Home
        GFK-2961, RSTi-EP Slice I/O Analog Output Modules
         Contents
1.    31 ppm current measurement   K    Max  error between Tmin and Tmax  220 ppm FSR  Monotony    Crosstalk between the channels  0 001   FSR max  Repeat accuracy  lt  1 mV eff    Output ripple max  0 001    Voltage load resistance  gt  1 ka  at  gt  50  C  122   F  max ambient temperature   total sensor current of 10 mA per channel but 25 mA per module     Current load resistance  Actuator connection  Short circuit proof  Module diagnosis  Individual channel diagnosis  Yes  es    Substitute value    Can be used with EP 19xx y  module   Supply   Supply voltage 20 4V   28 8V    Current consumption from   8         system current path Isys  Current consumption from      m    output current path lout       For public disclosure    RSTI EP Slice       Analog Output Module 3    GFK 2961    General data  Operating temperature  20  C to  60  C   4   F to  140   F      40  C to  85  C   40   F to  185   F     5  to 95   noncondensing as per IEC 61131 2    Current consumption from the system current path  Power consumption from input current path   Power consumption from output current path  Current demand of the connected sensors   Current demand of the connected actuators   Must be included when calculating the power supply    EP 4164 EP 4264    Module   Green  Communication over the system bus   Green  Communication over the system bus  Status   Red  Module System Fault or Diagnostic Fault   Red  Module System Fault or Diagnostic Fault    Red  Channel 0 at voltage output  overload  s
2.   Operational Notes    None    Product Documentation  RSTI EP Slice 1 0 Module User Manual  GFK 2958     RSTI EP Slice I O Functional Safety Module User Manual  GFK 2956     1 800 433 2682  1 454 978 5100  www ge ip com    GE Intelligent Platforms aa  For public disclosure       
3.  power down  prior to starting any maintenance activity   Refer to the RSTI EP Slice I O User Manual  GFK 2958  for additional information     Refer to the RSTI EP Power Supply Reference Guide  a software utility available on  PME V9 00  for detailed power feed requirements     Module Features     Control up to four analog outputs     Module diagnosis     Spring style technology for ease of wiring    DIN rail mounted         Double click installation for positive indication of correct installation    Analog Output Module    Supports indirect firmware update through the network monitor    Supports hot insertion and extraction       2015 General Electric Company  All Rights Reserved       Indicates a trademark of General Electric Company and or its subsidiaries  All other trademarks are the property of their respective  owners     2 RSTi EP Slice I O Analog Output Module  GFK 2961    Ordering Information    EP 4164 Analog Output  4 Channels Voltage Current 16 Bits 2  3  or 4 Wire       EP 4264 Analog Output  4 Channels Voltage Current 16 Bits with Diagnostics 2  3  or 4 Wire    Specifications    Data  Interface RSTI EP system bus  System bus transfer rate  Potential isolation Channel system bus   yes   Channel channel   no    Outputs  Number    Output levels 1  Voltage  0 5V 4 5V 0 10V 4 10V 1 5V 2 10V   2  Current  0   20 mA  4   20 mA     Response time 1 ms for 4 channels  Resolution 16 bits    Accuracy 0 1   FSR max   0 05   FSR typ     Temperature coefficient 20 ppm voltage
4. RSTI EP Slice I O  GFK 2961 Analog Output Modules EP 4164  EP 4264    November 2015    GE provides   5          analog output modules with up to 4 analog outputs at    10 V      5 V  0 10 V  0 5 V  2 10 V  1 5 V  0 20 mA or 4 20 mA  The resolution is 16 bit per  Module Status channel  An output can be connected to each connector  the internal switching is  Channel Status LED carried out automatically  The output range is defined using parameterization  A  LEDs status LED is assigned to each channel  The outputs are supplied with power from  the output current path  lour      The EP 4264 module provides individual channel diagnosis with channel related  error messages     Each module features a type plate  which includes identification information  the  key technical specifications  and a block diagram  In addition  a QR code allows for  direct online access to the associated documentation  The software for reading the  QR code must support inverted QR codes     Markers are available as accessories for labelling equipment  Each I O module can  be labelled using the markers to ensure clear identification when replacing  individual modules or electronic units     The RSTI EP station is usually installed on a horizontally positioned DIN rail   Installation on vertically positioned DIN rails is also possible     The outputs as well as the sense lines of the AO modules must not be used as  power outputs     Modules should to be allowed to de energize for a minimum 10 seconds after 
