1. SILENCE ON RESOUND ALARMS ACTIVE RESET SYSTEM CONTROLS MUTE BUZZER Key switch Activate Controls This Key switch is normally in the OFF position with the key withdrawn and stored where it can be accessed by authorised personnel in the event of an alarm or fault In the OFF position none of the functions are operable even though the system is completely operational with the exception of the mute buzzer key scroll 2 8 and 5 if an alarm should be present This is to enable viewing of the event text if no key is available If the keyswitch is turned to the ON position then the keypad becomes fully functional NOTE It is not possible to withdraw the key in the ON position Key lock This allows authorised engineering personnel access to the inside of the control unit WARNING The power to the alarm unit should be isolated before gaining access The voltages in this unit are high enough to cause severe injury Vector Operating Manual 8 CONTROL PANEL Continued General description The control panel comprises a sheet steel wall mounted enclosure with a lockable hinged door All the user controls and indicators are mounted on the fascia of the unit there are no user controls within the panel Normal Operation In the normal operating mode only the green Supply Healthy LED light emitting diode should be illuminated The LCD liquid crystal display should be showing the current time date and company
2. Essential fuses are monitored Vector Operating Manual 22 SYSTEM OPERATION continued Fault conditions When the control panel detects a fault condition one of the following occurs 1 The COMMON FAULT led will flash and the LCD will show the details 2 The PRE ALARM led will flash This indicates that a detector has recorded a higher than normal analogue value which could signal a possible fault with that detector or an impending fire condition The LCD will show the details 3 The SYSTEM FAULT led will flash indicating that the processor has halted This can only be reset by an engineer 4 The ALARM FAULT led illuminates to indicate a fault on the alarm circuit 5 The PSU led when lit indicates a power supply failure The LCD will show the details 6 For each of the above or combination of them the internal buzzer pulses slow pulse 7 The LCD will display the event information e g NO RESPONSE ZONE 001 01 OF 01 PE MAN ADD 003 18 20 23 03 The fault message is normally self explanatory for instance in the above example the message is NO RESPONSE indicating that the panel cannot communicate with the device ADD 003 which could indicate that it had been removed The fault condition can be accepted by pressing the SILENCE key 6 To view the text description of the device press keypad 5 The flashing LEDs go steady and the buzzer tone changes to an intermittent bleep The panel automatically returns to normal
3. name if programmed Fire Alarm Event A fire alarm event is caused by the activation of a field device It may be generated automatically by a smoke or heat detector sensing smoke or heat or manually by the operation of a call point In either case it will cause an audible alarm to be given usually throughout the building and the event details to be displayed and indicated on the control panel NOTE Each system is individually configured for the required operation Space is provided in the manual to record the method of operation of this system which should be completed by the installer The prescribed emergency fire alarm drill should commence immediately the alarm is heard see System Operation Fault Event A fault event is generated when the control panel detects an internal malfunction or a fault on an external circuit or device A fault is indicated by the relevant LED s and the buzzer sounding A fault description is shown on the LCD Control Event A control event is caused by the operation of one or more of the keyboard pushbuttons All controls are inoperable until the Controls keyswitch is set to the on position to prevent unauthorised operation A keypad is provided to silence and reset the system following a fire or fault event initiate an evacuation alarm and to access the menu functions Vector Operating Manual 9 PANEL INDICATORS TEST MODE DISABLEMENTS ACTIVE ACTIVE SUPPLY FIRE gt O O SD mam Commo
4. 2 8 TOGGLE SET ZONES gt SELECT ZONE EP cisascement hee EN DIS TOGGLE EN DIS es ey A 001 A126 TOGGLE oii gt E DISAB EMENT 2 8 scroll EN DIS SET AUTO gt 5 gt ENABLE DEVICES TIMERS EDIT TIME amp DATE OUTPUTS SET AUTO ENABLE TIME ON OFF 2 8 TO CONFIRM REMOVE ALL DISABLEMENTS Vector Operating Manual 18 MENU AND CONTROL FUNCTIONS Continued Set Disablements 1 Remote Contacts can be disabled or enabled for test purposes This applies to the signal relay the common fire common fault or the loop module relays 2 Sounders can be disabled if required and enabled again 3 The Loop can be isolated on this option 4 Any selected zone can be disabled or enabled 5 Any of up to 126 devices on the loop can be disabled or enabled 6 Timers can be set for devices or outputs to be re enabled automatically at a specified time and date with this option 7 All disablements on whatever device or line can be cleared simultaneously NOTE A new function in V4 1 allows a disablement to be made using a switch monitor or RIO device See Installation and Commissioning manual for further information Engineering Options In order to access the Engineering options a security code is needed which is normally restricted to engineering personnel only All the details of the Engineering Options and the options that allow the system to be re configured with the relevant f
