AN-X-MOD-MAS User Manual - Quest Technical Solutions
Contents
1. Comm Format N one Y Slot f 6 Chassis Size f 7 Revision fi fi a Electronic Keying Disable Keying Status Offline E 5 Cancel Apply Set the Slot to 16 Set the chassis size to 17 Set the Comm Format to None Set the IP address to match the AN X module Set Electronic Keying to Disable Keying Record the Name as you will use it if you create tags to access the data 2 Add Generic modules for each required connection January 2008 E Module Properties General Connection Module Info Backplane 1756 MODULE Generic 1756 Module AnsMod Anus lotO Description Comm Format input Data INT v Type Parent Name AN X MOD MAS Page 35 AnxMod 0 1756 MODULE 1 1 m Connection Parameters Assembly ee Input Output Configuration Status Input Size 250 16 bit jo ew Slot 0 oa al Status Output Apply Help Status Offline Set the parameters as shown Set the Slot to 0 for the first connection 1 for the second connection and so on 3 Set the RPI for each connection to match the RPI of the exclusive owner connection E Module Properties AnxMod 0 1756 MODULE 1 1 General Connection Module Info Backplane Requested Packet Interval RPI 10 04 ms Inhibit Module 0 2 750 0 ms I Major Fault On Controller If Connection Fails While in Run Mode r Module Fault amp pp ly
2. RxCre Received frames with a CRC error RxOvr Received frames too long RxAbort Received frames with an abort error RxShort Received frames too short RxErrMask Error mask for protocol errors To map the diagnostic counters include a line with the keyword DiagCtrs in the input section of a connection This maps all ten diagnostic counters they cannot be mapped individually Examples DiagCitrs 10 DiagCtrs offset 10 January 2008 TIP AN X MOD MAS Page 29 Drop Error Table The drop error table consists of 2 16 bit words one bit per drop Bit 0 of the first word corresponds to drop 1 bit 1 corresponds to drop 2 and so on If a configured drop is in error the bit is 1 If a configured drop is responding correctly the bit is 0 The bit is 0 for an unconfigured drop To map the drop error table include a line with the keyword DropErr Examples DropErr 10 DropErr offset 10 Map the drop error table to the first two words of input data of each connection If the connection to the AN X module is lost the ControlLogix sets the first 2 words of the connection to FFFF hexadecimal If your program is monitoring the drop error table it will see the error bit as set Module Health Bits Each Modicon drop returns 5 words of module health data Each word corresponds to a rack the first word corresponds to rack 1 the second corresponds to rack 2 and so on Bits in the word correspond to
3. Configuration File Format Viewing the Current Configuration Saving the Current Configuration Supported Modicon Modules EXCHANGING SCHEDULED DATA WITH A CONTROLLOGIX Mapping I O Data 20 21 23 23 23 24 24 Page 4 AN X MOD MAS Other Mappable Data Viewing the Current Configuration Saving the Current Configuration Configuring the AN X Module in RSLogix 5000 Input Only Connections ControlLogix Tags Using the ControlLogix Log Redundancy ControlLogix Ethernet Configuration File Aliases Criteria for Switching between AN X Modules Switchover Other factors to consider LEDs USING ANXINIT Anxlnit Log Locating Available AN X Modules Selecting an AN X Set AN X IP Configuration Restart an AN X AN X Info Read Kernel Parameters Run Config Mode Update AN X Flash Update Firmware Firmware Update Wizard Update Firmware Command Patch Firmware USING THE WEB INTERFACE 27 31 31 31 33 36 43 44 45 46 47 47 48 48 49 49 49 53 53 55 January 2008 908 I O Network Configure ControlLogix Support View Configuration Files View Active Configuration Log Files System Error Log System Info Log ControlLogix Log View All Logs Administration Menu Browse File System AN X IP Configuration Archive Configuration TROUBLESHOOTING LEDs Ethernet LEDs SYS LED NET LED Network Status UPDATING THE FIRMWARE Reading Version Numbers Obtaining the Latest Software SPECIFICATION
4. Drop 7 End the drop definition with a line with just the keyword EndDrop Between the Drop and EndDrop lines enter the rack and slot definitions for the drop Begin a rack definition with a line that consists of the keyword Rack followed by an equals sign and then the rack number from 1 to 5 There should be no spaces before or after the equals sign Example Rack 1 After the rack definition enter the slot definitions They consist of the keyword Slot followed by an equals sign and the slot number a comma then the keyword Type an equals sign and the module type There should be no spaces before or after the equals signs Examples Slot 4 Type B804 Slot 7 Type ACI_030_00 For rack 1 the rack definition line can be omitted It is required for racks 2 to 5 If there is no explicit Rack definition entry AN X assumes the following slot definitions are for rack 1 There is no EndRack command If there is more than one rack in a drop just start the new rack with a Rack definition Quantum Parameter Data Some Quantum modules have additional parameters to define configurable properties of the module January 2008 Page 22 AN X MOD MAS You can send this parameter data by adding a line after the slot definition that contains the length of the parameter data in words and the parameter data itself Example Slot 6 Type ACO_020_00 CfgLen 6 0x8001 0x5555 0x0000 0x0000 0x0000 0x0000 The leading Ox indicates a hexadec
5. To import the tags into RSLogix 5000 you must be offline Select Tools Import Tags and import the tag file Tag Format AN X builds the tags from the ControlLogix configuration Each tag is a ControlLogix alias For example ALIAS MOD_d05s4_Out B804 AnxMod 0 0 Data 0 In this example the tag name is MOD_d05s4_Out The name is made up of the ClxPrefix and the tagname from the configuration file If there is more that one word of data for the module AN X appends an underscore and a number to the tagname for example ALIAS MOD_d05r4s4_Inp_0 B863 AnxMod 0 1 Data 8 ALIAS MOD_d05r4s4_Inp_1 B863 AnxMod 0 1 Data 9 ALIAS MOD_d05r4s4_Inp_2 B863 AnxMod 0 1 Data 10 ALIAS MOD_d05r4s4_Inp_3 B863 AnxMod 0 1 Data 11 The address is AnxMod 0 0 Data 0 The address is made up of the ClxName and the data location January 2008 Page 38 AN X MOD MAS Using the ControlLogix Log If there are problems with scheduled connections to the AN X use the ControlLogix log to identify the cause From the web interface select Log Files ControlLogix Log to display the log Look for error messages that describe in detail the cause of any problem with the current configuration January 2008 AN X MOD MAS Page 39 Redundancy Version 2 2 1 and above of the firmware for the AN X MOD MAS includes features to make it easy to enable and disable AN X I O scanners It can be used to implement red
6. Connection Status Connected Duration 01 57 12 Speed 100 0 Mbps Activity m Sent Pa Received Packets 956 885 Disable Click the Properties button Double click on Internet Protocol TCP IP Internet Protocol TCP IP Properties General You can get IP settings assigned automatically if your network supports this capability Otherwise you need to ask your network administrator for the appropriate IP settings Obtain an IP address automatically IP address 192 168 O 10 Subnet mask 255 25 25 0 Default gateway 192 168 0 1 C Obtain DNS server address automatically Use the following DNS server addresses Preferred DNS server Alternate DNS server Advanced Cancel January 2008 Page 14 AN X MOD MAS In this example we will assign the computer an IP address of 192 168 0 10 Set the Subnet mask to 255 255 255 0 standard mask for the Class C network address of 192 168 0 x Set the Default gateway to 192 168 0 1 this address does not exist on the Ethernet network but AN X requires a valid default gateway entry Click OK to accept the settings Connect the computer to AN X using the crossover cable If this is the first time you have used the AN X module it will look for a DHCP server on the network It waits about three minutes then reverts to a default IP address of 192 168 0 41 Power up the AN X a
7. orange when monitoring and red when there has been an error or during switchover January 2008 Anxinit Log AN X MOD MAS Page 43 Using AnxInit AnxInit is a 32 bit Windows application supplied with AN X to perform the following functions e Locate and identify AN X modules on the Ethernet network e Select a specific AN X for configuration e Set the IP address and other network parameters for an AN X e Restart an AN X in production mode e Display information about the selected AN X e Read the kernel parameters for the selected AN X e Update the flash low level firmware on the selected AN X Update the firmware on the selected AN X e Patch the firmware on the selected AN X In addition it can be used to e clear the AnxInit log copy the contents of the log to the clipboard for use by another application This is often useful for technical support AnxInit logs messages in its main window These messages are often useful for determining the cause of errors or for technical support To clear the log select Edit ClearLog To copy the contents of the Log to the Windows clipboard so that they can be pasted into another application select Edit Copy January 2008 Page 44 AN X MOD MAS A EE Area Connection 0x2 00 0c 1a 00 00 09 192 168 0 9 Anximit a ici x Eg AN X Log Locating Available AN X Modules To locate all accessible AN X modules on the Ethernet network select Utilities Locate All AN X M
