Home

User Manual Model 1420 AC Power Supply

image

Contents

1. TEST INSTRUMENT SAFETY WARNING An electrical shock causing 10 milliamps of current to pass through the heart will stop most human heartbeats Voltage as low as 35 volts dc or ac rms should be considered dangerous and hazardous since it can produce a lethal current under certain conditions Higher voltages are even more dangerous Your normal work habits should include all accepted practices to prevent contact with exposed high voltage and that will steer current away from your heart in case of accidental contact with a high voltage You will significantly reduce the risk factor if you know and observe the following safety precautions 1 2 10 The Global Specialties Model 1420 Power Supply isa source of high voltage person using the instrument should be a qualified electronics technician or otherwise trained and qualified to work with high voltage Use only a polarized 3 wire ac outlet This assures that the power supply chassis case and ground terminal are connected to a good earth ground and reduces danger from electrical shock When servicing any equipment equipped with a two wire ac plug treat it as hot chassis type and connect it to the ISOLATED OUTPUT outlet of the ac power supply Even some equipment with a polarized plug are considered the hot chassis type Never connect two pieces of hot chassis equipment to ISOLATED OUTPUT outlets simultaneously There may be a serious shock hazard betwe
2. 4 Connect the ac power plug to the equipment under test to the ISOLATED OUTPUT receptacle of the ac power supply This provides the isolation as shown in Fig 8 WARNING CONNECT ONLY ONE HOT CHASSIS EQUIPMENT AT A TIME Unless both have an identical line to chassis relationship there is a shock hazard between two chassis 5 Turm the POWER ON 6 Select VOLTS function and adjust AC VOLTS control to desired voltage typically 120V 7 It is recommended that the chassis of the equipment under test be grounded with a test lead Connect Only One Hot Chassis EQUIPMENT UNDER TEST Equipment at a Time There May Be a Serious Shock Hazard Between Two Chassis aere MEN CIRCUITS Hot Earth Ground 1420 POWER SUPPLY Chassis 5 Isolated Isolated Output from AC Line Wall Outlet 120 VAC 60 Hz Q Transfi a Eliminates Hot Chassis Shock Hazard Ts a Test Lead Figure 8 Eliminating the Hazard of Servicing Transformerless Equipment 19 Wall Outlet TEST EQUIPMENT 120 VAC 60 Hz Connect Only One Hot Chassis Equipment at a Time There May Be a Serious Shock Hazard Between Two Chassis To Earth Ground or gt TRANSFORMERLESS Test Equipment Common EQUIPMENT UNDER TEST Figure 9 Using the AC Power Supply as an Isolation Transformer 20 The Model 1420 AC Power Supply offers continuously variable output voltage from 0 to 150 Se
3. Intermittent not to exceed 4 minutes at 4A followed by 5 minutes at 1A max METER SCALES Voltage cese e ERI En RR 0 150V 0 2A Volts 596 of full scale calibrated 120V AC Current 5 of full scale Leakage eec ree irte tees 200 A SPECIFICATIONS MODEL 1420 AC INPUT 120 VAC 60Hz 600 VA OPERATING TEMPERATURE RANGE 0 C to 40 STORAGE TEMPERATURE 30 to 60 C WEIGHT 2216 10kg DIMENSIONS WxHxD 10 5 x 5 7 x 12 267 x 145 x 305 mm PEAK CURRENT Inrush 30 max inrush limited to one cycle at 30A SOLDER IRON TEMPERATURE CONTROL 70 99 of power line 100W max FRONT PANEL CONTROLS Refer to Fig 1 1 2 3 POWER ON Switch POWER ON Pilot Light Function Switch Model 1420 Five interlocking pushbutton switches which select function and meter scale Pressing a button releases the previous selection The following selections are available VOLTS Connects meter to measure voltage at ISOLATED OUTPUT Use 0 150 VOLTS scales on meter Voltage is adjustable with AC VOLTS control AMPS 0 4 Connects meter to measure current of ISOLATED OUTPUT USE 0 4 AMPS scale on meter When voltage is set to 120 VAC the 0 480 VA scale may be used to measure the output load in volt amps AMPS 0 2 Connects meter to measure current of ISOLATED OUTPUT Use 0 2 AMPS scale on meter When voltage is set to 120VAC the 0 240VA
4. Monitor Voltage on Meter 5 Monitor Current on Meter 1420 AC POWER SUPPLY 3 Adjust to 120V or Other Rated Value EQUIPMENT UNDER TEST 1 Select 4 Select VOLTS AMPS Function Function Figure 11 Measuring Electrical Load 24 OPERATING INSTRUCTIONS Leakage Tester USING THE MODEL 1420 AS A LEAKAGE TESTER STANDARD LEAKAGE TEST As previously mentioned most equipment with a 2 wire ac power plug are the hot chassis type The plastic or wood cabinet normally insulates the chassis so the user cannot touch it Other exposed metal parts such as antennas antenna terminals knob shafts screw heads handles etc are also insulated or isolated with very high resistance to protect the user from electrical shock Most equipment manufacturers specify a leakage test after reassembly of the equipment to insure the continued protection of the user from electrical shock The standard leakage test requires a leakage probe consisting of a test lead in series with a 1 5kQ 10 watt resistor parallel by a 0 15uF capacitor One end of the leakage probe is connected to an earth ground Voltage across the resistor is measured on an ac voltmeter as the leakage probe is touched to each exposed metal part of the equipment An isolation transformer must not be used during the standard leakage test and the entire test must be repeated with the ac power plug reversed even if an adapter is required to reverse the connections of a
