Contents
1. The ways of coolant temperature adjustment Enter into setting interface the initializa tionis 0 Press lor lonce The current show value will be reduced or added for 2 units Ifthe screendisplay 4 units were higher please set 2 The ways of oil pressure battery voltage adjustment Enter into setting interface the initializationis 0 Press or lonce The current show value will be added or reduced for 2 units If the screen display 4 units were higher please set 2 Delay of Pre fuel Preheat Start the delay of Pre fuel Preheat before motor starting At the same time the Delay of Pre fuel Preheat relay became closed When delay was finished the relay was disconnect the motor start Default 5 Delay of ACCeleration DECeleration Start the delay of ACCeleration after the engine started successfully During this time the ACCeleration relay closed The Acceleration relay will disconnect when delay finished The engine start to work normally Default 20 When engine is normal or fail protection shut down all will start DECeleration delay time delay period DECeleration relay to have the output after the time delay had ended will the DECeleration relay will disconnect Delay of warm up It is between machine group ending successfully and running with load It will extend the time of providing power with load In the instance of no hurry up Page 4of 11 Mho it can make the dynamo
2. anything in the thirty second thesetting state will be exit and return to the measurement state and to normal display 00 coolant temperature upper limit 01 oil pressure lower limit 02 battery voltage lower limit 03 frequency rotation speed upper limit 04 trip frequency speed 05 Freewheel tooth number 06 coolant temperature adjust 07 oil pressure adjust 08 battery voltage adjust 09 delay of pre fuel 10 delay of ACCeleration DECeleration l 11 delay of warm up 12 delay of Energize To Stop ETS 13 delay of remote start 14 delay of retransform 15 delay of cool down 16 delay of Idle speed on starting 17 delay of idle speed on stopping 18 control parameter 1 19 control parameter 2 20 control parameter 3 Coolant temperature upper limit If the coolant temperature was selected the analog sensor to give alarm when coolant temperature exceeds this upper limit it will lead the engine protection to shut down Default 96 Oil pressure lower limit If oil pressure was selected to give alarm by the oil pressure sensor when oil pressure is lower than the lower limit it will lead the engine to shut down for protection Default 200 Battery voltage lower limit When the battery electric voltage is lower than lower limit voltage it will alarm but will not shut down the engine Defau
3. group reach to optimal work state and can availably reduce the abrasion of machine group Default 25 Delay of Energize To Stop ETS Only when the system was set to the state of shut down and stop fuel supply the delay of stop to provide fuel begin to work At this time the output of provide fuel is equivalent with the stopping of the machine While stopping the machine the relay of provide fuel is in the output state the delay of stop machine and fuel supply begin to work After above these is over and the oil pressure is low the relay of provide fuel stop output Default 30 Delay of remote start In the auto state of controller start to delay when the remote switch closed The engine start when delay finished Default 3 Delay of retransform Start delay of retransform when the engine work with onload and the the remote start switch was disconnected The engine will dis onload and empty onload to work when delay of retransform finished Default 5 Delay of cool down When the controller is in auto state and the remote start switch disconnect as well as the genset was load off The genset will work with empty onload The genset will be closed after the delay is over Default 20 Delay of Idle Speed in Starting Start to idle speed delay when the machine start succes sfully Start to ACCeleration when delay finished Default 10 Delay of Idle Speed in Stopping In the AUTO statement the idle speed delay will begin
4. 2 indicator lights they denote the state or alarm of controller and generator Five of them showed LED statement When Press key station willbe to changed display in 5 LED They will be displayed the different content and corresponding every light display the only content 1 RPM HZ Denote genset rotation rate or frequency concretely still basis that the speed measures way s from the speed sensor or frequency Unit RPM HZ 2 TEMP Denote the current engine coolant temperature Unit C 3 OIL P Denote the current engine oil pressure Unit kpa 4 BATT V Denote the current battery voltage Unit V _ 5 HOURS Denote current already working engine time Unit Hour There is five indicator light of statement LOADING REMOTE START AUTO RESET STOP The light of alarm If MINCO F2 controllers was set to the control ways of ACCeleration and DECeleration when they starting the ACCeleration delay or DECeleration delay begin to account at one time if account haven t examined but not to detect the ACC eleration limit or DECeleration limit input then the alarm light will be on but will not lead to shut down the machine for protection The light of fault when the engine appear to operation failure it will lead the MINCO F2 controller control engine shut down to protect the engine at the same time 5 high light LED denote the failure code The reason which led to shut down the machine for protecti on can be judge
