1. Industrial Electronic Devices User Manual Revision 1 130 English M Bus Master BACnet IP Slave Converter Order Codes HD67056 B2 20 HD6 7056 B2 40 HD67056 B2 80 HD67056 B2 160 HD67056 B2 250 M Bus Master BACnet MS TP Slave Converter Order Codes HD6 7056 MSTP 20 HD6 056 MSTP 40 HD67056 MSTP 80 HD6 7056 MSTP 160 HD67056 MSTP 250 For Website information www adfweb com Product HD67056 B2 For Price information www adfweb com Price HD67056 B2 20 www adfweb com Price HD67056 B2 40 www adfweb com Price HD67056 B2 80 www adfweb com Price HD67056 B2 160 www adfweb com Price HD67056 B2 250 Benefits and Main Features Very easy to configure Up to 1500 BACnet Objects Temperature range 40 C 85 C 40 F 185 F ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 1 of 35 Other Products EET S Lavin HD67056 B2 ian C 10 64 E2 07 18 0C www ADFweb com r net Converter 00 ONION UON NOY A UANI IO l 20 oH De CS B164 m 8 L 3 Serial Nr B5860 aetna s O EEFE BE SS ti 1 For others M Bus products see also the following link Converter M Bus www adfweb com Product HD67021 RS232 www adfweb com Product HD67022 RS485 Analyzer Scanner Sniffer M Bus www adfweb com Product HD67031 M Bus Repeater Isolator www adfweb com Product HD67032M Converter M Bus Modbus Slave ww
2. M Bus from O0 to 255 Device Identifier M Bus Baudrate 2400 Parity EWEN Cyclic Delay s 5 Node State value when slave device is not present Ox5a Zo Figure 3a Set Communication window ADFweb com S r l iy User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 16 of 35 Industrial Electronic Devices If selected BACnet IP the means of the fields for BACnet are Inthe fields IP ADDRESS insert the IP address that you want to give to the Converter Inthe fields SubNet Mask insert the SubNet Mask Inthe fields GATEWAY insert the default gateway that you want to use This feature can be enabled of disabled pressing the Check Box field In the field Port the port number used for BACnet communication is defined The default port used for BACnet communication is 47808 but is possible to insert any value except 10000 and 10001 Inthe field BACnet Device Name is possible to insert the name to give to the BACnet node Inthe field Device Identifier is possible to insert a number used for the Device Identifier of the BACnet node If selected BACnet MS TP or BACnet PTP the means of the fields for BACnet are In the field Baudrate it is possible to select the baudrate of the BACnet line 1200 2400 BACnet Type 4800 9600 19200 38400 57600 115200 Type BACnet MS TP Inthe fiel
3. Type of Data If the field From BCD to Integer is checked the Converter converts the BCD value of variable in Integer format This happens only if the variable is in BCD format and if the Data Type of BACnet is Positive Integer Value if it isn t nothing changes In the field BACnet Eng Unit it is possible to select a Engineering Unit of the Object by pressing to the button see BACNET ENG UNIT section for more details In the field Post Operation it is possible to select to do a math operation to the value The possibilities are 10 100 1000 10000 100000 10 100 1000 10000 100000 ADFweb com S r l iy User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 20 of 35 Having completed these fields to add the variable the button ADD VARIABLE must be pressed In order to modify a created variable it is necessary to select the desired variable change the wrong items and then press the MODIFY VARIABLE button SECTION VARIABLES By POSITION Selecting the desired node it is possible to add a variable In order to create a new variable it is necessary to fill these items M Bus Network N 41D 2 SE N E V Enable Variable To use the created variable the field Enable Variable must VAR Energy U0 50 TO 8 Description be checked If you have created a variable but for the 2 Nak Energy ot
4. BACnet Engineering Unit field or by selecting with the fields Select the Type and Select unit the Type Unit desired If the second way is used is necessary to press the Select Engineering Unit button for confirm the Select the Type Acceleration choice Selected BACnet Engineering Unit 18 gt watt hours Select a New BACnet Engineering Unit Select Unit meters per second per second Figure 5 Select the BACnet Engineering Unit window BACNET DATA TYPE When using the Variables List gt By Position is necessary to select the Data Type of the variable Is possible to select from these types Analog Input 1 DateTime 3 Positive Integer 2 String 4 See the number between in the VIFE section for know the type to assign to a variable ADFweb com S r l iy User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 23 of 35 Industrial Electronic Devices Possible choices for the fields used to create a variable Type of Data Function Field Energy Wh BACnet Data Type 1 _ Instantaneous Value Energy J 1 _ Minimum Value Volume m 1 Maximum Value Mass Kg 1 _ Value During Error State On Time 1 Operating Time 1 Power W 1 Power J h 1 Volume Flow m h 1 Dimension bit _ Volume Flow Ext m min 1 _ 8 Volume Flow Ext m s 1 16 Mass Flow Kg
5. Nr B8027 w iati ac Am LED Book Mode ia Tr Ge re Slate F a E mr M Mias Comm Emi s z a i x y lt E 2 3 HBs Eero F ae 3 oC E z A M Bus BACnet MSTP Converter a N Ee on meen eae S T a HD67056 MSTP 20 ati www ADFweb c Kii i Gn Bus Master BACret Ethernet Converter Dira l LJ HD67056 82 270 5 20 ON fart GND Dip Switch A ETHERNET 5 6 OEE Of rs232 JO SISISISISISI SISSE 663866660600 E a ll 71i mm 60 mm 106 mm 60 mm 27inch aes 4 17 inch 2 36 inch Housing PVC Housing PVC Weight 2009 Approx Weight 200g Approx Figure 11a Mechanical dimensions scheme for HD67056 B2 xxx Figure 11b Mechanical dimensions scheme for HD67056 MSTP xxx ADFweb com S r l iy User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 32 of 35 Industrial Electronic Devices ORDERING INFORMATIONS The ordering part number is formed by a valid combination of the following HD67056 B 2 xxx L Maximum number of slaves supported 20 up to 20 standard slaves 1 5mA consumption connected to M Bus 40 up to 40 standard slaves 1 5mA consumption connected to M Bus 80 up to 80 standard slaves 1 5mA consumption connected to M Bus 160 up to 160 standard slaves 1 5mA consumption connected to M Bus 250 up to 250 standard slaves 1 5mA consumption connected to M Bus Connectors Type 2 Fixed Screw Terminal Enclosure Type B Modulbox 4M 35mm DIN Rail mounting Device F
