        APC MX5000 Datasheet
         Contents
1.      Automatically starts up the connected equipment upon the return of utility  power     Provides fast serviceability and reduced maintenance requirements via self   diagnosing  field replaceable modules     Maximizes useful battery life by widening the input voltage window or  tightening the output voltage regulation     Plug and Play external Ensures clean  uninterrupted power to the loads when adding extra runtime to    batteries  Field replaceable  power distribution  panel   Manageability  SmartSlot   LCD display  Serial Connectivity  InfraStruXure  Manager Compatible  Serviceability  User replaceable  batteries   Predictive failure  notification  User replaceable  batteries  User replaceable  power modules  Audible Alarms    Protection    the UPS   Ensures compatibility with equipment that has different plug types     Customize UPS capabilities with management cards    Alpha Numeric Display which displays system parameters and alarms   Provides management of the UPS via a serial port    Enables centralized management via the APC InfraStruXure   Manager     Increases availability by allowing a trained user to perform upgrades and  replacements of the batteries reducing Mean Time to Repair  MTTR   Provides early warning fault analysis ensuring proactive component  replacement    Increases availability by allowing a trained user to perform upgrades and  replacements of the batteries reducing Mean Time to Repair  MTTR   Enables simple upgrades and replacements of the Powe
2.  8 1 Storage Conditions    The UPS should be covered and stored in a cool dry location  The UPS should be stored with the Battery Packs in a  fully charged state  That is  the reported battery capacity should be at 100  before the UPS is switched off for storage   Disconnect the Battery Packs from the UPS and from each other  where applicable   Store the Battery Packs in an  upright position     8 2 Extended Storage    To achieve expected run time following extended storage  the UPS should be allowed to refresh the Battery Packs every  6 months in environments where the ambient temperature is  15  C to  30  C  5  F to 86  F   For extended storage in  environments where the ambient temperature 1s  30  C to  45  C  86  F to 113  F   the UPS should be allowed to refresh  the Battery Packs every 3 months     9 0 Specifications    Note  Where specification ratings differ  values for the UPS configured for 240 Vac operation are given in brackets         9 1 Input    Nominal input voltage  single phase 208 Vac  240 Vac     Nominal input frequency  60 Hz    On line efficiency   full load   gt  92    gt  93  with fully charged batteries for the 3000VA and  5000VA models  respectively    Input circuit breaker  20 Amp  30 Amp  for the 3000VA and 5000VA models  respectively    Input connector  NEMA L6 30P  250V 30A      9 2 Transfer Characteristics    Frequency limits for on line operation  60 Hz   5     Input voltage limits for on line operation   25  to  15  of the nominal input voltag
3.  Backup Time    SmartCell  If a SmartCell XR is being used then an RBC14 may be purchased   27 8 minutes  1875 Watts     10 2 minutes  3750 Watts     at Full Load  Runtime Chart  Extended Run Options    Matrix UPS  APC Matrix UPS 5kVA 208V 240V In 120 208 240V Out          Communications  amp  Management    Interface Port s     Available SmartSlot     Interface    Quantity   Control panel   Audible Alarm   Emergency Power Off  EPO     Physical  Maximum Height  Maximum Width  Maximum Depth  Net Weight  Shipping Weight  Color   Units per Pallet    Environmental    Operating Environment  Operating Relative Humidity  Operating Elevation   Storage Temperature  Storage Relative Humidity  Storage Elevation    Audible noise at 1 meter from  surface of unit    Online Thermal Dissipation    Conformance    Regulatory Approvals  Standard Warranty    DB 9 RS 232 SmartSlot  1    Multi function LCD status and control console  Alarm when on battery   distinctive low battery alarm   configurable delays    Yes    683 00 mm  351 00 mm  452 00 mm  137 73 KG  155 91 KG  Beige   1 00    0 40   C   0    0 3000 meters   15  45   C   0    0 15000 meters  60 00 dBA    900 00 BTU hr    CE CSA FCC Part 15 Class A UL 1778    2 years repair or replace optional on site warranties available optional extended    warranties available      The time to recharge to 90  of full battery capacity following a discharge to shutdown using a load rated for 1 2 the full  load rating of the UPS     8 0 Storing the UPS   
