EMi2 series

image

Contents

1. UNINTERRUPTIBLE POWER SUPPLY UPS VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS SWITCH MODE POWER SUPPLY INDUSTRIAL POWER SUPPLY LIGHTING FLOW DIMMER STABILIZERS STATIC INVERTERS III SERVOMOTOR VOLTAGE STABILISERS series NENNEN ii USERS MANUAL 1 1 1 2 1 2 1 1 2 2 2 1 2 2 2 5 3 1 3 1 1 3 1 2 3 2 3 2 1 3 2 2 d d 3 3 1 3 3 2 3 3 3 3 4 3 4 1 3 4 2 41 411 4 2 4 2 1 4 2 2 4 2 3 4 2 4 4 3 4 3 1 4 3 2 4 3 3 4 3 4 4 3 5 4 4 4 4 1 4 4 2 4 5 9 1 5 1 1 5 1 2 9 19 5 2 INTRODUCTION GRATEFULNESS LETTER USING THIS MANUAL Conventions and used symbols For more information and or help QUALITY AND STANDARD GUARANTEE MANAGEMENT DECLARATION STANDARD ENVIRONMENT PRESENTATION FRONT VIEW Connectivity Synoptic DEFINITION AND STRUCTURE Nomenclature Structural diagram DESCRIPTION OF THE SYSTEM Main quality performances Constructive features Operating principle OPTIONS Maximum minimum output voltage protection Output ammeter INSTALLATION IMPORTANT SAFETY INSTRUCTIONS To keep in mind RECEPTION OF THE EQUIPMENT Unpacking and contents checking Transport Storage Location CONNECTION Connection terminals of single phase equipments Connection terminals of three phase equipments Connecting the earth Connecting the input Connecting the output START UP AND SHUTDOWN S
2. 3 1 FRONT VIEW E Eivi Control panels Switch type Salicr U 9 e Fig 1 View of three phase 60kVA stabilizer EMi2 series Switch 1 0 2 Control panels Fig 2 View of three phase 15kVA stabilizer EMI2 series Control owitch type 1 0 2 panel Fig 3 View of single phase 10kVA stabilizer EMi2 series Input phases Earth Neutral Output phases U V W Fig 4 Connection terminals of three phase model EMI2 1 60 6 a Ms USER MANUAL Neutral Input circuit breaker Fig 5 View of rear side and connection terminals of single phase model 3 1 2 Synoptic Indicator of output Indicators of output out of range LCD panel Indicators Indicators of displayed of displayed measure measure ment ments UP DOWN buttons MODE button Fig 6 View of indicators and buttons from synoptic oynoptic is divided in 3 parts e Display seven segments e LEDs e Buttons 3 1 2 1 Display seven segments The following measurements can be monitored in the LCD panel Input voltage output voltage output frequency and output current as an option These values are being displayed in the LCD panel when pressing button MODE There are 7 LED indicators in the front panel e Input voltage This LED lights when the input voltage has been selected with button MODE e Output voltage This LED lights when the output voltage has been selected with but
3. 40 V s See section 7 1 depending on the model 1 3 to 1 Nil Generals input output voltage output Intensidad optional output frequency digital Indicators Stabilizer in operating High Low output voltage EMi2 T 75 4FBM EMi2 T 90 4FBM EMi2 T 110 4FBM EMi2 T 140 4FBM EMi2 T 160 4FBM EMi2 T 220 4FBM EMi2 T 275 4FBM EMi2 T 330 4FBM 1087 297 130 4 597 1594 597 2029 5 95 23412 597 1 400 1 3985 297 4009 478 97 Tabla 2 Particular technical specificatgions for three phase models 9 4002 196 87 9 15 20 90 45 79 110 140 140 220 215 330 Output present stabilizer ON NO C Dry contacts Warning for high low output voltage NO C NC Noise level at 1 metre lt 45 dB A Operating temperature 5 to 55 C Storage temperature 30 to 70 C Relative humidity 0 to 95 non condensing een Between Failures 60 000 hours Mean Time To Repair MTTR 30 minutes STANDARDS Electromagnetic Compatibility EMC Safety EN 61000 6 4 EN 61000 6 2 IEC 60950 1 IEC 61558 1 Tabla 3 General specifications of all EMi2 series 1 When input voltage exceeds the allowed values the stabilizer checks its output and disconnects in those versions with circuit breaker In case the circuit breaker module is not present the stabilizer continues supplying output according to its transformation ratio Once the input voltage returns to the allowed limits the sta bilizer st
4. STRUCTURE 3 2 1 Nomenclature Three phase EMi2 series EMi2 T 20 2FBM MR CO 25 A 3 220 60Hz 4 EE61153 Special equipment EE Output accuracy different from 1 Frequency if it is not 50Hz Voltage if it is not 3x400Vac A Digital output ammeter 25 Input range if it is different from 15 CO Made in Spain silk screening in the equipment and packing customs purposes MR Max min protection with automatic rearming M Maxmin protection with manual rearming FBM Independent phase regulation manual bypass First character of voltage Power of the equipment in kVA Single phase EMi2 series EMi2 M 20 2BM MR CO 2 2596 A 220V 60Hz 4 EE61153 Ly Special equipment EE gt Output accuracy different from 1 Frequency if it is not 50Hz Voltage if it is not 230Vac A Digital output ammeter 25 Input range if it is different from 15 CO Made in Spain silk screening in the equipment and packing customs purposes MR Max min protection with automatic rearming M Maxmin protection with manual rearming BM Manual bypass First character of voltage Power of the equipment in kVA 3 2 2 Structural diagram EMI2 Max min prote Bypass Stabilizer tions manual INPUT SALIDA Opcional Fig 7 Single line diagram of EMi2 stabilizer 8 a es USER MANUAL 3 3 DESCRIPTION OF THE SYSTEM Voltage stabilizer from EMI2 series is a voltage regulator that due to its s
