Home
        Owners manual - Automatic Transfer Switch
         Contents
1.            To Set Exerciser    Press and hold  5 seconds  the Set Engine Exerciser  button  The exercise period occurs immediately and at  approximately the same time weekly thereafter  The  status light below the button blinks during the exercise  period  including the cooldown   The light stays on to  indicate that the exerciser has been set  If the light is off   the exerciser has not been set     To Cancel an Active Exercise Period    Press the Bypass Time Delay button to stop an exercising  generator  If exercise with load is set  the ATS  retransfers the load to the utility  then stops the  generator after cooldown        381333 319 D    Series 185    CONTROLLER  continued              S1 DIP switch    S2 DIP switch       on 2345     amp 910    12345678910          HSH 9955886    BABRBABARR      amp              Figure 6  DIP switches S1 and S2 at the top right     The time delay settings are shown in Figures 6 and 7 and  in Table C  The sensor settings are shown in Figure 6  and in Table D  The standard  factory  settings are    shown in Tables C  D  and H        HOC AL    1 22443678910    S3 DIP switch                            Table C  Time Delay Settings    Figure 7  DIP switch S3 at the bottom center                                   Time Delay Description Factory Setting Settings DIP Switch DIP Actuator Actuator Position  override momentary 1 second S2 1 on  up   utility outages 3 seconds   y  Qutag 3 seconds S2 1 off  down   transfer to generator 10 seconds  app
2.     ASCO Series 185  Operator S Automatic Transfer Switches  ache 100 through 400 ampere sizes       A DANGER Refer to the outline and wiring drawings provided with  your ASCO Series 185 ATS for all installation details           DANGER is used in this manual to warn of high  voltages capable of causing shock  burns  or death           ASCO Series 185 Automatic Transfer Switches  ATSs  are  Listed under Underwriter   s Laboratories Standard for  Transfer Switch Equipment  UL 1008  They are intended  for use only in optional standby systems in accordance with  the National Electrical Code  NEC NFPA 70  Article 702   This ATS is for use with 2   wire automatic start generators  only        WARNING is used in this manual to warn  of possible personal injury        Refer to Application Information 381339 292 to confirm  CAUTION is used in this manual to warn that you have selected the appropriate product for the  of possible equipment damage  intended installation        This automatic transfer switch is intended for standby  power applications in residential   light commercial use  only    This product is not intended for emergency  or life support systems    If you have more stringent application requirements contact    ASCO Power Technologies for other products suitable for  critical applications     An experienced licensed electrician must install the ATS     ASCO 185  Powe snsfer Switch       Rating Label  Each automatic transfer switch contains a rating label to  define the
3.   spacer  cable  1  switches  DIP  3 5    T    TB7 generator start connections  3  terminal block  1  test  functional  6    time delay  adjustment  3  4  gen set cooldown  4  how to change  3  override momentary outages  4  settings  3 5  transfer to emergency  4  transfer to normal  4    timer  gen exerciser   how to set  3  transfer switch position lights  2  Transfer Test  button  2  6  troubleshooting  8   9    U    unloaded running  gen  cooldown  4  Utility   failure  7   frequency  4   settings  4   voltage  4    Utility Acceptable  light  2  7  9    V    voltage  phase  4  voltage  pickup  amp  dropout settings  4    voltage checks  6       381333 319 D    Printed in U S A  10    Copyright     ASCO Power Technologies  L P  2009    
4.  applied to it     Press the Bypass Time Delay button for immediate load transfer to the generator        The ATS transfers the load to  the generator  but the genera   tor bogs down  struggles or  slows down   The ATS retran   sfers back to the utility     The generator may be overloaded  Check to see if the generator circuit breaker  tripped  Check the sum of the loads to be sure it does not exceed the capacity of  the generator  Some motor loads require three times more power for starting     Check for short circuit in a connected load   Observe the Load on Utility and Load on Generator lights        The generator stops after a  running for awhile  The ATS  retransfers back to the utility   if acceptable      Verify proper generator operation  it may have run out of fuel or shut down  because of low oil level  see generator manual         The generator may be overloaded  Check to see if the generator circuit breaker  tripped  Check the sum of the loads to be sure it does not exceed the capacity of  the generator  Some motor loads require three times more power for starting     Check for short circuit in a connected load   Observe the Load on Utility and Load on Generator lights        The ATS does not retransfer  the load back to the utility     Verify that the Utility Acceptable light is on  The ATS will not transfer the load to  an unacceptable source     Wait approximately 5 minutes for the retransfer to utility time delay  The utility  must be acceptable for 5 minutes 