8. Auto configure S908 network and ControlLogix configuration Otherwise check Auto configure S908 network the default Click the Auto configure Network button AN X sends messages to all possible drops and builds a configuration based on the replies it receives AN X then displays the configuration it generated Example Drop 4 Rack 1 slot 1 Type CPS_114_xx Addr d4s1 Inp 00 Out 00 AC PS 115 230V 10A slot 2 Type CRA_93x_00 Addr d4s2 lnp 00 Out 00 RIO DROP S908 slot 3 Tyoe DDI_353_00 Addr d4s3 Inp 04 Out 00 DC IN 24V 4x8 Slot 4 Type DDO_353_00 Addr d4s4 Inp 00 Out 04 DC OUT 24V 4x8 January 2008 Page 20 AN X MOD MAS Manual Configuration 0fgLen 2 0x0000 0x0000 olot 5 Type ACI_030_00 Addr d4s5 Inp 18 Out 00 AN IN 8CH UNIPOLAR ysCtgLen 1 0Ox0001 slot 6 Type ACO_020_00 Addr d4s6 Inp 00 Out 08 AN OUT 4CH CURR 0fgLen 6 0x8001 0x5555 0x0000 0x0000 0x0000 0x0000 EndDrop Drop 5 Rack 1 Slot 2 Type B810 Addr d5s2 Inp 00 Out 01 8 OUT ISO B810 olot 3 Type B804 Addr d5s3 Inp 00 Out 02 16 OUT B804 Slot 4 Type B863 Addr d5s4 Inp 08 Out 00 REG 4 CH IN B863 EndDrop When AN X creates a configuration file it includes comments in the file it creates based on the information in its module database If you edit the automatically generated configuration file edit the comments as well See page 23 for information on how to upload the configuration from AN X and save it t
9. MAS When you turn on the RedundCtl bit for an AN X MOD MAS module it waits for 10 ms of silence on the network before it starts scanning as master WARNING If the RedundCtl bits on both AN X modules are on only one will act as master However if the bits are set on both AN X modules and the current master is disconnected from the S908 network even for a very short period the backup will take over When the module that was disconnected comes online both modules will be master on the S908 network YOUR APPLICATION MUST ENSURE THAT THE RedundCtl BITS ARE BOTH ON ONLY DURING SWITCHOVER Other factors to consider LEDs Do not use the ScanModProg parameter if you are using redundancy Do not set the RedundCtl bits on both primary and backup AN X modules at the same time except during switchover When you modify the ControlLogix configuration file and add elements the mapped data may become larger than the maximum for a connection especially for large I O networks or for networks with many analog modules It may be necessary to change some of the mappings Also when you add elements the offsets in the comments generated by the autoconfiguration will no longer be correct Make sure the mappings in the ControlLogix configurations in both AN X modules are the same Each AN X module cannot check the configuration in the other AN X module When the AN X MOD MAS is used in redundant mode the network LED is green when scanning
10. RSLogix 36 5000 8 Import the tags into RSLogix 5000 37 9 Use the tags to access data January 2008 AN X MOD MAS Page 7 Ethernet Configuration The AN X MOD MAS module connects a computer or other device such as a ControlLogix processor on Ethernet to an S908 remote I O network Before you can use the AN X MOD MAS you must configure its network properties on Ethernet Ethernet Configuration AN X can be configured to use a static unchanging IP address or it can be configured to obtain its IP address from a DHCP server Unless you have control of the DHCP server in most applications you will want to configure AN X to use a static IP address Otherwise the DHCP server may assign a different IP address each time AN X powers up and any software that accesses the AN X module would have to be reconfigured AN X is shipped with DHCP enabled If it finds a DHCP server on the network the DHCP server assigns it an IP address You can use the utility AnxInit to find the IP address that the DHCP server has assigned Select Utilities Locate All AN X Modules and AnxInit will locate the AN X and display its IP address I Local Area Connection 2 0x2 00 Oc 1a 00 01 0d 192 168 0 105 Anxinit DBR Configuration Utilities Edit View Help x we Found 1 AN X device s O000010d Ethernet MAC 00 0c 18 00 01 0d 192 168 0 105 AnxzMod For Help press F1 January 2008 Page 8 AN X MOD MAS IMPORTANT IMPORT
11. at the filename dialog the AN X has already been reset and is in configuration mode Use the Utilities Restart AN X command to restart it in production mode Click the Next gt gt button and select the firmware file you want to download and click Open Look in E anxdesnet gt ae a anxamxdes v1 4 3 bin a anxamxdes 1 4 4 bin File name anxamxdes v1 4 4 bin Files of type fats Firmware File bin Cancel T Open as read only y h AnxInit transfers the firmware file and restarts the AN X After you run update the firmware you must reconfigure the AN X The Utilities Patch Firmware command applies small patches to the firmware running on the AN X These patch files files have extension pch January 2008 Page 54 AN X MOD MAS Ee eX Look in a downloads x e E a anxdes 1 00 0002 pch a anxdes v1 01 0006 pch a AnxDesEnetIp_ anxdes v1 00 0004 pch a anxdcs webupdate pch a AnxDcsEnetIp_ a anxdcs v1 00 0006 pch AnxDcsEnetIp_1 1 18 pch 4nxDcsEnetIp_ anxdes v1 00 0007 pch AnxDesEnetIp_1 1 19 pch a nxDcsEnetIp_ anxdes v1 00 0008 pch a 4nxDcsEnetIp_1 1 20 pch 4nxDcsEnetIp_ a anxdcs v1 00 0009 pch nxDcsEnetIp_1 1 21 pch a 4nxDcsEnetIp_ gt File name AnxDcsEnetlp_1 1 48 pch Files of type Jars Firmware Patch File pch x Cancel J Open as read only 4 This command resets the AN X You will r
12. it tagname tag1 27 d4r2s4 tag1 Example To map the Modicon module at address drop 14 rack 1 slot 3 to the next available ControlLogix location and assign it tagname tag2 d14r1s3 tag2 or since the rack number is 1 you can also use d14s3 tag2 January 2008 WARNING Other Mappable Data AN X MOD MAS Page 27 Example Configuration File ClxName ANX ClxPrefix MOD_ ClxSlot 0 DataOutput d4s4 Drop4Slot4Outputs Datalnput d4s7 Drop4Slot7 Inputs Program Mode Behaviour The ControlLogix processor that is the exclusive owner of the connection in slot 0 controls how the AN X MOD MAS module scans the S908 network For that reason when you map the data you must always include a connection to the generic module in slot 0 When the ControlLogix processor with the exclusive owner connection to slot 0 on the AN X is in program mode or the connection is stopped the AN X stops scanning the S908 network just as a Modicon scanner would Even if other ControlLogix processors have exclusive owner connections to other slots on the AN X and are in run mode AN X does not scan the network You can override this behaviour by including a line with the keyword ScanModProg in the configuration file This causes the AN X MOD MAS module to continue to communicate with the S908 network when the ControlLogix processor is in program mode Similarly ControlLogix processors with exclusive owner connections to other AN X slots
13. sending messages to the AN module using the MAC address and IP address you entered previously These messages tell the AN module to enter into Config state in preparation for updating the firmware If the AN module enters Config mode successfully the Nest button below will be enabled so you can move on to the next step If the AN module has been powered ON for more than 60 seconds and the Next button is still disabled press the Back button confirm the MAC and IP addresses and check the Ethernet cabling Next gt gt If the AN X does not enter config mode within about 60 seconds return to the previous screens and check the entries Click the Next gt gt button and select the firmware file you want to download and click Open Look in 5 andes o c E a anxamxdes v1 4 3 bin anxamxdes w1 4 4 bin File name anxamsdes v1 4 4 bin Files of type fats Firmware File bin Cancel Tl Open as read only Z h AnxInit transfers the firmware file and restarts the AN X After you run update the firmware you must reconfigure the AN X January 2008 AN X MOD MAS Page 53 Update Firmware Command Patch Firmware The Utilities Update Firmware command updates all the firmware on an AN X you have previously selected using the Utilities Select An AN X command This command resets the AN X You will receive a warning and be given the opportunity to Cancel the command If you cancel
14. that connection that refer to the Modicon module drop rack and slot where the data is to be found When you create a mapping for a module all the input or output data for the module is mapped you cannot map individual registers AN X can automatically create a default mapping file when you autoconfigure I O See page 18 for details Anything after a semicolon on a line is treated as a comment ClxName The first line in the file identifies the AN X module AN X uses this name in the ControlLogix tags it creates for the Modicon data The ClxName definition consists of a line with the keyword ClxName followed by a comma and the name you gave the emulated ENBT see page 31 Example ClxName AnxMod When AN X automatically creates a configuration file it uses the Ethernet host name as the default ClxName ClxPrefix The ClxPrefix is used in the tagnames AN X creates for import into RSLogix 5000 AN X prefixes each tagname with the ClxPrefix The ClxPrefix can be used to distinguish tags for the same Modicon address when the ControlLogix processor has connections to more than one AN X MOD MAS For example if the ControlLogix has connections to two AN X MOD MAS modules each controlling a different Modicon network each network could have a module with the same drop and slot address Using a different ClxPrefix in the configuration file for each AN X MOD MAS makes the tags for the two modules distinct The ClxPref