5. hort circuit  at current output  shunt  resistance too high or line break detected    Red  Channel 1 at voltage output  overload  short circuit  at current output  shunt  resistance too high or line break detected    Red  Channel 2 at voltage output  overload  short circuit  at current output  shunt  resistance too high or line break detected    short circuit  at current output  shunt  resistance too high or line break detected       Red  Channel 0 at voltage output  overload  short circuit  at current output  shunt  resistance too high or line break detected    Red  Channel 1 at voltage output  overload  short circuit  at current output  shunt  resistance too high or line break detected    Red  Channel 2 at voltage output  overload  short circuit  at current output  shunt  resistance too high or line break detected    Red  Channel 3 at voltage output  overload  short circuit  at current output  shunt  resistance too high or line break detected    For public disclosure    4 RSTI EP Slice I O Analog Output Module  GFK 2961    Field Wiring   The connection frame can take up to four connectors  and four wires can be connected to each connector  Those four  connectors are shown in the following figure  The Spring style technology allows either finely stranded or solid wire  conductors with crimped wire end ferrules or ultrasonically welded wires  each with a maximum cross section of 1 5  mm   16 guage   to be inserted easily through the opening in the clamping terminal without ha
6. ion Diagrams    Sense 1   Sense 1     A03        EP 4164 EP 4264    For public disclosure    6 RSTI EP Slice I O Analog Output Module    GFK 2961    Connection Block Diagrams       a                                                                l I    p 0  i  l F Sensa 0     I  l l sense l      I  I ADO  a l  I G          AQ     i I    Sense     9 l  i Sensa    Q i           1    gt   l s I  l D An 2   Q  I Sense 2   id I  I Sense 2   5      Ag      i  I 5 i  l D AQ 3     I  i Sanza 3   5 l  Sensa 3    I 203   I    I  I l   E               E E EET                                                        J  EP 4164  r                                                                                 oo    sansa                         AQ 0      OO                   16 Bit      Cx    AD 1                     sense           1      or Th    AD 2    sense 2    Sense 2    AD 2      Ol  000                 ht    AN  3    Tanza 3               3         3      OOK       A  ANNIX    VA       EP 4264    Release History    Catalog Number            Date Comments  Version       EP 4164  EP 4264 01 00 Nov 2015   Initial Release    For public disclosure    RSTI EP Slice       Analog Output Module 7    GFK 2961    Important Product Information for this Release  Updates    Initial Release    Funcional Compatibility    Initial Release    Problems Resolved by this Release  None   Initial Release    New Features and Enhancements  None   Initial Release    Known Restrictions and Open Issues  None  
7. ving to use tools  To    insert fine stranded wires without wire end ferrules  the pusher must be pressed in with a screwdriver and released to  latch the wire     an    i    i    R  8          a aa    8  ya     js      i       Connector Block    Connector Specifications   e conductor cross section 0 14 to 1 5 mm   26   16 guage      max  ampacity  10 A     4 pole    The modules do not have a fused sensor activator power supply  All cables to the connected sensors actuators must be  fused corresponding to their conductor cross sections  as per Standard DIN EN 60204 1  section 12      Refer to the RSTI EP Slice I O User Manual  GFK 2958  for additional information   For technical assistance  go to http   support ge ip com     Installation in Hazardous Areas      EQUIPMENT LABELED WITH REFERENCE TO CLASS    GROUPS A  B  C  amp  D  DIV  2 HAZARDOUS AREAS IS SUITABLE FOR USE IN  CLASS I  DIVISION 2  GROUPS A  B  C  DOR NON HAZARDOUS AREAS ONLY    A WARNING   EXPLOSION HAZARD   SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I  DIVISION 2     A WARNING   EXPLOSION HAZARD   WHEN IN HAZARDOUS AREAS  TURN OFF POWER BEFORE REPLACING OR WIRING  MODULES  AND    A WARNING   EXPLOSION HAZARD   DO NOT CONNECT OR DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN  SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS   ATEX Marking  II 3 G Ex nA IIC T4 Gc  Ta   20  C to  60  C   4   F to  140   F     For public disclosure    RSTI EP Slice I O Analog Output Module 5    GFK 2961    Connect
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
d2 hd SATA II User Manual  2 - VeranstaltungstechnikMueller  quaderni del ce.r.co. - Dipartimento Storia Culture Religioni  Cliquez pour visualiser  BRENNTAG Química, S.A. Área Industrial PRODUCTO: ÁCIDO  MANUEL D`UTILISATION DU FICHIER EXCEL ACHAT DANS  KitchenAid KECC604BSS Use and Care Manual  -manuale MP6infra TENS ITA giu09.qxp  Toshiba 52HMX94 Projection Television User Manual    Copyright © All rights reserved. 