5.  gilcnaa table 2  With ALL POWER OFF  verify that the generator feed is 220 240 V ac and 60   5 l Hz  Check DIP switch S2 actuator 2  and DIP S1 actuator 4  See Table D for   voltage and frequency settings    3  With ALL POWER OFF  verify that the generator feed is wired to the terminal  lugs on the top of the transfer switch marked L2 and L6  See the wiring diagram    4  With ALL POWER OFF  verify that the transfer switch harness is connected  properly to the controller  plug and receptacle tight     5  Verify generator ac output  voltage and frequency     see generator manual     The generator starts and runs  1  Verify that the Generator Acceptable light is on  If it is off  see previous trouble   but the ATS does not transfer shooting problem  The ATS will not transfer the load to an unacceptable source   the load to the generator  l   l l   2  With ALL POWER OFF  verify that the transfer switch harness is connected          properly to the controller  plug and receptacle tight            381333 319 D       TROUBLESHOOTING  continued  Series 185          Problem    Cause and Solution       The ATS does not immediately    transfer the load to the  generator     Verify that the Generator Acceptable light is on  If it is off  see previous trouble   shooting problem  The ATS will not transfer the load to an unacceptable source     Wait approximately 10 seconds for the transfer to generator time delay  This  fixed delay allows the generator output to stabilize before a load is
6.  loads and fault circuit withstand   closing ratings   Refer to the label on the transfer switch for specific values     APELIGRO  A DANGER    Do not exceed the values on the rating label     Exceeding the rating can cause personal  injury or serious equipment damage                          TABLE OF CONTENTS   page   INSTALLATION          cccccccceeeeeeees 1   CONTROLLER ooon  2 5   w FUNCTIONAL TEST   L a 6   SEQUENCE OF OPERATION               7   TROUBLESHOOTING              2000  8 9   ti l   100 230 ampere sizes INDEX g ap E E E T 10  a i  ASCO ines RESTEN TE E n 90999 0190    ASCO POWER TECHNOLOGIES CANADA PO Box 1238  17 Airport Road  Brantford  Ontario  Canada NST 5T3 EMERSON    Series 185       Nameplate Catalog Number Identification    The Transfer Switch nameplate includes data for A typical Catalog Number is shown below with its  each specific ASCO Series 185 ATS  Use the ATS elements explained  The example is for a D design     only within the limits shown on this nameplate  2 pole  200 A  220 240 V  in Type 1 indoor enclosure                                                                                            D 185 A 2 200 F 4 C  Neutral Phase Poles Amperes Voltage Controller Enclosure  A   standard 2   single    100 F 220 240 4   standard C  Type 1  200 4X  if M   Type 3R  230 accessories  260 ordered  400  clock battery cable spacers load power  i emergency   see INSTALLATION  connections power  connections     neutral  connections  terminals  for optio
7.  slide the DIP switch actuators up or  down to match setting shown     All power must be off before making any changes     The factory default settings are shown in Table G on  page 5           cover must be removed  to replace 9V battery   use alkaline type     SCrew                   Figure 5  Battery replacement     5     Automatic Generator Exerciser    The built in automatic generator exerciser can be set to  exercise the generator for 20 minutes once every week        Clock Battery    Be sure a fresh battery is installed and turned on  It will  maintain the exerciser clock for about 24 hours in case of  a power outage     Recommended 9 volt alkaline batteries are  see Figure  5   Duracell MN 1404  Everready 522  Panasonic 6AM6    Turn on battery by putting S2 DIP switch actuator 10 in  the on position  up   See Table B and Figure 6     Exercise with or without Load    The generator should be exercised under load or follow  the recommendations of the generator manufacturer  Be  sure the exerciser is turned on  Then select either  exercise with or without load  The ATS will transfer the  load to the generator when the exercise with load is  selected  See Figure 6 and Table B        Table B  Generator Exercise Settings                Functi Factory DIP DIP Actuator  ee Setting Switch   Actuator Position  clock on  up   battery off S2 10 off  down    l on  up   exerciser off S1 7 off  down   with load or without S1 g with  up   without load load without  down               
