QJ61BT11 Control & Communication Link

image

Contents

1. Hardware test D Transmission rate 5Mbps Connect the CC Link dedicated cable for the data link Refer to section 5 1 for details on the connection methods The terminals SLD and FG are connected inside the module This is a 2 piece method terminal block and the module can be exchanged without disconnecting the signal wires connected to the terminal block The station No setting switch and transmission rate mode setting switch details are validated when the module power is turned OFF to ON or when the PLC CPU is reset If the setting details are changed while the module s power is ON turn the module s power OFF and ON or reset the PLC CPU 5 External wiring 5 1 CC Link dedicated cable wiring The methods for connecting the CC Link dedicated cable for the master module local module standby master module remote module and intelligent module 1 The cable connecting sequence is not related with the station No 2 Be sure to connect terminal resistor of the unit accessory to the units on both ends CC Link system Connect the terminal resistor between DA and DB 3 In CC Link system the terminal resistor is different depending on the applied cable e CC Link dedicated cable 110Q 1 2W brown brown brown e CC Link dedicated high performance cable 130Q 1 2W brown orange brown 4 The master module can be connected to a place other than both ends 5
2. 5 473 2480 Tel 49 2102 486 0 Thailand F A Tech Co Ltd U K Mitsubishi Electric Europe B V UK 1138 33 34 Rama 3 Road Yannawa Branch Bangkok 10120 Thailand Travellers Lane Hatfield Herts AL10 Tel 66 2 295 2861 8XB UK Indonesia P T Autoteknindo SUMBER MAKMUR Tel 44 1707 276100 Kompleks Agung Sedayu Propertindo South Africa MSA Manufacturing Pty Ltd Harco Mangga Dua P O Box 39733 Bramley 201 8 Blok H No 4 JI Mangga Dua Raya Johannesburg South Africa Jakarta Pusat 10730 Indonesia Tel 27 11 444 8080 Tel 62 21 336292 Hong Kong Ryoden International Ltd India Messung Systems Put Ltd 10th Floor Manulife Tower 169 Electric Electronic Sadan NO 111 Unit No15 Road North Point HongKong M I D C BHOSARI PUNE 411026 Tel 852 2887 8870 Tel 91 20 7128927 China Ryoden International Shanghai Ltd Australia Mitsubishi Electric Australia Pty Ltd 3F Block5 Building Automation 348 Victoria Road PostalBag No 2 Instrumentation Plaza 103 Cao Bao Rd Rydalmere N S W 2116 Australia Shanghai 200233 China Tel 61 2 9684 7777 Tel 86 21 6475 3228 MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO 100 8310 TELEX J24532 CABLE MELCO TOKYO NAGOYA WORKS 1 14 YADA MINAMI 5 HIGASHI KU NAGOYA JAPAN Specifications subject to change without notice Printed in Japan on recycled paper
3. A star connection cannot be used 6 The connection method is shown below Master module Remote module Local module Terminal DA i 1 y DA i 1 i y LDA Terminal resistor DE y x LDE x x epee resistor DG 7 7 DG i 7 t 7 DG l eee e e a L FG CC Link FG CC Link FG dedicated cable dedicated cable IMPORTANT The CC Link dedicated cable and CC Link dedicated high performance cable cannot be used together If used together correct data transmission will not be guaranteed Connect the shielded wire of the CC Link dedicated cable to SLD of each module and ground both ends of the shielded wire using D type grounding via FG The SLD and FG are connected into the module 6 Outline dimensions QJ61BT11 R STATION NO 98 3 86 KNA NSA NA KA NSA RLY ALYY 90 3 54 27 4 1 08 Unit mm inch Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi machine damage or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi produ
4. MITSUBISHI Programmable Logic Controller QJ61BT11 Control amp Communication Link System Master Local Module Thank you for purchasing the Mitsubishi general purpose PLC MELSEC Q Series Before starting use please read through this manual and the details manual to ensure correct usage User s Manual Hardware HilELSEG Q IB NA 0800026 C 0009 MEE 1999 MITSUBISHI ELECTRIC CORPORATION Mitsubishi Programmable Logic Controller SAFETY PRECAUTIONS Always read these instructions before using this equipment Before using this product please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly The instructions given in this manual are concerned with this product For the safety instructions of the programmable controller system please read the CPU module user s manual In this manual the safety instructions are ranked as DANGER and CAUTION r Indicates that incorrect handling may cause hazardous conditions DANGER resulting in death or severe injury i Indicates that incorrect handlin iti l g may cause hazardous conditions CAUTION resulting in medium or slight personal injury or physical damage SE I eI rE Pay cea Oy oy ING Re RS Se ae gpa E al ee ae ee YY Note that the A CAUTION level may lead to a serious consequence according to the circumstances Always follow the instructions of both leve
