1. Reset button Instruction Manual 7 Fault Finding Front panel buttons not working To activate the front panel buttons turn the key switch in the top left of the panel to the ON position Power LED blinks intermittently This is perfectly normal and indicates that the processor is running an internal memory check Fault LED and sense zone fault LED flashing buzzer sounding Faults monitored are e Open circuit on the sense zone wiring e Short circuit on the sense zone wiring e Detector head removal Check all detectors and call points on the sense zone indicated Check wiring is as in example diagrams and ensure the end of line monitor is a 3k3 resistor or an active end of line device Fault LED and alarm zone fault LED flashing buzzer sounding Faults monitored are e Open circuit on the alarm zone wiring e Short circuit on the alarm zone wiring e Blown alarm fuse s Note that drawing excessive current from the 28V Aux supply will blow the fuse in Alarm Zone 2 Check alarm zone wiring is as in example diagrams and ensure that the 10k end of line resistor is fitted Check alarm zone fuses and fuse clips Fault LED flashing and PSU fault LED on buzzer sounding Faults monitored are e Battery supply not present Batteries damaged or not fully charged e Blown battery fuse e Mains supply not present e Blown mains fuse Check relevant fuses and fuse clips Ensure batteries are connected correctly and batt
2. WATCHDOG RESET REST T E BATTERY FUSE 2A Instruction Manual 17 Repeater PCB Board There is one jump JP1 on the repeater PCB board For each one fire alarm control panel can connect 64 repeaters in the same RS485 communication wires The default setting for RS485 JP1 jump is set to position 2 which EOF of RS485 is zero ohm For the end repeater of RS485 the jump JP1 should set to position 1 which the EOF of RS485 is 120 ohm O m U gt m U O DJ Ww O gt UO N oO S 3 o Fa 3 oO CA a 3 S 3 o 5 0 es 8 3 BP CR o 25 D S a gt zi 90 3 5 9 o 2s so 3 B a LS N bar 403 S8vSHy DAD DOD DO DOO A8Z ga v 92 ON ON 2 ON ON A82 18 Fire Alarm Control Panel 1 16 fire 1 16 System Log All events should be properly recorded in this log book An event should include fire alarms whether real or false faults tests temporary disconnections and the dates of installing or servicing engineer s visits with a brief note of work carried out and outstanding Name and address aiment lei eit oOfinstallation aerei lei aaa Person responsible Dates for log book Date ARA dw hee ene Dates am LR Date System installed by and is maintained under contract by o eeeeeeeeeseseeeeeeeeeeeeeeeeeeeeteeeeestaeeeenees Tel ren D re se Ne nie Notes Instruction Manual 19 Date Tim
3. the Silence button again Silencing the internal buzzer If a fault is detected by the panel the internal buzzer will sound To silence the buzzer press the Silence button Using the one man test function To enter test mode press the Test button The test LED will be lit and zone 1 fault LED will be flashing To place zone 1 into test mode press the Silence button Press the Test button again and now zone 2 fault LED will be flashing with zone 1 fault LED on steady if itis in test mode To select further zones press the Test button to cycle through the zones and use the Silence button to toggle the status of the selected zone Placing too many zones into test mode at the same time may leave the building with inadequate protection When a zone in test mode detects a fire event the alarms will ring for a few seconds before resetting If the panel is left in test mode and no events occur for approximately 10 minutes the panel will automatically exit test mode and resume normal operation 6 Fire Alarm Control Panel 1 16 If a fire is detected on a zone not in test then the panel will enter the fire condition and exit test mode To exit test mode and return the panel to normal operation press the Reset button Using the disable function The panel allows the user to selectively disable the sense zones and the alarm zones The selection process is very similar to that used in the test function To enter disable mode press the Dis
4. Fire Alarm Control Panel 1 16 User amp Installation Manual IMPORTANT This manual should be left with the panel after installation We reserve the right to change product specifications without prior notice Notes Instruction Manual 3 Introduction The information provided in this manual covers the fire 1 16 fire alarm control panel The fire range is designed to meet the requirements of EN54 Parts 2 amp 4 This product should be installed commissioned and maintained by suitably qualified service personnel with reference to IEE regulations and any statutory requirements General Description The fire 1 16 range of fire alarm control panels are microprocessor controlled and are available with 1 to 16 sense zones detector zones dependent on the model The panels have 2 alarm zones bell zones zone disable facility one man test a class change input non latching facility a permanent 28V fused supply a 28V supply energised on fire one set of volt free changeover contacts which operate on fault and two sets of volt free changeover contacts which operate on fire Installation Procedure Before proceeding with the installation please read the section Panel Operation Installation of the panel should be carried out by qualified personnel Using the metal box as a template mark the position of the fixing holes on the wall Drill and plug the wall then screw the panel to the wall Ensure the panel is free from knockou
