        EC2-371 Display Case and Coldroom Controller
         Contents
1.     2   adaptive superheat    U5  Superheatinit setpoint   v6  u6  Superheat setpoint min   3   wv  OK fT 3 fT    u7  Superheat setpoint max    u6   20   K  15     uu  Start openings 25   TS     TIO      P ANALOG SENSOR PARAMETERS  P1  Pressure sensor type selection  0   PT5 07M  1   PT5 18M  2   PT5 30M  DIGITAL INPUT PARAMETERS  S5 input l   inverse function   0   1       O      10  Functions for S5 0   normal input 0 8   0  1   cleaning 5   day   night switch  2   only fan 6   compressor safety chain  3   door contact 7   defrost request  4   permanent cooling 8   defrost inhibited    DIGITAL OUTPUT PARAMETERS    00  Output dL  inverse function   O   1      of    1     o P    i    u0  Refrigerant 0   R22 1   R134a  2  R507 3 R404A 4 R407C   ul   u   u3   u4   u5              nO  Functions for output_1 alarm   0    H OTHER PARAMETERS    Display access   0   all disabled  Caution  access to controller only via LON network possible    1   Keyboard enabled   2   IR remote control enabled   3   Keyboard and IR remote control  Temporary data display and manual  defrost enabled    4   Keyboard and IR remote control  Temporary data display disabled   Control setpoint with SEL key and manual defrost enabled     Password    PCN  865 016 15 05 2011    EC2 371 Display Case and Coldroom Controller    EMERSON     Operating Instructions       Remarks  r0 Door contact function   When the door opens the thermostat object can perform different tasks  The cooling  can stop  a timer can be st
2.    EC2 371 Display Case and Coldroom Controller    Operating Instructions    EMERSON        Note  This document contains short form instructions for experienced users   Use last column in List of Parameters to document your individual settings   More detailed information can be found in the User Manual     The EC2 371 is a dedicated refrigeration controller with superheat control and a  driver for an Alco Controls Electric Control Valve EX2  In addition the EC2 371  controls air temperature and manages defrost and fan s      Network           EMERSON    H og  e    Fra              ry             A PT5 pressure transmitter  1  and an ECN Nxx pipe temperature sensor  2   measure saturated suction gas pressure and suction gas temperature at the  evaporator outlet and feed the signals into the superheat control loop  The  superheat controller output modulates the opening of the EX2 pulse width  modulated Electrical Control Valve  6  thus optimizing the refrigerant mass flow  through the evaporator  The air temperature sensors  3  and  4  measure air in and  out temperature of the evaporator and feed signals into the air temperature  thermostat  The ECN Fxx fin sensor  5  is used for defrost termination  The  controller has 3 relay outputs to control the defrost heater  9   the evaporator fan   8  and an optional light  7   Please consult the technical data  right  for input and  output ratings    In case of power loss  due to the positive shut off characteristics of the EX2  Elec
3.   Ar No refrigerant flow detected   No refrigerant flow was detected  Au Valve open 100  for more than 10 minutes  dt Forced defrost termination  time or temperature   Ft Forced fan startup  time or temperature     Emerson Electric GmbH  amp  Co OHG is not to be held responsible for erroneous  literature regarding capacities  dimensions  applications  etc  stated herein   Products  specifications and data in this literature are subject to change without  notice  The information given herein is based on technical data and tests which  EMERSON believes to be reliable and which are in compliance with technical    Messages       No data to display  The display will show an        the display    In Reset to default values activated  The display will show an    In    when the factory default configuration data set  is initialized    Id Wink request received  The display will show a flashing    Id    when the wink request was received   The flashing    Id    will be shown on the display until the service button will  be pressed  or a 30 min delay timer will expire or a second wink request is  received    OF Node is offline  The node is offline and no application is running  This is the result of a  network management command and will happen for example during node  installation    dS Defrost standby   dP Pump down   dF Defrost cycle   dd Defrost drain delay   dI Defrost injection delay   du Defrost start up delay   Cn Cleaning   CL Alarms are cleared         at node start up and whe