5. Message to SMS provider was not sent if FIRETEXT module is in use xxxx refers to unique fault code Vector Operating Manual 24 SYSTEM OPERATION continued Action after a Fire The following actions are in compliance with EN54 2 The responsible person should ensure that the following work is carried out as soon as possible after any fire and that normal use of the area is not resumed until the work is complete a If the system includes detectors containing radioactive material ionisation type then special precautions may be required and the servicing company should be consulted b Each device which may have been affected by the fire should be tested c Each fire alarm sounder should be tested d A visual examination should be made of areas which might have been damaged by the fire including power supplies control equipment and interconnections e Any defect found should be recorded in the log book and immediate action taken to rectify the defect f The servicing company should be advised and instructed to carry out a check of the system The responsible person should also ensure that the following work is carried out although this can take place after normal working has resumed a A check should be made of the state of the battery ies and charger b The servicing company should be instructed to carry out a full inspection and test of the system to verify its operation This may include cables which are
6. be fully documented and implemented immediately upon hearing the alarm After the event note the event details i e the activated zone and the device details if not already determined Vector Operating Manual 20 SYSTEM OPERATION continued Silencing the alarm Before the alarm sounders can be silenced or any other control function activated the CONTROLS keyswitch must be set to the ON position by inserting the key and turning it clockwise a quarter of a turn With the controls enabled press the SILENCE RESOUND ALARMS keypad button once The alarm sounders on the system are silenced The LCD will illuminate to indicate the current status The flashing common fire and zone LEDs change to steady The buzzer tone changes to an intermittent bleep The LCD continues to show the event information OAN NOTE If another device is activated the sounders are re energised and the new event information is displayed If there are multiple events on the system the information for each event may be viewed by using the toggle function with keypad buttons 2 and 8 The MORE LED is illuminated if there are other events The LCD shows the total number of events Resounding the alarm If having silenced the sounders it is necessary to reactivate them e g because there are still personnel within the building press the SILENCE RESOUND ALARMS keypad button again Resetting the system To restore the system to normal op
7. buried and areas that may be hidden c If the fire was not detected by the system or the response was unacceptably slow then the reasons for this should be investigated and a report obtained Consideration should be given to modifying or upgrading the system if necessary On completion of the work a certificate should be obtained Vector Operating Manual 25 SYSTEM OPERATION continued Action after a false Alarm Any alarm from the system should be treated as an alarm of fire until it can be proved to be false False alarms can lead to a loss of confidence in the system and the responsible person should take steps to minimise the risk of such occurrences There are prescribed levels for the rate of false alarms and if this level is exceeded the responsible person must instigate special attention to resolve the problem The average number of false alarms from an installation should not exceed one false alarm per year for each 25 detectors The following actions should be taken following a false alarm a Where possible identify the device which has initiated the alarm b Do not attempt to reset the system before establishing the cause c Record the event in the log book and inform the servicing company Action following a Fault If a fault is indicated on the system then the responsible person should ensure that the following actions are taken a Determine the area affected by the fault and decide whether special acti
8. digits in their own right but also have the following additional finctions Test button for lamps panel sounder and LCD Scroll up Generate full alarm evacuate Scroll left Select to view option Toggle silence resound alarm Scroll down System reset Access to menu Bottom right Mute internal buzzer JUIN Vector Operating Manual 11 LCD DISPLAY The LCD displays event information status information and the option menus It has two lines of text each with 40 characters and is backlit when there is an active event on the system or the menu options are accessed In the normal operating mode the backlight is off and the top line displays a default text message or user defined text The second line displays the current time and date e g VECTOR MULTILOOP SYSTEM NORMAL 9 36 15 03 04 When an event occurs the backlight is activated and the LCD shows the event details e g FIRE PANEL 01 ZONE 001 CARETAKERS OFFICE The display shows the event type i e Fire the zone that the activated device is in i e zone 3 the device location text and the number of events i e 1 Pressing button 5 reveals the device information Type i e manual call point address number and time and date of the event This button will function regardless of status of keyswitch NOTE Fault conditions on the system are suppressed when Fire events are present The SYSTEM FAULT LED is illuminated and faults can be viewed if