5. 85 volts at minimum to 118 volts at maximum this variation will not be achieved unless a load is connected TROUBLESHOOTING If the previously listed Performance Tests are performed in the sequence listed this provides a logical approach to defining symptoms and isolating defective circuitry The following information may help further isolate the problem No POWER ON Pilot Light This symptom indicates either a fault in the primary power circuit or a tripped circuit breaker Model 1420 The following checks should isolate the problem 1 Make sure the unit is plugged into a live outlet 2 Reset the circuit breaker Model 1420 3 Ifthe circuit breaker or fuse is okay verify whether there is any output from the supply select VOLTS function and note meter reading on 0 150V scale If output is available the pilot light bulb is probably defective If no output is noted the trouble is probably an open in the power transformer primary circuit Check continuity of the power cord fuseholder POWER ON switch variable auto transformer and the wiring interconnecting these parts 4 Ifcircuit breaker does not trip again or replacement fuse does not burn out when unit is turned on previous fault may have been caused by an overload connected at the ISOLATED OUTPUT 5 breaker trips again or replacement fuse burns out check for shorted variable auto transformer or power transformer No Output Pilot Ligh
6. is applied to the meter circuit Diodes D4 and 05 are reverse biased below 500 pA for expanded scale feature At higher leakage current the diodes become forward biased and shunt part of the current to compress the meter scale SOLDERING IRON TEMERATURE CONTROL CIRCUIT Model 1420 Only Input power is applied through triac TR1 to the soldering iron outlet on the rear panel Breakdown diode D1 does not gate the triac into conduction until its 30 volt threshold is reached Thus the triac does not conduct for the entire input cycle SOLDER TEMP control R2 forms part of an RC phase shift network which varies the phase of the trigger voltage in relation to the anode voltage of the triac This varies the non conduction period which adjusts the soldering iron temperature The circuit is automatically reset each time the ac passes through zero MAINTENANCE AND CALIBRATION 1 The following instructions are for use by qualified service personnel only To avoid electrical shock do not perform servicing other than contained in the operating instructions unless you are qualified to do so 2 When the unit is plugged into an ac outlet even if the POWER ON switch is off ac line voltage is present as some input power circuits Observe caution any time the case is removed from the instrument PREVENTIVE MAINTENANCE Do not overload the instrument Excessive output current can damage the variable auto transformer Prolonged use at high current a
7. is inserted Touching a hot chassis is hazardous and can cause fatal electrical shock WARNING Just because a unit uses a polarized power plug does not guarantee safety Some equipment with a bridge rectifier uses a polarized power plug and as mentioned above always has a hot chassis 16 Transformerless Half Wave Rectifier Equipment Another commonly used transformerless power supply circuit is a half wave rectifier where one side of the ac power line connects directly to the chassis also shown in Fig 7 Unless the equipment is equipped with a polarized plug to prevent insertion the wrong way the chassis may be hot 120VAC with respect to earth ground and cause an electrical shock if touched Other Transformerless Hazards Equipment with voltage doubler power supplies may also be of the hot Chassis variety and pose the same safety hazard In fact and equipment with a 2 wire ac power plug should be treated as hazardous hot chassis type and the safety precautions listed on the next page should be taken Test Equipment Damage Hazard In addition to the electrical shock hazard if the hot chassis is touched there is also a high probability of damaging any ac powered test equipment used to service the equipment Most test equipment with a 3 wire power cord such as oscilloscopes and signal generators have an earth ground chassis connected to earth ground through the third wire of the ac power
8. plug Touching the ground lead of any such test equipment probe to a hot chassis shorts the hot side of the power line through the ground lead and instrument Since the path through the instrument is intended only as a signal ground the excessive current of a direct power line short may cause extensive damage to the test equipment or to the equipment under test OPERATING INSTRUCTIONS Troubleshootina Use As Isolation Transformer TM Full Wave ridge Rectifier vM of im Wall Outlet legardless ich Way 120 VAC 60 Hz 2 Wire Plug is Inserted Typical Half Wave r DC TEST EQUIPMENT Chassis May Be Hot or Common WA Depending Upon Which Way 2 Wire SERIOUS ELECTRIC Plug is Inse SHOCK HAZARD Figure 7 Servicing Hot Chassis Equipment Can Pose a Serious Shock Hazard 17 Troubleshooting Use As Isolation Transformer THE SOLUTION Don t Ground the Chassis Simply connecting a test lead from the chassis to a good earth ground is not a satisfactory solution If the chassis is hot this places a direct short from the hot side of the power line to earth ground Hopefully this would only trip the circuit breaker for the wall outlet But a wall outlet is a very high energy source and before the circuit breaker is tripped the grounding test lead may weld or disintegrate or severe damage may occur to the equipment under test Use An Isolation Transformer For servicing Hot Chassis equipment alw
9. polarized plug The maximum permissible leakage specified by OSHA UL and CSA is 500A Some manufacturers specify a lower limit for a greater margin of safety THE SIMPLER METHOD The Model 1420 AC Power Supply includes a built in leakage tester that greatly simplifies the leakage test Fig 12 25 The equipment under test remains connected to the ISOLATED OUTPUT just as if it was for servicing The voltage was probably already preset to 120 volts at the conclusion of servicing The permanently attached leakage probe of the ac power supply is merely touched to each exposed metal part of the equipment under test antenna terminals tuner knob knob shafts handle screw heads etc No separate voltmeter nor conversion of results is required Just press the LEAKAGE button and read leakage directly from the LEAKAGE scale of the meter in microamps in milliamps for higher values of leakage See the manufacturer s service literature for the maximum permissible leakage However leakage in excess of 500 is considered hazardous in equipment Locate and correct the cause of leakage The expanded scale meter gives good resolution in the normal 100 to 5008 range Reading give up to 5mA are measured on a compressed scale The amount of excess leakage can be a clue to the type of leakage path A full scale meter reading probably indicates a direct short to the power line but the meter is protected from damage The leaka