4.   Defrost at startup    im   d5  Delay powerupdefrost_        d3  Pulsed defrost    0   off  no pulsed defrost  heaters switched off at defrost termination    0   no      yes    1          180   min   0        EC2 371_65135_EN_RO3 doc Replacement for R02                  Pump down delay O   180   sec   a Compressor will run during pump down delay while valve is closed     d7  Drain delay Of 1s   min   2      Injection delay O   180 0   Valve is open during injection delay while compressor is not running    E Eo Eon HEM    0   off  1   on    2   on together with timed defrost  dd  Pulsed defrost differential   1   20   K   2      dH  Pulsed defrost setpoint    40   dt     C  S    dt  Defrost termination temperature    40   90     C   8      dP  Max  defrost duration   O  180 min   30      dI  Defrostinterval TO 192   h   8 f    du  Start up delay after synch   O   180   min   30       F FAN PARAMETERS    F1  Fan startup by  0   on  1   delayed by time Fd  error on temperature  F        2   by temperature Ft  error on time  3   first  whatever comes first time or temperature  no alarm  4   last  time and temperature must come  no alarm    During no cooling  During defrost 0   on      off    Stop delay time  During cleaning 0   off  1   on  Fan delay after defrost    5 R410A 6 R124 7 R744A   Correction glide   dp   Glide   positive values   Pressure drop   negative values   MOP control 1  0   MOP off  1   MOP on    MOP temperature  40  Superheat mode 0   off  1   fixed superheat
5.   difference  cut out   set point  2  cooling  modulating thermostat  cut in   set point  cut out   set point     difference  2  cutin   set point     difference  cut out   set point  4  on  external control using nvi Valve via SNMP  Air in and air out sensor  monitoring off  Temp  alarms will be generated    16  Setpoint night tt     PCO  17  Differential night FOL   200  K  20     18  Mean factor  day operation   O   100       100       3   heating  deadband control     19  Mean factor  night operation   O  10      50       1d  Differential day FNL 2007 K  20     St  Setpointday tt     e  20       d DEFROST PARAMETERS    Defrost mode            0   natural defrost  defrost heater not activated pulsed defrost not possible  1   forced defrost  defrost heater activated  pulsed defrost possible  2   forced defrost  defrost heater activated  pulsed defrost possible  defrost  termination using nviStartUp via SNMP   dl  Termination by   0  termination by temperature  termination by time will generate an alarm  1  termination by time  termination by temperature will generate an alarm  2   first  what ever comes first time or temperature  no alarm  3   last  by time and temperature  no alarm   d2  Defrost termination sensor  0   Dedicated defrost sensor must be installed    1   Air out sensor used for defrost termination    temperature dt or max  time dP whatever is selected  1   on  pulsed defrost  dd and dH in use  heaters are switched off at  dH and switched on again at dH     dd
6.  EC2 371_65135_EN_RO3 doc Replacement for R02    4 4 PCN  865 016 15 05 2011    
7.  evaporator outlet temperature sensor should be mounted on the common  suction header of the evaporator    A calibration correction can be made using the parameter ul  see procedure  below      Setup and Parameter Modification Using the Keypad   For convenience  an infrared receiver for the optional IR remote control unit is  build in  enabling quick and easy modification of the system parameters when a  computer interface is not available    Alternatively  the parameters can be accessed via the 4 button keypad  The  configuration parameters are protected by a numerical password  The default  password is    12     To select the parameter configuration    e Press the PRG button for more than 5 seconds  a flashing    0    is displayed    e Press  4  or be until    12    is displayed  password    e Press SEL to confirm password   The first modifiable parameter code is displayed   1     To modify parameters see Parameters modification below     Parameter Modification  Procedure    e Press      or be to show the code of the parameter that has to be changed   e Press SEL to display the selected parameter value     e Press L or MI to increase or decrease the value   e Press SEL to temporarily confirm the new value and  ie its code     e Repeat the procedure from the beginning  press 4 or M to show       To exit and save the new settings    e Press PRG to confirm the new values and exit the parameters modification  procedure    To exit without modifying any parameter    e Do not pres
