e NAC circuits are power limited e Type of NAC output is selectable and may be configured for strobe synchronization with Potter AMSECO Wheelock Gentex or System Sensor strobe devices Please refer to Potter document 5403592 NAC Compatibility Document for this information e Class A operation is accomplished by using a pair of NAC circuits NAC 1 amp 2 NAC 3 amp 4 and NAC 5 amp 6 this pairing provides three 3 Class A circuits each rated for a continuous 3 amps at 24 VDC NAC Maximum Impedance Formula The maximum impedance is a function of the load being applied to the circuit In order to calculate the maximum impedance as follows Alarm Current of Notification Appliances x Wire Resistance lt 3 Volts NAC Wiring Configurations Examples of Class A and B follow Figure 136 Class B NAC Wiring Example eee ejeje e e e eee eje ee ee Notification Appliance 5 1k EOL Potter Part 3005013 DWG 4602 24 Notes 1 The Potter part number for the listed end of line assembly is 3005013 EOL Resistor Assembly 2 The panel has ground f
14. G DRL3 IPCA Network Line Card RA 6500 LCD Remote Annunciator RA 6075 LCD Remote Annunciator PSN 1000 E Intelligent Power Supply Expander LED 16 LED Annunciator DRV 50 LED Driver RLY 5 Relay Board FCB 1000 Fire Communications Bridge FIB 1000 Fiber Interface Bridge SPG 1000 Serial Parallel Gateway Class A Expander CA 6075 Class A Expander Keltron 90 Series Fire Alarm printers or other UL Listed fire alarm printer Ancillary E 1 PFC 6030 5403595 e REV C 2 13 This section provides basic error messages their descriptions and recommended actions for each condition Table 26 Troubleshooting Error Description Action The panel is not able to communicate with the annunciator Action Check wiring and programming SLC H TYPE ERR Device is not programmed for the correct function Action Program device for correct function FACP found a non programmed device Action Run LEARN or program specific device Keypad Missing SLC FP XTRA DEV ee FACP found multiple devices with the same address ee ee UE R Action Manually reassign address of one of the devices SLC LOOP SHORTED There is a Short on the SLC loop wiring Action Locate short and repair accordingly NAC H OPEN There is an open on the wiring Action Locate open and repair accordingly There is a short on the Notification Circuit s wiring pn ie Ont Action Locate short and repair a
15. IL ec ere ee Controlcenter1 gmail com Y Q Sensitivity Controlcenter2 gmail com Fil Alarm Trou ble Supervisory E Controlcenter38 gmail com Pa and Test Events are sent gj Erai Reporting a immediately as they occur O O O e mame m EJ m m El EJ El El E EJ Event History and Detector Status reports may be scheduled to be sent on specific days of the week time or day of the month Up to twenty 20 e mail addresses may be programmed on this screen After the E mail Reporting section is completed and downloaded into the panel the panel will start sending e mails according to programming The panel is capable of sending automatic and on demand reports because it has a designated outgoing e mail address comprised of its model and serial numbers On demand reports can be requested directly from the panel s Data Transfer function or remotely from a PC if the user has a valid e mail address programmed on the E mail Reporting window The panel address is structured as PFCOXXXXXXXXXXX potterlink com where PFC6XXXXXXXXXXX refers to the panel serial number The serial number is the same as the NetBIOS name and is located on the panel as shown below Note Outgoing panel e mails are routed through a dedicated Potter server You must make a notation of your panel s outgoing e mail address in order to send e mail requests remotely Figure 85 Panel Serial Number Location Panel Serial Number DWG 5
16. O GGG 008 O O 000 TROUBLE MSN 000 OOO 000 l 000 ae bee Bda SILENCE EEN 000 ses V Le ODO O00 KS Tog a LI LI RESET fake i 000 OOO 000 000 L L D AA D O O O E A a A O Secs DWG 608 4 DWG 608 5 3 27 PFC 6030 5403595 REV C 2 13 The LED 16 is controlled over the 4 wire P Link connection The higher current required for the LED outputs can be provided by the panel or from an auxiliary power source as shown below The auxiliary power can be any 24VDC source and 1s fully supervised Figure 31 Examples of Wiring LED 16 Module to Control Panel or Auxiliary Power Supply Example Example Powered by Powered by control panel aux supply ool LED PWR P Link B A B Power from P Link from P Link from auxiliary control panel control panel suppl pply DWG 608 6 Setting Addresses The LED 16 s address is set by dip switch S1 which is located on the back of the annunciator The address must be set in the range of one to thirty one 1 31 to be recognized by the panel Refer to the P Link Addresses table shown earlier in this section for DIP switch programming Figure 32 LED 16 Back Panel Showing Dip Switch Location
17. These outputs are non power limited and are not supervised Note If the power supply is power limited then the outputs are power limited Figure 143 PSN 1000 s Relay Outputs aa one NC LOW AC TROUBLE COM NO NC COM NO DWG 602 31 6 101 PFC 6030 5403595 REV C 2 13 PSN 1000 PSN 1000 E Operations The PSN 1000 PSN 1000 E operates as a fully integrated power expander The input circuits and or NAC circuits are configured in the same manner as any input circuit or NAC circuit in the system Circuit functions and zone assignments are defined using the system software Status LEDs The PSN 1000 PSN 1000 E s status LEDs communicate system conditions by illuminating and or flashing the applicable green or amber indicators These are described in the table shown below Table 22 PSN 1000 PSN 1000 E Status LEDs Steady Green ON AC present OFF AC not present OFF No Fault Flashing Low Battery conditions ON Battery Charger Failure Steady Flashes l l Low Battery Amber Note The PSN 1000 transfers from AC to battery instantly upon AC failure or brownout The trouble relay on the panel will indicate the low AC condition after the Low AC Report Delay has elapsed 6 102 PFC 6030 5403595 e REV C 2 13 PSN 1000 PSN 1000 E Programming The panel can be programmed to support up to thirty one 31 PSN 1000 PSN 1000 E Power Expanders Each power supply provides
18. Type Status Time Medium URI Filename gt Status Complete 8 2010241 47 IP PFC6075R0000006 Status 2010 11 08 14 41 47 28vds History Complete 11 8 2010 2 40 09 IP PFCBO7SRO0000006 History 2010 11 08 14 40 01 80 vhs 4 Double click file to view results 5 Figure 73 Example of Detector Sensitivity Status Report Completed lt Sensor Current Night UI Drift Address Sensor Type Hame Condition Peak Value Day Sensitivity Sensitivil Aap E Drift Limit NFPA 72 Compliant f 018 PHOTO Point 18 0 00 000 0 18 003 3 5 055 3 5 055 n a 0 31 055 1 80 031 Yes 019 PHOTO Unused PO19 0 00 000 0 3196 005 3 5 055 3 5 055 n a 0 43 053 1 80 031 Yes E 020 PHOTO Point 20 0 00 000 0 24 004 3 5 055 3 5 055 n a 0 49 052 1 80 031 Yes Transfers Type Status Time Medium URI Filename kb Status ooo o Complete 11 8 2010 2 41 47 IP PFC6075R0000006 Status 2010 11 08 14 41 47 28 vds History Complete 11 8 2010 2 40 09 IP PFCBOFSROO00006 History 2010 11 08 14 40 01 80 vhs Notes Click the Print Q icon to print a copy of the report Refer to Printing Reports located in this section for more details Refer to System E mail Functions Receiving E mail Status Reports located in this section for a sample of a Detector Status Report sent via e mail Click the close button to close the report Printing Reports PFC 6030 5403595 REV C 2 13 The Print 9 icon allow
19. access and modify programming settings such as the system clock and day night mode sensitivity settings scheduling holidays displaying events and programming optional modules i e a DACT remote and LED annunciators and a Class A card Programming Options NOTICE To users installers authorities having jurisdiction and other involved parties This product incorporates field programmable software In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL 864 certain programming features or options must be limited to specific values or not used at all as indicated below Table 9 Programming Options f Feature or Permitted E Setting s Permitted Topic ando in UL Y N Possible Settings in UL864 Comment ry Initial Event Auto display of SLC Blink EJEM Normal Slow Off All settings allowed o Alarm Verification Time 0 60 Sec All settings allowed Misc DH Low AC No delay 15 sec 1 minute ETATE Dropout Delay 5 minute i Strobes Active l Display AM PM ME AM PM 24 Hour All settings allowed o 5 41 PFC 6030 5403595 REV C 2 13 Table 9 Programming Options Feature or Permitted A Setting s Permitted Alarm Supervisory Positive Alarm Sequence Zone Zone Type Y aan All settings allowed System Alarm System Supervisory System Trouble 0 300 Sec Full range allowed re lt lt lt Zone Auto Silence Zone Auto Unsil
20. 1000 Fiber Interface Bridge An accessory to the panel that converts the standard 4 wire P Link bus to and from optic cable capable of Class A operation maximum of 31 per system e PG 1000 Serial Parallel Gateway An accessory to the panel that allows a serial or parallel printer connection up to 31 maximum per system SLC Loop Accessories e Addressable Sensors e Photoelectric Smoke Detector PSA e Photoelectric Heat Smoke Detector PSHA e Fixed Temperature Heat Detector FHA e Rate of Rise Fixed Temperature Heat Detector RHA e Addressable Isolator Base AIB e Addressable Relay Base ARB e Addressable Sounder Base ASB e Addressable Pull Station APS e Addressable Modules e Miniature Contact Module MCM e Single Contact Module SCM 4 e Dual Contact Module DCM 4 e Twin Relay Module TRM 4 e Monitored Output Module MOM 4 e Conventional Input Zone Module CIZM 4 e Short Circuit Isolator SCI How to Use this Manual Refer to this manual before contacting Technical Support The information in this manual is the key to a successful installation and will assist you in understanding proper wire routing system requirements and other guidelines specific to the PFC 6030 system Common Terminology The following table provides you with a list of terms and definitions used with the PFC 6030 system Table 1 Terminology Definition PFC 6030 Cabinet Enclosure EOLD or Diode Assembly End of Line Diode Assembly EOLR En
21. 5 59 Day Nicht Sensitivity Mode Gnd Holiday Sehed ulin io 5 60 OSC OC oros 5 61 Ai aa OU ING ape A 5 62 P ink E mail NOM EAT LOCO UCI CIS vee ste scie case set ose seeeyina sie eray EErEE ES E aE TI TETEE 5 63 Conecte the TSI OC OI oa 5 63 TTA CW VOTE Sn E ETEA EE E TAE 5 64 PMA KPOri IRCOUCSICO TOMT E oras Sea E E EAE E S EAE 5 65 kecoaivine LIma oau RPO S att aos 5 67 CEL T A a 5 69 EEPO MA EEA E EE E E 5 70 NEES Lone OV CIVIC tia teste tenes ace tod e diodos ici 5 70 A AA 5 70 MANTE LOAN aa 5 70 MPD L AS 5 71 LOMO ANDES Y N A E N NE A NE A T 5 71 LONO O a E A E E E E T E A 5 72 VO A T E EI y Pe 5 74 CO N MS ass 5 75 E E EEN E N A N coin N EN E ace gst eie 5 75 NAC D O A E A E EE A A EEE EE A ARA E A 5 76 LETU OU ise 5 77 AUTOT OWLS TO LON E torta 5 80 EA 5 82 CTO SZOC OA CUT ONG oia aiipeis 5 83 Prosa MOdUlSS risa 5 84 CADO CASA CONV CIC MOGI C o as 5 84 Remote Annunciators RA 6500 and RADO 7 iaa id aa 5 84 ARNO OS LEA aca 5 85 LPI DORSO 5 85 PET AA A AEE sok sg vedas E ETEA EE E 5 86 Fioerinter ace Br dee TIDA OOO ae E E E E S E gente dele 5 86 Fie Communicalions bras LODO patos 5 87 Soral r arall SAO Asa 5 88 DAC E PA O a AE E AE EAE EE E EE E E E ateeeenes 5 89 Section 6 PSN 1000 PSN 1000 E Installing Operating Programming cccccssssseees 6 91 o AAA o A 6 91 Ai is E E RO IIA 6 91 Environmental Spec IICA LOOS nO cebada 6 91 PFC 6030 5403595 REV C 2 13 PETC CEI A PESCA O
22. A Expander Card 6 32 x 7 8 screws CA 6075 CA 6075 Class A card Class A Expander pou Appliance 6 32 x 1 4 screws DWG 593 27 DWG 602 5A 3 24 PFC 6030 5403595 e REV C 2 13 P Link Devices Accessory devices such as remote and LED annunciators and a relay expander RLY 5 are connected to the main control panel utilizing the four wire P Link bus for power and communication This panel supports a maximum of 64 P Link devices which can be connected using a Class B or Class A wiring style examples are provided throughout this topic Note If you have chosen to install an optional PSN 1000 PSN 1000 E power expansion board refer to Section 6 PSN I000 PSN I000 E Installing Operating amp Programming for instructions on installing this appliance Configuration Characteristics e P Link current rating is one 1 amp e P Link voltage rating is 24 VDC e The maximum wire length is 6 500 feet Maximum Wire Resistance Formula The maximum resistance is based on the load placed on the circuit To calculate the maximum wire resistance use the following formula Total Annunciator Alarm Current x Wire Resistance lt 6 Volts Figure 27 P Link Class B Wiring Example To the next device AA CAL FAFAFA Panel Connection Pelele elelee APR Expansion Device Ly A AL Expansion Device DWG 602 11A 3 25 PFC 6030 5403595 REV C 2 13 Figure 28 Example of P
23. ACK pushbutton Press the RESET pushbutton View Alarms Troubles Press arrows to view alarms troubles Press the DRILL pushbutton press the RESET button to exit Drill mode Conduct a Fire Drill Press ENTER to display the Main Menu Press 5 System Tools enter panel s code Wiew Polea Static Press 2 Point Control Scroll Up Down to choose Internal SLC PWR and press ENTER Enter Addr Ckt No and press ENTER Press Up Down to view previous next points Press ENTER to display the Main Menu Press 5 System Tools enter panel s code Press 1 SLC Tools Press 1 SLC Pinpoint Enter Addr press ENTER detector address and type displays Press ENTER to display current usage Press Up to display Day Night Sensitivity settings Press Up Down to scroll through point s day night sensitivity settings Check Detector Sensitivity PFC 6030 5403595 REV C 2 13 Table 24 Operating Instructions Press ENTER Main Menu e Press3 Set Date Time Set Date Time Use keypad to enter correct date use right arrow to move through date field and to display time field Press ENTER to save changes Press ENTER Main Menu Press 2 Enable Disable enter panel s code Press 1 By Point Up Down to select Device Internal SLC PWR and press ENTER Enter Addr Ckt No and press ENTER Press Up Down to scroll Point s current status displays Normal if enabled
24. Access Code is selected the remote user name and password displays Please refer to the examples shown below Figure 76 Panel Menu Options o General Options Zones cross Zones Points sensitivity Email Reporting Email Reminders users Ln Settings dialer 1 Reporting class 4 Card snnunciators sic Loop Power Supply oev so o is rvs Fce 1000 sPc 1000 Fs 1000 Figure 77 Example of Panel Menu Information Remote Access User Name Seems Q Job Details Remote Access Password Q General Options 5 55 PFC 6030 5403595 REV C 2 13 Program Icons The panel software uses several standard Windows icons such as the close button and scroll bars There are others that are unique to the panel software such as auto hide and window position which are summarized in the table below Table 11 Panel Configuration Icons Window Position Auto Hide O Window Tab Expand Collapse Located in the upper right region of some windows Click the icon to choose an option e Floating window floats over other windows right click title bar to reselect dockable Dockable default window position window is locked in place Auto Hide window is hidden when cursor is moved and tab displays as window placeholder point to window tab to redisplay Window Tab is explained below Shortcut to hide a window e Click to hide window
25. Analog Detector Wiring Example From FACP or the previous addressable device on the SLC loop To the next addressable device DWG 593 10 Connecting Addressable Modules This section provides examples of wiring addressable modules including Conventional Initiating Zones CIZM 4 Miniature Contact MCM Single Contact SCM 4 Dual Contact Module DCM 4 Twin Relay TRM 4 Monitored Output MOM 4 Analog Relay ARB Analog Sounder Base ASB and Addressable Pull Station APS modules Conventional Initiating Zones CIZM 4 Class A Figure 11 CIZM 4 Class A Note The resistance of external wiring shall be less that 1000 The capacitance of external wiring shall be less than 1 micro farads Conventional Detector 7 From FACP or Previous Module From FACP or Previous Module To Next Module Conventional Initiating Zone Module Model No CIZM 4 To Next Module DWG 593 11 Notes 1 The resistance of external wiring shall be less than 100 ohms 2 The capacitance of external wiring shall be less than 1 micro F 3 In this style the open circuit trouble condition of IDC is latched at the control panel until system is reset Therefore the system MUST be reset at the control panel after clearing the open circuit condition at the site 4 Refer to the CIZM data sheet for information on compatible devices 3 15 PFC 6030 5403595 REV C 2 13 Conventional Initiating Zones CIZM 4 Class B
26. Code 60 signals per minute Double Time 120 signals per minute The 3 5 default represents the percentage of obscuration per foot for all smoke sensing detectors e The term obscuration refers to the amount of reduction in air transparency caused by smoke e Day sensitivity is functional during the time a building is normally occupied The 2 5 default represents the percentage of obscuration per foot for all smoke sensing detectors e The term obscuration refers to the amount of reduction in air transparency caused by smoke e Night sensitivity is functional during the times the building is unoccupied 1 e weekends Holidays Sets alarm threshold for Fix Temperature Heat Detectors FHA Sets alarm threshold for Fixed ROR Heat Sensor RHA Defines the amount of time before silenceable NACs are automatically shut down Defines the amount of time before any silenced NACs are reactivated outputs only reactivate if panel is still in alarm Defines the amount of time you may not silence an output when in alarm Defines the amount of time before deactivating an output when the panel is reset 5 73 PFC 6030 5403595 REV C 2 13 Creating Zones When creating zones you may create one or more at a time This section explains this process and includes examples for your convenience To create a zone 1 Inthe Zones window right click on any zone name The shortcut menu displays 2 Click on Add Zones
27. General Purpose Built in Pwr Sup 5 NACS Conv NAC General Purpose Built in Pwr Sup 6 NAC ES Conv NAC General Purpose Built in Pwr Sup 7 Dki Cony NAC General Purpose Built in Pwr Sup a TO ck Conv NAC General Purpose Built in Pwr Sup 9 TO ck 3 Conv NAC General Purpose Built in Pwr Sup i0 10 Ckt4 Conv NAC General Purpose Built in SLC 1 Point 1 Unused Built in SLC 2 Point 2 Unused Note Click the columns to sort devices by the field selected 1 e Name Alarm Verification or Low Temp Trouble e Supervisory Designates a detector as a supervisory input instead of an alarm input e Alarm Verification Specifies that a detector will utilize the alarm verification feature e Low Temp Trouble Indicates that a device is below 40 F 2 Devices are listed by Built in SLC device addresses followed by the NACs and I O circuits Note Click on the Device field to sort the list by PWR Supply followed by SLCs To configure a single point 1 Double click in Name field to enter a descriptive name The current name is highlighted as shown 2 Enter a new name up to 16 alphanumeric characters 3 Click on drop down arrow in the Function field Select a function type from the list Figure 104 Example of Configuring a Single Point Device Addr Name Function Supervisory eats Saale Built in SLC 1 Point 1 Unused gt Built in SLC 10 Point 10 Unused Addr Detector Photo B
28. Link Class A Wiring Requiring a CA 6075 Si AO 09 are Connection P LINK Panel Peg ee Expansion Pi i Device Expansion DWG 602 12A Device P Link Addresses Each P Link device has a five position dip switch which 1s used to program the device address ranging from one 1 to thirty one 31 Use the chart below to reference Dip Switch Settings Off Off Off Off or on on om om on on on Off Off Off Off Note When assigning dip switch addresses each device must have a unique number within each device type group For example a group of LCD annunciators may be assigned 1 10 and PSN 1000 PSN 1000 E power expansion boards may also be assigned 1 10 3 26 PFC 6030 5403595 REV C 2 13 Remote Annunciators Installation RA 6500 and RA 6075 This panel supports up to 31 annunciators in any combination RA 6500 RA 6075 The RA 6500 provides a 4 x 40 character LCD display Whereas the RA 6075 provides a 2 x 16 character LCD display along with standard function and numeric keys All annunciator models listed are designed to be mounted on a flat non condensing surface or electrical box Setting Addresses An annunciator s address is set by dip switch S1 which is located on the back of the annunciator The address must be set in the range of one to thirty one 1 31 to be recognized by the panel Refer to chart on the previous page for P Link DIP switch programming Figure 29 Annunciator
29. O ls O s1 o A Dip OOO GOD r Switches eae Sas OO o OOO OOO O O O Oooo O 000 O ooo ooo P Link ooo ooo Connections ooo O00 ooo Oooo O O O DWG 608 23 LED Drivers Installation DRV 50 The panel supports up to ten 10 DRV 50s Each DRV 50 provides programmable LED outputs and 4 programmable dry contact inputs which can be individually mapped to any zone The DRV 50 is controlled over the 4 wire P Link connection and is installed onto a mounting bracket as shown below This can then be mounted into any of the compatible fire enclosures or in either of the AE 8 or AE 14 accessory cabinets Note This panel supports up to ten 10 DRV 50 drivers and or LED 16 annunciators in any combination Figure 33 DRV 50 Board DWG 608 7 3 28 PFC 6030 5403595 e REV C 2 13 The 50 programmable LED outputs are located on connectors P1 P5 each containing ten 10 LED outputs and two 2 5VDC outputs The system LEDs and PZT control outputs are located on connector P6 LEDs are wired as shown below no external resistor is required All outputs are power limited Figure 34 DRV 50 P1 P5 and P6 Connectors O LED1 ina O TP E O Ka O TRB TFL O E o SUP nT o apes gt ALR O hi O SIL O EARTH o LED10 O PWR o LED oO PZT a LED gt LEDs Programmable LED System LED and PZT Connectors P1 P5 Connector P6 DWG 608 8 The 4 programmable dr