10. scale may be used to measure the output load in volt amps LEAKAGE COM Connects meter to measure leakage with respect to common side of ac line Use LEAKAGE scale on meter Voltage must be preset to 120VAC for accurate leakage measurements LEAKAGE HOT Connects meter to measure leakage with respect to hot side of ac line Use LEAKAGE scale on meter Voltage must be preset to 120VAC for accurate leakage measurements 4 Meter Appropriate scale is selected by function switch 5 AC VOLTS Control Adjusts voltage at ISOLATED OUTPUT receptacle s from 0 to 150 volts CONTROLS AND INDICATORS 6 ISOLATED OUTPUT Receptacle s Isolated variable ac voltage outlet s The equipment under test plugs in here Dual outlets on Model 1420 7 Leakage Probe With LEAKAGE function selected touching probe tip to exposed metallic parts of equipment under test checks power line leakage 8 SOLDER TEMP Control Full counterclockwise rotation turns off soldering iron outlet on rear panel Initial clockwise rotation turns on outlet at standby warm temperature Further clockwise rotation increases soldering iron temperature Temperature adjustment is tapered allowing fine adjustment of hot temperature at upper end of adjustment range This control is completely independent of the POWER ON switch 9 Solder Temp Pilot Light Lights whenever soldering iron outlet on rear panel is powered REAR PANEL CONTROLS Refer to Fig 3 10
11. AC Power Cord 11 12 13 Fuse Model 1420 4A fuse protects auto transformer against excessive output current at low voltages which may not trip the input circuit breaker Circuit Breaker 3 15A circuit breaker protects against excessive input current Remove overload and push to reset Soldering Iron Outlet AC outlet for soldering iron Duty cycle and thus temperature is variable with SOLDER TEMP control on front panel This outlet is intended only for non transformer type soldering irons rated at 100 watts or less CONTROLS AND INDICATORS SSS a Figure 1 Front Panel Controls and Indicators Model 1420 8 CONTROLS AND INDICATORS Figure 3 Rear Panel Controls and Indicators Model 1420 10 OPERATING INSTRUCTIONS PRECAUTIONS SAFETY The Model 1420 AC Power Supply is a source of high voltage ac Improper or careless use could result in fatal electrical shock The most commonly encountered conditions which may pose a shock hazard are identified and corresponding precautions listed in the TEST INSTRUMENT SAFETY section which starts on the side front cover of this manual Know and observe these precautions Although Model 1420 is equipped with dual isolated outlets only one hot Chassis equipment should be connected at a time Unless the line to chassis relationship is identical a shock hazard will exist between the two chassis INPUT POWER These instruments are intended for use only
12. AGE CAL R11 for 500 on the built in meter PERFORMANCE TESTS The following checks test all functions of the ac power supply for proper operation The sequence of the checks also provides a logical symptom and fault isolation technique for troubleshooting After troubleshooting and repair these tests should be performed to assure that all faults have been corrected 1 Before the power supply is turned on the meter should rest at exact zero If mechanical zero adjustment is required calibration adjustments should be rechecked Set the POWER ON switch to on The POWER ON pilot light should illuminate Set the function switch to VOLTS and rotate the AC VOLTS control to minimum fully counterclockwise The output should go to zero as read on the front panel meter MAINTENANCE AND CALIBRATION Rotate the AC VOLTS control to maximum The control should rotate smoothly and the output voltage should increase smoothly to 150 volts as read on the meter TO check mete calibration measure voltage with calibrated external meter at 120 volts and compare reading to front panel meter Reduce the voltage to minimum and connect a load to the ISOLATED OUTPUT A load consisting of light bulbs totaling 240 watts is preferred Set the function switch to AMPS and increase the AC VOLTS control until the meter reads 2 amps or 120 volts whichever occurs first To check meter calibration measure current with calibrated external meter at 2 0 am
13. ATED OUTPUT receptacle s Model 1420 is protected by a circuit breaker CB1 This limits the maximum input current Additional protection for the auto transformer is offered by fuse F2 which limits the maximum output current at low voltages which would not open the protective device in the input circuit In Model 1420 this is a 4 amp fuse on the rear panel METERING CIRCUIT Since the output of the unit is ac the meter is connected across a bridge rectifier to provide the dc necessary for meter operation The rectifier circuit senses the average level while the meter is calibrated to read the equivalent rms value of a sine wave voltage the back to back diodes connected directly across the meter limit maximum voltage and thus offer overrange protection When the VOLTS function is selected the voltage across the ISOLATED OUTPUT is applied to the meter circuit The meter 29 is shunted by the VOLTAGE CAL trim pot which calibrates the voltage scale A 1 current sensing resistor two series 0 5 ohm in Model 1420 develops a voltage proportional to output current In the AMPS function this voltage is applied across the meter circuit The meter is now shunted by the AMPS CAL trim pot which calibrates the 2 amp current scale In Model 1420 the 4 amp scale is selected by sensing the voltage developed across only one of the 0 5 ohm resistors When the LEAKAGE function is selected Model 1420 only the current from the leakage probe