5. be repaired by an authorised engineer from technical staff S T S To open the equipment or any repairing attempt by any non authorised person will be very dangerous and will invalidate the warranty e Do not connect any load to the stabilizer that exceed its power Capacity e Read the maintenance and clean section carefully when the equipment is going to be cleaned e Always leave 30cm between the equipment and walls in order to guarantee that cooling is enough 4 1 1 To keep in mind Stabilizers are used to protect the critical loads against mains fluc tuations this way it makes possible an optimal operating of them Those points about safety have been detailed in section 4 1 Impor tant safety instructions Now these points will be repeated in order to provide information about the connections of both stabilizer and loads e When installing the stabilizer the use of inappropriate cross cable sections can entail danger for the user and for the integ rity of the device Earth cable has to be sized according to its current capacity which is shown in the front nameplate of the stabilizer All earth connections have to be done with this cable To not earth the equipment or to make an inappropriate connection the equip ments will mean a danger for the user and high risk of faults in the electronic circuit 4 2 EQUIPMENT RECEPTION 4 2 1 Unpacking and content checking e Before unpacking check that th
6. end of its useful life Our company commits to use the services of authorised societies and according to the regulations in order to treat the recovered product at the end of its useful life contact your distributor Packaging To recycle the packing follow the legal regulations in force EN SALICRU E 5 3 PRESENTATION stabilizer EMi2 has been designed for both to operate in unstable mains and to protect the critical loads Input mains and output are marked in the terminals of the equip ment When doing the installation of this device use the correct cross cable section in order to guarantee its correct operating stabilizer will automatically be shutdown when input voltage will be out of range one phase will fault or any output will be short circuited Once the failure has been solved the stabilizer will start up automatically again In case of a failure shorter than the delay shutdown the stabilizer will still be working In case of a failure longer than the delay shutdown the stabilizer will automatically be shutdown It has three LCD panels in the front side of the stabilizer which are used to check the voltage applied to the input of the equipment Input voltage can be checked with the indicators The equipment shutdown and transference of input mains to the output is done through a switch type 1 0 2 1 Bypass position from input to output 0 Shutdown position 2 Stabilizer position
7. its commissioning by SALICRU S A staff or other specifically authorised or 18 months from its factory delivery whichever expires first In case of failure of the product inside the warranty period SALICRU S A must re pair at your facilities at no cost the faulty part or parts The trans port expenses and packaging will be borne to the user A For equipments out from the national territory contact with the Export Department SALICRU S A guarantees for period time higher than 10 years the availability of parts and spare parts as hardware as software as well as a complete assistance regarding the reparations components replacement and software updating 6 3 3 Out of scope of supply SALICRU S A is not forced by the warranty if it appreciates that the defect in the product doesn t exist or it was caused by a wrong use negligence installation and or inadequate testing tentative of repairing or not authorized modification or any other cause beyond the foreseen use or by accident fire lightnings or other dangers Neither it will cover in any case compensations for damages or injuries 6 4 AVAILABLE MAINTENANCE AND SERVICE CONTRACTS When the warranty is expired SALICRU S A adapting to the customer s needs has several maintenance modalities e Preventive It guarantees a higher safety to preserve the cor rect operating of the equipments with a yearly Preventive visit in which the specialised te
