Home

T-200 SERIES

image

Contents

1. 14 5 5 UPS Port Sliarer i eH el 14 5 6 RSC24 RS232 RS485 Interface 14 VI CUSTOMER SERVICE 6 1 17 6 2 17 6 3 5 ue reete a rero me 17 VII LIMITED WARRANTY 18 200 Series UPS User Manual I SAFETY This manual contains important instructions for T 200 series UPS that should be followed during installation and maintenance IMPORTANT NOTICES 1 Read instructions carefully before operating the UPS 2 All warnings in the manual should be adhered to 3 All operating instructions should be followed 4 The unit should be supplied by a grounded outlet Do not operate the unit without ground source 5 Power cord of the UPS should be routed carefully so that they are not to be walked on 6 Please save this manual 7 Please save or recycle the packaging materials WARNING e Do not insert any object into ventilation holes or other openings e Toreduce the risk of fire or electric shock install in temperature and humidity controlled indoor area free of conductive contaminants e To reduce the risk of fire replace fuses with the same type and rating when necessary CAUTION e Only qualified personnel should install or service UPS batteries Riskof electric shock do not remove cover N
2. SLAdLNO AVTI38 LAdLNO f 26258 i AJAXIS 78 2 9 YIAYIS 74 YIAYIS v YJAYIS e AJAXIS 72 YJIAYIS L i i E Am EJ i i PP A A A A a nn 9 LOSZIN 18 2 ZSANY ZOSZIN 10 318V9 SANY LOSZIN 3189 SANY LOSZIN 318925052 1 09 68d SLINN 8 SN OML 40 NOILO3NNOO 5 JHL Ad SYJAY3S SL OL L dN S IOHINOO A DO xe pus zm 5 d J Sees sea 214729022 UM ar LINN H3HVHS H3AH3S 8 OL 8 5 WVADVIG NOLLOWNNOO 8 51 SLINN 9NIHVHS Sd SI143S SN 200 Series UPS User Manual RMP MASTER Special Or Special Standart RS232 RS485 RS232 cable code m2501 cc04 cable code cable code cable code 02 03 01 05 m2502 SE Slave COMPUTER COMPUTER comz T MON RUPS Standart 5232 cable code cc01 EA EAN AA AA AA DAA AAA AAA AA DAA AAA aa Connection Diagram Of The RMP 16 200 Series UPS User Manual VI CUSTOMER SERVICE WARNING There are no customer serviceable components inside DO NOT open the cover or attempt to service the unit High voltage may remain when the unit is shut down Unauthorized service will void the warranty and could cause serious injury 6 1 Maintenance The unit is designed for easy maintenanc
3. 10 Input Current 15 Input Frequency 50 Hz 5 RFI Level EN50091 OUTPUT Nominal Output Power 5250 W Output Voltage 220 230 VAC Output Voltage Tolerance 1 Output Frequency 50 Hz Output Frequency Tolerance Line Synchronized 1 Free Running 0 2 Efficiency 100 Load 85 87 Crest Factor 3 1 Overload capacity 100 125 Load 2 5 min 125 150 Load 10 sec gt 150 instant by pass Total Harmonic Distortion THD lt 3 BATTERY Batteries 20 x 12V Floating Charge Voltage 270 End of Discharge Voltage 200 Vdc Autonomy Time 100 Load 5 min Charging Current 2 5A ENVIRONMENT Operating Temperature 0 40 C Acoustic Noise lt 45dBA Dimension HxWxD mm Model A 710x265x740 Model S 945x265x740 Relative Humidity max 90 200 Series UPS User Manual DB9 Port PK1 On Off Switch Battery Fuse AC Output Main Switch 6 7 5 10 kVA DB9 Port Model A Rear view AC Output AA PK1 On Off BEBE Switch 25 Figure 2 2 1 Main Switch 6 7 5 10 kVA Rear view Battery Fuse 6 7 5 10 Model S Rear view 200 Series UPS User Manual 111 INSTALLATION 3 1 Unpacking The UPS is packed and enclosed in a structural cardboard carton to protect it from damag
4. done by the authorized service 3 During the storage period the batteries should be charged once per six months 4 Keep the equipment and the batteries in a dry cool place Best storage temperature for the UPS Between 0 C and 40 max Best storage temperature for the batteries Between 10 C and 35 C max 17 200 Series UPS User Manual VII LIMITED WARRANTY The UPS is warranted against all defects in workmanship and materials under normal use for a period of one year from the date of shipment to the original user The conditions of this warranty and the extent of responsibility of corporation under this warranty are as follows 1 The warranty does not apply if the product has been subjected to physical abuse improper installation unauthorized service or modification 2 The sole responsibility of corporation under this warranty shall be limited to the repair or replacement of the product at the sole discretion of corporation 3 If it becomes necessary to send a defecting unit to corporation the product should be shipped in its original carton or in suitable equivalent and with shipping charges prepaid corporation will not assume any responsibility for any loss damage incurred in shipping 18 AGKK3801 10 2008
