Home
        S751DA-S7751DA User Manual
         Contents
1.                  das ducts ued anna nene od 21  AZ  LEDCOPERATION esa aa cca ceeds usec Quid qua caes 21  4 2 1 LASER  LS  INDICATOR                      ote                                21  42 2 1                                                             22  423 AUDIO  A  IN OUT INDICATORS                     22  424 DATA  0  IN OUT                           22  42 5 CONTACT      IN OUT INDICATORS              cccccsscecceceesseceeesesscecerenssseeeess 22  4 2 6 ENABLED  ENA                                                    22       11 0751DA A  December 2003 3    Table of Contents S751DA     S7751DA User Manual        37  TEST MODE sa ns                               23     gt  IFROVBLESHGOTING              tele au o hot ta         24  APPENDIX     RS485 APPLICATION                                                           25  A 1 INTRODUCTIONS eras as          EEEE EEEn 25  A2 CONNECTION                        aa ia ada dia rute adia A 25      SC ONFIGUBRATION                           Saad 25     3                                                                  DARE E               25       4 11 0751         December 2003    S751DA     S7751DA User Manual Before You Begin    BEFORE YOU BEGIN    Read these instructions before installing or operating this product   Note  This installation should be made by a qualified service person and should conform to local codes     This manual provides installation and operation information  To use this document  you must have th
2.          Pin   Signal    SW1     Position 5          1 MANCHESTER BIPHASE OUT      Pin    Signal          MANCHESTER BIPHASE OUT      MANCHESTER BIPHASE OUT            NO CONNECTION    MANCHESTER BIPHASE OUT            NO CONNECTION    NO CONNECTION          MANCHESTER BIPHASE IN      NO CONNECTION          MANCHESTER BIPHASE IN      MANCHESTER BIPHASE IN            NO CONNECTION    MANCHESTER BIPHASE IN                        oO  a  AJOJN    GROUND    TERMINIATION   TIE TO PIN 5                             RI  OJN       GROUND             11 0751DA A  December 2003    17    Installation S751DA     S7751DA User Manual                                                                                                                                                       Table 11  J2 Connections for RS485 2 Wire Data Table 12  J2 Connections for RS485 4 Wire Data  SW1     Position 6  standard offset  SW1     Position 9  standard offset   Position 7  1V offset  Position A  1V offset   Position 8  2V offset  Position B  2V offset   Pin   Signal Pin   Signal  1 GROUND SHIELD 1 GROUND SHIELD  2 NO CONNECTION 2 RS485 OUT    3 NO CONNECTION 3 RS485 OUT    4  5 VDC BIAS OUT 4  5 VDC BIAS OUT  5 RS485   5 RS485 IN    6 RS485   6 RS485 IN    7 TERMINATION   TIE TO PIN 5 7 TERMINATION     TIE TO PIN 5  8 GROUND 8 GROUND  Table 13  J2 Connections for SensorNet Data Table 14  J2 Connections for Test Mode Loopback  SW1     Position 6 SW1     Position F  Pin   Signal Pin   Signal  1 GROUND SHIEL
3.    User  Manual    S751DA   S7751DA  Fiber Optic Transmission System       GE Interlogix  Video Systems Group       2003 GE Interlogix  Video Systems Group    All Rights Reserved     Any GE Interlogix  Video Systems Group  software  supplied with GE Interlogix  Video Systems Group   products is proprietary and furnished under license  and can be used or copied only in accordance with  the terms of such license     This document contains proprietary information that is  protected by copyright  No part of this document may  be reproduced or transmitted in any form or by any  means without the prior written permission of   GE Interlogix  Video Systems Group     The information contained in this document is subject  to change without notice  GE Interlogix  Video  Systems Group  in keeping pace with technological  advances  is a company of product innovation   Therefore  it is difficult to ensure that all information  provided is entirely accurate and up to date    GE Interlogix  Video Systems Group  accepts no  responsibility for inaccuracies or omissions and  specifically disclaims any liabilities  losses  or risks   personal or otherwise  incurred as a consequence   directly or indirectly  of the use or application of any of  the contents of this document     For the latest product specifications  visit   GE Interlogix  Video Systems Group  online at  www GE Interlogix com or contact your GE Interlogix   Video Systems Group  sales representative     For technical support before
