Home

1756 ControlLogix Power Supplies Specifications Technical Data

image

Contents

1. IEC 61000 4 3 10V m with 200 Hz 50 Pulse 100 AM at 900 MHz 10V m with 200 Hz 50 Pulse 100 AM at 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz Certification 1756 PSCA2 c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CSA CSA Certified Process Control Equipment See CSA File LR54689C CSA Certified Process Control Equipment for Class Division 2 Group A B C D Hazardous Locations See CSA File LR69960C FM FM Approved Equipment for use in Class Division 2 Group A B C D Hazardous Locations CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B C Tick e Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements 113 GExnA IIC T5 Gc X KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 1 When marked See the Product Certification link at http www ab com for Declarations of Conformity Cert
2. Isolation voltage Type tested 3260V DC for 60 s 250V continuous reinforced insulation type power input to backplane Weight approx 0 95 kg 2 10 Ib Dimensions 140 x 112 x 145 mm 5 51 x 4 41 x 5 71 in Module location Left side of 1756 chassis Chassis 1756 A4LXT 1756 A5XT 1756 A7LXT 1756 A7XT Wire size 2 5 mm2 14 AWG solid or stranded copper wire rated at 90 C 194 F or greater 1 2 mm 3 64 in insulation max Wire category 1 on power ports Conductor screw torque 0 8 Nem 7 Ibein North American temperature code T4 T4A IEC temperature code T4 Enclosure type rating None open style 1 2 3 4 publication 1770 4 1 The hold up time is the time between input voltage removal and DC power failure Use time delay type overcurrent protection in all ungrounded conductors This fuse is intended to guard against fire hazard due to short circuit conditions Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines Rockwell Automation Publication 1756 TDOO5D EN E March 2013 1756 ControlLogix Power Supplies Specifications Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 PAXT 1756
3. PBXT 25 70 C 13 158 F Temperature surrounding air max 70 C 158 F Temperature nonoperating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration 29 10 500Hz IEC 60068 2 6 Test Fc Operating Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM at 900 MHz 10V m with 200 Hz 50 Pulse 100 AM at 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity 4 kV at 5 kHz on power ports IEC 61000 4 4 Surge transient immunity 1 KV line line DM and 2 kV line earth CM on power ports IEC 61000 4 5 Conducted RF immunity 10 Vrms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz IEC 61000 4 6 Oscillatory surge withstand 3kV N A IEEE 37 90 1 Voltage variation 30 dips for 1 period at 0 and 180 on AC supply ports N A IEC 61000 4 11 60 dips for 5 and 50 period
4. 0 Hz 50 Pulse 100 AM 900 MHz 10V m with 200 Hz 50 Pulse 100 AM at 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 Surge transient immunity IEC 61000 4 5 4 kV at 5 kHz on power ports 4kV at 5 kHz on annunciator ports 1 kV line line DM and 2 kV line earth CM on power ports 12 Rockwell Automation Publication 1756 TDOO5D EN E March 2013 1756 ControlLogix Power Supplies Specifications Attribute 1756 PA75R 1756 PB75R Conducted RF immunity 10 Vrms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz IEC 61000 4 6 Voltage variation 30 dips for 1 period at 0 and 180 on AC supply ports N A IEC 61000 4 11 60 dips for 5 and 50 periods on AC supply ports 10 fluctuations for 15 min on AC supply ports gt 95 interruptions for 250 periods on AC supply ports Voltage variation NA 60 dips for 100 ms on DC supply ports IEC 61000 4 29 100 dips for 50 ms on DC supply ports 20 fluctuations for 15 min on DC supply ports 5 s interruptions on DC supply ports 10 ms interruption on DC supply ports Certification 1756 PA75R 1756 PB75R c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CSA CSA Certified Process Control Equipment See CSA File LR54689C CSA Certified Process Control
5. 4 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 1756 TD005D EN E March 2013 Supersedes Publication 1756 TDOO5C EN E January 2012 Copyright 2013 Rockwell Automation Inc All rights reserved Printed in the U S A