8.  starting  acceptable         E    utility  returns       waiting for utility  to return    load on generator    L    generator acceptable           load on utility                utility off   e generator  acceptable   generator  acceptable  wait 10 sec     for generator  load on generator to warm up        generator acceptable    electrical loads       switched to generator       7 381333 319 D    Series 185    TROUBLESHOOTING       This troubleshooting guide describes some of the simple    causes of problems with the installation of the automatic  transfer switch  Troubleshooting beyond the scope of this  guide should not be attempted by the installer  A licensed  electrician must perform all internal troubleshooting   ASCO Power Technologies can be contacted at     A DANGER  ELECTROCUTION FLASH HAZARD Do not work    on the transfer switch until both the utility and  generator are off  Turn OFF both circuit breakers        1 800 800 2726 or customercare asco com                      Problem Cause and Solution  The Utility Acceptable light 1  Verify that the utility feed is connected and that its circuit breaker is ON   does not come on when utility   5   With ALL POWER OFF verify that the utility feed is 220 240 V ac and 60 Hz   power is connected to the ATS   Check DIP switch S2 actuator 2  and DIP S1 actuator 4  See Table D for voltage  and frequency settings    3  With ALL POWER OFF  verify that the utility feed is wired to the terminal lugs  on the bottom of the transf
9. 0 and 400 ampere transfer switches           insulator  backing  piece                Figure 1  Insulator for 260 and 400 A     2     Electrical Power Connections    Refer to the wiring diagram  The ATS must be protected  by suitably sized circuit breakers feeding the utility and  generator source terminals  The rating of the circuit  breakers must be based on the requirements of the  National Electrical Code for its nameplate ampere and  short circuit withstand ratings     A DANGER       ELECTROCUTION HAZARD Turn off utility    power and turn off the generator to prevent  electrocution when wiring the transfer switch        Cable Spacers for 200 and 230 A    Three cable spacers are included with 200 and 230  ampere transfer switches  Run the copper power cables  through the cable spacers as shown in Figure 2  Position  the cable spacers approximately 11   2 inches from the  terminal lugs     CABLE LOOSENING DUE TO SHORT CIRCUIT  Install three cable spacers 1 1 2 inches from  the power terminals to prevent the cables from  loosening during a short short condition           1   inch approximate    use Copper power  cables only for  200 and 230A    cable spacer             Figure 2  Cable spacers for 200 and 230 A        381333 319 D    Series 185 CONTROLLER       The Group 4 digital Controller is used in ASCO Series 1     Push Buttons  185 automatic transfer switches  It provides the sensing   timing  and control functions for the ATS  This micro   processor based controller i
10. bled disabled s3 2 on  up   enabled  on  off  down                       Bypass load transfer to utility time delay    Normally   closed input  When opened  it bypasses or  cancels the generator to utility load transfer time delay   The load transfers back to the utility     Table G  Bypass load transfer to utility time       S3                                   OIOI NIOI oO  BR  OJN               O                      delay  Functi Factory DIP DIP Actuator  UNGROD Setting Switch   Actuator Position  disabled disabled S3 j on  up   enabled  on  off  down                             381333 319 D       Series 185    FUNCTIONAL TEST       After installing the Series 185 automatic transfer switch   ATS  perform the following three part functional test     1     Manual Operation    A handle is provided on the transfer switch for  maintenance purposes only  Manual operation of the  transfer switch should be checked before it 1s energized   operated electrically         Do not manually operate the transfer switch    until both power sources are disconnected   open both circuit breakers        1  Turn OFF both the utility and generator circuit  breakers feeding the ATS  Verify that ALL POWER  IS OFF     2  100 230A  Grasp the maintenance handle and turn it quickly  with your thumb and fingers to manually operate the  transfer switch   260 400 A  Insert the maintenance handle into the hole in the  shaft  left side of the operator  Move the handle as  shown to manually operate the tra
