Home
        ReadySET Aspirating Smoke Detection System Installers Handbook
         Contents
1.                VOLT FREE RELAY CONNECTIONS     Each relay is rated at 1 Amax  at 24 VDC      The FIRE  ALARM  and PRE ALARM contacts are connected as normally  open and change state upon alarm conditions      The FAULT relay contact is normally closed  and changes state on a loss  of power      Use shielded cable with shield connected to the detector EARTH terminal     INPUT DIP SWITCH CONNECTIONS      With the DIP switch number 7 set to the OFF position  connect to  PSU fault relay Normally Closed contacts for PSU monitoring      With the DIP switch number 7 set to the ON position  ClassiFire  override will reduce detector sensitivity by 50  while the input  terminals are shorted together  e g  by a key switch      Use shielded cable with shield connected to the detector EARTH  terminal     Optional communications card fitted  RS485 serial communications    mode       Connect Command Module or detector RS485  SenseNET  serial bus to  A and B      Set communications card address switches to identify detector      Use screened cable  Connect screen to SCREEN terminal s   Earth the   screen at one end ONLY  if using a chain of detectors connected to a   Command Module  earth the cable screen at the Command Module only      Optional APIC card fitted  addressable communications mode       Connect   and     IN and   and     OUT terminals to fire panel with a  communications protocol compatible with the APIC  Set APIC address  switches to identify detector      In a chain of detect
2.     e Notification appliances  such as bells  may not alert people if these appliances are  located on the other side of closed or partly open doors  or are located on another  floor of a building     e A fire alarm system will not operate without electrical power  If AC power fails  the  system will operate from standby batteries only for a limited time     e Auxiliary Equipment used in the system may not be technically compatible with the  control unit  It is essential to use only equipment listed for service with your control  unit     e Telephone lines needed to transmit alarm signals from the protected site to a central  monitoring station may be out of service or temporarily disabled     e The most common cause of fire alarm malfunctions is inadequate maintenance  All  devices and system wiring should be tested and maintained by professional fire  alarm installers following written procedures supplied with each device  System  inspection and testing should be scheduled monthly or as required by national  and or local fire codes and standards  Adequate written records of all inspections  should be kept     ReadySET Aspirating Smoke Detection System Installers Handbook 3    Chapter 1  Introduction    4 ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 2  Product description    Summary    This chapter provides descriptions of the detector features  specifications  and controls  and indicators     Content    Introduction 6  Features 6  Specifications
3.    F or  0   to 38   C  humidity 0   90   non   condensing      Ensure the detector is properly grounded     Remove or connect boards when  the detector is powered up     Attempt to adjust or alter detector  settings other than via the user   programmable functions  Any  attempts to adjust the laser  potentiometer are detectable and will  void the warranty on the product     Drop the detector or use excessive  force when fitting sampling pipes as  this may damage the detector     Connect internal 0 volt terminals to  local earth     Use sampling pipe of less than 1  inch  27 mm  outside diameter  without a suitable 1 inch  27  mm   pipe adapter  It is important that there  are no leaks where the pipe connects  to the detector     Place the detector so close to other  equipment that there is insufficient  room to access and change the dust  separator  filter  or access the RS   232 connector  if installed      Install the detector near high power  RF sources or in damp or exposed  areas     Attempt to re use dust separator   filter  cartridges once removed     Removing the front cover    To remove the front cover  unfasten the cover securing screw located on the bottom of  the unit  The cover may then be removed     20 ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 3  Installation and configuration    Mechanical installation    Refer to    Inside the detector    on page 9 for conduit  pipe interface information  and  mounting hole locations     The d
4.    ReadySET    TOwWAROS        1  ALARM  Illuminates to indicate that the smoke level has passed the detector s Fire 1 threshold  and  the normally open ALARM relay contacts have closed     2  PRE ALARM  Illuminates to indicate that the smoke level has passed the detector   s Pre Alarm  threshold  and the normally open PRE ALARM relay contacts have closed     3  FAULT  Illuminates to indicate a fault condition and that the normally closed FAULT relay contacts  have opened  Three additional LEDs indicate the type of fault     4  OK  Illuminates to show normal operation when there are no faults  The OK lamp will flash during  the 15 minute FastLearn period when the detector is first learning about its environment   Note  During initial setup  the OK LED will flash for 15 minutes while the detector learns its operating  environment  This does not indicate a problem with the detector     8 ReadySET Aspirating Smoke Detection System Installers Handbook     5     Chapter 2  Product description    FLOW  Illuminates to indicate an airflow fault  This may be due to blocked or broken pipes  although  it can also occur if  for example  factory warehouse doors are opened on a windy day  a large  pressure change occurs  or if industrial air conditioning turns on  Another possible cause is that the  aspiration fan connection cable is damaged or disconnected    FILTER  Illuminates to indicate that the detector   s filter needs to be changed    HEAD  Illuminates to indicate a problem with th
5.   Static discharge can be reduced by adhering to the following guidelines     e Always use conductive or antistatic containers for transportation and storage  if  returning any item     e Wear a wrist strap while handling devices and ensure that a good ground is  maintained throughout the installation process     e Never subject a static sensitive device to sliding movement over an ungrounded  surface and avoid any direct contact with the pins or connections     e Avoid placing sensitive devices onto plastic or vinyl surfaces     e Minimize the handling of sensitive devices and printed circuit boards  PCBs      12 ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 3  Installation and configuration    System design    Pre engineered piping designs simplify the installation of the detector pipe network   The following criteria ensure that the airflow and transport times are within the design of  the detector  The design parameters listed below must be adhered to for all pre   engineered pipe designs  Pre engineered piping networks should not exceed the  transport time requirement of 120 seconds  During the system test  transport times are  often less than 55 seconds     e The maximum of three elbows and one pipe tee can be used in any pipe network  design     e When using a pipe tee  it must be located within 20 feet of pipe from the detector     e All capillary tubes will have a maximum length of 3 feet and use a 9 64 inch  sampling hole size     e The f
6.   operating conditions     Commissioning checklist    The following brief checklist allows quick setup of the detector  This procedure will be  adequate for most standard installations     Caution  Ensure all wiring connections are checked prior to powering up the detector   Incorrect wiring of the detector will cause permanent damage to the detector     1  Before powering up the detector  visually check all cabling to ensure correct  connection  If wire identification is not immediately clear  e g   by use of different  colored wires or wire identification sleeves   an electrical check should be made     2  Disconnect the detector from the fire control unit  if applicable     3  Power up the detector and wait for the 15 minute FastLearn cycle to finish  The OK  LED will be steadily lit when complete     4  The detector automatically performs a FastLearn cycle which takes approximately 15  minutes  The OK indicator on the front panel will begin to flash  When using  day night switching  check that day start and night start settings reflect site  operations     30 ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 4  Commissioning    5  The detector will generate no alarms during the 15 minute FastLearn period and  after  this  the detector will operate at a reduced sensitivity for 24 hours while ClassiFire  learns and acclimates to the protected environment and sets up appropriate day and  night sensitivity settings     6  Reconnect the detector to the 