6. Point UO SO TO BACnet Eng Unit B YI N mow i VAR Time Point UO S17 TO g In the field Function Field it is necessary to select the VAR Time Point Uo 32 TO Post Operation None I type of data _ WAR Energy U0 S32 TO Max ATE GARAGE one T WAR Energy U0 S32 TO Ist The field Dimension is used to select the dimension of the VAR Time Point UO 33 TO Ey 4 i WAR Energy U0 S33 TO Max variable 8 16 24 32 32 real 48 64 bit VAR Energy UO 33 TO Ist In the field Length Variable Len insert the length of the canon PAE D i i 2 i i fob Energy ax data in the case of the dimension is Variable Length SVAR Energy U0 534 TO Ist 5 ID 28456571 Device 2 Jf OK x Cancel Import Network In the field Unit if it is necessary it is possible to select the unit of that variable The Unit is used for indicates from which device the data come Inthe field Storage Number if it is necessary it is possible to insert the value of storage counter of that variable With this field the Slave can indicate and transmit various stored counter states or historical values in the order in which they occur In the field Tariff if it is necessary it is possible to insert the value of the tariff of that variable The Tariff is used for indicates from which device the data come Inthe field VIFE it is possible to select a sub type of
7. the new folder with the button Open Project ADFweb com S r l iy User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 15 of 35 Industrial Electronic Devices SET COMMUNICATION This section define the fundamental communication parameters of two buses BACnet and M Bus By Pressing the Set Communication button from the main window for SW67056 Fig 2 the window Set Communication appears Fig 3 The window is divided in three sections the first for select the type of BACnet one for the BACnet ee parameters and the other for the M Bus Type BACnet IP In the field Type is possible to select the type of BACnet to use from BACnet BACnet IP use ethernet a a A BACnet MS TP use RS485 E BACnet PTP use RS232 SUBNET Mask 255 255 The means of the fields for M Bus are io W GATEWAY In the field Baudrate it is possible to select the baudrate of the M Bus line 300 600 192 168 1200 2400 4800 9600 19200 38400 Inthe field Parity it is possible to select the parity of the line None Odd Even E Ifthe field Cyclic Delay insert the time expressed in seconds between two scans from 0 BACnet Device Name to 65535 devicenamel In the field Node State value when slave device is not present it is possible to insert the value to assign to the Node State when the Gateway doesn t find the interrogated slave
8. 066 Power Supply M Bus MAC 10 64 E2 07 20 86 we OV W seral Hr B3027 1HY AE ii IR Ew DE _Dip Switch A_ ADFweb com S r l iy User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 11 of 35 Industrial Electronic Devices HD67056 MSTP xxx The device has got four LEDs that are used to give information of the functioning status The various meanings of the LEDs are described in the table below LED Normal Mode Boot Mode 1 Device state green Blinks slowly 1Hz OFF Blinks quickly when a reply to a 2 M Bus state green MBus gues ar Ve Ply OFF 3 BACnet Comm iach ae Penn OFF 4 Device state green OFF Blinks slowly ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 12 of 35 Industrial Electronic Devices BACNET HD67056 B2 XXX SERIE The BACnet connection must be made using Connector3 of HD67056 B2 with at least a Category 5E cable The maximum length of the cable should not exceed 100m The cable has to conform to the T568 norms relative to connections in cat 5 up to 100 Mbps To connect the device to an Hub Switch is recommended the use of a straight cable to connect the device to a PC PLC other is recommended the use of a cross cable Connectors BACNET HD67056 MSTP XXX SERIE R5232 port D SUBI Male _ _ _____ PIN2 RX The BACnet connection must be made us
9. 2 Must be at ON M Bus MAC 10 64 E2 07 20486 Serial Nr B8027 VW v i5 AC or HBL ka EXD Dip Switch A Led4 Yellow BACnet Comm V Positive wire VAC min 15V max 21V V DC min 18V max 35V Figure 1a Connection scheme for HD67056 B2 xxx ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 6 of 35 Industrial Electronic Devices Connector4 BACnet MS TP RS485 port Isolated Port S Shield to Isolated Ground B Negative wire Positive wire Led4 Green Device state Connectors R5232 port D SUB9 Male PIN2 RX PIN3 TX PINS GND Used for Programmation Port BACnet PTP IBACn et state SOQ0SO0G6 COLOQGOOOO To connect the device to the COM port _ Jofa PC in order to set it you have to M Bus use the programming cable AC34107 ora cable made as showed here Power Supply Dip Switch B Ww W z ra pez ow 15 JIV AC Ecot Mode on F i TE n E gt na gm Ce l are me De M Bus BACnet MSTP Converter Se ad i HD67056 MSTP 20 phat S44 wwr ADFweb com Doa Qnm me ON B B De ON bra GND a Dip SwitchA RS485 oem 0 Connector1 Power Supply OV Ground V Positive wire VAC min i5V max 21V vV DC min 18V max 35V Dip Switch B Dip1 Not used Dip2 Functioning mode B Boot M
