Home
FX0N-485ADP_E Installation Manual
Contents
1. Further information can be found in the associated manuals mentioned below Specifications are subject to change without notice Safety guidelines for the user and protection of the FXon 485ADP This manual has been written to be used by trained and competent personnel The definition of such a person or persons is as follows a Any engineer using the product associated with this manual should be of a competent nature trained and qualified to the local and national standards These engineers should be fully aware of all aspects of safety with regards to automated equipment b Any commissioning or service engineer must be of a competent nature trained and qualified to the local and national standards c All operators of the completed equipment should be trained to use this product in a safe and coordinated manner in compliance to established safety practices Note The term completed equipment refers to a third party constructed device which contains or uses the product associated with this manual Notes on the Symbols Used in this Manual At various times throughout this manual certain symbols will be used to highlight points of information which are intended to ensure the users personal safety and protect the integrity of equipment A 1 Indicates that the identified danger WILL cause physical and property damage A 2 Indicates that the identified danger could POSSIBLY cause physical and property damage Under no circumstanc
2. PLC I O points Pertorman e Communication ificati uni il 7 specification method Half duplex Baud rate N N network 384000 bps Parallel link 19200bps Computer link No protocol 300 600 1200 2400 4800 9600 19200 bps Communication N N network Parallel link format Computer dedicated protocol format 1 format 4 No protocol LED display LED color Power green RD red SD red 4 2 Outside Dimensions and Part Names 1 Top cover 2 POWER LED Lighting while power is correctly supplied 3 RD LED Lighting while receiving data 4 SD LED Lighting while sending data 5 Extension cable 6 Direct mounting hole 7 DIN rail mounting slot DIN rail width 35 1 37 8 DIN rail mounting clip Unit mm inches 2 4 5 0 18 FXon 485ADP 9 0 35 87 3 43 7 Weight Approx 0 3 kg 0 66 Ibs Color Munsell 0 08GY 7 64 0 81 DIN rail width 35 mm 1 37 Accessories Terminal resistors 330 Q x 2 and 110 Q x 1 Station number label for linking 4 3 Terminal configuration and terminal screws The terminal configuration of the RS 485 port on the 485ADP is as shown below Y d ki N A n ka ee 5 ed 5 x 485ADP ii PAER z w sD a 8 4 Zg 5 a2 basa n 6 7x0 Yee 2 r Zu oz LS 1 24 terminal Power supply terminal M3 screw 2 24G terminal Power
3. supply terminal M3 screw 3 FG terminal Frame ground M3 screw 4 SDA terminal Data transmission terminal M3 screw 5 SDB terminal Data transmission terminal M3 screw 6 LINKSG Signal ground M3 screw 7 RDB terminal Data transmission terminal M3 screw 8 RDA terminal Data transmission terminal M3 screw Terminals screws of terminal block for RS 485 are M3 threaded Therefore connect wiring by fitting a crimped terminal suited to the terminal screws see below to the cable Tightening torque of terminals is 0 5 to 0 8 N m Screw terminals must be secure enough to prevent a loose connection from causing a malfunction 6 2mm 0 24 inches or less M3 threads M3 threads l 6 2mm ue 0 24 inches K 00 3 or less Manual number JY997D53101 Manual revision D Date September 2003 afa MITSUBISHI ELECTRIC CORPORATION MITSUBISHI DENKI BLDG MARUNOUTI TOKYO 100 8310 HIMEJI WORKS 840 CHIYODA CHO HIMEJI JAPAN HEAD OFFICE Side B A JAPANESE lencusn Changes for the Better a MITSUBISHI PROGRAMMABLE CONTROLLERS MELSEG F FXon 485ADP Installation Manual JY992D53101D This manual contains text diagrams and explanations which will guide the reader in the correct installation safe use and operation of the FXon 485ADP hereafter abbreviated to 485ADP and should be read and understood before attempting to install or use the unit
