Home
        North Dakota Weatherization Field Standards
         Contents
1.      4  Record any pressure difference between the main body of the  dwelling and the outdoors  This is the reference background  pressure    a  Areference background pressure might be due to stack effect air  leakage  especially if it is cold outdoors  or wind    5  Turn on the air handler and measure the pressure of the main body  of the house with reference to the outdoors     a  If the pressure difference between the main body and the outdoors  is different with the air handler on than with the air handler off  there  is probably some duct leakage to the outdoors    i  Either from the return side of the system  the pressure  difference of the dwelling with reference to outdoors will  move toward positive when the air handler is activated   or    ii  From the supply side of the system  the pressure difference  of the dwelling with reference to outdoors will move toward  negative when the air handler is activated      6  Close all interior doors     North Dakota Weatherization Field Standards  January 2003 Page 115    11000 Diagnostic Testing Procedures    7  Repeat the pressure measurement from the main body of the house  with reference to the outdoors    a  If this pressure is different than it was when all the interior doors  were open  the interior doors are acting as dampers to the air  distribution system  This can cause thermal discomfort and  stuffiness in the room and it can increase the air leakage of the  dwelling when the air handler is running    8  Take the pr
2.  the pressure pan  readings is between 3 and 5 Pascals     Visually check all boots and repair and seal with mastic  if  necessary     Visually check any crossover ducts and repair and seal with mastic   if necessary  Make sure these ducts are supported properly     Visually check furnace plenum joint and repair and seal with  mastic  if necessary  and    Goal  Reduce the sum of pressure pan readings to 3 Pascals or  less     For a living space return system  if the sum of the pressure pan  readings is greater than 5 Pascals     Repair and seal as in 3 above  and    Perform duct blower test and implement duct blower guided duct  repair and sealing  Refer to page 121  Duct Blower Testing     Goal  Reduce duct leakage to the outdoors  as measured with a  duct blower and blower door  to10 percent of conditioned floor area     11922 Site Built Homes  Including Manufactured Housing    1  For ducts located in unconditioned spaces          The pressure pan readings must be adjusted for house zone pressure differences  See Pressure Pan  Multipliers chart and test on page 120 for instructions     North Dakota Weatherization Field Standards  January 2003 Page 117    11000 Diagnostic Testing Procedures    a  If possible  convert the unconditioned space where the ducts are  located to a conditioned space  making sure the air and thermal  barriers are installed effectively     i  Demonstrate the effectiveness of this weatherization work by  performing a house to zone pressure and flow tes
3. North Dakota  Weatherization Field  Standards    Home Weatherization Assistance Program    January 2003 Edition       State of North Dakota  Department of Commerce  Division of Community Services  DCS   Paul Govig  Director    Energy Division  Howard Sage  Weatherization Program Administrator  400 East Broadway  Bismarck  ND 58502   701  328 4140    11000 Diagnostic Testing Procedures    11800 Room to Room Pressure Testing    11810 Air Handler Pressure Balance Testing for Site Built  Homes    11811 Introduction    This test procedure is performed only in dwellings with air handlers  Room to   room pressure s  should be measured in all rooms with forced air heating return  or supply ducts and operable doors  after all weatherization installations have  been completed  The procedure indicates the magnitude of     1  Duct leakage to the outdoors  either through supply or return ducts     2  Imbalances of air distribution resulting from closed interior doors   These closed doors can act as dampers to the free flow of air within  the conditioned space of the dwelling     3  Imbalances of air distribution resulting from airflow differences  between the supply side and return side of the ductwork  for  example  a restricted return truck     11812 Test Procedure    1  Set house up in winter operating mode     2  Run a pressure hose from the main body of the house to the  outdoors     3  Setup amagnehelic gauge zeroed at 15 Pa or a digital pressure  gauge in the main body of the house
4. an reading with the maximum possible reading     12  Record the pre  and post weatherization readings on the Diagnostic  Field Form     11940 Duct Blower Testing for Leakage to Outdoors    11941 Introduction    This required duct blower test requires measurement of duct air leakage to the  outdoors  not total duct leakage  to outdoors and indoors      During this test procedure a blower door fan will be used to pressurize the  building to the test pressure  while the duct blower system is used to pressurize  the duct system to the same pressure as the building  Because the duct system  and the inside of the dwelling will be at the same pressure  there will be no  leakage between the ducts and the dwelling during the test     The blower door fan should be set up to blow air into the building for  pressurization  Airflow through the blower door does not need to be measured  during this test  Because of this  the blower door fan can either be set up in the  pressurization test mode  or it can be set up in the standard depressurization test  mode  with the fan direction switch reversed to blow air into the dwelling  Refer to  your blower door manual for complete instructions     For residential duct systems  generally is recommend as the test pressure  This  pressure has been adopted by the majority of residential duct testing programs in  the U S  because 25 Pascals represents a typical operating pressure seen in  many residential systems     The instructions below assume the us