14. LTAGE RANGE BUILT IN METER Output voltage continuously variable from 0 to 150 Model 1420 WIDE CURRENT RANGE 3 1 4 inch meter Multi color scales Overrange Model 1420 Heavy duty unit handles virtually all servicing needs protection Output current up to 3 amps continuous 4 amps Model 1420 offers the following additional features int ittent OU VE POWER LINE LEAKAGE TEST WIDE LOAD MEASUREMENT CAPABILITY OSHA UL and CSA power line leakage test capability fast Model 1420 and safe measurement Built in multi function meter 0 150V Two current ranges of 0 2A and 0 4A for improved resolution Current EXPANDED TEAKAGE SCALE scales also calibrated in VA at 120V 0 5mA 0 5000uA leakage scale is expanded in most commonly used 100 500uA portion compressed to 5 mA ISOLATED OUTPUT VOLTAGE full scale Overload protected Built in isolation transformer for safe servicing of hot chassis equipment Two CIRCUIT BREAKER OVERLOAD PROTECTION isolated outlet Model 1420 Du eg eee M any ae Isolated output protected by easily reset circuit breaker SOLDERING IRON TEMPERATURE CONTROL Built in solid state soldering iron temperature control SPECIFICATIONS MODEL 1420 OUTPUT ISOLATION Leakage less than 0 1mA 25 C 50 relative humidity VOLTAGE ADJUSTMENT RANGE 0 150VAC with input at 120 VOLTAGE CURRENT SENSING Sine wave average calibrated in RMS MAXIMUM CURRENT Isolated 3A continuous 4A intermittent 0 130V
15. THE SOLUTION refer to Fig 13 The solution to the problem just described is a variable ac voltage source The soldering iron could be kept warm to reduce oxidation of the tip quickly brought to operating temperature when needed and adjusted to the exact temperature desired The Model 1420 AC Power Supply includes a built in soldering iron temperature control feature A separate ac outlet is provided on the rear panel The output duty cycle at this outlet is variable from about 70 to 99 or the outlet can be switched off when not in use This outlet is intended for a soldering iron only It is not intended for transformer type soldering irons nor irons rated at greater than 100 watts Temperature is adjusted with the SOLDER TEMP control on the front panel A relatively low temperature setting is recommended between periods of soldering iron use to reduce 27 oxidation of the tip This setting keeps the iron warm enough that it can be quickly brought to operating temperature when needed The temperature control is non linear allowing for a larger temperature variation at the low end and more precise temperature control at the HOT end The exact temperature desired can be easily achieved The soldering iron temperature control is entirely independent of the isolated variable voltage output including separate on off switches and pilot lights Thus the soldering iron temperature control feature may be used with or without the other featur
16. ains higher than normal after other faults have been corrected a leaky filter capacitor is suspected Such problems should be corrected to prevent another impending failure 23 The normal electrical load or current drain for the equipment under test is usually specified in its servicing literature If that information is not available the normal current drain is typically 60 to 80 of the rated current of the circuit breaker or line fuse DESIGN APPLICATIONS The design goals of any ac powered electronic product include input power requirements Using the ac power supply as the power source for breadboard and prototype units provides continuous monitoring of electrical load for various circuit configurations at various input voltages and at various temperatures PRODUCTION TESTING Final testing of electrical and electronics equipment nearly always includes monitoring of electrical load in all modes of operation The 1420 ac power supply provides both variable voltage and electrical load measure meant capabilities needed in such a test station ENERGY EFFICIENCY Energy efficiency has become an important consideration in equipment selection Equipment with the least electrical load is the most energy efficient The electrical load of similar products can be compared side by side demonstrating energy efficiency to a customer in terms readily understood by a layman Troubleshooting Load Measurement OPERATING INSTRUCTIONS 2
17. ays connect an isolation transformer between the wall outlet and the equipment under test The Model 1420 AC Power Supply includes such an isolation transformer among its many other features As shown in Fig 8 when an isolation transformer is used the chassis of the equipment under test is electrically isolated from both sides of the power line The chassis of the equipment under test may not be grounded by connecting a test lead from the chassis to a convenient earth ground such as an earth ground terminal of the test equipment Summary Any piece of equipment with a 2 wire power plug may be the hot chassis type even if it is equipped with a polarized plug There is not disadvantage to using an isolation transformer even if the equipment under test already includes its own isolation transformer Therefore for safety treat all equipment with a 2 wire power cord as hot chassis and use the ISOLATED 18 OPERATING INSTRUCTIONS OUTPUT ofthe 1420 AC Power Supply for servicing such equipment PROCEDURE refer to Fig 9 1 Turm 1420 AC Power Supply and set AC Volts control to MIN 2 Connect the power plug of the ac power supply to a 120 volt 60 Hz ac wall outlet The wall outlet must be the 3 wire type with the third wire returned to a good earth ground 3 Connect any ac powered test equipment to be used to an ac wall outlet do not use the ISOLATED OUTPUT receptacles of the ac power supply for test equipment