30. POTTER Fire Panel Operating Instructions The Symbol of Protection Normal Standby Acknowledging Alarm Condition Silencing Alarm Resetting Alarm Supervisory Condition Restoring Supervisory Condition Trouble Condition Silencing Trouble s Ground Fault Pre Release Releasing Panels Only Release Releasing Panels Only Agent Release Abort Releasing Panels Only Testing and Maintenance Frame and display instructions adjacent to the fire alarm panel 540907 1 Rev B The green AC POWER LED will be illuminated and the user defined message on the LCD will be displayed If the AC power 1s removed for more than 5 seconds the green AC power LED will extinguish Off normal events are acknowledged by pressing the ACK key while reviewing events After all events have been acknowledged the buzzer will deactivate and the associated LED will stop flashing and remain on continuously During Positive Alarm Sequence operation the ACK key must be pressed within 15 seconds of the alarm initiation to activate the investigation timer The red ALARM LED will be illuminated anytime an alarm is occurring in the system The LCD will display the number of inputs in alarm and the buzzer will be activated The buzzer will remain active until all alarms have been acknowledged or until the Silence key is pressed When the system is in Alarm the notification circuits strobes and horns can be shut off by pushing the SILEN
31. Pi Built in SLC 4 Point 4 Addr Detector Photo F Fi Built in SLC 5 Point 5 Addr Detector Photo Fi F Built in SLC 5 Point 6 Addr Detector Photo F Fi Built in SLC 7 Point 7 Addr Detector Photo F Fi Built in SLC 8 Point 8 Addr Detector Photo F Built in SLC 9 Point 9 Addr Detector Photo F Fi Built in SLC 10 Point 10 Addr Detector Photo F Fi 5 75 PFC 6030 5403595 REV C 2 13 NAC Functions The two 2 on board circuits NACs 1 amp 2 are automatically configured as General Purpose but may be reconfigured and renamed Refer to the table below for descriptions of the configuration functions Table 18 NAC Circuit Configuration Functions 5 76 PFC 6030 5403595 e REV C 2 13 SLC Functions The SLC configuration options are described in the table below Table 19 SEC Configuration Functions Dry contact input options used with MCM SCM or DCM modules Note When using an input module on an abort function there 1s a 6 second delay before panel responds 5 77 PFC 6030 5403595 REV C 2 13 To configure points 1 Click on the Points function to display the Points Configuration window Figure 103 Example of a Configuration Window Device Addr Mame Function Supervisory tat ree ae aie Built in Pwr Sup 1 NAC 1 Conv NAC General Purpose Built in Pwr Sup 2 WAC Conv NAC General Purpose Built in Pwr Sup 3 NAC3 Conv NAC General Purpose Built in Pwr Sup 4 WAC 4 Conv NAC
32. The following is a recommended approach to programming the system 1 Install Software Address and Install SLCs Run LEARN Connect Ethernet Cable Upload Data to Computer Program the System Download Configuration File A A Note This approach may eliminate programming errors however these are only recommendations Software Installation It s easy to install the PFC 6030 software and requires only a few minutes to complete Once done the program automatically creates a shortcut icon on your desktop for easy access The system software 1s compatible with Windows XP Windows Vista and Windows 7 Operating Systems and incorporates conventional shortcuts and features i e right click to display short cut menus drag and drop etc The software s flexibility enables you to effectively program individual and or groups of devices Several examples in configuring a basic fire system are provided later in this section under the System Programming heading Note The latest version of Microsoft NET Framework is required To install the software e Access the Potter website at www pottersignal com and go to the Fire Alarm Systems link then click the Fire Panel Configuration Software icon to select program to download e The default installation directory is C ProgramFiles Potter Potter Fire Panel Programmer e You may change the location of the application files 5 44 PFC 6030 5403595 REV C 2 13 LEARN Programm
33. VAC 240 VAC 50 60 Hertz and are marked accordingly on the board The earth ground connection is marked as G and is the furthest connection from the line voltage connection The AC input power ratings are as follows e Maximum of 3A at the nominal 120 VAC rating e Maximum of 2A at the nominal 240 VAC rating 2 12 PFC 6030 5403595 e REV C 2 13 Section 3 Installation This section addresses installation procedures for SLCs NACs and optional modules including the DACT UD 1000 Class A Card and Remote Annunciators Wiring requirements and configuration examples are included throughout this section Instructions for addressing SLC devices which must be completed before programming your system are also included Please read this section carefully before installing devices and or modules to insure proper installation Note Instructions for installing the PSN 1000 PSN 1000 E and or the IP Dialer accessories are located in Sections 6 and 7 respectively Signaling Line Circuit SLC Installation The SLC panel provides power and communication to each of the sensors and modules connected The SLC is polled by the system every 4 5 seconds This panel has a loop capacity of 30 addressable points which may be configured in any combination of smoke sensors heat detectors and input or output modules NOTICE All devices require an address prior to connecting to the control panel Refer to Addressing SLC Devices located lat
34. Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 0 0 0 0 0 Q 0 Q 0 0 0 0 0 Q 0 0 0 0 0 Q 0 0 0 0 0 0 Q 0 0 0 0 Oo0oOO0ODOO0DODOODODOOOOOODOOOOOODOOOOODODODO LN UY LY LY LY LY LY LY LY LY LY LY LY LY LY LY LY LY LY LY UY LY LY LY LY LY a LY U U SCOOoOooocoooooocooooooooeoooooeoeoeooo a ss ps ps ps ps a a pp ps ps ps ps pa pa q ps ps ps pos ps ps po ps ps ps ps ps LY UY LY LY LY LY LN LY UY LY LY LN UY LY L LN UY L LY LN U dd LN a a ss 00 CO00 5 67 PFC 6030 5403595 REV C 2 13 AJH System e mail communications and functions are intended for informational reporting purposes only They are intended to be used as a convenience function E mail communications should NOT be used as a primary means of reporting emergency information Figure 93 Example of Detector Sensitivity Status Comma Separated Values file csv Ei Microsoit Excel iranin Panel Detector statie Csy BAE Edit View Insert Format Tools Data Window Help Type a question for help gt pre anal A yn 33 Fes _ mv C A hy Er 100 x ication gt WebEx Setting i Arial 10 _ A C D E E G J K Z 1 Potter Electric Signal PFC6075R RO Ad Status csv 3 Thu 01 13 2011 8 00 094M Potter North 6 11790 Troy Lane North LZ Maple Grove Refer to Table 17
35. account numbers 4 Inthe Reporting Accounts section make the necessary selections for the primary and secondary reporting accounts e Select the Report type s Alarms Troubles Supervisory e Enter the Accounts IDs and Phone Numbers e Select the Primary Report By option Panel Zone or Point e Choose the Primary Format option CID SIA Note Both SIA DCS and Ademco Contact ID protocols are supported Figure 132 Example of Report Accounts Setup Reporting Accounts E i Primary Report Report Report heh lc saeta Primary Report pore E Secondary Secondary Alarms Troubles Supervisory Ties e SE Format Test am T Report By Format Number By Beni ID Number Y Y F f 17042551234 Point CID Y 17045259876 Panel CID a Y 6789225544 Point CID 7709255544 Zone CID Point CID 5 Panel CID a El Point CID Panel CID The Pri t setti a e Primary account Setting roint CID Panel CID fields are displayed here 5 90 PFC 6030 5403595 e REV C 2 13 Section 6 PSN 1000 PSN 100 Installing Operating amp Programming The PSN 1000 and PSN 1000 E power supply boards provide power and communication expansion capability to the PFC 6000 series control panels They provide an electrically isolated P Link repeater output that supports additional power and communications distance The PSN 1000 E s larger cabinet allows space for m
36. bus A four wire cable P N 5210514 is supplied with the UD 1000 which should be used to connect the P1 on the UD 1000 and the P connection on the main panel board as shown in the illustrations below Setting Addresses The UD 1000 must be programmed with an address between one and thirty one 1 31 to be recognized by the panel Refer to the P Link Addresses table shown earlier in this section for DIP switch programming Figure 52 UD 1000 Board Showing Dip Switch amp P1 Connector Main Board P Connector P Connector on PFC 6030 main board iP a MIGO DWG 593 33 DWG 593 32B 3 36 PFC 6030 5403595 REV C 2 13 This section provides an overview of the control panel s basic operations which includes the status LEDs function pushbuttons and a Control Panel Menu Tree quick reference sheet Control Panel Basic Operation The control panel is comprised of a two 2 line x 16 character LCD display panel arrow keys push button function keys status LEDS and the numeric keypad A description of each component is included in this section and refer to the figure below for an example Figure 53 PFC 6030 Control Panel Display LCD PFC 6030 Arrow Keys Display 11 11 21 20 00 Status O POWER O ALARM LEDs O EARTH FAULT C SUPERVISORY O SILENCED TROUBLE SILENCE RESET Numeric Keypad Function Pushbuttons ACK DRILL Note Authorized system operators must use a key to open the outer door of t
37. by area region displays as shown Figure 114 Group by Area Field rou p by ares Drag a field here to group by that field Note Click on group bar at any time to collapse region 3 Drag and drop one field into the group by area region The information displays grouped by selected field Figure 115 Example of Points Grouped by Function e AS a mm Conv NAC General Purpose 2 items E Conv NAC Aux Door Holder 1 item Addr Detector Photo Heat 2 items E Contact Input Pull Station 1 item 4 Click next to the function to view a complete list of points Click to collapse list of points as needed Figure 116 Example of Points Configured as Addr Detector Photo PFUNC_ADDR_DETECTOR_HEAT_COMBO 1 item l A PFUNC_ADDR_DETECTOR_PHOTO_HEAT 1 item PFUNC_ADDR_DETECTOR_PHOTO 10 items Device Addr Name Function Supervisory caer Built in SLC 1 Point 1 Addr Detector Photo E Fl Built in SLC 2 Point 2 Addr Detector Photo Fj C Built in SLC 4 Point 4 Addr Detector Photo Ldl Fj Built in SLC 5 Point 5 Addr Detector Photo LI dl Built in SLC 5 Point 6 Addr Detector Photo Fi E Built in SLC 7 Point 7 Addr Detector Photo E Fi Built in SLC 8 Point 8 Addr Detector Photo E dl Built in SLC 9 Point 9 Addr Detector Photo E a Built in SLC 10 Point 10 Addr Detector Photo Pi Fi PFUNC_CONW_NAC_RELEASE_SOLENOID 1 item 5 Drag field out of group b
38. collapse point assignments Figure 112 Example of Expanding Point s Zone Assignment s j Points wax ame Swe am SEES ng Local Output Pattem DoY Naht Het Fae TE e 2 Zone 2 Alarm 11M E Constant 35 2 5 135 1 Pultimsic 3 Point a 3 Zone3 Alarm 1 MO Constant 3 5 25 135 49 Bultimsic 4 Point ES HEE Built in SLC 5 Point Zone 2 i Zone 3 a Built in SLC 6 Point Zone 1 Zone 2 Zone 3 Built in SLC 7 Point Built in SLC 8 Point A eee Wile Built in suc 9 Point Built in SLC 10 Point paie ady ahi pa Si defers o Built in SLC 11 Point Built in SLC 5 Point 5 Addr Detector Duct E Oo a Built in SLC 12 Point Built in SLC 6 Point 6 Addr Sounder Base E O Zone 2 Built in SLC 12 Point 12 Addr Sounder Base m oO Zone 3 Built in SLC 13 Point 5 8 PFC 6030 5403595 REV C 2 13 Group by Area You may group information by different fields in many of the program windows This flexibility is helpful when configuring or viewing a large amount of information such as all devices zones or remote annunciators Examples are included for illustration purposes only To group by area field 1 Click on group bar located at top of window if available Figure 113 Example of Group Bar in Points Window z Alarm Device Addr Name Function Supervisory Verification PWR Supply 1 NAC 1 Conv NAC General Purpose PWR Supply 2 NAC Conv NAC General Purpose 2 The group
39. connection PFC 6030 5403595 REV C 2 13 Optional UD 1000 DACT LI POWER E ALARM a Bu e E A A ELIE ad tol ll il kl il cl al heal ll k es a _ E om IS i A m a A NP 18Ahr 12Volt 18Ahr 12Volt 2 7 A High voltage phone connections Optional CA 6075 Class A Expander Power limited 7 wiring el AE SS DWG 593 2 PFC 6030 5403595 REV C 2 13 Battery Circuit Calculations Before selecting the battery it is important to determine the minimum size batteries for standby and alarm times desired for each application and SLC current draw If the wrong batteries are installed in a specific application or incorrect current draw used the proper standby and minimum alarm time will not be present The battery circuit is rated for 8 to 55 AH batteries and will operate the panel alarm for at least 24 hours and 5 minutes The cabinet will house up to two 2 8 AH or two 2 18 AH batteries Please use the worksheets listed below to calculate the battery size and current draw required for each application and the SLC 1 Battery Calculation Worksheet and 2 SLC Current Draw Worksheet Battery Calculation Worksheets rare Standby Total Alarm pot fo p20 o As po IS oa PP BR LED Current if applicable see Note 6 as A A DRV 50 LED Current if applicable see Note 6 RLY 5 Relay Current if applicable see Note 6 S e FIB 1000 BARRA o ee ac OC wo O SLC C
40. for specific outputs or events The panel configuration software allows you to efficiently group points to follow a sequence of events producing the same combination of outputs into different zones This section addresses how to accomplish these tasks 5 70 PFC 6030 5403595 e REV C 2 13 Mapping Terminology The table below provides mapping terms that may be helpful to you in understanding the mapping concept Table 15 Mapping Terminology Mapping Creating relationships between devices modules and sensors and defining their behavior A group of devices e Zones may represent a group of devices located in a specific physical area at the site Example Zone comprised of all devices located in the main lobby of a hotel 7 e pull station 1 one 1 sounder base and one 1 strobe NAC Zones may represent a set of devices configured for a specific function their location may be Zone scattered throughout the site This group is a logical grouping or zone Example Zone 2 comprised of all devices in Zone 1 as described above plus a 2 pull station located at end of a hallway and two 2 additional Sounder bases Notes 1 Ifall input output devices are grouped into one 1 zone when any input is activated all outputs activate 2 A device or point may be mapped into more than one 1 zone Any specific device module or appliance connected to panel Latching Device will not automatically reset device must be RESET
41. in the Name field to customize name 4 Double click in Address field to adjust address if needed 5 Repeat steps as needed to continue adding RLY 5s Fiber Interface Bridge FIB 1000 The panel supports up to thirty 30 FIB 1000 boards This optional board allows the standard 4 wire P Link bus to be converted to and or from fiber optic cable To add and configure the FIB 1000 1 Select the applicable function from the system panel 2 Click the Add Device button The 4dd Device window displays Figure 124 Example of the Add FIB 1000 Window Type Name Address Class A FIB 1000 FIB 1000 1 1 E 3 Double click in the Name field to customize name 4 Double click in Address field to adjust address if needed 5 Click in the Class A selection box if applicable 6 Repeat steps as needed to continue adding FIB 1000s PFC 6030 5403595 e REV C 2 13 Fire Communications Bridge FCB 1000 The panel supports one 1 FCB 1000 The FCB 1000 provides a remotely located IP connection into the panel which may be designated as the IP reporting device versus passing through the on board internet connection To add and configure the FCB 1000 1 Select FCB 1000 from the system panel 2 Click the Add Device button The 4dd Device window displays Figure 125 Example of Add FCB 1000 Window one Type Name Address FCB 1
42. lt iN gt Ss M gt 2 Click on one or more points to select use the SHIFT or CTRL keys to select a range or group of points Figure 109 Example of Selecting Multiple Points i Points wi Alarm Silence Name Style Ee EPA Latching Local Output Pattern Loop Addr Maia Function a PWR Su 1 NACI Conv NAC General Purpose Zone 1 Alarm 1 E E E Constant pply di PWR Supply 2 NAC2 Conv NAC General Purpose PWR Supply 3 IOCkti Conv NAC General Purpose PWR Supply 4 IOCk2 Conv NAC General Purpose Built in SLC 1 Point 1 Addr Detector Photo Built in SLC 2 Point2 Addr Detector Photo Built in SLC 3 Point3 Addr Detector Photo a iT j gt Built in SLC 4 Point 4 Addr Detector Duct Sn Built in SLC 5 Point 5 Addr Detector Duct Device Addr Name Function Built in SLC 6 Point 6 Addr Sounder Base i Built in SLC 7 Point7 Addr Sounder Base PWR Supply 1 NAC1 Cony NAC General Purpose Built in SLC 8 Point 8 Addr Detector Heat Fixed PWR Supply 2 NAC 2 Cony NAC General Purpose e Built in SLC 9 Point 9 Unused PWR Supply 3 IOCkti Cony NAC General Purpose Built in SLC 10 Point 10 Unused PWR Supply 4 IOCkt2 Cony NAC General Purpose Built in SLC 11 Pointii Unused Built in SLC 12 Pointi2 Unused Built in SLC 13 Pointi3 Unused Built in SLC 14 Pointi4 Unused v d gt lt JLL gt 5 80 PFC 6030 5403595 e REV C 2 13 3 Drag and drop selected points from the Points window to the Devi
43. or Disabled Press ENTER to change status press ENTER to save or ESC to exit without saving Enable Disable Point Press ENTER Main Menu Press 1 View History Press Left Right to view next previous events Press ESC to exit View Event History A 2 PFC 6030 5403595 e REV C 2 13 A ndix B Modem Connectivi If your computer uses a modem for connectivity to the panel choose the Options Communications menu option This involves choosing Modem as the transfer medium and specifying the modem com port In rare instances a modem may also require an initialization string Refer to your manufacturer s instructions for this information To setup a modem 1 Select Options Communication The Communication Options dialog box displays Figure 152 Example of Modem Communication Setup Communication Options Default Transfer Medium Modem Com Port Modem Init String Default Answering Machine Bypass Fi Answering Machine Bypass Hangup Delay secs 2 Click in Default Transfer Medium field and select modem 3 Click in Modem Com Port field to select the applicable com port If required enter the initialization string Figure 153 Example of Com Port Modem Setup Communication Options Default Transfer Medium Modem Com Port Modem Init String Default Answering Machine Bypass O Answering Machine Bypass Hangup Delay secs 5
44. six 6 NAC circuits 3A max and two 2 dry contact input circuits Both Class A and B configurations are supported however Class A requires that NAC circuits are paired as follows NAC 1 amp 2 NAC 3 amp 4 and NAC 5 amp 6 thus providing three 3 Class A circuits Adding a Power Supply To add and configure a power supply 1 Select the Power Supply function from the system panel The 4dd Device window displays Figure 144 Example of Add Power Supply Window Potter Fire Panel Programmer NAC 3 4 NAC 5 6 Name Address Class ae Class Internal Power Supply PWR Supply Internal N A N A N A 2 Click the Add Device button to create a new power supply Figure 145 Example of Add Power Supply Window Potter Fire Panel Programmer Ja lx Power Supply default name P NAC 1 2 NAC 3 4 NAC 5 6 Class Class Class Type Name Address Class Internal Power Supply PWR Supply Internal N A N A Psn 1000 Power Supply PSN 1000 1 1 B B 3 Configure the power supply as needed e Double click in the Name field to change the default name e Double click in the Address field to enter a different address e Click on the Class drop down arrow to select Class A for the repeated P Link circuit Figure 146 Example of Power Supply Class for P Link Operation Potter Fire Panel Programmer File Options Help NAC 3 4 NAC 5 6 Class Class 1 1 Internal Power Supply PWR Supply Internal IN
45. the listed end of line assembly is 3005013 EOL Resistor Assembly 2 The panel has ground fault detection on the NAC circuits The impedance to ground for ground fault detection is 0 ohms 3 22 PFC 6030 5403595 e REV C 2 13 Figure 24 NAC Class A Wiring Example CA 6075 Class A card Notification Appliance DWG 602 5A 3 23 PFC 6030 5403595 REV C 2 13 Relay Output Wiring The panel has three 3 dedicated common relays The dedicated trouble relay 1s a fail safe trouble relay that changes position anytime a trouble condition occurs Relays have a contact rating of 24VDC 3 0A 125VAC 3A and Power Factor of 1 0 These outputs are non power limited and not supervised Note If the power supply connected to the devices is power limited then the outputs are power limited Figure 25 Relay Outputs eee e99 9 9 9 TROUBLE SUPERVISORY NC COM NO NC COM NO DWG 4593 26 CA 6075 Class A Expander Installation The Class A configuration requires the use of the CA 6075 Once the card 1s installed the additional terminals are provided for the return loop of the NAC The CA 6075 provides the terminals for both NACs SLCs and P Link Refer to the figures below for examples of installing and wiring a Class A expander card Notes l One 1 CA 6075 Class A expander may be installed per panel 2 The CA 6075 provides the terminals for NACs P Link and SLCs Figure 26 Examples of Installing and Wiring a Class
46. the user code access to the Facility Management Tool 5 Repeat steps for up to 10 user codes Note The access rights for the Default Access user code can be modified if needed 5 61 PFC 6030 5403595 REV C 2 13 NOTICE System e mail communications and functions are intended for informational reporting purposes only They are intended to be used as a convenience function E mail communications should NOT be used as a primary means of reporting emergency information System E mail Functions The PFC 6030 comes with built in e mail capabilities The panel automatically sends status e mails including Alarms Troubles Supervisory and Test events to the e mail addresses designated on the E mail Reporting window as shown below Customizable e mail reminders may also be created and scheduled by the installer Figure 84 E mail Reporting Window O De S TT A A A 7 Event History and Detector li repo on these Gays a nas aS ss saturday sl Status reports will be sent Y Tuesday sunday ETA based on the weekly schedule Q Job Details 4 Wednesday Email reports on this day of the month time and day of the month 2 Thursday 15 Es ceneri options Friday indicated here AE ARE ZP AE l Q Zones imail reports to these addresses cos Zones Enable Event Detector Email Email Alarms Troubles Supervisory Test History Status Requests Reports Reports Q Points L BP er
47. the width of the Event column to display the entire descriptions otherwise the Event information will be truncated on the printed report Tip Double click on the Event column s border to automatically expand the width to accommodate the longest description Refer to the example below Figure 75 Example of the History Report Potter Fire Panel Programmer File Options Help gt o tT Config 2011 07 21 11 04 45 74 fpf History 2011 07 21 11 18 39 36 fphf Nov 11 2011 Test fpcf Event Date Time 03 22 2011 02 52 09 PM 03 22 2011 02 52 09 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 10 PM 03 22 2011 02 52 11 PM Trouble Pt 5 Built in SLC Unused P005 SLC Programming Begin Trouble Pt 34 Built in SLC Unused P034 Trouble Pt 33 Built in SLC Unused P033 Trouble Pt 32 Built in SLC Unused P032 Trouble Pt 31 Built in SLC Unused PO31 Trouble Pt 30 Built in SLC Unused P030 Trouble Pt 29 Built in SLC Unused P029 Trouble Pt 28 Built in SLC Unused P028 Trouble Pt 27 Built in SLC Unused P027 Trouble Pt 26 Built in SLC Unused P026 Tro
