Home

User manual M1

image

Contents

1. Hysterisis for limit values HY Tal m m m A o e g egen aE For all limit values exists a hysterisis function that reacts according to the settings threshold exceedance threshold undercut The limit value undercut can be selected with LOUU LOW lower limit value and limit value exceedance can be selected with HIGH HIGH upper limit value If e g limit value 1 is on a switching threshold of 100 and occupied with function HIGH the alarm will be activated by reaching the threshold If the limit value is allocated to Lak an alarm will be activated by undercut of the threshold 4 Setting up the device Menu level Parameterization level Limit value Limits Li 2 a 00800000250 For both limit values two different values can be parameterized With this the parameters for each limit value are called up one after the other Hysterisis for limit values HY 2 a g el g Pl al el o w P For all limit values exists a hysterisis function that reacts according to the settings threshold exceedance threshold undercut Function if display falls below exceeds limit value FU 2 GH Louw P To indicate if the value falls below the lower limit value LOUU can be selected LOW lower limit value and if it goes above the upper limit value HIGH can be selected HIGH upper limit value LOW corresponds to the quiescent current principle and HIGH to the operating current
2. 4 2 Standard parameterization 4 3 Extended parameterization 4 3 1 Min Max value inquiry TAST 4 3 2 Flashing of display FLAS 4 3 3 Threshold values F to Li c 4 3 4 Setpoints SPET Factory settings 5 1 Default values 5 2 Reset to default settings Technical data Safety advice Error elimination gt 0 0 0 N 01 A oa A O N k k oe ek oo fF a O O 1 Assembly 1 Assembly Please read the Safety advice on page 16 before installation and keep this user manual for future reference gt A SR S Gap for physical ce unit aw 4 After removing the fixing elements insert the device Check the seal to make sure it fits securely 3 Click the fixing elements back into place and tighten the clamping screws by hand Then use a screwdriver to tighten them another half a turn N CAUTION The torque should not exceed 0 1 Nm The dimension symbols can be exchanged before installation via a channel on the side 2 Electrical connection Type M1 1VR4B 0001 570BD with a supply of 230 VAC Input Supply Power supply 230 VAC 0 4 20 mA 0 10 V Connection examples Type M1 1VR4B 0001 770BD with a supply of 24 VDC ab Power supply 24 VDC 0 4 20 mA 0 10 V 2 Electrical connection Below you find some connection examples which demonstrate some practical applications M1 in combination with a 2 wire sensor 4 20 m
3. DIN 61010 15 6 Technical data 7 Safety advices 7 Safety advice Please read the following safety advice and the assembly chapter 1 before installation and keep it for future reference Proper use The M1 device is designed for the evaluation and display of sensor signals Danger Careless use or improper operation can result in personal injury and or damage to the equipment Control of the device The panel meters are checked before dispatch and sent out in perfect condition Should there be any visible damage we recommend close examination of the packaging Please inform the supplier immediately of any damage Installation The M1 device must be installed by a suitably qualified specialist e g with a qualification in industrial electronics Notes on installation e There must be no magnetic or electric fields in the vicinity of the device e g due to transformers mobile phones or electrostatic discharge e The fuse rating of the supply voltage should not exceed a value of 6A N B fuse e Do not install inductive consumers relays solenoid valves etc near the device and suppress any interference with the aid of RC spark extinguishing combinations or free wheeling diodes e Keep input output and supply lines separate from one another and do not lay them parallel with each other Position go and return lines next to one another Where possible use twisted pair So you receive best measuring resul
4. voltage signal it is only connected on one side or the input is open Not all of the activated setpoints are parameterised Check if the relevant parameter are adjusted correctly e The unit has found an error in the configuration memory Perform a reset on the default values and re configure the unit according to your application Program numbers for parameterising e Programming lock is activated of the input are not accessible Enter correct code ERRT lights up in the 7 segment display The device does not react as expected Please contact the manufaturer if errors of this kind occur e If you are not sure if the device has been parameterised before then follow the steps as written in chapter 5 2 and set it back to its delivery status 17 M1_11GB pdf Stand Oktober 2009