5. PU After unpacking confirm that the following products are enclosed QJ61BT11 body Terminal resister 110 Q 1 2W brown brown brown Terminal resister 130 Q 1 2W brown orange brown 1 1 Definition of Ver 1 10 The module of which the cable length between station and station is uniformly 20cm or more by improving the conventional limit of the cable length between station and station is defined as Ver 1 10 The conventional modules are defined as Ver 1 00 The conditions for setting the cable length between station and station uniformly to 20cm or more are indicated below 1 All modules configuring the CC Link system must use Version 1 10 2 All data link cables must be Version 1 10 compatible CC Link dedicated cable The Ver 1 00 specifications are applied for the maximum overall cable distance and the cable length between station and station when the CC Link system is configured with the modules and cables of Ver 1 00 and Ver 1 10 1 Checking Version 1 10 The CC Link logo is stamped on the plate for the Version 1 10 modules 3 CC Link 2 Performance specifications 2 1 Performance specifications The performance specifications of the QJ61BT11 are shown below Refer to the User s Manual of the CPU in use for the general specifications of the QJ61BT11 Select from 156kbps 625kbps 2 5Mbps 5Mbps 10Mbps Maximum overall cable distance Differs according to transmission rate Refer to section 2 2 Maxi
6. ay cause a module malfunction and cable damage When removing the communication cable or power supply cable from the module do not pull the cable When removing the cable with a connector hold the connector on the side that is connected to the module When removing the cable connected to the terminal block first loosen the screws on the part that is connected to the terminal block Pulling the cable that is still connected to the module may cause malfunction or damage to the module or cable About the Manuals The following manuals are also related to this product Order them if necessary Related Manuals Manual number QJ61BT11 Control amp Communication Link System Master Local SH 080016 Module User s Manual 13JL91 Conformation to the EMC Directive and Low Voltage Instruction For details on making Mitsubishi PLC conform to the EMC directive and low voltage instruction when installing it in your product please refer to Chapter 3 EMC Directive and Low Voltage Instruction of the PLC CPU User s Manual Hardware The CE logo is printed on the rating plate on the main body of the PLC that conforms to the EMC directive and low voltage instruction 1 OVERVIEW This manual explains the specifications names of each part and the settings etc for the QU61BT11 Control amp Communication Link System abbreviated as CC Link from here on Master Local Module hereinafter QJ61BT11 used in combination with the MELSEC Q Series PLC C
7. cts and to other duties For safe use e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life e Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi e This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system Country Region Sales office Tel Country Region Sales office Tel U S A Mitsubishi Electric Automation Inc Taiwan Setsuyo Enterprise Co Ltd 500 Corporate Woods Parkway Vernon 6F No 105 Wu Kung 3rd RD Wu Ku Hills IL 60061 Hsiang Taipei Hsine Taiwan R O C Tel 1 847 478 2100 Tel 886 2 2299 2499 Brazil MELCO TEC Rep Com e Assessoria Korea STC Techno Seoul Co Ltd Tecnica Ltda 1F Dong Seo Game Channel Bldg Av Rio Branco 123 15 and S 1507 660 11 Deungchon dong Kangsec ku Rio de Janeiro RJ CEP 20040 005 Seoul Korea Brazil Tel 82 2 3668 6567 Tel 55 21 221 8343 Singapore Mitsubishi Electric Asia Pte Ltd Germany Mitsubishi Electric Europe B V German 307 ALEXANDRA ROAD 05 01 02 Branch MITSUBISHI ELECTRIC BUILDING Gothaer Strasse 8 D 40880 Ratingen SINGAPORE 159943 GERMANY Tel 6
8. es and settings of each part QJ61BT11 Details LED display Confirms the data link state by turning the LEDs ON and OFF ST aA OFF Watch dog timer error i ON Communication error in all stations Turns ON when the following type of error occurs e When switch settings are incorrect e When master station is duplicated on same line e When there is an error in the parameter details e When the data link monitor timer functioned e When the cable is disconnected or the transmission route is being affected by noise etc Flicker Station with communication error found Pete le Communication error host Flicker Setting of switch 2 or 3 was changed while power was ON RD ON Receiving data Station No setting Set the module s station No Default setting 0 lt Setting range gt Master station 0 Local station 1 to 64 Standby master station 1 to 64 The ERR LED will turn ON if a value other than 0 to 64 is set Transmission rate Set the module s transmission rate and operation state Default setting mode setting switch 0 0 Transmission rate 156kbps 2 Transmission rate 2 5Mbps On line Line test 6 Transmission rate 625kbps When station NO setting switch is 0 Line test 1 8 Transmission rate 5Mbps When station NO setting switch is 9 Transmission rate 10Mbps__ 1 to 64 Line test 2 B Transmission rate 625kbps
