PowerFlex 22-HIM-A3 and 22-HIM-C2S Series C
Contents
1. Tool Device Version Required DriveExplorer Lite Full software 4 01 or later DriveExecutive software 3 01 or later PowerFlex 4 Class drive all versions compatible External 22 HIM xx Series C HIM all versions compatible RS_Linx Classic software 2 51 or later 7 Rockwell Automation Support Product Satisfaction Return Rockwell Automation provides technical information on the web to assist you in using our products At http support rockwellautomation com you can find technical manuals a knowledge base of Frequently Asked Questions FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools Rockwell Automation also provides complimentary phone support for drives communication adapters and peripherals If you experience a problem with a device please see the information in its User Manual For further help in getting your device operational contact a Customer Support representative United States 1 262 512 8176 Monday Friday 7am 6pm CST Outside United States Please contact your local Rockwell Automation representative for any technical support issues For an additional level of technical phone support for installation configuration and troubleshooting TechConnect Support programs are available For more information contact your local distributor a Rockwell Auto
2. Click OK If the Multiple Assemblies Found window appears select Port X 22 HIM xx SER C from the list and click OK If this window does not appear proceed with step 8 PowerFlex 22 HIM A3 and 22 HIM C2S Series C HIM Firmware Revision 3 001 A 8 With the Firmware Revision window displayed select 3 001 xx from the list of available updates 9 Click Next gt 10 Follow the remaining screen prompts until the update procedure completes and displays the new firmware revision 3 001 Using HyperTerminal Software to Update Firmware 1 With the Flash Kit installed see Installing the Flash Kit on page 4 launch HyperTerminal software 2 Using a 1203 USB or 22 SCM 232 converter go online with the drive that is connected to the HIM 3 Press Enter until the main menu appears Main Menu Enter Number for Selection 1 gt Display Setup Parameters 2 gt Display Event Queue 3 gt Flash Upgrade 4 Inthe main menu press 3 to flash upgrade 5 Press the number key that corresponds to the 22 HIM xx SER C in the list 6 Press Y for Yes to update the firmware The terminal program will start displaying the letter C This signals the Xmodem protocol that the download may proceed You then have one minute to start the transfer ATTENTION Risk of injury or equipment damage exists When you perform an update the drive will fault if it is receiving control I O from the HIM Verify
3. that the drive has stopped safely or is receiving control I O from an alternate source before beginning an update 7 From the Transfer menu choose Send File to display the Send File screen L Send File Folder C Program Files ControlFL4SH 0001 O07E 80FF Filename C Program Files ControlFLASH O0001 007E S0FF Browse 4 Protocol Xmodem v a Click Browse B Navigate to the flash file located in C Program Files ControlFLASH 0001 007E 80FF PowerFlex 22 HIM A3 and 22 HIM C2S Series C HIM Firmware Revision 3 001 C In the Select File to Send window list select the 22 HIM Ax BOOT 2 001 06 bin file D Click Open This file name now appears in the Filename box in the Send File screen E From the Protocol pull down menu choose Xmodem F Click Send A dialog box appears and reports the update progress When complete a Flash Complete message appears Press any key to continue Important Keep the HIM powered for 15 seconds after the operation has completed or until the HIM has re initialized with the drive gt TIP To cancel the flash update at any time press CTRL X 8 Repeat steps 3 through 7 for the 22 HIM Ax APP 3 001 06 bin file 9 Press the Enter key to return to the main menu Restrictions No restrictions apply to this revision of firmware Compatible Revisions To use this revision of firmware update your system tools as follows