10. 56 B2 XXX SERIE 12 REVISION LIST e tae Seo Se SERIE E Revision Date Author Chapter Description USE OF COMPOSITOR SW67056 14 1 100 04 07 2013 Fl All Type HD67056 MSTP 1 110 14 10 2013 Fl All Software changed v1 102 NEW PROJECT OPEN PROJECT 14 SET COMMUNICATION 15 1 120 27 02 2014 Fl All Software changed v1 104 M BUS 17 1 130 27 05 2014 Fl All Software changed v1 200 OBJECTS MAP 26 UPDATE DEVICE HD67056 B2 XXX SERIE 27 i UPDATE DEVICE HD67056 MSTP XXX SERIE 29 WARNING MECHANICAL DIMENSIONS 31 ORDERING INFORMATIONS 32 ADFweb com reserves the right to change information in this manual about ACCESSORIES 33 our product without warning ADFweb com is not responsible for any error this manual may contain DISCLAIMER 34 OTHER REGULATIONS AND STANDARDS 34 WARRANTIES AND TECHNICAL SUPPORT 35 RETURN POLICY 35 TRADEMARKS All trademarks mentioned in this document belong to their respective owners ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 3 of 35 Industrial Electronic Devices SECURITY ALERT GENERAL INFORMATION To ensure safe operation the device must be operated according to the instructions in the manual When using the device legal and Safety regulation are required for each individual application The same applies also when using accessories INTENDED USE Machines and systems must be designed so the faulty conditions do not lead to a dangerous situati
11. ARIABLES By TYPE Selecting the desired node it is possible to add a variable In order to create a new variable it is necessary to fill these items To use the created variable the field Enable Variable gi must be checked If you have created a variable but for the M Bus Network moment it is unused it is possible to uncheck the field 4 ID 2 Device 1 Nu n L fb Ener Enable Variable without delete it DE Enable Variable Description Energy UO SO TO Nodes VAR Energy UO S1 TO Tnet Dita ET A In the field Description it is possible to write a description Eo ae eee g virascu string i of the variable it isn t a necessary information it helps the VAR Time Point UO S8 TO Function Field Instantaneous Value v a i WAR Energy UO S8 TO Dimension bit I readability of the tree of network Logan Gacy pe bate gt Er 32 The field Type of Data is used to select the unit of FD vk enemrsncennisivsiontn _ VAR Volume UO S10 TO Unit 0 M measure _ VAR Volume UO SO TO Storage Number o aa z i f VAR Vol Flow UO SO TO In the field VIF ASCII String insert the string of VIF It is var power uo so To Tariff eoo SCid possible to use this field only if the Type of Data is VIF is VAR Flow Temperature UO SO TO MES Not Selected d m WAR Return Temperature UO SO TO _ From BCD to Integer in ASCII pal g 1 VAR Time
12. VIF Energy 0x00 Data Byte 4of4 0x00 Data Byte 30f4 0x00 Data Byte 2of4 0x00 Data Byte 1of4 0x44 DIF 0x06 VIF Energy 0x00 Data Byte 40f4 0x00 Data Byte 30f4 0x00 Data Byte 20f4 0x00 Data Byte 10f4 Other Variables 0x55 Check Sum 0x16 Stop Byte ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 21 of 35 Industrial Electronic Devices Identification Number or Secondary Address put in the reserved fields if Identification Number is checked Fixed Data Header Status of the meter put in the reserved field if Node State is checked First Variable O Second Variable 2 Tosbeuuseuimathes RosikionZeclcul Third Variable G User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 22 of 35 Industrial Electronic Devices Copy PASTE DELETE Is possible to copy paste delete a node or a variable simply by going with the right button of mouse on the desired item M Bus Network 4 ID 2 Device 1 WAR Eneray UO S WAR Ener Copy Variable j VAR V Paste Variable VAR Volu VAR Time Copy Node m VAR Paste Node Delete Items BACNET ENG UNIT By pressing to button the left window appears Fig 5 Is possible to insert directly the Unit using its unique number by compiling the Selected
13. after 1 frames By Type MODIFY NODE In the field Send Reset App Is checked the Converter send the Application Reset command to the slave ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 18 of 35 Industrial Electronic Devices In the field Variables List it is possible to select which type of variables definition to use If is selected By Type it is necessary to fill all fields in the section Variables with the correct values otherwise if By Position is selected you can insert the progressive number of the variable that you need page 13 for more information In the field Cut after frames it is possible to select after how many frames the Converter stop to require data to be used in case of Multi Telegram Slave To use the created node the field Enable Node must be checked If you have created a node but for the moment it is unused it is possible to uncheck the field Enable Node without delete it After that pressing the ADD NODE button a new node appears in the left side of the window In order to modify a created node it is necessary to select the desired node change the wrong items and then press the MODIFY NODE button ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 19 of 35 Industrial Electronic Devices SECTION V
14. amily HD67056 M Bus Master BACnet Converter Order Code HD67056 B2 20 Converter M Bus Master BACnet IP Slave up to 20 slaves connected to M Bus Order Code HD67056 B2 40 Converter M Bus Master BACnet IP Slave up to 40 slaves connected to M Bus Order Code HD67056 B2 80 Converter M Bus Master BACnet IP Slave up to 80 slaves connected to M Bus Order Code HD67056 B2 160 Converter M Bus Master BACnet IP Slave up to 160 slaves connected to M Bus Order Code HD67056 B2 250 Converter M Bus Master BACnet IP Slave up to 250 slaves connected to M Bus Order Code HD67056 MSTP 20 Converter M Bus Master BACnet MS TP Slave up to 20 slaves connected to M Bus Order Code HD67056 MSTP 40 Converter M Bus Master BACnet MS TP Slave up to 40 slaves connected to M Bus Order Code HD67056 MSTP 80 Converter M Bus Master BACnet MS TP Slave up to 80 slaves connected to M Bus Order Code HD67056 MSTP 160 Converter M Bus Master BACnet MS TP Slave up to 160 slaves connected to M Bus Order Code HD67056 MSTP 250 Converter M Bus Master BACnet MS TP Slave up to 250 slaves connected to M Bus ADFweb com S r l iy User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 33 of 35 Industrial Electronic Devices ACCESSORIES Order Code APWO20 Power Supply for M Bus Master device that supports up to 20 Slaves Order Code APWO40 Power Supply for M Bus Master device that supports