8. 371 Display Case and Coldroom Controller    Operating Instructions    EMERSON        Recommended Sensor Positions in Detail  see fig  on page 1      2  ECN Nxx coil out temperature sensor  Position directly after the evaporator on  the common suction line     3  ECN Sxx air in temperature sensor  Position in the middle of the cabinet as  high as possible     4  ECN Sxx air out temperature sensor  Position asymmetric closer to the  expansion valve as high as possible     5  ECN Fxx fin temperature sensor  Position on the evaporator  asymmetric closer  to the expansion valve    Recommendations for mounting the pipe sensor  Insure proper thermal contact by  using a metallic pipe clamp or temperature resistant plastic straps  Do not use  standard plastic tie wraps  as used for electrical wiring  as they may become loose  over time  which could result in faulty temperature measurements and poor  superheat control performance  It is recommended to insulate the pipe temperature  sensor with ARMAFLEX    or equivalent  The recommended position of the pipe  sensors is between 9 and 3 o   clock as shown in the picture     EC3_ColdDat cdr     1  PT5 07M suction pressure transmitter  Position on the common suction line  close to coil out temperature sensor  2    Both air temperature sensors should be mounted on spacers in the air duct so that  there is airflow around    Caution  The sensor cables can be extended if necessary  The connection must be  protected against water and dust    The
9. The cleaning mode should not be used in order to  isolate the application for maintenance purposes    e 3  Fans only   e 4  Set the electronic control valve to 100  open   e 5  Resets all parameters to the factory default setting  The controller will  indicate    oF    during the reset and the valve will close     Display of Data    The data to be shown on the display can be selected by the user  In case of an  alarm  the alarm code is displayed alternately with the selected data  The user can  inhibit the alarm code  Press the SEL button to scroll through all possible  displayable data    The display will show for one second the numerical identifier of the data and then  the selected data  After two minutes the display will return to the by parameter  1  selected data    It is possible to temporarily display the values of the different sensors  This is a  useful feature when initially setting up the system without the aid of the  WebPages  Press the SEL sequentially  The value displayed on the screen  corresponds to the number corresponding to the  1 parameter  Action only valid  when parameter H2   3     IR LED    Logical status of lighting relay  LON service LED    Logical status of fan relay  Logical status of defrost heater relay  Alarm condition       274 PCN  865 016 15 05 2011    EC2 371 Display Case and Coldroom Controller    EMERSON     Operating Instructions       List of Parameters    DISPLAY PARAMETERS    Value to show 0 9   0  0   Thermostat control temperature 
10. arted  when the timer expires an alarm can be generated  and the cooling can start again  If delay time Ad is set to zero the timer function  will not perform     Se   m J  w o o    off off fp  Sa a S    a a S    15 off off door alarm and cooling on and  temperature alarm on       Formula for Mean Factors AQ  r8  r9  Temperature calculation by the following formula   Temperature   Airin    1   Mean Factor   100    Airou   Mean Factor   100  Examples   Mean factor   0  Mean factor   100  Mean factor   50    Alarm Codes    EO _ Pressure sensor alarm   El Coil out sensor alarm   E2 Air in sensor alarm This Alarm Code is inhibited if no air in sensor used   AO  r8 and r9   100    E3  Air out sensor alarm This Alarm Code is inhibited if no air out sensor used   AO  r8 and r9   0  and