7.   unit and secure the cover to the unit using the cover mounting screw     Note  The detector is designed solely for operation with the front cover securely fitted  using the cover mounting screw     Removing the detector    Removing the detector is the reverse of the installation process  disconnecting the  pipework and wiring connections installed in the unit     28 ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 4  Commissioning    Summary    This chapter provides information to commission the ReadySET detection system     Content    Introduction 30  Precommissioning preparation 30  Commissioning checklist 30  Acclimation period 31  Suction pressure verification 31  Transport time verification 31  Gross smoke test 32    ReadySET Aspirating Smoke Detection System Installers Handbook 29    Chapter 4  Commissioning    Introduction    This chapter covers the commissioning procedures for the ReadySET detector   Commissioning strategy initially depends upon the detector   s environment   Commissioning should only be done by factory trained technicians in accordance with  the same applicable standards listed in Chapter 3    Installation and configuration    on  page 11     Precommissioning preparation    Commissioning should be performed after all construction has been completed and  cleaned of any lingering post construction dirt  If ambient monitoring conditions are  recorded before the installation is cleaned up  they may not accurately reflect normal
8.  268 Smoke Detectors for Fire Alarm Signaling Systems  UL 268A Smoke Detectors  for Duct Application  and ULC 5527 Standard for Control Units for Fire Alarm Systems     Limitation of liability    To the maximum extent permitted by applicable law  in no event will UTCFS be liable for  any lost profits or business opportunities  loss of use  business interruption  loss of data   or any other indirect  special  incidental  or consequential damages under any theory of  liability  whether based in contract  tort  negligence  product liability  or otherwise   Because some jurisdictions do not allow the exclusion or limitation of liability for  consequential or incidental damages the preceding limitation may not apply to you  In  any event the total liability of UTCFS shall not exceed the purchase price of the product   The foregoing limitation will apply to the maximum extent permitted by applicable law   regardless of whether UTCFS has been advised of the possibility of such damages and  regardless of whether any remedy fails of its essential purpose     Installation in accordance with this manual  applicable codes  and the instructions of the  authority having jurisdiction is mandatory     While every precaution has been taken during the preparation of this manual to ensure  the accuracy of its contents  UTCFS assumes no responsibility for errors or omissions     Only qualified persons experienced  trained and certified in the installation of this  equipment should design  servic
9.  7  Indicators 8   Inside the detector 9    ReadySET Aspirating Smoke Detection System Installers Handbook 5    Chapter 2  Product description    Introduction    The ReadySET detector is a highly sophisticated    next generation    aspirating smoke  detection product that provides early detection and warning of smoke  Designed for  easy installation and commissioning  the ReadySET incorporates a patented    artificial  intelligence    known as ClassiFire  which allows the detector to configure itself to  optimum sensitivity  alarm thresholds  and minimum nuisance alarms for various  environments  The ReadySET detector can monitor an area of up to 2 500 sq  ft    232 sq  m      The ReadySET detector is a smoke detector intended to provide localized fire  detection  It is suitable for use in a wide range of applications  such as  small noncompartmentalized rooms  warehouse racking  or pieces of electronic or  electromechanical equipment where it is desirable to achieve individual fire reporting  In  compartmentalized rooms  each compartment would normally use individual detectors     The ReadySET detector operates by drawing air from a protected space via a  supervised piping network in relatively small areas  The sampled air is passed through  a  dust separator  to remove dust and dirt before entering the laser detection chamber   Sophisticated  state of the art electronics are used to analyze the sampled air and  generate a signal representing the level of smoke present     C
10.  Alarm factor 6 OFF OFF   Alarm factor 7 ON OFF   Alarm factor 8 OFF ON   Alarm factor 9 ON ON   Classifire On OFF   Fixed alarms ON    Flow limit offset   40 OFF OFF   20 ON OFF   5 OFF ON    3 ON ON   Flow delay  240 seconds OFF  30 seconds ON   Input select  Psu fault OFF    Classifire ON  Override    Auto calibration  Enable OFF  Disable ON                                     Note  The settings in bold text are the factory default settings     26 ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 3  Installation and configuration    Alarm factor    The detector calculates sensitivity relative to the ambient pollution level  Higher Alarm  Factors provide reduced sensitivity     Note  Changing the alarm factor starts a new FastLearn cycle     Alarm factor  The ClassiFire system statistically analyzes the background smoke level  and sets detector sensitivity to a level giving a statistical probability of nuisance alarm   The software assesses the arithmetic mean and variance  standard deviation  of the     normal    ambient smoke level and places the alarm flags at a certain number of  standard deviations from the mean of the distribution     The number of standard deviations at which the alarm flag is set away from the mean is  directly proportional to the ClassiFire alarm factor chosen     The probability of nuisance alarm and the maximum detector sensitivity are higher when  a low level of alarm factor is chosen and lower as the alarm factor is incr
11.  Figure 11 on page  25     The INPUT terminals on the detector circuit board are set by default to monitor the  power supply  If power supply monitoring and ClassiFire override are not required  fit a  wire link across the two terminals to prevent a fault condition on power up     Make all connections shown in Figure 11 on page 25     24 ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 3  Installation and configuration    Figure 11  Wiring diagram    KEY   NC   Normally Closed  C   Common  NO   Normally Open       Detector    EOL Resistor  must be placed  at last daisy  chained    Short will indicate  Pre Alarm    PSU Fault Monitoring   DIP Switch  7 set    Short to reduce  Sensitivity by  50   DIP Switch   7 set to ON     Configuration    The default settings of the detector meet most application needs  These settings can be  customized to meet additional requirements  Customizing the ReadySET detector  requires changing the settings of the eight segments of the configuration DIP switch   Figure 12  mounted on the main PCB  See Table 3 on page 26 and the paragraphs  following the table to determine the proper switch setting for the application     ReadySET Aspirating Smoke Detection System Installers Handbook 25    Chapter 3  Installation and configuration    Figure 12  DIP switch          Table 3  DIP switch settings          Setting Switch   Switch   Switch   Switch   Switch   Switch   Switch   Switch  1 2 3 4 5 6 7 8   Set detector   sensitivity  
12.  detector head  is outside its normal range  a trouble condition will be generated   Cleaning the detector    The exterior of the detector should be cleaned as necessary  Clean the detector  with a damp  not wet  cloth     ReadySET Aspirating Smoke Detection System Installers Handbook 39    Chapter 6  Maintenance    Caution  Do not use solvents to clean the detector  Use of solvents may cause  damage to the detector     Replacing the dust separator filter cartridge    The only part that may require field replacement during servicing is the dust  separator filter cartridge  The    FILTER    LED will illuminate when the detector   s air  filter needs to be changed     WARNING  If  due to the environment of the area being protected  the dust in the  dust separator filter will expose maintenance personnel to health hazards  it is  recommended that suitable masks and protective clothing be worn when changing filters   Maintenance work should be performed in compliance with OSHA if applicable     Note  Used dust separator cartridges are not intended for reuse and should be  discarded    To replace the filter    1  Remove power to the detector    2  Remove the front cover mounting screw securing the unit   s front cover     3  With the front cover removed  grasp the filter firmly and pull the filter out  directly  towards you      4  Properly dispose of the used cartridge     5  Locate the orientation markings on the new filter cartridge  The word    IN    is  marked on one side and