5. A 24 VDC M1 in combination with a 3 wire sensor 0 10 V 24 VDC M1 in combination with a 3 wire sensor 0 4 20 mA 24 VDC 3 Function and operation descirption 3 Function and operation description Operation The operation is divided into two different levels Menu Level Here it is possible to navigate between the individual menu items Parameterization level The parameters stored in the menu item can be parameterized here Functions that can be adjusted or changed are always indicated with a flashing of the display Adjustments made at the parameterization level should be always confirmed by pressing the P key to save them However the display automatically saves all adjustments and then switches to operation mode if no further keys are pressed within 10 seconds Change to parameterization level with the relevant parameters Menu level For navigation at the menu level To confirm the changes made at the parameterization level Parameterization level To change the value or setting Beispiel Parameterization level 4 Setting up the device 4 Setting up the device 4 1 Switching on Once the installation is complete you can start the device by applying the voltage supply Before check once again that all electrical connections are correct Starting sequence For 1 second during the switching on process the segment test 8 8 8 8 is displayed followed by an indication of t
6. User manual M1 Standard signal 0 4 20 mA 0 10 V Technical features e red display of 1999 9999 digits optional green orange or blue display e minimal installation depth 25 mm without plug in terminal e min max value recording e 10 parameter driven setpoints e optical threshold value indication e tara offset value calibration e zero point tranquilization programming interlock via access code e protection class IP65 e plug in terminal 96x48 Identification STANDARD TYPES Direct voltage current Housing size 96x48 mm Options breakdown of order code Standard type M Line Installation depth Short plug in terminal 38 mm Housing size 96x48x25 mm without plug in terminal gt Display type Current voltage k Display colours Blue Green Red Orange lt l gt jo o Number of digits 4 digit gt Digit height e Ml Please state physical unit by order e g m min ORDER NUMBER M1 1VR4B 0001 570BD M1 1VR4B 0001 770BD Dimension D Physical unit Version Ble Setpoints no setpoints Protection class 7 iP6s plug in terminal Voltage supply 230 VAC 24 VDC galv insulated Measuring input 1 Standard signal 0 4 20 mA 0 10VDC Analog output without Sensor supply o Jwithout Contents A A Assembly Electrical connection Function and operation description Setting up the device 4 1 Switching on
7. ads alarm S1 S2 is on below the threshold and switched off on reaching the threshold jo Uua eJ v activated Off Display Hysterisis Alarms optical setpoint display An activated set point can be optically indicated by flashing of the 7 segment display Functional principle of the alarms Alarms Deactivated display value Threshold Threshold limit value for switch over Width of the window between the thresholds Function Limit value exceedance limit value undercut 11 5 Factory settings 5 Factory settings 5 1 Default values E3 3 Tic E3 153 m mca E 2313 no a an Em an A Sl nen Sel myo a oyo ion 1 Onyonjco onjon jo Halna co mon LR an un an 2 tn En un T O O o a yee My Eon fan a gt Lafen fono mimo e cl ole njoj si am t1 Oo no cn aS pa Pat THT A A pa on En a T N A D nan D ae in Y ny ny Ny nano ay E 2 on mo z N ny uy ny ny m ny Sa ea Er Eno nin ii mio Wl Lao Ale 12 5 Factory settings Default 5 2 Reset to default values To return the unit to a defined basic state a reset can be carried out to the default values The following procedure should be used e Switch off the power supply e Press button P e Switch on voltage supply and press P button until is shown in the display With reset the default values of the program table are loaded and used for sub