4. 1 Determining Firmware This section describes procedures to determine the firmware revision of Revision your external PowerFlex 22 HIM A3 or 22 HIM C2S Series C HIM Using the External 22 HIM A3 or 22 HIM C2S HIM Step 1 Power up the drive 2 Plug the HIM into the drive The Parameters menu for the drive will be displayed 3 Press the GS Sel key until the HIM Setup menu is displayed 4 Press the key to scroll to Device Version 5 Press the Enter key to display the present firmware version of the HIM shown on the Firmware line Using DriveExplorer Lite Full Software 1 Launch DriveExplorer software Example Screens Parameters Groups Linear List Changed Params DIAG EE DSEL MEM SEL gt HIM Setup Parameters Device Version Edit Ref Text PARAM DSEL MEM M SEL gt HIM Setup Parameters Device Version Edit Ref Text PARAM DSEL MEM B SEL gt Device Version 22 HIM CopyCat Keypad Series C Firmware 3 001 01 2 Using a 1203 USB or 22 SCM 232 converter go online with the drive that is connected to the HIM As an alternative when using DriveExplorer Full software you can go online with the drive on Ethernet through a connected 22 COMM E communication adapter 3 In the DriveExplorer treeview select the 22 HIM xx SER C see Figure 1 4 Click the information icon to display the HIM Proper
5. B Introduction Enhancements Corrected Anomalies Release Note PowerFlex 22 HIM A3 and 22 HIM C2S Series C HIM Firmware Revision 3 001 Important PowerFlex 22 HIM A3 C2S Series B HIMs do not exist Series B was intentionally skipped This release note describes major revision 3 minor revision 1 of firmware for the PowerFlex 22 HIM A3 and 22 HIM C2S Series C HIM Human Interface Module Important Firmware 3 001 can only be updated into a 22 HIM A3 C2S Series C HIM and is not compatible with a 22 HIM A3 C2S Series A HIM Conversely firmware 2 006 or earlier is not compatible with a 22HIM A3 C2S Series C HIM The following information is included in this document Topic o Q D Enhancements Corrected Anomalies Determining Firmware Revision Updating the Firmware Restrictions Compatible Revisions Rockwell Automation Support ICO ICO IN IN IS N le Product Satisfaction Return This section describes the enhancements provided in this revision of firmware e The redesigned and simplified circuit board provides better HIM reliability e The HIM is now brand neutral allowing it to successfully connect to and be used with an Allen Bradley brand DSI drive PowerFlex 4 Class or a Reliance Electric brand DSI drive There are no anomalies corrected in this revision of firmware 2 PowerFlex 22 HIM A3 and 22 HIM C2S Series C HIM Firmware Revision 3 00
6. ies screen 5 On the HIM Properties screen click the Component Details tab Important This update may cause the HIM parameters to revert to their default values You may want to save your configuration using DriveExecutive software or the HIM CopyCat feature before updating 6 Click Flash Update to start the update 7 Select the 22 HIM xx SER C from the list of available devices 8 Click Next gt 9 Select 3 001 xx from the list of available updates 10 Click Next gt 11 Follow the remaining screen prompts until the update procedure completes and displays the new firmware revision 3 001 Using ControlFLASH Software to Update Firmware 1 With the Flash Kit installed see Installing the Flash Kit on page 4 choose Start gt All Programs gt Flash Programming Tools gt ControlFLASH to launch the ControlFLASH software 2 On the ControlFLASH Welcome screen click Next gt 3 Choose the appropriate 22 HIM Ax update even though for example you may be updating a 22 HIM C2S from the list of available updates 4 Click Next gt Important This update may cause the HIM parameters to revert to their default values You may want to save your configuration using the HIM CopyCat feature or DriveExplorer or DriveExecutive software before updating 5 Expand the treeview for the communication path you are using and select the drive icon that represents the drive connected to the HIM you are updating 6
7. mation representative or visit http support rockwellautomation com Rockwell Automation tests all products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow the steps below United States Contact your distributor You must provide a Customer Support case number see phone number above to obtain one to your distributor to complete the return process Outside United States Contact your local Rockwell Automation representative for the return procedure U S Allen Bradley Drives Technical Support Tel 1 262 512 8176 Fax 1 262 512 2222 Email support drives ra rockwell com Online www ab com support abdrives www rockwellautomation com Power Conirol and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation Vorstlaan Boulevard du Souverain 36 1170 Brussels Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 22HIM RNO04A EN P September 2012 Copyright 2012 Rockwell Automation Inc All rights reserved Printed in USA