5. atherization Field Standards  January 2003 Page 122    11000 Diagnostic Testing Procedures    b  Turn the mode selection knob to fan select and select    8     Choose     8 0    for no duct blower rings     8 1    for one ring  and so on     c  Turn the mode selection to pressure     20  Turn on the duct blower and pressurize the ducts until the gauge  reads zero  that is  the pressure between the duct system and the  dwelling is zero  Leave the duct blower running     21  Re check the building pressure at the blower door and adjust if  necessary     22  Re check the duct blower system and adjust if necessary     23  On the DG 3 digital manometer  connected to the duct blower fan   turn the channel knob to    B    and turn the mode switch to    Flow     The  gauge will now display the air flow through the duct blower fan in  cubic feet per minute at 25 Pascals  CFMgs   This fan flow is the  measured duct leakage to the outdoors at the test pressure of 25  Pascals  This CFMzs5 flow can also be determined by reading fan  pressure from Channel B and converting that pressure reading to  flow by using the Duct Blaster    Flow Conversion Table in the Duct  Blaster    instruction manual     24  Check to make sure you have set the DG 3 correctly     25  It is a good idea to move the register pressure hose to other  registers  If the dwelling to duct pressure does not remain close to  zero  there are probably significant duct leaks  Inspect and repair any  obvious duct disconnects bef
6. e home ducts and site built homes with  ductwork in crawl spaces or attics are susceptible to leakage to and from the  outdoors     On the other hand  although duct leakage within the conditioned envelope    usually does not have a significant energy impact  it might impose a hazard to  occupant health by causing poor indoor air quality or backdrafting of combustion    North Dakota Weatherization Field Standards  January 2003 Page 116    appliances     11000 Diagnostic Testing Procedures    These potential problems are addressed on site by an IAQ appraisal    and by performing the worst case draft test  refer to page 111      Pressure pan and duct blower testing must be done in some dwellings to  determine if ducts are leaking to a significant degree to or from the outdoors     11920 Duct Leakage Standards    The following standards shall be followed for mobile homes  including double   wide mobile homes  and site built homes  including manufactured housing     11921 Mobile Homes    1     2     a     b     3     a     4     a   b     If there is a belly return system in the mobile home  convert it to a  living space return system  refer to Section 7700 on page 79      For a living space return system  if the sum of the pressure pan  readings is 3 Pascal or less     Visually check furnace plenum joint and repair and seal with  mastic  if necessary  and    Visually check all boots and repair and seal with mastic  if  necessary     For a living space return system  if the sum of
7. e of The Energy Conservatory Digital  Manometer  Model DG 3  and the Minneapolis Duct Blaster        11942 Test Procedure  1  Close all exterior doors and windows     2  Open all interior doors     3  Open doors to heated or conditioned spaces  Close doors to all  unconditioned spaces     4  Install blower door properly     North Dakota Weatherization Field Standards  January 2003 Page 121    11000 Diagnostic Testing Procedures    5  Shut down solid fuel appliances before activating blower door or duct  blower     6  Adjust the HVAC system controls so that the air handler fan will not  turn on during the duct blower test     7  Temporarily seal off all supply and return registers  except any  central return grille being used to connect the duct blower system to  the duct system     8  Temporarily seal off all combustion air and ventilation air inlets that  are directly connected to the duct system     9  Turn off all exhaust fans  vented dryers  and room air conditioners     10  Turn off all vented combustion appliances if there is a possibility that  the space containing the appliance will be depressurized during the  duct blower test     11  Remove all filters from the duct system and air handler cabinet  If the  duct blower will be installed at a central return grille  remove the filter  from that grille     12  If ducts run through unconditioned spaces such as attics  garages or  crawlspaces  open vents  access panels  or doors between these  spaces and the outdoors to el