8. digit with P After the last digit the display switches back to the menu level If SENS was selected as the input option you can only select between NOCA and CAL With NOCA only the previously set display value is taken over and with CAL the device takes over both the display value and the analogue input value 4 Setting up the device Menu level Parameterization level Setting the decimal point DOT The decimal point on the display can be moved with A W and confirmed with P The display then switches back to the menu level again The display time is set with A W The display moves up in increments of 0 1 sec up to 1 sec and in increments of 1 0 sec to 10 0 sec Confirm the selection by pressing the P button The display then switches back to the menu level again Activation deactivation of the programming lock and completion of the standard parameterization RUN With the aid of the A Y keys you can choose between the deactivated key lock ULOC works setting and the activated key lock LOC Make the selection with P After this the display confirms the settings with and automatically switches to operating mode If LOC was selected the keyboard is locked To get back into the menu level you must press P for 3 seconds in operating mode You must now enter the CODE works setting 72 3 Y that ap
9. he device Menu level Parameterization level 4 3 1 MIN MAX value inquiry Assignment of key functions TAST EHEr Lb a no P Here you can enter for the operating mode either a MIN MAX value inquiry a threshold value correction or a tara function on the arrow keys If the MIN MAX memory is activated with EHER the measured MIN MAX values will be saved during operation and can be called up via the arrow keys A Y The values are lost if the device is restarted If the threshold value correction Li 7 is selected the limit values can be changed during operation without hindering the operating procedure With the tara function the device can be set on a temporarily parameterized value This function is activated by pushing the two arrow keys W A simultaneously The device receipts the correct taring by showing 0000 in the display If NO is parameterized the arrow keys V A have no function in operating mode 4 3 2 Flashing of display FLAS Lil alo LP Here flashing of the display can be added as an extra alarm function either to the first limit value select LIi the second limit value select Li 2 or to both limit values select 18 With NO works setting no flashing is assigned at all 4 3 3 Limit values Limits L DO OA For both limit values two different values can be parameterized With this the parameters for each limit value are called up one after the other
10. he software type and after that also for 1 second the software version After the starting sequence the device switches to operation display mode 4 2 Standard parameterization To parameterize the display press the P key in operating mode for 1 second The display then changes to the menu level with the first menu item TYPE Menu level Parameterization level Selection of the input signal TYPE JD z 4 20 a SEn5 P There are several measuring input options 0 4 20 mA or 0 10 VDC signals as works calibration without application of the sensor signal and SENS as sensor calibration with the sensor applied Confirm the selection with P and the display switches back to menu level Setting the measuring range end value END aighg hg agen A E Md Set the end value from the smallest to the largest digit with A W and confirm each digit with P A minus sign can only be parametrized on the highest value digit After the last digit the display switches back to the menu level If SENS was selected as the input option you can only select between NOCA and CAL With NOCA only the previously set display value is taken over and with AL the device takes over both the display value and the analogue input value Setting the measuring range start offset value OFFS 5 _ la ICA al Enter the start offset value from the smallest to the largest digit A W and confirm each
11. pears using the A W keys plus P to unlock the keyboard FAIL appears if the input is wrong 4 Setting up the device 4 3 Extended parameterization By pressing the A 8 W buttons during standard parameterization for one second the display switches to the extended parameterization mode Operation is the same as in standard parameterization Menu level Parameterization Rescaling the measuring input values ENDA Ci Ci g g P g P geg aP With the aid of this function you can rescale the input value of e g 19 5 mA works setting without applying a measuring signal If sensor calibration has been selected these parameters are not available Rescaling the measuring input values OFFA a geXghigbg Ae With the aid of this function you can rescale the input value of e g 3 5 mA works setting without applying a measuring signal If sensor calibration has been selected these parameters are not available Setting up the tare offset value TARA OA The given value is added to the linerarized value In this way the characteristic line can be shifted by the selected amount Zero point tranquilization ZERO gn r With zero point tranquilization a value range around zero can be preselected at which the display shows zero If for example a 10 is set the display would show a zero in the range from 10 to 10 and continue below it with 11 and above it with 11 4 Setting up t