5. able button The disable LED will be lit and zone 1 disable LED will be flashing Pressing the Silence button will toggle the status of the selected zone and pressing the Disable button will cycle through the available zones Once the required zones have been selected press the Reset button If any zones were disabled the disable LED and the relevant zone disable LED s will remain lit All incoming signals from disabled sense zones will be ignored If the alarm zones are disabled then the alarms will not be activated even if the panel detects a fire event on an active sense zone Selecting a zone as non latching In some situations such as interlinking fire alarm panels it is necessary to set a sense zone as non latching When a fire event is detected on a non latching zone the panel will go into fire as usual but will automatically reset as soon as the device signalling fire is reset To enter the non latching selection mode press and hold down the Test button While still holding the Test button momentarily press the CPU RESET button inside the panel followed by the WATCHDOG RESET button Keep the Test button held down until the disable and general fault LEDs light then release the Test button Zone 1 fault and disable LEDs will be flashing Pressing the Silence button will toggle the status of the selected zone and pressing the Test button will cycle through the available zones After the relevant zones have been selected press the
6. e Zone Event Action Required Date Completed Initials 20 Fire Alarm Control Panel 1 16 Date Time Zone Event Action Required Date Completed Initials
7. ery leads are secure Fault LED flashing and 28V fault LED on buzzer sounding The panel has detected a problem with the permanent 28V supply Check the PERM 28V FUSE and fuse clips 8 Fire Alarm Control Panel 1 16 Fault LED flashing and earth fault LED on buzzer sounding The panel has detected an earth fault The only earth connection to the panel terminals should be to the mains input terminal block Check that no other earth connections are present Fault LED and CPU fault LED lit Processor fault detected If no other problems are found then reset the processor Inside the panel are two push buttons marked CPU RESET and WATCHDOG RESET Press CPU RESET followed by WATCHDOG RESET Panel does not indicate fire when a call point or detector is tested Either a faulty call point detector or wiring is not as shown in diagrams Check the firing resistance of the device is 510 200 ohms and ensure that the correct end of line device is fitted Head removal not working Check compatible base is being used and is wired correctly Either a zener clamp base with a 3k3 end of line resistor or a schottky diode base with an active end of line device must be used Fuse ratings Mains fuse 1A A S Alarm fuses F10 amp F11 300mA A S Battery fuse F2 2A A S Permanent 28V fuse F6 125mA A S Other faults For any other faults perform a CPU reset Ins
8. es one at a time makes fault finding and commissioning much simpler Make sure that no bare wires come into contact with the panel circuit boards during installation Detector Head Removal The fire 1 16 range supports head removal The basic principle of head removal is to ensure that all call points will function even if a detector head has been removed Head removal requires either zener clamp bases or schottky diode bases with the appropriate end of line device to be fitted When a detector head is removed the panel will show a fault but the sense zone circuit will remain intact Consult the table on page 9 for further information Instruction Manual 5 Panel Operation Enabling the front panel buttons To enable the front panel buttons the key switch in the top left of the panel must be turned to the On position Performing a lamp test If the panel is in its normal condition pressing the Reset button will cause the panel to perform a lamp test Resetting the panel after a fire is detected To reset the panel after a fire event press the Silence button followed by the Reset button Resetting the panel If any of the panel functions have been activated pressing the Reset button will return the panel to its normal condition Silencing resounding the alarms If a fire is detected the panel will automatically activate the alarm circuits To silence the alarms press the Silence button once To resound the alarms press
9. ide the panel are two push buttons marked CPU RESET and WATCHDOG RESET Press CPU RESET followed by WATCHDOG RESET This will restart the processor but all configuration information disable non latching will have to be re entered Fault Output The fault output marked FAULT on the PCB is a set of volt free changeover contacts When the panel is in fault common C is shorted to normally open NO In normal operation with no faults common C is shorted to normally closed NC Instruction Manual 9 Panel Specifications Rees Ter G Mains Voltage V AC 240 240 System Voltage V DC 28 4 28 4 Quiescent Current Unsilenced Fault mA 115 135 Minimum Battery Size 2 x 12V Required Ah 7 7 Detector Voltage V DC 20 20 Number of Sense Zones 1 8 9 16 Maximum Number of Detectors per Zone 30 30 Firing Resistance Ohms 510 200 510 200 Sense Zone End of Line Ohms 3k3 3k3 Alarm Voltage V DC 28 4 28 4 Number of Alarm Zones 2 2 Maximum Alarm Current per Zone MA 300 300 Maximum Number of Sounders per Zone 16 16 Alarm Zone End of Line Ohms 10k 10k Max Auxiliary Supply Current in Fire MA 50 50 Panel Weight Including Batteries kg 4 15 10 4 25 10 Panel Dimensions mm SIRIA 1999 LES X 87 87 Fire Alarm Control Panel 1 16 10 Detector Base and Call Point Wiring Information P Pa ike Apollo S60 Part Number Terof
