Home

- Owl Security Services

image

Contents

1. GT490X Engineer s Reference Guide The readings given from this point on are intended as Indicator Only and should be confirmed with a calibrated Test Meter 21 Press No The display will show for example oe 13 6V 22 Press Yes The display will show for example Battery Volts On Charge 13 6V 23 Press Yes The display will show Battery Volts Off Charge 12 9V The backlight will Dim at this point 24 Press Yes The display will show Aux Volts 13 6V 25 This concludes the Program Diagnostics Press 0 zero until the display shows 01 Jan 00 00 01 Page 79 GT490X Engineer s Reference Guide Programming Alarm Confirm This section is used to program options that are relevant to BS8243 Before programming these options please take time to read the following notes that will help in your understanding of BS8243 All communications systems that require a Police URN will need to conform to BS8243 These notes intended as a guide only and should be read in conjunction with the relevant standards relating to the alarm system giving particular attention to EN50131 1and BS8243 These may be obtained from the British Standards Institute BS8243 options available are Confirm Time Window default 60 This time window may be programmed between 1 and 120 minutes To comply the required time should be between 30 and 60 minute
2. Cus 1 Zone gt ___ Day Fol t 00 Cus 1 Zone gt 009 gt Day Fol t 00 Cus 1 Zone gt 009 Day gt Fol t 00 Cus 1 Zone gt 009 Day Fol t gt 00 Cus 1 Zone gt 009 Day Fol t Cus 2 Zone 000 Day Fol t 00 Program es PGM1 Custom 00 00 01 GT490X Engineer s Reference Guide Programming Engineer Code 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing 2 Press No twelve times The display will show 3 Press Yes The display will show 4 Enter your New Engineer Code 4 5 or six digits followed by Yes The display will show Program Zones Program Engineer Code Now Enter Code Then YES Code Unlocked Be careful if you lock your code in If the code is forgotten you may have to return the control panel to the factory to have it unlocked this will be a chargeable service 5 Press No until the required setting is displayed then press Yes The display will show 6 This concludes the Program Engineer Code Press 0 zero twice to return to Page 72 Program Engineer Code 01 Jan 00 00 01 GT490X Engineer s Reference Guide Programming Service Within this section you will program the Service Timer Also if required uplo
3. Program Confirm Secondary Time Program Confirm ET Mode ET Mode Set Only Program Confirm ET Mode Program Confirm Bell Mode 25 26 27 28 29 30 31 32 33 GT490X Engineer s Reference Guide Press Yes The display will show Press No until the required setting is displayed then press Yes The display will show Press No The display will show Press Yes The display will show Press No until the required setting is displayed then press Yes The display will show Press No The display will show Press Yes The display will show Press No twice The display will show Enter the time required followed by Yes The display will show Page 87 Bell Trigger Unconfirmed Program Confirm Bell Mode Program Confirm Strobe Mode Strobe Trigger Unconfirmed Program Confirm Strobe Mode Program Confirm Start Delay Start Delay 000m Start Delay gt m Program Confirm Start Delay GT490X Engineer s Reference Guide 34 Press No 35 Press Yes The display will show The display will show 36 Press No until the required setting is displayed then press Yes The display will show
4. Install Keypad Enter Keypad _ then YES or NO Press NO YES on Selected Keypad Keypad Installed OK 22 23 24 25 26 27 28 29 30 GT490X Engineer s Reference Guide Then Repeat from Step 19 until all the RKPs have ben installed onto the system Press 0 zero The display will show Press No The display will show Press Yes The display will show Press No until the setting you require is displayed then press Yes The display will show Press No The display will show Press Yes The display will show Note Use of this option will require a compatible G Tag RKP Enter Keypad _ then YES or NO Program Keypad Number Program Keypad Backlight Mode Backlight On if EE Key Program Keypad Backlight Mode Program Keypad ACE Prox Prox Tamp Detect Off Default is Off but maybe changed to On It is intended for use with the external prox reader E Reader and monitors the antenna of the reader for being disconnected Press No until the setting you require is displayed then press Yes The display will show This concludes the programming for Keypad Press 0 zero to return to Or Press 0 zero until the display shows Page 47
5. GT490X Engineer s Reference Guide Programming Custom Screens 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing Program eft Zones 2 Press No fourteen times The display will show Program Custom Screens 3 Press Yes The display will show LCD Status None Note The LCD Status is defaulted to None and may not be changed The display will only show the Set Unset status of the system for ten seconds after a Set or Unset 4 Press Yes The display will show San The LED Status refers to the LED in the G Tag E or P reader Choose from Off The reader LED will only show for ten seconds after a Set Unset On The reader LED will always be active 5 Press No until the setting you require is displayed Program Stans then press Yes The display will show Custom Screens 6 This concludes the Program Service Press 0 zero twice to return to 01 Jan 00 00 01 Page 75 GT490X Engineer s Reference Guide Programming Diagnostics Log The GT490X control panel has some limited diagnostic features available to the engineer To access these proceed as follows 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 s Ban Program EEEN With the display showing Zones 2 Press