11. ck battery  3    connections  electrical power  1  engine control contact  1    contacts  engine control  1    control features  remote  5    controller  2   5    D    DIP switches  3   5  dropout  4    E    electrical operation  2  6  electrical power connections  1    engine exerciser  2  3  9    F    features  see control features  frequency  pickup and dropout  4    functional test  6    G    generator  exerciser  2  3  9  frequency  4  settings  4  starting contacts  3  voltage  4    Generator Acceptable  light  2  7  9    ground connection  inside cover    H    handle  maintenance  6  warning  6    harness  inside cover    HELP  800 800 2726  ASCO   customercare asco com    indicator lights  2  installation  1    insulator  backing piece  1  illustration of  6  warning  6    L    labels   operator  transfer switch  6  rating  cover    lights  2  7  Load on Generator  light  2  7  Load on Utility  light  2  7    M    manual operation  6  illustration of  6  warning  6    mounting  1    O    operation  electrical  6  manual  6  sequence of  7    override momentary outages  4    P    pickup  4  problem  8 9    R    rating label  cover    remote control features  5  bypass transfer time delay  5  remote test  5  remote transfer to emergency  5    S    service   800 800 2726  ASCO   customercare asco com    Set Engine Exerciser  button  2  3    settings  changing  3   5  factory  3   5  frequency  3  4  phase  4  time delay  3  4  voltage  3  4    source acceptable lights  2
12. continuously     Press the Bypass Time Delay button for immediate load retransfer to the utility        The ATS retransfers the load  back to the utility but the  generator keeps running     Wait approximately 2 minutes for the unloaded running  engine cooldown  time  delay     The engine cooldown fixed time delay is important to prevent generator damage        The generator exerciser does  not seem to work     Verify that the Automatic Generator Exerciser status light 1s blinking       Light blinks during the exercise period    when the generator is running and during cooldown        Light stays on when then exerciser has been set       When light is off  no exercise period is set     With ALL POWER OFF  verify that the exerciser is turned on  Check DIP switch  S1 actuator 7  and S2 actuator 10  See Table B for generator exerciser settings     With ALL POWER OFF  check the 9 volt battery  Replace  if necessary  with a  quality alkaline battery  Duracell MN1404  Everready 522  Panasonic 6AM6  or  equivalent  See Figure 5           The generator exerciser does  not transfer the load to the  generator        With ALL POWER OFF  verify that exercise with load is turned on  Check DIP  switch S1 actuator 8  See Table B for generator exerciser settings           9 381333 319 D       Series 185    INDEX       A    Automatic Generator Exerciser  2  3   9    battery  clock  3  buttons  push  2  Bypass Time Delay  button  2  6    C    cable spacers  1  catalog number  inside cover  clo
13. d  with the ATS  Activate the appropriate DIP switch S3  actuators as shown in Tables E  F  or G  See Figure 7     Remote test    Normally   closed input  When opened  it simulates a  utility failure  The generator is signalled to start  immediately and the load transfers to the generator  if  acceptable   If the generator fails  the load stays on the  generator until the remote test circuit is closed     Table E  Remote test    Table H  Factory Settings   Summary    7     Factory Settings     Summary       DIP Switch    DIP Actuator    Actuator Position       S1    1    on  up        off  down        on  up        off  down        off  down        on  up        off  down        off  down        O  OI NI OO  oO   BR  OIN    off  down           O    on  up                       Functi Factory DIP DIP Actuator  sale Setting Switch   Actuator Position   disabled disabled 93 3 on  up   enabled  on  off  down                       Remote test  with automatic retransfer     Normally   closed input  When opened  it simulates a  utility failure  The generator is signalled to start  immediately and the load transfers to the generator  if  acceptable   If the generator fails  the load transfers  back to the utility  if acceptable      Table F  Remote transfer to generator    S2           off  down        on  up        off  down                       O OI NI OO  oO  ATIT OIN            O                      Functi Factory DIP DIP Actuator  UGHA Setting Switch   Actuator Position   disa
14. e is  acceptable for connection to the load     Load on Generator    This light indicates that the generator voltage is  acceptable for connection to the load     Automatic Generator Exerciser    This light indicates the status of the generator exerciser       blinks during the exercise period  including cooldown        stays on when the exerciser has been set        1s off when the exerciser has not been set        381333 319 D 2    CONTROLLER  continued     Series 185       3     Generator Starting Contacts    The generator starting contacts connections are on the  controller  Refer to the generator manual  Disconnect  the generator battery and verify that the ignition switch is  in the OFF position  Connect the generator starting  wires to the appropriate terminals on terminal block TB7  as shown on the wiring diagram  For wiring convenience  terminal block TB7 has a removable plug  See Figure 4  and    Table A                 OECO OUL    1224453678910    EEEE             TB7  removable  terminal block       TB7 4  TB7 5  TB7 6             Figure 4  TB7 generator starting contact terminals     Table A  Generator Start Connections       When the Utility fails Terminals on Controller       contact closes TB7   4 and TB7 5       contact opens TB7 5 and TB7 6                4     Settings    The time delay and sensor setting in the Group 4  controller are accessible on the inside  Refer to Tables B  and C and to Figures 6 and 7  Use a ball   point pen or  other pointed tool to
