S2000-KPB ver 1.08 User`s Manual
Contents
1. 2 3 Performance Instructions 2 3 1 The power supply being in use shall provide the current high enough to power all executive devices connected to the S2000 KPB module 2 3 2 It is recommended to situate the power supply so that the resistance R of the wire between the power supply and S2000 KPB see following figure meets the condition R lt 0 25 Q in case of 12 V input supplying or R lt 0 34 Q in case of 24 V input supplying The dependence of wire resistance from its length L for various wire cross sections is shown in following table Wire Section mani Wire Resistance Q L 1m L 2m L 4m L 6m L 8m L 10m 0 2 0 0875 0 1750 0 3500 0 5250 0 7000 0 8750 0 5 0 0350 0 0700 0 1400 0 2100 0 2800 0 3500 0 75 0 0233 0 0467 0 0933 0 1400 0 1867 0 2333 1 0 0 0175 0 0350 0 0700 0 1050 0 1400 0 1750 1 5 0 0117 0 0233 0 0467 0 0700 0 0933 0 1167 2 0 0 0088 0 0175 0 0350 0 0525 0 0700 0 0875 2 3 3 The length and section of conducting wires connecting executive devices to the S2000 KPB module shall provide the enough current consumption to comply with the requirements of the executive devices 2 3 3 1 The length of conducting wires for connecting of the automatic extinguishing installation shall agree with the following condition for resistance R see figure above U Ps min R n PR Re min 22 Where Ups is minimal power supply voltage 10 V in case of RIP 12 and 20 V in case
2. 10 2 up to 28 4 V from module s power commuting output current no more than 2A circuit failure monitoring current no more than 1 5 MA 1 2 7 Number of inputs for automatic extinguishing 2 system status monitoring 1 2 8 Overall dimensions 156x107x36 mm 1 2 9 Weight no more than 0 3 kg 1 2 10 The module is provided by electromagnetic noise proof features in order to avoid false output actuation or malfunction 1 2 11 The module construction design provides the ingress protection rating in accordance with IP20 1 2 12 After power on the module has been ready to operate within no more than 3 seconds 1 3 Standard Delivery 1 2000 KPB Executive Module 1 piece 2 This User s Manual lex 3 Woodscrews 1 3x25 016 3 pieces 4 Wallplugs 6x30 3 pieces 5 Diodes 1N5402 1N5406 6 pieces 6 Diodes 1N4002 1N4007 6 pieces 7 DIN 7982 Flat Head Tapping Screw with Cross Drive 2 2x6 5 1 piece 1 4 Performance 1 4 1 The module is designed to operate in such modes as follows OPERATING POWER FAILED DIAGNOSTIC FACTORY TESTING DEVICE FAILED 1 4 2 OPERATING mode 1 4 2 1 The OPERATING mode is indicated by READY LED as follows Module Mode Indicator Behavior OPERATING Lit steady 1 4 2 2 RS 485 connection operability in OPERATING mode is displayed by COMMUNICATION indicator in accordance with the table as follows Communication Status Indic
3. as usually hourly 1 4 11 Messages that cannot be transmitted due to the communication loss are storied within module event buffer storage its capacity being equal to 25 events 2 OPERATIONAL DIRECTIVES 2 1 Safety Precautions 2 1 1 There is no any harmful alive circuit within the S2000 KPB module 2 1 2 Shut off power supply voltage before mounting installation and maintaining of the module 2 1 3 The mounting and maintaining shall be carried out by personnel qualified and trained in safety rules 2 2 Preparation for Use 2 2 1 Change the S2000 KPB module net address which has to identify with no address of any existing device connected to this RS 485 line 2 2 2 Adjust if necessary the rest module s configuration parameters 2 2 3 Mount the module to in the location you want the module can be located on the wall above a suspended ceiling or at other places on premises being protected from atmospheric fallouts mechanical damages and unauthorized access 2 2 4 Assemble the module and connect conducting wires in according with connecting diagram represented in figure on page 8 2 2 4 1 If a single power supply is in use BOTH POWER INPUTS CONTROL parameter is set off it can be connected to any module power input 2 2 4 2 If the S2000 KPB module and net controller are powered separately then couple their 0 V circuits 2 2 5 If the module is not first or last device connected to the RS 485 interface line remove the jumper that i