13.  does have one major disadvantage  If the ventilation  becomes inoperative  the air flow through the duct system ceases and the smoke   detection system becomes ineffective     Figure 7  Return air duct sampling    Direction  of air flow    of duct width            2 3 to 3 4    1 4 to 1 3  of duct width       Exhaust pipe Intake pipe  from detector to detector    Figure 7 above shows a typical sampling pipe arrangement for an air duct  The right  pipe is the sampling pipe and the holes on it are drilled 4 inches apart and face into the  oncoming air stream  The left pipe exhausts air from the detector     The detector is UL 268A and ULC approved for duct applications with an operating air  velocity range of 300 to 4 000 ft min  1 52   20 32 m sec   The following guidelines    apply   e Only one duct can be monitored per detector     ReadySET Aspirating Smoke Detection System Installers Handbook 17    Chapter 3  Installation and configuration    e Ifthe sampling pipe system and ReadySET detector is used as the primary smoke  detection system  methods should be employed to notify stoppage of airflow in the  duct s      e The exhaust air from the detector must be returned back to the duct using an  exhaust port adapter and associated piping  This requirement assures positive  airflow through the detector     e Locate sampling pipe in the main supply duct return side  downstream of the filters  and a minimum of six duct widths from any source of turbulence  such as bends   inlet
14.  more frequent procedures may be required by applicable codes and  standards     Maintenance procedures    The following paragraphs outline general scheduled maintenance procedures     Visual check    The visual check must be performed at least every six months  This check is to  ensure pipe network integrity  Ensure that the design is still valid  Building upgrades  can require changes to the piping and detector requirements     To perform the visual check  observe the entire piping network and check for  abnormalities in the pipes including any breaks  blockages  crimps  etc   Battery status check    Caution  Any battery that has been in service for 36 months or more must be  replaced     The battery backup used in the power supply to power the detector must be tested  at least every six months     A battery status check is best accomplished by running the load with the batteries  for about one hour  While the load is still on  measure the individual battery voltages   If any battery reads 1 5 V or more below its rated voltage  that battery should be  replaced     38 ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 6  Maintenance    Generally  if one of a series set of batteries is low  the others will soon fail  Therefore  it  is advisable to replace all the batteries of a series set when one requires  replacement     Gross smoke test    The gross smoke test is a go no go test which ensures that the detector responds  to smoke  This test must be pe
15.  the other is marked    OUT        6  Insert the replacement filter cartridge  part number 33 30755  so that the    IN     mark on the cartridge is on the left as viewed in Figure 14 on page 41     7  Slide the cartridge all the way into place     8  Replace the detector cover and secure it into place  Initiate a FastLearn routine  by re energizing the detector     40 ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 6  Maintenance    Figure 14  Location of dust separator  filter  cartridge        1g  iik        a  ile    gt   pri  L      gt    9   ic  5J i  9  EE    Dust Separator  Filter Cartridge       ReadySET Aspirating Smoke Detection System Installers Handbook 41    Chapter 6  Maintenance    42    ReadySET Aspirating Smoke Detection System Installers Handbook    Appendix A  Communications card    Summary    An optional communications card can be fitted inside the ReadySET detector  The  ReadySET is also available in a model that is shipped with the communications card  factory installed     ReadySET Aspirating Smoke Detection System Installers Handbook 43    Appendix A  Communications card    Optional communications card    An optional communications card can be fitted inside the ReadySET detector to provide  an RS 232 serial port and RS 485 network communication  A ReadySET model is also  available with the communications card factory installed     Figure 15  Optional communications card    Detector address DIL switch  The detector address is s
16. 85 network  communication via the A  B  and SCREEN terminals on the detector main board  see  Figure 9 on page 22   This can be used for simple remote display indication or  integration into a larger site wide management and display system  separate from the  local fire detection and alarm system     ReadySET Aspirating Smoke Detection System Installers Handbook 45    Appendix A  Communications card    46 ReadySET Aspirating Smoke Detection System Installers Handbook    Glossary      C    F    AC  ADA  AH  AHJ  ARC  AWG  CSFM  DACT  DC  DET  EOLD  EOLR  FM    HSSD  Hz    LCD  LED  MEA    NAC  N C   NEC    Degrees centigrade   Degrees Fahrenheit   Ampere   Alternating current   Americans with Disabilities Act  Ampere hour   Authority having jurisdiction  Automatic release circuit  American wire gauge  California State Fire Marshal  Digital alarm comm  transmitter  Direct current   Detector   End of line device   End of line resistor   Factory Mutual   Feet   High sensitivity smoke detector  Hertz  frequency    Inches   Liquid crystal display   Light emitting diode    Materials and Equipment Acceptance  Division of the City of New York    Notification appliance circuit  Normally closed    National Electrical Code    ReadySET Aspirating Smoke Detection System Installers Handbook    47    Glossary    NFPA National Fire Protection Association  N O  Normally open   NYC New York City   PCB Printed circuit board   pF Picofarads   P N Part number   PSU Power supply unit   RAM Random a
17. Installers Handbook 13    Chapter 3  Installation and configuration    Sample pipe networks    Simple designs with short sampling pipes produce the best results  Maximum allowed  sampling pipe length is 164 feet  50 meters  in still air  In areas or applications where  the external airflow rate is greater than 3 feet per second  1 meter per second   the  maximum sampling pipe length is reduced to 33 feet  10 meters      Figure 3  Sample pipe network  Single pipe sampling network    10 ft  or greater           ReadySET  detector       Two branched pipe sampling network              10 ft  or greater        ReadySET  detector    14 ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 3  Installation and configuration    Air handling unit installation    No more than one air handling unit may be protected with one ReadySET detector   In this application  ensure that the sampling pipe is raised clear of high velocity air in the  immediate vicinity of the air intake grill on standoff posts as shown in Figure 4 below     Figure 4  Air handling unit in vicinity of the ReadySET detector  exhaust pipes not shown for  clarity        Sampling pipe aces       Incorrect        Detector        Direction  of smoke         Equipment  cabinet       Below above the ceiling installation    The ReadySET detector is supplied with an exhaust port  see Figure 2 on page 9   This  allows the ReadySET detector to sample from areas which may be at different air  pressure than the d
18. Intelligence    ReadySET Aspirating  Smoke Detection System  Installers Handbook    P N 9 14502   REV 03   ISS 19JUN12    Copyright  Manufacturer    Contact information       2012 UTC Fire  amp  Security  All rights reserved     Kidde Products Limited   Unit 2 Blair Way Dawdon   City  Seaham  County Durham  SR7 7PP   United Kingdom   Telephone   44  0 191 513 6100  Fax   44  0 191 513 6102    For contact information  see www utcfireandsecurity com     Content    Important information ii    Chapter 1 Introduction 1  About this manual 2  Intended audience 2  Aspirating smoke detection system limitations 3    Chapter 2 Product description 5  Introduction 6  Features 6  Specifications 7  Indicators 8  Inside the detector 9    Chapter 3 Installation and configuration 11  Introduction 12  Antistatic precautions 12  System design 13  Installation 19    Chapter 4 Commissioning 29  Introduction 30  Precommissioning preparation 30  Commissioning checklist 30    Chapter 5 Troubleshooting 33  Troubleshooting 34    Chapter 6 Maintenance 37  Introduction 38  Scheduled maintenance 38  Maintenance procedures 38    Appendix A Communications card 43  Optional communications card 44    Glossary 47    Index 49    ReadySET Aspirating Smoke Detection System Installers Handbook    Important information    Regulatory information    This product has been designed to meet the requirements of NFPA 72 National Fire  Alarm Code  UL 864 Standard for Control Units for Fire Protective Signaling Systems   UL
19. T Aspirating Smoke Detection System Installers Handbook    Chapter 1  Introduction    Summary  This chapter provides information about this manual     Content    About this manual 2  Intended audience 2  Aspirating smoke detection system limitations 3    ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 1  Introduction    About this manual    This manual provides information on how to install  configure  maintain  and operate the  ReadySET Aspirating Smoke Detector  It is organized as follows     Chapter 1  Introduction  Provides information about this manual     Chapter 2  Product description  Provides technical descriptions of the detector and its  operation  It also provides descriptions of the indicators     Chapter 3  Installation and configuration  Provides instructions for design and  installation of the ReadySET Aspirating Smoke Detection System     Chapter 4  Commissioning  Provides procedures for commissioning the ReadySET  detector     Chapter 5  Troubleshooting  Provides troubleshooting steps     Chapter 6  Maintenance  Provides scheduled and unscheduled maintenance  procedures     Appendix A  Communications card  Provides installation information for the optional  communications card     Intended audience    This manual is to be used by qualified and factory trained personnel  Knowledgeable of  NFPA standards and any other applicable standards in effect  and is intended to provide  guidance to qualified technical professionals for the inst