15. the command Configuration Firmware Update or Utilities Update Firmware in AnxInit Refer to page 49 for details Occasionally individual patch files are released They have extension pch and are downloaded using the Utilities Patch Firmware command in AnxInit Refer to page 53 for details Reading Version Numbers To read the version numbers of the various software components Boot code AnxInit AN X Info Configuration kernel AnxInit AN X Info Production kernel AnxInit AN X Info Firmware AnxInit AN X Info version depends on current mode boot configuration or production Individual applications Web interface System Info Log Obtaining the Latest Software Version numbers and software for the most recent AN X releases are available from the QTS website www qtsusa com January 2008 Page 66 AN X MOD MAS Specifications Parameter Specification Function Bridge between Ethernet and Modicon S908 remote I O network Description Processor 100MHz IDT MIPS FLASH memory 64M RAM 64M Typical Power Consumption 200 mA 12 VDC or 100 mA 24 VDC Maximum Power dissipation 2 4W Environmental Conditions Operational Temperature Storage Temperature 0 50 32 122F 40 to 85 40 to 185F Relative Humidity 5 95 without condensation AN X MOD MAS is referenced in the Rockwell Automation Encompass Americas program Rockwel
16. your local computer v Log Files AN X MOD MAS ControlLogix Configuration File Administration AN X MOD MAS Ethernet IP Tagname Files The AN X MOD MAS device create eral tagname files from the device s active configuration These files are intended to be used with ControlLogix programmin ware and or other Ethemet IP clients A link to these files is provided below Left clicking a link will display the AN X MOD MAS configuration file using the application that your web browser ciates with csy files Microsoft Excel a text editor etc Right click the links below t e the target to your local computer gt AN X MOD MAS Ethernet iP ControlLogix Exclusiv Click on the links to view the files using the application that is associated with CSV files Right click on the links to retrieve the files from AN X and store them on your computer View Active Configuration Select View Active Configuration to view the S908 remote I O or ControlLogix configuration file in the web browser January 2008 AN X MOD MAS Page 59 AN X MOD MAS Active Configuration Log e EthernetIP AN X MOD NAS I O Network Config File home axctr1 ModRioCfg csv 21 d05s1 ACO 020_00 40001 23 d05s2 DDO_353_00 1 Drop 5 O 12 I 0 MS 2 Parse Successful Click the Modicon S908 network link to view the current I O network configuration Click the Ethernet IP link to view the current ControlLogix scheduled data c
17. AN X MOD MAS Modicon 908 Remote I O Communication Module User Manual 10 109 Fha Network Quest Technical Solutions 4110 Mourning Dove Court Melbourne FL 32934 321 757 8483 www qtsusa com Page 2 AN X MOD MAS Throughout this manual we use notes to make you aware of safety considerations Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss These warnings help to WARNING e identify a hazard e avoid the hazard recognize the consequences Identifies information that is especially important for successful oe application and understanding of the product Identifies information that explains the best way to use the a AN X MOD MAS Microsoft is a registered trademark of Microsoft Corporation Windows Windows 95 Windows NT Windows 2000 and Windows XP are trademarks of Microsoft Corporation ControlLogix RSLinx and RSLogix 5000 are trademarks of the Allen Bradley Company Inc January 2008 AN X MOD MAS MODULE OVERVIEW Hardware Features Package Contents Modes of Operation INSTALLATION Prevent Electrostatic Discharge Power 908 Cabling and Termination Ethernet Cabling Software Installation QUICK START ETHERNET CONFIGURATION Ethernet Configuration Example Standalone Computer Reconfiguring an AN X from an Unknown State S908 NETWORK CONFIGURATION Autoconfiguration Manual Configuration
18. ANT IMPORTANT If AN X does not find a DHCP server within about three minutes of starting up it reverts to a temporary static IP address of 192 168 0 41 If AN X is using this temporary IP address it repeatedly flashes the SYS LED red three times followed by a pause If your computer is on the same subnet you can use the web interface to change the IP address Use this temporary IP address only for initial setup of AN X AN X will not function for its intended purpose at the temporary IP address If you are using multiple AN X modules configure them one at a time especially if there is no DHCP server on the network since they will all revert to the same temporary IP address when they fail to find a DHCP server If you are connecting AN X to an existing Ethernet network consult the network administrator to obtain a static IP address for AN X and to obtain information about how you should configure AN X The AN X must be on the local Ethernet same subnet as your computer when you set its IP address You configure the Ethernet properties using the Windows utility AnxInit supplied with AN X or the AN X web interface Use the Configuration AN X IP Settings command to start the AN X IP configuration wizard which takes you step by step through the IP configuration process Step 1 In step 1 you identify the AN X you are configuring January 2008 AN X MOD MAS Page 9 Step 1 AN X Selection Select this computer s Etherne
19. Cancel Status Offline January 2008 Page 36 AN X MOD MAS ControlLogix Tags AN X uses the Ethernet IP configuration to create tags that can be imported into RSLogix 5000 Use these tags in your RSLogix 5000 program to access the data on the AN X Even if the ControlLogix address for a Modicon address changes all you have to do is re import the tags If you change the Modicon or ControlLogix configuration re import tags so that the ControlLogix processor is using the correct addresses WARNING There are two sets of tag files one for the exclusive owner connection and one for the input only connection In the web interface select Automation Network View Configuration Files To view the files click either AN X MOD Ethernet IP ControlLogix Exclusive Owner Data Tags or AN X MOD Ethernet IP ControlLogix Input Only Data Tags To save the file to your computer right click on the link and select Save Target As January 2008 AN X MOD MAS Page 37 A QTS AN X MOD web interface v1 1 5 Microsoft Internet Explorer i File Edit Yiew Favorites Tools Help Os x a DO search she Favorites media o2 a W3 Address http 10 10 0 73 v GD Search Web gt Search ste EO Brae blocked Fa Options T A AN X MOD Modicon S908 RIO Configuration Viewing Modicon 8908 RIO Configuration Viewing Instructions anual X MOD Ethernet IP Tagname Files Importing Tags in RSLogix 5000
20. Comm Format Data INT sd aeaa Slot 0 ai Status Output Status Offline E Cancel Set the parameters as shown Set the Slot to 0 for the first connection 1 for the second connection and so on 3 Set the RPI for each connection January 2008 AN X MOD MAS Page 33 E Module Properties AnxMod 0 1756 MODULE 1 1 General Connection Module Info Backplane Requested Packet Interval RPI 100 ms 0 2 750 0 ms F Inhibit Module I Major Fault On Controller If Connection Fails while in Run Mode Module Fault Status Offline i j Cancel Help Input Only Connections The AN X MOD MAS supports one input only connection from a ControlLogix processor The ControlLogix will be able to read the same input data as the ControlLogix processor with the exclusive owner connection to the AN X MOD MAS To configure the input only connection to the AN X MOD MAS in RSLogix 5000 1 Right click on the ControlLogix Ethernet module that will be communicating with the AN X and select Add Module Add a 1756 ENBT A module Set the Major Rev to 1 January 2008 Page 34 AN X MOD MAS E Module Properties ENBT 16 1756 ENBT A 1 1 General Connection Module Info Port Configuration Port Diagnostics Backplane Type 1756 ENBT 4 1756 10 100 Mbps Ethernet Bridge Twisted Pair Media Vendor Allen Bradley Parent ENBT ten nma Address Host Name Description PAddress 192 168 0 105 C Host Name
21. Ctl Must be mapped to the output data for the connection to slot 0 ScanSts Scan status can be mapped to the input data for any connection LongInput Forces 800 series drops to send inputs on every scan January 2008 Page 40 AN X MOD MAS Parameter Description DataOutput In some redundant applications the array names arrayname can be used to creates aliases for the internal Datalnput ControlLogix arrays used for the data for the connection arraynamename RedundEna Include a line with the RedundEna parameter followed by a comma and a unique name for the AN X at the start of the ControlLogix configuration file The AN X uses the RedundPrefix when it generates aliases for elements that are unique to each AN X module such as diagnostics RedundCtl Map RedundCtl to the output data for the connection to slot 0 in the AN X RedundCtl consists of a single 16 bit word Only bit 0 is used To set an AN X to act as the scanner set bit 0 to 1 To set an AN X to act as a backup set bit 0 to 0 If the configuration file contains RedundEna you must map RedundCtl ScanSts ScanSts is an array of 5 INTs that contain information about the current operation Only the first 3 are used Offset Description 0 Scan state 0O idle 1 monitor 2 scanning 3 scan halted 1 Scan counter increments at the start of each scan 2 Init counter increments whenever a drop is reinitializ
22. Favorites Tools Help Heak gt Q A A Bsearch Favorites media lt 4 B Sp Sf Address http 192 168 0 gt Pao Links Google GPsearch web seachst g E1743 blocked feuloptions v Automation Network 5908 1 0 Network Configuration Configure ControlLogix Support View Configuration Files View Active Configuration y Log Files b Administration Home Page AN X MOD MAS ControlLogix Configuration Internet Type or browse the configuration file name into the Select file area Then click the Send To AN X button to send the file to AN X January 2008 Page 58 AN X MOD MAS Check the ControlLogix Log to determine if there have been any errors with the upload View Configuration Files Select View Configuration Files to view the S908 and ControlLogix configuration files face v1 1 12 Microsoft Internet Explorer 0A avortes meda Br A A E http 7 192 168 0 97 AN X MOD MAS Modicon 908 RIO Configuration Viewing Modicon 908 RIO Configuration Viewing Instructions The AN X MOD MAS device is configured using a csv file see user s manual for details A link to this file is provided below clicking this link displays the AN X MOD MAS configuration file using the application that your web browser associates with csv files Microsoft Excel a text editor etc Right click the links below to save the target to
