Home
        RAPID Control Installation Guide - Del
         Contents
1.                                                                                                                                                                                                                                                                                                                                                   Drain Wires connected to ground at 1 location only On all  Pa the rest of the connections drain wires are just tied together  a    SPDT Rela Zone 1 OO uis Zone 1 Sensor 2   i electronic ignition heater       p                 Fe    T a s  Zone 1 Sensor 1  To Heater      dH L1 Cable from    E L2 previous modul EB Anbient Sensor  L1 4amp Module   i Typical 4 amp  i    H   Module  go         To NW4K Fan   Li u Capaitor  E L2 ca  4amp Module   fy A  Network      E B  Network        To NW4K Fan                           L1 C  12V     E Typical Fan  BEM 12 D  12V     Connection  4 amp Module Im E  L1 Switched  out   Hl F  L2 N  out   is 3  B G  L2 N  in   To NW6K Fan 7 4  eo E H  L1  in   4 amp Module    fj  SPDT Relay    xr  B  To NW10K Fan  x   EM L1  E  L2 Typical 15 amp     Module  12 L1 4 amp Module Hi  SPDT Relay    pr E a P  To NW20K Fan    L1 B  Network      5 IL          H  HLI       C  12V     ki N D  12V  4   wu   E E  L2  White   SPDT Relay   4 rz 2 F  Switched  Blue    oo   H G  L1  Black          To NW20K Fan    2  nme  8 sd NOTE   i 25A relay must be used as shown if heaters are electronic ignition                          L2 L1       
2.      Zone1 Sensor2     gt   o       ge TT  Or Roco Rok oko      TB1 E  2  3  4  5 le 7  8  9 10 1112 113 1415 16 17 18 19 20 P1 l22  23  24  25  26  J7    Figure 4       Ambient Sensor  Zone2 Sensor1    Zone2 Sensor2                   For all wire types  lengths and other information concerning the RAPID Control please  refer to Appendix A        m 2 1 Power Input             Power is connected to the RAPID Control using  all the terminals of Terminal Block 1  TB1   The  control s power input is selectable to either 115  or 230 VAC  It will operate at 50 60 Hz   Connect power as shown in Figure 5                       e Before powering  make sure the power  selector switch is in the appropriate  position  See Figure 2   RAPID Control  Circuit Board        e Figure 4 shows the position of TBI     Figure 5    2 2 PC Network          The PC Network can be used with or without a computer connected to the network   Connecting the PC Net  with or without a computer  allows a single ambient sensor to be  used instead of every control in the facility needing an ambient sensor  The control with  the ambient sensor will broadcast the ambient temperature over the PC Net to the other  controls  The second use for the PC Net is connecting the controls to a PC running the  RAPIDPC software package  Using RAPIDPC you can view in real time how the control  is operating  make changes to settings  and log temperatures and events  As an  alternative to having a computer in the barn  RAPIDPC REM
3.    DELAIR RAPID  ISO 9001 CERTIFIED Environment Control  SY STEMS    INSTALLATION GUIDE    Ver 99C                                              RAPID Environment Control Installation Guide Ver99C    RAPID ENVIRONMENT CONTROL   INSTALLATION GUIDE    INTRODUCTION    The RAPID Control system is a distributed  networkable  2 zone control that has been  designed to simplify and economize installation  Figure 1 is a block diagram of some of  the devices that can be connected to the RAPID Control  They include     e Two Module Networks for control of many types of devices in two independent  zones    e Two Sensor Inputs per zone plus an additional Ambient Sensor       e Alarm devices including a local siren or auto dialer    e Central PC with RAPID PC software package  optional         Baro i Room Ambient    o la ze H   nad  m  z        728 J 4   ld mm                  i                             Multi Device  B RAPID  Module    e       l fik    1 2  1  9        isis                   Creep    Figure 1         Only one ambient sensor may be required per facility if multiple controls are  networked     RAPID Environment Control Installation Guide Ver99C    WHEN THIS CONTROL IS USED IN A LIFE SUPPORT HEATING AND  VENTILATION SYSTEM WHERE FAILURE COULD RESULT IN LOSS OR    INJURY  THE USER MUST INSTALL A FUNCTIONING ALARM SYSTEM AND  ADEQUATE BACK UP  OR ACCEPT THE RISK OF LOSS OR INJURY        LiMITED WARRANTY  DEL AIR SYSTEMS LTD  warrants to the original purchaser  that any device
4.   amp  12V Power  Supply    The network and 12V supply are  connected to TB1 of the Curtain  Module  The connections are in the same  order as the 4 Amp module  Refer back  to Section 4 1 The Network  amp  12V  Power supply for details     Section 2 5 The Module Network shows  the terminal locations of the network  and power supply on the RAPID  Control     Note   The connections on the AC Curtain  Module for network and 12V power    supply wires are identical to the 4 Amp  Module        6 2 AC Power and Load Output    The RAPID AC Curtain Module is  designed to switch the AC input to  operate a motor  actuator  in forward or  reverse motion  The module can be set to  operate Curtain 1  2  3 or 4  This  selection is made using the DIP switch  settings described in Section 9 Module  Addressing     Figure 26 shows the internal switching  part of the module  Using TB3  line 1  enters the module on terminal 1 and the  neutral is wired directly to the motor   The    switched    lines are terminals 2  and 3  Terminal 2 is activated for the    RAPID Environment Control    OPEN command and terminal 3 is  activated for the CLOSE command                    Neutral  AC Power Input Load  Figure 26    24    Installation Guide Ver99C    IMPORTANT   Network wires must be in separate  conduit than high voltage lines and must    be at least 16  from parallel running  high voltage lines  If network wires cross  high voltage wires they must cross at  90          6 3 Installation Check    When t
5.  4 and 3  as long as both legs  are connected     NOTE   Stranded wire is recommended since it  is much more flexible than solid wire   Solid wire may damage the terminal  block     IMPORTANT    Do NOT use the Multi modules variable  channels to switch relays  The leakage  current of the module may keep the coil  energized even when the module turns  off        NOTE    You can not measure the voltage of the  output of the variable channels if there  is no load attached  When there is no    load  the output will show whatever the  input voltage is  so readings will not  accurately show the state of the module        3 5 The Relay Output Channels    terminal block  The power enters on  terminal 2  The    switched    line is  terminal 1  This channel is simply a  relay that switches power just like a  light switch  The Line 2 Netural wire  does not get connected to the module    A module is wired to a load or device as  shown in Figure 16     RAPID Environment Control       Internal to Module   1 a  aa          1 2              L    42999998 i            AC Power  Load Ny Input    Figure 16                3 6 The Alarm Contact       The Multi Device Module is equipped  with one normally open alarm contact   This contact closes when the module is  in a state of alarm  There are two  conditions that cause an alarm  the first  is loss of power and the second is loss  of communication for a period of five  minutes  The alarm indicator on the  front panel shows the alarm condition   