5. on the Main Switch and battery fuse to 1 position on the rear panel In this case there is line voltage at the output and battery charger board is active 2 Turn the On Off Switch PK1 on the rear panel to 1 position In a few seconds the cooling fan will start to operate then the red LED by pass indicator will be off and the green LED indicator inverter will turn on and the UPS will start to give the inverter power to the output 3 Disconnect the input power The LINE FAILURE indicator will be on and audible alarm will sound intermittently Now the output receptacles are supplied from the battery source 4 Connect the power again and see that LINE FAILURE alarm is off 5 Now your UPS is ready to operate Plug in the critical loads to the output receptacles of the unit NOTE If any condition is different from the above situation call our local service representative for assistance CAUTION After initial start up keep power continuously to the unit for at least 12 hours to ensure that the batteries are fully charged During battery charging the inverter be shut down by turning the On Off Switch PK1 to off O position In this case the main switch should be kept in on 1 position and it must be kept in mind that there is line voltage at the output 200 Series UPS User Manual IV OPERATING PROCEDURE 4 1 Turn On procedure 1 Turn on the Main Switch and battery fuse on the rear panel to 1
6. Manual The safety earth cable must be connected to the earth bus bar and bonded to each cabinet in the system All cabinets should be earthed in accordance with local regulations The UPS itself has no effect on the earthing quality it doesn t change the unwanted voltage difference between the earth and neutral lines Once the equipment has been finally positioned and secured connect the power cables as described in the following section It is recommended that the UPS should be connected to the line voltage protected by a circuit breaker 1 Before connecting AC and DC power to the UPS make sure that the On Off Switch PK1 Main Switch and battery fuse on the rear panel are in the 0 position OFF 2 Connect the AC and or DC input power to the UPS according to the label on the rear panel Perform the load connections according to the same label too 3 Check if the connections are correct battery polarity ac voltage ratings etc FUSE 240V DC AC INPUT Figure 3 1 a 6 7 5 10 Model S 240VDCBATT INPUT AC OUTPUT Figure 3 1 b 6 7 5 10 kVA Model A CAUTION To reduce the risk of electric shock disconnect the UPS from the mains supply before installing a computer interface signal cable Reconnect the power cord only after signaling interconnections been made WARNING DO NOT DEFEAT GROUND CONNECTIONS 200 Series UPS User Manual 3 4 Start Up 1 Turn
7. Relay Common Battery Low Relay NO RS232 Signal Gnd 7 RS232 Receive 6 RS232 Transmit 9 1 3 8 Not Connected 13 200 Series UPS User Manual 5 4 Remote monitoring panel RMP You can see UPS status and parameters without using a computer up to 200 meters via RS485 interface And you can connect more than one remote panel in cascade for monitoring your UPS system from several different locations at the same time 5 5 UPS Port Sharer Multiple server shut down unit Using one of this units you can automatic shut down of 4 8 servers or PC where without LAN connected to the same UPS by RUPS software Please look at the following connection diagram US 8 US 4 1 gue Br mme 4 e Lese 5 6 RSC24 5232 RS485 Interface This interface should be used if the distance between the UPS and its remote monitoring panel exceeds 20 meters 7 je IT 14 200 Series UPS User Manual M
8. T 200 SERIES UNINTERRUPTIBLE POWER SUPPLIES 3 Phase Input amp 1 Phase Output T 206 6kVA T 207 7 5 KVA T 210 10 kVA USER MANUAL 5 ll SARE DY iiu ret sd 1 II INTRODUCTION 2 1 System 2 00 2 2 2 Technical 4 Ill INSTALLATION 3 1 Unpacking 2 sess 6 3 2 Location 6 3 3 Cable Connections xui eR d 6 3 3 Statt Up eee RR ee RM RR EEG 8 IV OPERATION PROCEDURE 4 1 Turn On 9 4 2 Turn Off 222 444 9 4 3 When Utility Power Is Interrupted 9 4 4 Operator Control 9 4 4 1 Push Buttons 8 10 4 4 2 First Message Line Of The LCD 10 4 4 3 Second M L ALARMS Of The LCD 11 4 5 Automatic Battery Test System optional 11 V OPTIONAL EQUIPMENT 5 1 Software 12 5 1 1 T MON Software sss 12 5 2 SNMP Module eese 13 5 3 UPS DB9 port definition 13 5 4 Remote Monitoring