6. View Modem Log Program Modem Functions Access Via Local PC Remote Access Modem Mode Off GT490X Engineer s Reference Guide Choose from the following settings No Return Return PC Return 1 or 2 Return 1 Only Return 2 Only From Site Only Off 39 Press No until the required setting is displayed then press Yes The display will show Communication to the panel is from GardTec Remote via Patch Lead or PC Modem The panel will ring the PC back on the number the PC has passed to the panel The panel will ring back the PC on the 1 or 2 number programmed into the panel The panel will ring back the PC on the 1 number programmed into the panel The panel will ring back the PC on the 2number programmed into the panel Remote Access will be initialised by the user On Site Modem Functions are disabled Double Ring Off This option may be used when when the panel is on a shared line and GardTec Remote is also used 40 Press No until the required setting is displayed then press Yes The display will show Keypad Lock Off In Use Text Off You may continue to program other Modem options if required For the purpose of this Step by Step section 41 Press 0 zero The display will show Program Comms Functions 42 Press Yes The di
7. 001 Ent Ex gt Remove We will now be changing the Zone Attributes Options available are Remove The zone may not be Removed Omitted by the end user Part Sets are still allowed Remove DK Zone may be Removed Omitted by the end user and is a Double Knock Zone 2 activations required within time window or zone left open for 15 seconds Remove DK Zone may not be Removed by end user Part Sets are still allowed and is Double Knock Zone Off Zone is turned Off Use with caution Norm Key Zone is a Keyswitch Zone for a normal type Keyswitch Bias Key Zone is a Keyswitch Zone for a Bias momentary type Keyswitch Remove Zone may be Removed by end user 11 Press No until the setting you require is displayed then press Yes 12 The display will show the next zone to program You should repeat from Step 7 until you have programmed all the zones 13 When all required Zones have been programmed press 0 zero key twice The display will show 14 Press No The display will show Program Zone Types Program Zone Descriptors 15 Press Yes The display will show Enter Zone _ _ _ Page 20 GT490X Engineer s Reference Guide 16 Enter the Zone number you wish to program the Descriptor for followed by Yes Zone 001 Name The display will show for example Zone 001 17 Press No The display
8. 5 6 7 8 9 With the display showing Enter the Engineer code 1234 default The display will show Enter the Authorisor code The Authorisor code is the Master User default 5678 The display will show Press YES The display will show This is Engineer Mode Press Yes The display will show Press Yes The display will show Enter the zone number you wish to program e g 1 followed by Yes The display will show for example Press No The display will show Note the chevron has now appeared before the Zone Type Now press the No key until the Zone Type you require is displayed Page 18 01 Jan 00 00 01 Enter Authorisor Do you want to Use ENGNR Mode Program Zones Program Zone Types Enter Zone 001 Ent Ex Remove 001 gt Ent Ex Remove GT490X Engineer s Reference Guide Zone Types available are 12 Hour Full Alarm if Control Panel is Set Access Will allow to pass through on exit Will allow to pass through on entry only if E E is opened first 24 Hour Internal Sounder if Unset Full alarm if Set Remains active in Engineer Programming Mode Entry Exit or E E Zone used as last exit point will terminate exit time if setting mode is set to E E or Time E E Will start E E time if opened when Control Panel is Set P
9. PSU Diagnostics PSU Test Time 01 Hrs PSU Test Time __Hrs Change List Test Limits Aux VMax 14 0V Aux VMin 13 0V Aux VMax 14 0V Aux VMin gt 13 0V GT490X Engineer s Reference Guide 14 15 16 17 18 19 20 Press No until the setting required for V Min is displayed then press Yes The display will show Press No until the required setting for On Charge Volts max Battery is displayed then press Yes The display will show Press No until the required setting for On Charge Volts min Battery is displayed then press Yes The display will show Press No until the required setting for Off Charge Volts max Battery is displayed then press Yes The display will show Press No until the required setting for Off Charge Volts min Battery is displayed then press Yes The display will show Press Yes The display will show Press Yes The display will show Page 78 On Chg max 14 0 On Chg min 12 6 On Chg max 14 0 On Chg min gt 12 6 Off Chg max 14 0 Off Chg min 12 6 Off Chg max 14 0 Off Chg min gt 12 6 PSU Diagnostics PSU Test Time 01 Hrs Change List Test Limits
10. Program Keypad ACE Prox Program Keypad 01 Jan 00 00 01 GT490X Engineer s Reference Guide Programming Digicom Vo Comm Off On Within this section we will program the Digicom and Modem Both of these devices are built on the main PCB of the control panel Only the main functions will be covered within this Step by Step section If required the 5 5 Yes No default may be used to set the basic comms configuration When this default is used all other settings that have been programmed will be returned to factory defaults When this default is used the following will be set Digicom Type Mod F F Modem Mode No Return This will allow for connection to GardTec Remote for programming functions 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 BGA With the display showing BE DE RER 2 Press No five times The display will show A Tooo i Program Digicom 3 Press Yes The display will show Type or Test p Digicom Type 4 Press Yes The display will show Mod F F Digicom Types available are Mod F F Modem enabled and Ademco Fast Format Central Station protocol enabled Mod SIA Modem enabled and SIA Central Station protocol enabled Mod PID Modem enabled and Point ID Central Station protocol enabled For programming details on PID Point ID Protocol and SIA please r