4. sensor unit contacts 01 1 Contact Type under normal extinguishant condition normally opened 7 Both Power Inputs Defines to control power inputs separately OFF OFF Control Defines the module number in the RS 485 8 Net Address Ts 127 127 line address space 1 4 6 1 The BOTH POWER INPUTS CONTROL parameter being set on the module generates Power Failed and Power Restore messages for each input separately In such a case the Power Failed message is generated after any input having failed but Power Restore message is generated after both input voltages having been returned 1 4 7 To change the configuration parameters connect the 2000 KPB module to a PC by means of interface converter RS 232 RS 485 for example PI GR or 2000 PI or S2000 USB and run uprog exe program of version no less then 4 0 0 871 The last version of the device configuration program uprog exe along with all additional information dealing with S2000 KPB module can be downloaded from the BOLID Company website http www bolid com The S2000 KPB module implements the commands received via RS 485 interface line as follows Output Control To switch the relay in agreement with the given program Configuration Writing Configuration Reading Net Addresses Assigning Time Synchronization Controlled Circuit Status Receiving Output Status Receiving 1 4 9 The module implements the switc
5. 5 WARRANTY 5 1 Manufacturer warrants its 2000 KPB module to be in conformance with specification under normal transportation storage mounting and maintenance 5 2 The average operating life of S2000 KPB module is at least 10 years 5 3 Manufacturer warrants its product to be free from defects in materials and workmanship for 18 months since putting the S2000 KPB into operation but no more then 24 months since production under normal use and service 5 4 Sending off the module to the manufacturer for repairing apply it with the damage certificate describing the defect Send your complaints to the manufacturer at the following address ZAO NVP BOLID 4 Pionerskaya street Korolyov Moscow Region Russia 141070 Tel fax 7 495 513 32 35 7 495 516 93 72 E mail info bolid ru Web site http www bolid com 6 ACCEPTANCE CERTIFICATE S2000 KPB Executive Module Product Designation Serial Number Produced tested by quality control department in compliance with state standards and specifications packed by NVP BOLID Company and qualified as deliverable Q C STAMP Name Date SECURITY SYSTEMS 12 S2000 KPB EXECUTIVE MODULE Pesan CG Version 1 08 T r s Manual SePrnagmeast ISO 9001 User s 5502 ynoo1 1 TECHNICAL DESCRIPTION 1 1 General 1 1 1 The S2000 KPB executive module hereinafter referred to as module is designed to operate as a part of integrated fire safety and security ORION system manufac
6. D mode after power having started up then return it to manufacturer to update the built in microchip software 1 4 5 FACTORY TESTING Mode 1 4 5 1 The module being in FACTORY TESTING mode the READY and COM indicators switches on alternately with 1 Hz frequency 1 4 5 2 If the module has entered to the FACTORY TESTING mode it means that the module is likely to be incompletely tested during production Send it to manufacturer for proper testing 1 4 4 3 If it is impossible to send the module to manufacturer switch it into the OPERATING mode by pressing and holding tamper switch plunger having opened the cover before However after resetting or succeeding power up the module will enter the FACTORY TESTING mode again 1 4 6 DIAGNOSTIC Mode 1 4 6 1 The switching of the module into the DIAGNOSTIC mode and its operation behavior in this mode are described closely in clause 3 2 of this manual 1 4 7 To adjust the module for specific operation some configuration parameters stored in nonvolatile memory should be programmed as follows Parameter Name Function Range Factory Default Value Defines the output control program to be ve started after power up or reset or after 1 Initial Output Status i a 1 2 2 OFF receiving of Initial Output Status Switching command Defines the executive time for each 2 Output Control output in case of programs 3 4 7 and 8 0 255 5 25 Time if this time is not contained within the command
7. ME parameter for output in question 1 4 9 3 2 For executive command with program 11 Automatic extinguishing system discharge the discharge pulse is generated that is the output is switched ON for a given time and then it is switched OFF If the time of executing is not contained within the command or is equal to zero then the output is switched ON for a time defined by OUTPUT CONTROL TIME parameter for output in question 1 4 10 The module transmits via RS 485 interface some messages as follows Relay Trbl Open open failure of a controlled output connected circuit Relay Trbl Short short failure of a controlled output connected circuit Relay Restore recovering of a controlled output connected circuit Fire Trouble malfunction of fire extinguishing equipment Fire Trbl Rst fire extinguishing equipment has been restored Tamper Alarm when the module enclosure has been opened Tamper Restore in case of the module enclosure has been closed Power Failed supply voltage is below the lower threshold Power Restore supply voltage is returned to the normal range If more than 60 seconds has elapsed since any event origin until its transmission that is in case of RS 485 line communication loss then such a message is transmitted with specifying of actual time accordingly to module internal clocks The synchronization of module internal clocks is executed by time synchronization command