23. Minimum time for last 100 O gt T updates 2 Maximum time for last 100 O gt T updates 3 Maximum O gt T time since connection opened 4 Reserved 5 Average time for last 100 T gt O updates 6 Minimum time for last 100 T gt O updates 7 Maximum time for last 100 T gt O updates 8 Maximum T gt 0 time since connection opened 9 Reserved The units for the times are 0 1 milliseconds A value of 87 means 8 7 ms To map the statistics for a given connection include a line with the keyword ConnStatsn where n is the connection number from 0 to 15 in the input section of a connection Examples ConnStats2 40 ConnStats2_ offset 40 January 2008 AN X MOD MAS Page 31 Viewing the Current Configuration To view the ControlLogix configuration currently stored in the AN X start the web interface and select View Active Configuration Click the Ethernet IP link to view the current ControlLogix scheduled data configuration The configuration will be displayed using whatever application is associated with csv files on your computer usually a spreadsheet or text editor Saving the Current Configuration To save the ControlLogix configuration currently stored in the AN X to a file start the web interface and Select View Active Configuration Right click the Ethernet IP link and select Save target to save the current ControlLogix scheduled data configuration to a file Configuring the AN X Module in RSLogix 5000 To con
24. S SUPPORT 56 57 58 65 65 66 67 AN X MOD MAS Module Overview The AN X MOD MAS communications module connects a ControlLogix PLC or other device to a Modicon 908 remote I O network over Ethernet The module acts as a scanner on the 908 network reading inputs and writing outputs The module supports 800 series and Quantum remote drops It supports up to 32 drops The module supports scheduled connections with a ControlLogix processor over Ethernet so the ControlLogix processor can read inputs from the Modicon network and write outputs The AN X MOD MAS module has a web interface for configuration You can communicate with the module using any standard web browser such as Internet Explorer A watchdog timer is implemented in the module s hardware If the firmware does not kick the watchdog within the timeout period the watchdog times out and places the module into a safe fatal failure state A jabber inhibit timer is implemented in the module s hardware If the network transmitter is on longer than 150 of the longest network frame time the transmitter is forced off and the module is placed into a safe fatal failure state AN X MOD MAS Page 3 The module firmware can be updated over Ethernet using the Windows utility supplied Refer to page 65 for details Hardware Features Package Contents Modes of Operation The module has LEDs to indicate the status of the connection to the Ethernet
25. The module has a standard F connector for connection to the S908 remote I O network AN X should be connected like any other node Ensure that the physical ends of the S908 remote I O network are properly terminated The AN X module does not connect the 908 cable to earth ground If a connection to ground is required use an F connector grounding block January 2008 Ethernet Cabling Software Installation AN X MOD MAS Page 5 AN X has a standard RJ 45 connector for connecting to Ethernet If you are connecting AN X to an existing network through a router or switch use a standard Ethernet cable If you are connecting directly between a computer and AN X use a crossover cable You must uninstall any previous version of the software before you can install a new version Use the Windows Control Panel Add and Remove Programs to remove the old version Insert the CD supplied with the AN X module and run the program setup exe on the CD January 2008 Page 6 AN X MOD MAS Quick Start Step See page 1 Install the AN X Windows software 5 2 Power up the AN X connect it to Ethernet and use 7 AnxInit to assign it an IP address Connect AN X to the Modicon S908 network 4 4 Use the AN X web interface to autoconfigure the 18 Modicon network and ControlLogix configuration 5 Configure the AN X in RSLogix 5000 31 6 Scan I O read inputs and write outputs 7 Use the web interface to create tags for
26. a slot The bit is 1 for a correctly functioning module and 0 otherwise To map the health bits for a given drop include a line with the keyword ModnHith where n is the drop number from 1 to 32 in the input section of a connection Example Mod2Hlith 20 Mod2Hlth offset 20 Note the module health bits do not update if the drop is offline or if the connection to the AN X module is lost Quantum Module Status Data Quantum modules each return a byte of module status data Refer to the documentation for each module for details on what the module status contains for a specific module There are 8 words of module status data for each drop The status byte for slot 1 is found in the low byte of the first word the status byte for slot 1 is found in the high byte of the first word and so on January 2008 Page 30 AN X MOD MAS To map the module status data for a given Quantum drop include a line with the keyword dnModSts where n is the drop number from 1 to 32 in the input section of a connection Examples d4ModSts 30 d4ModSts _ offset 30 Connection Statistics The module maintains statistics for each exclusive owner scheduled connection In the following table O represents the connection originator ControlLogix and T represents the connection target AN X There are 10 words of data for the connection Offset Description 0 Average time for last 100 O gt T updates 1
27. d of input data from the AN X to the ControlLogix processor Each connection can have its own RPI from 5 to 750 ms In general you should try to keep the number of connections small There is significant overhead in opening and maintaining each connection You map the inputs and outputs for the Modicon I O modules on the S908 network to these scheduled connections AN X can create the mappings automatically or you can create a mapping configuration manually You can have AN X create the mapping file automatically then edit the file to better suit your application For example in order to make the most efficient use of the available Ethernet bandwidth you can organize the data so that items that must update quickly are mapped to connections with short RPIs and items that are less time critical are mapped to connections with longer RPIs In addition the AN X module has diagnostic data that can be mapped to ControlLogix scheduled input data The mapping file can also contain options that apply to the entire configuration Anything after a semicolon on a line is treated as a comment Mapping I O Data You map Modicon input and output data to the ControlLogix scheduled data by creating a comma separated variable file that defines the mappings January 2008 AN X MOD MAS Page 25 The file consists of sections for each scheduled connection Within each scheduled connection there are definitions for the input and output data for
28. dapter that s on the same Ethernet subnet as the AN lt module you want to configure you may only have one Ethernet adapter in your computer Local Area Connection x Enter the Ethernet MAC Address of the AN module you want to configure ou can get this from the label on the AN lt module or by selecting Utilities Locate All AN x Modules if the module s current IP address is on the same subnet 00 00 17 a 00 00 09 Enter the IP address on the local subnet that you intend the AN module to use 192 168 0 9 1 Select the Ethernet adapter that s connected to the AN X In most cases there will be just one Ethernet adapter in the computer The AN X must be on the same subnet as the computer 2 Enter the MAC address of the AN X you are updating This is printed on the AN X label It consists of six pairs of hexadecimal digits separated by hyphens In the example above it s 00 Oc 1a 00 00 09 If the AN X is already online you can obtain its MAC address using the Utilities Locate All AN X Modules command 3 Enter the IP address of the AN X you want to update Step 2 In step 2 you choose a method of restarting AN X to put it in config mode January 2008 AN X MOD MAS Page 51 Step 2 Cycle Power or Reboot Command a x In order to configure the IP address or update the module s firmware the module must be be set to a specific mode There are two ways to do this 1 Cycle power on th
29. date AN X Flash Update Firmware Firmware Update Wizard AN X MOD MAS Page 49 The Utilities Update AN X Flash command updates the low level firmware configuration and production kernels Files have extension qtf This command resets the AN X You will receive a warning and be given the opportunity to Cancel the command If you cancel at the filename dialog the AN X has already been reset and is in boot mode Use the Utilities Restart AN X command to restart it in production mode Look in a downloads e naa a ANXBOOT QTF a AnxBoot_1_2_1 qtf zImage cfg v1 00 0001 qtf zImage cfg 1 00 0002 qtf zImage cfg v1 00 0003 gtf a 2Image cfg v1 00 0005 qtf File name Files of type Jats Flash File tf Cancel J Open as read only Z There are two ways to update all the firmware in an AN X module 1 The Configuration Firmware Update command starts the firmware update wizard which takes you step by step through the firmware update process 2 The Utilities Update Firmware command updates all the firmware on an AN X you have selected using the Utilities Select An AN X command Firmware files have extension bin Select the Configuration Firmware Update command to start the firmware update wizard January 2008 Page 50 AN X MOD MAS Step 1 In step 1 you identify the AN X you are configuring Step 1 AN X Selection xj Select this computer s Ethernet a
