1. EBDSPIR AD LV Ceiling PIR presence detector 1 10V 12 24V AC DC Overview Front features Mounting Bezel Back features Retaining Spring Power Input amp Switched Output Connector Channel 1 Retaining Spring Nx gt Sensor Lens which covers PIR Sensor IR Receiver Light Level Sensor Status LEDs Dimmable Control Output Connector Channel 2 Switch Input Connector Product Guide lEctronics intelligent energy control The EBDSPIR AD LV PIR passive infrared presence detector provides automatic control of low voltage loads including lighting and BMS systems with optional manual control Output Channel 1 comprises a relay capable of simple on off switching while Output Channel 2 provides dimmable control of 1 10V ballasts Functioning as a presence detector the unit can turn lights on when a room is occupied and off when the room is empty Optional settings allow lights to be turned off in response to ambient daylight or to implement a maintained illuminance daylight harvesting system All functionality is fully programmable using an IR handset PIR Sensor Detects movement within the unit s detection range allowing load control in response to changes in occupancy IR Receiver Receives control and programming commands from an IR infrared handset Light Level Sensor Measures the overall light level in the detection area Status LEDs The LED flashes Red to ind
2. ESTA energy services and technology association ISO ISO 9001 14001 Quality Environmental Management Management FM 45789 EMS 534520 Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice 10 Ceiling PIR presence absence detector 12 24V AC DC Ceiling PIR presence absence detector 12 24V AC DC for low current Ceiling PIR presence absence detector 12 24V AC DC open collector output lectronics intelligent energy control C P Electronics Ltd Brent Crescent London NW10 7XR United Kingdom Tel 44 0 333 900 0671 Fax 44 0 333 900 0674 www cpelectronics co uk enquiry cpelectronics co uk Ref WD486 Issue 2
3. and release down switch to turn off Press and hold up switch to dim up press and hold down switch to dim down Turns off after occupancy Channel mode Set to Switch and dim together Switch mode Set to 2 position switch together Note a single position switch can be used instead to toggle the output set to 1 position switch separate learst ES DIMMING LUMINAIRE DC Supply AC Supply 11 5VDC 36VDC OR 10VAC 26 5VAC CENTRE BIASED RETRACTIVE SWITCH Optional for presence mandatory for absence detection EBDSPIR AD LV SENSOR Load connections AD LV and AD LV GOLD LOAD INTERNAL RELAY COM OUT Load connections AD LV OC INTERNAL OPEN COLLECTOR TRANSISTOR LOAD COM OUT Power up test procedure When power is applied to the unit the load will turn on immediately Set the timeout to 10 seconds vacate the room or remain very still and wait for the load to switch off Check that the load switches on when movement is detected The unit is now ready for programming Fault finding What if the load does not turn ON e Check that the supply to the circuit is good e lf the detection range is smaller than expected check the diagram on page 2 Rotating the sensor slightly may improve the detection range HINT The Walk Test LED function can be used to check that the unit is detecting movement in the required area What if the load does not turn OFF e Ensure th
4. movement of the PIR sensor can be adjusted using the Sensitivity parameter HINT To assist in setting the Sensitivity turn on the Walk Test LED which will flash red when movement is detected Switch Level On Off Occupancy detection can be made dependant on the ambient light level using the Lux On Level and Lux Off Level parameters Brighter Lux Off Level Ambient Light Level Lux On Level Darker Occupancy detected Maintained llluminance daylight harvesting The detector measures the overall light level in the detection area and calculates the correct output for the luminaires to achieve a preset lux level maintained illuminance or daylight harvesting Overview It is a requirement of many fluorescent lamp manufacturers to have the lamps on at maximum output for a period of time to guarantee lamp life refer to the manufacturer s datasheet for details As this EBDSPIR AD LV is able to dim the lamps using 1 10V the product provides a facility to disable this for a given period of time Operation By setting the Burn in parameter you can select a time during which the lamps are not allowed to deviate from maximum output The unit counts the time and even remembers how long has elapsed in the event of a power failure To cancel the burn in function simply select a time of 0 Note that when the lamps are changed the burn in time should be set again Installation The EBDSPIR AD LV is designed to be mounted us