20. allation  operation  testing  and  maintenance of the ReadySET Air Sampling Detector  referred to in this manual as the  ReadySET or the detector     2 ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 1  Introduction    Aspirating smoke detection system limitations    An Aspirating smoke detection system     which can be made up of smoke detectors   heat detectors  manual pull stations  notification appliances  and a fire alarm control unit  with remote notification capability     can provide early warning of a developing fire   Such a system  however  does not assure protection against property damage or loss of  life resulting from a fire     Any fire alarm system may fail for a variety of reasons  The following are only examples     e Smoke detectors may not sense fire where smoke cannot reach the detectors  such  as in chimneys  in walls  on roofs  or on the other side of closed doors     e Smoke detectors on one level also may not sense a fire on another level or floor of a  building  A second floor detector  for example  may not sense a first floor or  basement fire     e All types of smoke detectors     ionization  photoelectric and air aspirating     have  sensing limitations  No type of smoke detector can sense every kind of fire caused  by carelessness and safety hazards such as smoking in bed  violent explosions   escaping gas  improper storage of flammable materials  overloaded electrical  circuits  children playing with matches  or arson 
21. ccess memory   SLC Signaling line circuit   TB Terminal block   UL ULI Underwriters Laboratories  Inc   V Volts   VAC Volts AC   VDC Volts DC   VRMS Volts root mean square    48 ReadySET Aspirating Smoke Detection System Installers Handbook    Index    A    Addressing  DIP switch location  7  Advisory messages  iii  Alarm factor  27  Antistatic precautions  12  Aspirating smoke detection system limitations  3  Auto calibration  28    C    ClassiFire  6  20  24  26  27  28  31  Cleaning the detector  39  Commissioning  29  Acclimation period  31  Commissioning checklist  30  Precommissioning preparation  30  Suction pressure verification  31  Transport time verification  32  Communications card  44  Configuration  25    D    Detector internal components  9  21  DIP switch settings  26  Dust separator filter cartridge  replacing  40    F    FastLearn  8  27  28  30  34  40  Fixed alarms  27  Flow delay  28    Indicators  8  ALARM  8  FAULT  8  FLOW  9  HEAD  9    OK  8  PRE ALARM  8   Input connection  24   Input select  28   Installation  19  Electrical installation  21  Installation guidelines  19  Mechanical installation  21    Maintenance  37  Maintenance procedures  38  Scheduled maintenance  38    P    Power supply connections  23    R    Relay connections  23  Removing the detector  28    S    Safety summary  iv   Specifications  7   System design  13  Air handling unit installation  15  Below above the ceiling installation  15  Return air duct sampling method  17  Retur
22. cur when the airflow rate into the detector exceeds the  programmed parameters  This usually occurs when there has been some  change in conditions  It may indicate that a sampling pipe is damaged  or  that the pipe has been blocked  e g   by nearby building operations     Flow monitoring is too sensitive for the environment  Increase the flow limit  offset     If the detector input is sampled from one area and the exhaust is in  another area with different pressure  e g   the detector is in a roof space and  sampling from an enclosed room   this may lead to flow faults  In this case  it  would be necessary to lead a pipe from the exhaust to the protected area  to ensure nominal flow     The airflow may be subject to temporary changes  spikes   Increase the flow  delay to 240 seconds     Check that installed pipework is fitted with end caps  When used   PipeCAD pipe modeling software prompts for the use of appropriate end  caps  Open bore pipes are not recommended     Sampling pipe may be too long or have too many sampling  holes capillaries or incorrect hole sizes  Check the design with pipe  modeling software  For pre engineered piping  ensure that the piping is  within the specified parameters     Sampling pipes  sampling holes and or the exhaust pipe may be partially  blocked by dust or debris  Clean pipe work with dry compressed air  and or clean the sampling holes     Fan may be defective  Send detector to manufacturer for repair   Electrical lead from fan may be disconn
23. e  maintain  test  install  and configure the ReadySET   They must be familiar and experienced with the wiring diagrams and components   electrical installation  and familiar not only with NEC  relevant NFPA and local codes but  also trained and qualified by the manufacturer and or its associated operating  companies  The manufacturer of the components that make up the ReadySET detector  is not responsible for its configuration or installation of the product     It is the responsibility of the professional installer  described above  to properly install   configure and test the systems  Under no circumstances will the manufacturer be liable  for improper installation  maintenance  servicing  testing or configuration of the systems     ii ReadySET Aspirating Smoke Detection System Installers Handbook    The technical data contained herein is provided for informational purposes only and  should not be used as a substitute for professional judgment and training  Although the  manufacturer believes this information to be true and correct  it is published and  presented without any guarantee or warranty whatsoever  The manufacturer disclaims  any liability for any use of the data other than as set out in this manual     Advisory messages    Advisory messages alert you to conditions or practices that can cause unwanted  results  The advisory messages used in this document are shown and described below     WARNING  Warning messages advise you of hazards that could result in injury o
24. e detector laser chamber  as might be caused by the  laser head connecting cable being damaged or disconnected  It can also be caused by certain kinds  of internal system faults  which appear in the detector   s event log as    process errors       Note  If the FAULT LED is illuminated but none of the additional LEDs are lit  it indicates a problem  with the power supply if its fault output is connected to the detector   s INPUT terminals     Inside the detector    Figure 2 below shows the main interior parts of a detector with the cover off     Figure 2  ReadySET internal components        43  Taa      WM     Two holes for conduit connection  There are two 3 4 in  drilling guides provided on the top of the  detector and one on the bottom providing holes for conduit    Pipe entries provide a connection for 3 4 inch pipe  A 3 4 in  male to 25 mm female adapter is  required when using larger than 1 inch  27 mm  O D  pipe    Note  Do not glue pipes into the detector to allow for future removal    Aspirating fan connector lead  If this lead is broken or not connected  the fan will not turn and the  detector will indicate a FLOW fault    Main PCB  No user serviceable parts     ReadySET Aspirating Smoke Detection System Installers Handbook 9    Chapter 2  Product description    Note  The PCB is fixed in place with 5 M3 x 6 screws  The detector should not be operated with any   of the screws missing  as this could cause air leaks and unreliable operation    Power supply connection t
25. e sampling holes  The sampling holes  should be in the direction of the airflow with an end cap     When using the air grill sampling without another sampling method  the smoke   detection system will be ineffective when the ventilation system is inoperative  If this  method is being used as the primary smoke detection system  the grill should be  monitored for stoppage of airflow     18 ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 3  Installation and configuration    Figure 8 below shows a typical mounting to stand sampling pipe away from high velocity  low pressure air at the entrance to the return air grill     Figure 8  Return air grill sampling method                      Air flow    f b Self tapping  NS screws iian      AN IN TITTY I  A   LL     Stand off post  saing NW  S   25 100mm  1 4    holes            Return air    Air flow au grill facia  Installation    Installation guidelines    The following is a brief set of guidelines on installing detectors     The detector should normally be mounted at a level where there is easy access     The exhaust air from the unit must not be impeded in any way  If the detector is  mounted in a different air pressure than where the air is being sampled  for example  an air duct   then a pipe must be routed from the exhaust port back to the same air  pressure zone as the sampling holes     All wiring must comply with NEC  NFPA 70  and the requirements of the local AHJ   All signal cables must be suitable 