8. ance with the following table Power Trouble Indicator Behavior 1 Any input voltage is dropped below the lower threshold the BOTH POWER INPUTS CONTROL parameter being set ON 2 Both inputs voltages are dropped below the lower threshold Slow flashing 0 1 s ON and 1 2 s OFF the BOTH POWER INPUTS CONTROL parameter being set OFF 1 4 3 2 Any input voltage being dropped below 10 V if the BOTH POWER INPUTS CONTROL parameter being set ON or both inputs voltages being dropped below 10 V if the BOTH POWER INPUTS CONTROL parameter being set OFF the module transmits the Power Failed message through RS 485 interface Synchronous with that READY indicator begins to flash slowly 0 1 s ON and 1 2 s OFF Power supply voltage being restored both inputs in case of both controlling being set on or any input in case of both input controlling being set off up to 11 V or more the module transmits Power Restore message via RS 485 interface READY indicator begins to light steady 1 4 3 3 The indicators COM MASS PRES and from 1 to 6 operate in POWER FAILED mode as well as in OPERATING mode see clauses 1 4 2 2 1 4 2 4 1 4 4 DEVICE FAILED Mode 1 4 4 1 The module being in DEVICE FAILED mode all facial indicators flashes 1 6 indicators flashes by yellow 1 4 4 2 The module enters in DEVICE FAILED mode in case of built in microchip memory test having failed If the module entered in DEVICE FAILE
9. ator Behavior 1 RS 485 interaction Lit steady 2 RS 485 connection loss more than 2 minutes Flashes with 0 7 Hz frequency 1 4 2 3 The statuses of control outputs and connected control circuits in OPERATING mode are displayed by means of appropriate 1 6 LED indicating Circuit f Status Output Indicator Behavior Normal ON Lit steady by red OFF OFF ON Red light interrupted by double yellow flashing with 0 7 Hz frequency Open Circuit OFF Double yellow flashing with 0 7 Hz frequency ON Red light interrupted by yellow flashing with 0 7 Hz frequency OFF Yellow flashing with 0 7 Hz frequency Short Circuit The pressing is considered to be long if tamper plunger is put in within at least 1 5 s while it is meant as short if the pressing lasts from 0 1 to 0 5 s The pause between pressings shall be at least 0 1 s and no more than 1 s In case of proper operability the module transmits the Manual Testing message through RS 485 interface line READY indicator flashes with 5 Hz frequency and 1 6 indicators switches on by red for a short time less than 1 s Then these indicators along with COM MASS and PRES switch on singly by yellow for a short time Together with 1 6 indicators turning on the relevant output contacts are closed After shutting down of the PRES indicator all control circuits are switched into full controlled mode allowing verifying all their ope
10. f group command designated to control all module outputs does not contain CONTROL DELAY parameter then the delay between command having been received and first output switching on will be equal to GROUP LAUNCH DELAY parameter The periods between succeeding outputs switching on will be equal to LAUNCH INTERVAL parameter Note If the activating command has been received by short failed output the switching on will not be realized However after repairing of the output circuit the program executing will be continued 1 4 9 2 Output executive commands with 5 6 7 and 8 programs Switch OVER can contain specifying information that defines the rate and pulse ratio of output switching If the command doesn t contain specifying information then the output by default switches OVER with 1 Hz frequency and pulse ratio of 2 1 4 9 3 Output executive commands with 3 4 7 and 8 programs Switch for a given time and 11 Automatic extinguishing system discharge can contain CONTROL TIME parameter Its value can range from 0 to 8192 s 2 hours 16 minutes and 32 s with discrete of 0 125 s 1 4 9 3 1 In case of output executive commands with 3 4 7 and 8 programs such a program is executed for given time and after then switches OFF programs 3 and 7 or ON programs 4 and 8 If time of executing is not contained within the command or is equal to zero then the output is activated in accord with given program for a time defined by OUTPUT CONTROL TI
