Home
        User manual M1
         Contents
1.    Hysterisis for limit values  HY       Tal m m m A  o e g egen aE       For all limit values exists a hysterisis function  that reacts according to the settings   threshold exceedance   threshold undercut                        The limit value undercut can be selected with LOUU  LOW   lower limit value  and limit  value exceedance can be selected with HIGH  HIGH   upper limit value   If e g  limit  value 1 is on a switching threshold of 100 and occupied with function    HIGH     the alarm  will be activated by reaching the threshold  If the limit value is allocated to    Lak     an  alarm will be activated by undercut of the threshold        4  Setting up the device    Menu level Parameterization level    Limit value  Limits  Li 2  a   00800000250    For both limit values  two different values can be parameterized  With this  the  parameters for each limit value are called up one after the other     Hysterisis for limit values  HY 2  a   g  el g  Pl  al  el o w   P     For all limit values exists a hysterisis function  that reacts according to the settings   threshold exceedance   threshold undercut         Function if display falls below   exceeds limit value  FU 2   GH     Louw      P   To indicate if the value falls below the lower limit value  LOUU can be selected  LOW    lower limit value  and if it goes above the upper limit value  HIGH can be selected     HIGH   upper limit value   LOW corresponds to the quiescent current principle and  HIGH to the operating current 
2.   4 2  Standard parameterization   4 3  Extended parameterization  4 3 1  Min Max value inquiry    TAST     4 3 2  Flashing of display    FLAS     4 3 3  Threshold values      F to   Li c  4 3 4  Setpoints    SPET      Factory settings   5 1  Default values   5 2  Reset to default settings   Technical data   Safety advice    Error elimination     gt     0 0 0 N 01 A oa A O N       k  k oe ek  oo fF  a O O    1  Assembly  1  Assembly    Please read the Safety advice on page 16 before installation and keep this user manual for  future reference                                 gt     A   SR S  Gap for physical ce  unit aw       4    After removing the fixing elements  insert the device    Check the seal to make sure it fits securely    3  Click the fixing elements back into place and tighten the clamping screws by hand   Then use a screwdriver to tighten them another half a turn     N    CAUTION  The torque should not exceed 0 1 Nm     The dimension symbols can be exchanged before installation via a channel on the side     2  Electrical connection    Type M1 1VR4B 0001 570BD  with a supply of 230 VAC       Input Supply    Power supply  230 VAC  0 4    20 mA             0   10 V    Connection examples     Type M1 1VR4B 0001 770BD  with a supply of 24 VDC       ab Power supply  24 VDC    0 4    20 mA       0   10 V    2  Electrical connection    Below you find some connection examples  which demonstrate some practical applications     M1 in combination with a  2 wire sensor 4 20 m
3.   DIN 61010    15    6  Technical data       7  Safety advices  7  Safety advice    Please read the following safety advice and the assembly chapter 1 before installation  and keep it for future reference     Proper use  The M1 device is designed for the evaluation and display of sensor signals     Danger  Careless use or improper operation can result in  personal injury and or damage to the equipment     Control of the device    The panel meters are checked before dispatch and sent out in perfect condition  Should  there be any visible damage  we recommend close examination of the packaging  Please  inform the supplier immediately of any damage     Installation    The M1 device must be installed by a suitably qualified specialist  e g  with a  qualification in industrial electronics      Notes on installation    e There must be no magnetic or electric fields in the vicinity of the device  e g  due to  transformers  mobile phones or electrostatic discharge     e The fuse rating of the supply voltage should not exceed a value of 6A N B  fuse     e Do not install inductive consumers  relays  solenoid valves etc   near the device  and suppress any interference with the aid of RC spark extinguishing combinations  or free wheeling diodes     e Keep input  output and supply lines separate from one another and do not lay them  parallel with each other  Position    go    and    return lines    next to one another  Where  possible use twisted pair  So  you receive best measuring resul
4.  voltage signal  it is  only connected on one side or the input is open       Not all of the activated setpoints are parameterised   Check if the relevant parameter are adjusted  correctly     e The unit has found an error in the configuration  memory  Perform a reset on the default values and  re configure the unit according to your application     Program numbers for parameterising e Programming lock is activated  of the input are not accessible    Enter correct code     ERRT lights up in the 7 segment  display    The device does not react as  expected           Please contact the manufaturer if errors of this kind  occur     e If you are not sure if the device has been  parameterised before  then follow the steps as  written in chapter 5 2  and set it back to its delivery  status     17       M1_11GB pdf Stand  Oktober 2009    