26. e shielded  screened  wire to the    EARTH    screw terminal     Figure 10  Power supply terminals       Relay connections    The ReadySET detector includes an Alarm and a Pre Alarm relay  which will  transfer to the normally open  NO  position on alarm  It also includes a general  Fault relay  which will transfer to the normally closed  NC  position during a fault  condition or on power down     ReadySET Aspirating Smoke Detection System Installers Handbook 23    Chapter 3  Installation and configuration    The relays are of the volt free type  with a maximum current capacity of 1 A at 24  VDC maximum  To comply with radiated immunity requirements  it is recommended that  the relay connection wires be looped once around a suppression ferrite  provided    There should be about 1 1 4 inch  30 mm  of wire between the end of the ferrite and the  terminal block to give adequate stress relief  To achieve this  it is necessary to strip  back the cable shield approximately   5 inches  130 mm   The shield should be terminated under the cable gland cap     The ReadySET detector interfaces to fire alarm panels using the detector   s ALARM   PRE ALARM  and FAULT relay contacts     Make all connections shown in Figure 11 on page 25     Input connection    The ReadySET detector is fitted with an    INPUT    connection  This provides an input  which can be used to monitor the PSU or to desensitize the detector by using the  day night feature  DIP switch number 7 must be set as described in
27. eased  A low  alarm factor may be desirable in the case of a high value computer center where the  cost of down time and call out costs may be offset by the high value of the protected  installation     On the other hand  this will not be desirable in a machine shop with very variable levels  of background smoke  In this case  it may be more important to ensure that an elevated  level of smoke really does indicate an incipient fire before alarms are raised     The probability of nuisance alarm for a given environment also depends on the     stability    of the background smoke level  For example  a clean  controlled environment  will unlikely have a smoke level that will vary over time  Under these circumstances  a  low alarm factor will not imply a radically increased probability of nuisance alarm     ClassiFire On    Selecting ClassiFire On allows the artificial intelligence system to continuously adjust  alarm thresholds in order to avoid unwanted alarms from environmental changes   recommended      Note  Disabling this feature means that nuisance alarms due to fluctuations in ambient  pollution levels become more likely   Fixed alarms    Switches the artificial intelligence system off  locking sensitivity to that set at initial  setup  This deactivates the dust filter monitoring system  not recommended      Note  Enabling this feature means that nuisance alarms due to fluctuations in ambient  pollution levels become more likely     ReadySET Aspirating Smoke Detection Syst
28. ected  Reconnect lead   This occurs when a problem is present in the detector laser chamber     Inspect wires that are connected to the laser head for damage and loose  connections     Contacting technical support    Tel  1 800 655 4497  Fax  1 866 226 2126  AirIntelligence  Techsupport fs utc com    ReadySET Aspirating Smoke Detection System Installers Handbook 35    Chapter 5  Troubleshooting    36 ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 6  Maintenance    Summary    This chapter provides scheduled and unscheduled maintenance procedures     Content    Introduction 38  Scheduled maintenance 38  Maintenance procedures 38    ReadySET Aspirating Smoke Detection System Installers Handbook    37    Chapter 6  Maintenance    Introduction    This chapter contains maintenance instructions for the ReadySET aspirating smoke  detection system  These procedures should be performed on a scheduled basis  In the  event that system problems are found during routine maintenance  refer to     Troubleshooting    on page 34  Failure to properly maintain the system may affect the  functioning of the system     Scheduled maintenance    The scheduled maintenance of the system should be performed at an established  interval  At a minimum  the interval between performance of maintenance procedures  should not exceed any applicable regulations   See NFPA 72 or other local  requirements   This chapter contains minimum maintenance procedures  however   additional and or
29. ectronic devices  this system may operate erratically or can be  damaged when subjected to lightning induced transients  Although no system is  completely immune from lightning transients and interference  proper grounding will  reduce susceptibility     This manual gives information likely to be needed for most installations  but for more  detailed information on pipe networks  please refer to the PipeCAD System Design and  Installation User Manual     WARNING  The use of overhead or outside aerial wiring is not recommended due to  the increased susceptibility to nearby lightning strikes  Consult with the Technical  Support department if any problems are anticipated or encountered     iv ReadySET Aspirating Smoke Detection System Installers Handbook    Do not install electronic assemblies prior to mounting and attaching conduit for field  wiring to the enclosure  Before making modifications  verify that they will not interfere  with battery and printed circuit board locations  Do not overtighten screw terminals   Overtightening may damage threads  resulting in reduced terminal contact pressure and  difficulty with screw terminal removal     This system contains static sensitive components  Always ground yourself with a proper  wrist strap before handling any circuits so that static charges are removed from the  body  Use static suppressive packaging to protect electronic assemblies removed from  the control unit     Follow the instructions in this manual  These instructions 
30. em Installers Handbook 27    Chapter 3  Installation and configuration    Flow limit offset    Flow limit offset sets the sensitivity of the airflow monitoring system  A small offset  makes the system very sensitive to air flow changes  This detector must react to  20   changes in airflow  which equates to a change in flow sensor reading of  5  Areas with  fluctuating air pressures may require a less sensitive setting     Note  Changing the flow limit offset starts a new flow calibration set up     Flow delay    Sets the time for which a flow fault must continue before a fault is signaled     Input select  The detector input terminal may be used to either monitor an associated power supply  for faults  or for ClassiFire override  reduces normal sensitivity by 50       Note  In the factory default condition  the switch is set to OFF  power supply  monitoring   This gives a fault condition if there is an open circuit on the INPUT  terminals  Fit a wire link if you do not require power supply monitoring  If you fit a wire  link across the INPUT terminals  you must set this switch OFF  or else the detector  sensitivity is dramatically and permanently reduced by the ClassiFire override function     Auto calibration    Auto calibration automatically starts a new FastLearn cycle when the detector is  powered up  This may be disabled if the previous settings need to be retained     Final installation    Once the power and signal connections are made  place the detector cover onto the
31. erminals   Volt free relay contact terminals   Configuration DIP switch  Used to configure user selectable detector functions    Input switch terminals   Optional communication terminals  used when the optional communication card is fitted to connect   the RS 485 network    10  Detector head ribbon connector  If this lead is broken or not connected  the detector will indicate a  HEAD Fault     11  Detector head assembly  No user serviceable parts  Do not remove this from the detector  due to the  risk of exposure to the laser     12  Detector head cover plate  This protects the laser head  The plate should not be removed from the  detector     13  Replaceable dust separator  This simply slides in and out of its mounting  The separator and its  replacement have IN written in red on one side  and OUT on the other to indicate correct orientation     14  Three mounting holes to mount the detector  Use  10 24 pan head screws for mounting   Note  Ensure that the detector is fixed to a flat surface so that the enclosure will not twist and  become damaged     5  6  7  8  9       E   w          10 ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 3  Installation and configuration    Summary    This chapter provides information necessary to install the ReadySET detector system     Content    Introduction 12   Antistatic precautions 12   System design 13  Sample pipe networks 14  Air handling unit installation 15  Below above the ceiling installation 15  Return a