4.   Connect and apply power to module       AUDIO IN OUT LED is OFF    Audio input not connected to module    Connect audio input to module       Audio source not powered up    Apply power to audio source       Audio source not transmitting    Check audio source and cabling       DATA IN LED is OFF    Tri state condition    No action required       Data input not connected to module    Connect data input to module       Data source not powered up    Apply power to data source       Data source not transmitting    Check data source and cabling       Red ENA LED    Test or invalid mode selected    Set DATA SELECT switch to valid format       ENA LED flashing red green    Both Transmitter and Receiver set to  Auto Configure mode    Set Transmitter or Receiver DATA  SELECT switch to valid format       ENA LED flashing red off    Invalid or Test mode configured  remotely    Set DATA SELECT switch to valid format  if not in Test mode          24    11 0751DA A  December 2003    S751DA     S7751DA User Manual RS485 Application Notes    APPENDIX     RS485 APPLICATION NOTES    A 1 INTRODUCTION    The S751DA is configurable for both full duplex  four wire  and half duplex  two wire  operation  It can be  used for interfacing to systems adhering strictly to the RS 485 specification and for use with systems that  use a modified   fail safe biased  RS 485 bus     A 2 CONNECTION    Use high quality twisted pair wiring  and make sure all connection points are clean and tight  A loose  connect
5.   December 2003 11    Installation S751DA     S7751DA User Manual    3 INSTALLATION    This fiber optic link is supplied as a rack card  The rack cards can also be used in a standalone  configuration if placed in a 501R rack card enclosure     Units should be installed in dry locations protected from extremes of temperature and humidity     3 1 RACK CARDS    Rack cards are installed in a 19 inch  483 mm   EIA standard card cage rack  either the 515R1 or the  517R1  Follow these guidelines to install rack cards        CAUTION    Although rack cards are hot swappable and can be installed without turning off power to the rack  the  power switch on the rack power supply should be turned off and the rack power supply disconnected  from any power source before installing rack cards        1  Make sure that the card is oriented right side up  and slide it into the card guides in the rack until the  edge connector at the back of the card seats in the corresponding slot in the rack   s connector panel   Seating may require thumb pressure on the top and bottom of the card   s front panel        CAUTION   Do not press on any of the LEDs when installing cards into the rack  Equipment damage may result        2  Tighten the two thumbscrews on the card until the front panel of the card is seated against the front  of the rack     3 2 501R RACK CARD ENCLOSURES    Follow these guidelines to install rack cards in the 501R rack card enclosure        CAUTION    A The rack card module can be pow
6.  and after installation  call 800 469 1676     Technical support is available 24 hours a day  7 days a week           This equipment has been tested and  found to comply with the limits for a  Class A digital device  pursuant to part  15 of the FCC Rules  These limits are  designed to provide reasonable  protection against harmful interference  when the equipment is operated ina  commercial environment  This  equipment generates  uses  and can  radiate radio frequency energy and  if  not installed and used in accordance  with the instruction manual  may cause  harmful interference to radio  communications     You are cautioned that any changes or  modifications not expressly approved by  the party responsible for compliance  could void the user s authority to  operate the equipment        Call  Tech Support 800 469 1676  6            5 P M  PST Monday through Friday   Tech Support 541 740 3589  all other times   Main 800 343 3358 or 541 754 9133   Fax  Tech Support 541 752 9096  available 24 hours a day   Main 541 754 7162   Web  www GE Interlogix com    11 0751DA A   December 2003       S751DA     S7751DA User Manual Table of Contents    TABLE OF CONTENTS  BEFORE YOU BEGIN                     E                                              5  T INTRODUCTION                                                                              7  2 MODULE SETUP  sacas reinicia Vis as in insano anna 8  2A  UNPACKING THE UN T ea a a n E e ae a 8  2 2 DATA TRANSLATION         la Pvc anc EE