9. possible to disable individual addresses complete zones and or remote outputs The normal condition is enabled Field device See Device Fire procedure A written procedure describing the actions to be taken in the event of a fire alarm Procedures should also include the actions required after a fire and in a fault condition All staff should be conversant with the fire procedures Input output I O device A device which either monitors a remote function or provides a signal to control a remote function or both Used with analogue addressable systems to interface with other services Each I O unit has an address Loop The method of wiring an addressable or analogue addressable system whereby the circuit connecting the devices is wired from the panel and is returned to the panel to form a loop With this method a break in the loop circuit although indicated as a fault does not disable the operation of any devices Vector Operating Manual 6 GLOSSARY Continued Manual call point MCP Also known as a break glass unit initiates a fire alarm condition when activated MCPs comprise a standard call point assembly fitted with an input module on analogue addressable systems and have a unique address Sensor See Detector Short circuit isolator SCI A device connected to the loop circuit which limits the loss of devices in a short circuit condition They are generally fitted between each zone to restrict the loss of d
10. the Apollo protocol and supports the XP95 amp Discovery detection devices The full range of detectors sounder controllers I O modules conventional zone monitors etc can be incorporated into the system In addition to the 64 fire zones there are three further options Alarms Contacts and Inputs which have special functions enabling auxiliary devices to be configured for alternative operation also four groups are provided for cause and effects configura tion It is possible to power the panel from a remote power supply if required and input terminals are provided to facilitate the remote supply input and also to monitor the unit for mains and battery failure Access to the panel functions and configuration options is at different levels enabling restricted access to certain functions At the user level it is possible to disable parts of the system set the time and date put the system into walktest mode and view the system status Advanced options include configuration maintenance checks and fault finding mode The control panel incorporates an auto learn feature which enables the system devices to be recognised on initial power up Configuration of the system operation can be achieved via the panel controls or by downloading data created in a PC software program Vector Operating Manual 5 GLOSSARY Address An address is the unique identification applied to each field device in an addressable system Addressable system An add
11. Fieve Analogue Addressable Fire Control Panel for Apollo XP95 amp Discovery Protocol V4 1 and above Operating Manual MVEC 02 Issue 3 0 July 2008 NOTE PLEASE READ THIS MANUAL BEFORE HANDLING THE EQUIPMENT AND OBSERVE ALL ADVICE GIVEN IN IT THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID E S D La Vector Operating Manual CONTENTS INTOdUCHON a aia 4 Product OVErVIEW te att als 5 A E E cece sta aint ae E EAEE 6 Control Panels iia 8 Panel INdicCatorS oooooooocccnnncccccconono conc nono non cnn coco nn ncc cnn cnc cnn o ncnnnnnccnnns 10 Keypad it e SE 11 LCD DS Pola oe 2s can pkg a oa a ka a eal eM at en RET 12 Menu and Control Functions 0 0 00000 cee eecc cece cceeseeea esse eeeeeaas 13 Function BUNOS seinen menean ni a n cand scene sees ninio aseos 13 Access LevelSo misotrol alcista 14 MenutiRlow Ghartinccsectac Sodenedhtus dhe riot AE EE APEN EEEE EAN ETT EE 16 Key tO Mon rores sAr e EASA E EREEREER theses Seed ATAS aa 17 Disablement Flow Chart o oocccncncccocccncnnncnnncnncnnnnnnnnnnnnnnnna nono nannnnnnannnnnnnnancns 18 Engineering Options oocococcnccncccnnconcncononcnnnncononnnnannnnnnnnnnnnonanconcnncnannenenicnens 19 System OP AA ane Mepererlsartale tt ineupieree ace taeunideasiadd aided 20 Fire Alaris a btt is dass 20 Silencing the Alaf Meurded a neste estates aes 21 Resetting the SyStem cccceeeee cece eee e ee eee e a eens aet
