Home

Manual - Vanguard Instruments Company, Inc.

image

Contents

1. Press the gt key next to the option LED indicators to In DRY CONTACT mode the PCI 600 will output a DC voltage to the TIMER STOP terminals to sense the state of dry contacts A change in this dry contact state will stop the timer and turn off the current source This mode requires an external input to the PCI 600 External timer stop input signals are sensed through the TIMER STOP connectors In WET CONTACT mode the PCI 600 will sense an AC or DC voltage applied to the TIMER STOP connectors The OFF state is any voltage from 0 to 10 V ac dc The ON state is any voltage from 24 to 300 V ac dc A change in the Voltage state will stop the timer and turn off the current source This mode requires an external input to the PCI 600 External timer stop input signals are sensed through the TIMER STOP connectors In CURRENT mode an interruption of the PCI 600 current source output CB contact opened will stop the timer and turn off the current source REV 2 PCI 600 USER S MANUAL 2 1 4 External Current Input The PCI 600 s EXT CURRENT input is a 10 ampere AC current meter This built in ampere meter allows the user to monitor an AC current This current input is isolated A typical application for this feature is to measure a Current Transformer CT current ratio The user can set the PCI 600 to output a current through the CT primary input The CT secondary output is measured with the PCI 600
2. by Vanguard Instruments Company factory personnel or by an authorized repair service provider Unauthorized modifications can cause safety hazards and will void the manufacturer s warranty REV 2 PCI 600 USER S MANUAL TABLE OF CONTENTS CONVENTIONS USED IN THIS DOCUMENT cseccccessecceceessccecsuenscceeeeeecceseeeeecessegeeessuageeeetseges 1 LO INIRODUCTHON nee none nc eee eee en ne en ee encore een ee ee ee ee ee 2 1 1 General Description and FEatures s iimnria 2 1 2 PCI 600 Technical SpecificationS seesseesseesneesenerresrsesrroseresrresreesressrersrensrenseenseesseesseee 3 13 COntroband MACAO Scansione nenen niee eana ENTIN ETENEE eiei 4 2 0 OPERATING PROCEDURES sl ii 6 21 FUNCHORA DEScrpioienmea ia 6 Dodie ACGCUTENESOUE bia 6 2 1 2 Current Output Control dai 6 213 Timer Stop input and CoMtrOl eapi nren ann EE S EE EEES 7 21A EKEN CUPP OEIC IN pU oere a EE OE ali 8 215 LIDO 8 22 100 ASCA O EA 9 2 2 1 Testing the Open Time Delay of a Protection Relay 9 2 2 2 Measuring Current Transformer Primary and Secondary Current tt 11 LIST OF TABLES Table 1 PCI 600 Technical SpecificationS i 3 Table 2 Functional Descriptions of PCI 600 Controls and Indicators 5 Table C rrent Output vs Telai 6 LIST OF FIGURES Figure 1 PCI 600 Controls and INGICATONS siria 4 PCI 600 USER S MANUAL REV 2 CONVENTIONS USED IN THIS DOCUME
3. 61010 1995 UL61010A 1 CSA C22 2 standards Operating 10 C to 50 C 15 F to 122 F Storage 30 C to 70 C 22 F to 158 F 10 foot 1 0 AWG test leads power cord ground cable Transportation case One year on parts and labor REV 2 PCI 600 USER S MANUAL 1 3 Controls and Indicators The PCI 600 s controls and indicators are shown in Figure 1 A leader line with an index number points to each control and indicator which is cross referenced to a functional description in Table 2 The table describes the function of each item on the control panel The purpose of the controls and indicators may seem obvious but users should become familiar with them before using the PCI 600 Accidental misuse of the controls will usually cause no serious harm Users should also be familiar with the safety summary found on the front page of this User s Manual TRIS 4 SA A ER r fe a PES Ach e A i RIMA Ra i s J N x 5 th si o 4 TIMER S OP l VIE x j N ges gt ory contact y w wer contact current TM PRIMARY CURRENT INJECTION AT Vanguard instrumen Co Inc Ontario California USA www vanguard instruments com Figure 1 PCI 600 Controls and Indicators PCI 600 USER SMANUAL REV 2 Table 2 Functional Descriptions of PCI 600 Controls and Indicators Item Number 1 2 oO O NO Oo a 10 11 12 13 Panel Markings DRY CONTACT WET CONTAC
4. EXT CURRENT input Both the PCI 600 output current and the CT secondary current are displayed on the LCD allowing the user to easily calculate the CT current ratio The External Current s polarity with respect to the PCI 600 drive current is indicated on the LCD by a sign in phase or a sign out of phase Proper phasing is indicated when the same colored PCI connectors are connected to corresponding terminals on the CT as shown below TIMER STOP CURRENT CONTROL RS 232C Vanguard Instruments Co Inc Ontario CoMomie USA 2 1 5 LCD Contrast Control PCI G00 m To change the contrast level on the PCI 600 s LCD screen press Aratta and hold the contrast 3 key next to the LCD screen Release the contrast gt key when the desired contrast level has been reached CONTRAST PCI 600 USER SMANUAL REV 2 2 2 Performing Tests 2 2 1 Testing the Open Time Delay of a Protection Relay Follow the steps below to test the Open Time Delay of a protection relay a Make cable connections per the illustration below CURRENT CONTROL CONTRAST oc O orr i RS 232C Vanguard Instruments Co Inc Ontario Callfomia USA b Turn the CURRENT CONTROL knob counter clockwise to the zero position c Turn onthe power switch After the initial informational screens the following screen will be displayed OmS O OCY Ext I 0 000 A Drv I 0 00 A REV 2 PCI 600 USER S MANUAL