5. Shift 1 and Shift 2 LEDs Advanced programming Parameter Name Default Value Range Options Description UHS5 UNLCDHS Detector Parameters Walk Test LED Off On or Off When set to On this causes a red LED to flash on the sensor when it detects VA vA movement Use this feature to check for adequate sensitivity levels Time Out 20 minutes 0 99 minutes Once the detector is turned on this value sets how long the lights will stay on once vA Time adjustment movement has ceased Select 0 for 10 second delay use for commissioning only S Manual Time Out 10 minutes 0 99 minutes When a manual operation occurs either via the switch input or the infrared it x vA invokes the timeout period Example 1 a detector in presence mode has a detector timeout of 15 minutes and a manual timeout of 3 minutes When the user leaves the room they press the off button The sensor will revert to automatic after 3 minutes and then walking back in the room will turn the lights on Example 2 using the settings above the user turns the lights off say for a presentation but stays in the room Every time a movement is detected the manual timeout period is re triggered but when it doesn t pick up for the short timeout period the sensor will timeout and revert to automatic This means the lights may turn on inadvertently during the presentation if the occupants are still for the manual timeout period so adjust the
6. at the area is left unoccupied for longer than the Time Out Period e Ensure that the sensor is not adjacent to circulating air heaters or lamps Basic programming The functionality of the EBDSPIR AD LV is controlled by a number of parameters which can D be changed or programmed by any of the following devices e UHS5 Infrared Handset See below for programmable functions e UNLCDHS Infrared Handset with LCD See user guide for full programming details For most basic programming operations the UHS5 handset can be used and the following procedures are based on using this device Point the handset at the Sensor and send the required programming commands to the unit as shown below Valid commands will be indicated by a red LED flash See page 1 for details of other LED responses Note other functions on the UHS5 which are not shown below are not applicable to this product Default Value Parameter Name UHS5 Handset Graphics Description On Raise Turn lights on or to raise lights Off Lower Turn lights off or to lower lights Walk test O ah When set to On this causes a red LED to flash on the sensor when it detects movement Use this feature to check for adequate sensitivity levels Time Out Time adjustment 20 mins 1 10 amp 5 15 amp Once the detector is turned on this value sets 20 30 seconds how long the lights will stay on once movement minutes minutes has
7. ceased Lux on 2 5 amp 7 4 68 amp 9 level Switch level on Lux level setting to prevent the luminaires being switched on if the ambient light level is sufficient adjustable between 1 and 9 The luminaires will always be switched on at level 9 Light Level 6 600 2 200 Sets a target light level to be maintained by the 5 500 lighting system 7 700 9 999 disabled Lux off level Switch level off 2 5 amp 7 4 68 amp 9 1 589 3 6 amp 8 Lux level setting to switch the luminaires off during occupancy if the ambient light level goes above the setting adjustable between 1 and 9 Level 9 will always keep the lights on This setting can be used for window row switching Note the Lux Off Level value must always be greater than the Lux On Level value Sensitivity Sensitivity level for detecting movement 1 low sensitivity 9 high sensitivity Defaults Returns the unit to the default settings Burn in Determines how long the output will be at 100 so that lamps burn in The burn in time is not affected by power supply interruptions Presence Presence Absence Presence mode allows the output to turn on when movement is detected and off when movement ceases Absence mode allows the output to turn off when movement ceases but must be manually turned on first Presence Absence Shift Use this button to select the settings in red and blue signified by the
8. e fitted will temporarily be switched off and will return to it s normal state 2 seconds after the read back has been completed Wiring diagrams Channel 1 switched output of the EBDSPIR AD LV pro Channel 2 dimmable output of the EBDSPIR AD LV can vides a switched low voltage output which can be used to be used to control the light output of luminaires that are power a mains load via an auxiliary relay or for other con fitted with dimming ballasts transformers trol purposes The optional Gold is used for low current The ballasts transformers can be connected in parallel to switching and the optional OC provides an open collector Channel 2 via the DIM and DIM terminals Refer to the output See diagrams below specification on page 10 for ballast quantities The wiring example below shows a common method of connecting the output channels for a single detector unit Single channel dimming Functions Switches the luminaire with occupancy and maintains illuminance Dims and switches using optional centre biased retractive switch MK K4900 or similar Configured to presence detection Turns on automatically with occupancy Maintains illuminance Press and release down switch to turn off Press and release up switch to turn back on Press and hold up switch to dim up press and hold down switch to dim down Turns off after occupancy Configured to absence detection Press and release up switch to turn on Maintains illuminance Press