12. L FUNCTIONS Continued Menu flow chart YES TOGGLE 2 amp 8 nue EXIT VIEW ACTIVE FAULTS gt kev 5 ro view FAULTS VIEW ACTIVE SELECT DISABLEMENTS lt LOOP kev 5 ro view DISABLEMENTS VIEW CLEAR EVENT L gt zb 4 zi NL ad LOGS gt VIEW SET sj ENTES PAGE 2 FAULT LOG 4 P DISABLEMENTS MANAGER da CODE gt VIEW 3 USER LOG CLEAR SET CLOCK rh ENTER TIME amp DATE 4 LOGS USING KEYPAD ACTIVATE ENTER SELECT ZONE IN SOUNDER 6 TEST 5b MANAGER p TEST elo ON OFF 2 8 MODE CODE 2 8 scroll OR ZONAL 0 ALL ZONES 1 v A print alarm log 80 G PRINT OPTIONS 2 8 2 print fault log j PLEASE a gt print user log 8 ENGINEERING __ REFERTO OPTIONS ENGINEERS print MANUAL parameters Vector Operating Manual 16 MENU AND CONTROL FUNCTIONS Continued Key to menu 1 View active faults This option provides a method of viewing faults on the system when there are active fire events present 2 View active disablements This option allows the user to identify parts of the system that have been isolated 3 View Clear event logs This option allows the Alarm log and the Event log to be inspected and if required can be cle
13. ared 4 Set disablements This option allows remote outputs sounders loop and zones to be disabled and also enabled manually or automatically at a preset time and date An optional managers code can be used to allow access to this function 5 Set clock Allows the time and date to be entered via the keypad 6 Activate test mode Allows zones to be tested individually or all together With or without sounder An optional managers code can be used to allow access to this function 7 Engineering options This option requires a security code to be entered before allowing entry Allows the system to automatically learn new devices To connect to a PC To set panel parameters To set system parameters To monitor individually the device response change loop poll direction and activate the device outputs To perform a maintenance check set a threshold and list all devices within this threshold To check a loop corruption counter To set a Management access code to restrict access to the Set Disablements option and the Activate Test Mode facility AA A lt A A O Vector Operating Manual 17 MENU AND CONTROL FUNCTIONS Continued Set Disablements MENU SET DISABLEMENTS SET REMOTE CONTACTS REMOTE SIGNAL DISABLEMENTS COMMON FIRE COMMON FAULT E gt SET SOUNDERS sobe DISABLEMENT ISO LOOP MODULES EJ SET Loop SELECT TOGGLE 5 ISOLATE LOOP No 1 4 ISO NORMAL scroll
14. eration after a fire alarm it is necessary to reset the control panel by pressing the RESET button Key 9 on keypad All the LEDs illuminate for 3 4 seconds lamptest function following which the panel reverts to its normal mode NOTE 1 It is not possible to reset the system until the alarms have been silenced 2 The system will not reset if the cause of the alarm is still present i e broken glass in call point or smoke heat in the vicinity of a detector Vector Operating Manual 21 SYSTEM OPERATION continued Evacuate The EVACUATE button keypad 3 may be operated at any time to activate the alarm sounders The CONTROLS keyswitch must be in the ON position Press the EVACUATE button once The sounders are energised and the common FIRE LED will flash To turn the Evacuate signal off Press the SILENCE button keypad 6 This will be displayed on the LCD and the flashing FIRE LED will change to steady Press RESET keypad 9 Panel buzzer The internal panel buzzer operates whenever an abnormal event is on the system lit operates in the following modes Fire Evacuate Fast Pulse Fault Slow Pulse Disablement Double Pulse Silenced Intermittent Bleep Monitoring The control panel internal circuitry is fully supervised in accordance with the requirements of EN54 2 1998 and indicates a failure as a fault condition Loop and sounder circuits are monitored for open circuit and short circuit fault conditions
15. etection to one zone in accordance with BS 5839 Part 1 SCls do not have an address and do not limit the number of devices on a loop Sounder A device which provides an audible warning of a fire alarm condition Sounders may be bells but are often electronic devices with a range of sound options and volume control In most systems the sounders must achieve a minimum level of audibility throughout the protected premises System type Systems complying with BS 5839 Part 1 are classifed depending on the application There are two main categories i e Life Protection L type and Property Protection P type Each category is sub divided depending on the level of protection required for the particular risk Zone A zone is the sub division of a building separated by fire resisting walls to form a compartment When applied to a fire alarm control panel it refers to the number of fire indicators available to identify the location of a fire within a building Each fire compartment generally comprises one or more zones Each floor of a multi storey building is a separate zone and each vertical structure staircase liftshaft etc is a separate zone Smaller zones may be required in areas of high risk In an analogue addressable system the zonal indicator denotes the general area of the fire whilst the LCD indicates the actual activated device Vector Operating Manual 7 CONTROL PANEL Panel Controls Logo Badge CONTROLS OFF EVACUATE ALARM