7.  materials in case it becomes necessary to return the unit        CAUTION   A Take all necessary precautions to protect the unit from static electricity during the following procedures   Equipment damage may result        2 2 DATA TRANSLATION    The data translation capability of the S751DA series is unique in the industry  It enables translation from  one data format to another and eliminates the need for external translation devices     The translation is in the physical layer only  it cannot interpret specific protocols or translate commands     Due to the encoding schemes utilized in Manchester and Biphase  these formats are exempt from  translation  Data translation examples are shown in Table 1     Table 1  Data Translations                                           Translation TX Switch RX Switch   Comments  Setting Setting  TTL to RS232 three wire 3 1 Signal level conversion  RS232  three wire to TTL 1 3 Signal level conversion  TTL to RS422 3 4 Single ended to differential conversion  RS422 to TTL 4 3 Differential to single ended conversion  RS232  three wire to RS422 1 4 Single ended to differential conversion  RS422 to RS232  three  wire 4 1 Differential to single ended conversion  RS232  five wire to RS485 2 7 A RS232 handshaking bit is used to indicate tri state  RS485 to RS232  five wire 7    2 Tri State detection circuitry activates handshaking bit       2 3 INPUT OUTPUT DATA FORMAT    Determine the data formats required for input and output for both data chann
8. 718 mim  E mm  B 2 im   210 mem        Gan         mm              149 mm        Figure 7  501R Rack Card Enclosure Mounting Data    3 3 CONNECTIONS    All audio  data  contact  and fiber connections are made to the back panel of the S751DA module  When  connecting audio  data  or contact signals  always wire the signal OUT pins on the audio data equipment  to the signal IN pins on the fiber links  and the signal IN pins on the audio data equipment to the signal  OUT pins on the fiber links  See Figure 8        11 0751DA A  December 2003 13    Installation    AUDIO OUT    AUDI IM                            DATA       i    CONTACT OUT    CONTACT IM       Audio Data Equipment    S751DA     S7751DA User Manual    E AUDIO IN    AUDIO OUT    e DATA IN  DATA OUT   e CONTACT IN  CONTACT OUT     751DA Link    Figure 8  S751DA Fiber Link Audio     Data     Contact Connections    3 3 1 BACK PANEL CONNECTIONS    Audio  data  and contact signals can be connected directly to the unit by wiring a 26 pin male D connector   AMP plug part number 748474 1  pin part number 748333 4  and attaching it to audio data connector J4  on the back panel of the unit  See Figure 9  Table 3 lists the signal and pin information             Audio Data                           Optical in           Optical Out       Note  Optical In connector is not present on 1 Fiber models     Figure 9  S751DA 2 Fiber Module Back Panel Connections       14 11 0751DA A  December 2003    S751DA   S7751DA User Manual Installat
9. AUDIO CHANNEL 1 OUT         AUDIO CHANNEL 1 OUT    GROUND                             Connector 46    1 CONTACT CHANNEL 1 IN                                                                                             2 CONTACT CHANNEL 1 IN    3 CONTACT CHANNEL 1 OUT    4 CONTACT CHANNEL 1 OUT    Table 5  J2 Connections for RS232 Data Table 6  J2 Connections for RS232 Data with  SW1     Position 1 Handshaking  SW1     Position 2  Pin   Signal  Pin   Signal  1 GROUND SHIELD  1 GROUND SHIELD  2 RS232 OUT  2 RS232 OUT  3 NO CONNECTION  3 RTS CTS OUT  4 NO CONNECTION  4 NO CONNECTION  5 RS232 IN  5 RS232 IN  6 NO CONNECTION  6 RTS CTS IN  7 NO CONNECTION  7 NO CONNECTION  8 GROUND  8 GROUND                            16 11 0751DA A  December 2003    S751DA     S7751DA User Manual    Table 7  J2 Connections for TTL Data       SW1     Position          Pin   Signal       1 GROUND SHIELD       NO CONNECTION       TTL OUT       NO CONNECTION       TIE TO PIN 1       TTLIN       NO CONNECTION                              BR  Ww  hd    GROUND             Table 9  J2 Connections for Manchester Biphase Data    Table 8  J2 Connections for RS422 Data       SW1     Position 4       Pin    Signal       1    GROUND SHIELD       RS422 OUT         RS422 OUT         NO CONNECTION       RS422 IN         RS422 IN         NO CONNECTION                      BR             GROUND             SW1     Position 5    Installation    Table 10  J2 Connections for Manchester Biphase    Termination Unit Data 
10. D 1 NO CONNECTION  2 NO CONNECTION 2 TIE TO PIN 5  3 NO CONNECTION 3 TIE TO PIN 6  4  5 VDC BIAS OUT 4 NO CONNECTION  5 SENSORNET   5 TIE TO PIN 2  6 SENSORNET   6 TIE TO PIN 3  7 TERMINATION   TIE TO PIN 5 7 NO CONNECTION  8 GROUND 8 GROUND                         3 3 3 BUILT IN TERMINATION    The S751DA features a built in termination on the Interface Board for RS485  Manchester  Biphase  and  SensorNet installations  Refer to Table 4  and Table 10 through Table 13        18 11 0751DA A  December 2003    S751DA     S7751DA User Manual Installation    3 3 4 AUDIO CONNECTIONS    Audio input and output signals are connected to the 26 pin connector located on the back of the module   or to the screw terminal connectors on the Interface board supplied with the unit  See Figure 9 and  Figure 10  Refer to Table 3 and Table 4 for wiring information     NOTE  Signal strength remains the same regardless of type of connection   Audio connection options include        Balanced transmitter input to balanced receiver output       Balanced transmitter input to unbalanced receiver output        Unbalanced transmitter input to unbalanced receiver output        Unbalanced transmitter input to balanced receiver output    1  Fora balanced connection  connect the external equipment to the     and     pins of the desired  channel     2  Foran unbalanced connection  add a short jumper between the     pin and the ground pin     3 3 5 FIBER OPTIC CABLE CONNECTIONS    Most cable manufacturers identi