8. more information and or help of the version of your specific unit request it to our Service and Technical Support S T S 3 E il ipee USER MANUAL 2 QUALITY AND STANDARD GUARANTEE 2 1 MANAGEMENT DECLARATION Our target is the client s satisfaction therefore this Management has decided to establish a Quality and Environmental policy by means of installation a Quality and Environmental Management oystem that becomes us capable to comply the requirements de manded by the standard ISO 9001 2000 and ISO 14001 2004 and by our Clients and concerned parts too Likewise the enterprise Management is committed with the devel opment and improvement of the Quality and Environmental Man agement System through e The communication to all the company about the importance of satisfaction both in the client s requirements and in the legal and regulations he Quality and Environmental Policy diffusion and the fixation of the Quality and Environment targets e To carry out revisions by the Management e o provide the needed resources Management agent The Management has designated as management agent the person in charge about the Quality and Environment department who with independence of other responsibilities has the responsibility and authority to assure that the processes of the quality and environ mental management system are established and maintained to inform to the Management about the operating o
9. Supplies Industrial Power Supplies Lighting Flow Dimmer Stabilizers Static Inverters Continuous Regulation Autotransformers Nota Salicru can give other electronics solutions according to the application specifications or technical specifications
10. arts up in normal operating automatically 2 Output voltage accuracy can be set to other value under request 3 This value can be set to other value under request EN SALICRU 17 18 a E USER MANUAL UNINTERRUPTIBLE POWER SUPPLY UPS VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS SWITCH MODE POWER SUPPLY INDUSTRIAL POWER SUPPLY LIGHTING FLOW DIMMER STABILIZERS STATIC INVERTERS SA LIC U Avda de la Serra 100 08460 Palautordera BARCELONA Tel 34 93 848 24 00 902 48 24 00 Fax 34 94 848 11 51 comercial salicru com Tel S T S 902 48 24 01 Fax S T S 34 848 22 05 sst salicru com SALICRU COM BRANCHES AND SERVICES and TECHNICAL SUPPORT S T S EK839A01 MADRID PALMA DE MALLORCA BARCELONA PAMPLONA BADAJOZ SAN SEBASTIAN BILBAO SANTA CRUZ DE TENERIFE GIJON SEVILLA LA CORUNA VALENCIA LAS PALMAS DEG CANARIA VALLADOLID M LAGA ZARAGOZA MURCIA SUBSIDIARIES FRANCIA RUSIA PORTUGAL CHINA HUNGRIA SINGAPUR REINO UNIDO M XICO POLONIA URUGUAY REST of WORLD ALEMANIA ECUADOR B LGICA PER DINAMARCA ARABIA SAUD GRECIA ARGELIA HOLANDA EGIPTO IRLANDA JORDANIA NORUEGA KUWAIT REP BLICA CHECA MARRUECOS SUECIA T NEZ SUIZA KAZAJST N UCRANIA PAKIST N ARGENTINA FILIPINAS BRASIL INDONESIA CHILE MALASIA COLOMBIA TAILANDIA Product Range Uninterruptible Power Supply UPS Voltage Stabilizers and Power Line Conditioners Switch Mode Power
11. chnicians from SALICRU S A make several tests and sets in the systems O Check and write down the input and output voltages and currents per phase Check the logged alarms Check the readings of the LCD panel Other measurements Check the fan status Check the load level Check the selected language Check the correct location of the equipment Qd uugoc o oc u eL General cleaning of the equipment This way it is guaranteed the perfect operating and the pos sible coming faults are avoided These supervisions are usually done without shutdown the equipment In those cases that a shutdown were needed date and time would agree with the customer to do the task This maintenance modality covers inside the working time table all the journey expenses and manpower e Corrective When a fault occurs in the equipment operating and previous notice to our Service and Technical Support S T S in which a specialized technician will establish the failure scope and he will determine a first diagnostic the corrective action starts The needed visits for its correct resolution are unlimited and they are included inside the maintenance modalities It means that in case of failure SALICRU S A will check the equip ments as many time as it were needed EN SALICRU 15 Besides inside these two modalities is possible to fix the ac tion timetable and response times in order to be adapted to the cust
12. current as an option Also LED indicators of syn optic provide information about the status of the equipment output voltage present fault high low It is also possible to receive infor mation through dry contact interface Fuses at front panel provide protection for loads and stabilizer against overcurrents Forced cooling is used in those models higher than 30kVA either single phase or three phase in order to keep a stable internal temperature Below this power the cooling is nat ural Under request it is possible to manufacture the models with wide input voltage range of 2 2596 input regulation window 3 3 1 Main quality performances Among others the main quality performances of this series are e High efficiency e Electromechanical protection of maximum minimum voltage op tional e Short circuit protection e Operating with non linear loads e Wide input voltage range optional e Warranty for 10 years optional 3 3 2 Constructive features Equipment is built from three single phase stabilizers with inde pendent control per each phase This way each phase is regulated as regards to neutral to the nominal voltage without modifying the voltage of the other ones whatever the load percentage is con nected to each phase Each phase is protected with its own circuit breaker which avoids against direct short circuits to trip the general protection Equipment has indicators made of light emit