11. hing ON OFF OVER of outputs in accordance with the executive program assigned by Output Control command received via RS 485 interface Program hg Final Status Number Program description 0 Return the output to the initial status 1 Switch ON until new command has been received 2 Switch OFF until new command has been received 3 Switch ON for a given time then switch OFF OFF 4 Switch OFF for a given time then switch ON ON 5 6 Switch OVER until new command has been received J Switch OVER for a given time then switch OFF OFF 8 Switch OVER for a given time then switch ON ON 11 Automatic extinguishing system discharge OFF 1 4 9 1 Output executive commands can comprise CONTROL DELAY parameter In such a case the program starts after specified time period having been expired CONTROL DELAY parameter can be ranged from 0 to 8192 s 2 hours 16 minutes and 32 s with 0 125 s discrete 1 4 9 1 1 For output executive commands with programs from 1 to 8 the last executive program retains in progress during the delay and when the control delay has been expired the program of the received command is starting If there is no CONTROL DELAY in the command or it is zero then the relay starts to execute the program just after command having been received 1 4 9 1 2 For executive command with program 11 Automatic extinguishing system discharge the output is switched off during control delay I
12. of RIP 24 Iis the required actuating current A R is the wire resistance between power supply and S2000 KPB see clause 2 3 2 Q R is the minimal fusehead resistance Q f min The dependence of wire resistance from its length L for various wire cross sections is shown in table mentioned above 2000 KPB Pressure Detector Mass Detector To the power supply 1 12V 24V OV To the power supply 2 12V 24V OV To S2000 M console 2000 ASPT or ARM ORION PC RS 485 V amp Lamp D Siren Lock XT2 1 Umain OV XT2 2 Uback OV XT2 5 RS 485A RS 485B Note You can connect any executive devices as needed in no particular order VD 1N4002 1N4005 VD 1N5402 1N5406 T E A g Table Extension Parameter Name Function Range Factory Default Value ae Defines the conditions of circuit 4 monitoring for open and 3 Circuit Control Type 1 4 f monitored by module short failures Defines the duration of program 11 4 Group Launch Delay control delay if it is not contained in the 0 255 s Os command Defines the time period between adjacent 5 Launch Interval output starting pulse generation for 0 255s 5s program 11 6 Mass Pressure Sensor Defines the status of
13. or short failure 4 The circuit is monitored for open and short failure 1 4 2 3 3 A circuit short or open failure if been monitored having been detected the module transmits the Relay Trbl Short or Relay Trbl Open message through RS 485 interface After returning to a normal status the module transmits Relay Restore message via RS 485 1 4 2 4 Statuses of circuits connected to the M and P terminals are displayed in OPERATING mode by means of MASS and PRES indicators correspondently Sensor Contacts Are Circuit Is Indicator Behavior Closed OFF Normally closed ose 7 Opened Flashes with 0 7 Hz frequency 0 d OFF Normally opened acta Closed Flashes with 0 7 Hz frequency 1 4 2 4 1 Normally closed sensor circuit connected to the P or M outputs being opened as well as normally opened sensor circuit being closed the executive module transmits the Fire Trouble 1 or Fire Trouble 2 messages correspondently through the RS 485 interface line Normally opened sensor circuit connected to the P or M outputs being opened as well as normally closed sensor circuit being closed the executive module transmits the Fire Trbl Rst 1 or Fire Trbl Rst 2 messages correspondently through the RS 485 interface line 1 4 3 2000 KPB Module Operating in POWER FAILED Mode 1 4 3 1 The S2000 KPB module POWER FAILED mode is displayed by READY indicator in accord
14. rational conditions At this step 1 6 indicators behavior shall agree with table of the clause 1 4 2 3 of this manual To exit TESTING mode press and hold the tamper switch 3 2 4 How to verify the communication conditions via RS 485 a Connect the RS 485 interface line to the net controller 6 Power up the module and the executive devices READY and COM indicators are to begin steady lighting within 3 s B Within 1 minute after power up the net controller is to display the message about S2000 KPB detecting Connected and about restarting of the device with S2000 KPB net address Device Restart If several messages are received from S2000 KPB module due to the accumulation at the module buffer scroll them by means of A and Y console keys Notes 1 Do shut off the module power supply before connecting and disconnecting wires 2 Take into account the module to be ready for operating within no more than 3 s after power switching up 4 OVERALL AND MOUNTING DIMENSIONS 124 Reavy O 10 20 30 40 s0 107 e0 L S2000 KPB Snap on clip for DIN rail mounting Press here and pull to open DIN 7982 flat head tapping screw 11 2 3 4 If the circuit being connected to the output is monitored only for short failure control circuit of type 3 then the diode VD1 is not brought in the circuit 2 3 5 If the circuit being connected to the output is monitored only for open failure control circui