6. Equipment for Class Division 2 Group A B C D Hazardous Locations See CSA File LR69960C FM FM Approved Equipment for use in Class Division 2 Group A B C D Hazardous Locations CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B European Union 2006 95 EC LVD compliant with EN 61131 2 Programmable Controllers Clause 11 C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions EX N A European Union 94 9 EC ATEX Directive compliant with EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements 113 G Ex nA IIC T4 GcX KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 1 When marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details ControlLogix Redundant Power Supply Chassis Adapter Module Table 2 Technical Specifications ControlLogix Redundant Power Supplies Chassis Adapter Module Attribute 1756 PSCA2 Current capacity at 1 2V DC 1 5A Current capacity at 3 3V DC 4A Current capacity at 5 1V DC 15A Current capacity at 24V DC 2 8A Wire category 1 3 on 1756 CPR2 connectio
7. PC75 B 1756 PH75 B UL N A UL Listed Industrial Control Equipment See UL File E65584 c UL us UL Listed Industrial Control Equipment certified for US and N A Canada See UL File 65584 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for US and Canada See UL File E194810 CSA CSA Certified Process Control Equipment See CSA File LR54689C CSA Certified Process Control Equipment for Class Division 2 Group A B C D Hazardous Locations See CSA File LR69960C FM FM Approved Equipment for use in Class Division 2 Group N A A B C D Hazardous Locations CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B European Union 2006 95 EC LVD compliant with EN 61131 2 Programmable Controllers Clause 11 CTick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with N A EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements I3GExnAIICT4 GcX KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 1 When marked See the Product Cert
8. Technical Data Allen Bradley 1756 ControlLogix Power Supplies Specifications Standard Power Supplies Catalog Numbers 1756 PA72 1756 PA75 1756 PB72 1756 PB 5 1756 PC75 1756 PH75 ControlLogix XT Power Supplies Catalog Numbers 1756 PAXT 1756 PBXT Redundant Power Supplies Catalog Numbers 1756 PA75R 1756 PB75R Chassis Adapter Module Catalog Number 1756 PSCA2 Topic Page Standard AC Power Supplies 2 Standard DC Power Supplies 4 1756 ControlLogix XT Power Supplies 7 9 Redundant Power Supplies ControlLogix power supplies are used with the 1756 chassis to provide 1 2V 3 3V 5V and 24V DC power directly to the chassis backplane Standard ControlLogix XT and redundant power supplies are available LISTEN aS Rockwell SOLVE Allen Bradley gt Rockwell Software Automation 1756 ControlLogix Power Supplies Specifications Standard AC Power Supplies Attribute 1756 PA72 C 1756 PA75 B Input voltage range 85 265V AC Input voltage nom 120V 240V AC Input frequency range 47 63 Hz Input power max 100VA 100 W Output power max 75 W 0 60 C 32 140 F 2 Power consumption 25 W 0 60 C 32 140 F Power dissipation 85 3 BTU hr Hold up time 5 cycles 85V AC 50 60 Hz 6 cycles 120V AC 50 60 Hz 6 cycles 200V AC 50 60 Hz 6 cycles 240V AC 50 60 Hz Inrush current max 20A Current capacity at 1 2V DC 1 5A Current cap
9. acity at 3 3V DC 4A Current capacity at 5 1V DC 10A 13A Current capacity at 24V DC 2 8 A Overcurrent protection max User supplied 15 Ae Fusing Non replaceable fuse is soldered in place Transformer load max 100VA Isolation voltage 250V continuous reinforced insulation type Type tested 3500V DC for 60 s power input to backplane Weight approx 0 95 kg 2 10 Ib Dimensions 140 x 112 x 145 mm 5 51 x 4 41 x 5 71 in Module location Left side of 1756 chassis Chassis 1756 A4 1756 A7 1756 A10 1756 A13 1756 A17 Chassis compatibility Series A Series B Series B Wire size 2 5 mm 14 AWG solid or stranded copper wire rated at 90 C 194 F or greater 1 2 mm 3 64 in insulation max Wire category 1 on power ports Conductor screw torque 0 8 Nem 7 Ibein orth American temperature code T4 Enclosure type rating None open style 1 The hold up time is the time between input voltage removal and DC power failure The combination of all output power 5 1V backplane 24V backplane 3 3V backplane and 1 2V backplane cannot exceed 75 W Use time delay type overcurrent protection in all ungrounded conductors This fuse is intended to guard against fire hazard due to short circuit conditions N F Aruna a 1770 4 1 2 Rockwell Automation Publication 1756 TDOO5D EN E March 2013 Use this conductor category information for planning conductor routing as described in the system level installation manual S