18. ccelerates failure Keep output current as low as possible and never exceed the maximum rating of the unit If possible power only one piece of equipment at a time Use the ISOLATED OUTPUT only for the equipment under test not for other test equipment It is very important to observe the maximum current derating Table 1 above 130 volts and to allow sufficient cooling time when operating Model 1420 at greater than 3 amps outlet Periodic inspection of the brush on the variable contact of the auto transformer is recommended Badly worn or arcing brushes should be replaced See the AUTO TRANSFORMER BRUSH REPLACEMENT paragraph for replacement procedures 30 RETURNING FOR SERVICE If you have encountered a problem with your unit and choose to return it for service check the following before returning 1 Is the circuit breaker reset Model 1420 See FUSE REPLACEMENT paragraph below if required 2 the fuses okay See FUSE REPLACEMENT paragraph below if required FUSE REPLACEMENT The ac power supply will trip its circuit breaker or blow a fuse only if it is severely overloaded or a failure occurs in the instrument Always turn off the unit to reset the circuit breaker or replace a fuse If fuses are internal unplug the instrument from its wall outlet before attempting replacement Before turning the unit back on reduce the output voltage or remove the overload that caused the blown fuse Replace the fuse only with the original type a
19. e rating at a low voltage such as 20 volts there is a major short in the power supply or one of the main power distribution circuits If current increases to its normal value more gradually allowing voltage to approach 100 volts or more an overload in one of the circuits is probably the cause Current that increases sharply above a certain voltage may indicate electrical breakdown or arcing within a component Voltage or current measurements in various circuits see Fig 10 while varying the input voltage can help isolate the fault INPUT VOLTAGE SPECIFICATION TESTING Most ac powered equipment is specified to operate over a range of input voltage such as 120 10 Complete performance testing cannot be conducted without a variable ac source Some testing may merely consist of measuring regulated dc voltages while varying the ac source voltage with other tests conducted at nominal line voltage LOW OR HIGH LINE VOLTAGE RELATED FAILURES Occasionally an equipment malfunctions only during conditions of low or high line voltage Troubleshooting of such problems is almost impossible without a variable ac voltage source Model 1420 AC Power Supply serves as a variable ac voltage source Troubleshooting Use As Variable Voltage Source OPERATING INSTRUCTIONS 3 Slowly Increase Voltage Until Output Current Begins Sharp Increase Localize Defective Component s EQUIPMENT UNDER TEST 2 Monitor Output Current on Meter Functi
20. ecialties com See the Service tab Or contact us via the Contact tab You may also contact us at GLOBAL SPECIALTIES A Cal Test Electronics Company 22820 Savi Ranch Parkway Yorba Linda CA 92887 800 572 1028 or 714 221 9330 38 lt 20150507 GI obal
21. en two chassis Don t expose high voltage needlessly Remove housings and covers only when necessary Turn off equipment while making test connections in high voltage circuits Discharge high voltage capacitors after removing power If possible familiarize yourself with the equipment being tested and the location of its high voltage points However remember that high voltage may appear at unexpected points in defective equipment Use an insulated floor material or a large insulated floor mat to stand on and an insulated work surface on which to place equipment and make certain such surfaces are not damp or wet Use the time proven one hand in the pocket technique while handling an instrument probe Be particularly careful to avoid contacting a nearby metal object that could provide a good ground return path When testing ac powered equipment remember that ac line voltage is usually present on some power input circuits such as the on off switch fuses power transformer etc any time the equipment is connected to an ac outlet even if the equipment is turned off Never work alone Someone should be nearby to render aid if necessary Training in CPR cardio pulmonary resuscitation first aid is highly recommended Instruction Manual for MODEL 1420 Isolated Variable AC POWER SUPPLY x a i Zi Global Yorba Linda CA 92887 www globalspecialties com TABLE OF CONTENTS page TEST INSTRUMENT SAFETY inside f
22. es of the instrument SUMMARY OF PROCEDURE refer to Fig 13 1 Set the SOLDER TEMP control to OFF Connect the ac power plug of the soldering iron to the outlet on the rear panel of the Model 1420 AC Power Supply THIS OUTLET IS FOR A SOLDERING IRON ONLY Do not connect electronic equipment here 3 Turn the SOLDER TEMP control clockwise to the on position The amber pilot lamp will light 4 Between periods of soldering iron use reduce temperature to minimize oxidation of the tip 5 When ready to use the soldering iron adjust the SOLDER TEMP control to the desired temperature Experience will quickly determine the typical setting for a given soldering iron Solderina Temperature Control OPERATING INSTRUCTIONS Turn On and Adjust to Desired Temperature Between Periods of Use Reduce Temperature Amber Pilot Light to Reduce Oxidation of Soldering Iron Tip When On Soldering Iron 100 Watt Max p 7 Plug into Outlet on Rear Panel 1420 VARIABLE AC SUPPLY Figure 13 Using the Variable Soldering Iron Temperature Feature 28 CIRCUIT DESCRIPTION Refer to the separately supplied schematic diagram while reading the following circuit descriptions VARIABLE VOLTAGE CIRCUIT Input power is applied through the POWER ON switch to variable auto transformer TI The output of TI is set with the AC VOLTS control from 0 to 150 volts The selected amount of voltage is applied across isolation transformer T2 to the ISOL