16. low charts can be found in the Installation and Commissioning Manual ESS ee A EEE Vector Operating Manual 19 SYSTEM OPERATION Fire alarm During normal operation the only active indication on the control panel is the green Supply Healthy LED The LCD shows the system normal message and the time and date The backlight is off The control keyswitch should be in the OFF position and the key should be removed and stored in a secure place readily available when required If a manual call point is activated or an automatic detector senses smoke or heat a fire alarm signal is generated and the following occurs 1 The alarm sounders operate in accordance with the programmed configuration This is normally a general evacuation continuous alarm throughout the building but may be an alert intermittent signal or alarm in certain parts of the building only 2 The common FIRE LED flashes on the front panel 3 The relevant zone LED flashes 1 64 4 The LCD illuminates and shows the event information 5 The internal buzzer pulses rapidly 6 The remote contacts operate and signal the fire brigade if this has been configured in the system 7 Remote control functions are initiated in accordance with the program e g doors closed ventilation shutdown etc 8 Event details are printed if a printer is fitted 9 SMS text messages are sent if FIRETEXT module is fitted The actions to be taken in the event of a fire alarm should
17. n raur D O OOOO o Dd FIRE SYSTEM ALARM REMOTE REMOTE ALARM FAULT FAULT ACTIVE DISABLED Fire Indicates the presence of a Fire Alarm signal or an Evacuate command Test Mode Active Indicates system is in the Engineers Test mode with limited operational capabilities Disablement Active Indicates that part of the system is disabled isolated Supply Healthy Indicates that the Mains or Battery supply is present Common Fault Indicates that a fault is present on the system The LCD will show the details Pre Alarm Indicates that a detector has recorded a higher than normal analogue value which could signal an impending fire condition System Fault Indicates that the processor has halted This can only be reset by an engineer Alarm Fault Indicates a fault on the alarm circuit Remote Active Indicates that the Remote output relay has been activated Remote Disabled Indicates that the Remote output relay has been isolated for maintenance or testing ARW Auto Reset Warning Indicates processor has automatically re started Must be reset by Reset System Key 9 on keypad More Indicates that there are more events PSU Indicates power supply failure The LCD will show the details Fire Detection Zones Sixteen indicators Zones 1 16 to show which area group of devices has activated in a fire condition Vector Operating Manual 10 KEYPAD TEST EVACUATE LAMPS ALARM MUTE BUZZER All the numbered keys are
18. na a eae dese ede ea esse een essa ees 21 EVACUALE E cucehdahtcaneccuuete beads once nensduben deekeeorssave idee imansemcasemeras 22 PanelBUZZO Ri ct2cecdeeshntd dented aaa a a tra 22 FaultGONdIIONS aida lara ida A era ET I 23 Faull Messages inicia A RA 24 Action atera MO et ha E aaa 25 Action after a False alarM ooo ococcnccccccconcnccnnnnnnn canon cnn nn nnn nn nn E Aa a Aaaa 26 Action following a rFaUliiriioni ii oo did 26 Avoiding false Ala iio acid 27 Vector Operating Manual 3 INTRODUCTION The Vector is a multi loop analogue addressable fire alarm control panel equipped with up to 64 zones It has been designed In accordance with European standards EN54 2 and EN54 4 Fire Detection and Alarm systems Control and Indicating Equipment It utilises the latest surface mount technology with a flash programmable 16 bit Micro controller for easier software updates It operates with the Apollo XP95 amp Discovery protocol and supports the Apollo range of field devices Two internal sounder circuits are provided per loop and additional sounder circuits can be connected to loop wired modules The control panel is programmable via the keypad controls or via a PC allowing the configuration to be created off site and downloaded In addition to the requirements of EN54 2 the control panel has the following facilities Test Condition to allow the automatic resetting of zones in alarm for testing purposes EN54 2 Section 10 option with
19. on such as fire patrols are needed in that area b If possible determine the reason for the fault or note the activities in the area immediately prior to the fault occurring c Record the fault in the log book and advise the servicing company Vector Operating Manual 26 SYSTEM OPERATION continued Avoiding false Alarms Generally false alarms are avoided by good system design and a properly designed system should provide troublefree service for many years However changes can occur in the layout of a building or the uses to which it is put which can affect the reliability of the system An awareness of the type of situation which can cause false alarms to be generated may prevent the effectiveness of the system being jeopardised Typical problem areas are as follows Manual call points MCPs do not normally cause problems unless they are sited where they can be inadvertently damaged e g by fork lift trucks or trolleys etc One cause of false alarms from call points is malicious damage i e vandalism which can occur if they are in an area accessible to the public Detectors Probably the largest single cause of false alarms smoke detectors can be susceptible to a number of factors in addition to smoke Careful siting eliminates most of the problems but smoke detectors can be activated by any of the following Insects can affect systems at certain times of the year and are more of a problem in some parts of