10. ating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration 29 10 500 Hz IEC 60068 2 6 Test Fc Operating Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM 900 MHz 10V m with 200 Hz 50 Pulse 100 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity 4 kV at 5 kHz on power ports IEC 61000 4 4 Surge transient immunity 1 kV line line DM and 2 kV line earth CM on power ports IEC 61000 4 5 Conducted RF immunity 10 Vrms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz IEC 61000 4 6 Oscillatory surge withstand N A 3kV IEEE 37 90 1 Voltage variation 60 dips for 100 ms on DC supply ports IEC 61000 4 29 100 dips for 50 ms on DC supply ports Rockwell Automation Publication 1756 TDOO5D EN E March 2013 20 fluctuations for 15 min on DC supply ports 5 s interruptions on DC supply ports 10 ms interruption on DC supply ports 1756 ControlLogix Power Supplies Specifications Certification 1756 PB72 C 1756 PB75 B 1756
11. ee the Industrial Automation Wiring and Grounding Guidelines publication 1756 ControlLogix Power Supplies Specifications Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 PA72 C 1756 PA75 B 0 60 C 32 140 F Temperature surrounding air max 60 C 140 F Temperature non operating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 29 10 500 Hz Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM 900 MHz 10V m with 200 Hz 50 Pulse 100 AM 1890 MHz 3V m with 1kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity 4 kV at 5 kHz on power ports IEC 61000 4 4 Surge transient immunity 1 kV li
12. icates and other certification details Rockwell Automation Publication 1756 TDOO5D EN E March 2013 Article 58 2 of Radio Waves Act Clause 3 1756 ControlLogix Power Supplies Specifications Standard DC Power Supplies Attribute 1756 PB72 C 1756 PB75 B 1756 PC75 B 1756 PH75 B Input voltage range 18 32V DC 30 60V DC 90 143V DC Input voltage nom 24V DC 48V DC 125V DC Input power max 95 W Output power max 75 W 0 60 C 32 140 F 2 Power consumption 20W 0 60 C 32 140 F Power dissipation 68 2 BTU hr Hold up time 35 ms 18V DC 50 ms 30 60VDCnom 50ms 90 143VDCnom 40 ms 24V DC 40 ms 32V DC Inrush current max 30A 20A Current capacity at 1 2V 15A Current capacity at 3 3V 4A Current capacity at 5 1V 10A 13A Current capacity at 24V 2 8A Overcurrent protection max User supplied 15 Ae Fusing Non replaceable fuse is soldered in place Isolation voltage Type tested 3500V DC for 60 s 250V continuous reinforced insulation type power input to backplane Weight approx 0 95 kg 2 10 Ib Dimensions 140 x 112 x 145 mm 5 51 x 4 41 x 5 71 in Module location Left side of 1756 chassis Chassis 1756 A4 1756 A7 1756 A10 1756 A13 1756 A17 Chassis compatibility Series A Series B Series B Wire size 2 5 mm 14 AWG solid or stranded copper
13. ificates and other certification details 14 Rockwell Automation Publication 1756 TDOO5D EN E March 2013 1756 ControlLogix Power Supplies Specifications Power Load and Transformer Sizing The following graphs show the input power requirements for the power supplies given the power they are providing to the modules in the chassis Follow these steps to determine the power requirements for you chassis 1 Calculate the Backplane Power Load by adding the power draw in Watts for all of the planned modules For module power draws refer to the module specification tables in the ControlLogix Selection Guide publication 1756 SGO01 2 Locate the Backplane Power Load on the graph s vertical y axis and determine the corresponding Real Power input power rating on the horizontal x axis The Real Power value is the amount of power consumed by the power supply Power Supply Power Requirements 1756 PA72 C 1756 PA75 B AC 1756 PBXT DC 75 42 54 60 35 45 Backplane Power 30 28 Load Watts Backplane Power 21 13 er Load Watts 14 0 7 0 20 40 60 80 100 120 43995 ol Real Power Watts 0 10 20 30 40 50 60 45809 Real Power Watts 1756 PB72 C 1756 PB75 B DC 75 1756 PA75R A AC 60 75 Backplane Power 4 60 Load Watts 30 45 15 Backplane Power 39 o l Load Watts 15 0 20 40 60 80 100 120 4389 0 Real P