8. essure gauge  being careful to level and zero on 15 Pa  when using a magnehelic gauge  and measure the pressure  difference across all interior doors  Pressure test and record  measurements for all rooms with reference to the main body of the  house  Make sure that registers and grilles are not blocked  even  though they appear open  Provide pressure relief to any room with  readings greater than 3 Pascals by    b  Opening the door slightly while measuring the pressure difference  across the door  Open the door until the pressure difference is less  than 3 Pascals and measure the square inches of opening  This is  the number of square inches    i  The door must be undercut  this usually works well in mobile  homes      ii  A direct grille  offset grilles  or jump duct must be to properly  relief the pressure imbalance caused by the distribution  system when the door is closed     9  Turn off air handler and return house to the condition it was in before  testing began     11900 Duct Leakage Testing    11910 Introduction    Duct leakage can lead to many problems in a dwelling  the most common one  being wasted energy  Other problems can include thermal discomfort   substandard indoor air quality  and combustion venting failure     Ductwork leakage can take place 1  within the confines of the conditioned  envelope of the building or 2  to and from the outdoors     Leakage to or from the outdoors wastes more energy than leakage within the  confines of the thermal envelope  Mobil
9. g the filter with the bag over it  This blocks the  filter opening and results in more accurate pressure pan testing   When the testing is completed  make sure to remove the plastic  bag from around the filter     4  Temporarily seal outside combustion air inlets or ventilation system  connections that are directly connected to the duct system  These  connections will show up as large leaks if not sealed prior to testing   If supply ducts are located in a garage or other unconditioned space   seal these registers so that the register opening does not show up as  a duct leak     5  Open attics  crawl spaces  garages  and other unconditioned spaces  to the outdoor air as much as possible  If the basement is being  treated as an unconditioned space  open it to the outdoor air     6  Only one person at a time should be taking pressure pan readings   Having 2 registers in different parts of the duct covered by a pressure  pan at the same time can affect readings     7  Depressurize the dwelling to  50 Pascals with the blower door     3 This section is primarily based on Using a Pressure Pan to Diagnose Duct Leakage by The Energy  Conservatory  March 2002  This document is available on the Internet at  www energyconservatory com manuals html  When you get to this page  find    Pressure Pan User Manual        Before fully opening or changing the position of balancing dampers  mark their position so that they can be  returned to that position after the pressure pan testing        Nor
10. iminate pressure changes during the  test procedure  This should also be done if the duct blower fan will be  installed in an unconditioned space  for example  connected to an air  handler in a garage or crawlspace     13  On the blower door  connect the outdoor building pressure tube to  the bottom tap on the 60 Pascal magnehelic gauge  The other end of  this tubing should either be run to the outdoors  or to the  unconditioned zone which contains the majority of the ductwork     14  Install the duct blower at the furnace or at a large return grille   15  Decide on the ring configuration for the duct blower   16  Connect the digital manometer correctly     a  Connect a pressure hose between a register and the input tap on  side    A    of the digital pressure gauge  Connect another pressure  hose from the reference tap on side    A    to the interior of the  dwelling  This means that if you are in the garage  the crawl space   or in the attic  you will need a pressure hose running under a door  back to the interior of the house     b  Connect a red hose to the top tap on channel    B     The other end of  this hose is connected to the duct blower flow ring     17  Pressurize the house with the blower door to the test pressure  25  Pascals  Leave the blower door fan running     18  Make sure the digital pressure gauge is set on channel    A      19  Set up the digital gauge properly   a  Turn the mode selection knob to time select and select    1 second        North Dakota We
11. ore continuing     26  When the duct sealing and duct blower testing are completed  shut  down and remove the blower door and duct blower     The final worst case draft test should be performed after the duct testing and  duct sealing is completed     111000 Zone Pressure Diagnostics  ZPD  Testing    111010 Introduction    Zone pressure diagnostics testing is performed to answer some fundamental  questions  where is the functioning air barrier and where should it be located   These test procedures can also be used to measure the size of the leakage  paths to various house zones  Leaking air often takes a path that moves through  two surfaces with a cavity or zone between  These zones can include attics   basements  garages  knee wall areas  or attached porch roofs     ZPD procedures require the measurement of pressure differences across air  barriers  like the pressure difference between the house and the zone  attic  for  example   while the house is depressurized by a blower door to    50 Pascals  The  procedures also require the determination of flows across air barriers  These  flows can be calculated with the steps of the ZPD procedures and a computer or    North Dakota Weatherization Field Standards  January 2003 Page 123    