9. e 1 Inspect for damage that may have occurred during the shipment If any damage is noted call the shipper immediately and retain the shipping carton and the UPS 2 Carefully open the carton and take the UPS out 3 Retain the carton and packing material for future use Unit package contents User Manual Guarantee Certificate Model A Y Model A Y Model A Y Model S Model S Model S Additional battery cabinet O O O UPS Monitoring Software RUPS II RUPS II RUPS Il O Optional Battery Cabinet 3 2 Location Selection The UPS is designed to be installed in a protected environment The following conditions should be prohibited 1 Blocking the airflow intake and outlet It is recommended to retain 10 cm 4 minimum Between the rear side and the wall 2 Environment temperature and humidity out of specification 3 Location subject to excessive moisture dust and corrosion 4 Location exposed to heat source or direct sunlight 3 3 Cable Connections CAUTION Only qualified personnel should install or service UPS batteries The ac input to the UPS should be supplied by a separate line from the ac distribution board The input output cables can be sized to suit the modules rating according to the table below 6 kVA 3 x 4 mm and 2 5 mm Eart Cable 7 5 kVA 3 x 6 mm and 4 Eart Cable 10 kVA 3 x 6 mm and 4 Eart Cable 200 Series UPS User
10. e Very little customer maintenance required The following will help to ensure trouble free operation for several years 1 Vacuum the dust from the ventilation intake on the front panel 2 Wipe the cover with a dump cloth 3 Periodically unplug the power cord of the UPS from the wall outlet to test the batteries condition lf automatic battery testing option not available CAUTION It is recommended to test the battery discharging capability only after the software in use has been saved and all files have been closed 6 2 Troubleshooting Due to the unique design the unit can be serviced only by authorized people In case of a persistent failure or problem properly turn off the unit first Then review the following check list Be prepared to answer the questions before calling the service 1 Did you follow the operation procedure Did it happen on installation 2 Is the on off switch PK1 on the rear panel turned to position 1 3 Is the utility power of the wall outlet correct 4 Did a power failure occur just after or before the malfunction noted on the UPS 5 What is the indicators status see LCD alarms and FAULT codes 6 Were any changes made recently to unit or the critical equipment connected to the unit T Did an overload condition occur Remove load from the unit and restart it 6 3 Storage 1 Check the batteries charge with the manual battery test before storage 2 Connection s uninstall operation will be
11. em please call for service INVERTER FAILURE Inverter can not generate AC output Turn off the FAULT 2 UPS and then turn it on again If it doesn t start please call for service The temperature on the heatsink inside the UPS cabinet has exceeded 90 FAULT 3 C three times in the last 30 minutes In such a case the UPS should be turned off and on again to resume normal operation FAULT 4 Output Failure alarm has occurred 4 times in the last 30minutes Please call for service BAT AUTONOMY END Battery autonomy has finished during line failure Battery test aborted Battery test performed whilst battery not perfectly BATTERY FAILURE charged or battery cells damaged Please call service FAULT 7 Rectifier fault Please call service for checking the UPS FAULT 8 Line voltage out of tolerance ONLINE MODE UPS operating mode is ONLINE mode ECONO MODE optional This message shown the alternate operating mode is active OFFLINE 4 5 Automatic battery test system optional There are some conditions to make this test e g availability of by pass supply line synchronization a min time requirement since the last line failure etc The first test is performed automatically 8 hours later following the first turning on of the UPS There is a 65 hours interval between two successive tests an each test lasts about 36 seconds During the battery test operation the inverter power w
