FX3U-4AD-PTW-ADP USER`S MANUAL

image

Contents

1. Series Hardware Manual Manual No JY997D28601 FX3UC 32MT LT 2 Hardware Manual Manual No JY997D31601 Regarding the standards that relate to the main unit please refer to either the FX series product catalog or consult with your nearest Mitsubishi product provider Attention e This product is designed for use in industrial applications Note e Authorized Representative in the European Community Mitsubishi Electric Europe B V Gothaer Str 8 40880 Ratingen Germany Caution for EC Directive The analog special adapters have been found to be compliant to the European standards in the aforesaid manual and directive However for the very best per formance from what are in fact delicate measuring and controlled output device Mitsubishi Electric would like to make the following points As analog devices are sensitive by nature their use should be considered care fully For users of proprietary cables integral with sensors or actuators these users should follow those manufacturers installation requirements Mitsubishi Electric recommend that shielded cables should be used If NO other EMC protection is provided then users may experience temporary loss or accuracy between 10 in very heavy industrial areas However Mitsubishi Electric suggest that if adequate EMC precautions are fol lowed for the users complete control system users should expect accuracy as specified in this manual e Sensitive analog cable should n
2. fire malfunctions User s Manual MODEL CODE specifications for I O wiring deterioration or damage may occur Hardware Edition 09R533 installation and maintenance pA pis 7 a x When drilling screw holes or wiring make sure cutting or wire debris does not FX3U Series JY997D16501 Explains FX3U Series PLC enter the ventilation slits User s Manual MODEL CODE specifications for I O wiring Failure to do so may cause fire equipment failures or malfunctions Hardware Edition 09R516 installation and maintenance Do not touch the conductive parts of the product directly FX3UC Series JY997D28701 Explains FX3UC Series PLC Doing so may cause device failures or malfunctions User s Manual MODEL CODE specifications for I O wiring Connect special adapter securely to their designated connectors Hardware Edition 09R519 installation and maintenance Loose connections may cause malfunctions How to obtain manuals For product manuals or documents consult with the Mitsubishi Electric dealer from who you purchased your product 3 Wiring 3 2 Power Supply Wiring 4 Specifications 4 4 Performance Specifications W
3. 2 holes of 4 5 0 18 mounting screw M4 screw Not used when connecting to FX3GC FX3UC Series PLC 6 POWER LED green Lit while 24 V DC power is supplied properly to terminals 24 and 24 7 Terminal block European type Connect platinum resistance thermometer Pt100 three wire type and 24 V DC power supply 8 Special adapter connector Used to connect this special adapter to PLC main unit or special adapter 9 DIN rail mounting hook 10 Special adapter fixing hook 11 Special adapter connector Used to connect communication or analog special adapters to the left side of the PTW ADP 2 Installation For installation uninstallation details refer to the respective PLC User s manual Hardware Edition INSTALLATION PRECAUTIONS Z WARN ING e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product INSTALLATION PRECAUTIONS Z CAUTION e Use the product within the generic environment specifications described in PLC main unit manual Hardware Edition Never use the product in areas with excessive dust oily smoke conductive dusts corrosive gas salt air Cl2 H2S SO2 or NO2 flammable gas vibration or impacts or expose it to high temperature condensation or rain and wind If the product is used in such conditions electric shock fire malfunctions deterioration or damage may oc
4. pitch Special adapter connector cover is removed Weight Approx 0 1 kg 0 22 Ibs 1 DIN rail mounting groove DIN rail DIN46277 2 Name plate 3 Special adapter slide lock Used to connect additional special adapters onto the left side of this special adapter 4 Special adapter connector cover Remove this cover to connect additional special adapters to the left side 5 Direct mounting hole 2 holes of 4 5 0 18 mounting screw M4 screw Not used when connecting to FX3GC FX3UC Series PLC 6 POWER LED green Lit while 24 V DC power is supplied properly to terminals 24 and 24 7 Terminal block European type Connect platinum resistance thermometer Pt100 three wire type and 24 V DC power supply 8 Special adapter connector Used to connect this special adapter to PLC main unit or special adapter 9 DIN rail mounting hook 10 Special adapter fixing hook 11 Special adapter connector Used to connect communication or analog special adapters to the left side of the PTW ADP 2 1 Connection to the PLC This section describes the connection method to the PLC FX3U Series PLC is used for the following example For installation method to other PLCs refer to the respective PLC User s manual Hardware Edition Procedure 1 Turn off the power Disconnect all the cables connected to the PLC main unit and special adapter and demount the main unit and sp