14. ification link at http www ab com for Declarations of Conformity Certificates and other certification details Rockwell Automation Publication 1756 TDOO5D EN E March 2013 1756 ControlLogix Power Supplies Specifications 1756 ControlLogix XT Power Supplies The ControlLogix XT products include control and communication system components that when used with FLEX I O X1T products provide a complete control system solution that you can use in environments where temperatures range from 20 70 C 4 158 F When used independently the ControlLogix XT system can withstand environments where the temperature ranges from 25 70 C 13 158 F Attribute 1756 PAXT 1756 PBXT Input voltage range 85 265V AC 18 32V DC Input voltage nom 120 240V AC 24V DC Input frequency range 47 63 Hz N A Input power max 82VA 64 W 54W Output power max 42 W 25 70 C 13 158 F Power consumption 22W 12W Power dissipation 75 1 BTU hr 40 9 BTU hr Hold up time 6 cycles 85V AV 50 60 Hz 35 ms 18V DC 6 cycles 120V AV 50 60 Hz 40 ms 24V DC 6 cycles 200V AV 50 60 Hz 40 ms 32V DC 6 cycles 240V AV 50 60 Hz Inrush current max 20A 30A Current capacity at 1 2V 1 5A Current capacity at 3 3V 4A Current capacity at 5 1V 8A Current capacity at 24V 1 75 A Overcurrent protection max User supplied 15 Ae Fusing Non replaceable fuse is soldered in place
15. ipment compliant with Article 58 2 of Radio Waves Act Clause 3 1 When marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details Redundant Power Supplies To build a redundant power supply system you need the following Cat No Description Amount 1756 PA75R A or 1756 PB75R A Redundant power supply 2 1756 CPR2 Redundant power supply cable Length 0 9 1m 3 ft 2 1756 PSCA2 Redundant power supply chassis adapter module 1 User supplied Annunciator wiring Max length 10 m 32 8 ft 2 1 The 1756 PSCA2 chassis adapter module is a passive device that funnels power from the redundant power supplies to the single power connector on the ControlLogix series B chassis backplane 2 Optional user provided annunciator wiring can be connected to the solid state relay for status and troubleshooting purposes Rockwell Automation Publication 1756 TDOO5D EN E March 2013 9 1756 ControlLogix Power Supplies Specifications System Configuration Recommendations We recommend you use one of these methods to configure your redundant power supply system Recommended Configurations for a System That Uses One Chassis oo oo oo oo L a 42655 42657 Recommended Configurations for a System That Uses Two Chassis q q 5 i
16. ll es bl E l 2 ies aj B 42658 42655 10 Rockwell Automation Publication 1756 TD005D EN E March 2013 1756 ControlLogix Power Supplies Specifications 1756 PA75R and 1756 PB75R Mounting Dimensions 7 0 Dimensions are in cm in Redundant Power Supply Features Top Mounting Hole Diameter Bottom Mounting Hole Diameter PO 45829 The redundant power supplies offer the same features as the standard power supplies in addition to the following e Automatic chassis load sharing between the redundant power supplies e Status indicators for visual operating status of the pair e Solid state relay for system recognition of supply status when wired to an input module Table 1 Technical Specifications ControlLogix Redundant Power Supplies Attribute 1756 PA75R 1756 PB75R Input voltage range 85 265V AC 19 2 32V DC Input voltage 120V 240V AC 24V DC Input frequency range 47 63 Hz DC Input power max 120VA 115 W 10W Output power max 75W 0 60 C 32 140 F Hold up time 2 cycles 60 Hz 20 ms 2 cycles 50 Hz Inrush current max 20A 30A Current capacity at 1 2V 15A Current capacity at 3 3V 4A Current capacity at 5 1V BA Current capacity at 24V 2 8A Annunciator power 240V AC DC 50 mA Resistive onl