12. ill be supplied from batteries At the end of this test if the battery voltage is below a predetermined value BATTERY FAILURE BATTERY LOW Fault messages appear on the LCD panel and the UPS starts operating in By Pass mode In this case you have to call your service If the batteries are in normal conditions the system will start operating in normal mode after 36 sec This test protects your operation against unexpected battery failures and indicates you if there are any damaged batteries It also discharges the batteries periodically which is a good thing for extending battery life 11 200 Series UPS User Manual V OPTIONAL EQUIPMENT 5 1 Software Options The UPS can send digital data optional to the computer thought the RS232 port No additional card is needed It also has two alarm relays Line failure and battery low Computer systems require time to perform an orderly shutdown without corrupting or losing data In an extended power failure a computer system protected by a UPS eventually will lose power when the battery is exhausted Using a UPS monitoring T MON RUPS RUPSII UPSILON 2000 software the UPS and the computer system communicate so that the computer system is warned of impending UPS shutdown Software T MON RUPS RUPSII UPSILON 2000 and SNMP devices is available for most operating systems and is supplied with a signaling cable that connects to the UPS RUPS software supports alarm relay
13. interruptible power supply UPS To choose the T 200 series as your equipment protector was a wise investment It includes many features to protect your critical equipments The T 200 series UPS system is connected between mains and critical loads such as computer systems telecommunication systems computerized instruments etc The advantages of using UPS e Increased power quality The UPS has its own internal voltage and frequency regulator circuits which ensure that its output is maintained within close tolerances independent of voltage and frequency variations on the mains power lines e Increased noise rejection By rectifying the input ac power to dc power and then converting it back to ac any electrical noise that may present on the input mains supply line is effectively isolated from the UPS output therefore the critical load sees only clean power e Power blackout protection If the mains power fails the UPS continues to power the critical load from its battery source leaving the load immune from power disturbances 2 1 System Description Features On line technology with pure sine wave output PWM and IGBT technology Microprocessor controlled main controller board Static STS and maintenance by pass LCD Liquid Crystal Display display Alarm history Memory for max 64 alarms Automatic battery testing optional High quality maintenance free lead acid type batteries High nonlinear load capacity
14. lly the unit switches to bypass within a few milliseconds Static Transfer Switch Static By Pass 3 Phase AC Input 1 Phase AC Output Inverter Rectifier Battery Charger Battery Figure 2 1 UPS Block Diagram Rectifier The first stage of the UPS It supplies the DC bus voltage which is necessary for operating the inverter by rectifying line voltage Inverter It is made by utilizing the latest technology of power transistor IGBT and pulse width modulation PWM Inverter converts dc bus voltage into an alternative voltage like line voltage And provides this voltage and frequency being fixed Static Transfer Switch static by pass Static transfer switch is an electronically controlled switching circuit checked by main controller board In case of inverter overload or any other faults STS transfers the critical load to the mains without any interruption Battery Group It keeps dc voltage which is necessary for the inverter as a reservoir dc power supply in case of mains failure Battery Charger It produces a well regulated dc voltage suitable for charging the UPS batteries 2 2 Technical Specifications T 200 Series UPS User Manual T 207 Power 7 5 Power Factor 0 7 Automatic Battery Test Alarm Relays Y RS 232 Y INPUT Input Voltage 380 400 AC 3Ph N Input Voltage Tolerance 15 15 By pass Voltage 220 230 VAC