15. ast readout sec s day s 2 _ Start date time of tariff 2 _ Duration of tariff nn 01 11 min to day 2 _ Period of tariff sec s to day s 2 ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 24 of 35 Period of tariff months s 2 Period of tariff year s 2 dimensionless no VIF 2 Volts 1 Ampere 1 Reset counter 2 Comulation counter 2 Control signal 2 Day of week 2 Week number 2 Time point of day change 2 State of parameter activation 2 Special supplier information 2 Duration since last comulation hour s year s 2 Operation time battery hour s year s 2 Date and time of battery change 3 Energy MWh 1 Energy GJ 1 Volume 1 Mass 1 Volume 0 1 feet 3 1 Volume 0 1 american gallon 1 Volume 1 american gallon 1 Volume flow 0 001 american gallon min 1 Volume flow 1 american gallon min 1 Volume flow 1 american gallon h 1J Power MW 1 Power GJ h 1 Flow Temperature 1 Return Temperature 1 Temperature Difference 1 External Temperature 1 Cold Warm Temperature Limit F 1 Cold Worm Temperature Limit C i Cumul Count max power 1 Industrial Electronic Devices persecond 2 per minute 2 perhour 2 _perday 2 per week 2 permonth 2 peryear 2 per revolution measurement 2 _ increment per input pulse on input channel 2 _ increm
16. at OFF position is used for the normal working of the device The second with Dip2 of Dip Switch B at ON position is used for upload the Project and or Firmware Dip Switch B Dipi Not used Dip2 Functioning mode For the operations to follow for the updating see UPDATE DEVICE section Bot Mod Serna rere According to the functioning mode the LEDs will have specifics functions see LEDS section A Warning Dip2 of Dip Switch A of HD67056 B2 xxx must be at ON position for working even if the Ethernet cable isn t inserted ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 10 of 35 Industrial Electronic Devices LEDS HD67056 B2 xxx The device has got five LEDs that are used to give information of the functioning status The various meanings of the LEDs are described in the table below LED Normal Mode Boot Mode 1 Device State green Blinks slowly 1Hz Blinks quickly Re Blinks quickly when a reply to a l 2 M Bus Comm green MBus request arrives Blinks quickly We Becames ON when the reply to l l Pe BUSTER MBus interrogation isn t arrived PNE Aay Change state when receive a 4 BACnet Comm BACnet request Blinks quickly ON Ethernet cable connected ON Ethernet cable connected 5 Ethernet Link green OFF Ethernet cable disconnected OFF Ethernet cable disconnected 666860606660 86
17. d Parity it is possible to select the parity of the line None Odd Even Inthe field MAC Address is possible to define the MAC of BACnet node from O to 254 BACnet In the field BACnet Device Name is possible to insert the name to give to the BACnet Baudrate 9600 node maximum 17 characters Parity NONE arit MAC Address BACnet Device Name idevicenamel M Bus Baudrate 2400 Parity EVEN Cyclic Delay 5 5 Node State value when slave device is not present Ox5a Zo Figure 3b Set Communication window ADFweb com S r l Industrial Electronic Devices M BUS User Manual Document code MN67056_ENG M Bus Master BACnet Slave Revision 1 130 Page 17 of 35 By Pressing the M Bus button from the main window for SW67056 Fig 2 the window M Bus Network appears Fig 4 SECTION NODES In the section Nodes it is possible to create the nodes of M Bus line F In order to create a new node it is necessary to select which address use selecting Primary ID Node or Secondary ID Node to makes the requests and then insert the Primary Address from 1 to 250 or the Secondary Address from 0O to 99999999 of M Bus device in the field ID Node M Bus In the field Description it is possible to write a short description of the node If the field Node State is checked the Converter creates a BACnet object Positive In
18. e the device ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 8 of 35 Industrial Electronic Devices POWER SUPPLY The devices can be powered at 15 21V AC and 18 35V DC The consumption depends to the code of the device For more details see the two tables below No Load W VA Caution Not reverse the polarity power N OV Ground HD67056 B2 xxx V Positive wire HD67056 MSTP xxx VAC min 15V max 21V V OV y DC min 18V max 35V IOV Ground I V Positive wire W AC min 15V max 21V V DC min 18V max 35V Connectori Power Supply ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 9 of 35 Industrial Electronic Devices FUNCTION MODES HD67056 B2 xxx serie The device has got two functions mode depending of the position of the Dip1 of Dip Switch A The first with Dip1 of Dip Switch A at OFF position is used for the normal working of the device The second with Dip1 of Dip Switch A at ON position is used for upload the Project and or Firmware Dip Switch A Dip1 Functioning Mode Normal Mode Boot Mode Dip2 Must be at ON HD67056 MSTP xxx serie The device has got two functions mode depending of the position of the Dip2 of Dip Switch B The first with Dip2 of Dip Switch B