fin sensor installed  d2   1    E4 Fin sensor alarm This Alarm Code is inhibited if no fin sensor used  d2   0    Explanations for E0     E4 Alarms  No sensor connected  or the sensor and or the   sensor cable is broken or short circuited     Temperature   Air in  Temperature   Air out  Temperature   Average between Air in and Air out    Er Data error display   out of range  Data send to the display is out of range    Ad Door alarm   AH High temperature alarm   AL Low temperature alarm    AE Thermostat emergency operation  Air sensor failure  system is in continuous cooling mode  AF Valve Status    Valve closed due to compressor safety loop active  Ao Superheat  emergency operation   Sensor s  failure
11. kwise  Mounting lugs will turn and gradually  move towards panel  2    Turn allen key until mounting lug barely touches  panel  Then move other mounting lug to the same  position  3    Tighten both sides very carefully until controller is  secured  Do not over tighten as mounting lugs will  break easily        EMERSON    Electrical Installation  Refer to the electrical wiring diagram  below  for electrical connections  A copy of    this diagram is labeled on the controller  Use connection wires cables suitable for  90  C operation  EN 60730 1     Cutout 71 x 29 mm                      24V    EMERSON   7 2    Climate Technologies    EC2 Series  Therm  EXV     1  Suction Press    2  Coil out Temp   3  Air in Temp  S4  Air out Temp  S5  Def  Temp DI S1 S2 S3       S4 S5 LON    EC2 analog inputs are for dedicated sensors only and should not be connected to  any other devices  Connecting any EC2 inputs to mains voltage will permanently  damage the EC2    Important  Keep controller and sensor wiring well separated from mains wiring   Minimum recommended distance 30mm    Warning  Use a class II category transformer for 24VAC power supply   EN 60742   Do not ground the 24VAC lines  We recommend to use one  transformer per EC2 controller and to use separate transformers for 3    party  controllers  to avoid possible interference or grounding problems in the power  supply  Connecting any EC2 inputs to mains voltage will permanently damage the  EC2     PCN  865 016 15 05 2011    S  EC2 
12. n no data is send to    Visualising Data  LON Monitoring Server   The EC2 371 has a LON communication interface enabling the controller to be  directly connected to a Monitoring Server  It can be connected by using the optional  cable assembly to a LON network  ECC 014  order no  804 381  with RJ45 to open   cable length 3m      Neuron ID   Service PIN     The service pin is available on the display  It is used to identify the controller in a    LON network  Press the button for app  1 second to send the Neuron ID  The  LED in the left upper corner will indicate the transmission of the Neuron ID    The default settings may be modified remotely from the Monitoring Server via the  LON network  Consult the Monitoring Server user manual for more information    It is also possible to display live graphical data on the server or to log data  containing the control temperature at defined intervals     knowledge of today  It is intended only for use by persons having the appropriate  technical knowledge and skills  at their own discretion and risk  Our products are  designed and adapted for fixed locations  For mobile applications failures may  occur  The suitability for this has to be assured from the plant manufacturer which  may include making appropriate tests  This document replaces all former versions    Emerson Electric GmbH  amp  Co OHG   Postfach 1251   HeerstraBe 111   D 71332 Waiblingen   Germany   Phone  49  0 7151 509 0   Fax  49  0 7151 509 200  www emersonclimate eu   