4. the Symbols Used in this Manual At various times throughout this manual certain symbols will be used to highlight points of information which are intended to ensure the users personal safety and protect the integrity of equipment A 1 Indicates that the identified danger WILL cause physical and property damage A 2 Indicates that the identified danger could POSSIBLY cause physical and property damage Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment e All examples and diagrams shown in this manual are intended only as an aid to understanding the text not to guarantee operation Mitsubishi Electric will accept no responsibility for the actual use of the product based on these illustrative examples e Please contact a Mitsubishi distributor for more information concerning applications in life critical situations or high reliability Associated Manuals PROGRAMMING MANUAL PROGRAMMING MANUAL II or FX COMMUNICATION USER S MANUAL mentioned below are not provided in sets with a product Contact our agent where the product was purchased to request the manuals accordingly Manual E Manual Name Nambar Description This FXon 485ADP INSTALLATION JY992D53101 Describes contents related to installation of the manual MANUAL FXon 485ADP Module i Describes conte
5. 76401 A D UL JY992D87201 PROGRAMMING MANUAL JY992D76401 Describes contents related to instruction in FXo FXos FXon FX FX2 FX2c Series PLC Describes contents related to instruction in FX1s PROGRAMMING MANUAL II JY992D88101 FEXin FXon EXonc Series PLC FXin CNV BD Ww i A JY992D84701 Special Adapter Connection Board Describes contents related to installation of the FX2n CNV BD each board JY992D63601 X Special Adapter Connection Board Indispensable manual ye Either manual is necessary This manual describes the installation the and specifications of the 485ADP For details on wiring including use of terminal resistor and preparation of cable with communication equipment system configuration and communication setting and program examples refer to the FX COMMUNICATION USER S MANUAL 1 Outline of Product 4 Product Specification The 485ADP is an insulated RS 485 communication adapter with an Terminal block for connecting RS 485 equipment Connected to the main unit of the FX Series PLC it enables signal exchange between the PLC and equipment via an RS 485 port 2 Communication Functions and Applicable PLC Available in indicated version or later 4 1 Specification All other specifications than the followings are equivalent to those of the FX Series PLC main unit Item Specification Withstand voltage 500 V AC 1 min Betwe
6. Side B A JAPANESE lencusn Changes for the Better a MITSUBISHI PROGRAMMABLE CONTROLLERS MELSEG F FXon 485ADP Installation Manual JY992D53101D This manual contains text diagrams and explanations which will guide the reader in the correct installation safe use and operation of the FXon 485ADP hereafter abbreviated to 485ADP and should be read and understood before attempting to install or use the unit Further information can be found in the associated manuals mentioned below Specifications are subject to change without notice Safety guidelines for the user and protection of the FXon 485ADP This manual has been written to be used by trained and competent personnel The definition of such a person or persons is as follows a Any engineer using the product associated with this manual should be of a competent nature trained and qualified to the local and national standards These engineers should be fully aware of all aspects of safety with regards to automated equipment b Any commissioning or service engineer must be of a competent nature trained and qualified to the local and national standards c All operators of the completed equipment should be trained to use this product in a safe and coordinated manner in compliance to established safety practices Note The term completed equipment refers to a third party constructed device which contains or uses the product associated with this manual Notes on