19. ecifics ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 14 of 35 Industrial Electronic Devices USE OF COMPOSITOR SW67056 To configure the Converter use the available software that runs with Windows called SW67056 It is downloadable on the site www adfweb com and its operation is described in this document This manual is referenced to the last version of the software present on our web site The software works with MSWindows XP Vista Seven 8 32 64bit Step 1 J Open project Step 2 Eza Set Communication When launching the SW67056 the right window appears Fig 2 Note It is necessary to have installed Net Framework 4 Step 4 Step 5 Er Update Device www ADFweb com Figure 2 Main window for SW67056 NEW PROJECT OPEN PROJECT The New Project button creates the folder which contains the entire device configuration Name of the new Project Name of the new Project Examplel Example MSTP Zox A device configuration can also be imported or exported To clone the configurations of a Programmable M Bus Master BACnet Converter in order to configure another device in the same manner it is necessary to maintain the folder and all its contents To clone a project in order to obtain a different version of the project it is sufficient to duplicate the project folder with another name and open
20. ent per output pulse on output channel 2 per liter 2 perm 3 2 perkg 2 _ per K Kelvin 2 per kWh 2 perGJ 2 perkW 2 per K I Kelvin liter 2 per V Volt 2 per A Ampere 2 _ multiplied by sek 2 _ multiplied by sek V_ 2 multiplied by sek A 2 _ start date time of 2 _ VIF contains uncorrected unit instead of corrected unit 2 _ Accumulation only if positive contributions 2 Accumulation of abs value only if negative contributions 2 _ upper lower limit value 2 ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 25 of 35 of exceeds of lower upper limit 2 Date time of begin end of first last lower upper limit exceed 2 Duration of limit exceed 2 Duration of first last 2 Date time of first last begin end 2 Multiplicative correction factor 2 Additive correction constant unit of VIF offset 2 Moltiplicative correction factor 10 3 2 future value 2 next VIFE s and data of this block are manufacturer specific 2 None 2 Too many DIFE s 2 Storage number not implemented 2 Unit number not implemented 2 Tariff number not implemented 2 Function not implemented 2 Data class not implemented 2 Data size not implemented 2 Too many VIFE s 2 Illegal VIF Group 2 Illegal VIF Exponent 2 VIF DIF mismatch 2 Unimplemented action 2 N
21. h 1 _ 24 Flow Temperature C 1 32 Return Temperature C 1 32 real Temperature Difference K 1 48 External Temperature C 1 _ 64 _ Pressure bar 1 Variable Length 4 Averaging Duration 1 Actuality Duration 1J _ Type of data in VIFE Time Point 3 VIF isin ASCII 2 Unit for H C A 2 Fabrication No 2 _ Enhaced Identification 2 Bus Address 2 ADFweb com S r l Industrial Electronic Devices VIFE Not Selected _ Credit of the nominal local legal currency units 2 _ Debit of the nominal local legal currency units 2 Access Number transmission count 2 Medium as in fixed header 2 _ Manufacturer as in fixed header 2 _ Parameter set identification 2 Model Version 2 Hardware Version 2 Firmware Version 2 _ Software Version 2 _ Customer Location 2 Customer 2 Access Code User 2 _ Access Code Operator 2 Access Code System Operator 2 Access Code Developer 2 _ Password 2 _ Error flags binary 2 _ Error mask 2 _ Digital Output binary 2 _ Digital Input binary 2 Baudrate Baud 2 _ response delay time bittimes 2 Retry 2 _ First storage for cyclic storage 2 _ Last storage for cyclic storage 2 Size of storage block 2 _ Storage interval sec s day s 2 Storage interval month s 2 _ Storage interval year s 2 Duration since l
22. h Mb Dimension bit 32 i A VAR Volume UO S1 TO ength Variable Len moment it is unused it is possible to uncheck the field var volume uo s2 To E Eee ton p Enable Variable without delete it VAR Time Point UO S8 TO E _ From BCD to Integer VAR Energy UO S8 TO gt Position In the field Description it is possible to write a description a yog Fri a sia i BACnet Eng a eas i i fo be m of the variable it isn t a necessary information it helps the var volume uo lt 10 TO A eta Tipe TS readability of the tree of network _ VAR Volume UO SO TO Post Operation None Tel i i i e VAR Volume Flow UO SO TO The field Dimension is used to select the dimension of the VAR Power U0 SO TO MONIY VARIANT EN VAR Flow Temperature UO SO TO variable 8 16 24 32 32 real 48 64 bit VAR Return Temperature UO SO TO v ne i VAR Time Point UO SO TO In the field Length Variable Len insert the length of the ii Tine Pont Gn Bi T data in the case of the dimension is Variable Length VAR Time Point U0 32 TO i mi WAR Energy U0 S32 TO Max If the field From BCD to Integer is checked the Converter VAR Energy U0 S32 TO Ist converts the BCD value of variable in Integer format This ereen cies i A po Energy ax happens only if the variable is in BCD format and if the Data VAR Energy UO 33 TO Ist Type of BACnet is Pos
23. ial Electronic Devices lt K Note When you install a new version of the software if it is the first time it is better you do the update of the Firmware in the HD67056 MSTP xxx device lt K Note When you receive the device for the first time you also have to update the Firmware in the HD67056 MSTP xxx device A Warning If the Fig 10 appears when you try to do the Update try these points before seeking assistance Try to repeat the operations for the updating INIT PROTECTION Try with another PC Try to restart the PC If you are using the program inside a Virtual Machine try to use in the main OS If you are using Windows Seven or Vista or 8 make sure that you have the administrator privileges Take attention at Firewall lock If you are using a USB D gt RS232 converter try with a native COM port or change the converter only for HD67053M series Check if the serial COM port selected is the correct one FIRMWARE PROTECTION PROJECT PROTECTION Figure 10 Protection In the case of HD67056 MSTP xxx you have to use the software SW67056 www adfweb com download filefold SW67056 zip ADFweb com S r l J iy User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 31 of 35 Industrial Electronic Devices MECHANICAL DIMENSIONS SALILLA eee Power Supply M Bus MAC 10 64 E2 07 20 86 Power Supply Dip SwitchB O M Bus OV v Serial