13. e a building the electrical distribution system should be made in a professional way and according to the distribution and earth principles by using duly cables with quality and cross section The end user has to pay attention to important aspects when installing the stabilizer between the load and mains The following points are important for his safety and correct operating of the equipment e Connection of the stabilizer to mains has to be done by author ised staff and according to both the instructions stated in the in Stallation section and by using the proper cross cable section e Stabilizers have to be fed through a switchgear panel with main earthing connection and protected with a suitable sized fused for the stabilizer according to the label located in its rear side e Risk of electrocution exists for the user when it is used a Switchgear panel with an inadequate main earthing connection or without it to feed the stabilizer Also the possibility of faults in the electronic circuits is increased Distribution system of some buildings has outlets with phase and neutral only that they seem that are connected to earth properly but they arent In those cases the earth has been connected to the neutral or it has not been connected When these outlets or others in parallel with them are connected to the critical loads the voltage in the neutral will be different from the earth one causing a risk of electrocution Also all the equ
14. e stabilizer has not been dam aged during transport If there were any damage in the packaging contact with the transport agency Check that all parts have been supplied with the equipment Contents J Automatic voltage stabilizer User s manual CD By means of forklift trucks move the unit to the suitable location to make its installation 4 2 2 Transport Stabilizer has to remain in vertical position during transport Check that the floor can support the weight of the equipment A In case the equipment has to be transported again make sure that it is packaged properly therefore it is recom mended to preserve the original packaging 4 2 3 Storage Equipment can be stored in a dry location between 25 C and Relative environment humidity has to be between 20 and 95 non condensing EN SALICRU 11 4 2 4 Location 4 3 2 Connection terminals for three phase equipments This product complies with the safety standards for equipments to be operated in restricted areas So according to the local regula tions the owner has to guarantee p Vo di NU 1 e Access only for both technical maintenance staff and duly me FEE EE 10999999999 trained users ie ar Restricted access under key or other safety measurements by pe FEE responsible staff i a a M It is recommended to operate between 0 C and 40 C humidity between 20 a
15. f the quality and environmental management system including the necessities for the improvement and to promote the knowledge of the client s re quirements and environmental requirements at all the levels of the organization In the next PROCESS MAP is represented the interaction among all the processes of the Quality and Environmental System CONTINUOUS IMPROVEMENT PROCESS MANAGEMENT REVIEW QUALITY ENVIRONMENTAL MANAGEMENT MANAGEMENT PROCES PROCESS QE mapPmocess KG m CLIENTS CLIENTS PRODUCT SERVICE COMMERCIAL MANUFACTURING gt PROCESS PROCESS INTERNAL LOGISTIC PROCESS i MAINTENANCE PROCESS jC TRAINING PROCESS Fig 0 Process map of Quality and Environment system 2 2 STANDARD The EMi2 product is designed manufactured and commercialized in accordance with the standard EN ISO 9001 of Quality Assur ance The C marking shows the conformity to the EEC Directive by means of the application of the following standards EMC EN 61000 6 4 Standard generic emission Industrial environ ment EN 61000 6 2 Standard generic immunity Industrial environ ment Safety e IEC 60950 1 IT equipments e EC 61558 1 Safety of transformers power supply engines and similar products 2 3 ENVIRONMENT This product has been designed to respect the environment and has been manufactured in accordance with the standard ISO 14001 Recycling the device at the
16. hil ippines Malaysia Pakistan Morocco Thailand Emirates Arabs United Egypt Australia and New Zealand 16 Hi USER MANUAL 7 ANNEXES 7 1 PARTICULAR TECHNICAL SPECIFICATIONS Single phase Regu Voltage Max Effi models lation V and output ciency range accuracy EMi2 M 5 2BM 2302 190 gt 96 Tabla 1 Particular technical specifications for single phase EMi2 M 7 5 2BM EMi2 M 10 2BM EMi2 M 15 2BM EMi2 M 20 2BM EMi2 M 25 2BM EMi2 M 30 2BM 7 2 GENERAL TECHNICAL SPECIFICATIONS Input Single phase 230 V Three phase 3x400 V 195 265 Vac 230Vac 15 Voltage Input Normal standard range 172 288 Vac 230Vac 25 Frequency 48 63 Hz Nominal current See section 7 1 depending on the model Output Voltage Single phase 230 V Three phase 3x400 V Accuracy 1 Disconnection voltage value 200 240 Vac Frequency 48 63 Hz Nominal power See section 7 1 depending on the model Maximum current See section 7 1 depending on the model 2 15kVA single Response 6 45kVA three 80 V s models Three phase Regula Voltage Effi tion rage V and ciency 96 accuracy 96 EMi2 T 15 4FBM 400 196 gt 96 EMi2 T 20 4FBM 4002 196 gt 96 EMi2 T 30 4FBM 400 196 gt 97 EMi2 T 45 4FBM 4002 196 gt 97 EMi2 T 60 4FBM gt 97 time gt 15kVA single gt 45kVA three Efficiency Power factor Crest factor Harmonic distortion Front panel