12. principle Setting the code CODE 7 J ya E p ege y ye With this setting it is possible to select an individual code works setting 1 2 3 4 for locking the keyboard To lock release the key proceed according to menu item RUN 4 3 4 Set points Number of additional set points SPCT m lA own In addition to the start and end value 8 extra set points can be defined to linearize non linear sensor values Only the activated set point parameters are displayed 4 Setting up the device Menu level Parameterization level Display values for set points DISI DISS ni 1 Ol ana PA Under this parameter the setpoints are defined on a value basis At the sensor calibration one will be asked at the end like at Endwert Offset too if a calibration shall be triggered Analogue values for set points INP INP8 Ape sae Ve Setpoints are only displayed under works calibration 4 20 mA Here you can choose your analog values The entry of constantly rising values need to be done self contained 10 4 Setting up the device Functional principle of the set points Alarms Limit value exceedance HIGH By limit value exceedance the STE ve alarm S1 S2 is off below the 1 threshold and on on reaching the threshold fallen off pajenoe y A I Off Display Hysterisis RA Alarms Limit value undercut LOW By limit value undercut the AE
13. sequent operation This puts the unit back to the state in which it was supplied Caution All application related data are lost 13 6 Technical data 6 Technical data 96x48x25 mm BxHxT 96x48x41 mm BxHxT including plug in terminal Panel cut out 96x48 92 0 0 8 x 45 0 0 mm Insulation thickness up to 3 mm Fixing snap in screw element PC Polycarbonate black UL94V 0 EPDM 65 Shore black standard IP65 front IPOO back side Material Sealing material Protection class Weight approx 50 g Connection plug in terminal wire cross section up to 2 5 mm2 Display Digit height 14 mm 0 oa Segment colour Display range 1999 bis 9999 Setpoints optical display flashing Overflow Underflow horizontal bars at the top horizontal bars at the bottom 0 1 to 10 0 seconds min 22 max 24mA 0 4 20 mA 100 0 0 1 of measuring range min 12 max 12 VDC 0 10 VDC 100kQ 0 1 of measuring range Temperature drift 100 ppm K 0 1 10 0 seconds Display time Measuring time Measuring principle U F conversion Resolution Power pack 230 VAC 10 max 6 VA 24 VDC 10 max 1 VA Memory EEPROM Data life approx 18 Bit at 1s measuring time gt 100 years 14 Ambient conditions Working temperature Storing temperature Climatic density CE sign Safety standard 0 60 C 20 80 C relative humidity 0 80 on years average without dew DIN 61326 Conformity to 89 336 EWG
14. ts e Screen off and twist sensor lines Do not lay current carrying lines in the vicinity Connect the screening on one side on a suitable potential equaliser normally signal ground e The device is not suitable for installation in areas where there is a risk of explosion e Any electrical connection deviating from the connection diagram can endanger human life and or can destroy the equipment e The terminal area of the devices is part of the service Here electrostatic discharge needs to be avoided Attention High voltages can cause dangerous body currents e Galvanic insulated potentials within one complex need to be placed on a appropriate point normally earth or machines ground So a lower disturbance sensibility against impacted energy can be reached and dangerous potentials that can occur on long lines or due to faulty wiring can be avoided 16 8 Error elimination 8 Error elimination The unit permanently indicates overflow The unit permanently shows underflow The word HELP lights up in the 7 segment display e The input has a very high measurement check the measuring circuit e With a selected input with a low voltage signal it is only connected on one side or the input is open Not all of the activated setpoints are parameterised Check if the relevant parameter are adjusted correctly e The input has a very low measurement check the measuring circuit e With a selected input with a low

Download Pdf Manuals

image

Related Search

Related Contents

    Flan Pâtissier ou Crème Pâtissière NESTLÉ Docello™ Etui de 1,2    Manual para el usuario de PowerPark P13405-02  UP200-GSM Manual - DuPol - GSM Door Phone, GSM Intercom  取扱説明書 お客さまへ    Control Features    

Copyright © All rights reserved.
DMCA: DMCA_mwitty#outlook.com.