32. et using a  reverse binary code  i e  switch 1 is  the least significant bit and switch 7  is the most significant bit  Switch 8  is not used   Set the address from 001 to 127 in    90999994S    order to identify the detector   Addresses in a detector network do  not have to be consecutive but must  be different     RS 232 serial port  e Use 9 pin D type null modem cable to  connect to PC        Direct connection of a PC to the communications card is done using a 9 pin  RS 232 interface on the communications card  using a null modem cable configuration   as shown in the diagram below     9 pin female  D  9 pin female  D   connector connector    en    on     a DUN G    44 ReadySET Aspirating Smoke Detection System Installers Handbook    Appendix A  Communications card    A connected PC can access the detector event memory to review previous or current  events  such as detector alarms or faults  The detector internal chart recorder can also  be accessed to allow analysis of detector behaviour  refer to the Remote Software  Configuration User Manual for further information   The PC cannot be used to configure  the detector except to enter time and date settings for the detector event log and chart  recorder to be viewed in the remote configuration software  The detector does not  incorporate a real time clock  so the time and date need to be re entered if the detector  is powered down for any reason     Installation of the communications card also provides the detector with RS 4
33. etector is connected to the installed sampling pipework and fixed to the mounting  surface using three screws of a type appropriate to the mounting surface  Ensure that  the sampling and exhaust pipes are securely seated in the pipe ports before securing  If  using a piped exhaust connection  be sure that the sampling and exhaust pipe are fitted  into the relevant port as shown in    Inside the detector    on page 9     Electrical installation    In keeping with good wiring practice  keep cables and individual stripped conductors as  short as possible while allowing stress relieving cable forming     Power cables should be current rated at 1 A or greater  Signal cable should be 120 Q or  less twisted pair     Figure 9 on page 22 shows the terminal block connections that connect the ReadySET  detector to other electronic components  It is recommended that all connection wires be  marked with suitable identification labels or colored rings to aid in the connection  process     ReadySET Aspirating Smoke Detection System Installers Handbook 21    Chapter 3  Installation and configuration    Figure 9  Detector terminal block connections    22    Zz  O  zZ  O  Q  O  zZ  O  Z  QO  O     Z  O  z  Q  O       cars  a  v    LONI    OOO 00 000 000 000  oo       Linvs NYv1V 34d 3813    Io weno       POWER SUPPLY CONNECTIONS     Connect to 24 VDC 1 A power supply unit      Do not connect 0 V to earth ground      Use shielded cable with shield connected to the detector EARTH terminal       
34. etector location  Typical uses are for air duct sampling and allowing  the installation of the detector in under floor or ceiling voids or when sampling from  pieces of computer related equipment  See Figure 5 on page 16 and Figure 6 on page  16     ReadySET Aspirating Smoke Detection System Installers Handbook 15    Chapter 3  Installation and configuration    Figure 5  Installation of pipework above ceiling with exposed detector  piped exhaust                   4    Sampling pipe  a Exhaust pipe    False ceiling    Figure 6  Installation with detector mounted in ceiling void  no exhaust piping     Sampling hole    Sampling pipe    Detector    False ceiling    16 ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 3  Installation and configuration    Return air duct sampling method    Duct sampling generally is the most cost effective method of air sampling because the  pipe runs are minimal and a single detector may be used to cover a larger area  The  speed of response of the detector to smoke is given by the exchange rate in the rooms  ventilated by the duct ventilation system  This tends to be rapid  giving early warning of  any smoke present  This type of sampling is particularly suited to aspirated smoke  detection  since the smoke content in the air will tend to be diluted to a level below that  of point type detectors  Also  the relatively high airflow in the duct reduces the  effectiveness of point detection devices     The duct sampling method
35. fire control unit  if applicable    Acclimation period    The detector will operate at a reduced sensitivity for 24 hours  ClassiFire will set up the  appropriate day and night sensitivity settings  All air handling units  thermostats  and  other systems that can have an effect on the operating environment should be turned  on to simulate normal operating conditions as closely as possible  Investigate and  correct any condition that cannot be accounted for     Suction pressure verification    Sample hole suction pressures can be measured and recorded on the checklist for  future reference using the steps below     To perform a pressure test   1  Attach a flexible hose onto the suction side of the magnehelic pressure gauge   2  Place the hose against the sampling hole and hold it in place     3  Hold the gauge in the plane in which it was calibrated and read the suction pressure  from the gauge as shown in Figure 13 below     Figure 13  Magnehelic test setup        CEILING TILE    NU SAMPLE POINT  HOSE       inal KEY  MAGNEHELIC K  7      PRESSURE  GAUGE    ReadySET Aspirating Smoke Detection System Installers Handbook 31    Chapter 4  Commissioning    Transport time verification    A maximum transport time verification test measures the amount of time it takes for the  detector to respond to smoke that enters the sampling point furthest from the detector   The results of this test and the calculated maximum transport time from PipeCAD must  be recorded on the checklist if app
36. for the application     The detector must not be placed in areas where either the temperature or humidity is  outside the specified operating range     The detector should not be placed in close proximity to any equipment expected to  generate high radio frequency levels  such as radio alarms  or units generating high  levels of electrical energy  such as large electric motors or generators      ReadySET Aspirating Smoke Detection System Installers Handbook 19    Chapter 3  Installation and configuration    Table 2 below contains a list of procedural guidelines for installation of the ReadySET  detector     Table 2  Procedural guidelines       Do    Don   t       Ensure that the ClassiFire alarm factor is  appropriately set     Ensure that the power and signal cables are  correctly connected before powering up by  use of cable identifiers or electrical  continuity checks  Incorrect connection could  damage the detector     Ensure that cable of an appropriate  approved type is used for interconnection     Place sampling points so that the detector  will be able to detect smoke at the earliest  opportunity     Ensure that the detector exhaust is in an  area with the same atmospheric pressure  as the sample pipes  either by placing the  detector physically in the protected area or by  leading a pipe from the detector exhaust to the  protected area     Ensure that the environment of the protected  area is within the environmental operating  parameters of the detector  32   to 100
37. h the detector in  a clean environment     Check that the detector sampling points are in the smoke stream     Check that sampling pipes are firmly and cleanly seated in their ports and  undamaged     Check that the correct alarm factor setting has been set  if the alarm  factor is too high  change the alarm factor to a lower  more sensitive  setting     Check that the detector has had a 24 hour learning period     Check that the dust separator cartridge does not require changing   refer to    Replacing the dust separator filter cartridge    on page 40 for  details  and that the air plenum chamber is clean  The chamber may  become clogged when  for example  heavy building activity has  occurred near the sampling pipes  If so  the chamber may require factory  service  The detector is not designed to handle large quantities of coarse  debris and dust     There are many reasons why particle densities may vary  and the  ClassiFire system is designed to automatically compensate for this in  order to reduce the likelihood of nuisance alarms due to normal  variations in background smoke density  Within limits set by the  ClassiFire alarm factor  this is a normal part of the detector s operation     ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 5  Troubleshooting       Problem    Flow fault errors      FLOW    LED  illuminated     Long transport  times    Detector laser chamber  error   HEAD    LED  illuminated     Solution or corrective action    These oc