48. 000 DACT communicates using the SIA DCS or Ademco Contact ID protocols Only one UD 1000 is allowed per main control panel for convenience the UD 1000 is typically programmed as device ID 01 The UD 1000 must be installed prior to any other telephone equipment in the building to ensure proper operation An RJ31X jack can be installed to provide the connection to the telephone lines a patch cable between the RJ31X jack and the built in RJ 11 jacks on the UD 1000 provide a convenient connection method The UD 1000 automatically monitors each phone line for voltage and has the ability to seize the line and connect with a remote receiver Once the communication is complete the DACT will hang up the phone line The DACT is provided with an RJ 11 jack for each phone line In order for the DACT to work properly 1t must be installed on a plain old telephone service POTS or equivalent as deemed by the authority having jurisdiction The DACT must be installed before any other equipment to ensure it can seize the line and disconnect any other lines PFC 6030 5403595 REV C 2 13 The UD 1000 slides into the guides located at the bottom of the panel and then secured with screws as shown in the following 1llustration Figure 51 Example of an Installed UD 1000 Dialer O POWER 000 3 000 MA e w soo Slides in guides under main board DWG 593 32A P Link amp Dip Switch Locations The UD 1000 is connected to the P Link
49. 000 FCB 1000 1 1 3 Double click in the Name field to customize name 4 Double click in Address field to adjust address 1f needed 5 Click the plus sign located in the left most column to display the Network Settings options Figure 126 Example of Add FCB 1000 Window Type Name E FCB 1000 FCB 1000 1 Network Settings Use DHCP 2 Automatic Private IP Address User Configured Alternate IP O Use Static IP 2 Use DNS address from DHCP server O Specify DNS Address 6 Set the IP address by choosing one of the following two methods e The built in DHCP Dynamic Host Configuration Protocol option is the default an IP address is automatically requested from the Host Computer e The Network Administrator or Installer may set the IP address using the software s Static IP function 7 Click the minus sign located in the left most column to suppress the Network Settings options from the window PFC 6030 5403595 REV C 2 13 Serial Parallel Printer SPG 1000 The SPG 1000 module allows up to 31 serial and or parallel printers to be used to log system events Note Parallel printers must be connected to the DB25 J1 connector serial printers to the DB9 J2 connection To add and configure the SPG 1000 1 Select SPG 1000 from the system panel 2 Click the Add Device button to display the Add Device window Figure 127 Example of the Add SPG 1000 Window P
50. 1 10 07 53AM System Login User 3 AEE e 01 12 2011 9 14 294M System Login User 3 01 12 2011 9 14 004M Remote Programming Pass 01 12 2011 9 14 004M System Powerup 01 12 2011 9 13 444M System Login User 3 01 12 2011 9 00 124M System Login User 3 01 12 2011 8 43 344M System Login User 3 01 12 2011 8 42 314M System Login User 3 01 12 2011 8 19 444M System Login User 3 01 12 2011 8 14 124M System Login User 3 5 68 4 mi Training Panel History mo PFC 6030 5403595 e REV C 2 13 lene System e mail communications and functions are intended for informational reporting purposes only They are intended to be used as a convenience function E mail communications should NOT be used as a primary means of reporting emergency information Creating E mail Reminders E mail reminders are fully customizable e mail messages that may be sent based on a predefined schedule The e mail subject and body are defined by the installer and the History and or Detector Status reports may be attached Up to eight separate e mail reminders can be created to be sent on a daily weekly monthly or yearly schedule Figure 95 Example of the Email Reminder Window Reminder 1 Reminder 2 Reminder 3 Reminder 4 Reminder 5 Reminder 6 Schedule O Yearly O Monthly O Weekly Total characters in all reminders 0 2000 To create Reminder e mails 1 Select the E mail Reminders option on the panel menu 2 Click a Schedu
51. 16s LED Driver DRV 50 The panel supports up to ten 10 LED drivers The DRV 50 provides up to 50 LED outputs which may be mapped to any zone Like the LED annunciator the LED driver provides five 5 non programmable system LEDs that annunciate the overall system condition Power Earth Silenced Alarm Supervisory and Trouble Additionally the LED driver has four 4 programmable supervised dry contact inputs Note This panel supports up to ten 10 DRV 50 drivers and or LED 16 annunciators in any combination To add and configure a LED driver 1 Select DRV 5 from the system panel 2 Click the Add Device button The 4dd Device window displays Figure 122 Example of the Add DRV 50 Window Add Device Type Name Address DRY 50 DRW 50 1 1 3 Double click in the Name field to customize name 4 Double click in Address field to adjust address if needed 5 Repeat steps as needed to continue adding DRV 50s PFC 6030 5403595 REV C 2 13 Relay Board RLY 5 The panel supports up to thirty one 31 Relay Boards Each RLY 5 provides five 5 Form C relay outputs which may be individually mapped to any zone To add and configure a relay board 1 Select RLY 5 from the system panel 2 Click the Add Device button to display the Add Device window Figure 123 Example of the Add RLY 50 Window Add Device Delete Device eee Type Name Address RLY 5 RLY 5 1 1 3 Double click
52. 24VDC source and is fully supervised Figure 39 RLY 5 Wiring to Control Panel or Auxiliary Power Supply Examples amp RLY 5 Showing Normally Open Normally Closed Contacts Example Example Powered by Powered by control panel aux supply D OIR P Lik RILY P Lin A B A P Link fi Power from P Link from eu auxiliary control panel control panel supply DWG 608 6 3 30 NC Normally Closed C Common NO Normally Open d ONC C NO NC C NO NC C NO NC C NO RELAY 1 RELAY 2 RELAY 3 RELAY 4 RELAY 5 eleele DWG 608 10C PFC 6030 5403595 e REV C 2 13 Setting Addresses The RLY 5 s address is set by dip switch S1 which is located on the back of the board The address must be set in the range of one to thirty one 1 31 to be recognized by the panel Refer to the P Link Addresses table shown earlier in this section for DIP switch programming Figure 40 Relay Board Back Panel View Showing Dip Switch Location O O 1211 1616 1 6
53. 75 O O IO O I O O OU pop ou dopo JU D O maana S 2 5 2 S 1 S 1 james S S suena S 2 r S 1 S 1 Potter Electric Signal Company a Potter Electric Signal Potter Electric Signal Compar O PO isg O PO acorn O PO menta O E a eid o o i E o o il ni o LOA O A O LOL O 22 Je C2 21 ncn C1 E oD 0 O 01 0 0 O SCI S O SCI PFC 6000 Series SLC Loop Class A Style 7 Terminal Connections GH E O O O O O O DWG 593 9 Notes 1 The Class A Style 7 requires installation of an isolator close nipple connected to every module or sensor Isolators may be either a SCI or an AIB addressable base 2 Class A Style 7 requires installation of a CA 6075 3 The SLC connection requires that the wires are separated by a minimum of 10 and installed in conduit or other mechanical protection 4 Maximum wiring resistance must not exceed 50 ohms 3 14 PFC 6030 5403595 REV C 2 13 Connecting Analog Detectors When installing analog detectors such as a photoelectric smoke sensor PSA photo smoke fixed heat detector PSHA heat detector FHA or an analog combination type heat detector RHA use detector bases i e AB 6 An analog detector activates its response LED when activated An example of wiring an analog detector is shown below Figure 10
54. 94 1 5 62 PFC 6030 5403595 e REV C 2 13 NOTICE System e mail communications and functions are intended for informational reporting purposes only They are intended to be used as a convenience function E mail communications should NOT be used as a primary means of reporting emergency information P Link E mail Notification Requirements The following table lists the necessary hardware and Internet connectivity requirements to use P Link functions such as DACT and e mail notification Table 13 P Link E mail Notification Requirements 10 100 Mbps Ethernet Network IP Address Protocol DHCP or Static IP factory default is DHCP Must have outbound access to Internet mail server connections only Outbound Connectivity Port 10025 for SMTP Port 110 for POP3 Inbound Connectivity None required or utilized Connecting the Panel to a Network In order to use the e mail feature the panel must be connected to a network with Internet connectivity This is usually accom plished by installing an Ethernet drop near the panel The IP address can be set one of two ways e The panel has a built in DHCP Dynamic Host Configuration Protocol and will ask for an IP address from the Host Computer e The installer or the Network Administrator may set the IP address using the software s Static IP function Figure 86 Setting the IP Address v IX Panel Network Settings Q Remote Access Code Netbios Name Set the IP addr
55. A N A N A I gt PSN 1000 Power Supply PSN 1000 1 118 B 6 103 PFC 6030 5403595 REV C 2 13 Notes e Ifa power supply is Class A select the applicable NACs NAC 1 2 NAC 3 4 or NAC 5 6 e Ifa power supply is Class B programming is completed e Class A operation may be independently selected for the P Link repeater output and any of the NAC circuit pairs 4 Repeat steps as needed to continue creating or adding additional power supplies Deleting a Power Supply To delete a power supply 1 Select the Power Supply function from the system panel to display all current power supplies Figure 147 Example of Power Supply Window Potter Fire Panel Programmer File Options Help eis _ Nov 11 2011 Test fpcf Oanavwnere Aa Ne a aii D NAC 1 2 NAC 3 4 NAC 5 6 Type Name oe oe a Internal Power Supply PSN 1000 Power Supply PSN 1000 1 PSN 1000 Power Supply PSN 1000 2 gt Psn 1000 Power Supply PSN 10003 Note The Internal Power Supply may not be deleted as indicated by the message in the following dialog box Figure 148 Example of Dialog Box Showing Internal Power Supply Cannot Be Deleted 2 Click anywhere in the power supply s line item then click the Delete Device button Tip You may delete more than one power supply in one step by first selecting a range or group using Window s SHIFT CLICK or CTRL CLICK methods respectively 6 104 PFC 6030 5403595 e REV C 2 13
56. B9 connector Supervise Port If selected the SPG 1000 continuously monitors the connected printer for the presence of a serial printer if not connected a Trouble event is annunciated Baud Rate This option specifies the baud rate used to transmit data to the connected printer default is 9600 baud rate Flow Control If selected this specifies the flow control method when sending data to the printer Refer to specifications of the connected printer for proper settings Data Bits This option specifies the number of data bits used when sending data to the printer Refer to specifications of the connected printer for proper settings Parity This option specifies the parity used when sending data to the printer Refer to specifications of the connected printer for proper settings Stop Bits This option specifies the number of stop bits used when sending data to the printer Refer to specifications of the connected printer for proper settings 6 Repeat steps as needed to continue adding and configuring printers 5 88 PFC 6030 5403595 e REV C 2 13 DACT UD 1000 Each system may have one DACT module or Digital Alarm Communicator Transmitter The DACT provides notification to a remote monitoring company when alarms troubles and supervisory conditions occur Programming options allow you to select separate accounts for test events and alarm trouble and supervisory conditions You may set up telephone parameters such as numb
57. Back Panel View P Link Connections DWG 593 31 LED Annunciators Installation LED 16 The panel supports up to ten 10 LED 16 annunciators which display alarm supervisory and trouble conditions for up to 16 zones per LED 16 It also provides Silence and Reset functionality Blank zone labels are provided for use with the LED annunciator to label each zone name or identifier The labels may be typed or written on the supplied card stock and then inserted into the back of the front panel as shown in the right most figure below Note This panel supports up to ten 10 LED 16 annunciators and or DRV 50 drivers in any combination Labels are inserted Figure 30 LED 16 Module amp Board Y here as needed i H D A S O O ce f ALARM f ALARM SYSTEM SUPERVISORY SUPERVISORY 5 TT ____ TROUBLE ____ TROUBLE POWER A A O ee ee Zone labels AM 000 panii M 000 will display here ooo DOO Si eS 000 r gt ALARM aie 000 O00 O CLE _ 000 SUPERVISORY s ooo
58. CE button After the condition that caused the alarm has been identified and corrected the system may be reset to the Normal Standby by pressing the RESET button When a supervisory condition is detected the amber SUPERVISORY LED will illuminate and the buzzer will sound The LCD display will indicate the number of supervisory events that are active The local buzzer will sound until all supervisory events have been acknowledged If the Supervisory condition is non latching once the device is restored to the normal condition the supervisory event will clear If the supervisory condition is latching the device that was activated must be restored and the RESET pressed When a fault condition occurs the amber TROUBLE LED will illuminate and the local buzzer will sound until the fault is removed or the ACK button is pressed acknowledging the trouble condition If the buzzer is acknowledged and the fault 1s not removed within 24 hours the buzzer will resound When a trouble is occurring the local buzzer will sound until either all troubles have been acknowledged or the SILENCE button is pressed When a conductor contacts and earth ground the amber EARTH FAULT LED will illuminate and the LCD display will provide further information of where the fault is located The amber Pre Release LED will illuminate when the system is in a count down timer for an agent release Additionally pre release events and countdown timers are displayed on the LC
59. D The red Release LED will illuminate when a release condition is active Additionally release events will be displayed on the LCD If the system 1s being used as an agent releasing panel and a pre discharge timer is programmed the release may be aborted by pressing the abort switch For ULI installations pushing the Abort will allow the timer to countdown until 10 seconds and then halt Releasing and reactivating the Abort will set the timer to 10 seconds Test this system monthly or more frequently as required by the AHJ Before conducting any testing contact the building personnel and the monitoring facility as applicable When testing a system configured for releasing activate the releasing disconnect switch to prevent accidental discharge of a suppression system Test the circuits as outlined in the Installation Manual Test in accordance with NFPA 72 Inspection Testing and Maintenance Chapter s and any local requirements The batteries should be marked with the date of installation and replaced every four years or sooner if battery trouble occurs Batteries should be checked with a tester acceptable to the AHJ such as a Stone Technologies model STC612A or equivalent In case of a fuse replacement refer to the Installation Manual for the proper rating Contact the agency below for service or operational questions For service contact Name Company Address Telephone
60. ILILILILIW p JUUUUL P Link Terminals Non power limited battery connection Power limited wiring 18Ahr 12Volt 18Ahr 12Volt DWG 602 23 6 94 PFC 6030 5403595 e REV C 2 13 Rechargeable Battery Circuit The battery charging circuit is on the power supply board providing terminal connections to connect the wire leads The battery must be a recognized or listed sealed lead acid battery or equivalent It is rated for 8 to 55 AH batteries and will operate the panel alarm for at least 24 hours and 5 minutes The battery charging voltage is approximately 27 3 VDC and the circuit 1s supervised The maximum battery charging circuit 1s 1 0 amp DC The cabinet will house up to two 2 18 AH batteries Battery Circuit Calculation Before selecting the battery the installer must determine the minimum size batteries for standby and alarm times desired for each application If the wrong batteries are installed or incorrect current draw used the proper standby and minimum alarm time will not be present Please use the Battery Calculation Worksheet located on the next page to calculate the battery size and current draw required for each application 6 95 PFC 6030 5403595 REV C 2 13 PSN 1000 PSN 1000 E Battery Calculation Worksheet Complete one for all P Link devices powered by the PSN 1000 PSN 1000 E mA mA Pno soona a o CD Reme R s l a S s o Tormes S o S o soore S o o o s E amp LED Current if applicab
61. Listed Herein From Potter Shall Be For Damages And Potter s Liability For Any And All Losses Or Damages Resulting From Any Cause Whatsoever Including Negligence Or Other Fault Shall In No Event Exceed The Purchase Price Of The Product In Respect To Which The Claim Is Made Or At The Election Of Potter The Restoration Or Replacement Or Repair Of Such Product Potter Electric Signal Company LLC 5757 Phantom Drive Ste 125 St Louis MO 63042 314 595 6900 800 325 3936 PFC 6030 5403595 e REV C 2 13 Table of Contents Section 1 IntrodU CIO cecesscacasanccsaisacessscscaivsncces lt caaavancesaitassuveeusaiseuscesccasavancssaiwadestebucuaweua amp esecaaaeaiecseinacessateas 1 1 a AA o OOO ER A 1 1 AI A ROI A 1 1 BW SUC 1M e AUIS A A E O ER 1 1 TELE AECA SA A E E 1 1 DEC OOD ACC OSS O cae tir 1 2 AOS SAL SHS OV 5 a A ooo 1 2 TE ODV OSS CO IMANES td tte it talca 1 2 Howto Use ts IV IIa AE csi das 1 2 Bes y AP e II e ENE 1 2 Section 2 Before You Start TSCA AMOI cscccsescosesccscncscuseovssrcausessteciassousesensasecosvesecansucstessescissesevcssensavesveass 2 3 gt OC ie eaten E E E E EE 2 3 EA E Ee CLIC 11S A E E A A TE O O TA E E E ees 2 3 System Contisutations Appa siii iris 2 3 Electrical CLC AMI ONS eos 2 4 Sa re a A 2 4 Mam Board Wiring PEC a 2 5 Sucia A PA 2 5 AT Diet 2 5 Es O O IR eo PRO OO IA 2 6 Cabe Wim Come OS sitiada adicta ela 2 7 Battery Cire iit CONS ici oa dnnalsesandesaiaaastie aisisiaed anal wsasdesaneiastiaie
62. Note Once enabled the remote access will time out after thirty 30 minutes 1f contact is not established 5 49 PFC 6030 5403595 REV C 2 13 File New The File New menu option is used to complete all programming from scratch on the computer You must select the correct panel model prior to programming Note It is imperative that you choose the correct panel model prior to programming or completing any data transfers otherwise you cannot complete a successful download to the panel If this occurs you will have to reprogram the entire panel Figure 64 Example of File New Dialog Box New Options File Ea lx Type of new file PFC6030 PFC6075 PFC6200 PFCES00 File Save Save As Once programming has been completed save your configuration file using either the File Save or File Save As function An audit is performed that checks for rule violations if errors are encountered you may choose to either save with errors or cancel the save operation Figure 65 Example of Save Panel Dialog Box Save Panel File Save in e pipc tion_6524981 6ff0a49cf_0001 0000_62t e E eE Ed 8 Config 2010 10 27 15 09 35 13 wcf Ee Config 2010 11 04 12 07 13 09 veF My Recent S5 Default 6030 vcf Documents 5 3Default 6075 vct 3 Default 6075R vef 8 download test wcf Desktop SM error test 1 ycf pa SJ marriott atlanta perimeter mall vcf My Documents My Computer My Networ
63. PFC 6030 Fire Alarm Control Panel Installation Operation amp Programming Manual MIER PFC 6030 Addressable Fire Alarm P The Symbol of Protection Potter Electric Signal Company LLC St Louis MO Customer Service 866 240 1870 Technical Support 866 956 1211 Fax 314 595 6999 www pottersignal com Manual 5403595 Rev C 2 13 PFC 6030 5403595 REV C 2 13 The Symbol of Protection P POTTER WARRANTY INFORMATION The essential purpose of any sale or contract for sale of any of the products listed in the POTTER catalog or price list is the furnishing of that product It 1s expressly understood that in furnishing said product POTTER does not agree to insure the Purchaser against any losses the Purchaser may incur even if resulting from the malfunction of said product POTTER warrants that the equipment herein shall conform to said descriptions as to all affirmation of fact and shall be free from defects of manufacture labeling and packaging for a period of one 1 or five 5 year s depending on the product from the invoice date to the original purchaser provided that representative samples are returned to POTTER for inspection The product warranty period is stated on the exterior of the product package Upon a determination by POTTER that a product is not as warranted POTTER shall at its exclusive option replace or repair said defective product or parts thereof at its own expense except that
64. PSN 1000 PSN 1000 E via the main P Link circuit This connection is electrically isolated from the rest of the PSN 1000 PSN 1000 E Figure 139 P Link Wiring from Control Panel P LINK P Link from Control Panel DWG 602 27 6 99 PFC 6030 5403595 REV C 2 13 Repeater Output The PSN 1000 PSN 1000 E repeater output provides power which supports additional P Link devices including LCD Annunciators and or SLC Loop expanders This 1s possible because the P Link repeater output reconditions and repeats all P Link communications Refer to the following figures for examples of Class A and B wiring Configuration Characteristics PSN 1000 current rating 1s one 1 amp PSN 1000 voltage rating 1s 24 VDC The maximum wire length is 6 500 feet Wiring is fully supervised and power limited Maximum Wire Resistance Formula The maximum resistance is based on the oad placed on the circuit To calculate the maximum wire resistance use the following formula Total Annunciator Alarm Current x Wire Resistance lt 6 Volts Note Any connection to ground of 0 ohms will be annunciated as a ground fault Figure 140 P Link Class B Repeater Wiring Example To the next device DOO OVO O DIO qu alo Ab Expansion Device ik q NAC 2 NAC 4 NAC 6 1 NAC 1 NAC 5 NAC 3