10. ire Hochiki Hochiki Apollo Co KAC Call Fulleon Resettable STB 4SDR YBK R 5ZD YBN R 4 Diode Base BASE Point Call Point Call Point Positive In 4 L1 2 L1 IN L1 IN 1 470 Ohms IN Positive Out 4 L2 1 L1 OUT L1 OUT 1 470 Ohms OUT Negative In 1 C5 5 L2 L2 2 COMMON IN Negative Out 6 C6 6 L2 L2 2 COMMON OUT Remote Indicator 4 L1 N A L1 IN L1 IN N A N A N A Positive Remote Indicator E J N A Negative 5 S3 N A R R N A N A I To Suit To Suit To Suit End of Line Device mete End of 3K3 Resistor 3K3 Resistor ACIS End of 3K3 Resistor Detector Detector Detector Line Line Base B ase Base Positive Out Yes Yes No Yes No Instruction Manual 11 Sense Zone Wiring Diagrams Find the detector bases you will be using in the table on page 9 and check to see which end of line device is required either a 3k3 resistor or an active end of line unit The 3k3 resistor should be used if a zone is comprised entirely of call points Sense zone with a 3k3 end of line resistor O one One je EOL SO D Q QO EDR Sense zone with an active end of line Sense Zone Sense Zone The colour bars on a 3k3 resistor are eBuelo eBuelo pai pjo6 Zi O OLO Ore ee EOL Q 0 Q black 0 The panel is supplied with 3k3 end of line resistors as standard Active end of line units are available separately Remote indicator connection details are shown in the table on page 9 12 Fire Alarm Control Panel 1 16 Alarm Zone Wi
11. ll sound Class Change CC Perm 28 Remote C NO Contacts Signalling fire to another panel By connecting two panels as shown below when panel B closes its auxiliary contacts panel A will go into fire If the zone on panel A is set to non latching it will automatically reset when panel B opens its auxiliary contacts If both panels need to signal fire to each other simply duplicate the circuit substituting panel A for panel B and vice versa 510R Resistor Sense O Zone Panel A 3k3 EOL Sense Zone O 7 Instruction Manual 15 Connecting magnetic door holders Low voltage magnetic door holders can be switched using a set of auxiliary contacts in the panel When the panel goes into fire power to the door holders is removed allowing the doors to close Care must be taken to ensure that the auxiliary contacts rating of 24V 1A is not exceeded Mains voltages MUST NOT be switched directly from the auxiliary contacts instead fit a heavy duty relay operated from the auxiliary contacts Door Door Door Holder Holder Holder Panel Auxiliary Contacts Fire Alarm Control Panel 1 16 16 Fire Alarm Control Panel Main PCB Board SENSE ZONES DETECTORS CALL POINTS ALARMZONES AUX AUXILIARY CONTACTS FAULT FETA 1 2 3 4 5 6 7 3 C NC NO C NC NO C NC NO 28V B_A 1D QO olo olo olo ojo ojo olo o bovcoaovdoocvoccadeoco 1D olo olo olo ol olo olo olo o MAIN PCB BOARD CPU
12. ring Diagram The alarm zones are wired as in the diagram below A 10k end of line resistor must be fitted at the end of the circuit Motorised fire bells may be used but solenoid bells MUST NOT be connected to the panel Alarm Zone 10k EOL Alarm Zone If you connect one electric bell into the sound output alarm zone one diode 1N4007 should be connect to the Sound output Alarm Zone and also each electric bell should connect one voltage dependent resistor 70271K 1N4007 Alarm Zone Voltage dependent r Alarm Resistor Resistor Zone Alarm Zone 10k EOL dependent Alarm Resistor Zone Instruction Manual The colour bars on a 10k resistor are Attaching a relay to an alarm zone Alarm Alarm Zone Zone 13 FUIT DR uMoiq yoe q eBuelo pjo6 A relay may be connected anywhere on the alarm zone wiring provided that two diodes 1N4001 or equivalent are fitted as shown in the diagram The end of line resistor is not shown but must be connected at the end of the alarm zone wiring The relay must have a 24V DC coil Alternatively a relay can be connected to the Aux 28V terminals however a diode must still be connected across the coil 14 Fire Alarm Control Panel 1 16 Additional Wiring Information Ringing the alarms remotely The class change CC facility allows a remote source to sound the alarms When the CC terminal is connected to the Perm 28V terminal the alarms wi
13. t discs swarf and other debris Do not remove any end of line resistors from the panel until after the following test is performed With all end of line resistors fitted inside the panel connect the panel mains supply to an exclusive 240V AC fused supply Switch the mains supply on The internal buzzer will sound Connect two sealed lead acid batteries to the panel they should be connected in series providing a 24V DC supply With both the mains and battery supplies connected the panel should be silent and in its normal operating mode power lamp on alarms amp buzzer silent If a fault is indicated refer to the fault finding section before proceeding Disconnect the batteries and switch off the mains supply Remove the 3k3 end of line resistor from sense zone 1 Terminate sense zone 1 circuit wiring in the panel observing correct polarity and fit the end of 4 Fire Alarm Control Panel 1 16 line resistor at the very end of the circuit Check that all the detectors and call points are correctly wired With sense zone 1 connected and all other end of line resistors fitted inside the panel connect the mains and battery supplies If the panel indicates a fault refer to the fault finding section before proceeding Do not megger cables connected to either the panel or any field devices If no faults are indicated then power down the panel and follow the same procedure with the additional sense zones and then the alarm zones Adding the zon