17. implicity reliability and robustness has achieved to persist along the ages but with a complete redesigning which has included technical improvements both electrical and mechanical It is very useful in those applications without requiring a fast response time but requiring a constant and accurate stabilization Voltage stabilizer provides protection against sudden changes ir regularities increasing and decreasing of mains voltage by means of an accurate voltage stabilization Also an optional module pro vides protection against maximum and minimum output voltages protecting the loads by disconnecting the output through a con tactor when the voltage exceeds the allowed range or any phase Is missed There is a delay of 2 seconds between the turning on off the contactor in order to keep the protection against sudden fluctuations in mains Also it has a manual Bypass otabilizer can be used to stabilize the voltage of any type of com puter fax photocopier medical equipment home or office lighting power supply for apartment or office buildings tools machines etc otabilizer makes a sensitive fast and efficient stabilization of the output voltage through the incorporated Booster transformer variac and microprocessor To keep the output stable inside a minimum tolerance the servo system uses a control through thyristors to manage the DC motor LCD panel can display the following values input output voltages frequency and
18. inal neutral N Output terminal neutral N Earth terminal PE Output terminal phase R Output terminal neutral N Fig 10 Connection terminals for 60kVA three phase model Input terminal phase R Input terminal neutral N Fig 8 Connection terminals for 10kVA single phase model 12 Eill a as USER MANUAL 4 3 3 Connecting the earth AN Both for safety and an operation without faults the equipment has to be earthed Earth the equipment be fore doing any connection Earthing terminal has to be connected to an electrical mains of good quality low impedance Load earthing connection should be done through the earth bonding terminal at the output of the stabilizer 4 3 4 Connecting the input A circuit breaker of two poles and an earth leakage breaker has to be added in the electrical line phase neutral of the switchgear panel that supplies the stabilizer It is recommended the use a circuit breaker in the switchgear panel with the same size of the circuit breaker of the stabilizer Circuit breaker size and type are defined in the technical specifications Earth leakage breaker should be sized with the sum of the earth leakage currents of the loads plus 30mA more These figures of current have been defined considering that the stabilizer is only supplied from the circuit breaker of the switchgear panel Otherwise they should again be calculated considering all loads A Any variation in the switchgear pane
19. ip ments connected to them will have a higher risk of failures 14 ami ipee USER MANUAL 6 MAINTENANCE WARRANTY AND SERVICE 6 1 BASIC MAINTENANCE GUIDE e tis not needed any maintenance by the user side From time to time dust the fans Check that the input BYPASS and OFF fuses are in posi tion 0 before cleaning Do not use detergent or cleaning materials that could damage the plastic parts Do not enter any liquid inside the device Check that the cooling grids are cleared The stabilizer body can be cleaned with a dry and clean cloth 6 2 TROUBLESHOOTING AND FREQUENT ASKED QUESTIONS FAQ In case of faults or wrong operating of the stabilizer before calling the technical service check the following points S T S e sthe switchgear panel connected to mains e Are the Input fuses circuit breakers blown tripped Bring the following data to the authorised technical service S T S Details of the equipment stated in its nameplate model serial number e Description of the fault 6 3 WARRANTY CONDITIONS The limited warranty by SALICRU S A only applies to those prod ucts that you acquire for commercial or industrial use in the normal development of your business 6 3 1 Covered product Voltage stabilizer from EMI2 series 6 3 2 Warranty terms SALICRU S A guarantees the product against any parts and or labour defect for 12 months period from