5. used 0 A ground terminal of PLC PLC main unit Insulation resistance 5 MQ or more by 500 V DC main unit 3 4 Grounding megger 3 1 Applicable cable and terminal tightening torque Grounding should be performed as stated below 3 1 1 Terminal block European type e The grounding resistance should be 100 or less 4 3 Power Supply Specifications 1 Wire size e Independent grounding should be performed for best results The power supply wire should use 22 20 AWG wire When independent grounding is not performed perform shared grounding of the Item Specification Wiring to a Pt100 platinum resistance thermometer should be used the following figure A AID conversion 24 V DC 20 15 50 mA for 24 V DC cable of it or a twisted shielded cable For details refer to the respective PLC User s manual Hardware Edition circuit driving power Connect a 24 V DC power supply to the terminal block 2 Applicable cable Other Other Other 5V DC 15 mA ai PLC i PLC i PLC i ivi Type Wire size equipment equipment equipment See aig 5 V DC power is supplied from the internal power supply of main unit Single wire 0 3 mm to 0 5 mm2 AWG22 to 20 I l ee A Independent grounding Shared grounding Common grounding 2 wire 2 pieces of 0 3 mm AWG22 Best condition Good condition Not allowed 3 Termination of cable end The grounding wire size should be AWG 22 20 0 3 0 5 mm This manual confers no industrial property rights or any rights of any other kind
6. 0 35 0 31 e Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with 2 6mm 0 1 14mm 0 55 Mitsubishi Electric lt r e This product has been manufactured under strict quality control However When using a stick terminal with insulating sleeve choose a wire with proper when installing the product where major accidents or losses could occur if the cable sheath referring to the above outside dimensions or otherwise the wire product fails install appropriate backup or failsafe functions in the system cannot be inserted easily The tightening t t be 0 22 to 0 25 Nem D t tighten terminal Serie exceeding the specified torque Failure to do sine cause equipment MITSUBISHI ELECTRIC CORPORATION failures or malfunctions HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN JY997D29101G MITSUBISHI ELECTRIC PROGRAMMABLE CONTROLLERS MELSEGAF JAPANESE ENGLISH FX3u 4AD PTW ADP USER S MANUAL Manual Number JY997D29101 Revision G i U Date April 2015 This manual describes the part names dimensions mounting and specifications of the product Before use read this manual and the manuals of all relevant products fully to acquire proficiency in handling and operating the product Make sure to learn all the product information safety information and precautions St
7. 0k2 cho rau to ve k pan failures in the product After transportation verify the away from the main circuit high voltage line or load line j Lot I gt OPETESONS ORME PISCUe A r Lo 2 Ground the shield of the analog input output cable at one point on the j 100kQ 4 1 Applicable PLC signal receiving side However do not use common grounding with heavy T g A electrical systems Model name Applicability Mak t ly wire to the terminal block E t i dna iti tha folowingiarecautions ock European type it FX3S Series PLC Ver 1 00 or later from first production mpar characteristics Failure to do so may cause electric shock equipment failures a short circuit Pt100 4 7kQ 4 7kQ FX3G Series PLC Ver 1 00 or later from first production wire breakage malfunctions or damage to the product 400kQ n cho i The disposal size of the cable end should follow the dimensions 7 Lot FAGE Series PLC Ver 1 40 onlater from first production described in the manual Lo ae FX3U Series PLC Ver 2 20 or later from first production Tightening torque should follow the specifications in the manual T lo ay Serius Die Ver 1 30 or later from the production manufactured in August Twist the end of strand wire and make sure that there are no loose wires SUC Series 2004 with SER No 48 Do not solder plate the electric wire ends External er supply e The photocoupler is adopted to insulate the analog input Do not connect more than the s
8. IRING For the power supply wiring refer to the following manual STARTUP AND it Description ie em PRECAUTIONS NWARNING FX3S FX3G FX3GC FX3U FX3UC Series User s Manual Analog Control Edition MAINTENANCE Z CAUTION Centigrade C Fahrenheit F i 7 PRECAUTIONS e Make sure to cut off all phases of the power supply externally before 3 3 Selection of platinum resistance thermometer sensors inputsianal 3 wire platinum resistance thermometer sensor Pt100 attempting installation or wiring work For the terminal configuration refer to Section 1 2 e Do not disassemble or modify the PLC B g JIS C 1604 1997 Failure to do so may cause electric shock or damage to the product Precautions on platinum resistance thermometer wiring Doing so may cause fire equipment failures or malfunctions Rated Type of platinum resistance thermometer For repair contact your local Mitsubishi Electric representative E 1400 C to 600 C 448 F to 1112 F WIRING Select Pt100 3 wire platinum resistance thermometer sensors e Do not drop the product or exert strong impact to it range PRECAUTIONS CAUTION This thermometer will not be affected by voltage drop in the cable connection area Doing so may cause damage and will ensure accurate measurement Digital output 1000 to 6000 1480 to 11120 s When drilling screw holes or wiring make sure cutting or wire debris does e Separate the cable of the platinum resistance thermometer sensors from th