11. E and               8  2 3 J INPUT OUTPUT  DATA                                           8  23 1  MANUAL DATA SELECTION             aces e    9  2 3 2 AUTO DATA CONFIGURATION c cnesccessesscentacseessconsarsucecseoesspessursceeseeentgrace 10  2 4  OPTICAL ALARM crus ias ear ee Es dA               e ad      ba a ado 10  25  AUDIO LEVE ate                           AS        MER ii io RN Odd 11  20 INPUT AMPEDANGE 2                                                                  LACAN          11  3  INSTALEA TION                      12        RACK                                                                                   12  3 2 501R Rack CARD ENCLOSURES                         12  33    CONNECTIONS                                                                  EN 13  3 3 1 BACK PANEL CONNECTIONS                                     14  3 3 2 INTERFACE BOARD                                                              15  3 3 3 BUILT IN TERMINATION cas cies cence                       18  3 3 4 AUDIO  GONNECTIONS                                                                    19  3 3 5 FIBER OPTIC CABLE CONNECTIONS juts suki sun                          vontsunixenoreebeence 19  3 3 6 STANDALONE MODULE POWER                                                                   19  3 3 7 RACK MODULE POWER                                                                 20       OPERATION       iether ee err eerste a Oi eee 21  Bel   NORMAL OPERATION A                  
12. LED performs a similar function  except that it refers to the audio output from the  module     4 2 4 DATA  D  IN OUT INDICATORS    The DATA IN LED indicates the level of the data signal being input to the S751DA over copper  A green  DATA IN LED indicates a logic HIGH is present on the data inputs     An amber DATA IN LED indicates a logic LOW is present on the copper  No color  OFF  indicates a tri   state or high impedance input     This LED can be used to determine the resting state of your equipment and  in the RS485 states  verify  that a tri state is being detected properly     The S751DA has special circuitry to capture data transitions and make them visible on the LEDs  High   speed bursts of activity  previously undetectable by standard LED circuits  are easily seen by this special  circuitry     The DATA OUT LED functions identically to the DATA IN LED except that the LED represents data that is  being output from the unit  This LED has the same high speed capture circuitry as the DATA IN LED     4 2 5 CONTACT  C  IN OUT INDICATORS    The CONTACT IN OUT LEDs indicate the presence of relay contact closure signals  A green CONTACT  IN OUT LED indicates a closed relay contact  and a red LED indicates an open relay contact     4 2 6 ENABLED  ENA  INDICATOR    The ENABLED LED monitors the selected mode of the Data channel  It has five states as follows       Green indicates a valid mode has been selected       Red indicates an invalid mode  spare or TEST mode  has been 
13. ction    1 INTRODUCTION    This is a guide to the installation and operation of the S751DA and S7751DA series fiber optic audio   data  and contact closure transmission system  Please read the entire manual before installing the  equipment     NOTE  The series numbers S751DAT and S751DAR are used to describe all models of transmitters and receivers unless noted  otherwise     The Series S751DA and S7751DA transmission systems offer simultaneous real time transmission of       One channel of two way high quality audio               One channel of two way multi protocol data  MPD       One channel of two way relay contact closure  The S751DA system operates over one or two multimode fibers and the S7751DA uses one or two  single mode fibers  A complete system consists of an S751DAT transmitter and an S751DAR receiver     Units are designed for installation in the 515R1 or 517R1 Card Cages or in the 501R rack card enclosure   Figure 1 shows a basic system diagram     TX RX              Audie      Audio In Out       Data InfOut                          In Out Contact             mg  Optical Fiber    Figure 1  S751DA System Diagram       11 0751DA A  December 2003 7    Module Setup S751DA     S7751DA User Manual    2 MODULE SETUP    2 1 UNPACKING THE UNIT    In the event that anything is missing from the following list  contact your authorized dealer or  representative   e S751DAT  S7751DAT  Transmitter or S7751DAR  S7751DAR  Receiver       User Manual    Save the original packing