17. ne line DM and 2 kV line earth CM on power ports IEC 61000 4 5 Conducted RF immunity 10 Vrms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz IEC 61000 4 6 Oscillatory surge withstand 3kV IEEE 37 90 1 Voltage variation 30 dips for 1 period at 0 and 80 on AC supply ports IEC 61000 4 11 60 dips for 5 and 50 periods on AC supply ports 10 fluctuations for 15 min on AC supply ports gt 95 interruptions for 250 periods on AC supply ports Certification 1756 PA72 C 1756 PA75 B UL UL Listed Industrial Control Equipment See UL File 65584 CSA CSA Certified Process Control Equipment See CSA File LR54689C CSA Certified Process Control Equipment for Class Division 2 Group A B C D Hazardous Locations See CSA File LR69960C FM FM Approved Equipment for use in Class Division 2 Group A B C D Hazardous Locations CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B European Union 2006 95 EC LVD compliant with EN 61131 2 Programmable Controllers Clause 11 C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions KC Korean Registration of Broadcasting and Communications Equipment compliant with 1 When marked See the Product Certification link at http www ab com for Declarations of Conformity Certif
18. nes for installing a Rockwell Automation industrial system Product Certifications website http www ab com Provides declarations of conformity certificates and other certification details You can view or download publications at http www rockwellautomation com literature To order paper copies of technical documentation contact your local Allen Bradley distributor or Rockwell Automation sales representative 16 Rockwell Automation Publication 1756 TDOO5D EN E March 2013 1756 ControlLogix Power Supplies Specifications Rockwell Automation Publication 1756 TDOO5D EN E March 2013 17 Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls publication SGI 1 1 available from your local Rockwell Automation sales office or online at http www rockwellautomation com literature describes some important differences between solid state equipment and hard wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of thi
19. ng IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock The hold up time is the time between input voltage removal and DC power failure 2 Use time delay type overcurrent protection in all ungrounded conductors This fuse is intended to guard against fire hazard due to short circuit conditions Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines 1756 PA75R 0 60 C 32 140 F 1756 PB75R Temperature surrounding air max Temperature nonoperating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 60 C 140 F 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 29 10 500 Hz Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 30 1000 MHz 10V m with 20
20. ns North American temperature code T5 IEC temperature code T5 Enclosure type rating None open style 1 Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Rockwell Automation Publication 1756 TD005D EN E March 2013 13 1756 ControlLogix Power Supplies Specifications Attribute 1756 PSCA2 Temperature operating 0 60 C 32 140 F IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock Temperature surrounding air max 60 C 140 F Temperature nonoperating 40 85 C 40 185 F IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 29 10 500 Hz Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 kV air discharges Radiated RF immunity 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz
21. ower Watts 0 20 40 60 80 100 120 43588 Real Power Watts 1756 PH75 B 1756 PC75 B DC 75 95 1756 PB75R A DC 60 75 60 BackplanePower 4 gt 45 Load Watts 30 30 15 Backplane Power o La Load Watts i 0 20 40 60 80 100 120 43618 Real Power Watts 0 20 40 60 80 100 120 43599 Real Power Watts 1756 PAXT AC 42 64 35 28 Backplane Power 34 Apparent Power Watts Transformer Load VA Real Power Watts Load Watts 14 7 6 0 10 20 30 40 50 60 70 45808 Real Power Watts Rockwell Automation Publication 1756 TDOO5D EN E March 2013 15 1756 ControlLogix Power Supplies Specifications Additional Resources These documents contain additional information concerning related products from Rockwell Automation Resource Description ControlLogix Selection Guide publication 1756 SG001 Provides overview of the ControlLogix system and its products ControlLogix Chassis Specifications Technical Data publication 1756 TD006 Provides technical specifications for ControlLogix chassis ControlLogix Chassis and Power Supplies Installation Instructions publication 1756 IN005 Provides planning and installation information for the ControlLogix chassis and power supplies ControlLogix System User Manual publication 1756 UM001 Provides information on how to install configure program and use ControlLogix systems Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Provides general guideli