24. ing D 7 PIN3 TX Connector4 or Connector5 of HD67056 MSTP PELD Mm PINS GND Used for Programmation Port BACnet PTP pieg ajisa To connect the device to the COM port ey sn lof a PC in order to set it you have to Dip2 Termination BACnet MS TP Line use the programming cable ACSATOT Open E 220 ohm jor a cable made as showed here _ a A J Connector4 BACnet MS TP RS485 port Isolated Port S Shield to Isolated Ground CABLE B Negative wire Side A A Positive wire FEM ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 13 of 35 Industrial Electronic Devices M BUS The M Bus is a unpolarized bus A two wire standard telephone cable JYStY N 2 0 8 mm is used as the transmission medium for the M Bus The maximum distance between a slave and the repeater is 350m this length corresponds to a cable resistance of up 29Q This distance applies for the standard configuration having Baud rates between 300 and 9600 Baud and a maximum of 250 slaves The maximum distance can be increased by limiting the Baud rate and using fewer slaves but the bus voltage in the space state must at no point in a segment fall below 12V because of the remote powering of the slaves In the standard configuration the total cable length should not exceed 1000m in order to meet the requirement of a maximum cable capacitance of 180nF Taken from M Bus sp
25. itive Integer Value if it isn t nothing a sen heer f FF Energy ax changes VAR Energy U0 34 TO Ist In the field Position insert the number of the variable that 7 75439571 Device 2 Jf OK x Cancel Import Network you want on BACnet In the field BACnet Eng Unit it is possible to select a Engineering Unit of the Object by pressing to the button see BACNET ENG UNIT section for more details In the field BACnet Data Type it is possible to select a type of Object used for saving the variable see BACNET DATA TYPE section for more details In the field Post Operation it is possible to select to do a math operation to the value The possibilities are 10 100 1000 10000 100000 10 100 1000 10000 100000 ADFweb com S r l j Industrial Electronic Devices o J AL Example 0x68 Start Byte OxBD L Fied OxBD L Field 0x68 Start Byte 0x08 C Field 0x02 A Field 0x72 CI Field 0x71 0x65 Identification Number Byte 30f4 0x45 4 Identification Number Byte 2of4 0x28 4 Identification Number Byte 1of4 0x4D Manufacturer Byte 2of2 Ox6A Manufacturer Byte 1of2 0x81 Version 0x04 Medium 0x3E Access Number 0x00 Signature Byte 2of2 0x00 Signature Byte 1of2 0x04 DIF 0x79 VIF Identification 0x00 Data Byte 4of4 0x00 Data Byte 30f4 0x00 Data Byte 2of4 0x00 Data Byte 1of4 0x04 DIF 0x06
26. l negative environmental factors and impact of human health which could otherwise be caused by inappropriate disposal The recycling of materials will help to conserve natural resources For more information about recycling this product please contact your local city office your household waste disposal service or the shop where you purchased the product RESTRICTION OF HAZARDOUS SUBSTANCES DIRECTIVE 4 The device respects the 2002 95 EC Directive on the restriction of the use of certain hazardous substances in electrical OHS and electronic equipment commonly referred to as Restriction of Hazardous Substances Directive or ROHS 2002 95 EC CE MARKING The product conforms with the essential requirements of the applicable EC directives ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 35 of 35 Industrial Electronic Devices WARRANTIES AND TECHNICAL SUPPORT For fast and easy technical support for your ADFweb com SRL products consult our internet support at www adfweb com Otherwise contact us at the address support adfweb com RETURN POLICY If while using your product you have any problem and you wish to exchange or repair it please do the following Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information about the problem Send the product to the address provided
27. o Press the Execute update firmware button to start the upload When all the operations are OK the device automatically goes at Normal Mode At this point the configuration firmware on the device is correctly update J Note When you install a new version of the software if it is the first time it is better you do the update of the Firmware in the HD67056 B2 xxx device J Note B When you receive the device for the first time you also have to update the Firmware in the HD67056 B2 xxx device A Warning If Fig 8 appears when you try to do the Update try these points before seeking assistance Try to repeat the operations for the updating Try with another PC Try to restart the PC eT eens If you are using the program inside a Virtual Machine try to use in the main FIRMWARE PROTECTION Operating System If you are using Windows Seven or Vista or 8 make sure that you have the administrator privileges Take attention at Firewall lock Check the LAN settings Ver 1 001 PROJECT PROTECTION Figure 8 Protection window A In the case of HD67078 B2 xxx you have to use the software SW67056 www adfweb com download filefold SW67056 zip ADFweb com S r l iy User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 29 of 35 Industrial Electronic Devices s UPDATE DEVICE HD67056 MSTP xxx serie By pressing the U