9. icate the following 7 Walk Test LED active Ge when movement is detected Pres ve Valid setting received RS Power Input amp Switched Output Connector Channel 1 Used to connect power to the unit and to connect a switched load Dimmable Control Output Connector Channel 2 Used to connect 1 10V controllable ballasts and transformers for dimmable loads Switch Input Connector Two input terminals can be used to manually override the dimming levels and override the lights on or off Detection diagram Area of high sensitivity Area of lower sensitivity Installation Choosing a Suitable Location The EBDSPIR AD LV is designed to be ceiling mounted and must satisfy the following criteria Avoid positioning the unit where direct sunlight may enter the sensor element Do not site the sensor within 1m of any lighting forced air heating or ventilation Do not fix the sensor to an unstable or vibrating surface Sensor functionality Detection Mode The Detection Mode for both output Channels 1 and 2 can be set to behave in Presence or Absence mode e Presence When movement is detected the load will automatically turn on When the area is no longer occupied the load will automatically switch off after an adjustable time period e Absence The load is manually switched on When the area is no longer occupied the load will automatically switch off after the adjustable time period has elapsed In either case sensitivity to
10. ing either e Flush fixing or e Surface fixing using the optional Surface Mounting Box part no DBB Both methods are illustrated below Flush Fixing Hole 64mm Warning be careful bending springs when mounting unit Pull out spring tab and rotate spring arm as shown Wire stripping details Important lt 4 Ensure that the cables are formed as shown before affixing the cable clamp The clamp MUST clamp the outer sheath s only 6mm Bend cores as shown 35 mm Readback function UNLCDHS handset only The UNLCDHS has the ability to read back the settings stored in a device To read back individual parameters e Navigate to the parameter and press the R Read button whilst pointing at the device The handset will click when the parameter has been read back the device will flash its LED and the value will be shown against the parameter in the menu To read back all of the parameters in a menu Press and hold the R Read button for more than 1 second The handset will click every time a parameter is received e The device will show multiple flashes of its LED All of the values will be shown against the parameters in the menu The individual parameters may be edited and then saved as a Macro Notes If a parameter s has been missed because of a communication error the missing value s is replaced by dashes When reading back the Channel 1 relay wher
11. m on immediately and revert to automatic operation using the manual timeout period SIS Override Off If the lights are on sending the IR command will turn them off immediately After the manual timeout period described above the sensor will revert to automatic ls OED Se Se el SS Cancel m Cancels the on or off override returning the detector to normal operation x 8 Advanced programming Parameter Name Default Value Channel 1 Switching Channel Detection Mode Presence Lux on level Switch level on Lux off level Switch level off Channel 2 Dimming Channel Detection Mode Presence Lux on level Switch level on Range Options Presence or Absence 1to9 For a higher resolution a scale of 101 199 is available 1to9 For a higher resolution a scale of 101 199 is available Presence or Absence 1to9 For a higher resolution a scale of 101 199 is available Description Presence mode allows the output to turn on when movement is detected and off when movement ceases Absence mode allows the output to turn off when movement ceases but must be manually turned on first Sets a minimum light level below which the PIR sensor is enabled allowing lights to be turned on by movement Note the Lux Level Off value must always be greater than the Lux Level On value Sets a maximum light level above which the PIR sensor is disabled preventing lights from being turned o
12. n by movement Presence mode allows the output to turn on when movement is detected and off when movement ceases Absence mode allows the output to turn off when movement ceases but must be manually turned on first Sets a minimum light level below which the PIR sensor is enabled allowing lights to be turned on by movement Note the Lux Level Off value must always be greater than the Lux Level On value UHS5 UNLCDHS lt S Lux off level 1to9 Sets a maximum light level above which the PIR sensor is disabled preventing Vv S Switch level off For ahigher resolution lights from being turned on by movement a scale of 101 199 is available Light Level 1 to 998 999 Sets a target light level to be maintained by the lighting system maintained illuminance disabled Max Value 0 to 100 Maximum dimming output level x Min Value 0 to 100 Minimum dimming output level x V Memorise Yes or No If this is set to Yes the last manual lux level set will be memorised and used as the y new switch on level x On value 0 to 99 Dimming output level when switched on 0 99 x s Off value Dimming output level when switched off 0 99 If a non zero off value is set then 36 ff the output will toggle between this value and completely off depending on the switch level on and off values For example if it is light outside the fittings will be off if there is no occupancy If it is dark outside they will adopt the preset off value Thi