38. ir duct sampling method 17  Return air grill sampling method 18   Installation 19  Installation guidelines 19  Removing the front cover 20  Mechanical installation 21  Electrical installation 21  Configuration 25  Final installation 28  Removing the detector 28    ReadySET Aspirating Smoke Detection System Installers Handbook 11    Chapter 3  Installation and configuration    Introduction    This chapter provides information necessary to install the ReadySET detector system   Installation consists of the following steps     1  Unpack the shipping carton  Ensure that the package contains product literature   one ferrite ring  and the detector     2  Determine the optimum location for the detector   3  Mount the detector at the selected location   4  Connect the detector to the sampling pipe network     Installation should only be done by factory trained technicians in accordance with  applicable installation requirements  These include     e NFPA 70  National Electrical Code   e NFPA 72  National Fire Alarm and Signaling Code   e Any other local  national  or installation requirements or standards   Note  Power should be turned off during installation     Antistatic precautions    This system contains static sensitive components  Always ground yourself with a proper  wrist strap before handling any circuits     Caution  When handling any electric components or printed circuit boards  antistatic  precautions must be followed  Failure to do so may result in component damage     
39. irst sampling hole must be 10 feet or more from the detector     e The use of sampling capillary tubes and sampling holes can be mixed in any  combination on the pipe network     e On branch designs  the same number of sampling holes must be used on each  branch     Table 1  Sample pipe network parameters       Total pipe Max amount Max sampling Sampling Capillary tube End cap  length elbows points hole size sample hole size hole  164 feet 3 10 1 8 inch 9 64 inch 5 32 inch       Note  PipeCAD pipe modeling software is used to design pipe networks outside the  above parameters  Refer to the PipeCAD System Design and Installation User Manual for  complete instructions     The ReadySET detector employs a fan designed to detect smoke in relatively small  areas  The ReadySET detector is not intended to protect large areas  or to sample from  areas where there may be any difference in airflow rates or pressure differentials  If  detection in environments conforming to these descriptions is required  other AIR   Intelligence products should be used     Always locate the sampling points in positions to which smoke may reasonably be  expected to travel  It is usually better to locate the sampling pipe directly in the airflow   for example  across the return air register of an air conditioning unit      Note  There is no substitute for carrying out smoke tests prior to installation of pipework  to indicate suitable sampling point location     ReadySET Aspirating Smoke Detection System 
40. lassiFire intelligence also monitors the detector chamber and dust separator  filter  for  contamination  continually adjusting the appropriate operating parameters to counteract  the negative effects of any contamination  The ReadySET detector is unique in being  able to provide a consistent level of protection in a very wide range of environments by  continuously making minor adjustments to sensitivity     The ReadySET can easily be installed without any specialized tools or software     An optional communications card can be fitted inside the ReadySET detector to provide  an RS 232 serial port and RS 485 network communication  There is also a ReadySET  model that is shipped with the communications card factory installed  Refer to  Appendix A    Communications card    on page 43     Features    The following is a list of major features of the ReadySET detector     e Patented    artificial intelligence    known as ClassiFire  automatically learns  environment    e Laser dust discrimination  LDD    e Quick and easy installation   e Self adjusting between the range of 0 4  and 2 0  obscuration   e Pre engineered sampling pipe network designs   e Up to 2 500 sa  ft   232 sq  m  area coverage    6 ReadySET Aspirating Smoke Detection System Installers Handbook    Specifications    Chapter 2  Product description    Caution  This equipment is only to be used in accordance with this specification   Failure to operate the equipment as specified may cause damage to the unit  injury  o
41. licable  Measured transport time less than the  calculated time is acceptable     To measure the maximum transport time of the system   1  Determine the furthest sampling point from the detector   2  Allow test smoke to enter pipe at the furthest sampling point     3  Record the amount of time for the detector to respond  This is the actual maximum  transport time  This time must not exceed 120 seconds     Gross smoke test    The gross smoke test is a measurement of the amount of time elapsing from the  activation of the smoke generating medium  until PRE ALARM and ALARM states are  reached  This test should be repeated at least three times with consistent results  The  recommended smoke generating medium is canned smoke or a wire burner  Smoke  from a punk or cotton wick is also acceptable     Caution  Oil based canisters that are used to test point detectors are not suitable for  testing aspirating systems  as the particulate is heavy and tends to drop out in the pipe   never actually reaching the detector  Also  the oily residue that is left behind may affect  the functionality of the detector     When using canned smoke  introduce only enough smoke into the protected area to  cause a FIRE condition  This may require a number of practice sprays  Follow the  manufacturer   s instructions     32 ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 5  Troubleshooting    Summary   This chapter provides information about troubleshooting the ReadySET detecti
42. must be followed to avoid  damage to the control unit and associated equipment  System operation and reliability  depend upon proper installation     Caution  While installing a fire alarm system may make lower insurance rates possible   it is not a substitute for insurance  An automatic fire alarm system or components of a  system     smoke detectors  heat detectors  manual pull stations  notification  appliances  and a fire alarm control unit with remote notification capability     can  provide early warning of a developing fire  Such a system  however  does not assure  protection against property damage or loss of life resulting from a fire     General precautions  The following general safety precautions are to be observed at all times       All electrical components associated with equipment should be installed and  grounded in accordance with NEC and local regulatory requirements     e Special precautionary measures are essential to prevent applying power to  equipment at any time maintenance work is in progress     e Before working on electrical equipment  use a voltmeter to ensure that the  system is not energized     e When working near electricity  do not use metal rulers  flashlights  metallic  pencils  or any other objects having exposed conductive material     e When connecting a meter to terminals for measurement  use a voltage range  higher than expected voltage to be measured     ReadySET Aspirating Smoke Detection System Installers Handbook v    vi    ReadySE
43. n air grill sampling method  18  Sample pipe networks  14    T    Technical support  contacting  35  Testing  Battery status check  38  Detector sensitivity test  39  Gross smoke test  32  39  Transport time verification test  39    Index    Visual check  38  Troubleshooting  33    W  Wiring diagram  25    50    ReadySET Aspirating Smoke Detection System Installers Handbook    
44. on  system    Content    Troubleshooting 34  Troubleshooting the ReadySET detector 34  Contacting technical support 35    ReadySET Aspirating Smoke Detection System Installers Handbook 33    Chapter 5  Troubleshooting    Troubleshooting    Troubleshooting the ReadySET detector    This chapter provides some possible solutions if a problem should occur with your  ReadySET detector  If the problem is not addressed in this chapter or  if after  performing the suggested actions  the problem persists  contact Technical Support        Problem    Nuisance alarms  occur too often    Elevated smoke  levels do not  generate alarms    Low mean output    Detector sensitivity  varies over time    34    Solution or corrective action    This normally indicates that the detector is set at an alarm factor  inappropriate to the installed environment   ncrease the alarm factor to  reduce sensitivity     Check that the ClassiFire alarm factor setting is appropriate for the  normal working environment of the protected area     Check that the ClassiFire override switch is appropriately set to reflect  active and inactive periods     The sensor chamber may be contaminated   f so  return the detector to  the factory for cleaning and recalibration     Check that detector is not in FastLearn  if in FastLearn  the OK light will  flash   Check if green OK LED is on and flashing     The detector FastLearn cycle may have been carried out during or  immediately after a smoke test  Reinitialize FastLearn wit