7. X Seeries FXon 485ADP PLC 4 2 Outside Dimensions and Part Names 1 Top cover 2 POWERLED Lighting while power is correctly supplied 3 RDLED Lighting while receiving data 4 SDLED Lighting while sending data 5 Extension cable 6 Direct mounting hole 7 DIN rail mounting slot DIN rail width 35 1 37 8 DIN rail mounting clip Unit mm inches 2 4 5 0 18 i Weight Color Munsell 0 08GY 7 64 0 81 DIN rail width 35 mm 1 37 Accessories Terminal resistors 330 Q x 2 and 110 Q x 1 Station number label for linking Approx 0 3 kg 0 66 Ibs 4 3 Terminal configuration and terminal screws The terminal configuration of the RS 485 port on the 485ADP is as shown below 1 gL 1 24 terminal Power supply terminal M3 screw Q d abs 2 24G terminal Power supply terminal M3 screw ae 3 FG terminal Frame ground M3 screw pars ae 4 SDA terminal Data transmission terminal M3 screw JE 5 SDB terminal Data transmission terminal M3 screw 6 LINKSG Signal ground M3 screw 8 4 Em 7 RDB terminal Data transmission terminal M3 screw 5 8 8 RDA terminal Data transmission terminal M3 screw 710 6 mi Terminals screws of terminal block for RS 485 are M3 threaded Therefore connect wiring by fitting a crimped terminal suited to the terminal screws see below to the cable Tightening torque of te
8. bles signal exchange between the PLC and equipment via an RS 485 port 2 Communication Functions and Applicable PLC Available in indicated version or later Communication FXin F type FXon FXis FXon FXenc Function N N network V2 00 ae V2 00 Pia Data transfer connecting up to eight FX Series PLCs product product j Parallel link V1 20 First v1 04 First Data transfer between two PLCs relationship specifying product product master slave station 5 First First Data transfer via link protocol between PLC and Computer link v1 20 product V1 06 product computer specified as the master station No protocol V1 20 First V1 06 First Serial communication without protocol between PLC communication product product and equipment via RS 485 interface Inverter mo V3 00 V3 00 Controlling Mitsubishi s FREQROL inverter using communication EXTR instruction in function expansion memory 3 Installation Caution e Use in the environments specified under the general specification in the manual Do not use the product in environments with excessive or conductive dust corrosive or flammable gas oily smoke moisture or rain excessive heat regular impact shocks or excessive vibration as it may result in electrical shock fire malfunction damage or deterioration on the product e Make sure to shut off the power outside the product before installing or wiring it Otherw
9. en all terminals in batch and FG terminal 5 MQ or more 500 V DC by Megger Between all terminals in batch and FG terminal 5 V DC supplied from PLC main unit max 30 mA 24 V DC supplied from External power supply max 50 mA General specification Insulation resistance Power supply Power supply specification voltage current Communication FXin 3 Transmission R type FXon FXis FX2n FX2nc Function standard Conforming to RS 485 RS 422 N N network V2 00 ab t V2 00 Pre t Data transfer connecting up to eight FX Series PLCs Type of isolation Photo coupler isolation rogue procu Transmission Total extension distance 500 m or less z First First Data transfer between two PLCs relationship specifying distance 50 m or less if FX2n 485 BD or FXin 485 BD is installed in connected equipment Parallel link V1 20 V1 04 product product master slave station Number of occupied Fi Fi D jer via link Ib PL J VO point 0 point unrelated to maximum number of controlled points of the PLC Computer link V1 20 irst v1 06 irst ata transfer via link protocol between Can Poriorman s points g product product computer specified as the master station specification Communication ificati a No protocol v1 20 First V1 06 First Serial communication without protocol between PLC P method klai duplex communication product product and equipment via RS 485 interface Ba N N network 384000 bps Paralle