6.  DC output to the actuator is  from terminals 1 and 2 of terminal  block TB4    e The module uses a potentiometer  connected to the actuator for  position sensing  Terminal 1 of TB2  supplies the 5VDC and terminal 3  provides the ground for the pot   Terminal 2 is the wiper of the pot  it  is this terminal that senses the  position of the actuator     7 3 Installation Setup and Test    When all connections to the module are  complete  the 12VDC power and AC  power may be applied  When it has  been powered  pressing the button  labeled    O     open  should light DS2  and open the inlets  pressing the    C     button should light DS1 and close the  inlets  If the inlets respond backwards  the wires on terminals 1 and 2 of TB4  can be reversed     When the module has been tested to run  properly  it then needs to be set up  The  module needs to know the Open Limit  and Closed Limit  To set the Open Limit  press the    O    button until the inlets are  fully opened  when they are open press    26    Installation Guide Ver99C    the    OL     Open Limit  button  When  the    OL    button is pressed DS4 lights  to indicate that the setting was saved   The Closed Limit is set the same way   by pressing the    C    button until the  inlets are closed and then pressing the     CL     Closed Limit  button  When the     CL    button is pressed DS3 lights to  indicate that the setting was saved     e DS5 is an indicator that the network  wires are operational  The indicator  is off when
7.  Each channel is  capable of controlling more than one  device as long as the maximum load is  not exceeded  The two variable channels  are capable of supplying 5 amps each at  either 120 or 240V AC  The three relay       The front panel of the module is set up to  show when each of the five devices are  being powered  when the module is in  alarm and whether the module is being  controlled automatically or manually  see  Figure 11     The top right indicator on the front panel  is the alarm indicator  When it is green  the module is running properly  when it is    Installation Guide Ver99C    Multi Device    Module    Alarm Indicator      Gi  0K    O    Manual Operation    3  o  Output 3 Indicator   4  o gt  Output 4 Indicator  5  o gt  Output 5 Indicator    120 240 V  50 60 Hz       12    channels are capable of supplying 10  amps each at either 120 or 240V AC     The Multi Device Module is most useful  when all of the power cables are  connected to each device from a single  point  When the power cables are  connected to multiple devices that are  not controlled identically then  individual 4 Amp modules are a better  choice for the control of the devices  since these can be mounted right at the  device     3 1 The Multi Device Modules Features    red the module is not communicating with  the RAPID Control    Under the alarm indicator is the Manual  Mode indicator  When the indicator is off   the module is being controlled by the  RAPID control  When the indicator is on  t
8.  The Power input may be 120 208 240  VAC   50 60 Hz  Figure 19 shows the  internal switching of the module  The  power enters on terminal H  The     switched    line is terminal E  The direct   common  line is connected to terminals  F and G  The direct line must be  connected to the module so that it can  make the necessary measurement for  speed control and On Off commands     A module is wired to a load or device as  shown in Figure 19      Internal to Module   AN                         E F  G H    m m m m    Load AC Power Input    Figure 19                      Installation Guide Ver99C    MODULE 1 MODULE 2       Module Network  12 V Power Supply  Module Network  12 V Power Supply                                                       I    NU NE  ENNE NENN  an y   A  e   3  A  A A  gt  gt   a Ad  me  Figure 18    19     gt    4 2 AC Power and Load Output    NOTE    Each module must have the AC  connected to terminals G and H  For  120V  the Line is connected to terminal  H and the Neutral to terminal G  For  240V  either leg can be connected to  terminals G and H  as long as both legs  are connected     IMPORTANT    When using the 4ADM to operate a  relay  you must cut the leg of the  capacitor on the 4ADM as shown in  Figure 20  Use relays with 120VAC  coils such as the Omron G4L series  relay        Partial Back View of 4 amp Module       USE WIRES SUITABLE FOR AT LEAST 90  C  ATTENTION  EMPLOYER DES FILS POUR AU MOINS 90 C    LOR                Cut lead of 2nd componen
9.  no signal is present and  flashes when signals are present     NOTE    The control should be in Monitor  program while doing any manual  movement of the actuator from the  module itself     IMPORTANT   When pressing the OPEN and CLOSE    buttons on the module  the only limit of  movement is any limit on the actuator  itself  Remember that while pressing  these buttons it is up to the user to judge  how long to continue movement  damage    to the inlet system may occur if  movement continues after the inlets have  reached their limits        RAPID Environment Control Installation Guide Ver99C    8 Output Device Module   Some equipment is controlled by receiving a signal from a controller  0 10VDC and 4   20mA are two common signals which equipment responds to  The Output Device Module  is designed to supply this type of signal    The Output Device Module is able to be set to any of the addresses that the 4 Amp device  module can be set to  see Table 2   Instead of supplying an AC voltage output which  directly drives loads the Output Device Module supplies a DC voltage proportionally to the  range that it is set to supply     8 1 The Network  amp  12V Power supply    The connections at the Output Device Module for network and 12V power supply wires  are identical to the 4 Amp Module     Refer back to Section 4 1 The Network  amp  12V Power supply for details     8 2 The Load Output    The module is able to supply only a small amount of current since it is not meant to power  
10.  to measure  temperature in the Zone Area     the    
11.  which  proves to be defective under normal use within two years from date of original purchase   will be repaired or replaced without charge     TERMS AND CONDITIONS  1  The warranty on this document does not apply    a  To any product subjected to misuse  negligence  abuse  defective or  improper wiring  improper installation  or any unit which has had the  serial number damaged or obliterated    b  To damage as a result of flood  fire  lightning  or any Acts of God    2  Parts replaced or repaired under this warranty are warranted only through the  remainder of the original warranty    3  This warranty does not cover cost of shipping defective or repaired or replaced  parts to or from original customer     4  DEL AIR Systems Ltd  reserves the right to make changes and improvements to its  product at any time with the express understanding that such changes and  improvements do not impose any obligation to install such changes and  improvements on products previously sold     Except to the extent prohibited by applicable law  no other  warranty  whether expressed or implied  including the warranties of  merchantability and fitness for a particular purpose  shall apply to  this product  Any and all implied warranties are excluded  DEL AIR  Systems Ltd  shall not be liable for consequential damages sustained  in connection with the said unit  DEL AIR Systems Ltd  neither  assumes nor authorizes any representative or other person to  assume for it any obligation or liability o