23. ge probe may also be used to verify proper wiring of equipment with polarized plug there should be very low leakage from the chassis to common and full scale leakage to hot Leakage of equipment with a 3 wire power plug is performed in the same manner as for 2 wire equipment Leakaae Tester OPERATING INSTRUCTIONS 6 Observe Leakage Scale of Meter Leakage Greater Than 500 pA Exceeds Green Portion of Scale 5 Touch Leakage Probe May Be a Safety Hazard to Each Exposed Metal 3 Set to 120V Part Knobs Screws 1420 AC POWER SUPPLY Antenna Terminals etc 1 Replace Housing or Cabinet 4 Select LEAKAGE Function Perform Entire Test for Both Common and Hot 2 Equipment Must Be EQUIPMENT UNDER TEST Plugged Into ISOLATED OUTPUT Figure 12 Power Line Leakage Testing 26 OPERATING INSTRUCTIONS Soldering Temperature Control SOLDERING IRON TEMPERATURE CONTROL THE NEED FOR TEMPERATURE CONTROL Most servicing work requires the use of a soldering iron If the soldering iron is plugged in only when it is needed time is wasted waiting for the iron to heat up But if it is left plugged in all the time oxidation quickly erodes the tip Also soldering iron temperature varies with line voltage Some irons reach the ideal temperature at 105 to 110 volts result at 120 volts some soldering irons are too hot which can more easily damage components being replaced or cause separation of circuit board plating
24. ltage rating of 130VAC If unsure of the maximum rating do not exceed 130 VOLTS On Model 1420 the 130 150 volt portion of the VOLTS scale is red as a reminder that caution should be observed OPERATING INSTRUCTIONS PRECAUTIONS Red Portion of VOLTS Scale Indicates Caution Zone Model1 420 Only Adjust Voltage Observe Caution if Voltage Exceeds Rating of Equipment Under Test Equipment May Be Severely Damaged EQUIPMENT UNDER TEST Read Voltage on 0 150V Scale of Meter Figure 5 Observe Caution Above 130V 13 Precautions OPERATING INSTRUCTIONS MAXIMUM OUTPUT CURRENT For Model 1420 the red portion of the 0 4A scale of the meter indicates the caution zone over 3A This is a reminder that only CAUTION intermittent duty operation is permitted NEVER EXCEED THE MAXIMUM OUTPUT CURRENT RATING OF THE UNIT Table 1 Excessive output current can damage the variable auto transformer Keep output current as low as possible power only one piece of equipment at a time Use the ISOLATED OUTPUT only for the equipment under test not for the test equipment It is very important to observe the maximum current derating Table 1 above 130 volts and to allow sufficient cooling time when operating Model 1420 in the intermittent duty region Even at low voltages the maximum output current should never exceed 4 amps for Model 1420 Higher current may damage the variable auto transformer where the brush contacts the
25. nd value never one of a large value A larger value may create a fire and safety hazard or cause serious damage to the equipment Also refer to the following specific fuse replacement information for each model MAINTENANCE AND CALIBRATION Model 1420 If this instrument is severely overloaded at higher output voltages circuit breaker CB1 on the rear panel will trip The unit will stop operating and the POWER ON pilot light will go off Remove the overload and push the button on the circuit breaker to reset A severe overload at low output voltage will blow fuse F2 on the rear panel In this case there will be no output but the pilot light will stay on If the soldering iron outlet is overloaded internal fuse F1 will blow Ifso the SOLDER TEMP pilot light will go off Fig 15 shows the fuse locations Replace fuse F1 only with a 1 amp normal blow type 3AG Replace fuse F2 only with a 4 amp slow blow type 3AG AUTO TRANSFORMER BRUSH REPLACEMENT To replace the brush unplug the instrument then gently lift the brush from the brush track Grasp the old brush assembly and snap it out of position by pulling radially Install the new brush assembly by lifting the spring arm and snapping the new brush assembly into position 31 It is imperative that newly installed or re installed brushes be seated correctly on the brush track for proper operation of the transformer With the power off insert a piece of garnet paper non metallic between
26. on 4 Multimeter Connected to Measure Current One Circuit At a Time Figure 10 Using the Variable Voltage Feature to Troubleshoot Equipment with Short Circuit 22 OPERATING INSTRUCTIONS Troubleshooting Load Measurement TROUBLESHOOTING USING THE AC POWER SUPPLY TO MEASURE ELECTRICAL LOADS LOAD MEASUREMENT PROCEDURE Measurement of electrical load is extremely simple when using the Model 1420 AC Power Supply as the power source Refer to Fig 11 The built in meter may be switched to measure the voltage and current being delivered to the equipment under test Multiplying the voltage times the current give the electrical load in volt amps For Model 1420 the calculations is not even required if the measurement is made at the standard value of 120 volts The 0 2A and 0 4A current scales are also calibrated as direct reading 0 24VA and 0 480VA scales NOTE The VA scales are accurate only at 120 volts At other voltages use the 0 2A or 0 4A current scales and calculate the electrical load by multiplying output voltage times output current SERVICING APPLICATIONS An initial check of electrical load can often give a clue to the problem when troubleshooting electronics equipment If the equipment under test is drawing considerably less current than normal perhaps one of the power supply voltages is absent disabling several circuits If current is higher than normal a transistor or other component may be shorted If current rem