22. s equipment The examples and diagrams in this publication are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Rockwell Automation Rockwell Software Allen Bradley ControlLogix ControlLogix XT FLEX I O XT and LISTEN THINK SOLVE are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies Rockwell Otomasyon Ticaret A S Kar Plaza Merkezi E Blok Kat 6 34752 erenk y stanbul Tel 90 216 5698400 www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 444
23. s on AC supply ports 10 fluctuations for 15 min on AC supply ports gt 95 interruptions for 250 periods on AC supply ports Voltage variation NA 60 dips for 100 ms on DC supply ports IEC 61000 4 29 100 dips for 50 ms on DC supply ports 20 fluctuations for 15 min on DC supply ports 5 s interruptions on DC supply ports 10 ms interruption on DC supply ports 8 Rockwell Automation Publication 1756 TDOOSD EN E March 2013 1756 ControlLogix Power Supplies Specifications Certification 1756 PAXT 1756 PBXT c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for US and Canada See UL File E194810 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN61000 6 2 Industrial Immunity EN61000 6 4 Industrial Emissions EN61131 2 Programmable Controllers Clause 8 Zone A amp B European Union 2006 95 EC LVD compliant with EN61131 2 Programmable Controllers Clause 11 C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with EN60079 15 Potentially Explosive Atmospheres Protection n EN60079 0 General Requirements I3GExnAlICT4GcX KC Korean Registration of Broadcasting and Communications Equ
24. wire rated at 90 C 194 F or greater 1 2 mm 3 64 in insulation max Wire category 1 on power ports Conductor screw torque 0 8 Nem 7 Ibein North American temperature code T4 IEC temperature code T4 N A Enclosure type rating None open style 1 The hold up time is the time between input voltage removal and DC power failure 1770 4 1 The combination of all output power 5 1V backplane 24V backplane 3 3V backplane and 1 2V backplane cannot exceed 75 W Use time delay type overcurrent protection in all ungrounded conductors This fuse is intended to guard against fire hazard due to short circuit conditions Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication Rockwell Automation Publication 1756 TDOO5D EN E March 2013 Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 PB72 C 1756 PB75 B 0 60 C 32 140 F 1756 ControlLogix Power Supplies Specifications 1756 PC75 B 1756 PH75 B Temperature surrounding air max 60 C 140 F Temperature nonoperating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoper
25. y Overcurrent protection max User supplied 15 Ae Fusing Non replaceable fuse is soldered in place Isolation voltage Type tested at 2500V DC for 60 s Rockwell Automation Publication 1756 TDOO5D EN E March 2013 250V continuous Reinforced Insulation Type Power Input to Backplane Power Input to Annunciator Annunciator to Backplane 11 1756 ControlLogix Power Supplies Specifications Table 1 Technical Specifications ControlLogix Redundant Power Supplies Attribute Dimensions HxWxD approx 1756 PA75R 1756 PB75R 175 x 145 x 137 mm 6 9 x 5 7x 5 4 in Weight approx 1 45 kg 3 2 Ib Chassis 1756 A4 1756 A7 1756 A10 1756 A13 1756 A17 Wire Size Power 2 5 mm2 14 AWG solid or stranded copper wire rated at 90 C 194 F or greater 1 2 mm 3 64 in insulation max Annunciator 0 25 2 5 mm2 22 14 AWG solid or stranded copper wire rated at 90 C 194 F or greater 1 2 mm 3 64 in insulation max Wire category 4 1 on power ports 3 on annunciator ports 3 on 1756 CPR2 connections Pilot duty rating Annunciator not rated Conductor screw torque 0 79 Nem 7 Ibein Solid state relay contact 240V AC DC North American temperature code T3C T4 IEC temperature code N A T4 Enclosure type rating None open style 1 3 4 publication 1770 4 1 5 Do not exceed 50 mA resistive only Attribute Temperature operati