Home
Zerio User Manual - Electro Detectors
Contents
1. For a list of faults their most common causes and ways to rectify faults see Appendix 2 Note that all faults will continue to be displayed on the panel until the system is reset even if the fault condition has been rectified 3 5 Alarm Conditions If the Alarm sounds the premises should be evacuated A screen will be displayed similar to below The Fire LEDs will flash and the appropriate zone LED s will flash The first line details the first zone that has been activated and the last zone to activate The second line provides a count of all zones in alarm The third line details the event number device type and number The last line details the text location of the device in alarm If the description is longer than 20 characters it will scroll across the screen If more than 1 event occurs the bottom two lines will scroll Version Z1000 V1 06 Electro Detectors Page 7 EDA Z1000 Operation Manual ED Note It is possible to configure the system to silence re set and re sound without the need to enter a valid user code by setting Code Protect to off in the panel configuration options Please be aware that turning code protect off may mean that the installation contravenes relevant standards 3 6 To Silence the Alarm When it is certain that it is safe to return to the building the Silence Re Sound button should be pressed The user will then be prompted to enter a valid user password Up to 30 seconds should be
2. LED will illuminate Once test options have been selected these can now be saved for quick setup in the future Once the test screen is entered the panel will prompt to use saved settings if unsure of the saved settings select NO and re define the test parameters Devices that require testing should now be set into a fire condition and the details on the screen checked Care should be taken to ensure the correct devices are tested as failure to do this could result in all the bells sounding Once the tests are complete and the user is satisfied that everything functioned correctly the test mode should be disabled If this procedure is forgotten the test mode will automatically time out after the selected period 4 4 To Disable the Test Mode Press the MENU button select 4 Test Modes then 2 Disable Test Press ENTER to disable test The Test Mode LED will extinguish 4 5 To view Zones in Test Press the MENU button select 4 Test Modes then 3 View Test Zones Use the Up Down keys to view the Zones that have been put into Test Version Z1000 V1 06 Electro Detectors Page 11
3. EDA Z1000 Radio Fire Alarm System Operation Manual Electro Detectors Ltd Electro House Edinburgh Way Harlow Essex CM20 2EG UK Tel 01279 635668 Fax 01279 450185 Email eda electrodetectors co uk Web www electrodetectors co uk Electro Detectors Version Z1000 V1 06 EDA Z1000 Operation Manual ED This manual should be provided to the site s nominated responsible person and left on the premises for easy reference Electro Dete ctors Page 2 Version Z1000 V1 06 EDA Z1000 Operation Manual Revision History anual Author Software Date Description ersion Version V1 00 DR 0 08 01 10 05 First Release VI 01 DR 0 10 01 11 05 Sounder Repeater Added to System Access code override function and ability to view access codes re program devices to factory settings re program unique Id Antenna monitoring configuration added V1 02 DR 0 10 22 12 05 Must reset booster panel to ensure memory cleared All other devices should also be reset on power up Operation of fire relays when silence reset pressed V1 03 SM 0 15 13 06 06 New features for disabling faults and Double knock functions V1 04 SM 1 01 14 03 07 New menu structure Survey mode function keys and sounder circuit V1 05 SM 1 02 18 02 08 HMO software antenna calibration option add Text via the panel and contrast settings added V1 06 PP 1 06 02 02 10 View Test Zones added Electro Detectors Version Z
4. 4 2 Changing Access Codes An advanced user can change the password for the basic and advanced user The password is a 4 digit number with each digit ranging from 1 to 4 To change the password press the MENU button select 1 Setup select 2 Access Codes and select 2 Change Codes Using the cursor keys select either the advanced user Access Level 2 or the basic user Access Level 1 password Once selected press ENTER Using the numbered keys enter the current password Assuming this matches the stored user code you will be prompted to enter the new password and then re enter the new password to confirm Press ENTER to save the new password A message will be displayed indicating that the password is being saved to the SIM and flash memory 4 3 To Select Test Mode Test mode is available to an advanced user so that a system can be tested with minimal disruption to the occupants of a building BS5839 and ENS4 specify what tests should be performed at what intervals Always follow any testing schedule or routine recommended by the system installer As a rough guide the system should be tested weekly but sounders only need to be tested every month The test mode allows various output devices and or sounders to be disabled To select the option press MENU and enter a valid password Select 4 Test Mode select 1 System Test and select 1 Enable Test For each device that is to be tested the zon