9. JY997D16701 analog control and foneitor Tor sansa details refer to the respective PLC User s manual User s Manual MODEL CODE programming method for ii 09R619 FX3S FX3G FX3GC FX3U Analog Control Edition FX3UC Series PLC INSTALLATION PRECAUTIONS Z WARNING FX3S FX3G FX3GC FX3U FX3UC Series JY997D16601 Describes PLC programming e Make sure to cut off all phases of the power supply externally before attempting Programming Manual MODEL CODE for basic applied instructions installation or wiring work Basic amp Applied Instruction 09R517 and devices Failure to do so may cause electric shock or damage to the product Edition FX38 Series JY997D48601 Explains FX3S Series PLC INSTACEATION Z CAUTION User s Manual MODEL CODE specifications for I O wiring PRECAUTIONS Hardware Edition 09R535 installation and maintenance e Use the product within the generic environment specifications described in PLC FX3G Series JY997D31301 Explains FX3G Series PLC main unit manual Hardware Edition User s Manual MODEL CODE specifications for I O wiring Never use the product in areas with excessive dust oily smoke conductive dusts Hardware Edition 09R521 installation and maintenance corrosive gas salt air Cl2 H2S SO2 or NO2 flammable gas vibration or F x impacts or expose it to high temperature condensation or rain and wind FX3GC Series Jy997D45401 Explains FX3GC Series PLC If the product is used in such conditions electric shock
10. JY997D29101G MITSUBISHI ELECTRIC PROGRAMMABLE CONTROLLERS MELSEGAF JAPANESE ENGLISH FX3u 4AD PTW ADP USER S MANUAL Manual Number JY997D29101 Revision G i U Date April 2015 This manual describes the part names dimensions mounting and specifications of the product Before use read this manual and the manuals of all relevant products fully to acquire proficiency in handling and operating the product Make sure to learn all the product information safety information and precautions Store this manual in a safe place so that it can be taken out and read whenever necessary Always forward it to the end user Registration The company and product names described in this manual are registered trademarks or the trademarks of their respective companies Effective April 2015 Specifications are subject to change without notice 2007 Mitsubishi Electric Corporation Safety Precaution Read these precautions before use This manual classifies the safety precautions into two categories Z WARNING and A CAUTION Indicates that incorrect handling may cause hazardous conditions resulting in death or severe injury Z WARNING Indicates that incorrect handling may cause hazardous conditions resulting in medium or slight personal injury or physical damage Z CAUTION Depending on the circumstances procedures indicated by A CAUTION may also c
11. Mitsubishi products and to other duties A For safe use e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life e Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi Electric This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN
12. Strip the coating of strand wire and twist the cable core before connecting it e The grounding point should be close to the PLC and all grounding wire should be nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be or strip the coating of single wire before connecting it as short as possible held responsible for any problems involving industrial property rights which may An alternative connection is to use a ferrule with insulating sleeve occur as a result of using the contents noted in this manual lt Reference gt Warranty Manufacturer Model Caulking tool El Mitsubishi will not be held liable for damage caused by factors found not to be A CRIMPFOX 6 the cause of Mitsubishi opportunity loss or lost profits caused by faults in the Phoenix Contact Co Ltd Al 0 5 8WH E h A or CRIMPFOX 6T F Mitsubishi products damage secondary damage accident compensation z z caused by special factors unpredictable by Mitsubishi damages to products 1 Old model name CRIMPFOX ZA 3 other than Mitsubishi products and to other duties 2 Old model name CRIMPFOX UD 6 Strand wire single wire Stick terminal with insulating sleeve A For safe use Insulation sleeve Contact area Crimp area e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in Cc 9mm 8mm a device or system used in purposes related to human life