14. d at one end of the system by using pull up down resistors on the data connector  The  S751DA has a  5 V bias pin and ground pins on the connector for this purpose  Contact the equipment  manufacturer s technical support for recommended resistor values and configuration           TERMINATION    RS485 systems need to be properly terminated in order to work reliably  Two terminating resistors are  used on each RS485 bus  at the farthest ends of the link     These resistors should be attached to the data audio connector on the back of the unit if the S751DA link  is at one end of the bus  If the terminating resistors are left out  the tri state condition will not be detected   and the bus might lock up  If there are too many terminations on the bus  signal levels might drop too  low  or driver circuitry might fail  The standard value of terminating resistors for RS485 is 120Q        11 0751DA A  December 2003 25      5485 Application Notes    S751DA     S7751DA User Manual       26    11 0751DA A  December 2003    
15. d strip approximately 0 25  inches  6 mm  of insulation from the ends of the cable     3  Taking care to observe the correct polarization of the cable  insert one lead into one of the screw  sockets and tighten the screw  Confirm the security of the connection with a light pull on the cable     4  Repeat step    for the other conductor    5  Seat the connector in its position in the fiber unit    6  Plug the power supply into a suitable outlet    7  Power up the peripheral equipment and verify system operation by observing video on the monitor    at the receiver end     3 3 7 RACK MODULE POWER CONNECTIONS    Power connections are made automatically when the card is installed  To supply power to the rack   connect the rack power supply to an AC outlet and set the power switch to ON        20 11 0751DA A  December 2003    S751DA     S7751DA User Manual Operation    4 OPERATION    4 1 NORMAL OPERATION    S751DA fiber links operate automatically after installation  Refer to paragraph 4 4 for details on how to  execute the test mode  For description of LED color codes and an explanation of how to diagnose system  faults using the LEDs built into the units  refer to section 5  Troubleshooting     4 2 LED OPERATION    The S751DA modules have built in Status Monitoring And Reliability Test System  SMARTS     diagnostic  capabilities that include LED indicators for monitoring data and optical status  The S751DA fiber units  have LED indicators that describe the current state of operat
16. e  following minimum qualifications         A basic knowledge of CCTV systems and components        A basic knowledge of electrical wiring and low voltage electrical hookups    Intended use    Use this product only for the purpose for which it was designed  refer to the product specification and user  documentation     Customer Support    For assistance in installing  operating  maintaining  and troubleshooting this product  refer to this  document and any other documentation provided  If you still have questions  please contact  Technical Support and Sales     GE Interlogix  Video Systems Group  Call  800 469 1676  Fax  541 752 9096  Note  You should be at the equipment and ready with details before calling Technical Support     Conventions Used in this Manual    Boldface or button icons highlight command entries  The following WARNING  CAUTION  and Note  statements identify potential hazards that can occur if the equipment is handled improperly          WARNING   Improper use of this equipment can cause severe bodily injury or equipment damage              CAUTION   Improper use of this equipment can cause equipment damage        Note  Notes contain important information about a product or procedure       This symbol indicates electrical warnings and cautions      This symbol indicates general warnings and cautions        11 0751DA A  December 2003 5    Before You Begin S751DA     S7751DA User Manual       6 11 0751DA A  December 2003    S751DA   S7751DA User Manual Introdu
17. els  The data formats may  be the same or different for each channel  The data format can also differ from input to output on the  same data channel        8 11 0751DA A  December 2003       S751DA     S7751DA User Manual Module Setup    2 3 1 MANUAL DATA SELECTION    To set the data format for channel 1  see Figure 2  Figure 3  Table 2 and perform the following   1  Select a data format on the transmitter using DATA SELECT switch SW1   2  Select a data format on the receiver using DATA SELECT switch SW1     NOTE  The DATA SELECT switch SW1 on the audio data card is shipped in the Auto Configure setting  position 0      5 1 5 7 SW5 SW6       SW3  Figure 2  S751DA Location of Switches       Figure 3  DATA SELECT Switch SW1       11 0751DA A  December 2003 9    Module Setup S751DA     S7751DA User Manual    Table2  DATA SELECT SW1 Settings                               Setting   Data Mode Setting   Data Mode  0 Not Configured or Auto Configuration 8 RS485 two  wire  2V offset  1 RS232 9 RS485 four wire standard  2 RS232 with handshake A RS485 four wire  1V offset  3 TTL B RS485 four wire  2V offset  4 RS422 two wire    Not used  5 Manchester Biphase D Not used  6 RS485 two wire Standard or SensorNet E Receiver Test mode  7 RS485 two  wire  1V offset F Transmitter Test mode                      2 3 2 AUTO DATA CONFIGURATION    The S751DA modules can be set for Auto Data Configuration  where the format of the data on channel 1  is controlled from one unit  either the transmitter 