13. s any button for at least 60 seconds  TIME OUT      e Press    ESC    on IR remote control     EC2 371_65135_EN_RO3 doc Replacement for R02    Defrost Activation   A defrost cycle can be activated locally from the keypad     e Press the he button for more than 5 seconds  a flashing    0    is displayed    e Press  4  or be until    12    is displayed  password   e Press SEL to confirm password  The defrost cycle is activated     Special Functions   The Special Functions can be activated by     e Press  1 and IM together for more than 5 seconds  a flashing    0    is displayed     e Press CJ or M until the password is displayed  default   12   If password was  changed  select the new password    e Press SEL to confirm password  a    0    is displayed and the Special Function  mode is activated     e Press  a  or be to select the function  The number of special functions is dynamic  and controller dependent  See list below    e Press SEL to activate the function without leaving the special function mode    e Press PRG to activate the function and leave the special function mode    Most of the Special Functions work in a toggle mode  the first call activates the   function  and the second call deactivates the function    The indication of the function can only be displayed after exiting the special   function mode    e 0  Display test function   e 1  Clear alarm messages   e 2  Cleaning mode  The cleaning mode is effectively a manual defrost with the  option of the fans on off  
14. trical Control Valves  a liquid line solenoid valve is not needed to prevent  flooding of the compressor     A Safety instructions    e Read installation instructions thoroughly  Failure to comply can result in  device failure  system damage or personal injury    e The product is intended for use by persons having the appropriate  knowledge and skills    e Ensure electrical ratings per technical data are not exceeded    e Disconnect all voltages from system before installation    e Keep temperatures within nominal limits    e Comply with local electrical regulations when wiring    EC2 371_65135_EN_RO3 doc Replacement for R02    Technical Data  EC2 Series Controller        Power supply 24VAC  10   50 60Hz  Class II  20VA max including EX2  LonWorks   Interface  FTT10  RJ45 connector    Plug in connector size Removable screw terminals  wire size 0 14     1 5mm     Temperature  storage  20      65  C  operating 0     60  C    Taaa  IP65  front protection with gasket   24VDC  4   20mA    SPDT contacts  AgCdO  Inductive  AC15  250V 2A  Resistive  AC1  250V 8A  12A total return current    Triac output for EX2  Electrical Control Valve  Coil  ASC 24V only     Mounting   The EC2 371 can be mounted in panels with a 71 x  29 mm cutout  See dimensional drawing below for  space requirements including rear connectors    Push controller into panel cutout  1    Make sure that mounting lugs are flush with outside  of controller housing   Insert allen key into front panel holes and turn  cloc
15. with Temp  alignment   C  1   Air in temperature   C   2   Air out temperature   C   3   Alarm temperature   C   4   Defrost termination temperature   C   5   Coil in temperature   C calculated from the pressure   6   Coil out temperature   C   7   Calculated superheat   K   8   Valve opening in     9   Displays defrost status     2  Alarm suppression O off l on   O   1       0     Temperature Unit 0   C 1 F   0  1      o    Decimal point 0 yes 1 n0o   0  1     0     Display during defrost 0 2 0  0   dF    defrost mode   1   dF   defrost termination temp   2   dF   control temperature   C  Temperature alignment for 1 0    20  20   K   F  00      A ALARM PARAMETERS   AO  Mean factor alarm temperature   0  100     100    AI  Low temp alarm delay   0  180  mn 5   _   A2  High temp alarm dey   o  180  mm   5      A3  Alarm delay after defro   0  180  min   10  Ad  Door alarm delay O   180   min 2  0   no door alarm     AH High temp aarm imi  a  o eo    AL  Low temp alarm imit  55  an    C K  s0     At  Alarm limit type 0 1   0  O absolute temperatures   C  1  relative temperatures K to setpoint    r THERMOSTAT PARAMETERS    10  Door contact function  seepage 4    0   15   6 a  rl  Min setpoint SO  e  PC   SOT  12  Setpoint max tl   60   PC   40      13  Day night control O off l on   O   1       1     r4  Thermostat mode 4    0  off  no thermostat function  continues cooling air in sensor monitoring  off  no temp  alarms generated  1  cooling  deadband control  cutin   set point 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Samsung Galaxy Tab 3 7.0 Lite 3G Užívateľská príručka  XR170C + AUX Italiano  Manual  Velodyne Acoustics LIDAR HDL-32E User's Manual  Elaboration dtun manuel d`entretien du téseau tertiaire et  Installation Manual for Positioning Modules LD75P4, LD75D4    GE BL Series Case Studies  ARS-1000  Bedienungsanleitung - MTP, Mig-Tig    Copyright © All rights reserved. 