12. 25A relay is not supplied by DEL AIR   Use Omron  G7L 2A BUB J CB AC120 or WW Grainger  2XC20    To 4 NW10K Fan 31                                                                                                                                                                                              M L1  E L2  DRAWING F DRAWING TITLE   B DELAIR W 10 17 03 Wiring Schematic  E aaa CUSTOMER  E S T E M s    DATE SCALE      DESIGNIDRAWN BY  Jason  SOLD BY   10 17 01 N T S  G W D S   DEL AIR Systems Ltd                Figure 3    NOTE   All wire used with the RAPID Control must be rated minimum 300V and be wired in  accordance with CEC NEC class 1 methods     IMPORTANT    When any wiring is being done at the RAPID Control all power to the control must be off  to insure the protection of the installer and the protection of the electronics  All power  includes the power that runs the control  TB1   and any power that may be run to the  alarm contacts  terminals 15  16  17 and 18      Figure 4 shows all the terminals on the RAPID Control that are used for installation   TB1 is the power input for the control  all other connections to the control  described in  Sections 2 2 PC Network to 2 5 The Module Network  are connected to the terminals on  J7        DELA    RAPID Environment Control Installation Guide Ver99C       AC Input  PC Net  12V  Network 1  12V supply  Network 2  Alarm 1  Alarm 2  Sensor   Common     z  gt   i             Digital Input 1  Digital Input 2  Zone1 Sensor1
13. 40 VAC 50 60Hz   DC Power Input 10 16VDC   Environment 0 50  C  32 122  F  non condensing   Network Rating 4 4Amp Modules   Rating  Output  10A DC   Module Network RS 485   Output Device Module Description   Type DC output   DC Power Input 10 16VDC   Environment 0 50  C  32 122  F  non condensing   Rating  Output  20mA DC   Network Rating 2 4Amp Modules   Module Network RS 485    32    RAPID Environment Control    Installation Guide Ver99C    Appendix C    TROUBLESHOOTING GUIDE    No power to control   DS1 not lit     Calendar  clock incorrect  after power loss to  control     Displays incorrect   erratic temperature     Alarm doesn   t activate     Module does not respond   device or load does not    respond to RAPID  Control     6     Breaker  Fuse    Voltage Selector Switch in correct position     Remove paper tab under battery   Check battery on control   Verify J6 has jumper on pins 2 and 3    Check that sensors are enabled properly or are disabled if no  sensor is connected    Check sensor wiring at the control terminals  Make sure the  polarity is correct and wires are in proper terminals    Make sure the control and cable shielding are grounded    Check calibration  Re calibrate if necessary     Replace sensor     Check the alarm band  Re adjust if necessary   Run Alarm Test  Listen for clicking action on the alarm relay   Inspect wiring from control terminals to the alarm system     Test alarm device without using the RAPID Control     Put the control in TEST and tes
14. 9C    The codes can be changed at any time  powered or not     The switch up is ON    The switch down is OFF  Figure 29       10 Testing The Operation Of The Control    After all devices have been wired and  are ready to be run  they can be tested  from the RAPID without having to  program any of the setup into it     First the control has to be put in  MONITOR mode so it does not try to  control the devices  This is  accomplished by pressing the VENT  button   4   then selecting which zone is  to be tested using the up down arrows  and pressing OK     29    After selecting the zone  use the  up down arrows to select MONITOR  and press OK  When it says PROGRAM  RUNNING press OK to finish    To actually test the devices  press the  TEST button   7   select the zone and  then the device to test  See the User  Manual for more information on how to  run the tests on the modules     RAPID Environment Control    Installation Guide Ver99C    Appendix A    Wiring Installation Requirements    Control    Power Input  Wire type  Connections    PC Network  Wire Type    Connections  Maximum Length  Max  Controls    Module Network and 12V Supply  Wire Type    Connections  Maximum Length  Max  Modules   Network    Alarm  Auto Dialer   Wire Type  Polarity  Maximum Length    Sensor  Wire Type    Polarity  Maximum Length    16 AWG stranded  minimum  300V minimum rating  TB1 terminals 1 2 and 3  See Section 2 1 Power Input     20 AWG stranded  shielded  twisted pair  300V minimum  rating   J7 t
15. Network wires  cross any high voltage wires they must  cross at 90          The RAPID Control has two normally open contacts  terminals 15  16 and terminals 17   18  which may be used to control a central auto dialer or local siren  When the RAPID  Control is properly powered  the contacts on the relay are open  with no alarms   These  contacts will remain open until an alarm occurs  Alarms include  High Temp  Low Temp     Sensor Failure and Power Failure     RAPID Environment Control Installation Guide Ver99C    Connecting to an auto dialer     Autodialer Control 1 Control 2             aq  15 16 15 16    From autodialer To Control To next control                                        Figure 7    See Figure 4 for the terminal positions     e The auto dialer should not be      connected until all controls have  been connected    e Refer to the installation guide that  was included with your autodialer  for more information                          Connecting to a local siren        Either pair of alarm terminals may be  used to power any device that does not  exceed 1 0 Amp  120VAC or 2 0 Amps   External Power Supply not included      25VDC  The device must be powered     by an external supply  Figure 8       2 4 Sensors                Each standalone control must have one ambient sensor and at least one room sensor  per zone  The ambient sensor must be installed on each control unless the PC Net is  connected  If the PC Net is connected  only one control needs to have an am
16. OTE can be installed so  that you dial into the network with a remote computer    The RAPID Control uses an RS 485 twisted pair network to connect all controls and an  optional computer together  The connection is made using a daisy chain configuration   The Daisy Chain is shown below     RAPID Environment Control    Computer    RAPID Control 1                1  E                         M    Installation Guide Ver99C    RAPID Control 2                                     From Computer    To Control    To Next Control       Figure 6    IMPORTANT    The network connection is polarity  sensitive  Ensure that all wiring is  consistent between all devices     HINT    The PC Network wires and the Alarm  System wires can be run in a single 2  pair twisted pair cable since both these  pair usually run to all the controls and  then back to a central office where the  computer and alarm are located     Lo  2 3 Alarm System    What Is A Daisy Chain Configuration     Like a chain  the network is linked so  that there are only two ends  This is a  requirement for the communications  network  It is not permissible to split the  connection at one control and go to  multiple controls  as this would create  more than two ends in the chain  As  well  the chain is not looped together  it  must be installed such that there are two  ends        IMPORTANT   Network wires must be in separate  conduit from high voltage lines and must    be at least 16  from parallel running  high voltage lines  If 
17. When the indicator is green there is no  alarm  When the indicator is red then  the module is in alarm and the contact  will be closed        The Multi Device Module has two  modes of operation  Manual and  Automatic  The mode is chosen using  Switch 6  Switch 6 is the toggle switch  on the top left of the Multi Device  Module board  see Figure 12   This  switch can be changed at any time   powered or not    When the switch is flipped to the left   the control is in automatic mode  In auto  mode  the module responds to  commands from the RAPID control  The  buttons on the front panel will not  operate then the module is in auto mode  and is being controlled by the RAPID  control    When the switch if flipped to the right   the control is in manual mode  When the  control is in manual  the manual mode  indicator on the front panel is lit  In    16    Installation Guide Ver99C    The alarm contact is meant to be used in  either of two of the following ways  not  both    1  Connect the alarm contact to the  RAPID control s alarm  Doing this will  activate the alarm system that is  connected to the RAPID control as soon  as the module recognizes an alarm    2  Wire the alarm contact to turn on a  piece of equipment when the module  goes into alarm  It may be set up so that  the minimum ventilation will  automatically turn on if the module  fails     3 7 Automatic and Manual Operation    manual mode the module will not  respond to commands from the RAPID  control  instead you can 