28. o data available undefined value 2 Data overflow 2 Data underflow 2 Data error 2 Premature end of record 2 OBJECTS MAP Industrial Electronic Devices User Manual Document code MN67056_ENG M Bus Master BACnet Slave Revision 1 130 Page 26 of 35 By Pressing the Objects Map button from the main window for SW67056 Fig 2 is possible to create a csv document with the map of BACnet Objects ADFweb com S r l YS lt P A AT OS 1 M Bus ID Node amp Primary ID Node 2 9 Primary ID Node 2 10 Primary ID Node 2 11 Primary ID Node 2 12 Primary ID Node 2 13 Primary ID Node 2 14 Primary ID Node 2 15 Primary ID Node 2 16 Primary ID Node 2 17 Primary ID Node 2 18 Primary ID Node 2 19 Primary ID Node 2 20 Primary ID Node 2 21 Primary ID Node 2 22 Primary ID Node 2 23 Primary ID Node 2 24 Primary ID Node 2 25 Primary ID Node 2 26 Primary ID Node 2 27 Primary ID Node 2 28 Primary ID Node 2 29 Secondary ID Node 28456571 30 Secondary ID Node 28456571 31 Secondary ID Node 28456571 32 Secondary ID Node 28456571 Var Description Time Point U0 58 Energy U0 58 TO Energy U0 59 TO Volume U0 59 TO Volume U0 510 TO Volume U0 50 TO Volume Flow U0S Power U0 50 TO Flow Temperature Return Temperatu Time Point U0 50 Time Point U0 S1 Time Point U0 53 Energy UO 532 TO Energy UO 532 TO Time Point U0 53 Energ
29. ode H Normal Mode Figure 1b Connection scheme for HD67056 MSTP xxx ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 7 of 35 Industrial Electronic Devices CHARACTERISTICS The HD67056 B2 xxx is a M Bus Master BACnet IP Converter The HD67056 MSTP xxx is a M Bus Master BACnet MSTP PTP Converter It allows the following characteristics Electrical isolation between Ethernet and M Bus for HD67056 B2 xxx serie Electrical isolation between RS485 RS232 and M Bus for HD67056 MSTP xxx serie Baud Rate and Parity changeable with software Mountable on 35mm Rail DIN Power Supply 15 21V AC or 18 35V DC Temperature range 40 C to 85 C t 4 At the Converter can be connected up to 250 standard M Bus devices This number depends of the code expressed by the xxx number HD67056 B2 20 and HD67056 MSTP 20 support up to 20 M Bus devices HD67056 B2 40 and HD67056 MSTP 40 support up to 40 M Bus devices HD67056 B2 80 and HD67056 MSTP 80 support up to 80 M Bus devices HD67056 B2 160 and HD67056 MSTP 160 support up to 160 M Bus devices HD67056 B2 250 and HD67056 MSTP 250 support up to 250 M Bus devices CONFIGURATION You need Compositor SW67056 software on your PC in order to perform the following Define the parameter of BACnet line Define the parameter of M Bus line Define which M Bus variables are readable on BACnet Updat
30. on for the operator i e independent limit switches mechanical interlocks etc QUALIFIED PERSONNEL The device can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installation assembly commissioning and operation of this equipment and who have appropriate qualifications for their job RESIDUAL RISKS The device is state of the art and is safe The instruments can represent a potential hazard if they are inappropriately installed and operated by untrained personnel These instructions refer to residual risks with the following symbol This symbol indicates that non observance of the safety instructions is a danger for people that could lead to serious injury or A death and or the possibility of damage CE CONFORMITY The declaration is made by our company You can send an email to support adfweb com or give us a call if you need it ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 4 of 35 Industrial Electronic Devices EXAMPLE OF CONNECTION ee cum HD67056 B2 xxx Slave M Bus ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 5 of 35 Industrial Electronic Devices CONNECTION SCHEME Dip Switch A Dip1 Functioning Mode Normal Mode Boot Mode Dip
31. ow the actual IP address of the device you have to use this procedure Turn off the Device Insert the IP Address of HD67056 Put Dipl of Dip Switch A in ON position Turn on the device 168 2 Connect the Ethernet cable A Check the Connection the device Insert the IP 192 168 2 205 Press the Ping button Device Found must appear Press the Next button Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations are OK turn off the Device Put Dip1 of Dip Switch A at OFF position Update Device Options Turn on the device ral Firmware At this point the configuration firmware on the device is correctly updated i Read Firmware when finish ral Project ral Read Project when finish Execute update firmware Ver 1 001 INIT Waiting FIRMWARE Waiting PROJECT Waiting Figure 7 Update device windows ADFweb com S r l iy User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 28 of 35 Industrial Electronic Devices If you know the actual IP address of the device you have to use this procedure Turn on the Device with the Ethernet cable inserted Insert the actual IP of the Converter Press the Ping button must appear Device Found Press the Next button Select which operations you want to d
32. pdate Device button it is possible to load the created Configuration into the device and also the Firmware if is necessary If you don t know the actual IP address of the device you have to use this procedure Turn off the Device Follow these steps to update the HD67056 from R5232 Put Dip2 of Dip Switch B at ON position i man OF ihe ea Turn on the device 2 Insert the Boot Jumper see the manual Connect RS232 Null Modem Cable form your PC to the Converter 3 Select the COM port and press the connect button Select the COM port and press the Connect button m Press the Next button 4 Turn ON the Device Select which operations you want to do 5 Check the BOOT led It must blink quickly Press the Execute update firmware button to start the upload When all the operations are OK turn off the Device Put Dip2 of Dip Switch B at OFF position Disconnect the RS232 cable Update Device Options Turn on the device ral Firmware ral Read Firmware when finish At this point the configuration firmware on the device is correctly updated fw Project il Read Project when finish Execute update firmware INIT Waiting FIRMWARE Waiting PROJECT Waiting Figure 9 Update device windows ADFweb com S r l iy User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 30 of 35 Industr