13. ators these users should follow those manufacturers installation requirements Mitsubishi Electric recommend that shielded cables should be used If NO other EMC protection is provided then users may experience temporary loss or accuracy between 10 in very heavy industrial areas However Mitsubishi Electric suggest that if adequate EMC precautions are fol lowed for the users complete control system users should expect accuracy as specified in this manual e Sensitive analog cable should not be laid in the same trunking or cable conduit as high voltage cabling Where possible users should run analog cables separately e Good cable shielding should be used When terminating the shield at Earth ensure that no earth loops are accidentally created e When reading analog values EMC accuracy can be improved out by averaging the readings This can be achieved either through functions on the analog special adapters or through a users program 1 Outline FX3U 4AD PTW ADP hereinafter called PTW ADP is an analog special adapter for measuring temperature via four channels three wire sensors of a connected Pt100 platinum resistance thermometer 1 1 Incorporated Items Verify that the following product and items are included in the package Product FX3U 4AD PTW ADP Pt100 temperature sensor input special adapter 1 2 External Dimensions Part Names and Terminal Layout 10 5 106 4 18 98 3 86 mounting hole
14. ause severe injury It is important to follow all precautions for personal safety Associated Manuals Applicable standards FX3U 4AD PTW ADP units comply with the EC Directive EMC Directive and UL standards UL cUL Further information can be found in the following manual FX3S Series Hardware Manual Manual No JY997D48301 FX3G Series Hardware Manual Manual No JY997D46001 s Hardware Manual Manual No JY997D45201 s Hardware Manual Manual No JY997D18801 FX3uc D DS DSS Series Hardware Manual Manual No JY997D28601 FX3UC 32MT LT 2 Hardware Manual Manual No JY997D31601 Regarding the standards that relate to the main unit please refer to either the FX series product catalog or consult with your nearest Mitsubishi product provider Attention e This product is designed for use in industrial applications Note e Authorized Representative in the European Community Mitsubishi Electric Europe B V Gothaer Str 8 40880 Ratingen Germany Caution for EC Directive The analog special adapters have been found to be compliant to the European standards in the aforesaid manual and directive However for the very best per formance from what are in fact delicate measuring and controlled output device Mitsubishi Electric would like to make the following points As analog devices are sensitive by nature their use should be considered care fully For users of proprietary cables integral with sensors or actu
15. bove description with a special adapter and perform the procedure as indicated Please replace the following procedures similarly 5 Connect the special adapter fig C to the main unit as shown on the right 6 Slide back the special adapter slide lock fig B of the main unit to fix the special adapter fig C 3 Connection precautions Connect all the high speed I O special adapters before connecting other special adapters when they are used in combination Do not connect a high speed I O special adapter on the left side of any special adapters other than other high speed I O special adapters 3 Wiring WIRING PRECAUTIONS Z WARN ING e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product WIRING PRECAUTIONS Z CAUTION e When drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Make sure to observe the following precautions in order to prevent any damage to the machinery or accidents due to abnormal data written to the PLC under the influence of noise 1 Do not bundle the power line or shield of the analog input output cable together with or lay it close to the main circuit high voltage line or load line Otherwise noise disturbance and or surge
16. cur When drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Do not touch the conductive parts of the product directly Doing so may cause device failures or malfunctions Connect special adapter securely to their designated connectors Loose connections may cause malfunctions 2 1 Connection to the PLC This section describes the connection method to the PLC FX3U Series PLC is used for the following example For installation method to other PLCs refer to the respective PLC User s manual Hardware Edition Procedure 1 Turn off the power Disconnect all the cables connected to the PLC main unit and special adapter and demount the main unit and special adapter mounted on DIN rail or mounted directly using screws 2 Install an expansion board to the main unit For the expansion board installation procedure refer to the following manual FX3u Series User s Manual Hardware Edition Remove the special adapter connector cover on the expansion board fig A When connecting this product to another special adapter please replace the expansion board in the above description with a special adapter and perform the procedure as indicated 4 Slide the special adapter slide lock fig B of the main unit When connecting this product to another special adapter please replace the main unit in the a