12. t  if  possible  before and after converting the unconditioned  space to a conditioned space     ii  Always repair disconnected ducts in the space     iii  It is preferred to seal the shell of the space rather than  sealing the duct joints    b  If the unconditioned space is impossible to convert to a conditioned  space or it is determined impractical to convert to a conditioned  space    i  Use a duct blower to determine the duct leakage to the  outdoors  Examples of these types of unconditioned spaces  include crawlspaces  unconditioned basements  attics   attached or tuck under garages  and exterior walls     ii  Repair  seal with mastic  and thermally insulate ducts in  unconditioned spaces to at least an R 8    iii  Goal  Reduce duct leakage to the outdoors  as measured  with a duct blower and blower door  to 10 percent of  conditioned floor area    2  For ducts located in conditioned spaces  such as a basement or  crawlspace    a  Perform a house to zone pressure and flow test  if conditions  warrant  to determine if the space in question is conditioned in  terms of its shell air barrier  The house to zone pressure should be  20 Pascals or less     b  Visually inspect the conditioned space to ensure that the shell is  properly insulated    c  If it is determined that weatherization work should be done to the  shell of the conditioned space housing the ducts  perform a house   to zone pressure and flow test  if possible  before and after the  work to quantify the effecti
13. th Dakota Weatherization Field Standards  January 2003 Page 119    a     C     Table 11 8    11000 Diagnostic Testing Procedures    Make sure the pressure pan is properly connected to the manometer   The proper connection should be reading the space under the  pressure pan with reference to the main dwelling pressure     Place the pressure pan completely over each register and grille in  conditioned areas     If a register or grille is larger than the pressure pan  cover the  oversized portion of the register or grille with tape while the reading  is recorded     If access to a register or grille is difficult  for example at a kitchen  counter kick space  cover the entire opening with tape and insert  the pressure probe through the tape  near the center of the taped  opening  while the reading is recorded     When two registers or grilles are closely connected to the same  duct run  for example  two registers on opposite sides of the same  partition wall   seal one and use the pressure pan on the other  unsealed register or grille  Once you have taken the pressure pan  reading  remove the seal before proceeding to the next register        Pressure    Pan Multipliers 10  Record the pressure pan readings       House Zone  Pressure    Pressure Pan before and after duct sealing  Multiplier activities to get an idea of sealing       1 0 effectiveness  It will sometimes be          1 useful to record readings during duct       125 sealing  Always start your       1 66 measurements 
14. using the blower       2 0 door as a reference point and work       2 5 clockwise around the dwelling           a  If an unconditioned space is not                10 0 well connected to the outdoors       North Da     e g  unvented crawlspaces or  unvented attics  or has very large connections to the house  then  the unconditioned space will be at a pressure between the outside  and inside house pressure during the blower door test  In this case   the pressure pan reading will show an artificially low number  To  correct this misleading number     i  With the dwelling at  50 Pascals  measure the pressure  difference between the main dwelling and the unconditioned  space in question   For example  the house to zone pressure  is 10 Pascals and the pressure pan reading is 2 0 Pascals      ii  Multiply the pressure pan reading by the multiplier in Table  11 8 to get the corrected and true reading   For example   multiply the pressure pan reading of 2 0 Pascals by the    kota Weatherization Field Standards  January 2003 Page 120    11000 Diagnostic Testing Procedures    multiplier of    5     resulting in a pressure pan reading of 10  Pascals      11  If you are testing a house with a very leaky building shell and are not  able to create a 50 Pa pressure difference with the blower door   perform your pressure pan tests with the house at the highest  achievable pressure  In this case  you will need to interpret your  pressure pan readings carefully  Compare the measured pressure  p
15. veness of the work     i  Always repair disconnected ducts in the space     ii  Sealing the shell of the space rather than sealing the duct  joints is preferred     iii  Goal  The house to zone pressure should be 20 Pascals or  less     North Dakota Weatherization Field Standards  January 2003 Page 118    11000 Diagnostic Testing Procedures    11930 Pressure Pan Testing Procedures     11931 Introduction    Pressure pan testing helps find ductwork leaks or disconnections that are  connected to outdoor air  Testing before and after duct sealing gives an  indication of the effectiveness of sealing efforts  Pressure pans do not read duct  leakage directly  they infer leakage to the outdoors by reading the pressure at  individual registers     11932 Test Procedure    1  Install the blower door for a depressurization test  Make sure the  dwelling is set up for winter conditions     2  Open all interior doors  including the door to the basement if the  basement is considered conditioned space  heating system  water  heater  washer or dryer located there and it is determined that the  basement is part of the conditioned envelope      3  Make sure the furnace burner and air handler is off and will not start  during the testing  Remove the furnace filter and ensure that all  registers  grilles  and balancing dampers are fully open      a  Exception  When performing pressure pan testing in a mobile  home  block the filter opening by covering the filter with a plastic  bag and reinsertin
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
イヤーファイン Fit 取扱説明書(4.2MB)  Nova 3_guide_08.indd  Kohler K-16111 User's Manual    Handbuch - BlackVue    User manual / Technical Information  Fonctionnement  取扱説明書 - 日立の家電品      Copyright © All rights reserved. 
   Failed to retrieve file