10. es will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment e All examples and diagrams shown in this manual are intended only as an aid to understanding the text not to guarantee operation Mitsubishi Electric will accept no responsibility for the actual use of the product based on these illustrative examples e Please contact a Mitsubishi distributor for more information concerning applications in life critical situations or high reliability Associated Manuals PROGRAMMING MANUAL PROGRAMMING MANUAL II or FX COMMUNICATION USER S MANUAL mentioned below are not provided in sets with a product Contact our agent where the product was purchased to request the manuals accordingly Manual ae Manual Name Nambar Description This FXon 485ADP INSTALLATION JY992D53101 Describes contents related to installation of the manual MANUAL FXon 485ADP Module Describes contents related to communication FX COMMUNICATION USER S MANUAL JY992D69901 available in FX Series PLC such as wiring communication setting and program examples x FX1s HARDWARE MANUAL JY992D83901 x FXo FXon HARDWARE MANUAL JY992D47501 Describes contents related to hardware of FX FXin HARDWARE MANUAL JY992D89301 Series PLC such as specifications wiring and Ww FX2n HARDWARE MANUAL JY992D66301 installation de FX2nc HARDWARE MANUAL DSS DS JY992D
11. holes Tightening torque 0 7 to 1 0 N m For the pitch and positions of mounting screw holes refer to the external dimensions Screws FXon 485ADP Mounting on DIN rail Dismounting from DIN rail Fix the 485ADP to the DIN rail Slightly pull down the DIN rail mounting clip using a DIN46277 35 mm 1 37 wide tool such as a slotted screwdriver rXon 485ADP PROD F via FR ABBAD f wo E 25o i me A ET a FX Seeries 5 etach DIN rail FXon 485ADP PLC 4 Product Specification 4 1 Specification All other specifications than the followings are equivalent to those of the FX Series PLC main unit Item Specification Withstand voltage 500 V AC 1 min Between all terminals in batch and FG terminal General specification Insulation resistance 5 MQ or more 500 V DC by Megger Between all terminals in batch and FG terminal Power supply Power supply specification voltage current 5 V DC supplied from PLC main unit max 30 mA 24 V DC supplied from External power supply max 50 mA Transmission standard Conforming to RS 485 RS 422 Type of isolation Photo coupler isolation Transmission distance Total extension distance 500 m or less 50 m or less if FX2n 485 BD or FX1N 485 BD is installed in connected equipment Number of occupied 0 point unrelated to maximum number of controlled points of the
12. ise electric shock or serious damage to the product may occur e Never drop wire chips or shavings into the vent slits when drilling screw holes or performing wiring as they may cause fire breakdown or malfunction e Securely install the 485ADP to the designated port Poor connection may cause malfunction 3 1 How to Install to FX Series PLC Installation to FX1s FX1N FX2N Turn OFF the PLC before beginning any work 1 Remove the panel cover from the top face of the main unit 2 Take off the resin cover from the left side of the main unit 3 Install the following board to the port on the main unit Board name Corresponding model FXiN CNV BD FX1N FX1s FX2nN CNV BD FX2N 4 Fix the above board using the M3 screws supplied Tightening torque 0 3 to 0 6 N m Installation to FX1S FX1N FX2N lt FXan in the gt diagram 5 Connect the in built cable of the 485ADP to the port on the Eder tio board from the left side FXanc in the diagram Installation to FXon FX2nc Turn OFF the PLC before beginning any work 1 Remove the cover of the port for a special adapter provided on the left side of the main unit 2 Connect the in built cable of the 485ADP to the port for a special adapter 3 2 How to Install to Panel Face Direct installation to the panel face Directly fix to the panel face using 2 sets of a screw M4 a spring washer and a flat washer in the mounting
13. l link 19200bps Inverter V300 vzoo Controlling Mitsubishis FREQROL inverter using Buel ole Computer link No protocol 300 600 1200 2400 4800 9600 19200 bps communication E j EXTR instruction in function expansion memory Communication N N network Parallel link format Computer dedicated protocol format 1 format 4 No protocol LED display i i 3 Installation LED color Power green ROA SD red Caution e Use in the environments specified under the general specification in the manual Do not use the product in environments with excessive or conductive dust corrosive or flammable gas oily smoke moisture or rain excessive heat regular impact shocks or excessive vibration as it may result in electrical shock fire malfunction damage or deterioration