18. asure the  temperature of the air being used to cool  the zones  The outside air temperature     Area  An area within a zone  such as Creep  Area    Auto Dialer   A device that dials a series of phone  numbers and plays a recorded message  to inform when an alarm has occurred     Creep Area  An area in a zone  usually at floor level  where young pigs are located     Creep Sensor  A sensor used to measure  temperature in the Creep Area     the    Module Network   The 4 wires  network and 12V supply   that run to the modules connected to a  RAPID Control  There are 2 Module  Networks available per control     Normally Open Contact   A switch that is open when no alarm  condition exists and close when an  alarm occurs     PC   An IBM compatible computer system  powered by an Intel Pentium 100 or  greater and running Windows 9x or  Windows Millenium     35    PC Net   A two wire network that connects all  the controls and a PC  if installed   together to allow them to communicate  with each other     Room Sensor  Either a Zone temperature sensor or  Creep temperature sensor     Sensor  A device used to measure temperature     Terminal  A connection on a module or control  where wires are connected to     Terminal Block  A block made up of a number of  terminals     Zone  A single room that is to be controlled by  the RAPID    Zone Area   An area in a zone encompassing the  majority or all of the room  excluding the  floor area if a Creep Area exists     Zone Sensor  A sensor used
19. bient sensor  installed  The control that has the ambient sensor installed and enabled will transmit the  ambient temperature to the rest of the controls over the PC Net        RAPID Environment Control    RED BLACK                                N   E Ib  N  B  N  eo  m  o                Lititt  IILI  biiiit  JIJIINI              e                e         e             e         e                  e                  a a a                  cot       TERET  Qu  LI  r4             Ambient  Sensor 1  Sensor 2  Sensor 1  Sensor 2    N  o  3  o  N    Zone 1  Figure 9    There are three common terminals on the  sensor block  19 to 21   These are the  positive terminals of the sensor   indicated by a red  or white  wire  The  positive wires may be tied together and  installed in any of the three positive  terminals  The negative wire on the  sensors  black wire  connects to the  terminal labeled for that particular  location    e g  The creep sensor for Zone 1 has its  black wire connect to terminal 24     The drain wire  which is connected to  the cable shield  should be connected to  the ground wire at the RAPID Control     MIT   aad    The RAPID Control uses distributed     SMART    modules to control both  Variable Speed and On Off outputs   The RAPID Control communicates with  the modules using a network similar to  the PC Net    In addition to the network  the RAPID  Control also supplies the DC voltage for    2 5 The Module Network    Installation Guide Ver99C    Sensor Opti
20. e Inlet Module 25  7 1 The Network  amp  12V Power Supply 25  7 2 AC Power and Actuator Connections 25  7 3 Installation Setup and Test 26  8 Output Device Module 27  8 1 The Network  amp  12V Power supply 27  8 2 The Load Output 27  9 Module Addressing 28  10 Testing The Operation Of The Control 29  Appendix A 30  Appendix B 31  Appendix C 33  Appendix D 34  Appendix E 35       RAPID Environment Control Installation Guide Ver99C    1 Pre Installation Check                                                                                                             Figure 2   RAPID Control Circuit Board    Figure 2   RAPID Control Circuit Board displays the features on the control circuit board  that are important to the installer  They include     1     2     Main Power Fuse   Replacement  3AG 2 10 Amp slow blow  250V    Voltage Selector Switch   See Section 2 1 Power Input    PC Network Fuses   Replacement  2AG 1 8 Amp 250V   Module 12V Ground Fuses   Replacement  2AG 1 5 Amp 250V   Battery   The RAPID Control uses a back up battery to maintain time  date  and  logs when a power failure occurs  The RAPID Control is shipped with a piece of  paper under the battery clip so it will not discharge in shipping  Remove the paper  after the RAPID is installed to enable the battery     DS1   This LED will light when the RAPID Control is properly powered  If the LED  is off  no power is present     RESET Switch   This switch  S2  is used to reset the control   Please refer to the troub
21. e is a separate terminal  block  TB2  for AC power to be  connected that runs the electronics on  the board  The power can be split off  from either of the variable channels or be  supplied from a separate breaker  There  must be a ground wire run to the  module  The AC input is to supply only  the power needed to run the electronics  on the board and it not used for any of  the output channels    The AC power terminal block  TB2  is  located to the right of the Network 12V  terminal block The connections for the  AC are set up identically to the RAPID    3 3 The AC Power Supply    14    Installation Guide Ver99C    MODULE1 MODULE 2       Module Network  12 V Power Supply  Module Network  12 V Power Supply                                                       CIE Jee IL   1 pm A f  e  2    A ee  3   Bee  4  p  Figure 13    Since it is self powered it is not  necessary to run the 12V wires to the  module although generally it is easier to  run the wires to it and then carry on to  the next modules that do need the 12V  wires    In the case of surges on the  communication lines the module is  protected by a surge suppression circuit   In the event of an extreme surge the  communication lines are also protected  with fuses     Control s AC input  Figure 14 shows the  connections                                1 2 3  TB2 E C1 E  Li L2      N  Figure 14    Before applying power to the Multi  module ensure that the voltage selector  switch is in the proper position for the  power t
22. ejele ejeje h TB3 TB4 rar TBS TB6 TB7 TB8  TB2       L1 L2 Gnd Load Line Load Line  Figure 12    IMPORTANT   When any wiring is being done at the Multi Device Module all power must be off to  insure the protection of the installer and the protection of the electronics  All power    includes the power that runs the module  TB2   the power that is run to each of the  channels  including alarm  and the power to the RAPID Control        On the bottom left of the Multi Device Module board is the network and 12V supply  terminals  TB1   The network and 12V wires from the RAPID Control are connected to  these terminals  Section 2 5 The Module Network shows the terminal locations of the  network and power supply on the RAPID Control  The connection at the module is  shown in Figure 13     13    RAPID Environment Control    IMPORTANT    Network and 12V terminals are  reversed on the modules compared  to the placement on the RAPID  control     From Control  See Section 2 5 The  Module Network    NOTE    Network wires must be in conduit  separate from high voltage lines and  must be at least 16  from parallel  running high voltage lines  If network  wires cross high voltage wires they must  cross at 90          The Multi module is the only module  that is self powered and is able to run  without the 12V wires being attached        Unlike the other RAPID modules  the  electronics on the Multi Device Module  is powered by 120 240VAC instead of  the 12V supply from the RAPID  Control  Ther
