Contents
1. a 6 8K Ohm resistor at the end of the circuit EOL 8 4 3 Bell the two terminals will have a 24 27VDC output to drive a bell circuit then fire alarm comes There must be a 6 8K Ohm resistor at the end of the circuit EOL Note sounder output circuit should use polarities sounder bell strobe or 5 7 horn 8 4 4 Detect the two terminals connect with the detectors and manual call points There must be a 6 8K Ohm resistor at the end of the circuit EOL 9 Wire diagram 9 1 Manual call point Call point resistor Loop In out Call point resistor Call point switch Loop In out Normal Position Activated Position The call point resistor should be between 470 and 680 ohms 9 2 Zone loop circuit PANEL ZONE TERMINALS CALL POINT CALL POINT DETECTOR DETECTOR PANEL ZONE TERMINALS NEVER SPUR LOOP THEN NOT MONITORED EOLR End of Line Resistor 6800Q CPR Call Point Resistor 470 680Q Usually supplied with call point 9 3 Sounder circuit TYPICA RCUIT Note Sounders must be polarised DO NOT SPUR EOLR end of line resistor 6k89 SOUNDERS SOUNDER TERMINALS Do not make off more than 2 circuits in the panel 6 7 Note Don t pull in or out any cable or board when power is on 7 7
2. the J4 number is 1 then after 30 seconds the panel will make a System Fault Zones board DIP switch J4 it is for indicating the zones board No in the panel For example if the zones board is No 1 for Zone 1 to 4 so the J4 is 1 If the zones board is No 2 for Zone 5 to 8 so the J4 is 2 The last zones board J4 number is equal to the main board J5 number Number the number is binary When the pin position is at ON it is 1 when the pin position is at OFF or not ON it is 0 From left to right can read out the number The decimal binary table is below Decimal Binary 1 0001 2 0010 3 0011 4 0100 4 7 0101 0110 0111 SINI 1000 Installation 7 1 7 2 7 3 Wall mounted installation open the panel use M8 expansion bolt fix the panel on the wall via the installation holes on the back Connect the battery unit to the board Note the 2 batteries should be serial connected the end voltage is about 24VDC Connect the main power supply Terminals 8 1 8 2 8 3 8 4 24V GND the two terminals supply 22V 27 2VDC 25mA Fire Protection this output is for control the fire protection devices there are 3 terminals with 2 functions dry relay and wet source 8 2 1 C P O the 3 terminals work as normally open and normally close dry relay output when fire alarm comes C P Normal Close O P Normal Open This function is available when
3. 0VAC 240VAC 240VAC Main supply monitor for fault Yes Battery protection for low voltage Yes Batteries default configuration 12V2AH 2 Detector circuit specification Number of circuit l 2 4 16 4 32 Line fault monitor for open circuit Yes Line fault monitor for short circuit Yes Line fault monitor for detector Yes if End of Line Monitor Unit fitted in place of End of Line Resistor 1 7 removal End of Line device 6 8k Q 5 tolerance 0 25W colour code blue grey red gold Detector continuity diodes Silicon 1N4001 or Schottky type required if End of Line Monitor Unit fitted to give Detector Removal Fault Call point resistor value 470 to 680 2 0 225 or 0 5 watt Maximum number of smoke heat detectors per zone 20 based on a total detector current of 2mA each detector consuming 100 u A Note if End of Line Monitor Unit is fitted for correct operation maxmum voltage drop must not exceed 12 volts Maximum number of manual call No limit points per zone Sounder circuit specification Number of general circuits 2 End of line resistor value 6 8k Q 5 tolerance 0 25W colour code blue grey red gold Line fault monitor for open circuit Yes Line fault monitor for short circuit Yes Outputs fused AT 400mA Maximum number of bells 20mA 20 of each sounder output Fuses 27VDC fuse 3A F 20mm Fire and fault output Output type Dry relay out