17. e other DISPOSAL Resolution 0 2 to 0 3 C 0 4 to 0 5 F not enter the ventilation slits 2 r i motive power cables or areas easily affected by inductive noise of the commercial PRECAUTIONS Z CAUTION Failure to do so may cause fire equipment failures or malfunctions power etc 0 5 for full scale when ambient temperature is 25 C 5 C Make sure to observe the following precautions in order to prevent any ae e Please contact a certified electronic waste disposal company for the Total accuracy 1 0 for full scale when ambient temperature is in the range damage to the machinery or accidents due to abnormal data written to the Example of platinum resistance thermometer wiring environmentally safe recycling and disposal of your device of 0 to 55 C PLC under the influence of noise PTW ADP e FX3U FX3UC Series PLC 200 us 1 Do not bundle the power line or shield of the analog input output cable hgmnorneter ais ERANSPORTATIONANDI A CAUTION E The data will be updated at every scan time of the PLC hoe with or lay it close to the main circuit high voltage line or load ne e FX3S FX3G FX3GC Series PLC 250 us Otherwise noise disturbance and or surge induction are likely to take Pt100 Terminal 4 7kQ 4TKQ The product is a precision instrument During transportation avoid any impacts The data Will be updated at every scan time of the PLC place As a guideline lay the control line at least 100mm 3 94 or more cue wire __ block 10
18. ecial adapter mounted on DIN rail or mounted directly using screws 2 Install an expansion board to the main unit For the expansion board installation procedure refer to the following manual FX3u Series User s Manual Hardware Edition Remove the special adapter connector cover on the expansion board fig A When connecting this product to another special adapter please replace the expansion board in the above description with a special adapter and perform the procedure as indicated 4 Slide the special adapter slide lock fig B of the main unit When connecting this product to another special adapter please replace the main unit in the above description with a special adapter and perform the procedure as indicated Please replace the following procedures similarly 5 Connect the special adapter fig C to the main unit as shown on the right 6 Slide back the special adapter slide lock fig B of the main unit to fix the special adapter fig C 3 Connection precautions Connect all the high speed I O special adapters before connecting other special adapters when they are used in combination Do not connect a high speed I O special adapter on the left side of any special adapters other than other high speed I O special adapters Manual name Manual No Description Accessories User s manual This manual Deserib TEET 2 Installation oe RASCE
19. induction are likely to take place As a guideline lay the control line at least 100mm 3 94 or more away from the main circuit high voltage line or load line 2 Ground the shield of the analog input output cable at one point on the signal receiving side However do not use common grounding with heavy electrical systems Make sure to properly wire to the terminal block European type in accordance with the following precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual Tightening torque should follow the specifications in the manual Twist the end of strand wire and make sure that there are no loose wires Do not solder plate the electric wire ends Do not connect more than the specified number of wires or electric wires of unspecified size Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed Make sure to properly wire the terminal block in accordance with the following precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual of the PLC main unit Tightening torque should follow the specifications in the manual of
20. ns Basic amp Applied Instruction 09R517 and devices Edition FX3S Series JY997D48601 Explains FX3S Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R535 installation and maintenance FX3G Series JY997D31301 Explains FX3G Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R521 installation and maintenance FX3GC Series JY997D45401 Explains FX3GC Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R533 installation and maintenance FX3U Series JY997D16501 Explains FX3U Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R516 installation and maintenance FX3UC Series JY997D28701 Explains FX3UC Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R519 installation and maintenance How to obtain manuals For product manuals or documents consult with the Mitsubishi Electric dealer from who you purchased your product Applicable standards FX3U 4AD PTW ADP units comply with the EC Directive EMC Directive and UL standards UL cUL Further information can be found in the following manual FX3S Series Hardware Manual Manual No JY997D48301 s Hardware Manual Manual No JY997D46001 FX3GC Series Hardware Manual Manual No JY997D45201 FX3U Series Hardware Manual Manual No JY997D18801 FX3uc D DS DSS