20. l has to be done by technical staff Once all changes have been finished move the circuit breaker switch to position 0 Connect the lines phases and neutral to their corresponding terminals through the circuit breaker A Minimum cross cable section between the stabilizer and switchgear panel has to be according to the power rate of the stabilizer In case of sizing a lower cross cable section could be risk of fire Before connecting the input cables the circuit breaker of the switchgear panel has to be in position 0 4 3 5 Connecting the output It is recommended the use of separate circuit breakers and earth leakage breakers at the output of the stabilizer in case it feeds sev eral loads If each load is connected to the stabilizer through sepa rate circuit breakers in case of a short circuit in any load the circuit breaker of the short circuited line will trip and the rest of connected loads will not be affected The size of the circuit breakers of the loads has to be lower than the value of the short circuit current Otherwise in case of short circuit circuit breaker will not trip in less than 10ms and all loads Will be shutdown A Before doing the connections all inputs output fuses from stabilizer and circuit breakers from switchgear panel have to be in position 0 Loads are connected to OUTPUT NEUTRAL and EARTH terminals of the stabilizer A Cross cable section between the
21. nd 95 non condensing and altitude up to 1000 metres It is possible to require an air conditioning to comply these premise Il bd B H EH Other requirements e Equipment should not have to be exposed to direct sunlight Do not expose the equipment to rain or liquids in general Do not enter any object inside Earth terminal PE Input terminal phase R Output terminal phase W e Avoid dusty locations or areas where conductive dust or cor i s Input terminal phase utput terminal phase rosive materials are present Input terminal phase T Output terminal phase U e Preserve a space of 20 cm in front of the cooling grids A eN 4 3 CONNECTION Fig 9 Connection terminals for 15kVA three phase model Connections can only be done by authorised technical staff If the stabilizer is moved from its location it is possible to have condensation In that case wait as minimum for two hours before starting with the installation procedure Connection terminals are located in the front side of the stabilizer Remove the lower front panel to have access to the connection terminals IE M cw lOO Ra 4 3 1 Connection terminals for single phase equipments me R 1 Earth Input terminal phase R termina Output terminal phase W PE Input terminal phase S Output terminal phase V d ec Input terminal phase T Output terminal phase U E i Input term
22. omer s needs CJ LV8HLS Customer s attention from Monday to Friday from 9 h to 18 h The response time is inside the same day or as maximum in the next 24 hours of the fault notification O LS14HLS Customer s attention from Monday to Saturday from 6 h to 20 h Response time is inside the same day or as maximum at first time of the next working day CJ LD24HLS Customer s attention from Monday to Sunday 24 h 365 days per year Response time in less than two or three hours after the fault notification Additional arrangement 1 m cb e Index 1 t means the number or Preventive visits per year It includes displacement and manpower expenses inside the established timetable for each maintenance modality as well as all the needed Corrective visits Excluding all the parts and batteries in case of reparation O Index m It means to include all the spare parts O Index cb It means to include batteries 6 5 TECHNICAL SERVICE NETWORK The covering as national as international of Service and Technical support S T S points are made up by At national level Andorra Barcelona Madrid Bilbao Gijon A Coru a Las Palmas de G Canaria M laga Murcia Palma de Mallorca San Sebastian santa Cruz de Tenerife Seville Taco La Laguna Tenerife Valencia and Zaragoza At international level France Brazil Hungary Portugal Singapore U K China Mexico Uruguay Chile Venezuela Colombia Argentina Poland The P
23. oncession of this manual is prohibited without the previous written authorization of our firm 1 2 USING THIS MANUAL The purpose of this manual is to give explanations and procedures for the installation and operating of the equipment This manual has to be read carefully before installing and operating it Keep this manual for future consults 1 2 1 Conventions and used symbols A Warning symbol Carefully read the indicated para graph and take the stated prevention measures A Danger of electrical discharge symbol Pay special attention to it both in the indication on the equipment and in the paragraph referred to this user s manual Qn protective earthing terminal symbol Connect the earth cable coming from the installation to this terminal ees of information symbol Additional topics that complement the basic procedures Preservation of the environment The presence of this mmm symbol in the product or in their associated documentation states that when its useful life is expired it will not be disposed together with the domestic residuals In order to avoid possible damages to the environment separate this product from other re siduals and recycle it suitably The users can contact with their pro vider or with the pertinent local authorities to be informed on how and where they can take the product to be recycled and or disposed correctly 1 2 2 For more information and or help For