18. ence and 0 dBu  4 dBu audio reference level  All units are shipped with the audio level  switches set to 18 dBu  0 dBu audio reference level   At this setting  the 18 dB of operating range will  support maximum audio levels of  18 dBu  Switches SW5 and SW7 on the audio data card select the  audio input and output levels  To set the audio levels  see Figure 2 and Figure 5 and perform the  following     swe ay  SUDO INPUT LEVEL SWATCH            OUTPUT LEVEL SELECT SWITCH                    12          BOTH HATCHES SWATCH 1   AUDIO 1   MUST             TO     THE SAME POSITION SWITCH 2  NOT USER      da                      Figure 5  AUDIO LEVEL Switches SW5 and SW7    1  Ifa low audio input level causes the output audio signal to degrade  the input sensitivity of the  S751DA can be increased by switching to the 8 dBu maximum scale     2  For systems running at  10 dBu  typical for VCRs and DVD players  switches SW5 and SW7 should  be set to 8 dB     3  You can set the transmitter input to 8 dBu and the receiver output to 18 dBu to add 10 dB of gain to  the system  however  this also increases system signal to noise ratio  S N      2 6 INPUT IMPEDANCE    The S751DA units are shipped with the input impedance set at high impedance  high Z   To select a  6000 input impedance in place of the high Z input  set switch SW6 on the audio data card to 600  See  Figure 2 and Figure 6     SWITCH 1   AUDIO 1    SWITCH 2   NOT USED  HI Z       Figure 6  IMPEDANCE Switch SW6       11 0751DA A
19. ered only by 13 5   16 VDC  AC power must not be used  It is  recommended that the 613P power adapter be used to supply power to the module  Damage to the  equipment may result if AC power is used           CAUTION   Complete all instruction steps before supplying power to the unit           12 11 0751DA A  December 2003    S751DA     S7751DA User Manual Installation    1  Look inside the enclosure to determine the location of the socket for the edge connector on the  card  Orient the card so that it will seat in the socket  and slide it into the card guides in the  enclosure until the edge connector at the back of the card seats in the socket  Seating may require  thumb pressure on the top and bottom of the card   s front panel        CAUTION   Do not to press on any of the LEDs when installing cards into the enclosure  Equipment damage may  result        2  Tighten the two thumbscrews on the card until the front panel of the card is seated against the front  of the enclosure     3  Determine where the module will be installed  and ensure that there is adequate space for making  the various cable connections and for reading the diagnostic LEDs  See Figure 7     NOTE  The type of screws chosen must be suitable for the surface on which the module is to be mounted     4  Standalone modules can be attached to suitable flat surfaces with four No  6  3 mm  screws  After  the enclosure is securely attached to a flat surface  the cable connections can be made         9 31 1 15 in   
20. fy the individual fibers in the cable  Select appropriately terminated fiber  and mark both ends with a unique identification label  e g  for cable no  03  fiber no  08  to ensure that the  fiber connected to the near end is the same as the one connected to the far end     The proper optical connection will link the transmitter s TRANSMIT  OUT  port to the receiver s RECEIVE   IN  port  See Figure 9     1  Wipe the inside of the port   s sleeve with a lint free pipe cleaner moistened with reagent grade  isopropyl alcohol  Blow dry with dry air     2  Clean the connector using a lint free cloth dampened with reagent grade isopropyl alcohol   Thoroughly wipe the side and end of the ferrule  Blow the ferrule dry with dry air  Visually inspect  the ferrule for lint     3  Fasten the fiber optic cable to the port     3 3 6 STANDALONE MODULE POWER CONNECTIONS       CAUTION   Standalone modules can be powered only by 13 5   16 VDC  AC power must not be used  Damage to  the equipment will result        The 501R rack card enclosure has a removable screw terminal connector for the electrical input  connection  Pin 1 of this connector is the GROUND terminal  pin 2 is not used  and pin 3 is the  DC  terminal as marked on the enclosure  Connect the input power as follows     1  Identify the power connector and remove it from the module        11 0751DA A  December 2003 19    Installation S751DA   S7751DA User Manual    2  Make sure the power supply is not connected to any power source  an