5. A       24 VDC    M1 in combination with a  3 wire sensor 0 10 V       24 VDC    M1 in combination with a  3 wire sensor 0 4 20 mA       24 VDC       3  Function and operation descirption  3  Function and operation description    Operation  The operation is divided into two different levels     Menu Level  Here it is possible to navigate between the individual menu items     Parameterization level    The parameters stored in the menu item can be parameterized here    Functions that can be adjusted or changed are always indicated with a flashing of the display   Adjustments made at the parameterization level should be always confirmed by pressing the   P  key to save them    However  the display automatically saves all adjustments and then switches to operation mode  if no further keys are pressed within 10 seconds     Change to parameterization level with the relevant parameters  Menu level  For navigation at the menu level    To confirm the changes made at the parameterization level    Parameterization    level To change the value or setting    Beispiel     Parameterization level                         4  Setting up the device  4  Setting up the device    4 1  Switching on   Once the installation is complete  you can start the device by applying the voltage supply   Before  check once again that all electrical connections are correct    Starting sequence    For 1 second during the switching on process  the segment test  8 8 8 8  is displayed  followed  by an indication of t
6. User manual M1    Standard signal 0 4 20 mA  0 10 V       Technical features     e red display of  1999   9999 digits  optional  green  orange or blue display   e minimal installation depth  25 mm without plug in terminal   e min  max value recording   e 10 parameter driven setpoints   e optical threshold value indication   e tara    offset value calibration   e zero point tranquilization     programming interlock via access code   e protection class IP65   e plug in terminal    96x48       Identification    STANDARD TYPES    Direct voltage  current  Housing size  96x48 mm       Options     breakdown of order code     Standard type M Line    Installation depth    Short  plug in terminal    38 mm    Housing size  96x48x25 mm   without plug in terminal       gt      Display type  Current  voltage    k     Display colours  Blue   Green   Red   Orange     lt l gt  jo  o     Number of digits  4 digit      gt      Digit height    e  Ml      Please state physical unit by order  e g  m min     ORDER NUMBER    M1 1VR4B 0001 570BD  M1 1VR4B 0001 770BD    Dimension     D  Physical unit    Version     Ble    Setpoints  no setpoints    Protection class     7  iP6s   plug in terminal    Voltage supply  230 VAC  24 VDC galv  insulated    Measuring input    1  Standard signal 0 4 20 mA   0 10VDC    Analog output  without    Sensor supply     o Jwithout       Contents    A A      Assembly   Electrical connection   Function and operation description   Setting up the device   4 1  Switching on 
7. ads alarm S1 S2 is on below the  threshold and switched off on  reaching the threshold     jo Uua   eJ    v    activated       Off Display    Hysterisis    Alarms   optical setpoint display    An activated set point can be optically indicated by flashing of the 7 segment display     Functional principle of the alarms  Alarms Deactivated  display value    Threshold Threshold limit value for switch over  Width of the window between the thresholds  Function   Limit value exceedance   limit value undercut       11    5  Factory settings    5  Factory settings    5 1  Default values    E3   3 Tic  E3 153 m  mca  E 2313    no a an Em an A Sl   nen  Sel myo a oyo ion  1  Onyonjco onjon  jo Halna  co mon LR an un an 2 tn En  un  T  O O o  a yee  My  Eon fan a    gt  Lafen fono mimo  e cl ole njoj  si am t1 Oo no cn  aS pa    Pat THT    A A    pa  on    En a T N    A    D  nan    D  ae    in    Y    ny  ny     Ny  nano  ay    E  2    on   mo      z N    ny  uy    ny  ny    m  ny    Sa ea Er      Eno    nin    ii    mio            Wl     Lao    Ale       12    5  Factory settings    Default       5 2  Reset to default values    To return the unit to a defined basic state  a reset can be carried out to the default values     The following procedure should be used    e Switch off the power supply   e Press button  P    e Switch on voltage supply and press  P  button until           is shown in the display     With reset  the default values of the program table are loaded and used for sub