5. NT This document uses the following conventions e Akey switch input or knob on the PCI 600 is indicated as KEY SWITCH INPUT KNOB e Menu options are referenced as WENU OPTION e PCI 600 LCD screen output is shown as e Warning messages are indicated as e Important notes are indicated as w REV 2 PCI 600 USER S MANUAL 1 0 INTRODUCTION 1 1 General Description and Features The PCI 600 is a programmable AC high current source designed specifically for utility substation applications This device is well suited for primary injection testing of protective relays This versatile device can also be used for testing thermal magnetic and solid state motor protection relays and molded case circuit breakers as well as any application that requires a high current source Built in Timer The PCI 600 s built in timer can test the time delay characteristics of protection relays and molded case circuit breakers Once the test is initiated the current source and the timer are automatically turned on at the next zero crossing point of the AC The timer stops when the PCI 600 input detects a change in the dry contact or voltage input or detects the removal of the test current The test results are then displayed in milli seconds and fractions of a cycle s on the unit s back lit LCD screen 20 characters by 4 lines Current Source Test currents ranging from 10 to 600 amperes can be set by using the ro
6. PCI 600 PRIMARY CURRENT INJECTION DEVICE USER S MANUAL 90 240 Vac 50 60 Hz 20A TIMER STOP EXT CURRENT ory contact wer contact current CURRENT CONTROL PC PRIMARY CURRENT INJECTION RS 232C Vanguard Instruments Co Inc Tu Ontario California USA anguard instruments com Vanguard Instruments Company Inc 1520 S Hellman Ave Ontario California 91761 USA TEL 909 923 9390 June 2013 FAX 909 923 9391 Revision 2 PCI 600 USER SMANUAL REV 2 SAFETY SUMMARY FOLLOW EXACT OPERATING PROCEDURES Any deviation from the procedures described in this User s Manual may create one or more safety hazards may damage the PCI 600 or cause errors in the test results Vanguard Instruments Company Inc assumes no liability for unsafe or improper use of the PCI 600 All safety precautions provided in this manual must be observed during all phases of testing including test preparation test lead connection actual testing and test lead disconnection SAFETY WARNINGS AND CAUTIONS Only trained operators shall use this device All circuits under test shall be off line and fully isolated DO NOT MODIFY TEST EQUIPMENT To avoid the risk of introducing additional or unknown hazards do not install substitute parts or perform any unauthorized modification to any PCI 600 test unit To ensure that all designed safety features are maintained it is highly recommended that repairs be performed only
7. T CURRENT TIMER STOP EXT CURRENT GROUND CURRENT CONTROL RS 232C HIGH CURRENT PRESENT CONTRAST Functional Description Current lead connectors Back lit LCD screen 20 characters by 4 lines viewable in bright sunlight and low light levels Timer and current source stop input selection with LED indicator Stop input mode is selected by using the arrow keys Timer STOP input connectors External current input connectors Input power connector Circuit Breaker Power Switch PCI 600 ground stud Connect ground stud to substation ground using provided cable Current control knob RS 232C port for factory calibration diagnostics and firmware updates High current presence indicator LED The up and down arrows are used to control the current source output and timer Three modes are available ON TMR Turns on current source and timer OFF Turns off current source and timer MONT Turns on current source momentarily LCD screen contrast control REV 2 PCI 600 USER S MANUAL 2 0 OPERATING PROCEDURES 2 1 Functional Description 2 1 1 AC Current Source AC test currents from 10A to 600A are set by turning the CURRENT CONTROL knob on the front panel The test current is measured and displayed on the LCD screen The PCI 600 output current ratings are shown in Table 3 below CURRENT CONTROL Table 3 Current Output vs Time Output 120 Vac Output 240 Vac Time 5 6 Vac 100 A 9 5 Vac 100A 1 ho