21. ion    Table 3  J4 Audio Data Connections                                              Pin   Signal Pin   Signal  1   AUDIO OUT   14   AUDIO IN    2   GROUND 15   NO CONNECTION  3   NO CONNECTION 16   GROUND  4   CONTACT IN   17   DATA OUT    5   AUDIOIN  18   DATAIN   6   NO CONNECTION 19   NO CONNECTION  7   DATA OUT   20   CONTACT OUT    8   DATA        21   CONTACT OUT    9   NO CONNECTION 22    5 VDC BIAS  10   NO CONNECTION 23   GROUND  11   AUDIO OUT   24   NO CONNECTION  12   NO CONNECTION 25   NO CONNECTION  13   NO CONNECTION 26   NO CONNECTION                      3 3 2 INTERFACE BOARD CONNECTIONS    The S751DA units are also supplied with an interface board that attaches directly to the back of the  module  The interface board contains screw terminal connectors for the audio  data  and contact inputs  and outputs  Refer to Figure 10 and Table 4 through Table 14 for interface board wiring information     J2 J4 J6    J1  Mates with J4  on S751DA  Back Panel                Not Used Not Used Not Used  Figure 10  S751DA Interface Board       11 0751DA A  December 2003 15    Installation S751DA     S7751DA User Manual    Table 4  Interface Board Connections  Pin Signal          Connector J2       1 GROUND       DATA CHANNEL 1 OUT    DATA CHANNEL 1 OUT             5 VDC BIAS       DATA CHANNEL 1 IN         DATA CHANNEL 1 IN    TERMINATION          Orn            BR          GROUND       Connector J4  AUDIO CHANNEL 1 IN    AUDIO CHANNEL 1 IN    GROUND                     
22. ion  the current status of audio and data  signals  and fiber optic signal strength     These indicator pairs are LASER  LS  and LEVEL LOSS  LL   AUDIO IN OUT  DATA IN OUT  CONTACT  IN OUT  and ENABLED  ENA   See Figure 11  The operation of the front panel LEDs is described in the  following paragraphs        Figure 11  Front Panel LEDs    4 2 1 LASER  LS  INDICATOR    A green LASER LED indicates the laser is operating normally  A red LASER LED indicates the laser is  malfunctioning        11 0751DA A  December 2003 21    Operation S751DA     S7751DA User Manual    4 2 2 LEVEL LOSS  LL  INDICATOR    This LED indicates the relative optical signal strength received at the module  When sufficient optical  power is being received  the LED is green  As the optical power decreases  as happens through long fiber  runs  splices or connections  the LEVEL LOSS LED stays green until the optical power drops below the  minimum level     The LEVEL LOSS LED will turn bright red to indicate an insufficient amount of optical power is being  received  All data will default to its failure state level to eliminate bus contention     4 2 3 AUDIO  A  IN OUT INDICATORS    The AUDIO IN  or OUT  LED indicates the strength of the audio signal by varying in intensity  The AUDIO  IN LED remains green as long as an adequate audio signal level is being input to the module     If the audio input becomes too weak  the LED will turn off  The LED will be red when the audio level is  clipped     The AUDIO OUT 
23. ion on one of the wires can appear to function  yet cause intermittent errors  DATA LEDs may be  flashing as signals pass through the system  but those signals will be corrupt     A 3 CONFIGURATION    The S751DA multi protocol data  MPD  units are designed to work with virtually any RS485 system   Unfortunately  some systems operate on a  modified  version of RS485 that use a fail safe biasing to pull  up down their bus during a tri state condition  In a standard RS485 system  when a driver on a properly  terminated bus goes into tri state  the voltage between the differential outputs should be less than   200 mv      This is considered  standard offset  in the product instruction manuals   A differential output tri state  voltage this small can cause some non standard systems to latch up  because they are designed for  much larger   fail safe   offsets     To be able to interface to such equipment  the S751DA MPD units offer two more  offset  level modes  In  most cases  the S751DA unit should be configured for  standard offset  operation     When the system is operating properly  the DATA IN and DATA OUT LEDs are off when there is no   communication  tri state  and flash when data is being sent or received  If the link is not functioning   properly  LEDs will most likely not turn off   change the DATA SELECT switch on the unit to a higher  offset mode     First try 1 V  then 2 V  If switching the mode switch does not prove effective  the offset level may have to  be emulate