27. ps and compare to front panel meter For Model 1420 check that the meter reads 2 amps on both the 0 2A and 0 4A range For Model 1420 check the leakage function as follows a Reduce the voltage to minimum and connect the leakage probe to the hot side of the ISOLATED OUTPUT b Select the LEAKAGE function and slowly increase the AC VOLTS control until meter reads 500 on the leakage scale This should occur at about 6 volts To check meter calibration measure leakage current with calibrated external meter and compare to front panel meter c Increase the AC VOLTS control until the meter reads 5mA on the leakage scale This should 35 occur at about 60 volts With the reverse polarity of LEAKAGE function the meter should read Zero d Change the leakage probe to the common side of the ISOLATED OUTPUT and select both polarities of the LEAKAGE function One polarity should read zero and the other should indicate 5mA of leakage 8 For Model 1420 check the soldering iron temperature control function as follows a Connect a load to the soldering iron outlet on the rear panel A lamp of 25 to 100 watts is preferred or a soldering iron may be used Turn on the SOLDER TEMP control The amber pilot light should illuminate b Connect an ac voltmeter across the load and vary the SOLDER TEMP control from minimum to maximum At 120 volts line voltage the light bulb intensity should vary and the voltmeter should read from roughly
28. ront cover FEATURES oat ERR GNU 3 SPECIFICATIONS ccccssccssccsscessecsscesessessscensscsscesseceecesaeenes 4 CONTROLS AND 5 222 2 0 6 OPERATING INSTRUCTIONS eese 12 Precautiofis eco cit SER ques 12 Troubleshooting Using the AC Power Supply as an Isolation 0200 16 Troubleshooting Using the Power Supply as a Variable AC Voltage 21 Troubleshooting Using the AC Power Supply to Measure Electrical Loads sse 23 Using the Model 1420 as a Leakage 25 Soldering Iron Temperature Control sess 27 page CIRCUIT 12 2 402 400 0000000 1 81 00904 29 MAINTENANCE AND 30 Preventive Maintenance 30 Returning for Serv16e E Eee e pee pe 30 Fuse Replacements E Hg 30 Auto Transformer Brush 31 Calibration Adjustments 31 Performariice T65l5 5 ne reste Yen e a ne e eee 34 Tro blesliooting iue REED Ed ene ets 35 CUSTOMER 21 24 02 0 ener 37 WARRANTY 37 Warranty Service 38 FEATURES WIDE VO
29. st Electronics warrants this product to be free from defective material or workmanship for a period of 1 year from the date of original purchase Under this warranty Cal Test Electronics is limited to repairing the defective device when returned to the factory shipping charges prepaid within the warranty period RETURNS Units returned to Cal Test Electronics that have been subject to abuse misuse damage or accident or have been connected installed or adjusted contrary to the instructions furnished by Cal Test Electronics or that have been repaired by unauthor ized persons will not be covered by this warranty 37 CHANGES Cal Test Electronics reserves the right to discon tinue models change specifications price or design of this device at any time without notice and without incurring any obligation whatsoever LIABILITIES The purchaser agrees to assume all liabilities for any damages and or bodily injury which may result from the use or misuse of this device by the purchaser his employees or agents NO OTHER WARRANTIES This warranty is in lieu of all other representations or watranties expressed or implied and no agent or representative of Cal Test Electronics is authorized to assume any other obligation in connection with the sale and purchase of this device WARRANTY SERVICE INSTRUCTIONS CALIBRATION AND REPAIR If you have a need for any calibration or repair services please visit us on the web at globalsp
30. t Okay 1 Ifnooutput voltage is indicated on the front panel meter check voltage at ISOLATED OUTPUT with external ac voltmeter 36 If no voltage is measured on external meter check rear panel fuse Model 1420 and replace if burned out If fuse is okay check brush of variable auto transformer Check for open winding in isolation transformer or open current sensing resistor If voltage is measured on external meter but none is indicated on front panel meter see troubleshooting procedure in next paragraph Incorrect or No VOLTS AMPS or LEAKAGE Meter Reading l 2 Check meter reading in all three functions to further isolate the fault For inaccuracy perform calibration adjustments If no reading or inability to adjust to correct reading a defective component is indicated If trouble appears in more than one mode check bridge rectifier diodes meter and series resistors If trouble is in one mode only check function switch and associated metering resistors SOLDER TEMP Operation Abnormal Model 1420 Only 1 Ifno SOLDER TEMP pilot light check internal fuse F1 and replace if burned out If fuse is good check voltage at soldering iron outlet If voltage at outlet is okay pilot lamp is defective If pilot light is okay but no output voltage or incorrect output voltage check triac TR1 breakdown diode D1 resistors R1 R2 and R3 capacitors C1 C2 and inductor L1 CUSTOMER SUPPORT WARRANTY Cal Te
31. the brush and brush track rough side toward the brush A few swing of the brush over the garnet paper will mate the brush contact face to the brush track Remove the garnet paper and blow away loose particles before applying power CALIBRATION ADJUSTMENTS This unit was carefully checked and calibrated at the factory prior to shipment Readjustment is recommended only if repairs have been made in a circuit that affects calibration or it you have reason to believe the unit may be out of calibration Locations of the calibration adjustments are shown in Fig 14 Test Equipment Required 1 Multimeter ac voltage accuracy of 0 5 or better at 120 V 60Hz ac current accuracy of 1 or better at 500 microamps and 2 amps 60Hz 2 60 ohm 240 watt resistive power supply load Must be capable of dissipating 2 amps at 120 VAC A variable electronic load of sufficient power rating may be used or parallel light bulbs totaling 240 watts are suitable MAINTENANCE AND CALIBRATION Circuit Breaker Input Soldering Iron Outlet T2 Isolation Transformer Solder Temperature TOP VIEW Figure 14 Location of Fuses and Calibration Adjustments Model 1420 33 MAINTENANCE AND CALIBRATION Meter VOLTS Calibration 1 2 3 4 With the power supply turned off adjust the mechanical zero of the meter to exact zero Connect an external multimeter of 0 5 or better ac voltage accuracy