23. er   the wiring has an incorrect  polarity  Switch the two wires to  correct the polarity  Check meter  reading     e If there is no voltage present at the  device  there is either a blown fuse in  the control or there is a problem in  the wiring     34    Testing the Module Network     1  Use the same setting on the meter as  for the power supply test as above    2  Connect the black lead to terminal A  on the module    3  Connect the red lead to terminal B  on the module     With the control power on  the meter  should read between  3 0 to  4 5VDC   Every five seconds the reading will  oscillate very quickly to a negative  voltage and back for a few seconds after  which it will again settle at the 3 to  4 5VDC  This reading indicates that the  module network wiring is correct and  functioning     e If the reading is negative  indicated  on meter   the wiring has an incorrect  polarity  Switch the two wires to  correct the polarity  Check meter  reading     e If there is no reading on the meter   for example   0 0 VDC  there is  either a broken wire between the  module and the control  or there is a  short circuit  Check wiring  test  2      e If all tests above pass  and  modules s  fail to respond  replace  the module  If replacing the  module does not fix the problem    consult your dealer     RAPID Environment Control    Installation Guide Ver99C    E E    Address  A combination of switch settings to  identify the load of a module     Ambient Sensor   A sensor used to me
24. erminals 1 and 2  See Section 2 2 PC Network    1200 Meters  3900 ft     31    20 AWG stranded  shielded  twisted pair  300V minimum  rating   Use wire suitable for at least 90  C   J7 terminals 3 10  See Section 2 5 The Module Network   107 Meters  350 ft     32 4Amp Modules  See each module   s specifications for  the network under Network Rating     20 AWG stranded  twisted pair  300V minimum rating  J7 terminals 15 to 18  See Section 2 3 Alarm System   N A    20 AWG stranded  shielded  twisted pair  300V minimum  rating   J7 19 to 26  See Section 2 4 Sensors    107 Meters  350 ft      Device Modules  Multi  4A  15A  Curtain  Cable Inlet  Output     Load  Power  VAC Output   Wire Type    Polarity    16 AWG stranded  minimum   300V minimum rating  Use wire suitable for at least 90  C  See Sections 3 4  3 5  4 2  5 2  6 2  7 2 and 8 2       30    RAPID Environment Control Installation Guide Ver99C    Appendix B  RAPID Specification Sheet    Control Description   Power Input 120  240 VAC  108 127 212 254    0 2 0 1A 50 60 Hz   Environment 0 50  C  32 122  F  non condensing   Module Power Output 12 VDC unregulated  9 12 VDC   14 8 VDC    1 8 Amp   Digital Inputs  2  5 VDC   Control Network RS 485   Alarm Outputs  2  Relay Contact  Normally Open  1 0 Amp   120VAC  2 0 Amp   25VDC    Temperature Sensor Inputs  5  AD590  resolution    0 1  C   Main Power Fuse 3AG 2 10 Amp slow blow 250V   PCNET Fuses 2AG 1 8 Amp 250V   12V Ground Fuses 2AG 1 5 Amp 250V    Multi Device Module Desc
25. for  locations     Figure 10 shows how to connect module                                     itself  See Section 9 Module network 1 and its 12V supply at the  Addressing   RAPID Control   2 T 2 N  a x a x  o o  D E D E    o x Q  o z o z  a 2 o 2  a  2    5   gt  E  gt  E                          4  3 4 5 6  7 8   9 10  T eo  o     See Section 3 2  4 1  5 1  6 1 7 1 and 8 1  Figure 10     2 6 Terminating the shielding  d    aaa    All the wire used for the low voltage  wiring   12V  network  sensors  digital  inputs  PCNET and alarm  should be  using shielded cable  see Appendix A    This section describes how to terminate  the shielding properly    The purpose of the shielding around the  wires inside the cable is to protect the  wires from induced voltage spikes   These spikes can range from small noise    10    caused by AC wires that may be around  the cable to extreme spikes caused by  lightning    Shielded cable will have a bare wire  included with the other wires in the  cable  This wire is called the drain wire   The drain wire is connected to the  shielding inside the cable    To protect the wires from spikes the  drain wire must be tied to ground  The    RAPID Environment Control    drain wire should be connected directly  to the ground wire  not using any of the  RAPID Control terminals to make the  connection  This should be done at one  point only  never have the drain wire  connected to ground at more than one  point per cable  For sensors that means  connecting 
26. hat is connected to the AC  input     RAPID Environment Control       The variable channels are labeled as  CH1 and CH2  These channels can be  configured to run any of the devices  listed in Table 2 of Section 9 Module  Addressing     The Power input may be 120 208 240  VAC   50 60 Hz  Figure 15 shows the  internal switching of the module  Each  channel is made up of a four terminal  block  The power enters on terminal 4   The  switched  line to the motor is  terminal 1  The direct  common  line is  connected to terminals 2 and 3  The  direct line must be connected to the  module so that it can make the  necessary measurement for speed  control and On Off commands     A module is wired to a load or device as  shown in Figure 15        Internal to Module   l    EA                                a     3         X i  i  EE I                      Load C    VW  AC Power Input       Figure 15       The relay channels are labeled as CH3   CH4 and CH5  These channels can be  configured to run any of the devices  listed in Table 2 of Section 9 Module  Addressing     The Power input may be 120 208 240  VAC   50 60 Hz  Figure 16 shows the  internal switching of the module  Each  channel is made up of a two screw    15    Installation Guide Ver99C    3 4 The Variable Output Channels    NOTE     Each module must have the AC    connected to terminals 3 and 4  For  120V  the Line is connected to terminal  4 and the Neutral to terminal 3  For  240V  either leg can be connected to  terminals
27. he module has the 12VDC power  supplied as well as the AC power  the  control can be manually operated by  pressing the buttons labeled    O     open    and    C     close   When    O    is pressed  DS2 should light and the curtain open   When  C  is pressed DS1 should light  and the curtain should close  If the  actuator runs backwards  closes when   O  is pressed  then wires on terminals  2 and 3 have to be reversed to correct  the problem     NOTE   Pressing the  O  or  C  buttons will    override any signals sent by the control  at the time        RAPID Environment Control    Installation Guide Ver99C    7 RAPID DC Cable Inlet Module    The RAPID Control uses a special  module for controlling the inlets used in  mechanical ventilation systems  The DC  Cable Control Inlet Module is enclosed  in a box that is similar to the RAPID  Control itself    When the cover is opened  the board sits  in the top left corner of the enclosure   Figure 27 shows the layout of the DC  Cable Module           Fuse                         DS2 d  d       Jg  2    DS4    DS3       q  od  2             DIP  Switches           00000                     Open    Close                      OL CL                      TB2   TBI TB4     TB3                            Figure 27    Since this is still a module  it has the  basic configuration and advantages of  the 4 Amp Module described in Section  4 RAPID 4 Amp Module  In addition to  those advantages  having modules allow  for control of multiple actua