65. Purchaser shall pay all shipping insurance and similar charges incurred in connection with the replacement of the defective product or parts thereof This Warranty is void in the case of abuse misuse abnormal usage faulty installation or repair by unauthorized persons or if for any other reason POTTER determines that said product is not operating properly as a result of causes other than defective manufacture labeling or packaging The Aforesaid Warranty Is Expressly Made In Lieu Of Any Other Warranties Expressed Or Implied It Being Understood That All Such Other Warranties Expressed Or Implied Including The Warranties Of Merchantability And Fitness For Particular Purpose Are Hereby Expressly Excluded In No Event Shall Potter Be Liable To Purchaser For Any Direct Collateral Incidental Or Consequential Damages In Connection With Purchaser s Use Of Any Of The Products Listed Herein Or For Any Other Cause Whatsoever Relating To The Said Products Neither Potter Nor Its Representatives Shall Be Liable To The Purchaser Or Anyone Else For Any Liability Claim Loss Damage Or Expense Of Any Kind Or Direct Collateral Incidental Or Consequential Damages Relative To Or Arising From Or Caused Directly Or Indirectly By Said Products Or The Use Thereof Or Any Deficiency Defect Or Inadequacy Of The Said Products It Is Expressly Agreed That Purchaser s Exclusive Remedy For Any Cause Of Action Relating To The Purchase And or Use Of Any Of The Products
66. RANCH 4 DWG 593 3 Configuration Summary Branch 1 has 3 devices 8 power allocations Branch 2 has 2 devices 8 power allocations Branch 3 has 10 devices 10 power allocations Branch 4 has 4 devices 8 power allocations Total addressable devices 15 Sensors only out of 30 addressable points Total device load 34 out of a possible 127 power unit allocations 2 11 PFC 6030 5403595 REV C 2 13 Battery Connections The battery charging circuit 1s located on the main panel in the lower left portion of the board The maximum battery charging circuit is 1 0 amp DC the charging voltage is approximately 27 3 VDC and is supervised Note The battery should be clearly labeled as Sealed Lead Acid Battery or equivalent UL listed or UL Recognized Connect the battery wire leads to the terminal connections as shown Batteries should be replaced every five 5 years or sooner depending on annual testing Figure 5 PFC 6030 Battery Connections IREI O men Panel Connections 12 V Battery DWG 593 5 Main Supply Circuit The AC terminals are located in the upper left hand portion of the main board The main board supervises the main AC power and provides indication that the AC power is absent Figure 6 PFC 6030 AC Terminals 120VAC 50 60 Hz 240VAC 50 60 Hz Connect to separate Unswitched AC circuit DWG 593 6 The terminals are rated at 120
67. Zone Attributes HS ao 9096 in this Section for an explanation of 11 tech dpottersignal com F E 12 ones potasa com Day Night Sensitivity settings 13 k A 15 Address Sensor Type Sensor Name Current Condition Peak Walue Day Sengditivity Night Sensitivity Thermal Alarm Level Drift Percentage Drift Limit NFPA 72 Compl 1 PHOTO Point 1 0 00 000 0 00 000 3 5 055 3 5 055 n a 0 00 060 1 80 089 Yes 2 PHOTO Point 2 0 00 000 0 00 000 3 5 055 3 5 055 n a 0 00 060 1 80 089 Yes 3 PHOTO Point 3 0 00 000 0 00 000 3 5 055 3 5 055 n a 0 00 060 1 80 089 Yes F 4 PHOTO Point 4 0 00 000 0 00 000 3 5 055 3 5 055 n a 0 00 060 1 80 089 Yes 5 PHOTO Point 5 0 00 000 0 00 000 3 5 055 3 5 055 n a 0 00 060 1 80 089 Yes 6 PHOTO Point 6 0 00 000 0 00 000 3 5 055 3 5 055 n a 0 00 060 1 80 089 Yes 7 PHOTO Point 7 0 00 000 0 00 000 3 5 055 3 5 055 n a 0 00 060 1 80 089 Yes 8 PHOTO Point 8 0 00 000 0 00 000 3 5 055 3 5 055 n a 0 00 060 1 80 089 Yes 9 PHOTO Point 9 0 00 000 0 00 000 3 5 055 3 5 055 n a 0 00 060 1 80 089 Yes 10 PHOTO Paint 10 0 00 000 0 00 000 3 5 055 3 5 055 n a 0 00 060 1 80 089 Yes 11 PHOTO Point 11 0 00 000 0 00 000 3 5 055 3 5 055 n a 0 00 060 1 80 089 Yes 12 PHOTO Point 12 0 00 000 0 00 000 3 5 055 3 5 055 n a 0 00 060 1 80 089 Yes 13 PHOTO Point 13 0 00
68. able Sensing Technology e Drift Compensation e Drift Alert e NFPA 72 compliant calibrated smoke test built in P Link Accessories e RA 6500 or RA 6075 Remote Annunciator Maximum of 31 per system in any combination e UD 1000 Dual Line Fire Communicator Maximum of 1 per system e CA 6075 Class A converter module Maximum of 1 per system allows for Class A wiring of the SLC circuit P Link communication bus and the two 2 built in NAC circuits 1 1 PFC 6030 5403595 REV C 2 13 e PSN 1000 PSN 1000 E Intelligent Power Supply Expander An accessory to the panel providing ten 10 amps of additional power with four 4 input points six 6 notification circuits and a P Link interface e LED 16 Annunciator module Maximum of 10 total per system the total may be any combination of LED 16 and DRV 50 LED modules allows for up to 16 zones alarm supervisory and trouble conditions to display and 5 non programmable system LEDs that display system s overall condition e DRV 50 LED Driver module Maximum of 10 total per system the total may be any combination of LED 16 and DRV 50 LED modules allows output to up to 50 LEDs 4 dry contact inputs and 5 non programmable system LEDs that display system s overall condition e RLY 5 Relay Board module Maximum of 31 per system provides five 5 Form C relay outputs e FCB 1000 Fire Communications Bridge An accessory that provides a remotely located IP connection to the panel e FIB
69. allocations or device load Figure 3 Example of a Class A Loop Isolated Branches LEGEND ISO Module Device Sensor O Total addressable devices 8 Total isolators 9 PANEL DWG 593 4 Configuration Summary Total addressable devices 8 sensors only out of 30 possible addressable points Total device load 17 calculated as follows 8 sensors 9 isolators out of 127 power unit allocations Example If a configuration uses 30 sensors up to 97 isolators may be supported Solution 127 30 97 2 10 PFC 6030 5403595 e REV C 2 13 Scenario 2 Class B Loop Isolated Branch Configuration In this configuration there are 4 separate branches each with an isolation device module and 1 or more sensors Each sensor requires an address as shown in Scenario 1 isolators do not require an address However in this scenario each isolator consumes power equal to 8 devices To calculate the total device load refer to the following rule Device Load Rule for Branch Configurations Count all devices including isolators on the branch e Ifthe count is lt 8 allocate 8 as the device load e Ifthe count is gt 8 allocate the actual device count number Figure 4 Example of a Class B Loop Isolated Branches BRANCH 1 OO Total devices 3 O Total devices 2 O de ES Total devices 4 LEGEND ISO Module Device BRANCH 2 Sensor Total devices 10 BRANCH 3 B
70. arallel Settings Serial Settings Event Off line Event Off line iene Supervise Supervise n unha Supervise Flow Data n Stop Type Name Address Printing Out of Paper off line time Printing Port time Baud Rate Control Bits Parity Bits Enabled secs Enabled secs SPG 1000 SPG 1000 1 1 E E 60 E E 0 9600 None 8 None 1 SPG 1000 SPG 1000 2 2 E O 60 E 0 9600 None 3 None 1 3 Double click in the Vame field to customize name 4 Double click in Address field to adjust address if needed 5 Select the applicable Parallel Serial setting options as described below PARALLEL PRINTERS Event Printing Enabled If selected system events are logged to a connected parallel printer via the DB25 connector Supervise Out of Paper If selected the SPG 1000 continuously monitors the connected printer for an out of paper condition When this condition occurs a Trouble event is generated and is annunciated by the panel Supervise Off line This option continuously monitors the connected printer for an off line condition 1f selected When this condition occurs a Trouble event is generated and annunciated by the panel Off line time secs If this option is selected the off line time specifies the amount of time the condition must be present before a Trouble event is generated Default time is 60 seconds SERIAL PRINTERS Event Printing Enabled If selected system events are logged to a connected serial printer via the D
71. as needed To configure a group of selective points 1 Click the first point in Function field to configure 2 Press and hold the CTRL key then click selective points from Function field Figure 106 Example of Configuring Multiple Selective Points Device 2 Addr Name Function Built in SLC 1 Point 1 Unused Built in SLC 2 Point 2 Unused Built in SLC 3 Point 3 Unused Built in SLC 4 Point 4 Unused Built in SLC 5 Point 5 Unused Built in SLC 6 Point 6 3 Right click from Function field to display configuration options Note If you select points or right click outside of Function field the points are deselected and only one 1 device will be configured 5 79 PFC 6030 5403595 REV C 2 13 4 Click on device type from the shortcut menu In the example shown here Addr Detector Photo Heat has been selected as the device type Figure 107 Example of Configuring Selective Points Device amp Addr Name Function Built in SLC 1 Point 1 Addr Detector Photo Heat Built in SLC 2 Point 2 Unused Built in SUC 3 Points Addr Detector Photo Heat Built in SLC 4 Point 4 Unused Built in SLC 5 Point 5 Unused Built in SLC 6 Point 6 Built in SLC 7 Point 7 Built in SLC 8 Point 8 Unused Built in SLC 9 Point 9 Unused Adding Points to Zones This section provides procedures and examples of adding points to one or more zones Points can be moved and deleted from
72. at the keypad to remove condition Nenciatehin Device will automatically reset when condition is no longer present i e smoke detector resets once 8 condition clears The purpose of creating cross zones is to ensure that two 2 or more separate zones are activated before an output zone is triggered Example Smoke detector in Zone 1 R amp D Lab and a heat detector in Zone 2 Main entrance are Cross Zoning activated triggers an air handler circuit 7 E e The redundancy in this example provides verification of an alarm condition by requiring that both sensors in two 2 different zones are activated before an output occurs e There are no limits to the number of cross zones that can be mapped to the same output as soon as a pair of input devices detects an alarm condition the output will be activated Zone Types Styles You may define or configure each zone to serve a specific purpose or to create specific output results For procedures on how to select Zone styles refer to the Configuring Zones section of this manual The following zone styles are available Table 16 Zone Styles e Default zone type e Sets system into an Alarm condition when any input is activated Supervisory Used for all Supervisory inputs Alarm Positive Alarm Sequence Implements Positive Alarm Sequence Auxiliary Used for all Aux inputs Fire Drill Comprised of input output devices that will activate when running a Fire D
73. ated work surfaces tools jewelry and coins e Ifa battery is shorted the battery and any connected equipment may be damaged Additionally a short may injure personnel C PFC 6030 5403595 e REV C 2 13 Appendix D PSN 1000 PSN 100 Maintenance and Testing De Energize Unit Prior to Servicing The power supply board has one fuse on the board for the AC power over current protection The AC fuse is rated at 8A 250VAC Time Lag and screened onto the main board as Fl The batteries are to be replaced at least once every four years The batteries are required to be UL recognized batteries with a date of manufacture permanently marked on the battery The battery 1s to be tested at least annually and if the battery is showing signs of failure it 1s to be replaced The battery is to remain in the cabinet with nothing on or around the batteries Only properly sized sealed lead acid batteries are to be used with the control panel Use of another battery or not providing the proper clearance may result in a fire or an explosions The PSN 1000 is required to be installed in accordance with local and state building codes and NFPA 72 National Fire Alarm Code The PSN 1000 and related system is required to be inspected and tested in accordance with NFPA 72 PFC 6030 5403595 e REV C 2 13 This section provides a listing of all NAC appliances two wire 2 wire smoke detectors releasing and SLC circuit devices optional modules and
74. ates 6 91 WVIAC C1 CAI ONG ind 6 91 CV COG O 1 AA ete cosas evap neste ese EAT EEE A EIE A asst a cero eed gt eas 6 9 ASA NESEN PP A 6 92 Cabinet DIMAS oo toco 6 92 Ss o REO A 6 93 Cabinet Wir o Conde a E E I E O A O OE O E 6 94 Recharecable Balseros opone da nae EEE 6 95 Battery 10 I AIC AOU airis 6 95 PSN 1000 PSN 1000 E Battery Calculation Worksheet oooccccccncnccononononinonicononinonineninicininininess 6 96 Notification Atypon S06 eC TSI Ds t ties 6 97 NAC VOTO ici caa 6 97 NAC WINS CON Ora NONS iia tobr 6 97 TA POUAL ICU iaa a ori ase eccdcasaauasnoatecanacsaneiaaniaccauaseauaseatecianee 6 99 COM TWA OM CHAVA OV ISUICS a A taa cias 6 99 A AS A 6 99 Konea IU didas 6 100 SONDAS A P EE 6 100 NACI Mire Iesistanco TOV espia OEREO 6 100 Nuntcipal Box Connec ON siseses nnee e oc 6 101 CON O ATA TOTIS OS ati 6 101 AA II E A O E E OE EES 6 101 PSN IO0O PSN 1000 E V Operations sisi diritto tel n 6 102 TUS E D D liada 6 102 PSN I000 BS Na OOO Pi Sr ta ol 6 103 PRODI TT AS casera ose sets E E E E E ss sz24ieeaicpigendsc lt tesenacniesasy 6 103 DANS OW OF UDI aes cs see E E E E EA S E EE E S 6 104 Secon 7 IF COMMUnICA ION inerciales 7 105 Programming the IP Communicator rr cette 7 106 LPR DOT O ACCO S r E EA E E E AEE E E E 7 106 Appendix A Basic Operating InstructionSs ssesssccecccsssssscecocoossssseccocoossssscecooossssssceccososssssseesossssssssee A 1 Appendix B Modem Connectivity Setup esessssssss
75. ault detection on the NAC circuits The impedance to ground for ground fault detection is 0 ohms 6 97 PFC 6030 5403595 REV C 2 13 Figure 137 PSN 1000 PSN 1000 E Class A NAC Wiring Example 12 i NAC 2 l I1 NAC 1 i1 NAC 5 NAC 3 Notification Appliance l DWG 602 25 6 98 PFC 6030 5403595 e REV C 2 13 Input Circuits The panel is equipped with two 2 input circuits I1 and I2 that are low voltage power limited and supervised When configured the circuits function as dry contact monitoring circuits Note These circuits operate as Class B only Please refer to the figure shown below Configuration Characteristics e Maximum allowable wire length is 10 000 feet e Maximum allowable wiring resistance is 100 ohms e Maximum wiring capacitance is uF e Maximum IDC voltage is 24 VDC and current is 15 ma Figure 138 Example of PSN 1000 PSN 1000 E Input Circuit Normal Open Dry Contact NAC 1 NAC 5 NAC 3 Normally Open Dry Contact 5 1k EOL DWG 602 26 Potter Part 3005013 Notes 1 The Potter part number for the listed end of line assembly is 3005013 EOL Resistor Assembly 2 The panel has ground fault detection on the input circuits The impedance to ground for ground fault detection is 0 ohms 3 The end of line resistor is a 5 1K ohm resistor Wiring to Control Panel The control panel communicates with and supervises the
76. ccordingly The panel is not able to communicate with a device Action Check device is currently operating and or connect device to SLC loop SLC 1 Missing Monitored Output Module is missing 24 VDC connection Action Check for 24 VDC to the device Back up batteries are missing or need to be replaced Action Connect or replace batteries as needed SLC HP OPEN PWR F 1 PFC 6030 5403595 e REV C 2 13 MAIN MENU 1 View History 2 Enable Disable 3 Set Date Time 4 Walk Test Boo el 1 By Point 2 By Zone Select Device Zone 1 Internal SLC 1 Disable Inputs Internal PWR 2 Disable Outputs MAIN MENU 5 System Tools 6 Programming 7 Data Transfer Y 1 SLC Tools 1 LEARN Mode Select Data 2 Point Control 2 Panel Default 1 Remote Access 3 Ethernet Status 3 IP Settings 2 E mail Det Stat 4 DACT Test 4 Dflt ID Pswd 3 E mail History 5 DACT Reset 5 Prog ID Pswd 4 E mail Config 6 Erase History Esc Exit 5 E mail Test 7 Lamp Test 6 Server Status 8 App Revisions Esc Exit 1 SLC Pinpoint 2 SLC Stats 3 SLC Addr Prog 1 Username 2 Password Esc Exit 1 Single Device 2 Mltp Device Ethernet Options 1 DHCP Settings 2 Default IP 3 Default Gateway 4 Default Subnet 5 Alternate IP 6 Alt Gateway 7 Alt Subnet Ese Exit TIP To save time enter the menu selection number on the keypad to select a function For example press 3 to select Set Date Time from the Main Menu G 1 P
77. ce window The selected points display in the Device window as shown below Figure 110 Example of Moving Selected Points into a Zone Points ax Name Style am ro Latching Local Output Pattern i Loop Addr Name Function a Zone 1 Alarm i O Constant PWR Supply 1 NACI Conv NAC General Purpos PWR Supply 2 NAC2 Conv NAC General Purpos PWR Supply 3 IO Ckt 1 Conv NAC General Purpos PWR Supply 4 IOCkt2 Conv NAC General Purpos Built in SLC 1 Point 1 Addr Detector Photo Built in SLC 2 Point 2 Addr Detector Photo Built in SLC 3 Point 3 Addr Detector Photo Built in SLC 4 Point 4 Addr Detector Duct Built in SLC S Point 5 Addr Detector Duct Built in SLC 6 Point 6 Addr Sounder Base gt Built in SLC 7 Point 7 Addr Sounder Base Built in SLC 8 Point 8 Addr Detector Heat Fixed pai pets o Funcion Built in SLC S PointS Addr NAC General Purpos PWR Supply 1 NACI Conv NAC General Purpose E Built in SLC 10 Point 10 Unused PWR Supply 2 NAC 2 Conv NAC General Purpose E Built in SLC 11 Point 11 Unused PWR Supply 3 IOCktii Conv NAC General Purpose e Built in SLC 12 Point 12 Unused PWR Supply 4 IO Ck 2 Conv NAC General Purpose E Built in SLC 13 Point 13 Unused Built in SLC 1 Point 1 Addr Detector Photo E Built in SLC 14 Point 14 Unused Built in SLC 2 Point 2 Addr Detector Photo E Built in SLC 15 Point 15 Unused Built in SLC 3 Point 3 Addr Detector Photo E Built in SLC 16 Point 16 Unused Built in SLC 4 Point 4 Addr Detector Duc
78. ciators sic Loop DOOBABOAAAARAOAODAAS SBS a a 4 a 4 A a B A BB 4 0 O E E E a a 4 A 4 A a B Bd 00000 m c m c m m m m m m m El m 5 66 PFC 6030 5403595 e REV C 2 13 ele System e mail communications and functions are intended for informational reporting purposes only They are intended to be used as a convenience function E mail communications should NOT be used as a primary means of reporting emergency information Receiving E mail Status Reports When a system status Alarm Supervisory Trouble events e mail is received the body of the e mail contains the information entered in the Job Details section of the software as shown below If nothing is entered in the software the body of the e mail will only indicate the events that occurred The events are listed after the Job Details information They are formatted with a date time stamp showing when the event occurred event type and the event description or the point information Figure 91 Example of Job Details in System Status E mail hip e _ Fil Insert Format Tools Actions Help e Job Name Potter Fire Control Panel te Nia A 4 oes Address Line 1 5757 Phantom Drive 0 i r 4 mat pfc6075r0000023 potterlink com Q Job Details l Address Line 2 Suite 125 l Ec a Subject Potter Fire Control System Status Q General Options l Address Line 3 Hazelwood MO 63042 i Pot
79. codes when required to access restricted functions Alternatively the numbers may be used to quickly select menu options vs using the arrow and Enter keys to select a function Figure 55 Control Panel Numeric Keypad Function Pushbuttons The four 4 function pushbuttons are used when system alarm trouble conditions occur or to perform a fire drill Figure 56 Control Panel Pushbuttons 4 38 PFC 6030 5403595 e REV C 2 13 The table below provides a brief summary of the pushbuttons Table 7 Control Panel Pushbuttons Press to acknowledge the currently displayed condition Press to silence all outputs programmed as silenceable and buzzer Press to reset panel to normal condition Press to begin a fire drill Status LEDs The control panel s LEDs communicate system conditions by illuminating and or flashing the applicable green red or amber indicators These are described in the table below Figure 57 Control Panel Status LEDs POWER ALARM EARTH FAULT SUPERVISORY SILENCED TROUBLE Table 8 Status LEDs Power is present Steady Green Note If power is absent for more than 5 seconds LED will extinguish 4 39 PFC 6030 5403595 REV C 2 13 Control Panel Menu Tree This section provides a reference to menu options as they appear on the LCD panel Appendix G also provides a copy of the menu tree MAIN MENU 2 Enable Disable 1 View History 3 Set Date Time 4 Walk Te
80. cribe to the panel e Subscribe to activate e mail settings for the sender Note Keywords are NOT case sensitive and more than one can be entered in the subject line of the e mail 4 There are no restrictions on contents entered into the body of the e mail Important Reminders e The person sending the e mail must be added to the e mail list in the E mail Reporting section of the software as shown below If the sender is not in the list the panel will not respond e The Enable E mail Requests option must also be checked for the sender to receive e mails when requested from the panel or a remote PC Figure 90 E mail Reporting Window wx Note You may choose not to select Email reports on these days Email reports at this time specific event types or reports for emote Access code sele aun e mail addressees Q Job Details Y Wednesday l Email reports on this day of the month f so choose Browse List from thursday Senders e mail must be inthe p E the Data Transfer panel menu General options Friday e Mail list and the Enable E mail option Then scroll through e mail Requests box must be checked addresses and select one or more mail reports to th recipients Q Cross Zones Email Email Alarms Troubles Supervisory E a E Controlcenter1 gmail com Q Sensitivity Controlcenter2 gmail com Controlcenter3 gmail com Lan settings dier O Reporting css 4 card O snnun
81. d of Line Resistor Assembly LCD type Remote Annunicator Notification Appliance Circuit Signaling Line Circuit DACT Digital Alarm Communicator Transmitter UD 1000 1 2 PFC 6030 5403595 e REV C 2 13 A Da A D 4 4 4 N A h 4 N 4 4 This section addresses information that will help you in completing a successful installation such as the PFC 6030 cabinet layout specifications environmental considerations and calculating the battery circuit and SLC current draw requirements System Specifications Cabinet Description e Sixteen 16 gauge sheet steel with hinged removable locked door e Enclosure dimensions 16 x 17 x 3 7 8 Visual Indicators e LCD 2x 16 alphanumeric character display e LED indicators Red Green Amber LCD Description e Alarm Supervisory and Trouble conditions display applicable condition status and circuit for each correlating condition Environmental Specifications e Mount indoors only e Temperature 32 to 120 F humidity 93 non condensing e Verify panel is properly grounded e Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides bottom or rear of the cabinet Verify that they will not interfere with the batteries or other components e The panel and system must be tested and maintained in accordance with all local and national codes and ordinances System Configurations App