21. olution 0 2 to 0 3 C 0 4 to 0 5 F 0 5 for full scale when ambient temperature is 25 C 5 C Total accuracy 1 0 for full scale when ambient temperature is in the range of 0 to 55 C e FX3U FX3UC Series PLC 200 us Saha The data will be updated at every scan time of the PLC time e FX3S FX3G FX3GC Series PLC 250 us The data will be updated at every scan time of the PLC a ju 1D ic Input characteristics i e The photocoupler is adopted to insulate the analog input area from the PLC Laskua e The DC DC converter is adopted to insulate the power method A g supply line from the analog input area e Channels are not insulated from each other Occupied 0 point This number is not related to the maximum number of points input output points of the PLC This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi opportunity loss or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than
22. ore this manual in a safe place so that it can be taken out and read whenever necessary Always forward it to the end user Registration The company and product names described in this manual are registered trademarks or the trademarks of their respective companies Effective April 2015 Specifications are subject to change without notice 2007 Mitsubishi Electric Corporation Safety Precaution Read these precautions before use This manual classifies the safety precautions into two categories Z WARNING and A CAUTION Indicates that incorrect handling may cause hazardous conditions resulting in death or severe injury Z WARNING Indicates that incorrect handling may cause hazardous conditions resulting in medium or slight personal injury or physical damage Z CAUTION Depending on the circumstances procedures indicated by A CAUTION may also cause severe injury It is important to follow all precautions for personal safety Associated Manuals Manual name Manual No Description FX3S FX3G EX3GC EX3U Describes specifications for FX3UC Series JY997D16701 analog control and User s M l MODEL CODE programming method for S EAN 09R619 FX3S FX3G FX3GC FX3U Analog Control Edition FX3UC Series PLC FX3S FX3G FX3GC FX3U FX3UC Series JY997D16601 Describes PLC programming Programming Manual MODEL CODE for basic applied instructio
23. ot be laid in the same trunking or cable conduit as high voltage cabling Where possible users should run analog cables separately e Good cable shielding should be used When terminating the shield at Earth ensure that no earth loops are accidentally created e When reading analog values EMC accuracy can be improved out by averaging the readings This can be achieved either through functions on the analog special adapters or through a users program 1 Outline FX3U 4AD PTW ADP hereinafter called PTW ADP is an analog special adapter for measuring temperature via four channels three wire sensors of a connected Pt100 platinum resistance thermometer 1 1 Incorporated Items Verify that the following product and items are included in the package Product FX3U 4AD PTW ADP Pt100 temperature sensor input special adapter Accessories User s manual This manual 1 2 External Dimensions Part Names and Terminal Layout 15 10 6 7 FI G ale ejz Bol Ssg 3 E q Y N Special adapter connector cover is removed Weight Approx 0 1 kg 0 22 Ibs 1 DIN rail mounting groove DIN rail DIN46277 2 Name plate 3 Special adapter slide lock Used to connect additional special adapters onto the left side of this special adapter 4 Special adapter connector cover Remove this cover to connect additional special adapters to the left side 5 Direct mounting hole
24. pecified number of wires or electric wires The version number can be checked by monitoring D8001 D8101 as the last three i EI area from the PLC of unspecified size avoe H 24 2 digits indicate it ma e The DC DC converter is adopted to insulate the power Affix the electric wires so that neither the terminal block nor the connected 4 2E T f 4 2 General Specifications piled from ails ne tie h i parts are directly stressed i 7 r Items other than the following are equivalent to the those of the PLC main unit 7 eS ae eae aoe aes Make sure to properly wire the terminal block in accordance with the Grounding L For general specifications refer to the respective PLC User s manual Hardware Occupied 0 point This number is not related to the maximum number of following precautions Ground resistance ooooVo Editi i i Per 100 Q or less ition points input output points of the PLC Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product LO LO 10 chO Clrepresents the channel number Item Specification The disposal size of the cable end should follow the dimensions 7 FE z i Dielectric withstand i described in the manual of the PLC main unit 1 24 V DC service power supply of the FX3S FX3G FX3U Series PLC can also be voltage 500 V AC for one minute Between all terminals and Tightening torque should follow the specifications in the manual of the