13. s feature is only enabled if Min value is set to 99 Burn in 0 disabled or 1 to 999 hours Determines how long the output will be at 100 so that lamps burn in The burn in time is not affected by power supply interruptions Fade value 0 to 99 After occupancy ceases this dimming output level is loaded for the fade time adjustable between 0 and 99 x Fade mins 0 to 99 This is the time period adjustable between 0 and 99 minutes that the luminaire Vf will be held at the fade value before turning off A value of 0 disables the fade x function Speed On Measured in 0 1 Determines the dimming response speed after the setup time has finished x sec intervals Speed Set Measured in 0 1 Determines the dimming response speed during the set up time Measured in 0 1 sec intervals sec intervals If set to 0 will disable dimming for Set seconds below used if x fittings are required to warm up before dimming Set Seconds 1 to 999 seconds Determines how long the dimming response set up period lasts on power up or on setting change This enables the desired lux level to be achieved rapidly when the x vA Switch Modes lights come on or during setup 2 position switch Default together 1 position switch together A single centre biased retractive switch will be used to control both channels together A single position retractive switch controls both channel
14. s together Technical data Dimensions Weight Supply Voltage Maximum Load Power consumption Dimming output Terminal Capacity Temperature Humidity Material casing Type IP rating Compliance See diagrams opposite EBDSPIR AD LV 0 15kg Min 11 5VDC max 36VDC min 10VAC max 26 5VAC Channel 1 switching EBDSPIR AD LV Low voltage supply with relay output rating 16A resistive 10A inductive EBDSPIR AD LV GOLD Low voltage with relay contact for low on resistance suitable for control wire applications 3A resistive load Not suitable for inductive loads EBDSPIR AD LV OC Low voltage supply with open collector output rating 50mA 30VDC max Channel 2 dimming Maximum number of 1 10V ballasts is 10 On 616mW Off 270mW Basic insulation only Although low voltage this is not an SELV output and should be treated as if mains potential Use mains rated wiring 2 5mm 10 C to 35 C 5 to 95 non condensing Flame retardant ABS and PC ABS cE IP40 EMC 2004 108 EC LVD 2006 95 EC Part numbers Part number EBDSPIR AD LV EBDSPIR AD LV GOLD EBDSPIR AD LV OC Accessories DBB Description Detector Surface mounting box UHS5 Programming IR handset UNLCDHS Universal LCD IR handset IMPORTANT NOTICE This device should be installed by a qualified electrician in accordance with the latest edition of the IEE Wiring Regulations and any applicable Building Regulations
15. t elapse first If at any time during the timed delay the lux change reverses then the process is cancelled Lux Time enables absence detection to be implemented with a lux off level set When the button is pressed the lights will go on regardless of ambient light level However if there is sufficient ambient light they will turn off again after the Lux Time Note that whenever the an external switch is pressed whether in absence or presence mode if the lights were out because of the lux level they will be immediately turned on again for at least the Lux Time On N Inhibit 4 seconds 1 to 999 seconds When the detector turns off a delay is instigated to prevent retriggering In certain x vA circumstances this delay may not be enough This parameter allows the delay to be changed Factory default z Restores factory default settings z Y Channel Modes Switch and dim Default The detector will switch and dim the lighting together x v4 together User Modes Raise E z Increase light level Reverts when occupancy cycle complete Lower Decrease light level Reverts when occupancy cycle complete Scene up Steps up between 6 pre defined scenes Scene down Steps down between 6 pre defined scenes x SIS Scene Select the individual scene between 0 and 6 1 min output 2 10 3 25 4 50 5 75 6 100 x Override On If the lights are off sending the IR command will turn the
16. timing carefully 1 min to 9 max Sensitivity level for detecting movement when the detector is already on UHS5 vt va sets Sensitivity On and Off to the same value Sensitivity On 1 min to 9 max Sensitivity level for detecting movement when the detector is off UHS5 sets ve Sensitivity On and Off to the same value x Power Up State On or Off Select No for a 30 second delay on start up If Yes is selected there will be no x wA delay on start up and the detector will always power up detecting Disable Detector YorN Disables detection leaving the relay output permanently off with the dimming x lt S output operational This mode is used when the unit is for maintained illuminance only 0 minutes 0 99 minutes The On Delay to allows the first channel to switch on after the second channel A x vA typical application for this would be where a detector is controlling lighting and air conditioning in an area When the occupant is detected the lighting will be turned on immediately whereas the air conditioning may be turned on after 15 minutes If the area is vacated and the detector times out before the delay then the air conditioning would never go on The delay can be set only for channel 1 using the on delay parameter On Delay Sensitivity Off Lux time 0 disabled If the detector measures the lux level and decides that the output needs switching x WA 1 99 minutes on or off as a consequence the lux time mus
Download Pdf Manuals
Related Search
Related Contents
消費生活用製品の重大製品事故に係る公表済事故において、製品に USER ManUal NEXHO-NT Istruzioni di montaggio e funzionamento Télécharger le PDF Sea Gull Lighting 31292-57 Installation Guide ViewZ VZ-15RTV USER`S MANUAL DA200/ DA300 Series Direct Thermal Bar Code Entretien et Réparation des Moteurs Diesel. コンパクトキッチン『アピスカ』・『オフェリアR』 Manual - SAP Help Portal Copyright © All rights reserved.