82. d press Enter to complete addressing device 3 Repeat steps for each device Note The R22 LED is selected by default if the R22 LED is not lit press Power until it is reselected To address devices from the Panel 1 Press ENTER to display Main Menu 2 Press 5 to access System Tools or press the down arrow to display 5 System Tools main Menu e Press ENTER to select The Enter Code prompt displays 1 View History e Enter the applicable user code on keypad to continue 2 Enable Disable 3 Set Date Time Note User code displays asterisks on LCD panel 4 Walk Test 5 System Tools e The System Tools menu displays 1 SLC Tools 1 SLC Pinpoint 3 Press 1 to select SLC Tools 2 SLC Stats 4 Press 3 to select SLC Addr Prog The prompt Enter key will Shutdown System 3 SLC Addr Prog 1 Single device 2 Mltp device displays on LCD panel and emits beeping until acknowledged 5 Press ENTER to shutdown or press ESC to exit SLC Addr Prog The SLC Addr Prog menu displays 3 SLC Addr Prog 1 Single device 2 Mltp device Next you must connect the device s cable to the panel s SLC PGM terminals as shown below Figure 22 Example of Control Panel Showing SLC Program Terminals O POWER O ALARM O EARTH FAULT O SUPERVISORY n O SILENCED o o TROUBLE o 1 SILENCE RESET e o o SLC Program Terminals i DWG 593 21 3 20 PFC 6030 5403595 e REV C 2 13 For a Single Device l PA gt
83. e 3 35 P DIS WC LOCOS ea E E AAE E E 3 36 IO o AAN on 4 37 Control Panel Basic OP iia RA 4 37 LCD S a A cocida 4 37 MN O O AAA 4 38 NOTE asia 4 38 P ON IAS U TON it aia 4 38 AA A e ee ae S ee eee nn 4 39 COTO Pah MEU TS ritos one ooo 4 40 AAA o gn E E E 5 41 PA O OPOS eeo conten clon Ea e go ptt aco raS r A r 5 4 ena A e A 5 44 TOPOS UNC aes wha eGo se oriol cialis E E see steiadaseeocaatanse 5 44 DO abe TASA AION isis 5 44 MTT PAIRING PIO AUN NIN ra ea 5 45 Comm ctaine tho Computer and Me AN ssid zon diria rete neane ela ania a sams de ctves site 5 45 Transtornos Dit iii digo 5 47 Uploodine TOM T aneio COMU ln its 5 48 Downloading Conteuration pulso Lane ria 5 49 ADE RENO ACTOS nd td oa in edcie es 5 49 TEIN CW AP o tote UA II A 5 50 FUE SOV FSV A iaa vc 5 50 FAUT TV OVS ii Co a ete ose 5 50 Uploading History Events amp Detector Sensitivity Status ReportS ococcooooooooononononcccccnnnonononononononnnos 5 52 PATS CON TOC OV IS A e ear gasses 5 52 Delecior DENSAS MES a 5 53 PATE ICI OWES e cn POPE OC N ROO PUE OOO OR A E A 5 54 PFC 6030 5403595 e REV C 2 13 Pan Boa a A o eee E ere ee 5 55 VARO W IRC P1015 FAV COS a daa 5 55 TA A 5 56 Programmins Pucon CYCLIC W cicesiestycacrensiersta oreen N EE EEEE EED DEEDEE EE 5 57 e OCG eE o E A 5 58 UNCrName LOS WO E E E E EEA 5 58 E EA E 0 a PROE en i ne en ne E A E EAE 5 59 2 OAD IAS E E A E E R EA E AE E EA E E A E E EEA A 5 59 Cna nn E E E E ete
84. e Sensitivity Alternates between line DACT Daily Test Call Y Any time of day All settings allowed l and 2 if line 2 1s enabled Specifies use of NAC circuit s Full listed range of smoke detector Up to 50 holidays where All settings allowed day mode is not active Alarms Troubles Supervisory Test History amp Status Reports ANSI Output City Tie Output E mail Status IP Based Central eas Station Reporting Alarms Supervisory Trouble amp Test Reports All settings allowed 5 43 PFC 6030 5403595 REV C 2 13 Programming Overview The LEARN function is available through the control panel and is an efficient way to automatically configure all system devices LEARN detects all connected devices assigns a name and selects the applicable device type i e module sensor or P Link device The system configuration mirrors a basic fire protection system where all inputs and outputs are a one to one relationship The panel configuration software allows custom programming and configuration for all points via a network or remote computer At the click of a mouse you may fine tune device behavior characteristics or create mapping zones for a more sophisticated fire protection system By using the system software you will realize the power and flexibility of the PFC 6030 system Please refer to Panel Software Overview and Mapping Zones in this section for details on these procedures The Programming Cycle
85. e Time Event gt RASTA Ser Loi ue 10 21 2010 10 26 41 AM Trouble Restore NAC 2 PWR Supply NA 10 21 2010 10 26 40 AM Trouble NAC 2 PWR Supply NAC 2 10 21 2010 02 08 48 AM Trouble Restore NAC 2 PWR Supply Nas 10 21 2010 02 08 47 AM Trouble NAC 2 PWR Supply NAC 2 10 20 2010 09 10 22 PM Trouble Restore NAC 1 PWR Supply NA 10 20 2010 09 10 21 PM Trouble MAC 1 PWR Supply NAC i 10 20 2010 02 03 08 PM Trouble Restore MAC 1 PWR Supply NA 10 20 2010 02 03 07 PM Trouble MAC 1 PWR Supply NAC i Note Click the Print more details icon to print a copy of the report Refer to Printing Reports located in this section for Click the close button to close report Note Refer to System E mail Functions Receiving E mail Status Reports located in this section for a sample of a History Events Report sent via e mail 5 52 PFC 6030 5403595 REV C 2 13 Detector Sensitivity Status Reports The Upload Detector Status File to Computer icon allows you to create reports showing sensor sensitivity related settings This information may be used to troubleshoot detector issues To transfer detector sensitivity status information 1 Click the Upload Detector Status File to Computer icon T or right click from Transfers region and choose Add 1A 2 Verify that Detector Status is selected in the Transfer Type field Click OK The Transfers window displays results Figure 72 Example of Transfer Status Transfers
86. e selected Silenceable Non Silenceable If zone defined as silenceable allows an operator to silence outputs by Default Silenceable pressing the SILENCE button Latching Non Latching Available for one 1 count zones only Latching zone requires operator to press Reset Non latching zone will automatically turn off outputs when condition clears Default Latching Local Non Local Used only for Report by Zone option Default Non Local Allows a zone to be specified as a non reporting zone 5 72 PFC 6030 5403595 e REV C 2 13 Table 17 Zone Attributes Output Pattern Default Constant Day Sensitivity Default 3 5 Range 1 1 3 5 Night Sensitivity Default 2 5 Range 1 1 3 5 Heat Sensitivity Default 135 F Range 135 F 185 F Fixed ROR Heat Sensitivity and 15 increase in 1 minute Default 135 F Range 135 F 174 F Auto Silence Timer Default 0 minutes Range 0 360 minutes Auto Unsilence Timer Default 0 minutes Range 0 60 minutes Silence Inhibit Timer Default 0 minutes Range 0 60 minutes Restore Delay Default 0 minutes Range 0 300 seconds Defines the output pattern of general purpose NAC circuits in the zone that occurs during alarm conditions Click on drop down arrow to display and select an option Constant 24VDC ANSI 5 sec on 5 sec off 5 sec on 5 sec off 5 sec on 1 5 sec off March
87. ection provides instructions on setting up connectivity between a laptop or networked computer and the control panel Once this is achieved you may program your system using the panel configuration software Note These instructions are relevant to all system configurations If your PC connects directly to the panel any procedural differences are noted throughout Connecting a Computer to the Panel via a Network 1 Connect cable to the Ethernet port on network or directly to the panel if not using a network 2 Connect Ethernet cable to port as shown below Figure 58 Control Panel Ethernet Port Ethernet port O POWER O ALARM O EARTH FAULT SUPERVISORY E a OSILENCED O En o TROUBLE o SILENCE RESET CJ G CJ SLC Program Terminals I DWG 593 21 5 45 PFC 6030 5403595 REV C 2 13 The following series of messages display on the LCD Notes e Ifthe Ethernet cable is connected to PC you will see the Initializing IP message prior to the Obtaining IP message e If your PC is connected directly to the panel the Obtaining IP message displays for approximately 45 seconds followed by the Private IP message the Private IP message is not shown here Note The number 10 0 5 27 shown above represents an example of a panel s IP or identifier used for illustration purposes only The panel s IP is unique to each computer network Write down the IP address it is required to transfer progra
88. efix F 3 Number Of Rings Number Of Rings H j 3 Reporting Accounts Repart Report Report Primary Primary mary Primary Primary Secondary Secondary Seconder Secondary Secondary Alarms Troubles Superviso Account Phone Report B Format Report oe Phone Report By Format Report ci ARN Number Po gt 2y Test Events ID Number gt Test Events O O O Panel CID O Panel CID O O O O Panel CID O Panel CID O j Fl O O O Panel CID O Panel CID F l O O O Panel CID O Panel CID O O O O Panel CID O Panel CID O i 3 Inthe Phone Line 1 and Phone Line 2 fields make any necessary changes Figure 131 Example of Phone Lines Options Phone Lime 1 Phone Line 2 v Enabled v Enabled Answering Machine Bypass Answering Machine Bypass Enable Line Monitor Enable Line Monitor Disable Dial Tone Detection Disable Dial Tone Detection Number OF Rings Number OF Rings 3 Each comma creates Line Prefix Line Prefix a 1 second pause before E 3 a the dialer attempts to dial a reporting account number e Enter the number of rings you want the DACT to pickup when receiving a call Note If you do not change the default from 0 the DACT will never pick up a call e Enter the appropriate line prefix if any is required for your phone lines Example In the example shown above the phone line requires that 9 is dialed to get an outside line The two commas instruct the dialer to pause 2 seconds before dialing the reporting
89. el e Double click in the Supervision Interval field to adjust the amount of time in seconds that the panel s IP Communicator will send a supervision signal to the remote monitoring receiver Default setting is 20 seconds Contact the remote monitoring station to verify the correct setting The receiver is programmed with a specific window of time to see the supervision signal If the supervision signal is not seen within the programmed time the receiver generates a Trouble signal after six 6 failed communication attempts e Double click in Encryption Key to enter an applicable number as provided by the remote monitoring station e Click on the Encryption Method ix drop down arrow to select 128 bit if applicable Note If the Encryption Method is set to None then an Encryption Key is not needed Click on the 2 collapse icon to hide the account setting field when finished an Reminder Click the 2 expand ellipsis icon to review or modify the account settings at any time Repeat steps for each Primary Secondary reporting account or to edit an account 7 107 PFC 6030 5403595 e REV C 2 13 D o O N 0 i l s A h J h ADDeNGILX A Da These instructions must be framed and displayed next to the PFC 6030 panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems Test the system in accordance to NFPA 72 Table 23 Button Functions Press the SILENCE pushbutton Press the
90. el Programmer File Options Help di ds _ Nov 11 2011 Test fpcf Remote Access User Name Potter Q Job Details Remote Access Password Q General Options Q Zones Q Cross Zones Q Points sensitivity Q Email Reporting Status Time Medium URI Phone Filename Complete 1 4 2012 11 05 20 AM IP 10 0 5 11 C Documents and Settings denisew My Documents Complete 1 4 2012 11 04 58 AM IP 10 0 5 11 C Documents and Settings denisew My Documents gt User Name Password The default user name and password is Potter as shown below they can be changed to ensure that only authorized personnel can transfer data to and from the panel Figure 79 Remote Access Code Screen Remote Access User Name Remote Access Password Notes 1 The remote access user name and password may be changed to increase security on the system 2 The remote user name and password must match the panel s user name and password 5 58 PFC 6030 5403595 e REV C 2 13 General System Functions Job Details Site specific information such as company name address and phone numbers may be entered in this window This information is stored in the panel and is used to identify the panel when using e mail reporting options Please refer to the figure shown below To enter site information 1 Click the Job Details program option The Job Details window displays Figure 80 Job Details Window hx Job Name Potter Fire C
91. ence Restore Delay March Code Zone Output Pattern Y Double Time Zone Day Sensitivity x 1 1 3 5 Full range allowed AS of sensor Zone Night Sensitivity Y 1 1 3 5 Full range allowed we a of sensor Zone Y 135 F 185 F Full range allowed NA aE Setting of sensor Combo ROR y 135 F 174 F All setines allowed Within listed range of sensor Photo Detector PSA Photo Duct Detector DSA Photo Heat Detector PSHA Fixed Heat Detector FHA Combination Fixed ROR Heat Detector RHA Conv Zone Module CIZM Mini Contact Mod MCM Single Contact Mod SCM Dual Contact Mod DCM Mon Output Mod MOM Constant ANSI Temporal All settings allowed Zone Fixed Setting Specifies use type of SLC Point Function SLC device All settings allowed Twin Relay Module TRM Sounder Base ASB Relay Base ARB Pull Station Water Flow Supervisory Tamper Fire Drill Trouble Monitor Aux Abort Reset Silence Fire Alarm Disable Inputs Disable Outputs Disable Inputs Outputs Lamp Test Applies to all dry All settings allowed contact input devices and circuits Dry Contact Input Dee oie Functions 5 42 PFC 6030 5403595 e REV C 2 13 Table 9 Programming Options Feature or Permitted Setting s Permitted P l Potter Amseco Sync Gentex Sync System Sensor Sync Wheelock Sync Function Constant Output All settings allowed Resettable Output Door Holder Output Day Night Smok
92. er in this section for details SLC Wiring Requirements The wiring parameters listed below MUST be followed to ensure proper installation Maximum wiring resistance between two 2 Short Circuit Isolators SCIs must be less than 10 ohms Total resistance must be below 50 ohms Maximum wire resistance must be calculated based on 0 1 ohm per SCI Maximum loop capacitance must be 0 5 micro farads All SLC wiring is low voltage and power limited Class B Style 4 Wiring Configuration Figure 7 Example of SLC Wiring Class B Style 4 PFC 6000 Series SLC Loop Class B Terminal Connections DWG 593 7A 3 13 PFC 6030 5403595 REV C 2 13 Class A Style 6 Wiring Configuration Figure 8 Example of Class A Style 6 Requiring CA 6075 O 5 1kQ Q O 5 1kQ 5 1kQ Q PFC 6000 Series SLC Loop Class A Terminal Connections DWG 593 8 Notes 1 The Class A Style 6 configuration does not provide the level of protection as Class A Style 7 2 Class A Style 7 requires installation of a CA 6075 3 The use of a SCI or AIB is not required 4 The SLC connection requires that the wires are separated 10 installed in conduit or other mechanical protection 5 Maximum wiring resistance must not exceed 50 ohms Class A Style 7 Wiring Configuration Figure 9 Example of SLC Wiring Class A Style 7 Requiring CA 60
93. er of rings when and where to send reports by specifying phone numbers and other report output options An example of the 4dd Dialer window 1s shown Figure 128 Example of DACT Add Dialer Window Phone Line 1 Delete Dialer Ae Enabled Answering Machine Bypass Enable Line Monitor Disable Dial Tone Detection Device Name Dialer 1 Device ID r Phone Line 2 Enabled _ Answering Machine Bypass Enable Line Monitor _ Disable Dial Tone Detection These fields are important Be sure to Number Of Rings Number Of Rings 1 o To m modify of rings and line prefix fields Lhe et oer according to your site s telephone setup ae l Refer to procedures on next page Reporting Accounts Primary Primary z Primary Secondary Secondary Secondary Home Troubles Supericoy AOUE Phone ReportBy Format REPOR count Rhoe Reporty Format BOPO O O O Panel CID O Panel CID O E O O O Panel CID O Panel CID O O EJ O Panel CID O Panel CID Fl O O O Panel CID O Panel CID O O O O Panel CID O Panel CID O Notes l A daily test is automatically sent to a remote monitoring location the test time may be programmed through the General Options program window Time to Send Autotest field 2 lines on each daily call If the system has been programmed to use a dialer and two 2 phone lines are used DACT will alternate between If a DACT UD 1000 is installed and the IP Comm
94. ered Allows software s general panel settings to be customized such as alarm verification time and door holder low AC dropout delay Define and configure zone s characteristics and mapping points Establish relationships between multiple zones Define and view all addressable and non addressable points Enable Day Night Sensitivity setup Holiday schedule and other related sensitivity options Schedule e mail reports by day and time setup e mail addresses and select type of report s to send to each e mail addressee Create and schedule customized daily weekly monthly or yearly reminder e mails Create up to ten 10 user codes and passwords and set access rights Configure Ethernet connectivity options Add or remove DACT module appliance Configure IP reporting options for primary and secondary accounts Add or remove Class A card Add or remove Remote Annunciators Add or remove SLC Loops Add or remove Power Supplies Add or remove DRV 50 driver modules Add or remove LED 16 Annunciators Add or remove RLY 5 modules Add or remove FCB 1000 modules Add or remove SPG 1000 modules Add or remove FIB 1000 modules 5 57 PFC 6030 5403595 REV C 2 13 Remote Access Code The Panel Configuration window displays the remote access user name and password on the right section of the screen refer to the example shown below Figure 78 Example of the Panel Configuration Screen Potter Fire Pan
95. erent device and the DCM 4 will operate as a single point device Press ESC when finished 3 2 PFC 6030 5403595 REV C 2 13 Notification Appliance Circuits Installation There are two 2 NAC circuits provided on the PFC 6030 rated as continuous 3 amps at 24 VDC The NAC circuits may be configured for Class A or Class B Please refer to the Class A and B wiring examples located in this section NAC Wiring e Outputs are supervised and regulated e Circuits are power limited e Type of NAC output is selectable and may be configured for strobe synchronization with Potter AMSECO Cooper Wheelock Gentex or System Sensor strobe devices Refer to the listing of compatible models located in the NAC Compatibility Document Potter 5403592 for this information e The CA 6075 Class A Expander may be programmed to allow for operation of the NACs The expander adheres to the same circuit rating supervision and regulation as other circuits NAC Maximum Wiring Impedance Formula The maximum impedance is a function of the load placed on the circuit To calculate the maximum line current impedance use the following formula Alarm Current of Notification Appliances x Wire Resistance lt 3 Volts NAC Wiring Configurations Examples of Class B and Class A Wiring follow Figure 23 NAC Class B Wiring Example Notification Appliance 5 1k EOL Potter Part 3005013 DWG 602 4A Notes 1 The Potter part number for
96. es do not require any additional water or electrolyte The system will keep all batteries fully charged by the system s power supply modules float charger A typical discharged battery will recharge at 1 0 A and reaches the float voltage of 27 3 VDC within 48 hours The battery is to remain in the cabinet with nothing on or around the batteries Replacement and Testing Recommendations The batteries are to be replaced at least once every four years or more frequently if specified by local AHJ and manufacturer recommendations Batteries should be dated at the installation Minimal replacement battery capacity displays on the control panel marking label The batteries are required to be UL Recognized batteries with a date of manufacture permanently marked on the battery The battery is to be tested at least annually and if the battery 1s showing signs of failure it should be replaced Immediately replace a damaged or leaking battery and always replace batteries in pairs Proper Handling First Aid Procedures e In the event a battery leaks and contact is made with the Sulfuric Acid immediately flush eyes and or skin with water for at least 15 minutes Water and household baking soda provides a good neutralizing solution for Sulfuric Acid e If Sulfuric Acid makes contact with eyes seek immediate medical attention e Ensure proper handling of the battery to prevent short circuits e Take care to avoid accidental shorting of the leads from uninsul
97. ess using a am SaaS A 20b Details Use DHCP the DHCP function or Automatic Private IP Address O User Configured Alternate IP IP Address 0 0 0 Q Zones Subnet Mask 9 0 0 0 Defa t Gate jay D O 0 0 cross Zones aaa Sere piinia Q General Options Set the IP address using Points pd A the Static IP function Qe Senvitivity Subnet Mask 255 255 255 0 Default Gateway Q Email Reporting e O Specify DNS Address LAN Settings Alternate DNS Server Q Dialer 5 63 PFC 6030 5403595 REV C 2 13 eile System e mail communications and functions are intended for informational reporting purposes only They are intended to be used as a convenience function E mail communications should NOT be used as a primary means of reporting emergency information E mail Report Programming To setup History and Detector Status reports schedule 1 Click on the E mail Reporting option The E mail Reporting window displays 2 Click in the days of the week 5 selection box to choose the days that the History and Detector Status report s will be sent 3 Adjust time if necessary 4 Select a day of the month if you wish reports to be sent on a specific day of each month Note Be sure to select each report type in the next E mail section for each recipient you wish to send these reports To setup addresses and select events and or reports 1 Inthe E mail address section as shown below enter up to twenty 20 e ma
98. essential when analyzing system operations You may choose to print the History and Detector Status reports by using the Print icon These reports may also be scheduled to be sent automatically to authorized e mail addresses Refer to the System E mail Functions topic located later in this section for details on programming these e mail reporting options History Reports The Event History transfer option creates a report of all events held in the panel s buffer Up to 1 000 events are held in the buffer at one time This information may be used to troubleshoot errors or to assess ways to improve the system configuration To transfer event history information l T Click the Upload History File to Computer icon or right click from Transfers area and click Add The Transfer dialog box displays Verify that History is selected in the Transfer Type field and click OK to display results Figure 70 Transfer Window Results m Type Status Time Medium URI Phone Filename p Hitoy Complete 7 21 2011 11 18 41 AM IP 10 0 5 18 C Documents and Settings de ewe ETA Complete 7 21 2011 11 15 22 AM IF 10 0 5 18 C Documents and Settings de Download Complete 7 21 2011 11 10 23 AM IP 10 0 5 18 C Documents and Settings de Upload Complete 7 21 2011 11 04 46 AM IP 10 0 5 18 C Documents and Settings de Double click file to view results Figure 71 Example of Transfer Results Window Dat