30. e check logs Fast red flash Reconfiguration set station number and baud rate failed Single red flash Unscheduled messaging addressing or connection problem Slow red flash Script or application problem during startup January 2008 Page 64 AN X MOD MAS At startup the SYS LED sequence is e boot code starts fast flashing red e boot code loads a kernel solid red e if the configuration kernel is loaded 2 red flashes followed by a pause e if the production kernel loads with no errors solid green NET LED Network Status The NET LED indicates the status of the S908 remote I O network connection Solid green All configured drops are responding Some modules may be in error Yellow No configured Modicon I O Flashing or solid red Network error January 2008 AN X MOD MAS Page 65 Updating the Firmware The AN X operating software consists of several parts e boot code runs at startup e configuration kernel runs when you update firmware e production kernel runs in normal operation e application software for network communication and scheduled messaging The kernels are supplied in file with extension gif and are updated using the AnxInit utility Run the command Utilities Update AN X Flash and select the file you wish to download Refer to page 49 for details Firmware files contain the application programs for AN X and have extension bin They are downloaded using
31. e AN X Module This is the preferred method but the AN module must be nearby If you choose this option POWER OFF the 4N module and click on the Next button C 2 Send a command on Ethernet that restarts the AN X module This method is more convenient if the module is not nearby If you choose this option make sure the AN module is powered ON and fully up and running then click on the Next button lt lt Back The preferred method is to cycle power on the AN X Select the first option on the screen and click the Next gt gt button The second method useful if the AN X in not easily accessible is to send it a command over Ethernet The AN X must be powered on and completely running for this method to work For example if this is the first time you are configuring a new AN X allow sufficient time for it to acquire an IP address from a DHCP server or to time out and use its default IP address about 3 minutes Select the second option on the screen and click the Next gt gt button Step 3 Wait for AN X to enter config mode While AnxInit is waiting the Next gt gt button will be disabled When AN X is in boot mode the Next gt gt button will be enabled January 2008 Page 52 AN X MOD MAS Step 3 Wait for Config Mode xi IF you selected the Cycle Power option power ON the AN module now If you selected the Reset Command option a reset command has been sent to the AN module This program is now
32. eceive a warning and be given the opportunity to Cancel the command You do not have to reconfigure the AN X after applying a patch All configuration information will be left intact When the patch has been applied AnxInit restarts the AN X in production mode If you cancel at the filename dialog the AN X has already been reset and is in configuration mode Use the Uftilities Restart AN X command to restart it in production mode January 2008 AN X MOD MAS Page 55 Using the Web Interface The AN X module contains a webserver capable of commuincating with standard web browsers such as Internet Explorer Use the web interface to e set the S908 remote I O network configuration e set the ControlLogix scheduled data configuration e view the current configuration view AN X logs To use the web interface you need to know the IP address of the AN X Use the Utilities Locate All AN X Modules command in AnxInit to find all AN X modules on the Ethernet network To access the web interface start your web browser and type the AN X IP address where you normally enter web addresses in the browser i QTS AN X MOD MAS web interface 1 1 12 Microsoft Internet Explorer Juest Technical Solutions AN X MOD MAS Modicon 8908 RIO Ethernet Configure ControlLogix Support Gat eway v Configuration Files Introduction This is the main configuration screen for the Modicon S908 RIO Etherne
33. ed 3 not used 4 not used Map ScanSts to input data for any connection By default when you perform an autoconfiguration AN X maps ScanSts to the connection to slot 15 but comments out the mapping January 2008 Aliases AN X MOD MAS Page 41 LongInput Most 800 series drops send inputs only when the inputs change You can force 800 series drops to send inputs on every scan by including the LongInput parameter in the ControlLogix configuration file That way when you switch between AN X modules you can be sure that the backup has the latest inputs The AN X MOD MAS creates aliases that can be imported into RSLogix 5000 Item Alias name prefix Base tag Unique elements RedundPrefix ClxName such as diagnostics TO inputs ClxPrefix DataInput name if present TO outputs ClxPrefix DataOutput name if present Criteria for Switching between AN X Modules Switchover The ControlLogix processor maintains connections to both AN X modules It can monitor data on both AN X modules and can switch between them based on e diagnostic counters e drop error table e module health bits To switch between AN X modules 1 Set RedundCtl on the backup AN X to 1 The backup AN X will not go online while it ses the primary AN X as master on the network 2 Set RedundCtl on the primary AN X to 0 The backup AN X will now become master on the S908 network January 2008 Page 42 AN X MOD
34. etwork select Obtain an IP address automatically DHCP To configure the AN X to use a static IP address select Use the following Settings and enter the following e the desired IP address for the AN X e the Subnet mask for the AN X e the default gateway for your network January 2008 Restart an AN X AN X Info AN X MOD MAS Page 47 You must enter a default gateway address that is valid for the subnet even if there is no device at the gateway address on the network Click OK to complete the configuration Use the Utilities Restart AN X to restart the AN X in production mode If you Cancel the Utilities AN X IP Configuration command AN X is left running in boot mode Use the Utilities Restart AN X command to restart the AN X Use the Utilities Restart AN X command to restart the currently selected AN X in poduction mode The Utilities AN X Info command provides information about the currently selected AN X in the log window The information shown AN X Info Ethernet MAC address SerNum Serial number DaughterID Daughterboard ID 10 for AN X MOD MAS BootRev Boot code version ConfigRev Configuration kernel version ProdRev Production kernel version HwRev Hardware version FirmwRev Firmware release version depends on current operating mode Status see below Vendorld Vendor ID ProdId Product ID IpAddrStr AN X IP address HostName AN X host name In boot mode Firm
35. figure the AN X MOD MAS in RSLogix 5000 1 Right click on the ControlLogix Ethernet bridge module that will be communicating with the AN X and select Add Module Add a 1756 ENBT A module Set the Major Rev to 1 E Module Properties LocalENBT 16 1756 ENBT A 1 1 General Connection Module Info Port Configuration Port Diagnostics Backplane Type 1756 ENBT 4 1756 10 100 Mbps Ethernet Bridge Twisted Pair Media Vendor Allen Bradley Parent LocalENBT Kane aama o Address Host Name Description 192 168 0 105 C Host Name Comm Format fi Slot 16 Chassis Size fiz a Revision fi Electronic Keying Disable Keying Status Offline Cancel Help Enter the Name This is usually the host name you assigned to AN X when you configured its IP properties January 2008 Page 32 AN X MOD MAS Set the Slot to 16 Set the chassis size to 17 Set the Comm Format to None Set the IP address to match the AN X module Set Electronic Keying to Disable Keying Record the Name as it is used to create tags to access the data 2 Add Generic modules for each required connection E Module Properties AnxMod 0 1756 MODULE 1 1 General Connection Module Info Backplane Type 1756 MODULE Generic 1756 Module Parent AnsMod r Connection Parameters Assembly Instance Size Name AnwSlot0 Input 250 16 bit Description Output 248 H 16 bit Configuration 4 8 bit
36. guration file and send it to the AN X MOD MAS You can also use autoconfiguration to build an initial configuration file edit the file to add features then perform a manual configuration with the modified file Before you can perform an autoconfiguration the remote I O network must be connected to the AN X From the AN X web interface select Automation Network S908 I O Network Configuration January 2008 AN X MOD MAS Page 19 AQTS AN X MOD MAS web interface v1 1 12 Microsoft Internet Explorer File Edit View Favorites Tools Help EBak gt OA A Qeearch Favortes Gmedia Edy lt b Sh H Address http j 192 168 0 9 z so Links Google Gpsearch web GBsearchsite g Ghi74ablocked feuloptions Zoo maton NENDE AN X MOD MAS Modicon 908 RIO Configuration 5908 VO Network Configuration Modicon S908 RIO Configuration Instructions Configure ControlLogix Support at ult in a disruption in the Modico be performed with the C in run mode View Configuration Files a create a M O configuration file View Active Configuration v Log Files Automatically scan b Administration Manually create file using e f select the local file Use the Send button to apply this configuration Browse Send rie o AN AN X can generate a default ControlLogix data mapping configuration based on the I O it finds see page 24 If you want AN X to generate the ControlLogix configuration check