8. o update the HIM See the respective section below and follow the instructions Using DriveExplorer Lite Full Software to Update Firmware 1 With the Flash Kit installed see Installing the Flash Kit launch DriveExplorer software 2 Using a 1203 USB or 22 SCM 232 converter go online with the drive that is connected to the HIM In the DriveExplorer treeview select the 22 HIM xx SER C HIM 4 Click the information icon see Figure 1 to display the HIM Properties screen 5 On the HIM Properties screen click the Details tab Important This update may cause the HIM parameters to revert to their default values You may want to save your configuration using DriveExplorer software or the HIM CopyCat feature before updating Click Flash Update to start the update Select 3 001 xx from the list of available updates Click Next gt een See oat oe Follow the remaining screen prompts until the update procedure completes and displays the new firmware revision 3 001 PowerFlex 22 HIM A3 and 22 HIM C2S Series C HIM Firmware Revision 3 001 5 Using DriveExecutive Software to Update Firmware 1 With the Flash Kit installed see Installing the Flash Kit launch DriveExecutive software 2 Using a 1203 USB or 22 SCM 232 converter go online with the drive that is connected to the HIM In the DriveExecutive treeview select the 22 HIM xx SER C HIM Click the information icon see Figure 2 to display the HIM Propert
9. om Database Source SP Protocol Support DSI DB Created Using DSI Last Upload Unknown Connection Unknown USMEQDMWISNIEZIUSB 1 4 PowerFlex 22 HIM A3 and 22 HIM C2S Series C HIM Firmware Revision 3 001 Updating the Firmware A This section describes procedures to update the HIM firmware Flash kits for drives communications adapters and peripherals are provided on the Allen Bradley Web Updates site at http www ab com support abdrives webupdate Updating can be performed using a 1203 USB or 22 SCM 232 converter For information about how to connect to your drive see their respective User Manual They can be viewed downloaded on the Literature Library website at http www literature rockwellautomation com ATTENTION Risk of permanent equipment damage exists Once an update has been started do not remove power from the drive until after the download has completed and the HIM has re initialized with the connected drive If power is removed before this occurs the HIM may be permanently damaged A HIM that has been damaged in this way cannot be repaired Installing the Flash Kit 1 Go to the Allen Bradley Web Updates site at http www ab com support abdrives webupdate and install the flash kit for the PowerFlex 4 Class HIM Series C which also automatically installs the ControlFLASH software on your computer 2 You are now ready to use DriveExplorer DriveExecutive ControlFLASH or HyperTerminal software t
10. ties screen The Revision field shows the present revision of the HIM firmware for example 3 001 gt TIP When selecting the 22 HIM xx SER C using DriveExplorer Lite or Full software version 5 01 or later the HIM firmware revision is also shown in the right pane of the DriveExplorer window PowerFlex 22 HIM A3 and 22 HIM C2S Series C HIM Firmware Revision 3 001 3 Figure 1 DriveExplorer Window with Information Icon and Device Properties DriveExplorer is erates 22 HIM A3 O PowerFlex 40 1P 110V SOHP Parameter List Parameters 22 HIM A3 1 1203 US8 USB to DST CopyCat Keypad gt Port 2 Custom Views Compare Results Using DriveExecutive Software 1 Launch DriveExecutive 2 Using a 1203 USB or 22 SCM 232 converter go online with the drive that is connected to the HIM 3 In the DriveExecutive treeview select the 22 HIM xx SER C see Figure 2 4 Click the information icon to display the HIM Properties screen 5 The Revision field shows the present revision of the HIM firmware for example 3 001 Figure 2 DriveExecutive Window with Information Icon and Device Properties Q DriveExecutive USB 1 lt PowerFlex 40 gt B 0 Powerflex 40 of Overview fA Linear tist i Ga Parameters Ga Default Custom mG 1 1203 US8 E 22 HIM A3 Properties General Component Detais Product 22 HIM A3 User Text 22 HIMAS Default Cust