20. on can have serious effects on the operation of the equipment and should only be undertaken by a competent person who has information concerning the devices installed and the specified operational requirements The system should be fully tested after any alterations to the configuration program Level 2 Options Menu View active faults View active disablements View Clear event Logs Set disablements Set Clock Activate test mode Engineering options SON OR est Vector Operating Manual 14 MENU AND CONTROL FUNCTIONS Continued Menu Procedures The following procedures are common to all of the menu options and should be understood before attempting to alter the system status To access the Options Menu the CONTROLS key switch must be in the ON position Press the MENU button on the KEYPAD to display the following SELECT MENU OPTION 1 VIEW ACTIVE FAULTS Use the 2 and 8 keypad buttons to toggle scroll to the required option then press 5 to display the required information At any time pressing MENU again will return you to the menu options or in some cases return you to the last step Depending on the option selected there will be sub menu items which can be accessed by the 5 key or scrolled across to using the 4 and 6 keypad buttons When satisfied with the data obtained press MENU to return to the initial screen AA A eee sea Vector Operating Manual 15 MENU AND CONTRO
21. operation when the fault condition clears however certain faults e g SYSTEM FAULT require the CPU to be reset Vector Operating Manual 23 SYSTEM OPERATION continued The following list describes the typical fault messages Any fault that does not have a logical explanation should be immediately reported WARNING High voltages are present within the panel which could cause fatal shock The front door should only be opened by a competent engineer There are no user serviceable parts inside the panel IF INDOUBT CALL AN ENGINEER Fault messages The following events are detected and reported Message Fault Condition No response Device removed Type error Device fault wrong device type installed Loop open circuit Loop circuit open Loop short circuit Loop circuit short Power supply fault PSU failed Sounder short open Open short circuit on sounder circuit Mains fail Mains failed Battery fault Battery disconnected max 30s delay Earth fault Earth fault Double resp onse Duplicate address CPU fault CPU failed Network Communications failure Charger fault PSU failure external only Voltage fault 28 volts outside spec lt 22v gt 30v Device fault Analogue value low Warning Prog switch on SW 2 on DIL switch set to on Bad response Loop data corruption Ancillary relay fault A device is unplugged from an ancillary unit Ancillary sounder fault which relies on it for operation GPRS fault xxxx
22. required via the View Active Faults option when button 5 is pressed NOTE Keyswitch must be on to view active faults with button 5 The bottom line displays a text message describing the device location In the engineering mode menu options are displayed as follows SELECT MENU OPTION 5 SET CLOCK The Keypad is used to navigate through the menu options and select functions as described in the installation and commissioning manual Vector Operating Manual 12 MENU AND CONTROL FUNCTIONS General The control panel incorporates facilities to alter the status of the system e g it is possible to isolate parts of the system if there is work in progress or a particular device is faulty and causing unwanted alarms The system can be put into test mode to allow an engineer to activate devices without causing a general alarm and the time and date can be changed e g for British Summer Time These functions are accessible to the user at access level 2 but care should be exercised when utilising the functions as it is possible to disable some or all of the system It is recommended that before attempting to enter the options menu the features are fully understood and the operator is familiar with the controls used to navigate the menus and select options Function buttons Four of the keypad buttons are used as function buttons when the options menu is invoked Most of the panel functions including configuration are con
23. requirements Fire Alarm Devices to enable an audible warning to be sounded throughout a premises upon the detection of a fire condition or the operation of a manual call point EN54 2 Section 7 8 option with requirements In addition to the requirements of EN54 2 all control panels have voltage free relay contacts for fire and local fire which operate upon fire condition These are to be used for local control and signalling The Vector has individually isolatable panel contacts via the menu with an Auto enablement feature and the option to remove all disablements The menu is comprehensive yet easy to use allowing electrical isolation of the loop via the keyboard The menu includes an enhanced test mode with or without sounders allowing all zones to be tested simultaneously if required It has a real time clock with back up utilising a smart cap rather than a battery thus eliminating battery life issues The Vector incorporates a very fast auto learn sequence only learning selected parts of the loop and if required can unlearn devices from the system It supports the new Apollo ancillary base sounders and relays local zonal or common operation A device monitoring mode allows activation of the device outputs and control of the loop polling direction Also there is a selectable maintenance scanning threshold The Vector has genuine peer to peer 16 panel networking utilising reliable CAN bus technology with response settings to evacua