8. digit with  P   After the last digit the display switches back to the menu level  If  SENS was selected as the input option  you can only select between NOCA and CAL  With  NOCA  only the previously set display value is taken over  and with CAL  the device takes  over both the display value and the analogue input value              4  Setting up the device    Menu level Parameterization level    Setting the decimal point  DOT                          The decimal point on the display can be moved with  A   W  and confirmed with  P    The display then switches back to the menu level again                                                              The display time is set with  A   W   The display moves up in increments of 0 1 sec up  to 1 sec and in increments of 1 0 sec to 10 0 sec  Confirm the selection by pressing  the  P  button  The display then switches back to the menu level again     Activation   deactivation of the programming lock and completion of the  standard parameterization  RUN                          With the aid of the  A   Y  keys  you can choose between the deactivated key lock  ULOC  works setting  and the activated key lock LOC  Make the selection with  P   After  this  the display confirms the settings with              and automatically switches to  operating mode  If LOC was selected  the keyboard is locked  To get back into the  menu level  you must press  P  for 3 seconds in operating mode  You must now enter  the CODE  works setting 72 3 Y  that ap
9. he device    Menu level Parameterization level    4 3 1  MIN MAX value inquiry   Assignment of key functions  TAST     EHEr     Lb a no  P   Here  you can enter for the operating mode either a MIN MAX value inquiry  a  threshold value correction or a tara function on the arrow keys   If the MIN MAX memory is activated with EHER  the measured MIN MAX values will be  saved during operation and can be called up via the arrow keys  A   Y   The values  are lost if the device is restarted   If the threshold value correction Li 7 is selected  the limit values can be changed during  operation without hindering the operating procedure   With the tara function the device can be set on a temporarily parameterized value   This function is activated by pushing the two arrow keys W   A  simultaneously  The  device receipts the correct taring by showing    0000    in the display   If NO is parameterized  the arrow keys  V   A  have no function in operating mode     4 3 2  Flashing of display  FLAS     Lil    alo  LP     Here  flashing of the display can be added as an extra alarm function  either to the first  limit value  select  LIi    the second limit value  select  Li 2  or to both limit values   select      18   With NO  works setting   no flashing is assigned at all     4 3 3  Limit values   Limits  L        DO OA                         For both limit values  two different values can be parameterized  With this  the  parameters for each limit value are called up one after the other  
10. he software type and  after that  also for 1 second  the software version   After the starting sequence  the device switches to operation display mode     4 2  Standard parameterization     To parameterize the display  press the  P  key in operating mode for 1 second  The display  then changes to the menu level with the first menu item TYPE     Menu level Parameterization level    Selection of the input signal  TYPE    JD z 4 20 a SEn5  P    There are several measuring input options  0 4 20 mA or 0 10 VDC signals as works  calibration  without application of the sensor signal  and SENS as sensor calibration     with the sensor applied   Confirm the selection with  P  and the display switches back  to menu level                       Setting the measuring range end value  END     aighg hg    agen A E                            Md    Set the end value from the smallest to the largest digit with  A   W  and confirm each  digit with  P   A minus sign can only be parametrized on the highest value digit  After  the last digit  the display switches back to the menu level  If SENS was selected as the  input option  you can only select between NOCA and CAL  With NOCA  only the previously  set display value is taken over  and with   AL  the device takes over both the display  value and the analogue input value     Setting the measuring range start offset value  OFFS     5     _ la  ICA  al    Enter the start offset value from the smallest to the largest digit  A   W  and confirm  each 
11. pears using the  A   W  keys plus  P  to unlock  the keyboard  FAIL appears if the input is wrong        4  Setting up the device    4 3  Extended parameterization    By pressing the  A  8  W  buttons during standard parameterization for one second  the  display switches to the extended parameterization mode   Operation is the same as in standard parameterization     Menu level Parameterization    Rescaling the measuring input values  ENDA     Ci Ci g     g P  g P geg aP    With the aid of this function  you can rescale the input value of e g  19 5 mA  works  setting  without applying a measuring signal  If sensor calibration has been selected   these parameters are not available                 Rescaling the measuring input values  OFFA      a   geXghigbg Ae    With the aid of this function  you can rescale the input value of e g  3 5 mA  works  setting  without applying a measuring signal  If sensor calibration has been selected   these parameters are not available        Setting up the tare offset value  TARA     OA       The given value is added to the linerarized value  In this way  the characteristic line  can be shifted by the selected amount       Zero point tranquilization  ZERO     gn  r       With zero point tranquilization  a value range around zero can be preselected at which  the display shows zero  If  for example  a 10 is set  the display would show a zero in  the range from  10 to  10 and continue below it with  11 and above it with  11        4  Setting up t