5. allowed for all sounders to silence with a radio system If the device is still in an alarm condition the sounders will not sound again unless another device goes into alarm The sounders will automatically silence after 30 minutes 3 7 To Re Sound the Sounders There may be times when the sounders have been mistakenly silenced for example if the alarm was genuine but someone mistakenly pressed silence To do this press the Silence Resound button To prevent the user from inadvertently silencing and re sounding the system there is a programmable lock out time during which this button is inactive 3 8 To Reset the Alarm Assuming the reason for the alarm condition has been investigated pressing Reset will return the system to its normal operation screen The user will need to enter a valid password The screen will display any faults that were detailed prior to the alarm condition or any new fault that occurred during the alarm condition 3 9 Menu Navigation To enter the menu system press MENU and enter a valid password Main Menu will appear To scroll through the menu the 7 or Y keys should be pressed In order to select a menu option the key should be pressed To return to the previous menu screen from a sub menu the should be pressed Pressing Cancel will return to the system screen where any faults or alarms will be displayed if present If a sub menu is selected the cancel button
6. and select 3 Event Log A sub menu will appear detailing VIEW EVENTS Using the cursor keys to select this The panel stores up to 255 fire or fault events in memory A description of the fault or fire is recorded together with the date and time of the event When the log becomes full the oldest entries are automatically removed to make room for new ones To scroll through the event log use the cursor keys Version Z1000 V1 06 Electro Detectors Page 9 EDA Z1000 Operation Manual ED 4 Advanced User Operations 4 1 General Assuming the correct password is entered the user can sign on as an advanced user This allows some extra functions not available to the basic user Only people who have been trained in the operation of the system should be allowed access at this level as certain operations of the fire alarm can be disabled although they will be automatically enabled after a short timeout period 4 2 To View Access Codes The access code password is a 4 digit number with each digit in the range of 1 to 4 To view the current passwords the following procedure should be followed Press the MENU button and enter the correct password for an Advanced User The default is 2222 Using the cursor keys select 1 Setup select 2 Access Codes and select 1 View Codes A screen as shown below will list the passwords for the basic user labelled AL1 and the advanced user labelled AL2
7. currently displayed faults fault acknowledgement Silence Re Sound If the panel is in a fire condition this will silence the sounders If the sounders are already silenced and the panel not reset pressing this button will re sound the sounders using the preconfigured re sound tone Reset Resets the panel from an alarm condition Note that the system must be silenced before it can be reset from a fire condition Electro Detectors Navigation Keys Used to navigate through the menu structure and programming status screens In a multiple fault or alarm condition the up and down arrow keys allow the user to scroll through all the current events The display will also scroll automatically every 6 seconds Page 6 ED Status Supply This LED will be illuminated when mains is present Delays Active Illuminated if a fire condition exists and delays are programmed Disablements Illuminated if any devices or zones are isolated Test Mode Illuminated if any test modes are operational The buzzer will pulse and can be silenced by pressing Silence Buzzer Remote Signal Not implemented Faults Common Device or panel has a fault see the main display for details System Not implemented Tx Rx Not implemented Remote Signal Not implemented Device Battery Not implemented Version Z1000 V1 06 EDA Z1000 Operation Manual ED 3 User Operation 3 1 System Norm