24. rminals although the led Output is turned on and the output voltmeter displays the voltage value it doesn t mean that there is voltage in the output ter minals Proceed to start up the stabilizer the equipment will supply voltage at its output The device is ready start up the loads to be fed 3 4 1 2 Automatic version MR start up Automatic rearming As maximum minimum voltage protections are located between the stabilizer and output terminals although the led Output is turned on and the output voltmeter displays the voltage value it doesn t mean that there is voltage in the output ter minals Proceed to start up the stabilizer if output voltage is inside the range 77 5 the equipment will supply output voltage The device is ready start up the loads to be fed This version if the output voltage is out of the quoted range the equipment will disconnect the system automatically till the voltage Is restored to its nominal value of 7 5 96 The re connection of the equipment is delayed 15 seconds approximately in order to avoid unnecessary connections and disconnections 3 4 2 Output ammeter Under request it is possible to provide the LCD panel with the output current measurements per phase 10 Ell a E USER MANUAL 4 INSTALLATION 4 1 IMPORTANT SAFETY INSTRUCTIONS For safety of user data and product read carefully the following instructions before installing the equipment e Sy
25. stabilizer and loads has to be sized properly and according to the current drawn by the loads A Maximum power of the connected loads does not have to exceed the nominal power of the stabilizer 4 4 START UP AND SHUTDOWN 4 41 Startup Once the connection of the equipment has been done to start up the equipment it is enough by turning to position I all circuit breakers of switchgear panel and to turn to position Regulation all fuses of the stabilizer If input mains is inside the allowed voltage range the stabilizer will be started up 4 4 2 Shutdown To shutdown the equipment turn all fuses and circuit breakers from stabilizer and switchgear panel to position 0 In case of maintenance tasks in the stabilizer without disconnecting the loads move the Bypass switch to position Line 4 5 BYPASS Manoeuvring switch type 1 0 2 can be turned to position 1 or By pass which makes a direct connection of the equipment output with its input This operating can be used when in case of equipment failure the loads can t be shutdown EN SALICRU 13 5 OPERATING 5 1 OPERATING MODES 5 1 1 Regulator mode The equipment operates on regulator mode when input voltage Is inside the specified range In this mode the equipment stabilizes the input voltage and feeds the loads at the nominal input voltage with its particular tolerance range Input range values and o
26. stem has been designed to provide all safety conditions to protect the electronic equipments of the office including the IT systems In case there was any question call to technical service S T S e To avoid damages to the equipment transport it inside its own packaging e Incase of sudden changes in temperature from cold to normal operating temperature it is possible to form condensations in side the device It is absolutely essential to start up the equip ment when it is completely dry Therefore wait for two hours as minimum before operate with it e Once dry check that all environmental conditions of the equip ment stated in the technical specifications are met before making the connection Once the equipment is installed use the suitable cross cable section to make the connection Neutral and earth has to be properly connected e Arrange the wiring in such way that it does not exist any risk of electrocution or it does not obstruct the way and cause an acci dent Before starting up read carefully all instructions and warn ings in the chapter dedicated to its location and operating e Avoid that strange objects clips bolts etc enter inside the equipment n emergency situations damages in both front panel and in input connections or strange objects or liquids inside the equip ment shutdown the equipment immediately disconnect it from mains and call to technical service S T S e Stabilizer can only
27. tart up Shutdown BYPASS OPERATING OPERATING MODES Regulator mode Bypass mode Line Faulty operating modes IMPORTANT NOTES OF ITS OPERATING 6 1 6 2 0 3 5 9 1 0 2 7 6 3 3 6 4 6 5 74 7 2 MAINTENANCE WARRANTY AND SERVICE MAINTENANCE BASIC GUIDE TROUBLESHOOTING AND FREQUENT ASKED QUESTIONS FAQ WARRANTY CONDITIONS Covered product Warranty terms Out of scope of supply DESCRIPTION OF AVAILABLE MAINTENANCE CONTRACTS AND SERVICES TECHNICAL SERVICE NETWORK ANNEXES PARTICULAR TECHNICAL SPECIFICATIONS GENERAL TECHNICAL SPECIFICATIONS SALICRU 3 1 INTRODUCTION 1 1 GRATEFULNESS LETTER We would like to thank you in advance for the trust you have placed in us by purchasing this product Read this instruction manual care fully before starting up the equipment and keep it for any possible future consult that can arise We remain at you entire disposal for any further information or any query you should wish to make Yours sincerely SALICRU O The equipment here described can cause important physical damages due to wrong handling This is why the installa tion maintenance and or fixing of the here described equip ment must be done by our staff or specifically authorised O According to our policy of constant evolution we reserve the right to modify the specifications in part or in whole without forewarning CJ All reproduction or third party c