33. teger type for saving the status of the counter If the field Identification Number is checked the Converter creates a BACnet object Positive Integer type for saving the Secondary Address of the device If the field Convert BCD in Integer Identification Num is checked the Converter converts the Identification Number that is normally expressed in BCD in a Integer Number and saves the number in the reserved positions If the field Send SND_NKE is checked the Converter send the SND M Bus Network a ID 2 Device 1 i VAR Energy U0 SO TO Energy UO Si TO Volume UO S1 TO Volume UO S52 TO Time Point UO 58 TO Energy UO 58 TO Energy UO 59 TO Volume UO 59 TO Volume UO S510 TO Volume UO S0 TO Volume Flow UO SO TO Power UO S0 TO Flow Temperature UO S0 TO Return Temperature UO S50 TO VAR Time Point UO SO TO Time Point UO S17 TO Time Point UO S32 TO Energy UO S32 TO Max Energy UO S32 TO Ist Time Point UO 533 TO Energy UO S33 TO Max Energy UO S33 TO Ist 2 VAR Time Point UO 534 TO Energy U0 534 TO Max Energy UO S34 TO Ist t ID 28456571 Device 2 v y Enable Node iy Hesston Variables Figure 4 M Bus Network window _NKE frame to start the communication Primary ID Node Secondary ID Node Node State Identification Number E Ba Swap Identification Num None Convert BCD in Integer Identification Num Send SND_NKE Send Reset App Valiables List Cut
34. up to 40 Slaves Order Code APWO8O Power Supply for M Bus Master device that supports up to 80 Slaves Order Code APW160 Power Supply for M Bus Master device that supports up to 160 Slaves Order Code APW250 Power Supply for M Bus Master device that supports up to 250 Slaves ADFweb com S r l User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 34 of 35 Industrial Electronic Devices DISCLAIMER All technical content within this document can be modified without notice The content of the document is a under continual renewal For losses due to fire earthquake third party access or other accidents or intentional or accidental abuse misuse or use under abnormal conditions repairs are charged to the user ADFweb com S r l will not be liable for accidental loss of use or inability to use this product such as loss of business income ADFweb com S r l shall not be liable for consequences of improper use OTHER REGULATIONS AND STANDARDS WEEE INFORMATION Disposal of old electrical and electronic equipment as in the European Union and other European countries with separate X collection systems m This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an applicable collection point for the recycling of electrical and electronic equipment If the product is disposed correctly you will help prevent potentia
35. w adfweb com Product HD67029M 232 on RS232 www adfweb com Product HD67029M 485 on RS485 Gateway M Bus Modbus TCP www adfweb com Product HD67044 Gateway M Bus CANopen www adfweb com Product HD67051 B2 Gateway M Bus PROFIBUS www adfweb com Product HD67053M Gateway M Bus Concentrator www adfweb com Product HD67054M Gateway M Bus Slave Modbus RTU master www adfweb com Product HD67059M 232 Do you have an your customer protocol www adfweb com Product HD67003 Do you need to choose a device do you want help www adfweb com Cmd helpme iy User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 2 of 35 Industrial Electronic Devices INDEX UPDATED DOCUMENTATION Page Dear customer we thank you for your attention and we remind you that INDEX 2 you need to check that the following document is UPDATED DOCUMENTATION 2 Updated REVISION LIST 2 raed tot ance WARNING 5 elated to the product you own URADE E 2 To obtain the most recently updated document note the Document code Soe Na ail 2 that appears at the top right hand corner of each page of this document EXAMPLE OF CONNECTION 4 PP p rng pag e With this Document Code go to web page www adfweb com download CONFIGURATION 5 and search for the corresponding code on the page Click on the proper POWER SUPPLY g Document Code and download the updates FUNCTION MODES 9 LEDS 10 i BACNET HD670
36. with the PRN having prepaid the shipping costs shipment costs billed to us will not be accepted If the product is within the warranty of twelve months it will be repaired or exchanged and returned within three weeks If the product is no longer under warranty you will receive a repair estimate ADFweb com S r l Via Strada Nuova 17 IT 31010 Mareno di Piave TREVISO Italy Phone 39 0438 30 91 31 Fax 39 0438 49 20 99 www adfweb com ADFweb com S r l
37. y UO 533 TO Energy UO 533 TO Time Point U0 53 Energy U0 534 TO Energy U0 534 TO NS Device 2 IN Device 2 Energy U0 50 TO Energy U0 51 TO Figure 6 Objects Map example file Istance wc s om anp amp 11 19 20 BACnet Data Type DateTime Value Object Analog Input Object Analog Input Object Analog Input Object Analog Input Object Analog Input Object Analog Input Object Analog Input Object Analog Input Object Analog Input Object DateTime Value Object DateTime Value Object DateTime Value Object Analog Input Object Analog Input Object DateTime Value Object Analog Input Object Analog Input Object DateTime Value Object Analog Input Object Analog Input Object Positive Integer Value Object Positive Integer Value Object Analog Input Object Analog Input Object BACnet Eng Unit no units watt hours watt hours cubic meters cubic meters cubic meters cubic meters per hour watts degrees Celsius degrees Celsius no units no units no units watt hours watt hours no units watt hours watt hours no units watt hours watt hours no units no units watt hours watt hours User Manual M Bus Master BACnet Slave Document code MN67056_ENG Revision 1 130 Page 27 of 35 Industrial Electronic Devices UPDATE DEVICE HD67056 B2 xxx serie By pressing the Update Device button it is possible to load the created Configuration into the device and also the Firmware if necessary If you don t kn