on the product e Make sure to shut off the power outside the product before installing or wiring it Otherwise electric shock or serious damage to the product may occur e Never drop wire chips or shavings into the vent slits when drilling screw holes or performing wiring as they may cause fire breakdown or malfunction e Securely install the 485ADP to the designated port Poor connection may cause malfunction 3 1 How to Install to FX Series PLC Installation to FX1s FX1N FX2N Installation to inni FX1S FX1N FX2N Turn OFF the PLC before beginning any work 7 PN in the 1 Remove the panel cover from the top face of the mai
14. n unit diagram 2 Take off the resin cover from the left side of the main unit 3 Install the following board to the port on the main unit Board name Corresponding model FX1iN CNV BD_ FX1N FX1S FX2N CNV BD_ FX2N 4 Fix the above board using the M3 screws supplied Tightening torque 0 3 to 0 6 N m 5 Connect the in built cable of the 485ADP to the port on the board from the left side Installation to FXon F X2NC FXanc in the diagram Installation to FXon FX2nc Turn OFF the PLC before beginning any work 1 Remove the cover of the port for a special adapter provided on the left side of the main unit 2 Connect the in built cable of the 485ADP to the port for a special adapter 3 2 How to Install to Panel Face Direct installation to the panel face Directly fix to the panel face using 2 sets of a screw M4 a spring washer and a flat washer in the mounting holes Tightening torque 0 7 to 1 0 N m For the pitch and positions of mounting screw holes refer to the external dimensions FX Series PLC Screws FXon 485ADP Mounting on DIN rail Fix the 485ADP to the DIN rail DIN46277 35 mm 1 37 wide Dismounting from DIN rail Slightly pull down the DIN rail mounting clip using a tool such as a slotted screwdriver rXon 485ADP rower Oo r Vid Pho 8540 zA 4 p T z wee sy D etach fe DIN rail E
15. nts related to communication ch dane USER S JY992D69901 available in FX Series PLC such as wiring communication setting and program examples x FX1s HARDWARE MANUAL JY992D83901 x FXo FXon HARDWARE MANUAL JY992D47501 Describes contents related to hardware of FX FXin HARDWARE MANUAL JY992D89301 Series PLC such as specifications wiring and x FX2n HARDWARE MANUAL JY992D66301 installation de FX2nc HARDWARE MANUAL DSS DS JY992D76401 A D UL JY992D87201 A Describes contents related to instruction in FXo ww PROGRAMMING MANUAL JY992D76401 EXos FXon FX FX2 FX2c Series PLC Describes contents related to instruction in FX1s x PROGRAMMING MANUAL II JY992D88101 FXiNn EXon EXonc Series PLC FXin CNV BD axe JY992D84701 Special Adapter Connection Board Describes contents related to installation of the re FX2n CNV BD each board ve Special Adapter Connection Board aeveP boat Indispensable manual yr Either manual is necessary This manual describes the installation the and specifications of the 485ADP For details on wiring including use of terminal resistor and preparation of cable with communication equipment system configuration and communication setting and program examples refer to the FX COMMUNICATION USER S MANUAL 1 Outline of Product The 485ADP is an insulated RS 485 communication adapter with an Terminal block for connecting RS 485 equipment Connected to the main unit of the FX Series PLC it ena
16. rminals is 0 5 to 0 8 N m Screw terminals must be secure enough to prevent a loose connection from causing a malfunction M3 threads M3 threads 6 2mm 6 2mm 0 24 inches 103 0 24 inches 103 or less or less Manual number JY997D53101 Manual revision D September 2003 Date sa MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE MITSUBISHI DENKI BLDG MARUNOUTI TOKYO 100 8310 HIMEJI WORKS 840 CHIYODA CHO HIMEuI JAPAN
Download Pdf Manuals
Related Search
Related Contents
ダウンロード - Panasonic の取扱説明書がダウンロードできます。 Serie 500 MANUALE DI ISTRUZIONI Le nouveau PLV-Z4 Samsung Galaxy Tab S2 (9.7, Wi-Fi) manual de utilizador(Lollipop) Hog Slat® Gestation Stall Installation Manual Sony GPS-CS1KA Operating Instructions SEDNet model3000 Version 2.40 リリース内容 Procedimiento para la Medición de Coliformes Totales y E. Coli Copyright © All rights reserved.