4.  Hours  2 8   2 7   3 8   4 9   6   7    The case of one SmartCell does not apply to 5000 VA Matrix UPS    Calculations based on loads with a  75 power factor  Lower power factor loads will yield higher run times   Run times are typical at 25   C  77   F     Recharge times to 90  of rated capacity after discharge into 50  of rated load        Number of SmartCell XR Battery Packs    Computer Load     VA  i    2 3 4 5 6 7  Te fs ps fo  fs fw fs  ss  po fe    e   fs   om    0 9 1 6 2 4 3 2 4 4 8    0 37    Recharge Time  in Hours    8   8 1   12 5   16 9   21 3   255    30 1    Calculations based on loads with a  75 power factor  Lower power factor loads will yield higher run times   Run times are typical at 25   C  77   F    Recharge times to 90  of rated capacity after discharge into 50  of rated load     At B_ uo ININ   gt   e  Ce Se ys oS ae Pe o  ea  e a ae a ee a a  Of Oe fo a   o    Go    
5.  to 60 dB over 100 kHz to 30 MHz range   Normal mode let through   lt  1  of applied ANSI C62 41 Category A or B  6 kV test   Common mode let through   lt  2  of applied ANSI C62 41 Category A or B  6 kV test     9 5 Battery Pack    Battery type  spill proof  maintenance free sealed lead acid    Nominal battery pack voltage  48 Vdc    Typical battery life  3 to 6 years  depends upon number of discharge cycles and normal ambient  temperature     Recharge time  see table in section 9 9    Maximum number of Battery Packs  limited only by desired recharge time     9 6 Environment    Operating temperature  0  C to 40  C  32  F to 104  F     Storage temperature   15  C to 45  C  5  F to 113  F     Operating and storage relative humidity  0 to 95   non condensing    Operating elevation  0 to 3 000 m  10 000 ft     Storage elevation  0 to 15 000 m  50 000 ft     Electromagnetic immunity  IEC 801 2  801 3  801 4  801 5  severity level HI or IV   Audible noise   lt  55 dBA at 1 m  3 ft      9 7 Physical    UPS dimensions  EU and IU mated   17 8  H x 13 8  W x 17 8  D  45 2 x 35 1 x 45 2 cm     Battery pack dimensions  9 1  H x 6 9  W x 17 8  D  23 1 x 17 5 x 45 2 cm     UPS weight  EU and IU mated   145 lb  65 8 kg   176 lb  79 8 kg  for the 3000VA and 5000VA  models  respectively    Electronics Unit  EU  weight  40 Ib  18 1 kg   45 lb  20 4 kg  for the 3000VA and 5000VA models   respectively  Add 8 lbs  3 6 kg  for shipping independent of IU    Battery pack weight  64 Ibs  29 0 kg   A
6. Arc    by Schneider Electric    APC Matrix UPS 5kVA 208V 240V In  120 208 240V Out    APC Matrix UPS  3750 Watts   5000   VA  Input 208V   Output 120V  208V  Interface  Port DB 9 RS 232  SmartSlot  Extended runtime  model    Includes  CD with software  Smart UPS  signalling RS 232 cable  User Manual       Standard Lead Time  Usually Ships within 2  Weeks    Matrix UPS Features  amp  Benefits    Availability  Automatic internal  bypass   Intelligent Battery  Management  Hot swappable  batteries  Hot swappable  modules   Scalable runtime  Automatic self test    Manageable external  batteries   Battery modules  connected in parallel  Automatic restart of  loads after UPS  shutdown   Modular design    Adaptability    Adjustable voltage   transfer points    Supplies utility power to the connected loads in the event of a UPS overload  condition or fault    Maximizes battery performance  life  and reliability through intelligent   precision charging    Ensures clean  uninterrupted power to protected equipment while batteries  are being replaced   Ensures clean  uninterrupted power to protected equipment during Power  Module replacement    Allows additional run time to be quickly added as needed    Periodic battery self test ensures early detection of a battery that needs to be  replaced    Reduces preventative maintenance service needs by monitoring the health  and status of the external batteries and their expected runtime    Delivers higher availability through redundant batteries