5. 5 LED 6 press keys and 12 indicator lights The press keys control genset to start or stop and set working parameters the indicator lights indicate the state of controller and failure of genset 1 The control key instruction IRUNI When press key the above green light become always bright indicate controller is be placed in running directly start the generator manually and keep running AUTO When press this key the above yellow light become always bright indicate controller is be placed in automatic state the controller receive the remote start switch signal if this switch is close then delay to starte the generator Otherwise will delay to stop machine To realize the auto start control of gen set Remote start switch signal can be provided by the detect module of the normal supply or timer In order to realize an engine Page lof 11 Mico automation controlling staying RESET When press this key the above red light always bright indicate controller is be placed in STOP RESET state if at this time generator just in the running press this key once the engine will shut down normally press this key two times continuonsly the engine will stop immediately ra FE The key is used to change the LED display con tent and to change parameter setting under setup circumstances SET The key is used to enter into or exit parameter settings 2 Instruction of the indicator light The front panel of the controller has 1
6. At this time the Acceleration relay have output when the delay of idle speed start The Deceleration relay have output when the delay of idle speed stop Connect the Acceleration and Deceleration relay together then you can link the electronic speed adjusting machine 4 About the the frequency rotation speed upper limit and trip frequency rotation speed upper limit to know it denotes frequency or rotation speed will depends on the measurement of rotation speed If changing the measurement of rotation speed please bear in mind to change these two parameters accordingly and make it correspond to the measure ways of rotation speed 5 If the the measurement of rotation speed was gained from magnetic sensor the frequency rotation rate upper limit indicate that upper limit At this time the actual rotation speed upper limit is 10 times of setting value For example if rotation speed upper limit was set the value 165 of the rotation rate upper limit correspondly will be 1650 RPM IV The controller interface explaination 1 Power Supply range DC8 36 v Port 1 connect battery pole When the controller works regularly power supply current is smaller than 300 mA Port 13 connect battery pole If power source polarity meet on the contrary since the inside connect have a protecting diode in general it will not breakdown the controller 2 Speed sensor input When the sensor gains a rotation spe
7. Minco F2 Engine Controller User Manual GuiLin Minco Electronic CO LTD CHINA Add Building B 216 Venture Park of Returned Scholars uilin High tech Zone Guangxi China Tel Fax 86 773 5828281 5812281 www glminco com Mico MINCO F2 engine controller operating instruction manual MINCO F2 engine controller adopts high performance microprocessor and industrial class devices with high bright LED display and 96 X 96 mm standard machines shell It has the properties of compact structure marked display and easyily install The controller can control the genset to start and stop detect and measure the work state of genset and realize the auto protect function And it can also provide autostart and ATS control functions I Characteristic 1 The engine controller control the genset to run or stop by either pass key Or outside switch 2 Provids remote start port can set the delay start and stop It can control the the genset to auto start and stop 3 Acceleration Deceleration and idle control compatible 4 Two speed input frequency or speed sensor 5 There are two kinds connecting ways of Water temperature oil pressure option input That s analog input or switch alarm input 6 Auto record the running times of genset 7 Protection function low oil pressure high coolant overspeed emergency stop and overcrank II The front panel function explaination The front panel of MINCO F2 engine controller have
8. OJsuRI OMY Hes OINY WeiseIp Zuu pismo xIpueddy Mico Appendix 2 MINCO F2 front amp back panel diagram RPM HZ TEMP OIL P BATT V HOURS FAILURE ALARM REA E01 OVER CRANK ALARM a LOADING REMOTE Engine Monitor Moduli Page 11 of 11
9. d according to the failure code Failure code and corresponding failure cause E 01 start failure E 02 emergency stop E 03 over speed E 04 loss speed E 05 high coolant E 06 low oil pressure E 07 option input failure E 08 low battery voltage If the machine is conk out then will lead the machine to shut down for protection at the same Page 2 of 11 Mico Time the malfunction reason will be locked and the motor can not be start again until the malfunction was solved and then pree the key RESET Then you can start the motor again III Parameter setup When press SET key the LED will display the value of option input default oil temperature firstly If want to display fuel level or other parameters need to provide the sensor characteristic curve to us in order to customize and revise in the factory _ When press SET key again it will enter into the setting state two LED on the left will show 00 20 twenty one in total codes three LED on the right will show correspon ding parametric content The parameter will increase or decrease according to pressing the or key And according to press SET key the set parameter will be saved and display next parameter the parameter code add one Continue to press SET key until all parameters were set Finally exit parameters setting state On the setting status if you do not press
10. ed from magnetic sensor it needs to connect an engine Port 14 magnetic sensors rotation speed signal input The rotation speed wire is a pair of shield wire another wire connect port 13 3 Analog input Port 15 coolant temperature sensor input Port 16 oil pressure sensor input Port17 Monitoring sensor input 4 Switch input That entering adds photoelectricity isolator the short circuit is effectivewith GND Page 6of 11 Port 18 remote start Port 19 emergency stop When emergency or repairing the machine the machine will not start when lock and close this port Port 20 high coolant temperature Port 21 low oil pressure Port 22 option alarm input Port23 ACCeleration Limit input Port 24 Deceleration Limit input 5 Relay output Relay isolator touching capacities 2 A 250V Port 2 common output All of exporting relay have one contact connect the possessions in comm 1 portexcept DEC relay Port 3 start output Port 4 fuel fuel stop output Port 5 engine failure output Port 6 pre fuel pre heat output Port7 genset onload output Port 8 common 2 output The ACC and DEC relay have one contact connect the possessions in comm2 _ Port 9 ACCeleration output Port10 DECeleration output 6 Frequency input Need connect the engine whe