32. to the ISOLATED OUTPUT Turn on the ac power supply and set the AC VOLTS control for 120 volts on the multimeter Set function switch to VOLTS and adjust VOLTS CAL R14 for Model 1420 for 120 volts on built in meter Meter AMPS Calibration 1 Connect 60 ohm 240 watt resistive load to the ISOLATED OUTPUT receptacle Parallel light bulbs totaling 240 watts is suitable Connect a calibrated multimeter of 1 or better ac current accuracy in series with the load to measure each current Set the multimeter to a 2 amp range Turn on the ac power supply and slowly increase the output voltage until the multimeter measures 2 0 amps Set the function switch to AMPS and adjust AMPS CAL R12 for Model 1420 for 2 0 amps on the built in meter For Model 1420 adjust calibration on the 0 2A range The adjustment calibrates both scales If 0 4A range is inaccurate replace R5 and R6 with matched equal resistors and repeat calibration adjustment 34 Meter LEAKAGE Calibration 1 2 Connect the leakage probe in series with 220 4 watt resistor Connect a calibrated multimeter of 1 or better ac current accuracy in series with the 220kQ resistor and leakage probe Set the multimeter to measure 500 ac current Carefully connect the other lead of the multimeter to the hot side of the ISOLATED OUTPUT receptacle Adjust the AC VOLTS control for exactly 500u A on the multimeter Select the LEAKAGE function and adjust LEAK
33. veral applications are listed below but the versatile instruments may be used in any application where an ac power source of any value from 0 to 150 volts is required and within the maximum current rating of the instrument 24 VOLT APPLICATIONS Class II industrial control equipment operates from nominal 24 volt 60 Hz ac power Such equipment is widely used in industrial plants These power supplies can be adjusted to 24 volts ac for bench servicing of the equipment 130 150 VOLT APPLICATIONS The ability to go higher then 130 volts is indispensable in component and equipment testing where specifications must be exceeded to verify designs and overvoltage margins TROUBLESHOOTING EQUIPMENT THAT BLOWS FUSES One of the problems with troubleshooting equipment with a severe overload or short is that it repeatedly trips its circuit breaker or blows fuses Full power cannot be applied long enough for normal voltage and waveform measurements to be performed The variable voltage feature permits operation at a lower voltage that does not activate the protective device testing and troubleshooting can be performed with power applied 21 Using the Model 1420 AC Power Supply as shown in Fig 10 voltage can be set to 0 volt and slowly increased while monitoring the current Problems such as a defective circuit breaker that open too soon are quickly spotted If current reaches its normal value typically about 70 of the fuse of protective devic
34. winding A 3 15A circuit breaker limits maximum input current to Model 1420 Additionally output fuses limit the output of the 1420 to 4 amps at low voltages that would not open the input protective device Never bypass the circuit breaker or fuses or replace fuses with a higher value Remove the overload to reset the circuit breaker or replace a fuse Turn off the unit when connecting or disconnecting equipment from the ISOLATED OUTPUT receptacle s Table 1 Maximum Output Current Derating 14 Troubleshooting Use As Isolation Transformer OPERATING INSTRUCTIONS TROUBLESHOOTING USING THE AC POWER SUPPLY AS ISOLATION TRANSFORMER THE HAZARD Most equipment with a 2 Wire Plug is Transformerless Most recent television receivers and other consumer products such as stereo amplifiers tuners tape decks etc do not contain an isolation transformer Such products often have a plastic or wood cabinet which completely insulates the chassis and prevents the user from touching it However when the cabinet is removed for servicing the product the chassis is exposed and may become an electrical shock hazard to the service technician Bridge Rectifier Transformerless Equipment One of the most commonly used types of power supply circuits in television receivers and audio equipment is the transformerless full wave bridge rectifier shown in Fig 7 In such cases the chassis is always hot regardless of which way the 2 wire ac plug
35. with 120 volt 60Hz line voltage Do not operate from 50Hz or 220 240 volt power systems The instrument may be safely operated from 100 volt 60Hz line voltage although the maximum output voltage will be lower VENTILATION The holes in the case provide convection cooling hot air rises and escapes through the top vents while cool air is drawn in to replace it through the bottom Never block these ventilation holes with a manual schematic diagram other equipment etc If the air is blocked the temperature inside the ac power supply may 12 become excessive and cause failure of the unit Similarly avoid operating locations near sources of heat MAXIMUM OUTPUT VOLTAGE CAUTION Exceeding the maximum input voltage rating of the equipment under test typically 130VAC may cause severe damage to the equipment The output voltage of the ac power supply is adjustable from 0 to 150VAC This is very useful in certain testing situations for stressing equipment beyond its normal operating range to determine its breakdown point However for most testing and servicing applications input voltages higher than the maximum specified by the manufacturer should be used with great precaution For normal testing and servicing check the maximum input voltage specification of the equipment under test and make sure you do not adjust the output voltage of the ac power supply higher than that value Most ac powered equipment has a maximum input vo

Download Pdf Manuals

image

Related Search

Related Contents

De'Longhi SDH2000 User's Manual  Luci Connected Light 100V 取扱説明書  Strong Pools and Spas The Antigua User's Manual  SR 25, SR38, SR 65, SR68, SR 75 (S) - WEKA Service  User`s Manual    Manual de Usuario Uriges 5.1, el editor para su web  Sony M673V Handheld Cassette Voice Recorder  Notice - Castorama  無料テキストの配布・説明、セミナー・相談会  

Copyright © All rights reserved.
Failed to retrieve file