9. ls because they are important to personal safety Please save this manual to make it accessible when required and always forward it to the end user DESIGN PRECAUTIONS CAUTION Do not bunch the control wires or communication cables with the main circuit or power wires or install them close to each other They should be installed 100mm 3 9inch or more from each other Not doing so could result in noise that may cause malfunction INSTALLATION PRECAUTIONS CAUTION Use the PLC in an environment that meets the general specifications contained in the CPU user s manual to use Using this PLC in an environment outside the range of the general specifications may cause electric shock fire malfunction and damage to or deterioration of the product When installing the module securely insert the module fixing tabs into the mounting holes of the base unit while pressing the installation lever located at the bottom of the module downward Improper installation may result in malfunction breakdown or dropping out of the module Securely fix the module with screws if it is subject to vibration during use Tighten the screws within the range of specified torque If the screws are loose it may cause fallout short circuits or malfunction If the screws are tightened too much it may cause damage to the screw and or the module resulting in fallout short circuits or malfunction Switch all phases of the external power supply
10. mum transmission distance Maximum No of connected modules for master station 64 modules No of occupied stations for local station One station or four Remote input output RX RY 2048 points Remote register RWw 256 points Master station remote device _ station local _ station intelligent device station standby master station Remote register RWr 256 points Remote device station local station intelligent device station standby Maximum No of link points per system master station master station Remote input output RX RY 32 points 30 points for local station Remote register RWw 4 points Master station gt remote device station local _ station intelligent device station standby master station Remote register RWr 4 points Remote device station local station intelligent device station standby master station master station Communication method Polling method Synchronization method Flag synchronous system No of link points per remote station local station intelligent device station standby master station Connection cable CC Link dedicated cable CC Link dedicated high performance cable e Automatic return function RAS functions e Slave station cutoff function e Error detection with link special relay register 0 46 5VDC internal current consumption A The CC Link dedicated cable and CC Link dedicated high performance cable cannot be used together Also attach the termi
11. nal resister which matches the kind of the cable 2 2 Maximum overall cable distance The maximum overall cable distance differs according to the transmission rate For the relationship between transmission rate and max total cable length refer to CC Link Catalog L NA 74108143E 2 3 CC Link dedicated cable specifications Use the CC Link dedicated cable with the CC Link system The performance of the CC Link system cannot be guaranteed with cables other than the CC Link dedicated cables For the specifications of CC Link dedicated cable and the reference office refer to CC Link catalog L NA 74108143E 3 Mounting and installation 3 1 Precautions for handling The precautions for handling the module are given below 1 The module case is made of resin so do not drop it or apply strong impacts on it 2 Crimp terminals with insulated sleeves cannot be used with the terminal block Covering the wire connection section of the crimp terminals with mark tubes or insulated tubes is recommended 3 Tighten the module installation screws within the following ranges Always turn the power of the corresponding station OFF before mounting or removing the terminal block If the terminal block is mounted or removed without turning the corresponding station s power OFF correct data transmission by the mounted or removed station will not be guaranteed 3 2 Installation environment Refer to the User s Manual of the CPU module in use 4 Nam
12. off when mounting or removing the module Not doing so may cause damage to the module Do not directly touch the conductive area or electronic components of the module Doing so may cause malfunction or failure in the module WIRING PRECAUTIONS CAUTION When turning on the power and operating the module after wiring is completed always attach the terminal cover that comes with the product There is a risk of malfunction if the terminal cover is not attached Tighten the terminal screws within the range of specified torque If the terminal screws are loose it may cause fallout short circuits or malfunction If the terminal screws are tightened too much it may cause damage to the screw and or the module resulting in fallout short circuits or malfunction Be careful not to let foreign matters such as sawdust or wire chips get inside the module These may cause fires failure or malfunction The top surface of the module is covered with protective film to prevent foreign objects such as cable offcuts from entering the module when wiring Do not remove this film until the wiring is complete Before operating the system be sure to remove the film to provide adequate heat ventilation Be sure to fix communication cables or power supply cables leading from the module by placing them in the duct or clamping them Cables not placed in the duct or without clamping may hang or shift allowing them to be accidentally pulled which m