99. from control panel PFC 6030 5403595 REV C 2 13 Setting Addresses The FCB 1000 s address is set by dip switch S1 The address must be set in the range of one 1 to thirty one 1 31 to be recognized by the panel Refer to the P Link Addresses table shown earlier in this section for DIP switch programming Figure 43 FCB 1000 Back Panel View Showing Dip Switch Location o o o o o o O ojo o jo i 2 o0ooo 0000 oooo gt o o o ED ooo 0000 ooo0 0 o o D Q oo oo oo oooo o0o00oo 000000 P Link gt Se Connections S T o o o 6 s BARBA st O A DWG 608 20 Dip Switch Fiber Interface Bridge Installation FIB 1000 The panel supports up to thirty 30 FIB 1000s Fiber Interface Bridge which enables the 4 wire P Link bus to be converted to and or from the fiber optic cable e Utilizes multimode 62 5 125 micron fiber optic cable e Cable Length up to 2000 meters or 6500 feet e Installed in pairs refer to the FIB 1000 Wiring heading for details The first installed FIB 1000 can be mounted into any of the compatible fire enclosures in either of the AE 8 or AE 14 or the optional rack mount kit FIB 1000RM The FIB 1000RM includes a standard 19 inch rack mou
100. from the Transfers region then click Add The Transfer dialog box displays Fi Transfer Type Filename User name Password Transfer Wia IP IP URI Netbios name O Modem 2 Verify that Download is selected in the Transfer Type field 3 Enter the file name in the Filename field or click the Browse button to select file name 4 Enter the IP address in the Transfer Via IP field Figure 68 Transfer Download Dialog Box MM Transfer Transfer Type v Username sun Note To capture the panel s unique IP address Password 1 Disconnect the Ethernet cable from panel 2 The message Ethernet Lost displays indicating Transfer Via connectivity is lost 3 Reconnect the cable and write down the IF _ _ 4 rei LL l Modem PONE MUTE 5 Click OK The Transfers window displays the transfer progress Figure 69 Example of Transfers Window Showing Download Completed Transfers I 3 Type Status Time Medium i URIPhone Filename History Complete 7 21 2011 11 18 41 AM IP 10 0 5 18 C Documents and Settings del gt Download Complete 7 21 2011 11 15 22 AM IP 10 0 5 18 C Documents and Settings de1 5 51 PFC 6030 5403595 REV C 2 13 Uploading History Events amp Detector Sensitivity Status Reports The Upload History File to Computer and Upload Detector Sensitivity Status to Computer icons allow you to view valuable information that can be
101. gs _ icon displays all Primary gt o Cl Point DERNE a O account setting m m m Point he Whe l E m m Point gt O D o O re O O ua E E Point i Shan KA 2 Inthe Reporting Method Priority field select the applicable priority Reporting Method Priority O Primary O Secondary e Primary IP Reporting account 1s used as the first path of communication to the remote monitoring station e Secondary IP Reporting account is used as the alternate path of communication to the remote monitoring station 3 In the Panel UDP Port field click to enter an ingoing and outgoing UDP Port The UDP or User Data Protocol is the pathway for which data is sent and received between the panel and the remote monitoring station Note The default UDP Port is 3060 however an alternate port number may be used Check with your Network Administrator to determine if an alternate port number for FACP IP Reporting should be assigned 4 Inthe JP Reporting Accounts section make the necessary selections for the primary and secondary reporting accounts e Select the Report type s Alarms Troubles Supervisory e Click on the Report By ha drop down arrow to choose an option Panel Zone or Point 7 106 PFC 6030 5403595 e REV C 2 13 e Click on the Primary Secondary Account Settings A2 expand ellipsis icon to display additional setup options as shown below Figure 151 Example of Primary Account Settings Expanded Window Repor
102. he cabinet LCD Display The LCD panel displays the standard Start up menu as shown below The LCD displays up to thirty two 32 characters of information displays providing important feedback to system users 1 e system messages status information trouble conditions or input changes The LCD also provides access to the Main Menu for daily system operations and specific programming functions refer to Section 5 Programming Menu Functions for details on these topics Figure 54 LCD Start Up Screen Note You may customize the Start up screen to display a specific job site name or other relevant descriptive text PFC 6030 5403595 REV C 2 13 Menu Navigation Keys The arrow keys allow you to scroll or move through the control panel menus The Enter and Esc keys may also be used to navigate through menus they are located on the numeric keypad The table shown below provides a summary of the navigation keys Table 6 Menu Navigation Keys Moves scrolls up or down through menus Scrolls to the left or right to display details if any of current menu item Note When the LCD panel displays a LEFT and or RIGHT arrow this indicates more information may be viewed ENTER Displays the Main Menu or selects the current menu option Note The blinking gt indicates the current menu option Returns to previous menu or backs up to previous screen Numeric Keypad The numeric keypad allows you to enter user
103. igure a remote annunciator 1 Select Annunciators from system panel 2 Click the Add Device button to display the Add Device window Figure 120 Example of the Add Annunciator Device Window Type Name Address b LCD Annundiator 3 Double click in the Name field to customize name 4 Double click in Address field to adjust address if needed 5 Repeat steps as needed to continue adding annunciators PFC 6030 5403595 e REV C 2 13 LED Annunciators LED 16 The panel supports ten 10 LED annunciators The LED annunciator provides sixteen 16 LEDs which may be assigned to a specific zone when that zone becomes active the LED will display the alarm supervisory or trouble conditions Each LED annunciator also provides five 5 non programmable system LEDs that annunciate the overall system condition Power Earth Silenced Alarm Supervisory and Trouble Note This panel supports up to ten 10 LED 16 annunciators and or DRV 50 drivers in any combination To add and configure a LED annunciator 1 Select the LED 16 function from the system panel 2 Click the Add Device button The 4dd Device window displays Figure 121 Example of the Add LED 16 Window Add Device Type Name Address LED 16 LED 16 1 1 3 Double click in the Name field to customize name 4 Double click in Address field to adjust address 1f needed 5 Repeat steps as needed to continue adding LED
104. il addresses if needed 2 Select the Enable E mail Requests option if the e mail addressee may request reports from the panel Note If Enable E mail Requests is not selected the panel will ignore an e mail request for an on demand report Select each type of event s and or report s you wish to send to the applicable e mail address 4 An v displays in each selected report type Figure 87 E mail Reporting showing Enable E mail Request Email reports on these days Email reports at this time Important Note The Enable ma El Saturday E mail Requests option must Tuesday Sunday be selected in order for the Wednesday Email reports on this day of the month panel to respond to an e mail io addressee requesting an on demand report SS ue EEN Z l Email reports to these addresses Email Email Alarms Troubles Supervisory Test E Requests History Status controlcenterl El El El Eg controlcenter2 m m Y E mail Sent from Panel To send a report from the panel 1 Select the Data Transfer Menu Option 7 on the panel menu 2 Select one of the transfer options as described below Table 14 Data Transfer Options Allows e mail server status to be verified 5 64 PFC 6030 5403595 e REV C 2 13 011 0 Sy
105. indows e Flexibility in configuring points into multiple zones promoting sophisticated mapping relationships e Simple sorting and grouping by select fields enhances viewing and analysis of data e Options to view points by type address and function or description Mapping Zones Overview Mapping is creating relationships between devices modules and sensors and their behavior between each other Whereas the zone is the framework in which you group the devices These terms and other related mapping concepts are provided in this section Single Zones The LEARN feature creates or maps a basic one to one relationship where all devices are automatically grouped into one zone When all devices are in the same zone and an input device is activated all output devices will activate Please refer to the illustration below for an example of a one to one device relationship Figure 97 Mapping all Devices to One Zone Zone 1 OOOO A Panel Hardware Multiple Zones The panel configuration software allows you to customize the operational mode behavior of devices by grouping them into a maximum of 99 different zones All SLC devices including the two 2 on board NAC circuits NACs 1 and 2 may be configured to behave in a specific manner This flexibility enables you to configure system points to maximize protection throughout your site By organizing devices into different zones you can create unique relationships between devices
106. ing The LEARN mode enables you to efficiently configure all connected addressed input and output devices Refer to Section 3 Installation Addressing SLC Devices for detailed instructions Only authorized users may access this function LEARN generates a list of all points which may be viewed through the Points and Zones functions on a remote computer Refer to the Configuring Points and Mapping Zones sections for details To run the LEARN mode 1 From the control panel press the Enter button to display the Main Menu e Press 6 to select Programming The Enter Code prompt displays e Enter the user code as prompted The Learn prompt displays e Press 1 to select LEARN The SLC Initializing prompt displays and the system begins the initialization process 2 Results are grouped by device type If no changes are detected the prompt No changes displays e Use down arrow to scroll through results by device type 1 P Link Found 2 P Link Removed 3 Pts Found 4 Pts Removed 5 Pts Changed Esc Exit Note The abbreviation Pts refers to addressable SLC points e Select Esc when finished reviewing results The system prompts to save or discard file 3 Press 1 to save changes press 2 to discard changes e If option 1 is selected the Accept confirmation prompt displays e Press Enter to accept or Esc to discard 4 Press Esc to exit programming menu Connecting the Computer and Panel This s
107. ion is not selected or enabled by default Holiday Schedule Month Day BM Uh PFC 6030 5403595 e REV C 2 13 User Codes The Users option allows you to create up to ten 10 user code profiles if needed Each profile may have different access rights which controls the panel functions a user may access as well as the option to connect to the Facility Management Tool Note Please refer to the Facility Management Tool manual to learn more about programming installing and using this tool To create a new user These two fields may be selected to allow the user 1 Click on the Users option The User s Code window displays these fields allow the user io ee access to these panel functions Management Tool Figure 83 Example of Users Profile Window a when selected l PC Connect PC Connect jrme RRE SE EE ERRE Tods programming EEE ss 2 a aaa Eng Office 789 m E E m E El m E El E Security Off 456 E m m m E E El E E E User 2 222 El El m m Command Ctr 123 m m m m m m El User 1 111 El m User 7 El El T E E m E m m E m m E User 8 m E E E E m E El m E m E m User 9 E m m m m m E m m E m m E 2 Double click in the Name field to enter a descriptive user name 3 Click in the appropriate field selection boxes to grant access to each panel keypad option applicable for the user 4 Click in the last two 2 fields PC Connect Unsupervised Multi User and PC Connect Supervised Single User to allow
108. k File name Places Save as type Panel Files wcf y Cancel Notes 1 All site specific configuration data is stored in the panel s non volatile memory 2 The next time you make programming changes you may overwrite the original configuration file with changes If you choose to do this you will lose the original programming report information 3 The panel configuration file has a fpcf file extension Audit Errors The Audit Error Save Anyway dialog box displays if programming errors are encountered when saving the configuration file You may choose to save the file with errors however you cannot download the data until all errors are corrected Figure 66 Example of the Save anyway Dialog Box Audit Errors Total errors 5 Primary reporting accounts set to report must have an account number and phone number entered Secondary reporting accounts set to report must have an account number and phone number entered Secondary reporting accounts if either account number or phone number is entered then both must be entered Primary reporting accounts set to report must have an account number and phone number entered Secondary reporting accounts if either account number or phone number is entered then both must be entered 5 50 PFC 6030 5403595 e REV C 2 13 Downloading a Configuration File To download the configuration file 1 Click the Download Configuration File to Panel icon v or right click
109. le see Note 6 IS 210 E rre LED Current if applicable see Note 6 10 215 E DI O E Relay Current if applicable see Note 6 10 135 From a TCs EI PO IO COS E sci o o ETT EE ET EE ac Sd ace EE Pacs SCS ac O MS NO SLC Current Draw of Total ma Total ma Convert to Amps x 0 001 x 0 001 Refer to maximum allowable standby current Total A 60 minutes per hour Alarm time minutes Multiply by standby hours x Example 5 minute alarm enter 12 10 minute alarm enter 6 IN EST A E ME VETO tat tay A tat ey Factor 0 85 Regier Maximum Allowable Standby Current Paper oe UL 24 Hour Standby Time 1 The PSN 1000 E enclosure can house up to two 2 18 AH batteries Larger 7 AH 230A batteries require accessory enclosure part SSU00500 18 AH 619A NFPA 72 requires 24 hours of standby power followed by 5 minutes alarm 33 AH 151 activation o 55 AH 1930 A NFPA 12 12A requires 24 hours and five minutes of alarm activation Door holder circuits configured to disconnect upon AC loss need not be included in the battery standby calculation since they will not draw power during that time Door holders will contribute to standby current draw when AC 1s present Total current must not exceed power supply rating 10A LED Relay current must be accounted for in the battery calculation for the supplying source 6 96 PFC 6030 5403595 e REV C 2 13 Notification Appliance Circuits NACs There are six
110. le option 1 e Yearly Monthly Weekly or Daily 3 Select the specific scheduling frequency 1 e Days to send for a Weekly reminder or Time for a Daily reminder 4 Click in Attach History and or Attach Detector Status selection box es if needed 5 Complete the following information e Inthe To field enter up to 20 addressees e Inthe Subject field enter an applicable subject e Inthe Body field enter up to 2000 characters if needed Figure 96 Example of Creating a Daily Reminder Reminder 1 Reminder 2 Reminder 3 Reminder 24 Reminder 5 Reminder 6 Reminder 7 Schedule Yearly am to send Time Monthly Monday 03 00 AM O Bera O Daily v Wednesday O Disabled Thursday Friday E Saturday Sunday w Attach History Attach Detector Status Ta controlcenter1 gmail com Subject History report co Body Enmaii Body 6 Continue setting up additional Reminders if needed 5 69 PFC 6030 5403595 REV C 2 13 System Programming System programming involves defining the function of devices and their relationships to each other referred to as mapping You can define behavior characteristics of individual or groups of devices map devices into zones and further customize your system using the panel configuration software from a computer The panel configuration software features include e Easy to use Windows based editing techniques including drag and drop between w
111. liances Table 2 System Configurations Appliances fue Central PFC 6030 Main Board Panel Assembly e i 6075 Class A Expander IO IC A CA UD UD 1000 O DAT RA 6500 PSN 1000 or LED LED Annunciator a e l avs reina o o o o 0 coo reccommenenom 0 o o o 0 raw Formene o o o 0 0 seco soarana 0 o o o 0 Y Yes required for applicable section N No not required for applicable section O Optional may or may not be used has no affect on the applicable section 2 3 PFC 6030 5403595 REV C 2 13 Electrical Specifications Please refer to the table below for electrical specifications Table 3 System Panel Electrical Specifications Rating VO Circuits EN NACs Pea NAC sas SLC Power Style and Class SLC Class A or B NAC Class A or B Maximum Load Maximum of 30 P Link Class A or B PE OUIU i Emp Leap of 56 055 mA addressable points All are Low Voltage and Power Limited System Size Specifications Please refer to the table below for system size specifications Table 4 System Size Specifications Accessories Subassemblies Maximum System Size e One 1 built in SLC Loop with 30 addressable points e Two 2 notification circuits on the main board UD 1000 One 1 DACT PFC 6030 2 4 PFC 6030 5403595 e REV C 2 13 Main Board Wiring Specifications There are several wiring requirements to consider before connec
112. ll can be sent to both reporting accounts 3 Ifthe IP Communicator is not programmed and the UD 1000 is not installed the system will operate as a local panel 4 Where the fire alarm transmitter is sharing on premises communications equipment the shared equipment shall be UL listed 5 Secondary power shall be provided for all equipment necessary for the transmission and reception of alarm supervisory and trouble signals at the protected premises 6 Secondary power shall be provided for all equipment necessary for the transmission and reception of alarm supervisory and trouble signals at the supervising station 7 105 PFC 6030 5403595 REV C 2 13 Programming the IP Communicator IP Reporting Accounts The IP Reporting Accounts section 1s used to program the IP Communicator operations and to customize the format of the reporting accounts You may choose different settings for Alarms Troubles and Supervisory conditions Up to five 5 primary or secondary accounts may be configured To add and configure a IP Dialer 1 Select IP Dialer from the system panel and click the Add IP Reporting button The JP Reporting window displays Figure 150 Example of the IP Reporting Window Delete IP Reporting Reporting Method Priority D Primary Panel UDP Port O Secondary 3060 IF Reporting Accounts E Report Report Report Report Att old The expand ellipses Alarms Troubles Supervisory By Settin
113. m No1 an S NC1 S pNO2 NC2 Ip Twin Relay Module Model No TRM 4 On Normally Open 1 Common 1 From FACP or Previous Module Normally Closed 1 SLC Loop Normally Closed 2 To Next Module DWG 593 17 3 17 PFC 6030 5403595 REV C 2 13 Monitored Output Module 4 inch mount MOM 4 If the power supply connected to the MOM 4 is power limited then the outputs are power limited An example of a MOM 4 wired as a conventional application is shown here Figure 18 Example of MOM 4 with NAC Connections Select DC Notification Appliance Output Rating 24VDC 2 0A To Next Module From FACP or Previous Module 5 1KQ 1 2W EOLR ED Monitored Output Module Model No MOM 4 To Next Module DWG 593 18 Analog Sounder Base ASB Figure 19 Example of Analog Sounder Base Wiring To Next Module From FACP or Previous Module SLC Loop Analog Sounder Base Model No ASB DWG 593 19 Notes 1 The supply power must be coded in order for the output to be coded 2 ASB does not generate a coded output It will track the pattern delivered to its 24 VDC input Analog Relay Base ARB Figure 20 Example of Analog Relay Base Wiring LC Loop CO Oo OO _ SLC Loo From FACP or Previous Module 24 VDC AE 24 VDC 24 VDC 24 VDC p 5 C2 2A 21 8 0A 240VAC 8 0A 30VDC Analog Relay Base Model No ARB 2 0A 240VAC 2 0A 30VDC
114. mming data between the panel and the computer 3 The IP configured and IP address prompts alternatively display until configuration is completed Note If Ethernet connectivity 1s lost the message Ethernet Lost displays on panel This indicates that the Ethernet cable is disconnected at the panel or network computer port 5 46 PFC 6030 5403595 REV C 2 13 Transferring Data This section provides step by step instructions for completing uploading and downloading data transfers The Transfer icons are located at the top of the Programmer window and are briefly described below Table 10 Transfer Functions IC B Downloads configuration file from computer to panel ES Uploads configuration file from panel to computer E Uploads history events file from panel to computer Uploads detector sensitivity status file from panel to computer Prints selected file The Transfers region is located at the bottom of the Programmer window and lists all completed transfers This area displays transfer details including their date and time You may also access the Transfer shortcut menu from this location to select any of the transfer functions Figure 59 Example of Programming Window Showing Transfer Icons and Transfer Section Potter Fire Panel Programmer B File Options Help Vebt a N _ Nov 11 2011 Test fpcf a A Remote Access User Name MO Remote Access Code 7
115. nnnnnnnnnnns 3 18 Analog Sounder Base ASD ticos 3 18 EIA A 3 18 Single Action Dual Action Pull Station APS SA APS DA ooonnnnninnnncnccccccccccnnnnnnnnnnonnnnnononnnnnnnos 3 19 POS St o LC IDE VIC poa ioaaticos 3 20 PFC 6030 5403595 REV C 2 13 Notification Appliance Circuits Install tivas 3 22 DA Me PB PI PR E eter auanince E E E A oe 3 22 IO Wiring Impedance Formula PP 3 22 MECT TO OM O UANO e E ese eens asec eaten eee 3 22 EN AAA E E E A AE E E E 3 24 CA 6075 Class A Expander Installation ooooonnnnnnccnnnnnnnnnnnnnonononononononononoconononnnnnnnnnnnnnnnnnnnnnoccnccnnnnnss 3 24 EA A E E A e E E AE E O 3 25 COn urani on CAVA er iS S ossea deci 3 25 Maximum n re CST S QC T Or T opa EE E ESO 3 25 e EP O Lo A E A A A 3 26 Remote Annunciators Installation RA 6500 and RA 6075 oocccccnnncnooonccccnnononononorocccnnonononananonocnnnnnns 3 27 YT R EIE E A ESO EE 3 27 LED Annunciators Installation LEDA isos tia 3 27 LED Drivers Installation DRV lt entrantes 3 28 Relay Board Installation RLY 5 titanes 3 30 Fire Communications Bridge Installation FCB 1000 ooooooooconncccccncnnnnnnnnnnnnnnnnnnnnnonnnnncnnnnncnnnnnnnnnnnnnos 3 31 Fiber Interface Bridge Installation PIB 1000 nn tna 3 32 A PP EA E E E See gue sande en og caeseenaiae ene anaes 3 33 Serial Parallel Gateway Installation SPG 1000 cocccccccnnnnnnnnnnnnnnonnnnnnnnnonnnnnnnnnnnnnnnnnnonnnnnnnnnnnnnnnnnnos 3 34 DACTTA CAN NGI area