12. principle     Setting the code  CODE       7 J ya   E p ege y ye                      With this setting  it is possible to select an individual code  works setting 1 2 3 4   for  locking the keyboard  To lock release the key  proceed according to menu item RUN     4 3 4  Set points   Number of additional set points  SPCT     m lA   own       In addition to the start and end value  8 extra set points can be defined to linearize  non linear sensor values  Only the activated set point parameters are displayed        4  Setting up the device    Menu level Parameterization level    Display values for set points DISI     DISS   ni    1 Ol ana    PA                Under this parameter the setpoints are defined on a value basis  At the sensor  calibration one will be asked at the end  like at Endwert Offset  too   if a calibration  shall be triggered     Analogue values for set points INP     INP8     Ape sae Ve       Setpoints are only displayed under works calibration  4 20 mA   Here you can choose  your analog values  The entry of constantly rising values need to be done self   contained        10    4  Setting up the device    Functional principle of the set points    Alarms Limit value exceedance    HIGH              By limit value exceedance the    STE ve   alarm S1 S2 is off below the    1 threshold and on on reaching the  threshold     fallen off  pajenoe    y A    I  Off Display    Hysterisis    RA     Alarms Limit value undercut    LOW       By limit value undercut the  AE 
13. sequent  operation  This puts the unit back to the state in which it was supplied     Caution  All application related data are lost     13    6  Technical data    6  Technical data    96x48x25 mm  BxHxT    96x48x41 mm  BxHxT  including plug in terminal  Panel cut out  96x48 92 0 0 8 x 45 0 0 mm  Insulation thickness up to 3 mm  Fixing snap in screw element   PC Polycarbonate  black  UL94V 0  EPDM  65 Shore  black    standard IP65  front   IPOO  back side     Material  Sealing material  Protection class    Weight approx  50 g    Connection plug in terminal  wire cross section up to 2 5 mm2    Display    Digit height 14 mm    0   oa    Segment colour  Display range  1999 bis 9999  Setpoints optical display flashing  Overflow    Underflow    horizontal bars at the top    horizontal bars at the bottom    0 1 to 10 0 seconds    min   22   max 24mA   0 4 20 mA 100 0 0 1   of measuring range  min   12   max  12 VDC   0 10 VDC 100kQ   0 1  of measuring range    Temperature drift 100 ppm  K  0 1   10 0 seconds    Display time    Measuring time  Measuring principle U F conversion  Resolution    Power pack 230 VAC     10   max  6 VA  24 VDC     10   max  1 VA    Memory EEPROM  Data life    approx  18 Bit at 1s measuring time     gt  100 years       14    Ambient conditions  Working temperature    Storing temperature    Climatic density    CE sign    Safety standard    0   60  C    20   80  C   relative humidity 0 80  on years average without dew  DIN 61326    Conformity to 89 336 EWG  
14. ts     e Screen off and twist sensor lines  Do not lay current carrying lines in the vicinity   Connect the screening on one side on a suitable potential equaliser  normally  signal ground      e The device is not suitable for installation in areas where there is a risk of explosion     e Any electrical connection deviating from the connection diagram can endanger  human life and or can destroy the equipment     e The terminal area of the devices is part of the service  Here electrostatic discharge  needs to be avoided  Attention  High voltages can cause dangerous body currents     e Galvanic insulated potentials within one complex need to be placed on a  appropriate point  normally earth or machines ground   So  a lower disturbance  sensibility against impacted energy can be reached and dangerous potentials  that  can occur on long lines or due to faulty wiring  can be avoided     16    8  Error elimination    8  Error elimination    The unit permanently indicates  overflow     The unit permanently shows  underflow     The word  HELP  lights up in the 7   segment display     e The input has a very high measurement  check the  measuring circuit    e With a selected input with a low voltage signal  it is  only connected on one side or the input is open       Not all of the activated setpoints are parameterised   Check if the relevant parameter are adjusted  correctly     e The input has a very low measurement  check the  measuring circuit     e With a selected input with a low
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Brodit ProClip 854925  "service manual"  DJA802 - Billiger.de  INSTALLATION MANUAL  Phoenix Gold Speaker ATc8 User's Manual  取扱説明書  Procès verbal du 23 mars 2012  Le marketing est mort. Vive le Marketing  Z-337J/338J User`s Manual  3226-TLMB User`s Manual 20070430.indd    Copyright © All rights reserved. 
   Failed to retrieve file