4. Conventional fire alarm panel Introduction User Manual 1 AW CFP2166 series conventional fire alarm panel is designed based on EN54 part 2 amp 4 standard It is modularized design the panel can expend from 1 zone to 32 zones easily tN ee fs ih It has 2 level control mode by a lock It has 27VDC power supply output It has FIRE PROTECTION FIRE ROUTING and FAULT signal output the output can be configured to dry relay type or wet sources type It has 2 channel general sounders output Each zone can be disable by a button 6 7 Each zone has 1 circuit detectors input 8 9 It has RESET button to reset the panel 10 It has SILENCE button to stop BUZZER and SOUNDERS 11 It has EVACUATE button to start a manual fire alarm immediately 12 It has TEST button to test all LEDs orderly 13 It has battery low protection function when battery voltage lower than 21 VDC battery will be cut off automatically until the mains power is on 14 It has an optional GSM module for fire alarm by SMS 15 It is economic user friendly and easy maintenance Parameters ITEM 1Zone panel 2Zone panel 4 8Zone panel 4 32 Zone panel Model No AW CFP2166 01 AW CFP2166 02 AW CFP2166 04 AW CFP2166 04 16 32 Power specification Mains supply voltage 110VAC or 240VAC Internal power supply 27 2VDC Total output current limited 500mA 500mA 3A 240VAC 3A 24
5. J12 pin 1 is on the OFF position 8 2 2 the 2 terminals work as wet source output when fire alarm comes and the circuit is Enable the ouput is 100mA 24 27VDC This function is available when J12 pin 1 is on the ON position There must be a 6 8K Ohm resistor at the end of the circuit EOL Fire Routing this output is for supplying output to fire routing devices there are 3 terminals with 2 functions dry relay and wet source 8 3 1 C P O the 3 terminals work as normally open and normally close dry relay output when fire alarm comes C P Normal Close O P Normal Open This function is available when J12 pin 2 is on the OFF position 8 3 2 the 2 terminals work as wet source output when fire alarm comes and the circuit is Enable the ouput is 100mA 24 27VDC This function is available when J12 pin 2 is on the ON position There must be a 6 8K Ohm resistor at the end of the circuit EOL Fault this output is for supplying output for fault signal there are 3 terminals with 2 functions dry relay and wet source 8 4 1 C P O the 3 terminals work as normally open and normally close dry relay output when fault alarm comes C P Normal Close O P Normal Open This function is available when J12 pin 3 is on the OFF position 8 4 2 the 2 terminals work as wet source output when fault alarm comes and the circuit is Enable the ouput is 100mA 24 27VDC This function is available when J12 pin 3 is on the ON position There must be
6. detector circuit is open 1 2 3 Fire it shows there is at least one detector or one manual call point break glass is under fire status 1 2 4 Disable it shows this zone is disable by the zone enable disable button For one zone panel only 1 3 1 Mains on this LED on shows the main power 240VAC or 110VAC is on 1 3 2 Batter Power Supply Fault this LED on shows the main power or the battery power is fault or off 1 3 3 Sounder Fault this LED on shows the sounder output circuit is short or open 1 3 4 Zone Fire this LED on shows there is at least one detector or one manual call point break glass is under fire status 1 3 5 Zone Fault this LED on shows the detector circuit is short or open Key control 2 1 Enable when the key turn to Enable the buttons are available for pressing 3 7 2 2 Disable when the key turn to Disable the buttons are not available for pressing Buttons 3 1 Reset when the Reset button is under pressing this LED will be on and all current Fire or Fault alarm will be clear and all the zones will be power off and then power on 3 2 Silence when the Silence button is under pressing this LED will be on The silence button can stop the Buzzer and Sounder output for the current alarm 3 3 Evacuate when the Evacuate button is under pressing this LED will be on This button can make the manual Fire alarm and let the Buzzer Sounder Fire Protection Fire routing be active if they are not disable 3 4 Te