45. ontrol unit and associated  equipment may be damaged by servicing while the unit is energized  Do not attempt to  install  service  or operate this control unit until this manual is read and understood     Cautions    System Reacceptance Test after Reprogramming  To ensure proper system  operation  this system must be retested in accordance with NFPA 72 Chapter 10 after  any programming change  Reacceptance testing is also required after any addition or  deletion of system components  and after any modification  repair  or adjustment to  system hardware or wiring     All components  circuits  and system operations known to be affected by a change must  be 100  tested  In addition  to ensure that other operations are not inadvertently  affected  at least 10  of initiating devices in a single installation that are not directly  affected by the change  up to a maximum of 50 devices  must also be tested and proper  system operation verified  in accordance with NFPA     This system meets FM and UL 268 requirements for operation at 32 to 100  F  0 to  38  C  and at a relative humidity of 90   noncondensing  at 90  F  32 2  C   However   the useful life of the system   s standby batteries and the electronic components may be  adversely affected by continuous operation at these environmental limits  Therefore  it is  recommended that this system and its peripherals be installed in an environment with a  nominal room temperature of 60 to 80  F  15 to 27  C      Like all solid state el
46. ors linked to a Command Module  use a serial  communications card in each detector  each set to an individual address   and communicate with the fire panel via a single APIC in the Command  Module     Use screened cable with screen connected to the detector EARTH   terminal     ReadySET Aspirating Smoke Detection System Installers Handbook    Chapter 3  Installation and configuration    WARNING  Electrocution hazard  All connections should be made with the power  turned off     Power supply connections    The grounded power supply cable should be routed through the metal cable gland  provided  leaving about 1 1 4 inch  35 mm  of the cable extending from the bottom of  the cable gland  Depending on the type of cable used  it may be necessary to  increase the diameter of the cable with sleeving or insulating tape to ensure that the  cable is firmly held when the cable gland is fully tightened     Note  If this equipment is part of a fire detection system  power should be supplied  from a supervised UL Listed power supply  designed for fire system use   To connect the power supply     1  Remove the ReadySET detector front cover  and then locate the power supply  terminal block     Refer to Figure 2 on page 9 for an illustration of the ReadySET detector with the  front cover removed  Refer to Figure 10 below for a detailed illustration of the power  input terminals     2  Connect 0 V and  24 VDC to the    OV      24  and     24V    screw terminals   respectively     3  Connect th
47. r    property damage           Specification Value   Supply voltage 22 25   26 40 VDC   Current consumption 350 mA   Dimensions 7 5 W x 9 0 H x 4 3 D  in   190 W x 230 H x 110 D   mm    Weight 2 65 Ibs   1 2 kg     Operating temperature range  Operating humidity range  Coverage area    Sensitivity range    obs ft      obs m     Maximum sensitivity resolution  Preengineered piping sample hole  Detection principle   Particle sensitivity range   Relay contact rating   Sampling pipe inlets   Sampling pipe internal diameter  Relay outputs    Chamber service intervals    Dust separator  filter  replacement intervals    Laser lifetime  MTTF   Programming  APIC compatible    Enclosure    32 to 100  F  0 to 38  C   UL 268 compliance   0 to 90  noncondensing  2 500 sq  ft   232 sq  m     Min    7 62   Max    0 122  FSD  Min    25   Max    0 4  FSD    0 12  obs ft   0 4  obs m    0 5  to 1 5  obs ft   1 64  to 4 92  obs m   Laser light scattering mass detection   0 0003 m to 10 m   1 A at 24 VDC resistive load   1   3 4 inch  20 mm    Alarm  Pre Alarm  and Fault   Greater than 8 years  depending on environment   Greater than 5 years  depending on environment   Greater than 1 000 years   Internal DIP switches   Yes   NEMA 1       ReadySET Aspirating Smoke Detection System Installers Handbook 7    Chapter 2  Product description    Indicators    Figure 1 below shows the seven indicators on a ReadySET detector     Figure 1  ReadySET detector indicators         P   ALARM     RENA    P FAULT 
48. r loss  of life  They tell you which actions to take or to avoid in order to prevent the injury or  loss of life     Caution  Caution messages advise you of possible equipment damage  They tell you  which actions to take or to avoid in order to prevent the damage     Note  Note messages advise you of the possible loss of time or effort  They describe  how to avoid the loss  Notes are also used to point out important information that you  should read     Product Symbols    This symbol appears on the main board of the unit and indicates that the  board contains static sensitive components     This label is located on the laser chamber at the bottom right of the open  detector and signifies that the unit is a Class 1 Laser product as specified  in IEC 60825 1  The unit incorporates a Class 3B embedded laser which    must not be removed from the detector  as retinal damage may result if  the laser beam enters the eye     This symbol indicates the safety ground studs  These are for grounding  cable screens  etc   and should not be connected to OV or signal earth           ReadySET Aspirating Smoke Detection System Installers Handbook iii    Safety summary    This entire manual must be read and understood before installation     Installation precautions  Adherence to the following will aid in problem free installation with long term reliability     WARNING  Several different sources of power can be connected to this detector   Disconnect all sources of power before servicing  The c
49. rformed at system commissioning and at least every  year thereafter     To perform this test  smoke must be introduced into the last sampling hole in each  branch of the pipe network and the proper detector response must be verified  Smoke  from a punk or cotton wick may be used  Canned smoke may also be used     Caution  Oil based canisters that are used to test point detectors are not suitable  for testing aspirating systems as the particulate is heavy and tends to drop out in the  pipe  never actually reaching the detector  Also  the oily residue that is left behind may  affect the functionality of the detector     Transport time verification test    The maximum transport time of the pipe network must be measured and compared to  the recorded transport time at commissioning   Refer to    Transport time verification     on page 32 for test details   The transport time verification test must be done at  commissioning and at least every year thereafter    Detector sensitivity test    The detector sensitivity test must be performed within one year of installation and at  least every alternate year thereafter     Example     e Year one check  e Year three check    The detector employs a self monitoring  automatically adjusting calibration for the  system  The inspection only requires a periodic visual inspection for a detector fault  indication and performing the detector sensitivity test function     If the self monitoring feature of the system senses that the operation of the
50. s  or deflection plates  to reduce the effects of stratification  In installations  where the filter is capable of removing smoke  install the sampling tube upstream of  the filter     Note  Where it is physically impossible to locate the sampling pipe in accordance  with this guideline  the sampling pipe may be positioned closer than six duct widths   but as far as possible from inlets  bends  or deflection plates     e Locate the sampling pipe such that dampers do not restrict airflow at the sampling  pipe    e The sampling pipe should be located before air exhausts from the building or before  diluting return air with outside air     e For accurate identification of the source of an alarm  locate sampling pipe as close  as possible to the protected area s air entry into the duct system     e Locate sampling pipe on the downstream side of the filter to sense fire in the filters   Note  If filters are blocked  sufficient airflow may no longer be present for proper  operation     e Do not locate sampling pipe near outside air inlets except to monitor smoke entry to  the handling system for adjacent areas     e Whenever possible  locate sampling pipe upstream of air humidifiers and  downstream of dehumidifiers     Return air grill sampling method    Return air grill sampling systems are designed with sampling pipes centered in the front  of the return air grill  Sampling holes should be spaced so that a minimum of three holes  are used for each grill  Larger grills require mor
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
インディアンテント「ティピー」標準価格表  user`s guide  Nova Pad Coffee Maker  LTODRIVE2.3    iDRAC Service Module 2.0 Guía de instalación  BitsyX User`s Manual - Eurotech Support Forums Topic Index  MSI Workstation WT60 2OK(4K Edition)-1252TR  Kenwood KDC-3020R User's Manual  Manuel d`utilisation    Copyright © All rights reserved. 
   Failed to retrieve file