11. lt 10 5 Page 3 of 11 Mico Freguency rate speed upper limit When the engine frequency rotation rate is higher than upper limit it will lead the engine to shut down for the protection and instruct the over speed malfunction Default 55 Trip frequency speed When the Trip frequency speed is higher than upper limit then indicate the engine start successfully and stop striking the motor Default 13 50 Oil Pressure lower limit Ifthe parameter was set to alarm by oil pressure sensor it will lead to shutting down the engine for protection if the oil pressure is lower than lower limit Freewheel tooth number If the parameter was set to the rotating speed was gained from magnetic sensor nearby the freewheel tooth this parameter is valid If the parameter was set to the rotating speed was gained from voltage frequency this parameter will be inva lid Default 135 Coolant temperature adjust oil pressure adjust battery voltage adjust when you measure the water temperature oil pressure battery voltage it may bring some meas urement error this error value was allowed to adjust in arange of 10 more or less in MINCO F2 Especially the coolant or oil pressure sensor maybe positive modulus the sensor output enhances with input enhancing or may be minus modulus the sen sor output diminishes with input enhancing The effects that arised from imcreasing or decreasing adjusting value will depend on the actual circumstance
12. n frequency gains a rotation speed from voltage entering voltage range is AC35 300 V Port 11 Port 12 frequency input IV Size of form and outside wiring diagram Page 7 of 11 e 84mm gt 96mm Paan spear meas 69mm MA 13mm Size of form 96 mm Width X96 mm Height X13 mm Depth front panel 84 mm Width X84 mm Height X69 mm Depth back shell Hole size of panel 85 1 mm Width X 85 1 mm Height Explanation 1 When output connects the inductance property load such as RL you need to plus the current absorption electric circuit in outside wiring otherwise it will probably influence the controller to work normally 2 The input port of remote start can also connect with the timer or other devices to realize time start machine automatically and others 3 Whether the engine is onload or not willdependsonthe remote start If the engine START by pressing START button the engine will not onload automatically as long as the remote start switch input is not closed Therefore the consumer should pay more attention to this point if having no need of automation starting engine when applying only start the engine onload by hand please bear in mind to short connect GND with remote start switch input 4 All the coolant temperature oil pressure sensor and alarm sensor that GuiLin MINCO electronic CO LTD provides are electric resistance type sensor For electric resistance
13. type sensor the measure method needs to connect allotted resistance The MINCO F2 controller has taken over three allotted resistance already inside so do not need to connect the allotted resistance outside 5 Ifthe MINCO F2 controller was set to get the engine rotation speed from voltage it doesn t need the speed sensor linking If set to gain a rotation rate from Page 8 of 11 Mico the magnetic sensor it does not need the voltage input 6 Acceleration deceleration of speed control and the idle speed are compatible if using the idling speed you must set the delay of Acceleration the deceleration zero and connct the ACC and DEC then you can connect AVR unit If chooseing ACC DEC mode you must set the needed time of the delay of starting idle and the delay of stopping idle 7 For ACC DEC Speed Control under normal circumstances you need to connect the acc eleration limits in place and deceleration Limit but in some cases lowerprotection is done in the device without spacing signal to MINCO F2 at this time MINCO F2 can control ACC DEC normally but it will appear contact failure Alarm but it does not affect the genset to work GuiLin Minco Electronic CO LTD CHINA Add Building B 216 Venture Park of Returned Scholars Guilin High tech Zone Guangzi China Tel Fax 86 773 5828281 5812281 Website www glminco com E mail sales glminco com Page 9 of 11 Il Jo 01 9329 91218 YOJIMS WI
14. when the delay of DEC eleration was finished Fuel stopping when delay finished Default 15 Control parameter 1 Default 0 0 engine speed source genset frequency fuel mode Energize To Run ETR 1 engine speed source speed sensor fuel mode Energize To Run ETR 2 engine speed source genset frequency fuel mode Energize To Stop ETS 3 engine speed source speed sensor fuel mode Energize To Stop ETS Control parameter 2 Default 0 0 coolant temperature alarm temp switch oil pressure alarm pressure switch 1 coolant temperature alarm temp sensor oil pressure alarm pressure switch 2 coolant temperature alarm temp switch oil pressure alarm pressure sensor 3 coolant temperature alarm temp sensor oil pressure alarm pressure sensor Control parameter 3 Only be set by manufacturer don t set them by yourself please Notice 1 When delay parameter was set 0 it may have less than one second delay Page 5of 11 Mico 2 When the start up of the machine idle finished the warm machine delay and the ACCeler ation delay begin at the same time To ensure the machine sets not onload until working at full tilt the delay time of warm up should be more than ACCeleration delay time 3 If the delay of Acceleration and Deceleration was set the zero the process of Acceleration and Deceleration will be forbid