7. e Protection Fire Routing Fault 1 1 10 1 Active this LED on shows the output is active 1 1 10 2Short this LED on shows the circuit is short for Fire Protection Fire Routing Fault circuits only the corresponding pin of the switch J12 on the T O board is at the ON position the wet source function is available 1 1 10 3 Open this LED on shows the circuit is open for Fire Protection Fire Routing Fault circuits only the corresponding pin of the switch J12 on the T O board is at the ON position the wet source function is available 1 1 10 4Disable this LED on shows the circuit is disable when there is a fire alarm or a fault alarm but the corresponding circuit dose not have output 1 1 11 Reset when the Reset button is under pressing this LED will be on and all current Fire or Fault alarm will be clear and all the zones will be power off and then power on 1 1 12 Silence when the Silence button is under pressing this LED will be on The silence button can stop the Buzzer and Sounder output for the current alarm 1 1 13 Evacuate when the Evacuate button is under pressing this LED will be on This button can make the manual Fire alarm and let the Buzzer Sounder Fire Protection Fire routing be active if they are not disable 1 1 14 Test when press this button the Test LED will be on and all front boards LED will be on and off orderly Zone indicators 1 2 1 Short it shows the detector circuit is short 1 2 2 Open it shows the
8. put NC and NO relay wet source output Maximum current 100mA Connection block Largest acceptable conductor size 2 5mm Smallest acceptable conductor size 0 75mm Size and weight Dimensions mm 272 200 70mm 320 231 90mm 395X502X124 362X565X124 Weight without batteries 4kg 5kg 7kg 8kg Weight with batteries 5 8kg 6 8kg 9 6kg 12 5kg User guide 1 LED indicators 1 1 General indicators 1 1 1 Power this LED on shows the main power 240VAC or 110VAC is on or backup battery is connected 1 1 2 Mains Fault this LED on shows the main power 240VAC or 110VAC is off 1 1 3 Battery Fault this LED on shows the battery is fault or connection is broke 1 1 4 Fire this LED on shows there is at least one detector or one manual call point break glass is under fire status 1 1 5 2 7 General Fault this LED on shows there are one or more faults in the internal 2 1 2 1 3 panel or the input output circuit of the panel 1 1 6 Earth Fault this LED on shows there is an earth fault some circuit is touching the iron shell or earth 1 1 7 Fuse Fault this LED on shows there is a fuse fault of the 27VDC power supply the fuse is on the power board with label F1 Main Fuse 1 1 8 MCU this LED flash shows the MCU in the panel work normally 1 1 9 System fault this LED on shows the panel internal is fault most time is indicated the communication from the main board to each zones board is fault 1 1 10 Sounder Fir
9. st when press this button the Test LED will be on and all front boards LED will be on and off orderly 3 5 Battery Reset this button is inside the panel when the main power and battery power are all off if the battery unit voltage is over 21VDC press this button can restore the battery power supply 3 6 Disable Sounder Fire Protection Fire Routing Fault and Zone Disable buttons when the Disable button is pressed the Disable Enable LED will be on off it shows the corresponding circuit is disable enable Note for reliable the Disable button must be pressed again after 5 seconds Switch 4 1 Mains power switch it is for switch on off the mains power supply 4 2 Battery switch it is for switch on off the battery power supply Power on self test when power on within 5 minutes the panel system will test itself if in the first 5 minutes some zone has fire or fault alarm the panel system will reset the corresponding zone several times until the fire or fault alarm disappeared DIP switch 6 1 6 2 6 3 Main board DIP switch J5 it is for indicating the total number of the zones boards For example if there are 2 pcs zones boards in the panel so the J5 is 2 If there are 5 pcs zones boards in the panel so the J5 is 5 If the main board J5 number is not according to the total zones boards or some zones boards is lost or wrong number for example the main board J5 number is 2 but there is only one zones board and