25. ply wiring refer to the following manual FX3S FX3G FX3GC FX3U FX3UC Series User s Manual Analog Control Edition 3 3 Selection of platinum resistance thermometer sensors For the terminal configuration refer to Section 1 2 Precautions on platinum resistance thermometer wiring e Type of platinum resistance thermometer Select Pt100 3 wire platinum resistance thermometer sensors This thermometer will not be affected by voltage drop in the cable connection area and will ensure accurate measurement e Separate the cable of the platinum resistance thermometer sensors from the other motive power cables or areas easily affected by inductive noise of the commercial power etc Example of platinum resistance thermometer wiring 4 Specifications STARTUP AND MAINTENANCE PRECAUTIONS e Do not disassemble or modify the PLC Doing so may cause fire equipment failures or malfunctions For repair contact your local Mitsubishi Electric representative Do not drop the product or exert strong impact to it Doing so may cause damage Z CAUTION DISPOSAL PRECAUTIONS Z CAUTION e Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of your device TRANSPORTATION AND STORAGE PRECAUTIONS CAUTION e The product is a precision instrument During transportation avoid any impacts Failure to do so ma
26. the PLC main unit 3 1 Applicable cable and terminal tightening torque 3 1 1 Terminal block European type 1 Wire size The power supply wire should use 22 20 AWG wire Wiring to a Pt100 platinum resistance thermometer should be used the cable of it or a twisted shielded cable 2 Applicable cable Type Wire size 0 3 mm to 0 5 mm2 AWG22 to 20 Single wire 2 wire 2 pieces of 0 3 mm AWG22 3 Termination of cable end Strip the coating of strand wire and twist the cable core before connecting it or strip the coating of single wire before connecting it An alternative connection is to use a ferrule with insulating sleeve lt Reference gt Manufacturer Model Caulking tool CRIMPFOX 67 or CRIMPFOX 6T F Phoenix Contact Co Ltd Al 0 5 8WH 1 Old model name CRIMPFOX ZA 3 2 Old model name CRIMPFOX UD 6 Strand wire single wire e2 Stick terminal with insulating sleeve Insulation sleeve Contact area Crimp area 8mm 0 31 2 6mm 0 1 14mm 0 55 Ka When using a stick terminal with insulating sleeve choose a wire with proper cable sheath referring to the above outside dimensions or otherwise the wire cannot be inserted easily The tightening torque must be 0 22 to 0 25 Nem Do not tighten terminal screws exceeding the specified torque Failure to do so may cause equipment failures or malfunctions 3 2 Power Supply Wiring For the power sup
27. toring D8001 D8101 as the last three digits indicate it 4 2 General Specifications Items other than the following are equivalent to the those of the PLC main unit For general specifications refer to the respective PLC User s manual Hardware Edition Item Specification Dielectric withstand 500 V AC for one minute voltage Between all terminals and ground terminal of PLC 5 MQ or more by 500 V DC main unit megger Insulation resistance 4 3 Power Supply Specifications Item Specification AID conversion 24 V DC 20 15 50 mA for 24 V DC circuit driving power Connect a 24 V DC power supply to the terminal block Other Other Other 5V DC 15 mA PLC i PLC i PLC i ivi q equipment a equipment shat ariving 5 V DC power is supplied from the internal power supply of l I main unit Common grounding Not allowed Shared grounding Independent grounding Good condition Best condition e The grounding wire size should be AWG 22 20 0 3 0 5 mm e The grounding point should be close to the PLC and all grounding wire should be as short as possible 4 4 Performance Specifications Description Item Centigrade C Fahrenheit F laputelanall 3 wire platinum resistance thermometer sensor Pt100 oe JIS C 1604 1997 Rated temperature 100 C to 600 C 148 F to 1112 F range Digital output 1000 to 6000 1480 to 11120 Res
28. y cause failures in the product After transportation verify the operations of the product 4 1 Applicable PLC Model name Applicability FX3S Series PLC FX3G Series PLC Ver 1 00 or later from first production FX3GC Series PLC Ver 1 40 or later from first production Ver 1 00 or later from first production zi PTW ADP thermometer wiring Pt100 _ Terminal 4 7kQ 4 7kQ r Shielded wire block 100kKQ p cho Lo 4 Lo ji gt Toe 100kQ T al Pt100 4 7kQ 4 7kQ T Loft 100kQ cho 14 Lo a 4 Toe 100k2 m7 External power supply wiring 1 24 4 24VDC 24 E i i L oT Grounding L Ground resistance 100 or less LO LO 1 chO O represents the channel number 1 24 V DC service power supply of the FX3S FX3G FX3U Series PLC can also be used 3 4 Grounding Grounding should be performed as stated below e The grounding resistance should be 100 Q or less e Independent grounding should be performed for best results When independent grounding is not performed perform shared grounding of the following figure For details refer to the respective PLC User s manual Hardware Edition FX3U Series PLC Ver 2 20 or later from first production Ver 1 30 or later from the production manufactured in August FXSUC Series PLC 5094 with SER No 48 The version number can be checked by moni