24. or the receiver  To use the Auto Data Configuration  feature  perform the following     1  Set the DATA SELECT switch SW1 on one unit to position O  default setting    2  Set the DATA SELECT switch SW1 on the other unit to the desired format     3  Ifthe data format needs to be changed for a particular channel  only the DATA SELECT switch on  one unit need to be changed  The other unit remains in position 0 and will auto configure according  to the selected data format     2 4 OPTICAL ALARM    Rack cards are supplied with an alarm function that activates if the optical signal input to the module fails   This alarm can be output to the rack power supply  where an audible alarm and alarm output contact  closure can be activated  The optical alarm is controlled using DIP switch SW3 on the data card  To set  the optical alarm  see Figure 2 and Figure 4 and perform the following     ENABLE         SWITCH 1   FIBER ALARM    SWATCH 2   NOT USED  DISABLE    Figure 4  ALARM Switch SW3  1  Set switch SW3 1 to the ON position to enable the FIBER  optical  alarm   2  Set the switch SW3 1 to the OFF position to disable the alarm     NOTE  Setting ALARM switch SW3 1 to the OFF position does not affect the operation of the LEVEL LOSS LED  A red LED always  indicates signal loss        10 11 0751DA A  December 2003    S751DA     S7751DA User Manual Module Setup    2 5   UDIO LEVEL    The S751DA system features dual audio level operation to meet the system requirements of  10 dBu  audio refer
25. receive circuitry is working properly     e LEVEL LOSS might be red or green indicating received fiber signal strength   4  The receiving unit should operate as follows   e ENABLED LED is GREEN indicating a valid data format is selected     e DATA OUT LED should slowly flash amber  green  off  This indicates that the fiber path from the  unit set for Test mode is reliable     e DATA IN LED should be OFF indicating there is no input copper connection made     e LEVEL LOSS LED should be green to off  but not red   indicating that sufficient optical power is  being received     e The AUDIO OUT LEDs should be green indicating sufficient audio output signal level     5  In addition to the LED operation described above  verify a 1 kHz test tone is emitted on the audio  system connected to the receiving unit    After the test has been performed at one end  swap switch positions and connectors to perform the test  on the other end  If the test is successful  the copper in to fiber to copper out conversion is working in  both directions        11 0751DA A  December 2003 23    Troubleshooting    5 TROUBLESHOOTING     751DA     S7751DA User Manual    Table 15 contains troubleshooting information for the S751DA units     Table 15  Troubleshooting       Problem    Probable Cause    Solution       Red LASER LED    Laser is malfunctioning    Replace module       Red LEVEL LOSS LED    Fiber not connected    Connect fiber to receiver and transmitter       Transmitter Receiver not powered up  
26. selected         Flashing red green indicates that no mode has been selected        22 11 0751DA A  December 2003    S751DA     S7751DA User Manual Operation        Flashing green off indicates a valid mode is configured remotely         Flashing red off indicates either an invalid mode or the Test mode is configured remotely     4 3 TEST MODE    The Test mode enables you to verify the operation of the audio  and data circuits in the S751DA units  as  well as the fiber connection from the S751DA transmitter to the S751DA receiver  To execute the test  mode  perform the following     Note  DATA SELECT switch SW 1 can be set to position F to enable the 1 kHz test tone generator to verify and audio operation     1  Setthe DATA SELECT switch on the S751DA you are testing to F  TX Test Mode   At this end only   wire the data connections as follows  refer to Table 14      e Connect the DATA IN  pin to the DATA OUT  pin    e Connect the DATA IN  pin to the DATA OUT  pin   2  Atthe opposite end  set the DATA SELECT switch on the S751DA to E  RX Test Mode    3  The transmitting unit should operate as follows    e ENABLED LED is RED  indicating that a valid data format has not been selected     e DATA OUT LED is slowly flashing between amber  green  and off  This indicates that the test  mode is generating an output pattern and sending it out on copper     e DATA IN LED should mimic the DATA OUT LED  This indicates a good  proper loopback  connection  and proves that the data transmit 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
QUICK INSTALLATION GUIDE - D-Link  CMS3.0 User Manual 8-8-2014 - KARAGIANNIS – Security Systems  3M 800ab 39600 Fan User Manual  コッコロ EG/コッコロS  Samsung E1050 Korisničko uputstvo  Triton 9100 User Manual  AP 落下式ブラストガン 取扱説明書  Manual de Instruções  Extox-Uni xTM controller user manual  Bristol-Myers Squibb PQP10 Boating Equipment User Manual    Copyright © All rights reserved. 
   Failed to retrieve file