28. hen the module is in manual mode and  can be controlled by the buttons on the  front panel     RAPID Environment Control    Above buttons 1 and 2 and to the right of  buttons 3  4 and 5 are channel output  indicators  These indicators show whether  the module is supplying power to the  devices on that channel or not  Since  channels 1 and 2 are variable  the indicator  brightens and dims according to the  amount of power being supplied by the  module for that channel  The indicators    Installation Guide Ver99C    for channels 3  4 and 5 are either on or off  depending on the state of that channel   The Multi device module board inside has  two more indicators  see Figure 12   On  the top left area of the board is DS2  DS2  will flash when it sees communication on  the network wires  DS5 1s located below  DS2  DS5 is on when the Multi Device  Module is being properly powered     3 2 The Network  amp  12V Power supply       Multi Device Module CH1    DEL AIR SYSTEMS LTD  H  JP4    AUTO   S   MAN  LS   1  swe          CH2 CH3 CH4 CHS       JP3          2AG T  1 8A 1                                                    DS2             F1 T                                                                                                                                                                                                                                           3AG  1 2A F3  250V  xi _ CH1 CH2 CH3  CH4  CH5  ALARM  m DELIV AC input     ojojo elejei  Teje  leje  el  ajo  el
29. increase and  decrease the variable channels and turn  on and off the relay channels using the  front panel    When the switch is flipped from Auto to  Manual  the module continues to run the  equipment as it was before the switch  was flipped    To vary the 2 variable channels you  press either the up arrow to increase or  the down arrow to decrease the output   Pressing the arrow and releasing  increases or decreases by a single step   Pressing and holding the arrow button  results in the speed continuing to  increase or decrease  It takes about four  seconds to go from 0  to 100  when  holding down the up arrow button  As    RAPID Environment Control    you increase and decrease the variable  channels  the indicator for that channel  will brighten and dim accordingly    To turn the 3 relay channels off and on  press the number button for that       Each of the channels is configured using  the blocks of switches in the top right  side of the circuit board  Each of the  switch blocks is labeled for which  channel it configures  Channel 1 is on the       When the Multi Device Module is  powered  DS5 on the circuit board  should light up  If it does not light up  check the breaker  the voltage selector  switch and the main fuse  F3   If all of  these are OK then measure the voltage  at the AC input to make sure it is OK    If the network wires are connected and  the RAPID Control running  DS2 on the  circuit board should be flashing   Generally the light will be off for two  
30. leshooting guide for further information     RAPID Environment Control Installation Guide Ver99C    2 RAPID Control Wiring Instructions    Figure 3 is a wiring diagram of a typical barn  To make the drawing as clear as possible  only the modules for one zone are shown  If the second room were identical there would  be the same modules connected to terminals 7  8  9 and 10                                                                                                                                                                          TE  s    NOTE   H 53  Please read installation guide 3 zest bE Partial Back View of 4 amp Module  for mounting instructions and ri FENN Os  wire size recommendations  3 EEEE ke  3 sb Hii  g sers sB ATTENTION    EMPLOYER DES PLS POUR AMONG 90    RAPID Control DE  NOTE              Select only one controller  to use ambient sensor and Cut lead of 2nd component   C1    connect pc net terminals so that it no longer makes contact  on all controls as shown     Only on 4A modules using a 25A relay    Nu TB   oloo Jr in section 2 4 of Installation Guide                                                                                                                                          g Cable                                                                                                                                                                                                                                                                    
31. ng   When mounted vertically  the module  will be less likely to be affected by  moisture and contaminants present in  the barn        RAPID Environment Control Installation Guide Ver99C    5 RAPID 15 Amp Module    Electrically  the 15 Amp module  shown  in Figure 22  is identical to the 4 Amp  module described in Section 4 RAPID 4    Amp Module  Larger components and an      external heat sink allow this module to    power loads at up to 15 Amps either    variably or On Off   Figure 22    IMPORTANT   When any wiring is being done at the 15 Amp Module all power must be off to insure the    protection of the installer and the protection of the electronics  All power would include  the power that the module is switching  L1 and L2 Neutral  and the power to the  RAPID Control        5 1 The Network  amp  12V Power supply    The connections at the 15 Amp Module for network and 12V power supply wires are  identical to the 4 Amp Module     Refer back to Section 4 1 The Network  amp  12V Power supply for details     5 2 AC Power and Load Output    The RAPID 15 Amp Module may be The line power is connected to the   used as either a Variable Speed or BLACK wire  The BLUE wire is the   On Otf Module   switched  line  Line 2 or Neutral is   This selection is made using the DIP connected to the WHITE wire    switch settings described in Section 9   Module Addressing  A module is wired to a load or device as  follows     The Power input may be 120 208 240  VAC   50 60 Hz    Figure 23 show
32. ons   Sensor 1 must always read the Zone   room  temperature    Sensor 2 can be configured as the Creep  Sensor or a second Zone Sensor  When  used as a second Zone Sensor  its reading  is averaged with Sensor 1 to give the  average Zone  room  temperature    See User Manual for more information        NOTE   Sensor wires can be run in the same  conduit as the module network wires     IMPORTANT   Sensor wires must be in separate    conduit than high voltage lines and must  be at least 16  from parallel running  high voltage lines  When crossing high  voltage lines  sensor wires must cross at  90    Temperature readings may be  affected by electrical noise if this  precaution is not taken       the electronic part of the module   Therefore  the Daisy Chain will be made  using 2 pairs of wires     There are two module network outputs  on the control  Terminals 5 and 6 are  used for Module Network 1 and  terminals 9 and 10 are used for Module    RAPID Environment Control    Network 2  Related to the network is  the 12V power  terminals 3 and 4 are  used with Module Network 1 and  terminals 7 and 8 are used with Module  Network 2 to supply the 12V power   Neither network is zone specific  The  RAPID Control sends all commands to  all modules over both networks  The  Zone selection is made on the module    Installation Guide Ver99C    Networks 1 and 2 must not be tied  together  A separate Daisy Chain must  be run for each network if both are used   e the terminal    See Figure 4 
33. ription   Type 2   Variable voltage dimmer channels  3   Relay operated channels   AC Power Input 120  240 VAC  108 127 212 254    0 2 0 1A 50 60 Hz   Environment 0 50  C  32 122  F  non condensing   Variable Channel Output Rating   5 Amps per channel   Relay Channel Output Rating 10 Amps per channel   Module Network RS 485   Main Power Fuse 3AG 1 0 Amp 250V   Network Rating 1 4Amp module   Network Fuses 2AG 1 8 Amp 250V    4 Amp Module Description   Type Variable voltage dimmer   AC Power Input 120 208 240 VAC  104 127 187 220 208 254   50 60Hz   DC Power Input 10 16VDC   Environment 0 50  C  32 122  F  non condensing   Output Rating 4 Amp   Network Rating 1 4Amp Module   Module Network RS 485    15Amp Module Description   Type Variable voltage dimmer   AC Power Input 120 208 240 VAC  104 127 187 220 208 254   50 60Hz   DC Power Input 10 16VDC   Environment 0 50  C  32 122  F  non condensing   Output Rating 15A   Network Rating 1 4Amp Module    Module Network RS 485       31    RAPID Environment Control Installation Guide Ver99C    Cable Control Module Description       Type Relay operated   AC Power Input 120 208 240 VAC  104 127 187 220 208 254   50 60Hz   DC Power Input 10 16VDC   Environment 0 50  C  32 122  F  non condensing   Rating  Output  30VDC  1 6 A  2 8A peak    60 Hz  30VDC  1 5A  2 8A peak    50 Hz   Module Network RS 485   Network Rating 4 4Amp Modules   Fuse 3AG 4 0 Amp 250V   Curtain Control Module Description   Type Relay operated   AC Power Input 120 208 2