8. 1000 V1 06 Page 3 EDA Z1000 Operation Manual Contents Index 1 0 Introduction 2 0 Front Panel Display and Keys 3 0 User Operations 3 1 System Normal 3 2 Fault Conditions 3 3 To Silence a Fault 3 4 To Reset a Fault 3 5 Alarm Condition 3 6 To Silence Sounders 3 7 To Re sound the Sounders 3 8 To Reset an Alarm 3 9 Menu Navigation 3 10 To Change Date and Time 3 11 To Isolate a Zone 3 12 To Isolate a Device 3 13 To Enable a Zone 3 14 To Enable a Device 3 15 View System History of Events 4 0 Advanced User Operations 4 1 General 4 2 To View Access Codes 4 3 Changing Access Codes 4 4 To Select a Test Mode 4 5 To Disable a Test Mode 4 6 To View Zones in Test Electro Detectors Page 4 ED Version Z1000 V1 06 EDA Z1000 Operation Manual ED 1 Introduction Electro Detectors has been manufacturing radio fire alarm systems for over 16 years and has now complemented its range of products with a smaller purpose built control panel the Zerio system It has been designed for smaller systems and is capable of handling 99 devices in 8 zones Typical installations could be small offices private houses HMO s guest houses and small hotels The system has been designed to allow very simple set up with most operations being automated The system is capable of displaying full text and having sophisticated cause and effect programming The panel requires a single 2 8Ahr Lead Acid battery to achieve 48 ho
9. ER Select the timeout in hours and press ENTER After this time has expired the device that was isolated will automatically be enabled Assuming the information is correct press ENTER to isolate the device The Disablements LED will be illuminated 3 13 To Enable a Zone To enable a previously isolated zone press MENU and enter a valid password Select 2 Disable Enable select 2 Enable select 1 Enable Zone Using the Tory keys select the zone number to be enabled and press ENTER To enable more zones press ENTER or CANCEL to exit If all zones have been enabled No Zones to enable will be displayed and the Disablements LED will extinguish assuming that no other Disablement conditions such as isolated devices exist 3 14 To Enable a Device To enable a previously isolated device press MENU and enter a valid password Select 2 Disable Enable select 2 Enable select 2 Enable Device Using the Tord keys select the device number to be enabled and press ENTER To enable more devices press ENTER or CANCEL to exit If all devices have been enabled No Devices to enable will be displayed and the Disablements LED will extinguish assuming that no other Disablement conditions such as isolated zones exist 3 15 Viewing Event History To view a log of historical system events press MENU followed by a valid password
10. al In normal operation the screen will show either the date and time contact details or alternate the two depending on the customers requested settings Also a single green Supply LED will be illuminated 3 2 Fault Conditions If a fault occurs a message describing the fault will be displayed and the internal buzzer will sound This will detail the device type a description of the fault the unit device number and a location description if programmed The description has a maximum length of 59 characters and will scroll across the screen Appropriate action should be taken to remedy the fault as this may affect the operation of the fire alarm system If in doubt the system maintenance company should be contacted If more than one fault exist on the system they will scroll round every 5 seconds Pressing the cursor keys will automatically move to the previous or next fault 3 3 To Silence a Fault Press Silence Buzzer Once the Silence buzzer button has been pressed the panel assumes that the fault has been acknowledged and does not resound the buzzer If a different fault occurs the panel will sound the buzzer until the new fault has been acknowledged 3 4 To Reset a Fault Assuming the fault has been rectified pressing reset will reset the system and the system normal screen will be displayed If the fault is still present or re occurs it will be re displayed this could take some time depending on the type of fault
11. e that the device is located in must be selected by scrolling to the appropriate zone number and pressing the A will be indicated by the zone for any zones selected Failure to select the correct zone will mean the system will operate as normal if the device is set into alarm Having selected the zones that are to be tested press Enter The operation of the alarm can now be selected Sounders If sounders are not required to sound set Sounders to OFF Actuators If actuators are not required to operate then set Actuators to OFF Actuators are output devices used to control equipment like magnetic doors other alarm systems gas valve shut offs air conditioning etc It would be normal for actuators to be isolated in an alarm test Version Z1000 V1 06 Electro Detectors Page 10 EDA Z1000 Operation Manual ED Fire Relay If the fire relay inside the panel is required to be disabled this should be set to OFF This is often used as a way of triggering a link to the fire brigade or to an alarm monitoring station Always follow the procedure outlined by the system installer Timeout This is the amount of time before the system will automatically exit test mode operation This should be set slightly longer than the test should take It can be set in 1 hour intervals and is selected using the cursor keys A maximum of 48 hours can be set The user should now press enter to enable the test mode The Test Mode