8. d From the Timer Stop section on the control panel press the key until DRY CONTACT is selected as shown below pry contact O wert contact O current Press and hold the 4 key to momentarily turn on the current source on tm Turn the CONTROL KNOB clockwise to set the desired current The screen will be updated as shown below OmS O OCY Ext I 0 000 A Drv I 20 00 A Release the 4 key Press the N key to select ON TMR mode and start the test on tm The PCI 600 will inject the preset current into the bus and turn on the timer The LCD will be updated as shown below A5bmS 57 2CY Ext I 0 000 A Drv I 20 00 A The timer will stop and the current source will turn off when the PCI 600 TIMER STOP input detects a change in the relay dry contact or if the operator presses the J key to select the OFF mode 7A INNS N PCI 600 USER SMANUAL REV 2 2 2 2 Measuring Current Transformer Primary and Secondary Currents Follow the steps below to measure current transformer primary and secondary currents a Make cable connections per the illustration below TIMER STOP gt pry contact wer contact Q current CURRENT 600 CONTROL PRIMARY CURRENT INJECTION CONTRAST RS 232C Vanguard Instruments Co Inc Ontario California USA www vanguard ins ram ans cow b Turn the CURRENT CONTROL knob counter clockwise t
9. o the zero position c Turn on the power switch The following screen will be displayed OmS O OCY Ext I 0 000 A Drv I 0 00 A d Press and hold the VY key to momentarily turn on the current source REV 2 PCI 600 USER S MANUAL E Turn the CURRENT CONTROL knob clockwise to set the desired current The screen will be updated as shown below Release the W4 key when the desired current is displayed on the screen Press the 4 key to select ON TMR mode and start the test on Tur Q orr o The CT primary and secondary currents will be displayed as well as the polarity as shown below Turn off the current source by pressing the 4 key on Tur Q orr oon Vanguard Instruments Company Inc 1520 S Hellman Ave e Ontario CA 91761 e USA Phone 909 923 9390 e Fax 909 923 9391 www vanguard instruments com Copyright 2013 by Vanguard Instruments Company Inc PCI 600 User s Manual e Revision 2 e June 28 2013 e TA
10. tary dial knob on the control panel The test current is then measured and the results are displayed on the LCD screen When the PCI 600 is used as a current source the current on time duration of current flow is displayed on the LCD screen External Current Input The PCI 600 also has an external current input 0 10 A Both the internal current source amplitude and the external current source measurement readings can be viewed at the same time PCI 600 USER S MANUAL REV 2 1 2 PCI 600 Technical Specifications Table 1 PCI 600 Technical Specifications TYPE PHYSICAL SPECIFICATIONS INPUT POWER INTERNAL METER RANGE MEASUREMENT METHOD EXTERNAL METER RANGE MEASUREMENT METHOD TIMER READING RANGE TIMER STOP INPUTS DISPLAY COMPUTER INTERFACE SAFETY ENVIRONMENT CABLES OPTIONS WARRANTY 100 600 Amp current source Dimensions 17 W x 12 5 H x 10 5 D 42 6 cm x 32 0 cm x 27 0 cm Weight 46 lbs 21 kg 100 120 Vac or 200 240 Vac factory pre set 50 60 Hz 100 mA 1000 A Accuracy 1 of reading 20 mA Isolated CT 10 mA 10 A Accuracy 1 of reading 2mA Isolated CT 1ms 2 hours Accuracy 0 1 of reading 1ms Voltage input 24V 300V DC or peak AC dry contact input or removal of primary current Back lit LCD Screen 20 characters by 4 lines viewable in bright sunlight and low light levels RS 232C port for factory calibration and diagnostics Designed to meet IEC
11. ur 5 3 Vac 200 A 9 4 Vac 200A 5 minutes 4 9 Vac 300A 9 0 Vac 300 A 2 minutes 4 6 Vac 400 A 8 2 Vac 400A 1 minute 4 2 Vac 500A 7 5 Vac 500 A 30 seconds 3 9 Vac 600 A 7 0 Vac 600 A 20 seconds 2 1 2 Current Output Control The PCI 600 current source output is controlled by the T and Q on TMR LV keys Three control modes are available Q orr Q mont ON TMR_ This mode turns on the PCI 600 s current source and timer This initiates a test and is stopped by using the Timer Stop inputs The test results will be displayed on the LCD The test can be terminated by pressing the y key The PCI 600 s built in time cycle counter is used to time events in milliseconds and cycles The elapsed time is displayed on the LCD along with the test current after a test is completed OFF In this mode both the current source output and timer are off MONT This mode turns on the current source momentarily To turn on the current source press and hold the 4 key The PCI 600 current output can now be set by turning the CURRENT CONTROL knob Release the 4 key to turn off the current source PCI 600 USER SMANUAL REV 2 2 1 3 Timer Stop Input and Control TIMER STOP select the mode pry conracr PRY CONTACT wert contact O current WET CONTACT CURRENT After a test is started the PCI 600 timer can be stopped and the current source turned off using one of three options listed below