15. m appears you have to shut down all your loads immediately and turn the main switch PK1 to position 0 4 4 Operator Control Panel The panel can be divided into two functional sections LED indications and control and display As can be seen the upper section consists of leds which indicate the operation mode This panel shows the systems operation such as input and output Voltages Frequency Load Status etc by LCD 4 4 1 Push buttons T 200 Series UPS User Manual 1 Sound on off button When you push this button it will disable the audible alarm on the UPS If you want to enable the sound alarm again you have to push the DISPLAY SELECT button for 2 sec 2 Display select button Each time you push this button you can see one of the parameters of the FIRST up MESSAGE LINE Display Select On Line UPS O Status Indicators Sound LCD On Off Button Figure 4 1 Control Panel 4 4 2 First message Up line of the LCD The percentage of the load connected to the UPS output during this message LOAD the sound button enables disables sound alarm UPS output Voltage during this message the sound button enables disables OUTPUT sound alarm BATTERY UPS battery Voltage during this message the sound button enables disables sound alarm LINE Line Voltage at the UPS input during this message the sound button enables disables sound alarm LANG ENGLISH Display language during this message the s
16. o user serviceable parts inside refer servicing to qualified service personnel e output may be energized when the unit is not connected to a mains supply Riskof electric shock hazardous live parts inside this unit energized from the battery supply even when the input AC power is connected e To reduce the risk of electric shock disconnect the UPS from the mains supply before installing a computer interface signal cable Reconnect the power cord only after signalling interconnections have been made ABOUT THE BATTERY A battery can present a risk of electric shock or burn from high short circuit currents The following precaution should be observed when working on batteries Remove watches rings or other metal objects Use tools with insulated handles e batteries in this UPS are recyclable Batteries must be disposed of according to local environmental laws The batteries contain lead and pose a hazard to the environment and human health if not disposed of properly e Do not dispose of batteries in a fire The batteries will explode Do not open or mutilate the batteries They contain an electrolyte which is toxic and harmful to the skin and eyes If electrolyte comes into contact with the skin the affected area should be washed immediately e internal energy source the battery cannot be de energized by the user 200 Series UPS User Manual Il INTRODUCTION Thank you for selecting this un
17. option Line Failure amp Battery Low Cable code M2501 CCO4 T MON RUPSII amp UPSILON 2000 software support RS232 option Cable code M2502 CC05 5 1 1 T MON Software T MON SERVER UPS monitoring Lokal T MON SERVER UPS monitoring Lokal KGK Dosya Grafik Kontrol Yard m Dosya Grafik Kontrol Yard m Client y netimi Demo FREKANS Ak G z Voltaj M IGIRIS VOLTAJI basic 230 0 2 48 3 DATA a 4 31 10 2002 11 25 49 WEB SERVER QueryUnload Using this software the monitoring and control functions of the LCD panel of the UPS can be performed using your PC or Server It is also possible to monitor a remote Ups with TCP IP protocol and to shutdown your server and users with T MON server Connector Software Operating systems MS Windows 95 98 2000 XP NT Server UNIX Client 12 200 Series UPS User Manual 5 2 SNMP Module Using the SNMP module your UPS is seen as a network device in your WAN or LAN applications and with this way it can be monitored more than one UPS s connected to your network through SNMPVIEW Software supplied with the module or it is possible to monitor the UPS through an Internet Browser It is possible to shutdown the servers or users with Client mate Software that communicates with SNMP module 5 3 UPS DB 9 female port definition Pin assignments Pin number Line Failure Relay Common 4 Line Failure Relay NO 2 4 5 Battery Low