24. ressable system is one where each field device has an address which can be identified and displayed in an abnormal condition or for normal monitoring purposes The address is normally accompanied by a user defined text message describing the device location e g First floor corridor Addressable devices are usually wired in a loop configuration Analogue addressable system In addition to device addressability the detectors employed are analogue devices transmitting data to the control panel which is then analysed and processed so that the appropriate condition can be displayed Analogue systems can provide greater immunity to false alarms and give advance information about impending fire conditions Automatic system An automatic system is one which includes detectors of some description as opposed to one fitted with manual call points only Device A component of an addressable system connected to the loop circuit It can be an input device such as a detector or call point or an output device such as a relay or sounder controller Devices in an addressable system are uniquely numbered and there is a finite number which can be connected to a single loop Detector A device which detects either flame smoke or heat Analogue detectors are often referred to as sensors because of their ability to transmit variable data to the control panel Disabled The condition of the system when part or parts of it have been isolated for any reason It is
25. te 1st alarm 2nd alarm precinct and fault signals with programmable responses for loop sounders panel sounder circuits remote relays and loop modules This User s manual is supplied with the control panel which in addition to explaining the operation of the panel incorporates a log book and details of the user s responsibilities for testing and maintaining the system It is intended that the user s manual forms part of the documentation package passed to the customer on completion Vector Operating Manual 4 PRODUCT OVERVIEW The control panel is a 1 4 loop 64 zone analogue addressable unit with integral power supply and space for a standby battery It has two sounder circuits per loop auxiliary volt free contacts and various remote inputs and outputs The control panel comprises a sheet steel enclosure suitable for wall mounting with a hinged lockable front access door It can be semi recessed if required by using a suitable flushing bezel Cable entry is via the top or rear of the cabinet 20mm knockouts are provided in the top and in the rear A separate key fits the door lock and the control enable key switch A 2 x 40 character backlit LCD is fitted to display event information and function and configuration menus Alarm and status information is provided by LED indicators and there is a 12 button keypad which controls the system and allows access to the function and configuration options The control panel operates with
26. the country Detector manufacturers have long been aware of the problem and have introduced more sophisticated measures to eliminate them Cooking a common cause of false alarms is people cooking especially in bedrooms and mess rooms where toasters and similar appliances are often used Air currents draughts from open windows and air flows from ventilation systems or air conditioning units can activate detectors Smoking can activate detectors but is usually easily resolved by eliminating smoking in the immediate area e Steam fumes Steam from kitchens and laundries and fumes from vehicles industrial processes etc can all cause unwanted alarms e Heat detectors are obviously affected by any form of heat and care should be taken with the siting of heating appliances in the vicinity of detectors Vector Operating Manual 27
27. trolled by these buttons which have the following functions MENU The Menu button is used to initially invoke the options menu Press once to enter the Menu and press again to Exit 2 and 8 The 2 and 8 buttons are used to move to and then select the Menu options Once an option has been selected the Menu button should be pushed again to exit 5 The 5 button on the keypad is pressed when the option selected needs to be viewed or to view the text or an active event 4 and 6 The 4 and 6 buttons are used to position the cursor along a full display line in order to adjust various options available Vector Operating Manual 13 MENU AND CONTROL FUNCTIONS Continued Access levels To prevent unauthorised operation of the panel controls and functions access is restricted in accordance with the requirements of EN54 2 The following access levels apply Level 1 Full restrictions The internal buzzer MUTE only is available at this level and Scroll and Select if Fire is active Level 2 CONTROL keyswitch ON The control switches are operable and limited menu fuctions available Level 3 An access code must be entered to gain access to the configuration and advanced options An additional access code must be entered in order to set the Disablements and to activate the Test Mode Level 4 Configuration software Download facilities are available for off site programming NOTE Amending the system configurati