15. er switch marked L1 and L5  See the wiring diagram    4  With ALL POWER OFF  verify that the transfer switch harness is connected  properly to the controller  plug and receptacle tight     The generator does not crank  1  Hold the Transfer Test button for at least 15 seconds    when the utility source fails or            whenthe Tun fer Test buttonis 2  Verify ae generator starting controls are set for automatic operation  not in  pressed  manual mode     3  Verify that the generator battery is connected and that the battery voltage meets  the generator manufacturer   s recommendation    4  Verify that the correct contact  normally open or normally closed  is being  utilized  see the generator manual     5  With ALL POWER OFF  verify engine start low voltage wiring between the  controller terminal block and the generator  See the wiring diagram  Check that  the plug is properly seated in the receptacle on the controller    The generator cranks but does  1  Verify proper generator operation  fuel in tank  oil level  spark plugs     see   not start and run when the util  generator manual     ity source fails or when the a   my nsfer Test button is pressed  2  With ALL POWER OFF  verify engine start low voltage wiring between the  controller terminal block and the generator  See the wiring diagram  Check that  the plug is properly seated in the receptacle    The generator starts and runs  1  Verify that the generator feed is connected and that its circuit breaker is ON    ba ile
16. nal  switch  position  contacts   shown  d installed   a Transfer  E Switch  EAA D S ground      connections            g membrane enerator N a  i ae  controls   ntrol Comoe Mh ae i  connections harness plug    200 ampere size in typical enclosure with location of customer connections       381333 319 D    INSTALLATION    Series 185       Installation of the ASCO Series 185 automatic transfer       switch  ATS  must be performed by a licensed electrician     It must be installed according to the National Electrical  Code  NEC  and all local electrical code requirements   Remove the enclosure cover and inspect the ATS for  shipping damage  If damage is evident do not install the  ATS        1     Mounting    Refer to the enclosure outline drawing  Mount the ATS  according to details and instructions shown on this  diagram  Mount the ATS vertically to a rigid supporting  structure  Level all mounting points by using flat washers  behind the holes to avoid distortion of the enclosure     MALFUNCTION or SHORTENED LIFE    Protect the ATS from construction grit and metal  chips to prevent malfunction or shortened life        Transfer switches rated 260 and 400 amperes are  mounted on an insulator backing piece  installed behind  the transfer switch   If the transfer switch is removed  from the enclosure and then reinstalled  this insulator  must be placed behind the transfer switch  See Figure 1     FLASH HAZARD   DAMAGE  Be sure that the insulator piece is installed behind  the 26
17. ncludes built   in control  buttons and status lights for control of the ATS and  generator     On the front control display are three push buttons that  control the operation of the generator and the ATS        Before using the transfer test button  be sure that          clock  battery conditions are safe for running the generator and  cover for load transfer   see page 3  O Transfer Test    Use this button to test the system  This operation starts  the generator and transfers the load  Be sure that  conditions are safe to do this operation     Bypass Time Delay    Use this button to cancel the active time delay or exercise  period  stops the generator after cooldown                      Utility  a Set Engine Exerciser  Use this button to set the automatic generator exerciser    Load on  page 3    Utility light    Transfer  Test  button       2     Indicator Lights  Bypass  Time Delay  button       On the front control display are five lights that indicate    Set Engine the status of the sources and the ATS   Exerciser    button       Load on  Generator    light Utility Acceptable    Automatic _    Ganoraier This light indicates that the utility voltage is acceptable    Generator Acceptable for connection to the load   Exerciser light  light    Generator Acceptable    This light indicates that the generator voltage is  acceptable for connection to the load                 Figure 3  Front view of controller  _  Load on Utility    This light indicates that the generator voltag