15. s End Of Line terminator situated near the RS 485A and RS 485B terminals
16. t of type 2 then the diode VD2 is not brought in the circuit 2 3 6 If the circuit being connected to the output is not monitored neither for open nor short failure control circuit of type 1 then the diodes VD1 and VD2 are not brought in the circuit 2 3 7 If the executive device being connected includes the diode in series with it then the external diode needs not be brought in the circuit 2 3 8 The statuses of outputs from 1 to 6 and of their connected circuits are to be monitored by means of LED indicators 1 6 2 3 9 The M u P inputs statuses are to be monitored by means of MASS and PRES indicators correspondently 3 MAINTENANCE 3 1 General Scheduled preventive maintenance of the S2000 KPB module has to be conducted annually by service employee Such maintenance includes procedures as follows walk around inspection functional test in accordance with clause 3 2 2 of this manual module attachment security inspection interconnecting wiring and contact connection integrity checking 3 2 Functional Test 3 2 1 On Receipt Inspection a check the package and unpack the module 6 check the delivery set and replacement components in accordance with clause 1 3 of this manual B ensure the enclosure integrity r shake up the module and verify any debris to be absent within it 2 check the attachment of the terminal blocks x ensure the module serial number and date of manufacturing to be consistent with those subjec
17. t to this document 3 2 2 Functional Testing a Switch on the module power READY indicator has to begin to light steady within 3 seconds 6 COM indicator has to begin flashing after a 2 minutes with 1 Hz frequency in case of RS 485 line disconnected from net controller B measure the consumed current its value has not to exceed 200 mA 3 2 3 Testing in DIAGNOSTIC Mode DIAGNOSTIC mode is designed to inspect the built in indicators and relay operation Caution The module being diagnosed all control circuit have to be disconnected from the module outputs To switch the module into DIAGNOSTIC mode remove its lid and make short short short long pressing of tamper switch plunger 10 1 4 2 3 1 The controlled circuit statuses are evaluated depending on negative relative to 0 V output terminal voltage as follows Normal status corresponds to any voltage from 0 26 V to 4 1 V Open circuit status corresponds to any voltage more than 4 2 V under de energized output condition and less than 0 05 V under switch on output one Short circuit status corresponds to a voltage less than 0 25 V in case of switched off output and more than 4 5 V in case of switched on output 1 4 2 3 2 Monitored statuses of control circuits depend on its types accordingly with the following table Circuit Type Monitored Statuses 1 The circuit status is not monitored 2 The circuit is monitored for open failure 3 The circuit is monitored f
18. tured by BOLID Company under control of 2000 ASPT panel or C2000 ver 1 12 C2000M console or PC supplied by any version of ARM Orion 2000 KPB module is used to implement fire alarm and extinguishing access control and video surveillance functions 1 1 2 The S2000 KPB module is designed to control lamps sirens video cameras electromagnetic locks and automatic systems for gas powder or aerosol fire fighting 1 1 3 The module has to be located within protected premises near the driven devices The module is designed for round the clock operation 1 1 4 The module is not meant for use in corrosion or dust ambient conditions or in explosive premises 1 1 5 The module is designed to operate under following ambient conditions operating temperatures from 30 C to 50 C relative humidity up to 98 for 25 C non condensing vibration load from 1 to 35 Hz with maximum acceleration of 0 5 g 1 2 Specifications 1 2 1 Power supply external d c from 10 2 V up to 28 4 V RIP 12 RIP 24 1 2 2 Number of power inputs p 1 2 3 Power Consumption max 3 W 1 2 4 Current Consumption without regard to 130 mA under 12 V power supplying executive devices no more than 70 mA under 24 V power supplying 1 2 5 Current Consumption in OPERATING mode 45 mA under 12 V power supplying with all outputs being switched OFF no more than 25 mA under 24 V power supplying 1 2 6 Number of outputs 6 commuting voltage from