12. ing When manufactured each device is programmed with a unique ID Whenever a device transmits a message this ID is included as part of the message Also included in the message is the status i e alarm condition unit removal low battery etc The amount of smoke inside the head at the time of the transmission is included as part of the message Even if there is no change in status the device will transmit an I m OK verify message approximately every 3 minutes If these transmissions are not received from the device within the verify period typically 120 minutes then a Verify Fail fault is generated Version Z1000 V1 06 Electro Detectors Page 5 EDA Z1000 Operation Manual 2 Front Panel Display and Keys Figure 1 1 Front Panel Display and Buttons Zones In OFIREO 0000 1 2 3 4 INFORMATION STATUS Supply O Delays Active O Disablements O Test Mode O Remote Signal O O Remote Signal O Device Battery 1 2 3 4 Function Function2 Cancel Enter Silence Silence Buzzer Re sound Keys Function 1 amp 2 Programmable for use as Evacuate and Alert functions Cancel Used to return to the main screen from a menu or to return to the menu from a programming screen Enter This is used to accept information programmed into the panel Menu Press to enter the menu system If held down for longer than 4 seconds all LED s will flash lamp test Silence Buzzer Silences the buzzer for all
13. should be pressed to return to the previous menu 3 10 Changing the system date and time To set the date and time press MENU enter the correct password select 1 Setup 1 Time amp Date Use the lt and keys to navigate to the value to change and the or Y keys to select the desired value Press ENTER to accept or CANCEL to exit The Zerio panel automatically adjusts the clock for daylight savings 3 11 Isolating a Zone Once a zone is isolated it will not display any fault or alarm events for devices located in this zone Press MENU enter the correct password select 2 Disable Enable select 1 Disable select 1 Disable Zone Using the Tord keys select the zone number to be disabled and press ENTER Select the timeout in hours and press ENTER After this time has expired the isolated zone s will be automatically enabled Press ENTER to confirm The Disablements LED will be illuminated If more zones need to be isolated press ENTER or press CANCEL to exit Version Z1000 V1 06 Electro Detectors Page 8 EDA Z1000 Operation Manual ED 3 12 To Isolate a Device Once a device is isolated it will not display any fault or alarm event Press MENU and enter a valid password Select 2 Disable Enable select 1 Disable select 2 Disable Device Using the or Y keys select the device number to be disabled and press ENT
14. urs standby Two 6V 4Ahr batteries connected in series will provide a 72 hour HMO compliant standby Devices for the system are visually the same as the standard Millennium devices but are labelled differently with a yellow label In order to maintain compatibility the Zerio panel can re program a Millennium device to operate with the Zerio format providing the devices are version V1 6 or later A memory module is plugged into the processor board This stores a copy of any set up information including device text and cause and effects This can be used as a means of swapping data between panels should the need arise In order to log devices and program devices into the system they need to be connected via a supplied programming lead The system also stores the data programmed into each device allowing replacement devices to be easily cloned onto the system Prior to installation the building where the system is to be installed must be surveyed to ensure that each device to be fitted has a good radio communication path to the control panel If this is not done correctly the system will operate unreliably Having successfully completed this survey when installing the devices they must be positioned as per the survey Installing a device only a few tens of centimetres away from the surveyed position can reduce the signal strength significantly especially if any metal work is contained in the ceiling above the new position e g air conditioning duct