37. haracters long It can contain alphanumeric characters and a hyphen To configure the AN X to obtain its IP address from a DHCP server on the network select Obtain an IP address automatically DHCP To configure the AN X to use a static IP address select Use the following Settings and enter e the desired IP address for the AN X e the Subnet mask for the AN X e the default gateway for your network You must enter a default gateway address that is valid for the subnet even if there is no device at the gateway address on the network Click OK to complete the configuration If you click Cancel AN X is left running the boot code Use the Utilities Restart AN X command to restart the AN X in production mode Example Standalone Computer TIP Since you are connecting directly from the computer to AN X use a crossover Ethernet cable The following instructions assume Windows 2000 The procedure for Windows NT or Windows XP is very similar They also assume that an Ethernet network card has been installed in the computer and that AnxInit has been installed on the computer The parameters in this example will work when you set up any standalone computer to work with AN X First configure the computer to use a static IP address From the Start menu select Start Settings Network and Dialup Connections Double click on Local Area Connection January 2008 AN X MOD MAS Page 13 Local Area Connection Status zi General
38. here are two ways to create a Modicon View Active Configuration y Log Files t Administration alLogix configuration Auto configure Network Manually create a csv file using your e dus form below t oc Use the Send button ta this configurat atl file Send File to AN X O l interme Autoconfiguration If you are autoconfiguring the S908 remote I O network make sure the network is connected to the AN X MOD MAS To configure just the I O check Auto configure S908 network To configure the remote I O network and also generate a default ControlLogix configuration on the AN X check Auto configure S908 network and ControlLogix configuration Click the Auto configure Network button January 2008 AN X MOD MAS Page 57 Manual Configuration Manual configuration does not require that the network be online Create a configuration file Refer to page 24 for details on the file format Browse or type the file name Click the Send File to AN X button to send the values to AN X Configure ControlLogix Support AN X exchanges scheduled data with a ControlLogix processor over Ethernet Refer to section Exchanging Scheduled Data with a ControlLogix on page 24 for information on configuring scheduled data exchange Select Automation Network Configure ControlLogix Support in the web interface to upload the configuration e QTS AN X MOD MAS web interface v1 1 12 Microsoft Internet Explorer File Edit View
39. imal number Some Quantum discrete output modules for example the DRA 840 00 can be configured to either set their outputs to the last value or set their outputs to a user defined value when they lose communication with the network master To set these modules to hold their last state add a line after the slot definition that contains the keyword CfgOutLast Example Slot 4 Type DRA_840_00 CfgOutLast If you use both CfgOutLast and additional numerical parameters they can be on the same line or on separate lines CfgOutLast should be first If you do not enter any parameter data AN X uses the default parameters from its module database Refer to the document AN X MOD Parameters supplied with the AN X for detailed information about parameters for specific Quantum modules Sample RIO Configuration File In this example drop 1 is an 800 series drop and drop 2 is a Quantum drop Drop 1 Rack 1 Slot 4 Type B804 Slot 5 Type B805 Rack 2 Slot 4 Type B888 EndDrop Drop 2 Rack 1 January 2008 AN X MOD MAS Page 23 Slot 4 Type DAI_353_00 Slot 7 Type DAO_840_00 EndDrop Viewing the Current Configuration To view the S908 remote I O configuration currently in AN X access the web interface and select Automation Network View Active Configuration You can also view the configuration file by accessing the web interface and selecting Automation Network View Configuration Files Click on the AN X MOD MAS S908 Network C
40. ix consists of a line with the keyword ClxPrefix followed by a comma and the prefix text Example ClxPrefix MOD _ January 2008 Page 26 AN X MOD MAS Scheduled Connection Data Each scheduled connection to the AN X begins with a line that consists of the keyword ClxSlot followed by a comma and then a number from 0 to 15 Example ClxSlot 0 Each scheduled connection consists of output data and input data Scheduled outputs from the ControlLogix processor for that connection begin with a line with just the keyword DataOutput Scheduled inputs to the ControlLogix processor for that connection begin with a line with just the keyword DataInput Data definitions consist of lines that define the mapping between the ControlLogix data table and the Modicon I O module location drop rack and slot They consist of lines of the form CLX_offset optional Modicon_Location tagname The CLX_offset is the offset into the data for the connection You can select the offset where the data is located or you can leave it out and AN X will automatically assign the offset The Modicon_location consists of an address in the form dxrysz where x is the drop number from 1 to 32 y is the rack number from 1 to 5 and s is the slot number from 1 to 16 If the rack number is 1 the explicit rack number ry can be omitted Example To associate ControlLogix offset 27 with the Modicon module at address drop 4 rack 2 slot 4 and assign
41. l Automation Encompass Product Partner Americas January 2008 AN X MOD MAS Page 67 Support Technical support is available from Quest Technical Solutions Quest Technical Solutions 4110 Mourning Dove Court Melbourne FL 32934 321 757 8483 website qtsusa com email support qtsusa com If you need to make a return contact QTS to obtain a return authorization number January 2008
42. n X t DI eS i i Archive Configuration Technical support will provide the password and supply detailed information on any further steps AN X IP Configuration You can change the AN X IP configuration from the web interface This requires that you know the currect IP address and can use it to access the web interface Select Administration AN X IP Configuration January 2008 Page 62 AN X MOD MAS o z s raa QTS AN X MOD MAS web interface v2 1 5 Microsoft Internet Explorer DER Fie Edt Wew Favorites Tools Help i i o Google v C Search Ge S gD E 2340 blocked Autolink Ea Options links wy Qa dA E J search She Favorites es w Ba 3 Norton Antivirus E z al Address http 192 168 0 105 Eo v Automation Network PN NED IP Configuration Log Files Administration DHCP a Static AN IP Configuration Gg AN X Hostname AN X IP Address NET Mask era 192 168 0 1 SUBMIT You can configure the AN X to use DHCP or to use a static IP address The host name can contain alphanumeric characters and a hyphen Click SUBMIT to set the parameters When prompted click CONTINUE to reboot the AN X with the new parameters Archive Configuration You can archive all the current AN X configuration files and log files from the web interface The archive file is a standard gzip compressed tar archive Select Administration Archi
43. nd wait for the search for a DHCP server to time out When the search for a DHCP server times out AN X repeatedly flashes the SYS LED red three times followed by a pause Run AnxInit Select Utilities Locate All AN X Modules and confirm that it finds the AN X I Local Area Connection 2 0x2 00 Oc 1a 00 01 0d 192 168 0 105 Anxinit DBR Configuration Utilities Edit View Help x X device s O000010d Ethernet MAC 00 0c 18 00 01 0d iNet aise UL ela AnxMod For Help press F1 January 2008 AN X MOD MAS Page 15 Select Utilities Select An AN X and enter the MAC Address and IP address Set Ethernet amp IP Address Adapter Local Area Connection 2 Ethernet MAC Address 00 0c 1 a 00 01 0d IP ddress 192 168 O 41 Cancel Click OK to accept the setting Select Utilities AN X IP Configuration AN X TCP IP Configuration Enter the IP configuration you want the previously selected AN lt module to use You MUST enter a valid Default gateway IP address that is on the same subnet as the AN module but you don t need to have a device at that address Host Name AnxM od Obtain an IP address automatically DHCP Use the following Settings IPAddress 192 168 0 105 Subnet mask 255 255 255 O Default gateway 192 168 0 1 Cancel Enter an IP Address In this case we chose 192 168 0 105 Enter the same Subnet mask and Default gateway that you entered for the c
44. o 255 Both MAC address and IP address must match the settings on the AN X in order for communication to occur January 2008 Page 46 AN X MOD MAS Click OK to select the AN X The title bar of AnxInit shows the MAC Address and IP Address of the currently selected AN X Set AN X IP Configuration Utilities AN X IP Configuration sets the AN X IP address and hostname The AN X must be on the local Ethernet to set its IP address First select the AN X using the Utilities Select An AN X command Next select Utilities AN X IP Configuration The AN X TCP IP Configuration dialog appears AN X TCP IP Configuration x Enter the IP configuration you want the previously selected AN lt module to use You MUST enter a valid Default gateway IP address that is on the same subnet as the AN module but you don t need to have a device at that address Host Name Erea Obtain an IP address automatically DHCP Use the following Settings IP Address 192 168 0 10 Subnet mask 255 255 255 0 Default gateway 192 168 O 1 Cancel Enter a Host Name for the AN X AN X uses the host name to create ControlLogix tags so give the AN X a meaningful host name This name is used internally by AN X and may be used to identify the AN X if you have a DNS server on your network The name can be from 1 to 31 characters long To configure the AN X to obtain its IP address from a DHCP server on the n