18. ound button enables disables sound alarm UPS output frequency during this message the sound button enables disables FREQ sound alarm SOUND ON Audible alarm is active Each press to this button SOUND OFF Audible alarm is not active disabled by the user will change the status BATT USED It shows battery operation time the time passed after the last line failure alarm MOD ONLINE This parameter determines the operation type of the UPS Econo mode means MOD ECONO that if the mains is okay the load is fed from mains if the line failure alarm occurs UPS feeds the load OFFLINE UPS SYNC OK UPS and LINE synchronization status 2 Communication active If sends data to UPS message will be showed for 3 seconds Your UPS records and keeps all its faults and alarms up to 64 events in its memory for future monitoring Events are recorded in the order of occurrence LOG EVENT The upper line on LCD indicates the recorded event number 000 being the last event The lover line shows the name of the event While monitoring the recorded events you can return to event number 000 by pressing the sound off button for a relatively long time 10 T 200 Series UPS User Manual 4 4 3 Second message line of the LCD VERSION XXXX Micro controller software version of the UPS BYPASS FAILURE This message shown that there is a problem of the static bypass syst
19. position There is line voltage at the output 2 Turn on the On Off Switch PK1 on the rear panel to the 1 position Turn on the power switches on your critical load after the Inverter indicator green light is turned on There is inverter voltage at the output 4 2 Turn Off procedure 1 Turn off all the power switches on your critical equipments that are connected to the UPS 2 Turn off the On Off switch PK1 and the Main Switch to 0 position CAUTION A For daily TURN ON TURN OFF operation it is recommended to keep the Main switch and battery fuse at 1 position to ensure proper battery operation B If the Main switch is in 1 position the line power will be supplied to output receptacles directly DO NOT insert objects other than equipment power cords into outlets 4 3 When Utility Power Is Interrupted In case the utility power is interrupted the UPS converts the built in battery source to output terminals immediately to protect your critical loads from loss of data or damage Battery back up time is more than 10 minutes for full load and can be extended by removing non critical loads After an utility power blackout the audible alarm and LINE FAILURE indicator on LCD panel will start operating 1 minute after the power is interrupted and you will see the message BAT USED 001min on the LCD panel This will show you for how long the batteries were used since the power was interrupted When the Battery Low alar
20. special for computers Accessories o Optional UPS monitoring software T MON RUPS RUPSII UPSILON SNMP devices compatible to any operating system o Remote Monitoring Panel RMP available You can observe the UPS status and parameters without using a computer at a remote location up to 200 meters away via RS485 interface o UPS Port Sharer available T 200 Series Uninterruptible Power Supplies UPS are advanced true On Line Sine wave devices with static transfer switch which provide reliable regulated transient free AC power to sensitive equipment Since the UPS is a true On Line system conditioned power is provided continuously to the connected equipments Unlike standby power systems the UPS is constantly regulating and filtering the output power When incoming power is interrupted the UPS protects the computers instantaneously without any transfer time T 200 Series has high non linear load capability i e Crest Ratio 3 1 and this is suitable for powering special loads such as switching power supplies or highly capacitive inputs like computers 200 Series UPS User Manual The system s static transfer switch STS provides by pass power as its standby source During an overload condition the S T S will switch the customer s load over to the bypass line with no interruption The S T S will transfer back to the inverter automatically when the overload condition has been cleared If the inverter fails interna

Download Pdf Manuals

image

Related Search

Related Contents

  OrgPublisher 9 Deployment Guide  Emerson 627 Series Commercial/Industrial Regulators Drawings & Schematics  Operating Instructions Type 8222 ELEMENT  ダウンロード  080210 AS200 Capture ans Analysis Software User Manual  Mega Drive : Instruction Manual (FR)  VM Bundle  User's Manual SP200F SERIES - i  Évaluation des aspects matériels (imprimés) du matériel didactique  

Copyright © All rights reserved.
Failed to retrieve file