34. s the internal switching  of the module     21    RAPID Environment Control       Internal to Module             Blue White    Line 2    AC Power Input    Load    Figure 23    NOTE     Each module must have the AC    connected to the Black and White wires   For 120V  the Line is connected to Black    and the Neutral to White  For 240V   either leg can be connected to Black and  White  as long as both legs are  connected           Installation Guide Ver99C    NOTE    Network wires must be in separate  conduit than high voltage lines and must  be at least 16  from parallel running  high voltage lines  If network wires cross  high voltage wires they must cross at  90       NOTE    You can not measure the voltage of the  output of the 15 Amp Module if there is  no load attached  When there is no  load  the output will show whatever the  input voltage is  so readings will not  accurately show the state of the module     5 3 15 Amp Module Enclosure    The RAPID 15 Amp Module comes with  its own enclosure  It is shipped in a  modified Scepter brand FDC15 or  FDC20  The module can be replaced  without removing the entire enclosure  but the module will not fit into a  standard FDC box     Figure 24    22    The module slides in between the lid  mounting screws on the side of the  enclosure     IMPORTANT    Ensure that the enclosure is properly  sealed once the module is coded and  installed    Improper sealing of the enclosure may  lead to an electrical failure to the  module as a res
35. seconds and then will flash very quickly  for 3 seconds  If the light is doing the  reverse then the network wires are most    17    Installation Guide Ver99C    channel  When the channel is on the  indicator for the channel will be lit   when the channel is off the indicator will  go off as well     3 8 Configuring the Multi Device Module    far left and channel 5 is on the far right   These switches can be changed at any  time  when the board is powered or not   See Section 9 Module Addressing for  the addressing codes     3 9 Troubleshooting the Multi Device Module    likely reversed  If the indicator does not  light up at all then check fuses F1 and  F2    The module can also be tested without  having to be connected to the RAPID  Control or with the control off  With  power being supplied to the module   switch SW6 to the right  Manual Mode   and use the front panel to turn on and  off the channels    If the display does not respond  make  sure the ribbon cable from the front  panel is plugged into JP3 properly     RAPID Environment Control Installation Guide Ver99C    4 RAPID 4 Amp Module    Having modules designed this way  allows     e Modules to be located near the load  that it is operating  AC power does  not have to be brought back to the  control for each load that is       controlled   e Control of multiple devices on any  stage   e Greatly reduced electrical  management of the facility  The  Figure 17 module itself reads the phase    information from the AC inp
36. t from left   C1    so that it no longer makes contact     Only on 4A modules controling a relay      Figure 20    RAPID Environment Control    NOTE   Network wires must be in separate  conduit than high voltage lines and must    be at least 16  from parallel running  high voltage lines  If network wires cross  high voltage wires they must cross at  90      S     4 3 4 Amp Module Enclosure     lt a    Installation Guide Ver99C    NOTE    You can not measure the voltage of the  output of the 4 Amp Module if there is  no load attached  When there is no  load  the output will show whatever the  input voltage is  so readings will not  accurately show the state of the module        The RAPID 4 Amp Module does not come with its own enclosure  It has been designed  to fit in a standard single gang F Series Scepter brand box or equivalent     The enclosure chosen for the 4 Amp Module must be a CSA and UL approved  non metallic box with sizing of at least 4 1 4  X 3 1 2  X 2  with NEMA 4 rating               Figure 21    The module slides in between the lid  mounting screws on the side of the  enclosure     IMPORTANT    Ensure that the enclosure is properly  sealed once the module is coded and  wired    Improper sealing of the enclosure may  lead to an electrical failure at the  module as a result of moisture damage     IMPORTANT    The 4 Amp module enclosure should be  mounted so the module sits vertically   as in Figure 21  and not horizontally   Do not mount the module on the ceili
37. t the device in question    Check module address   Check AC power input to the module  using a test light  meter   Check polarity of signal and power supply wires  t   Check the load  by pass the module and power the load  directly     If all tests above pass  replace the module        t See SIGNAL TEST  Appendix D     33    RAPID Environment Control    Installation Guide Ver99C      i endix D    Paired Wire Test Instructions    Important     The following tests should be performed by a certified electrician  Consult       your dealer for further information     These tests are included to provide assistance for the electrician  They are helpful in  confirming that all wiring installation is correct     This test is performed to ensure that  signal is transmitted from the control to  the modules  If the module is not  responding to commands from the  control  it may be possible that the  wiring is faulty  To test the signals  a  digital or analog multimeter is required     Testing the 12VDC power supply     1  Using a digital voltage meter  select  the VDC position     If the meter does not have an auto   range feature  select the 20VDC  range     2  Connect the black lead to terminal C  on the module    3  Connect the red lead to terminal D  on the module     With the control power on  the meter  should read between 49 0 to  14 0  VDC  This reading indicates that the  power supply wiring is correct and  functioning properly     e If the reading is negative  indicated  on met
38. the drain wire to ground at  the control  For the module network   12V and digital inputs that means  connecting the drain wire to ground at  the control  For the entire length of cable  to be protected  the drain wire in the  cable coming into the module must be  connected to the drain wire in the cable  going out of the module     11    Installation Guide Ver99C    Connecting the drain wire for the  PCNET and alarm is somewhat  different  Since the drain wire is to be  connected to ground at one spot only   DO NOT connect the drain to ground at  each control Pick ONE location to  connect the drain to ground  this could  be at one control OR where the cable  goes to the alarm system OR where the  cable comes to the computer system    Ideally the ground that any electronics  are connected to should be an isolated  ground  a ground that is used  specifically for the electronic equipment   This is not necessary but can be decided  by the electrician doing the wiring as  well as the electrical code     RAPID Environment Control    3 RAPID Multi Device Module    RAPID    Environment Control    Variable Ouput 2 Indicator    Variable Ouput 1 Indicator    DELAIR    SY S T EM S    Figure 11    The Multi Device Module is the primary  means for controlling the devices that  make up the ventilation system  This  module has five separate outputs for  controlling devices  Two of the channels  are capable of supplying variable  voltage out  the remaining three channels  are relay operated 