45. o a file Manual configuration is useful when the Modicon network is not attached to the AN X or when you need something other than the default configuration Create the configuration file using a text editor or a spreadsheet such as Excel and save it as a comma separated variable CSV file with extension csv The file format is described on page 21 To send the configuration to AN X 1 From the AN X web interface select Automation Network S908 I O Network Configuration 2 Type or browse the configuration file name into the Select file area 3 Click the Send To AN X button to send the file to AN X AN X parses the file and shows either the current configuration if configuration was sent successfully or an error message if there was a problem with the file January 2008 AN X MOD MAS Page 21 Configuration File Format The remote I O configuration file defines the contents of the drops to be scanned It is a comma separated variable csv text file which can be created with a text editor or with a spreadsheet such as Excel Anything after a semicolon on a line is treated as a comment Comments can be inserted at the end of a line or on a separate line The file defines the contents of the drops on the 908 network Begin a drop definition with a line that consists of the keyword Drop followed by an equals sign and then the drop number from 1 to 32 There should be no spaces before or after the equals sign Example
46. odules Anxlnit displays a list of the AN X modules it finds showing their MAC IDs IP addresses and host names This command is useful for determining IP addresses when they have been set by a DHCP server or for confirming that an AN X is accessible January 2008 AN X MOD MAS Page 45 device s 00000009 Ethernet MAC 00 0c 1a 900 00 08 IpAddrstr 192 168 090 411 test 0000000a Ethernet MAC 00 0c 1a 00 00 0a IpAddrstr 1692 168 0 106 ANXNOOO0O00a For Help press F1 Selecting an AN X Before you can perform an operation on an AN X you must select which AN X you want the operation performed on Choose Utilities Select An AN X to select a specific AN X Set Ethernet amp IP Address x Adapter Local Area Connection Ethernet MAC Address 00 0c 1 a 00 00 0a IPAddress 192 168 0 10 Cancel From the Adapter list select the network adapter that connects to the Ethernet network that contains the AN X In the Ethernet MAC Address field enter the MAC Address of the AN X you wish to select It can be found on the AN X label or by using the Locate All AN X Modules command The format is as shown above six pairs of hexadecimal digits separated by hyphens In the ZP Address field enter the Ethernet IP address of the AN X you wish to select It can be found using the Locate All AN X Modules command The format is as shown above four decimal numbers each in the range 0 t
47. omputer The default gateway address does not exist on the network but AN X requires that the field have a valid entry Click Finish to accept the settings Select Utilities Restart AN X to restart AN X with the new parameters When the AN X has restarted SYS LED is solid green select Utilities Locate All AN X Modules and confirm that the AN X is found with the new parameters January 2008 Page 16 AN X MOD MAS Local Area Connection 2 0x2 O0 Oc 1a 00 01 Od 192 168 0 41 Anxinit Configuration Utilities Edit View Help device s 0000010d Ethernet MAC 00 0c 18 00 01 0d TORATE RANAS AnxMod For Help press F1 Reconfiguring an AN X from an Unknown State It sometimes happens that an AN X has been previously configured with an IP address that causes it to be inaccessible on the current Ethernet network To reconfigure it to a known state run the command Configuration AN X IP Settings to start the AN X IP Configuration Wizard and reconfigure AN X January 2008 AN X MOD MAS Page 17 January 2008 Page 18 AN X MOD MAS Autoconfiguration S908 Network Configuration Before you can scan a Modicon S908 remote I O network you must configure the network in the AN X MOD MAS There are two methods of configuring the S908 remote I O that the AN X MOD MAS is to scan e autoconfiguration The AN X MOD MAS reads the network contents by sending messages to the attached network e manual configuration You build a confi
48. onfiguration January 2008 Page 60 AN X MOD MAS Log Files System Error Log System Info Log ControlLogix Log View All Logs Administration Menu Browse File System AN X maintains various logs to record diagnostic and error messages Use the Log Files menu in the web interface to view these logs The System Error log records errors that occur during AN X operation This log is normally empty The System Info Log records informational messages during startup and normal operation The Ethernet IP log shows messages and errors associated with the ControlLogix scheduled data operation Use View All Logs to list and view all the AN X logs To view a log file double click on the file name The Administration Menu is used to set the AN X IP address and to view and edit files on AN X The file edit function is password protected and is used only for AN X technical support If you are required by QTS technical support to examine files on the AN X select Administration Browse File System January 2008 AN X MOD MAS Page 61 Z QTS AN X MOD MAS web interface v2 1 5 Microsoft Internet Explorer DER i File Edit View Favorites Tools Help ay Googe M Osh a BB Boboded atk Fomes trie Om OA GD Psowe krones O R I BL ws ina E Address http 192 168 0 105 We Bo Restricted Access Automation Network Log Files Administration ovo as Submit AN Xx TP Configuratio
49. onfiguration File link and select Open to open the file in whatever application is associated with CSV files on your computer usually a spreadsheet or a text editor Saving the Current Configuration To save the configuration currently in AN X to a file access the web interface and select Automation Network View Configuration Files Right click on the AN X MOD S908 Network Configuration File link and save the file Supported Modicon Modules To view a list of supported modules view the current configuration AN X appends a list of supported modules to the end of the file January 2008 Page 24 AN X MOD MAS Exchanging Scheduled Data with a ControlLogix A Modicon S908 remote I O network can contain up to 2048 words of input data and 2048 words of output data 32 drops x 64 words per drop Each scheduled connection with a ControlLogix contains at most 250 words of input data and 248 words of output data In order to be able to scan the largest possible Modicon network the AN X MOD MAS module supports multiple scheduled connections with a ControlLogix processor over Ethernet The AN X MOD MAS module behaves like a 17 slot ControlLogix rack with an ENBT A module in slot 16 and generic modules in slots 0 to 15 A ControlLogix processor can open scheduled connections to each of these 16 generic modules Each scheduled connection consists of up to 248 words of output data from the ControlLogix processor to the AN X and up to 250 wor
50. sing the MAC address and IP address you entered previously These messages tell the AN module to remain in its Boot state in preparation for configuring the IP settings If the AN module enters Boot mode successfully the Next button below will be enabled so you can move on to the next step If the AN module has been powered ON for more than 10 seconds and the Next button is still disabled press the Back button confirm the MAC and IP addresses and check the Ethernet cabling If the AN X does not enter boot mode within about 10 seconds return to the previous screens and check the entries The AN X TCP IP Configuration dialog appears AN X TCP IP Configuration Enter the IP configuration you want the previously selected AN module to use You MUST enter a valid Default gateway IP address that is on the same subnet as the AN module but you don t need to have a device at that address Host Name Obtain an IP address automatically DHCP Use the following Settings IP Address 192 168 0 105 Subnet mask 255 255 255 0 Default gateway 192 168 0 1 Cancel Enter a Host Name for the AN X AN X uses this name when it creates tags so give the AN X a meaningful name that is unique on your January 2008 Page 12 AN X MOD MAS network This name is also used internally by AN X and may be used to identify the AN X if you have a DNS server on your network The name can be from 1 to 31 c
51. t adapter that s on the same Ethernet subnet as the AN X module you want to configure you may only have one Ethernet adapter in your computer Local Area Connection 2 v Enter the Ethernet MAC Address of the AN module you want to configure ou can get this from the label on the AN lt module or by selecting Utilities Locate All AN lt Modules if the module s current IP address is on the same subnet 00 0c 1 a 00 01 0d Enter the IP address on the local subnet that you intend the AN module to use 192 168 0 105 1 Select the Ethernet adapter that s connected to the AN X In most cases there will be just one Ethernet adapter in the computer The AN X must be on the same subnet as the computer 2 Enter the MAC address of the AN X you are configuring This is printed on the AN X label It consists of six pairs of hexadecimal digits separated by hyphens In the example above it s 00 Oc 1a 00 01 0d If the AN X is already online you can obtain its MAC address using the Utilities Locate All AN X Modules command 3 Enter the IP address you intend the AN X to use Step 2 In step 2 you choose a method of restarting AN X to put it in boot mode January 2008 Page 10 AN X MOD MAS Step 2 Cycle Power or Reboot Command In order to configure the IP address or update the module s firmware the module must be be set to a specific mode There are two ways to do this 1 Cycle power on the AN X Module This is