18. nsfer switch        3  The switch should operate smoothly without binding     If it does not  check for shipping damage or  construction debris     4  After checking the manual operation  use the handle  again to return the transfer switch to the utility  source position    100 230 A see Figure 8    The letter P  utility  on the round weight is facing  you    260 400 A see Figure 9    The letter N  utility  on the round weight is facing  you    Remove the maintenance handle and store it on the  transfer switch in the place provided     260 400 A Remove the maintenance handle  before proceeding        2     Voltage Checks    The ATS is rated for 220 240 V ac 60 or 50 Hz  Verify that  both the utility and generator sources are 220 240 V ac 60  or 50 Hz               maintenance handle    With ALL POWER OFF  grasp maintenance  handle and turn it  quickly with your  thumb and an       weight marked P  utility  and A  generator        Figure 8  Maintenance handle for 100 230 A           maintenance  handle             Figure 9  Maintenance handle for 260   400 A     3     Electrical Operation    This procedure checks the electrical operation of the ATS   1  Install the enclosure cover and tighten the screws     2  Verify that the generator battery is connected and  that the generator   s starting controls are set for  automatic     3  Turn on both the utility and generator circuit breakers     4  Verify that the Utility Acceptable and Load on Utility  lights are on     5  This ste
19. p will start the generator  Press and hold the  Transfer Test button until the Generator Acceptable  light comes on and stays on  Then release the button        6  After the Generator Acceptable light comes on  the  ATS transfers the load from the utility to the  generator  after approx  10 second delay   The Load  on Generator light comes on     7  The ATS stays connected to the generator for  5 minutes  approx    The utility must be acceptable  for 5 minutes continuously  Then the load is  transferred back to the utility  To bypass time delay   press the Bypass Time Delay button     8  After load retransfer to utility  the generator runs  2 minutes  without load   then shuts down  The  Generator Acceptable light goes off indicating that  the generator is off     This completes the Functional Test        381333 319 D          Sequence of Operation     Utility Failure    Series 185       generator  stops  generator runs  unloaded  for 2 min   electrical loads  Switched back           utility acceptable    to utility       Ye load on utility       generator       W light is on       O lightis off  Utility power good   Electrical loads on utility Utility fails  Pe ses  longer than  E    utility acceptable 3 sec       load on utility   0 utility off start  generator  oWo generator off  o load off    EJ       O 0O generator off        acceptable observe observe  wait 5 min  these these  for utility power switch  7 as s generator  to stabilize utility lights lights   O utility off
20. rox                     override momentary 4 second S3 9 on  up    4 seconds   generator outages 0 S3 9 off  down   transfer to utility 5 minutes  approx                    unloaded running 2 minutes S1 10 on  up    generator cooldown  enue    g 5 minutes S1 10 off  down                       Table D  Voltage and Frequency Settings                                                                Setting Description Setting Factory Setting Settings DIP Switch DIP Actuator Actuator Position  voltage     220   240 V non adjustable S2 2 on  up   50 Hz S1 4 on  up   frequency nominal 60 Hz  60 Hz S1 4 off  down   phase     single non   adjustable S1 6 on  up   l 198 V S1 3 on  up   pickup 198 V  209 V   S1 3 off  down   S1 1 off  down   198 V    S1 2 off  down   S1 1 on  up   utility voltage 187 V  S1 2 off  down   dropout 187 V  S1 1 off  down   176 V  S1 2 on  up   S1 1 on  u  154 V  up   S1 2 on  up   pickup 198 V l  generator voltage non adjustable            dropout 165 V    57 Hz  nom 60 Hz   generator frequency   pickup 48 Hz  nom 50 Hz   non adjustable          d t 51 Hz  nom 60 Hz   FORSS 43 Hz  nom 50 Hz                            If the dropout voltage is set to 198 V  the pickup voltage must be set to 209 V        381333 319 D          CONTROLLER  continued     Series 185       6     Remote Control Features    These remote control features require a customer   supplied normally   closed contact suitable for a5 V dc  low energy circuit  Refer to the wiring diagram provide
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
  User Guide - University of Edinburgh      Weed Eater 96024000100 Lawn Mower User Manual  Instructions for Use  My Document  2.4GHz 150Mbps 802.11n Wireless Outdoor Access Point    Copyright © All rights reserved. 
   Failed to retrieve file