39. the load  There are three different voltage ranges that the module can supply  0 10V  2 10V  and 3 7V  When a 4 20mA signal is required  use the 2 10V setting and a 500     resistor   To select the voltage range set the S1  DIP switches as show in Table 1    Table 1    0 10V    2 10V       27    RAPID Environment Control Installation Guide Ver99C    9 Module Addressing    Each module must be addressed to the device that it is controlling  This is necessary  because the RAPID Control sends all commands to all of the modules over the twisted  pair of wires     The codes that the Multi Device Module  4 Amp Module  15 Amp Module and Output  Module can be set to are shown in Table 2     Table 2    Device  OFF    OFF   OF     OFF _   OFF  O  OFF OFF  ON OFF  O  O  O  O    O  OFF OFF OFF  O   OFF   OFF _      OFF        ON    OFF  OFF  OFF  OFF  ON  N N  N    O  O  O    o    Stage 1 Tunnel Fan  Stage 2 Tunnel Fan O  O    The codes that the Cable and Curtain Modules can be set to are shown in Table 3   Table 3    Cable Control OFF     OFF          OFF N  N      T     Ti       Every module must be told what zone it is in  Table 4 shows how to address the zone  switch     Table 4    It is possible to set more than one module on the same code  If  for example  three Stage  1 fans are required in a zone  set all three modules to the same code  The RAPID Control  will communicate to and control all three modules simultaneously     28    RAPID Environment Control    Installation Guide Ver9
40. ther than such as it expressly  set for herein     All complaints should be directed first to the authorized distributor  who sold the product  Only if satisfaction is not obtained or the  name of the distributor is not known should DEL AIR Systems Ltd   be contacted directly at 1 800 667 1722    RAPID Environment Control    Table of Contents    Installation Guide Ver99C                                                                                                                                     1  Pre Installation Check 4  2 RAPID Control Wiring Instructions 5  2 1 Power Input 6  22 PC Network 6  2 3 Alarm System 7  2 4 Sensors 8  2 5 The Module Network 9  2 6 Terminating the shielding 10  3 RAPID Multi Device Module 12  3 1 The Multi Device Modules Features 12  3 2 The Network  amp  12V Power supply 13  3 3 The AC Power Supply 14  3 4 The Variable Output Channels 15  3 5 The Relay Output Channels 15  3 6 The Alarm Contact 16  3 7 Automatic and Manual Operation 16  3 8 Configuring the Multi Device Module 17  3 9 Troubleshooting the Multi Device Module 17  4 RAPID 4 Amp Module 18  4 1 The Network  amp  12V Power supply 18  4 2 AC Power and Load Output 19  4 3 4 Amp Module Enclosure 20  5 RAPID 15 Amp Module 21  5 1 The Network  amp  12V Power supply 21  5 2 AC Power and Load Output 21  5 3 15 Amp Module Enclosure 22  6 RAPID AC Curtain Control Module 23  6 1 The Network  amp  12V Power Supply 23  6 2 AC Power and Load Output 23  6 3 Installation Check 24  7 RAPID DC Cabl
41. tors on any  zone if a facility is large enough to need  more than one actuator per zone     IMPORTANT    When any wiring is being done at the  cable module all power must be off to  insure the protection of the installer and    the protection of the electronics  All  power would include the power that  runs the module  TB3  and the power to  the RAPID Control        25    7 1 The Network  amp  12V Power  Supply    The network and 12V supply are  connected to the module using TBI   Section 2 5 The Module Network shows  the locations of TB1 and the remaining  terminal blocks     The connections at the Cable Module   TB1  for network and 12V power  supply wires are identical to the 4 Amp  Module     Refer back to Section 4 1 The Network   amp  12V Power supply for details    7 2 AC Power and Actuator  Connections    The RAPID DC Cable Module is  designed to receive the AC input  it  converts this to a DC output that is able  to operate a motor  actuator  in forward  or reverse motion  The DIP switch  settings are described in Section 9  Module Addressing for the Inlet Control  Module     Figure 28 shows the connections for the  AC power and the Actuator                                OL CL                TB2 TB1 TB4  1234 1234                                            DC AC  Actuator  Potentiometer    Actuator In       Figure 28    RAPID Environment Control    Connection Description     e Line 1 and Neutral enter the module  on terminals 1 and 2 of terminal  block TB3    e The
42. ult of moisture damage        IMPORTANT   Install the enclosure as shown in Figure  24  If it is installed in another    orientation the heat sink may not have  enough airflow and could overheat       RAPID Environment Control    Installation Guide Ver99C    6 RAPID AC Curtain Control Module    The RAPID Control uses a special  module for controlling the curtains used  in the Natural Ventilation system  The  Curtain Module is enclosed in a box that  is similar to the RAPID Control itself   When the cover is opened  the board sits  in the top left corner of the enclosure   Figure 25 shows the layout of the AC  Curtain circuit board     e TB2 is not used when the module is  set for curtain applications        DS2    DS4 CURTAIN MODULE    DS3       nunnunnununnnnnu                      TB2 TB1 TB3                            Figure 25    Since this is still a module  it has the  basic configuration and advantages of  the 4 Amp Module described in Section  4 RAPID 4 Amp Module  In addition to  that  having curtain modules will allow  control of multiple curtains on any one  stage if a facility is large enough to need  multiple actuators for a stage of curtain     23       IMPORTANT    When any wiring is being done at the  curtain module all power must be off to  insure the protection of the installer and    the protection of the electronics  All  power would include the power that the  module is switching  L1 and  L2 Neutral  and the power to the  RAPID Control     6 1 The Network
43. ut to  provide variable speed control for  the load  The module   s power input  does not have to be on the same  phase as the control itself  Two or  more modules addressed to the    The 4 Amp Module consists of three  main parts     1  RAPID Module Network  amp  Power    Supply Input Terminals  suave sia      ge do not have to be on the  2  Module Addressing Switches   DIP same phase of power   Switches     3  AC Power Input and Load Control  Output Terminals     IMPORTANT   When any wiring is being done at the 4Amp Module all power must be off to insure the    protection of the installer and the protection of the electronics  All power would include  the power that the module is switching  L1 and L2 Neutral  and the power to the  RAPID Control        SL 4 1 The Network  amp  12V Power supply    The network and 12V terminal block is the terminal block on the left side of the module  as shown in Figure 17  Section 2 5 The Module Network shows the terminal locations of  the network and power supply on the RAPID Control  The connection at the module is  shown in Figure 18     18    RAPID Environment Control    IMPORTANT    Network and 12V terminals are  reversed on the modules compared  to the placement on the RAPID  control     From Control  See Section 2 5 The  Module Network       s      SS    The RAPID 4 Amp Module may be used  as either a Variable Speed or On Off  Module    This selection is made using the DIP  switch settings described in Section 9  Module Addressing    
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
1996-1998 MUSTANG COBRA  Manual de instrucciones Digibirds Casa 2 Digibirds ES  User's Manual - Security Camera Shop  Instructions et conseils    GI-2850 SI Inserter User`s manual    Copyright © All rights reserved. 
   Failed to retrieve file