52. t gateway product v Log Files Directions Administration The main menu located on the left provides a list of that can be configured using this web interface To see the sub menus for ea 2m click 3 d arrow icon beside each main option Menu Details Automation Network Contains all the option pages that pertain to the Modicon 5908 network 908 I O Network Configuration This screen is used to configure the Modicon 5908 IO network options RIO Ethernet gateway Configure ControlLogix Support The left pane contains commands Click on the arrows at the left of the main headings to expand or contract the sections January 2008 Page 56 AN X MOD MAS The contents of the right pane depend on the current command being executed S908 I O Network Select Automation Network S908 I O Network Configuration to configure the I O the AN X MOD MAS is to scan E QTS AN X MOD MAS web interface v1 1 12 Microsoft Internet Explorer Bile Edt View Favorites Tools Hep Back gt Q A A Bsearch Favorites meda 3 B 3 SY S Address hetpiii92 168 0 9 60 Links Google gt Gpsearch web GPsearchsite g E1743 blocked options v Automation Network S908 If twork Configuration Configure ControlLogix Support All confiquration s result in a disruption in the Modico One nd Ethernet IP c ons These should not p be performed with the PLC in run mode View Configuration Files T
53. the module s internal state and state of the connection to the S908 remote I O network an Ethernet connector a power connector an F connector to connect to the S908 network AN X MOD MAS module CD containing software and documentation rubber feet for desktop use There are three AN X modes of operation Boot mode The AN X is running its low level startup firmware Configuration mode This is the mode when you are updating the firmware in the AN X Production mode This is the normal runtime mode of operation January 2008 Page 4 AN X MOD MAS Installation Prevent Electrostatic Discharge The module is sensitive to electrostatic discharge WARNING Electrostatic discharge can damage integrated circuits or semiconductors Follow these guidelines when you handle the module e Touch a grounded object to discharge static potential Do not touch the connector pins Power AN X requires a DC power input of anywhere from 12 to 24 VDC 1 2 3 na GND Left to right the pins on the power connector are chassis ground negative voltage and positive voltage The chassis ground should be connected Power consumption is 200 mA 12VDC or 100 mA 24VDC The part number for the power connector is Phoenix MSTB 2 5 3 ST 5 08 908 Cabling and Termination Refer to the Modicon Remote I O Cable System Planning and Installation Guide 890 USE 101 00 Version 3 0 for detailed information on cabling and installation
54. the preferred method but the AN module must be nearby If you choose this option POWER OFF the 4N module and click on the Next button C 2 Send a command on Ethernet that restarts the AN module This method is more convenient if the module is not nearby If you choose this option make sure the AN module is powered ON and fully up and running then click on the Next button lt lt Back The preferred method is to cycle power on the AN X Select the first option on the screen and click the Next gt gt button An alternative method useful if the AN X in not easily accessible is to send it acommand over Ethernet The AN X must be powered on and completely running for this method to work For example if this is the first time you are configuring a new AN X allow sufficient time for it to acquire an IP address from a DHCP server or to time out and use its default IP address about 3 minutes Select the second option on the screen and click the Next gt gt button Step 3 Wait for AN X to enter boot mode While AnxInit is waiting the Next gt gt button is disabled When AN X is in boot mode the Next gt gt button is enabled January 2008 AN X MOD MAS Page 11 Step 3 Wait for Boot Mode If you selected the Cycle Power option power ON the AN lt module now If you selected the Reset Command option a reset command has been sent to the AN module This program is now sending messages to the AN lt module u
55. undant I O scanners redundant controllers etc One ControlLogix and AN X is designated the primary and acts as the scanner the other is designated the secondary and acts as a backup If the primary ControlLogix decides there is a problem it takes its AN X offline and the backup takes over The backup AN X constantly monitors the S908 network When it becomes the primary it has the current state of inputs drop status etc Each ControlLogix processor has access to current I O data from the S908 network The backup AN X listens to the S908 network when it is told to go online as a scanner It waits for 10 ms of silence on the network before it takes over It does not start scanning if it hears another master already online There have been changes and additions to the ControlLogix configuration file to support redundancy No changes are required to the 908 I O Configuration file The firmware is backwards compatible Existing applications do not need to be modified The AN X distribution CD and website have technical notes that describe in detail the procedure for using redundant AN X modules ControlLogix Ethernet Configuration File There have been changes and additions to the ControlLogix configuration file to support redundancy Parameter Description RedundEna Must be included at the beginning of the RedundPrefix ControlLogix configuration file RedundPrefix is used to create aliases for certain data Redund
56. ve configuration Click on the Archive File link and save the file Select the destination where the file will be stored January 2008 LEDs Ethernet LEDs SYS LED AN X MOD MAS Page 63 Troubleshooting The AN X MOD MAS has LEDs that indicate the state of the Ethernet connection the overall module state and the connection to S908 remote I O network There are two LEDs that indicate the state of the Ethernet connection The orange LED labelled 100 is on if the link is running at 100 Mbits second and is off otherwise The green Link Act LED is off if the link is inactive and is on if the link is active If activity is detected the link blinks at 30 ms intervals and continues blinking as long as activity is present The SYS LED is used by the AN X operating system and software to indicate the state of operations and errors Errors or status indication in boot mode cause the LED to flash yellow Otherwise the LED flashes red The SYS LED should be used in conjunction with the logs to locate the cause of problems In the following red 3 means three red flashes followed by a pause and so on SYS LED State Possible cause Red 2 AN X is in config mode Red 3 DHCP configuration failed Red 4 Fatal application error check logs for cause Red 5 Application memory access violation check logs Red 6 Application failed illegal instruction check logs Red 7 Application crashed unknown caus
57. wRev Vendor ID and Product ID and not valid and IpAddrStr and HostName are not shown January 2008 Page 48 AN X MOD MAS Possible status values are Value Meaning 1 Boot mode 2 Configuration mode 4 Production mode Read Kernel Parameters The Utilities Read Kernel Parameters command displays various communications parameters for the currently selected AN X This command resets the AN X You will be warned and given the opportunity to cancel the command AEEA Area Connection 0x2 00 0c 1a 00 00 0a 192 168 0 10 AnxInit l0 x Configuration Utilities Edit Yiew Help XIR AnxInit Ready A BN X now in BOOT mode AN X Kernel Parameters console ttyS0 115200 ip 192 168 0 10 192 168 0 105 192 168 0 1 255 255 255 0 ANxX00000a ethO none LJ For Help press F1 The Utilities Read Kernel Parameters command leaves the AN X running the boot code Use the Utilities Restart AN X command to restart the AN X in production mode Run Config Mode The Utilities Run Config Mode command is used to restart the currently selected AN X in configuration mode normally used internally for updating firmware This command is not used in normal operation but may be required for technical support The AN X is in configuration mode when the SYS LED flashes red twice followed by a pause To exit configuration mode use the Utilities Restart AN X command to restart AN X in production mode January 2008 Up
58. will also update If the exclusive owner connection to slot 0 stops AN X stops all communication with the S908 network This option is included for debugging since it allows inputs to update in the ControlLogix It is NOT recommened for normal operation For maximum compatibility with Modicon hardware it should not be used in normal operation In addition to the I O data there are other items that can be mapped to connection input data For all these items you can assign an offset for the data within the ControlLogix input data or your can leave out the offset and let AN X assign the offset automatically January 2008 Page 28 AN X MOD MAS TIP All items are of the form offset optional ItemKeyword If you create the ControlLogix configuration automatically when you autoconfigure the S908 network these items are mapped by default to ClxSlot 15 If you map the diagnostic data to a separate connection use a long RPI to reduce the Ethernet traffic since the diagnostics do not need to be updated as frequently as I O data Diagnostic Counters The AN X MOD MAS maintains the following diagnostic counters Counter Description TxCount Transmitted network frames RxGood Received frames with good status RxPrtcl Received frames with a protocol error RxNoise Received frames with a noise error RxTout Receive timeout Scanner sent a message to a drop but did not receive a reply within the timeout period
Download Pdf Manuals
Related Search
Related Contents
MAT5D Denon AVR-391 DVD Player User Manual O Poker Estratégia - uma forma de melhorar o seu Poker Estratégia Electric Riva2 670 Installation & User Instructions Руководство по эксплуатации Гидромассажные ванны с Hoshizaki DCM-300BAH User's Manual CQ-VAD7300U - Panasonic Canada Ex Mode d`emploi 5 (Page 2) www.silverlinetools.com Bakers Pride Oven BLF-F User's Manual Copyright © All rights reserved.