116. nt enclosure which can then be installed directly in an equipment rack The second installed FIB 1000 must be installed in a PSN 1000E cabinet as illustrated in the following drawings Figure 44 FIB 1000 Bridge amp FIB 1000RM Showing Rack Mount DWG 608 12 PFC 6030 5403595 e REV C 2 13 FIB 1000 Wiring FIB 1000s are installed in pairs Please refer to Diagrams 1 amp 2 shown below to properly wire the two FIB 1000s The first FIB 1000 referred to as FIB 1000 A below can be installed in any of the compatible fire alarm enclosures or the FIB 1000RM It is connected via the 4 wire P Link connection Set S2 on FIB 1000 A to the OFF position which provides an outgoing fiber option connection That fiber optic connection can be connected as Class A or Class B to the second FIB 1000 referred to as FIB 1000 B below The second FIB 1000 B is installed in a PSN 1000E shown in Diagram 2 below Set S2 on FIB 1000 B to the ON position It then provides an outgoing P Link connection Connect the 4 wire P Link on the FIB 1000 B to the P Link connection on the PSN 1000E To power the FIB 1000 B connect the 24VDC and terminals on PSN 1000E shown in Diagram 2 below to the isolated P Link 24 VDC and terminals The PSN 1000E s isolated P Link can now be used to connect any other P Link appliance including the RA 1000 LED 16 and PSN 1000 PSN 1000E Figure 45 Diagram 1 FIB 1000 Wiring Diagram Sho
117. o consider before connecting circuits to the PSN 1000 PSN 1000 E board 1 the circuit separation and 2 the wiring types Circuit Separation e Separations between the different wiring types must be maintained by at least 1 4 inch and the wire insulation must be for the higher voltage e The two cabinets have various conduit knockouts located for ease of wire installation and allowing the installer to maintain power limited and non power limited connections 6 91 PFC 6030 5403595 REV C 2 13 Wiring Types Wiring specifications must be followed to prevent damage and or other consequences Table 21 PSN 1000 PSN 1000 E Board Circuit Wiring Types Type of Circuit Cabinet Dimensions Figure 133 PSN 1000 E Cabinet Dimensions 17 60 18 91 a x 3 9 NO N N N to DEPT 1 f RIGHT SIDE LEFT SIDE DWG 602 21 6 92 PFC 6030 5403595 REV C 2 13 Cabinet Installation The PSN 1000 PSN 1000 E slides into the guides located at the bottom of the panel and then secured with screws as shown in the following illustration Figure 134 PSN 1000 Panel Installation Showing Cabinet ey 22 la A A y Ik DWG 602 22 6 93 PFC 6030 5403595 REV C 2 13 Cabinet Wiring Connections Figure 135 PSN 1000 Wiring 120VAC 50Hz 60Hz 240VAC 50Hz 60Hz Connect to separate unswitched AC circuit 000000 Non power limited relay connection P T
118. ods between formal testing and at regular intervals the control system should be subjected to the following operational performance checks The Authority Having Jurisdiction AHJ should be consulted for requirements on frequency of system testing e Check that the green AC power LED is lit e Check that all amber LED s are off e Using the system menus perform a Lamp Test function Verify that all LED s and LCD segments operate e Before proceeding 1 Notify the fire department and the central alarm receiving station if transmitting alarm status conditions 2 Notify facility personnel of the test so that alarm indicating devices are disregarded during the test period and 3 When necessary bypass activation of alarm notification appliances and speakers if installed to prevent sounding of evacuation signals e Activate an input device i e manual station heat or smoke detector and check that all notification appliances function e Notify Fire Department central alarm receiving station and or building personnel when finished with testing the system e The test of ground fault must be measured in below 10k ohms impedance AC Fuse The control panel has one fuse on the board for the AC power over current protection The AC fuse is rated at 8A 250VAC Time Lag and screened onto the main board as F1 Battery Maintenance The system has been designed to use maintenance free sealed lead acid batteries These sealed lead acid batteri
119. ontrol Panel Q Remote Access Code Address Line 1 5757 Phantom Drive P Job Details Address Line 2 Suite 125 P General Options Address Line 3 Hazelwood MO 63042 P Zones Phone 1 800 325 3936 Cross Zones m OOO o O Q Points Email tech pottersignal com Q sensitivity Email 2 customerservice pottersignal com Q Email Reporting vse 2 Click in each applicable field to enter information Note You may also press the TAB key to move to next field General Options The General Options window contains a variety of general system settings such as the panel s default name idle message and the time an Autotest will be sent to the monitoring station Figure 81 General Options Window Panel Name Remote Access Code Potter Fire Control System Idle Message PJ inak Y Enable Idle Message AE EEE RRA AAA Default Outgoing Email Address Q Zones username company com Q Cross Zones Display Events Initial Event v SLC Blink es 3 Points Alarm Verification Time seconds Sensitivi e Ss Water Flow Delay seconds OQ Email Reporting AC Report Delay hours e Door Holder Low AC Dropout Delay 15 seconds v Time to Send Autotest 02 00 AM E _ Strobes Active When Silenced Q Dialer 4 Enable Power Line Clock Synchronization 2 Display Time as AM PM Reporting Time Zone GMT 06 00 CST Central Standard v 7 e A 2 Enable Daylight Savings Time Adjus
120. other device compatibilities Table 25 Device Modules Compatibilities Module Device Compatibilities NAC Appliances Refer to Potter document 5403592 NAC Compatibility Document Two Wire 2 Wire Smoke Detectors SLC Devices DACT DACR UD 1000 Receivers RS 485 Devices None listed with the control panel all devices listed the Conventional Input Zone Module CIZM please refer to CIZM Installation Sheet PSA Photoelectric Smoke Detector PSHA Photoelectric Heat Smoke Detector FHA Fixed Temperature Heat Detector RHA Rate of Rise fixed Temperature Heat Detector AIB Addressable Isolator Base ARB Addressable Relay Base ASB Addressable Sounder Base APS Addressable Pull Station MCM Miniature Contact Module SCM 4 Single Contact Module DCM 4 Dual Contact Module TRM 4 Twin Relay Module MOM 4 Monitored Output Module CIZM 4 Conventional Input Zone Module SCI Short Circuit Isolator UD 1000 DACT The DACT transmits in Ademco Contact ID and Security Industries Association s Digital Communication Standards SIA DCS Each account may be configured for Contact ID or SIA DCS independent of the other account s setting Therefore some account s could be Contact ID and others could be SIA DCS or vice versa Similarly accounts could be the same reporting type Silent Knight Model 9500 9800 Ademco MX8000 Sur Gard System III SG DRL3 POTS Line Card
121. oto do y a stos conto mr deco RBA O Comenten mining zone modue Firmom ci er os a inicias mos 009 Js os Sne onae moda amero BO a raices icon f os tow entro pen mom von noe os f o Tiny modue amamos io o EXT FE EEE FO EE stgo se aspas os os CTE TI O FCE E ACE e O E SLC SLC alarm LED Current LED Current Te Standby E Alarm Current Current Note 1 CIZM requires 24VDC power source Standby current Style D 4 90 mA Style B 8 5 mA Alarm Current 50 0 mA Note 2 MOM requires 24VDC power source Standby current 1 60 mA Alarm Current 1 60 mA Note 3 ASB requires 24VDC power source Standby current 5 mA Alarm Current 100 mA Note 4 ARB requires 24VDC power source Standby current 5 mA Alarm Current 50 mA 2 9 PFC 6030 5403595 REV C 2 13 Isolator Device Load Calculation This section covers the distinction between an addressable sensor and an isolator to correctly calculate the total SLC device load A device uses an address and consumes power Whereas an isolator does not use an address but does consume power The following scenarios explain how to calculate the current device load based on the SLC configuration Scenario 1 Class A Loop Isolated Devices Configuration In this configuration each sensor and isolator device module counts as one 1 when calculating the total device load Formula Total addressable devices Total isolators Total power unit
122. oughout controlled site s Purpose of This Manual This manual is intended to assist in the installation and programming the PFC 6030 Fire Alarm Control Panel Refer to this manual to properly install and program the PFC 6030 It is recommended that the user follows the procedures as outlined in this manual to assist in proper installation and prevent damage to the control panel and associated equipment System Overview The PFC 6030 system is designed for use as a fire control panel for life safety applications System Features e The PFC 6030 features a built in signaling line circuit SLC and is capable of supporting 30 Potter Nohmi protocol devices e 3 5 Amp 24vdc Power Supply e Two 2 Notification Appliance Circuits NACs each rated at 3 0 Amps maximum e Power Limited e Built in Sync e Cadence Patterns e Auxiliary Power e Support for all major synchronization patterns e Potter e Gentex e CooperWheelock e System Sensor e Built in Ethernet port for programming and network connectivity e Built in e mail support to communicate system status and event information e Customizable Reminder E mails e P Link RS 485 bus supports system accessories e 1 000 event non volatile history buffer e Learn mode enrolls connected sensors and modules for efficient system programming e 99 Software Zones e Dead front Cabinet Design e 2 X 16 character LCD display e Dedicated Alarm Supervisory and Trouble Form C Relays e Analog Address
123. ounting up to six 6 additional P Link and expansion cards i e FIB 1000 etc Board Specifications Cabinet Descriptions e Sixteen 16 gauge sheet steel with hinged locked doors e Enclosure dimensions PSN 1000 16 x 17 x 3 7 8 non removable door PSN 1000 E 26 x 17 6 x 3 75 removable door Visual Indicators e LED indicators Green amp Amber Environmental Specifications e Mount indoors only e Temperature 32 to 120 F humidity 93 non condensing e Verify panel is properly grounded e Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides bottom or rear of the cabinet Verify that they will not interfere with the batteries or other components e The panel must be tested and maintained in accordance with all local and national codes and ordinances Refer to Appendix D PSN 1000 PSN 1000 E Maintenance and Testing for information on maintenance and testing recommendations Electrical Specifications Please refer to the table below for the board s electrical specifications Table 20 PSN 1000 PSN 1000 E Board Electrical Specifications NACs Rating per NAC Input Circuits Style and Class Class A or B NACs are Power Limited 3 Amp 1 Amp Note Refer to the NACs Wiring topic located in this section for Class A wiring requirements Wiring Specifications There are several wiring requirements t
124. r DIP switch programming Figure 37 DRV 50 s Back Panel View Showing Dip Switch Location Connections Relay Board Installation RLY 5 O O a e camroeen st EA O LN IU LN fu ao oo o o o oOo Oo o a 000000 vee ary oooooo0oo oo0 a AS In U Hu U Q o o O o PICO Ce Gara at H gi H A gi g Hb o bl ln p nma Oo pom aA E 4 i 4 N O Pink Dip Switch S1 DWG 608 22 This panel supports up to thirty one 31 RLY 5s The RLY 5 Relay Board module is controlled over the 4 wire P Link connection The RLY 5 mounts in a mounting bracket as shown below and then installed into the panel cabinet or in either of the AE 8 or AE 14 accessory cabinets Figure 38 RLY 5 Board Showing Mounting Bracket DWG 608 10 The RLY 5 higher current required for the relay outputs can be provided by the panel or from an auxiliary power source as shown below The auxiliary power can be any
125. rill 5 71 PFC 6030 5403595 REV C 2 13 Table 16 Zone Styles System Alarm Used for outputs that will be activated upon any alarm System Supervisory Used for outputs that will be activated upon any supervisory System Trouble Used for outputs that will be activated upon any trouble Zone Attributes Zone attributes are the settings that control the overall behavior of devices within the zone The zone may be configured as latching or non latching silenceable vs non silenceable among other attributes Tips Double click in a field to modify an applicable field i e zone name or alarm count Click in fields with a selection box to select or deselect the option i e silenceable or latching All zones default to an Alarm style or type when first created The figure shown below is an example of the default attributes of a Alarm zone Figure 98 Example of Zone Attributes Fields 1 10 Alarm Silence Night Heat Fixed ROR d a l Day ae Count able O ton Sens Sens Sens Heat Sens Alarm 1 C Constant 3 5 2 5 135 135 F Refer to the table below for a brief explanation of zone attributes Table 17 Zone Attributes Zone Name Default Zone x Zone name may be up to sixteen 16 alphanumeric characters where x is a sequential number Alarm Count Defines the number of inputs that must be in alarm before outputs are activated Default 1 Default is one 1 up to 10 inputs may b
126. s you to print History and Detector Status reports Double click the History or Status file listed in the Transfer window prior to clicking the Print icon An example of the Report window which displays a History report is shown below Report a El ES Date Time 02 07 2011 08 26 17 02 07 2011 08 26 23 02 07 2011 08 26 24 02 07 2011 08 26 32 02 07 2011 08 26 38 02 07 2011 08 26 38 02 07 2011 08 26 38 02 07 2011 08 26 38 02 07 2011 08 26 38 02 07 2011 08 26 38 02 07 2011 08 26 38 02 07 2011 08 26 38 02 07 2011 08 26 45 02 07 2011 08 27 23 02 07 2011 08 27 23 02 07 2011 08 27 35 02 08 2011 02 27 05 02 08 2011 02 27 20 02 08 2011 02 27 39 02 08 2011 02 27 47 Figure 74 Example of the History Report Print Window Event System Powerup Comm Trouble Device Comm Trouble Device Trouble AC Pwr PWR Trouble Pt 9 Built in 5 Trouble Pt 3 Built in S Trouble Pt 7 Built in 5 Trouble Pt 6 Built in S Trouble Pt 5 Built in 5 Trouble Pt 3 Built in S Trouble Pt 2 Built in S Trouble Pt 1 Built in 5 Trouble SLC ClassA Wi Local Programming Pa System Powerup Trouble AC Pwr PWR System Powerup Trouble AC Pwr PWR Trouble Restore AC Pw Trouble AC Pwr PWR To print a History or Detector Status Report l PA Ejes a Move the mouse across the Print icons to display their descriptions Double click the History or Status report listed in the Transfers window to display the report Adjust
127. shortcut menu Save File As Note Click the Add option from the shortcut menu to choose the transfer type The Transfer dialog box displays Figure 61 Example of Transfer Upload Dialog Box MN Transfer Transfer Type Upload Filename o History Click here to choose applicable Detector status transfer type if necessary Password 6075 Transfer Via IP Modem 2 Verify that Upload is selected in the Transfer Type field 3 Enter the configuration filename in the Filename field or leave blank to Autoname Figure 62 Example of Transfer Upload Window WN Transfer Transfer Type Filename User name Enter file name or leave blank to auto name Password Transfer Via IP O Modem Notes e Ifyou do not name the file the program automatically names it using the transfer type and date stamp as the file name e Once the file has been saved and additional programming changes are made at a later date click the Browse button to locate the file name to replace the old file with the updated configuration changes 5 48 PFC 6030 5403595 e REV C 2 13 Enter IP address or panel name in the Transfer Via IP field Notes e To capture your panel s unique IP address disconnect the Ethernet cable from panel The message Ethernet Lost displays indicating connectivity is lost Be prepared to write down the addre
128. ss and reconnect cable e Ifyou are connecting via a modem please refer to Appendix B Modem Connectivity Setup Click OK The Transfers region displays the uploaded file Figure 63 Example of Transfers Download Results 11 8 2010 3 48 08 IP PFCBO7SROOO0006 Config 2010 11 08 15 48 03 36 vcf e Double click on the transfer file to display results e All points detected during the LEARN process have been uploaded to the panel configuration software Note Details on viewing and configuring points are addressed in detail later in the System Programming Configuring Points topic Downloading Configuration File to Panel The Download Configuration File to Panel icon o allows you to copy all programming changes to the panel Notes e Be sure to Enable Remote Access at the panel before choosing this option If your PC is directly connected to the panel versus a network this step is not necessary e Verify that the Remote User Name and Password match the panel s user name and password You will receive an error message when attempting to download data to the panel if they do not match Enable Remote Access To enable remote access l 2 3 4 5 At control panel press ENTER to display the Main Menu Press 7 to select Data Transfer The ENTER CODE prompt displays Enter the user code to continue The Select Data option displays Press 1 to select Remote Access Press ESC to return to Main Menu
129. sseccccccsssssececocosssseseccooossssssececosssssssececosssssssceessssssssssee B 1 Appendix C System Maintenance and Testing escscsssssssecccccsssssseccccossssssccecoscsssssceesosssssseseesossssssseee C 1 Appendix D PSN 1000 PSN 1000 E Maintenance and Testing scssssscccccssssssssssssccccsseceeees D 1 Appendix Es Compatible Devices Ta lO ivsisiscccsccccceasssssccccscavsensantecteccsscesassatessecceawecscseucacsccccteaxssescsszoccsteces E 1 Appendix F Troubleshootino Tips xcsceessssesseececesetevsseseescctesscesssasssetecsssdessivanssdetcsstexstenetesscessdenstesassdenescteess F 1 Appendix G Control Panel Vi Ci cvscscscsstensccccncsscenssvvaccccesesscsssveaceseutestecsnvsosescecesbeceaucacesoutestecsnssaccatocestecs G 1 PFC 6030 5403595 e REV C 2 13 Section 1 Introduction The Model PFC 6030 1s a listed and approved microprocessor based addressable fire control panel and complies with UL 864 NFPA 13 NFPA 70 and NFPA 72 The PFC 6030 system software 1s compatible with Windows XP Windows Vista and Windows 7 Operating Systems additionally the latest version of Microsoft NET Framework is required The system software incorporates conventional shortcuts and provides great flexibility in effectively programming individual or groups of devices The operational mode behavior of the two 2 on board NAC 1 and 2 circuits can be customized This flexibility enables configuration of system points to maximize protection thr
130. st 1 By Point 2 By Zone Select Device Zone 1 Internal SLC 1 Disable Inputs Internal PWR 2 Disable Outputs MAIN MENU 5 System Tools 6 Programming 7 Data Transfer Y 1 SLC Tools 2 Point Control 3 Ethernet Status 4 DACT Test 5 DACT Reset 6 Erase History 7 Lamp Test 8 App Revisions 1 LEARN Mode Select Data 2 Panel Default 1 Remote Access 3 IP Settings 2 E mail Det Stat 4 Dflt ID Pswd 3 E mail History 5 Prog ID Pswd 4 E mail Config Esc Exit 5 E mail Test 6 Server Status Esc Exit 1 SLC Pinpoint 2 SLC Stats 3 SLC Addr Prog 1 Username 2 Password Esc Exit 1 Single Device 2 Mltp Device Ethernet Options 1 DHCP Settings 2 Default IP 3 Default Gateway 4 Default Subnet 5 Alternate IP 6 Alt Gateway 7 Alt Subnet Esc Exit TIP To save time enter the menu selection number on the keypad to select a function For example press 3 to select Set Date Time from the Main Menu 4 40 PFC 6030 5403595 e REV C 2 13 Section 5 Programming This section addresses programming options and their parameters provides an overview of the programming process and addresses how to use the two programming methods 1 the LEARN function and 2 the remote computer programming process This section also includes procedures on uploading and downloading configuration data using the panel configuration software Please refer to this section to learn how to navigate within the software
131. stem e mail communications and functions are intended for informational reporting purposes only They are intended to be used as a convenience function E mail communications should NOT be used as a primary means of reporting emergency information 3 Select one or more e mail address using one of the following options e Choose Use Default to select the address entered in General Options as shown below e Choose Browse List to scroll through and select one or more e mail addresses entered in the E mail Reporting section of the software e Choose Specify New to enter additional e mail addresses if needed Figure 88 Example of the General Options Window Default Outgoing E mail Address gt Panel Name PJ Remote Access Code Potter Fire Control System Idle Message A o vetaits ai aki no Use the Default outgoing General options e mail address rr errr ree rr rr rr rr rr ult oing Email Address oe Zones username company com eo Cross Zones Display Events Initial Event v SLC Blink Normal x Q Points Alarm Verification Time seconds 60 e a Water Flow Delay seconds Q Email Reporting AC Report Delay hours 1 e Door Holder Low AC Dropout Delay 15 seconds v Time to Send Autotest 02 00 AM O Lan settings Cl Strobes Active When Silenced Q Dialer 2 Enable Power Line Clock Synchronization 2 Display Time as AM PM Repor
132. suniees none idad 2 8 Ba ry Calculation Works heel unta EEEE EE EE ASe 2 8 SU Cuenca VOTES ESE sensata raio posees lante retador asado iberia 2 9 Isolator Device Load CUCU lIOn e enere a e a ea aae aS 2 10 Scenario 1 Class A Loop Isolated Devices CONfIgUrAtiOD oooooonnnmmmmmmnmnnnnnnnnnnnnnnnnnnnnnnnnnnnnnos 2 10 Scenario 2 Class B Loop Isolated Branch Configuration drid 2 11 Battery COMES sets 2 12 Mau is 2 12 Section PIS CAM AMON E E E E EAO EEE T O E EE O OE E 3 13 Signalne Line Circuit SLC Installato ses ienn anasi a ean naiera aaa 3 13 SLE Trn RO IIS ri toi EEE 3 13 CHISTE CON TOT OOM aaa 3 13 Class A Style 6 Wiring COMO A diodes 3 14 Class A Style 7 Wiring COR SAO A roca 3 14 Connecting Analog TC COIS ccoo leticia dia 3 15 Connecting Addressable Mod 3 15 Conventional Initiating Zones CIZM 4 Class A ooooononccconcoooonnnoaananonnnnnonnnnnnnnnnnononnnnnannnnnnnnnnnnnnnnos 3 15 Conventional Initiating Zones CIZM 4 Class B oonoonnnnnnananananannnonononononnnnnnnnnnnnnnonononnnnnnncnanannnnnos 3 16 Single Contact Module 4 inch Mount SCM 4 oocccccccnnnnnnnnnnnnnnnnnnonannnnnnnnnnnnnnnnnnnonon ono nnnnnananannnnos 3 16 Dual Contact Module 4 inch Mount DCM 4 oooooooconnncnaaanananananononnnnnnnnnnnnnnnnnnnnnnnnnnnanannnnnnnnnnnnnnnns 3 17 Twin Relay Module 4 inch Mmoni TRMA oo a da drid 3 17 Monitored Output Module 4 inch mount MOM A ooonnnnnnncnnnnnnnnnccnnnnnnnnnnnnnnnonnnonononnnnnnn