7. dd 5 lbs  2 3 kg  for shipping independent of UPS    Total shipping weight   3000VA model  244 Ib  110 7 kg   Includes weight of packaging  mated EU  and IU  and one  1  Battery Pack    Total shipping weight   5000VA model  344 Ib  156 0 kg   Includes weight of packaging  mated EU  and IU  and two  2  Battery Packs    Color  beige     9 8 Approvals    Safety approvals  UL per 1778  CSA per C22 2   EMC verification  FCC  CDC Class A verified     9 9 Typical On Battery Run Times    Number of SmartCells    1 2 3 4 5 6 7    Cow or e o a i w e T  om oa or o ae o e i e  Co on  oe o o o e oe oa  0 13 0 36 0 62 0 92 1 25 1 59 230  oe Recharge Time  in Hours   12   2 8   2   3 8   4 9   6   7    Calculations based on loads with a  75 power factor  Lower power factor loads will yield higher run times   Run times are typical at 25   C  77   F    Recharge times to 90  of rated capacity after discharge into 50  of rated load        Computer Load   VA        o    o o   o  es s  ms  ams   o  w  e fs eo fos  ms    ma   99     fe fs fs fs fs fw fs  es  Ce f o f a e e a a e  6 15 9 05 10 5  a Recharge Time  in Hours   3 8   8 1   12 5   16 9   21 3   25     30 1    Calculations based on loads with a  75 power factor  Lower power factor loads will yield higher run times   Run times are typical at 25   C  77   F    Recharge times to 90  of rated capacity after discharge into 50  of rated load     Number of SmartCells    Computer Load     VA     0 17 0 31 0 46 0 62 0 78 0 98  el Recharge Time  in
8. e    Transfer to from on battery  0 ms typical with computer loads  1 5 ms maximum  Transfer occurs  synchronous with the utility voltage phase    Transfer to from bypass  Transfers to and from bypass occur synchronously with the utility voltage  phase  Transfers both to and from bypass mode occur in 0 mS typically     9 3 Output Characteristics    Maximum load  3000 VA or 2250 W   0 75 power factor  4700 VA or 3750 W   0 8 power factor   5000 VA  3750 W   0 75 power factor  for the 3000VA and 5000VA models  respectively    Nominal output voltages  208 Vac   120 Vac  240 Vac   120 Vac     On line voltage regulation   5   When  Auto  or  Low  utility failure sensitivity is selected by the  user  the output voltage regulation may become relaxed to  5    12     On line frequency regulation  60 Hz   5   synchronized to the utility     On battery output voltage regulation   5     On battery output frequency regulation  60 Hz   0 1 Hz unless synchronized to utility frequency  during utility brownout    On battery output voltage total harmonic distortion   lt  5      Protection  overcurrent and short circuit protected  latching shutdown upon overload   Output connections   6  NEMA 5 15R receptacles   1  NEMA L14 30R receptacle  and  2  NEMA  L6 30R receptacles     9 4 Noise and Surge Isolation    Isolation  galvanic isolation  output neutral bonded to ground    Normal mode EMI RFI noise attenuation  40 to 60 dB over 100 kHz to 30 MHz range   Common mode EMI RFI noise attenuation  40
9. r Modules     Actively let you know if the unit is on battery  if the battery is low or if there  is an overload condition     Power conditioning Protects connected loads from surges  spikes  lightning  and other power  disturbances    Boost and Trim Gives higher application availability by correcting low and high voltage   Automatic Voltage conditions without using the battery    Regulation  AVR     Output    Output Power Capacity   Max Configurable Power  Nominal Output Voltage  Efficiency at Full Load   Output Voltage Distortion   Output Frequency  sync to mains   Crest Factor   Wavetorm Type    Output Connections    Bypass    Input  Nominal Input Voltage  Input Frequency    Input Connections    Cord Length    Input voltage range for main  operations    Other Input Voltages    Batteries  amp  Runtime  Battery Type    Typical recharge time    RBC    Quantity    3750 Watts   5000 VA   3750 Watts   5000 VA  120V 208V   93    Less than 5  at full load   57   63 Hz for 60 Hz nominal  up to5      Sine wave     6  NEMA 5 15R     1  NEMA L14 30R    q           2  NEMA L6 30R          Internal Bypass  Automatic and Manual     208V  60 Hz     5 Hz    NEMA L6 30P    1 83 meters    156   252  208    176   282   240V V    240    Maintenance free sealed Lead Acid battery with suspended electrolyte   leakproof  3 30 hour s   2    Replacement battery cartridge note The MX5000 ships with 2 SmartCell s  There is no RBC available for a standard    Typical Backup Time  at Half Load    Typical
    