28. ting diodes in its frontal part which inform us about the status of the equipment 3 3 3 Operating principle The electronic control supervises the output voltage of the stabi lizer continuously providing a correction signal to the step by step motor in case the sensed voltage is wrong Motor moves the au totransformer ARC in order to increase or decrease the voltage by moving the carbon brush to left or right The resulting voltage is applied to the primary winding of Booster transformer which adds in phase or counter phase to mains voltage through its secondary winding this way any fluctuation on mains voltage Is corrected EN SALICRU 9 3 4 OPTIONALS 3 4 1 Maximum minimum output voltage protection Basically it is detector of maximum and minimum voltage which is located at the output of any stabilizer or conditioner either single phase or three phase and it analyses at all times the output voltage of the own equipment If the output voltage is inside the range 7 5 of nominal the equipment supplies voltage and feeds the loads connected to the device In case the output voltage is out from this range the detector breaks the electrical power supply to the loads to feed There are two different standardised versions of protection 3 4 1 1 Manual version M start up Manual rearming As maximum minimum voltage protections are located between the stabilizer and output te
29. ton MODE e Output current This LED lights when the output current has been selected with button MODE If the stabilizer doesn t include this option of current trans formers when selecting this mode the LCD panel will display the value 0 e Frequency This LED lights when the output frequency has been selected with button MODE Output This LED lights when there is voltage at the output High output This LED lights when the output voltage is higher than the allowed limit Low voltage This LED lights when the output voltage is lower than the allowed limit 3 1 2 3 Buttons There are 3 buttons at the front side of the equipment Their func tions are Button MODE It is used to monitor the input output param eters e Buttons 7 They are used to set the preset factory values and to make all calibrations They do not have any use for the end user 3 1 2 4 Dry contacts The stabilizer has two relays that can provide the following informa tion of Output voltage out of range and Mains present fault If a contactor or relay is going to be used with the dry contacts of the stabilizer a snubber has to be fitted at the output of the con tactor or relay which would be based on a resistor of 220Q 2W and capacitor of 470 nf 300V both connected in serial The relays are standard but their outputs are only wired to its port terminal as an option EN SALICRU 3 2 DEFINITION AND
30. utput accuracy are described in the technical specification section 5 1 2 Bypass mode Line Loads can be transferred to Bypass mode by means of turning the switch to position LINE Loads are directly supplied from mains in this mode Bypass mode is usually used to make the maintenance of the sta bilizer 5 1 3 Faulty operating modes 5 1 3 1 Overload When the stabilizer is loaded exceeding its nominal power capacity there is an overload When the equipment is overloaded in regulator mode it still sup plies the load till the output fuse is blown For safety operating do not overload the stabilizer 5 1 3 2 Output short circuit In case of short circuit the stabilizer is a current source and tries to blown the fuse of the short circuited line When doing it the short circuit situation is cancelled and the rest of loads are not affected for this condition otabilizer can only make the described short circuit behaviour if the loads connected to the stabilizer are protected by separate inde pendent fuse protections and if they are sized according their load nominal currents 5 2 IMPORTANT NOTES OF ITS OPERATING Stabilizer is used to protect those equipments sensitive to damages due to a bad quality or fluctuations of the electrical mains The end user from the quality supplied by mains is ready to supply clean and good quality energy to their equipments by means of using the Stabilizer Insid

Download Pdf Manuals

image

Related Search

Related Contents

MultiPac 8500 User`s Manual  Database driven user friendly web application using Ajax  Philips Economy Twister Twisted energy saving bulb 871829121797800  USB RetroPad Adapter v1.1b for XBOX User Manual Rev. 1.0 – 06  A4 Tech. Wireless Optical Zoom Mouse Mouse User Manual  IntelliPack Configuration Software Model 5030-881  3843 Module d`extension pour commande de stores RXC41.1  Mousse de purée de pommes de terre, fleur de sel à la truffe Il y a  Hoover SteamVac User's Manual  