133. t DCM 4 Refer to the figure shown below for a Class A DCM 4 wiring example Figure 15 DCM 4 with One Class A Circuit Note The resistance of external wiring shall be less that 1000 The capacitance of external wiring shall be less than 1 micro farads Dual Contact Module Model No DCM 4 sai From FACP or Previous Module SLC Loop To Next Module Select Style 6 DWG 593 15 Note In this configuration the DCM 4 operates as a single point Class A module When configuring a Class B the DCM 4 has two 2 addresses If address No 1 is set input circuit No 1 NO1 C1 will be addressed as No 1 and input circuit No 2 NO2 C2 will automatically be addressed as No 2 Refer to the figure below for an example of wiring a Class B DCM 4 Figure 16 DCM 4 with Two Class B Circuits Note The resistance of external wiring shall be less that 1000 The capacitance of external wiring shall be less than 1 micro farads Dual Contact Module Model No DCM 4 z Address From FACP or Previous Module SLC Loop To Next Module Select Style 4 DWG 593 16 Twin Relay Module 4 inch mount TRM 4 The TRM 4 has two 2 contacts that are active simultaneously when TRM 4 is in the active mode Normal output is nonpower limited unless the power supply connected to the TRM 4 is power limited and the circuits are power limited Figure 17 Example of TRM 4 Wiring Contact Rating 24VDC 2 0A 125VAC 5A
134. t E Built in SLC 17 Point 17 Unused To move one or more points into multiple zones 1 Select the applicable Zones in the Zones window and select points 2 Drag and drop selected points into Device window Figure 111 Example of Moving Selected Points into Two Zones Points vix Alarm Silence Name Style pa pres Latching Local Output Pattern Addr Name Function a ECE EE 1 NACI Conv NAC General Purpose Zone 2 Alarm 1 7 Constant P Zone 3 Alarm i El Constant 2 NAC2 Conv NAC General Purpose aizir saiakera ee ee ee ee 3 IOCkti Conv NAC General Purpose 4 IOCkKt2 Conv NAC General Purpose SA F amp 1 Point 1 Addr Detector Photo In l Selects S 2 Point2 Addr Detector Photo example 3 Point3 Addr Detector Photo 4 Point4 Addr Detector Duct p A A A A A A 1 l 5 Point5 Addr Detector Duct l ji 6 Point 6 Addr Sounder Base 5 i gt i 7 Point7 Addr Sounder Base 8 Point8 Addr Detector Heat Fixed Points 5 6 amp 12 Device Addr Name Function 9 Point9 Addr NAC General Purpose are selected Built in SLC 5 Point5 Addr Detector Duct i 10 Pointi0 Addr Relay General Purpose Built in SLC 6 Point6 Addr Sounder Base 11 Pointii Addr Relay Base ie ee Built in SLC 12 Point 12 Addr Relay Base 12 Point 12 Addr Relay Base Points 5 6 amp 12 13 Pointi3 Unused are configured into 14 Point14 Unused Zones 2 and 3 3 Click in Points window to display point assignment by Zone s Click to
135. ter Electric Signal O Zores Phone 1 800 325 3936 NN cee ee eee d Tue 02 15 2011 7 4849AM O coss Zones la l Job Name one 2 Address Line 1 Points i i l Address Line 2 l Q Lu l Email tech pottersignal com Address Line 3 A z erase Job Details display here Sensitivity jo Al Phone i Phone 2 Email Reporting es ee J Email Email 2 Mi a Q Users 02 15 2011 7 47 40 AM System Powerup e LAN Settings Do not reply to this message Contact your installation company Q Dialer When a history or detector sensitivity status e mail is received it contains two attachments e A text file txt e A comma separated values csv file Figure 92 Example of a Detector Sensitivity Status text file txt File Edit Format View Help Potter Electric Signal Training Panel Detector Status txt Thu 01 13 2011 8 00 094m Potter North Refer to Table 17 Zone Attributes 11790 Troy Lane North llamas in this Section for an explanation of 300 325 3036 Day Night Sensitivity settings tech pottersignal com orders pottersignal com R A sensor Sensor current Peak Day Night Thermal Drift i NFPA 72 condition sensitivity sensitivity Alarm Level Percentage imi Compliant 00 C000 00 C000 00 C000 00 C000 00 C000 00 C000 00 000 00 C000 00 C000 00 C000 00 C000 00 C000 00 C000 00 C000 00 C000 00 C000 00 C000 00 C000 Yes Yes Yes Yes
136. ting Accounts Primary Primary Primary Primary Supervision Primary Primary Primary Primary Secondary feos Penat Saron kopat Account Account cat Report alt IP Jolla UDP Interval Encryption Encryption Receiver Account Account A A 16 Settings ID Test Events si Port sec Key Method Number Prefix Settings a Point SIA T 0 0 0 0 SIA DC09 20 None Al E Point lt SIA 0 0 0 0 SIA D009 20 None A vin Click here to collapse additional fields 0 0 0 0 SIA DOD9 20 None 9 Point 0 0 0 0 SIA DC09 20 None 9 O O O O Oo Ot Point lt SIA E 0 0 0 0 SIA DO09 20 None gt Sa Notes Use the scroll bar to display additional fields if not shown on right Click the s collapse icon at any time to hide the account setting fields e Enter the Account ID e Select the applicable Primary Format option CID STA e Click in the Report Test Events selection box Ed to send Test signals to this account e Double click in the Receiver IP field and enter the IP address provided by the remote monitoring station e Click on the Protocol Y drop down arrow to select Fibro Note Fibro communications is used with the Sur Guard receiver e Double click in the UDP port field to enter the Primary Secondary port number as provided by the remote monitoring station Note The UDP port number is the pathway for data which the receiver receives from the system panel and sends to the system pan
137. ting Time Zone GMT 06 00 CST Central Standard gt e AE A ET Enable Daylight Savings Time Adjustment Daylight Savings Time O annunciators Month Day e SLC Loop Start Mar v Second Sunday v e End Nov First Sunday E mail Report Requested from PC To request a report from a remote PC 1 Open or create a new e mail 2 Inthe To field enter the panel s e mail address as shown below Refer to the Panel Serial Number Location shown earlier in this topic Figure 89 Example of Keywords in E mail Subject Field S History Status Message Insert Format Tools Table Window Help lit By ol Option HTML panelserialnumberm potterlink com el nter keyword s In Subject field History Status 5 65 PFC 6030 5403595 REV C 2 13 AJH System e mail communications and functions are intended for informational reporting purposes only They are intended to be used as a convenience function E mail communications should NOT be used as a primary means of reporting emergency information 3 Inthe Subject field enter one or more of the following keywords e History to send a current event history report back to sender e Status to send a current detector sensitivity status report back to sender e Configuration to send a current configuration file back to sender e Unsubscribe to stop the current e mail settings for the sender until panel is reset or that e mail address sends a Subs
138. ting circuits to the main board 1 the circuit separation and 2 wiring types Circuit Separation Proper separation between the different types of circuits must be maintained between Power Limited Non Power Limited and High Voltage wiring to reduce electrical interferences transient voltage or voltage ratings e Separations between the different wiring types must be maintained by at least Y inch and the wire insulation must be for the higher voltage e The control panel cabinet has sufficient knockouts located around the periphery allowing the installer to maintain separation between power limited and non power limited connections Wiring Types Wiring specifications must be followed to prevent damage or other consequences Refer to table below for a breakout of the different wiring requirements shown by circuit type Table 5 Main Board Circuit Wiring Types Trouble Relay Low Voltage Non Power Limited 2 5 PFC 6030 5403595 REV C 2 13 Cabinet Dimensions Figure 1 PFC 6030 Cabinet Dimensions DEPTH 3 75 DOOR 16 07 l BACKBOX 15 77 DEPTH 3 84 OO DOOR 16 78 BACKBOX 16 56 LEFT SIDE RIGHT SIDE BOTTOM DWG 593 1 2 6 Cabinet Wiring Connections Figure 2 PFC 6030 Cabinet Wiring 120VAC 50Hz 60Hz 240VAC 50Hz 60Hz Connect to separate unswitched AC circuits 120 240 VAC Jumper Position Non power limited battery connection Non power limited relay
139. tment Daylight Savings Time Q Annunciators Month Day e SLC Loop Start Second Sunday v End Nov First Sunda v Q Power Supply E PFC 6030 5403595 REV C 2 13 Day Night Sensitivity Mode and Holiday Scheduling The Sensitivity option allows you to enable the Day Night Sensitivity feature establish the starting and ending times for Night sensitivity create a Holiday Schedule and choose the days of the week that the site is normally occupied To enable day night sensitivity and setup holidays l oe a Panel we 4 0 Remote Access Code 0 Job Details 0 General Options 0 Zones O cross Zones O on O sensitivity Email Reporting O users Month Day 12 25 11 25 1 18 2 15 7 4 2 Note You may enter up to fifty 50 holidays in the Holiday Schedule field which enables night sensitivity mode on those dates Click on the Sensitivity option The Sensitivity window displays Figure 82 Example of the Day Night Sensitivity Enabled Night Sensitivity Window Start Time End Time Normal Occupancy Schedule Monday Saturday Tuesday C Sunday Wednesday Thursday Friday Click in Enable Day Night Sensitivity selection box to enable Adjust start and end times 1f needed Click in applicable days of the week selection boxes to select or deselect Enter holidays in the Month Day field as shown 5 60 Note The Day Night Sensitivity opt
140. to display zone styles Alarm nal Unused Alarm SUperndsory Pos Alarm Seq AUX Releasing Fire Drill Sys Alarm Sys Super Sys Trouble 3 Choose the applicable zone style refer to the Zone Styles Table in this section for descriptions of zone styles 4 Continue editing zone s fields Refer to the Zone Attributes Table for field descriptions Configuring Points This section addresses how to define or configure points through the Points function Each device may have a unique function in relation to the zone as well as the entire system The user determines the Point s role specific behavior characteristics and customizes its name if desired The list of available functions is associated to the device or module type selected Notes e Points may be configured from either the Zones or Points functions however for purposes of this manual points are configured in the Points function e Points can be configured individually or by groups or ranges of devices An example of the Points window is shown below Figure 102 Example of Points Window Device Addr Name Function Supervisory nl PWR Supply 1 NAC 1 Conv NAC General Purpose PWR Supply 2 NAC2 Conv NAC General Purpose PWR Supply 3 Door Holder Conv NAC Aux Door Holder PWR Supply 4 Door Holder Conv NAC Aux Door Holder Built in SLC 1 Point 1 Addr Detector Photo F Fi Built in SLC 2 Point 2 Addr Detector Photo F F Built in SLC 3 Point 3 Addr Detector Photo dl
141. uble Pt 25 Built in SLC Unused P025 Trouble Pt 24 Built in SLC Unused P024 Trouble Pt 23 Built in SLC Unused P023 Trouble Pt 22 Built in SLC Unused P022 Trouble Pt 21 Built in SLC Unused P021 Trouble Pt 20 Built in SLC Unused P020 Trouble Pt 19 Built in SLC Unused P019 Trouble Pt 18 Built in SLC Unused P018 Trouble Pt 17 Built in SLC Unused P017 Trouble Pt 52 Built in SLC Unused P052 Double click here to adjust the column width based on the longest event description Transfers Type Status Time Medium URI Phone Filenan gt History Complete 7 21 2011 11 18 41 AM Ip 10 0 5 18 C Doc Download Complete 7 21 2011 11 15 22 AM IP 10 0 5 18 C Doci Click the Print icon then click the Report Print l icon or CTRL P to open the print dialog box Click the Print button 5 54 PFC 6030 5403595 e REV C 2 13 Panel Software Overview This section gives you an overview of the Panel Configuration Software It addresses navigating through the program windows understanding the purpose of icons and program features using Window s conventional editing techniques and other program shortcuts to efficiently configure your system Window Regions Areas What you select a function from the Panel window located on the left this determines the information displayed on the right The selected panel function is highlighted which helps direct your eye to the related information shown on the right For example when Remote
142. uilt in SLC 100 Point 100 Addr Detector Photo Heat PN Addr Detector Duct Built in SLC 101 Point 101 Addr Detector Heat Fixed Built in SLC 102 Point102 Addr Detector Heat Combo a Contact Input Pull Station Built in SLC 103 Point 103 Contact Input Water Flow Built in SLC 104 Point 104 Contact Input Supervisory sd ei Contact Input Tamper Built in SLC 105 Point 105 Contact Input Fire Drill ei Contact Input Trouble Monitor Built in SLC 106 Point 106 Contact Input Aux Built in SLC 107 Point 107 Addr Relay General Purpose UN Addr NAC General Purpose Built in SLC 108 Point 108 Addr Zone Module 4 Continue configuring other points as needed 5 78 PFC 6030 5403595 e REV C 2 13 To configure a range of points 1 Click the first point to configure from the Function field 2 Press and hold the SHIFT key then click in Function field of last point Figure 105 Example of Configuring a Range of Points Device Addr Name Function Built in SLC 1 Point 1 Built in SLC 2 Point 2 Built in SLC 3 Point 3 Built in SLC 4 Point 4 Built in SLC 5 Point 5 Built in SLC 6 Point 6 Built in SLC 7 Point 7 Built in SLC 2 Point 2 3 Right click from Function field to display configuration options Note If you right click outside of Function field the range 1s deselected and only one 1 device will be configured 4 Click on device type from shortcut menu Continue configuring other points
143. unicator is programmed the daily test call can be sent to both reporting accounts Please refer to Section 7 for more information on the IP Communicator Reporting Accounts If a DACT is not installed and the IP Communicator is not programmed the system will operate as a local panel The Reporting Accounts section 1s used to program DACT operations and to customize the format of the reporting accounts You may choose different settings for Alarms Troubles reporting accounts may be configured Figure 129 Example of Dialer Reporting Options Reporting Accounts and Supervisory conditions Up to five 5 primary and secondary SEE secondar Regane Alarms Troubles Supervisory ID Thee Report By Format Test Events ID e Report By Format Test Events d O O Panel CID O Panel CID O d O O Panel CID O Panel CID O O O O Panel CID O Panel CID O C F O Panel CID F Panel CID O F F O Panel CID O Panel CID O 5 89 PFC 6030 5403595 REV C 2 13 To add and configure a DACT module 1 Select Dialer from the system panel 2 Click the Add Device button The 4dd Dialer window displays Figure 130 Example of Add Dialer Window i Phone Line 1 Phone Line 2 Delete Dialer Enabled Enabled Device Name _ Answering Machine Bypass _ Answering Machine Bypass Enable Line Monitor Enable Line Monitor Dialer 1 Device ID Disable Dial Tone Detection Disable Dial Tone Detection Jo NO Line Prefix Line Pr
144. urrent Draw refer to SZC Current Draw Worksheet for calculation OOO OO o y Ta Convert to Amps x 0 001 x 0 001 Refer to maximum allowable standby current Total A PP Todal SS 60 minutes per hour Alarm time minutes Multiply by standby hours Example 5 minute alarm enter 12 10 minute alarm enter 6 Total StandbyAH Total Alarm AH C Toi sandoy AH Tot AH Required O Important Notes FACP enclosure can house up to two 2 18 AH batteries Larger batteries require accessory enclosure part SSU00500 NFPA 72 requires 24 hours of standby power followed by 5 minutes alarm activation NFPA 12 12A requires 24 hours and five minutes of alarm activation Door holder circuits configured to disconnect upon AC loss need not be included in the battery standby calculation since they will not draw power during that time Door holders will contribute to standby current draw when AC is present Total current must not exceed power supply rating 3 5A LED Relay current must be accounted for in the battery calculation for the supplying source i FCB 1000 5 100 Maximum Allowable Standby Current UL 24 Hour standby time 7 AH 230 A 18 AH 619 A 33 AH 1 151 A 55 AH 1 930 A PFC 6030 5403595 e REV C 2 13 SLC Current Draw Worksheet r A ES mA mA Analog photo smoke detector PSA photo smoke detector PSA INES 329 0325 325 a e asis photo smote rearea deco 5 os os aos c
145. wing Detail PSN 1000 Master Panel or PSN1000E FIB 1000 B To Additional P Link Devices FIB 1000 A Fiber Optic DWG 608 25A Cable Downstream FIB S2 ON ON Upstream FIB S2 OFF OFF Figure 46 Diagram 2 FIB 1000 Wiring Diagram Shown Installed in PSN 1000E Cabinet PSN 1000E To Additional P Link Devices Fiber In R2 T2 R1 T1 FIB 1000 B DWG 608 25B PFC 6030 5403595 REV C 2 13 Setting Addresses The FIB 1000 s address is set by dip switch S1 which is located on the back of the board The address must be set in the range of one to thirty 1 30 to be recognized by the panel Refer to the P Link Addresses table shown earlier in this section for DIP switch programming Figure 47 FIB 1000 Back Panel Showing Dip Switch Location O LJ P Link TIT I II eco gt III H ae h H 1 AAA AAA s1 O DWG 608 24 Dip Switches Serial Parallel Gateway Installation SPG 1000 An optional SPG 1000 serial parallel gateway printer drive board can be mounted inside the AE 8 or AE 14 accessor
146. y enclosure or the AE RM rack mount enclosure kit The SPG 1000RM includes a standard 19 inch rack mount enclosure which can then be installed directly in an equipment rack Up to thirty one 31 printers may be installed on this panel Figure 48 SPG 1000 Serial Parallel Gateway Board amp Rack Mount DWG 608 15 DWG 608 16 Figure 49 SPG 1000 Wiring to Control Panel Example Example Powered by control panel P Link P Link from DWG 608 26 control panel PFC 6030 5403595 e REV C 2 13 Setting Addresses A SPG 1000 address is set by dip switch S1 The address must be set in the range of one 1 to thirty one 1 31 to be recognized by the panel Refer to the P Link Addresses table shown earlier in this section for DIP switch programming Figure 50 SPG 1000 Back Panel View Showing Dip Switch Location O O 7 O osas o O E 00 nd s MA REEF em mU O i P Link DWG 608 25 Connections DACT Installation eile Phone lines are high voltage and should be run in a separate conduit from other circuits The wire conductors connecting the DACT to the phone system should be 26 AWG or larger The UD 1000 Digital Alarm Communicator Transmitter provides connections for two 2 phone lines for communication to a monitoring station The UD 1
147. y area region to redisplay items in original order 5 82 PFC 6030 5403595 e REV C 2 13 Cross Zone Configurations The purpose of creating cross zones 1s to ensure that two 2 or more separate zones are activated before an output zone is triggered Although crossing two 2 zones is the most common configuration up to eight 8 zones may be combined In this case when all the zones that have been crossed are active the specified outputs will be activated To create a cross zone 1 Create two or more Alarm or Supervisory type zone s and name appropriately 2 Configure and name devices 3 Move devices into zones 4 Open the Cross Zones window Click in the Enabled box Figure 117 Cross Zones Window Showing Enabled Panel w A A Enabled Input Input Input Input Input Input Input Input Output 0 Remote Access Code Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone d Y 0 Job Details O O cenea Opti A eneral Options OD 0 Zones O O 0 Cross Zones F Note If the Enabled option is not selected the cross zone relationship will not be in effect 5 Click on the drop down arrow in the Input Zone 1 field All available zones display Input _ Input Fone 1 Zone 2 1 Main Building 2 R amp D Lab Smk 3 R amp D Lab Heat 4 Air Handler Shutdown 6 Click to select input zone 7 Repeat steps for the next field Input Zone 2 field 8 Click on drop down arrow in the
148. y contact inputs are located on connector P7 All input circuits are power limited and use a 5 1k EOL resistor The inputs can be programmed for any of the contact input functions available for other input circuits available on the panel Figure 35 DRV 50 P7 Dry Contact inputs P7 O 5 1k Y gt Max wiring resistance 100 ohm O Max wiring capacitance 1 uF 5 1k mM o Max wiring length 10 000 ft nl Max IDC voltage 24 VDC 5 1k f N Max IDC current 5 mA 5 1k fs O Dry Contact Inputs P7 DWG 608 9 The higher current required for the LED outputs can be provided by the panel or from an auxiliary power source as shown below The auxiliary power can be any 24VDC source and is fully supervised Figure 36 Examples of Wiring DRV 50 from Control Panel or Auxiliary Power Supply Example Example Powered by Powered by control panel aux supply LED PWR Lin B A l Power from P Link from in dele auxiliary control panel p supply DWG 608 9B 3 29 PFC 6030 5403595 REV C 2 13 Setting Addresses The DRV 50 s address is set by dip switch S1 which is located on the back of the board The address must be set in the range of one to thirty one 1 31 to be recognized by the panel Refer to the P Link Addresses table shown earlier in this section fo
149. zones through the Zones panel using the drag and drop technique The examples illustrate how to use shortcuts to expedite configuring zones and also to reinforce the interaction between the Zones and Points windows To move one or more points into one zone 1 Open the Zones configuration window and adjust Points window to display functions Figure 108 Example of Resizing Points Window Alarm Silence 5 Name Style e bl Latching Local Output Pattern Loop Addr Name Function a PWR Su ply 1 NACI Conv NAC General Purpose Zone 1 Alarm 1 C Constant pply d PWR Supply 2 NAC2 Conv NAC General Purpose PWR Supply 3 IOCkti Conv NAC General Purpose PWR Supply 4 IOCkt2 Conv NAC General Purpose _ Built in SLC 1 Pointi Addr Detector Photo Built in SLC 2 Point 2 Addr Detector Photo Built in SLC 3 Point 3 Addr Detector Photo lt T gt Built in SLC 4 Point 4 Addr Detector Duct PPP Biitiin SLC 5 Point 5 Addr Detector Duct Device Addr Name Function Built in SLC 6 Point 6 Addr Sounder Base Built in SLC 7 Point 7 Addr Sounder Base PWR Supply 1 NAC1 Cony NAC General Purpose Built in SLC 8 Point 8 Addr Detector Heat Fixed PWR Supply 2 NAC2 Cony NAC General Purpose Built in SLC 9 Point 9 Unused PWR Supply 3 IOCkti Conv NAC General Purpose Built in SLC 10 Point 10 Unused PWR Supply 4 IOCkt2 Cony NAC General Purpose Built in SLC 11 Point 11 Unused Built in SLC 12 Point 12 Unused Built in SLC 13 Point 13 Unused Built in SLC 14 Pointi4 Unused wy
Download Pdf Manuals
Related Search
Related Contents
Samsung Tủ lạnh 2 cửa với Công nghệ Digital Inverter 442L (RT43H5231SL) Hướng dẫn sử dụng sterilizzatore a vapore art. 2400 Instrukcja - Hendi Rental Copyright © All rights reserved.
Failed to retrieve file