11. of 45 seconds EN2 Only Note Entry Time 2 is defaulted to 30 seconds and may not be changed 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing 2 Press No twice The display will show 3 Press Yes The display will show 4 Press Yes The display will show 5 Press No twice The display will show 6 Enter the Time required in seconds followed by Yes The display will show Page 38 Program Zones Program Entry Times Program Entry Time 1 Entry Time 1 30s Entry Time 1 gt __s Program Entry Time 1 10 GT490X Engineer s Reference Guide Press No The display will show Press Yes The display will show Note Entry Time 2 is defaulted to 30 seconds and may not be changed Warning Bell Default is set to On but may be changed to Off If Warning Bell is On then Bells will operate during Entry Time 2 after the theoretical expiry of Entry Time 1 has been reached If set to Program Entry Time 2 Entry Time 2 30s Warning Bell On Off the bells will activate only when both Entry Time 1 and 2 have expired Press No to change the setting followed by Yes The display will show This concludes the programming for Entry Times Press 0 zero to return to Or Press 0
12. 0 N C Devices multiple devices are in series LZ 8ZV 1 End of Line Zone Wiring Standard 2 Wire Zone Wiring Multiple units can only be used with BS Standard If using EN2 one unit per zone Page 9 GT490X Engineer s Reference Guide Typical Wiring Modes Where Anti Mask detectors are used one of the following wiring modes may be used Alarm Tamper eet tes Fault Mask ELF1 wiring is used for detectors that have a relay output a pair of terminals for Fault or Mask The installer should check what output type the detectors are noting that all the dectectors should be of the same type with regards to the Fault Mask output Typical ELF1 Fault Mask Alarm Tamper 6K8 4K7 ELF2 wiring is used for detectors that have a transistor output a single terminal for Fault or Mask AZx Note For ELF2 wiring format the 12K resistor must be linked to the positive Side of the zone terminals Typical ELF2 More Zone Wiring Methods Zone Wiring 2 Wire TZ Tamper J N C Tamper Contact Zone Doubling Detector on Zone 1 will be Zone 1 and the Doubled Zone will be Zone 9 Zone 2 will be Zone 2 and the Doubled Zone will be Zone 10 E g Zone number 8 Zone number for Doubled Zone The Zone triggered will be identified through the Z
13. 37 Press No 38 Press Yes The display will show The display will show Always On Keypad is always active Off in Entry Keypad is disabled during Entry Time Of in Ent Alm Keypad is disabled during Entry time or if Entry Time goes through into Alarm 39 Press No until the required setting is displayed then press Yes The display will show 40 This concludes the Program Diagnostics Press 0 zero three times to return to Page 88 Program Confirm Comms Restore Comms Restore On Program Confirm Comms Restore Program Confirm Keypad Opening Keypad Opening Always On Program Confirm Keypad Opening 01Jan 00 00 01 GT490X Engineer s Reference Guide NovActive Description amp Programming NovActive utilises a four core bus to the NovActive sounders that are fitted to the system This allows each individual Bell to to programmed and also gives access to unique Diagnostic Features that allow the individual NovActive sounders to be diagnosed from either the control panel or via GardTec Remote PC Software GardTec Remote may be used from either a remote location via a Modem or on site via a GardTec Modem Patch Lead To program the NovActive sounder s please follow the instructions below Wiring of the NovActive should be carried out in conjunction wi
14. In order to use this option the Setting Mode for Full Set MUST be Time E E and a Door Contact must be fitted to the door If the system sees the door open and close during a setting procedure the system will Full Set If the system does not see the door open and close during a setting procedure the system will Part 1 Set It is not possible to use Silent Part Sets with this option as the decision to do a Part 1 set is taken after the Entry Time has expired 41 Press Yes The display will show ee 42 To change this press No twice The display will show AU Earset On Program Setting 43 Press Yes The display will show A DEAT 44 This concludes the programming for Setting Modes Press 0 zero to return to Program sn Setting Modes Or Press 0 zero until the display shows 01 Jan 00 00 01 Page 37 GT490X Engineer s Reference Guide Programming Entry Times Two Entry Times are available Entry Time 1 amp Entry Time 2 On entry to the premises via the Entry Door Entry Time 1 will start If deviation from Entry Route during Entry Time 1 then Entry Time 2 starts Entry Time 2 is 30 seconds and cannot be changed Note that comms cannot take place until the later of the theoretical expiry of Entry Time 1 or the expiry of Entry Time 2 Note Entry Time 1 is defaulted to 30 seconds but maybe changed to a maximum
15. This option allows for the use of new control panel boards with V5 1 or later software to be used with earlier keypads If older non BS8243 compliant type keypads are used with V5 1 or later this option should programmed to Off It is a requirement of BS8243 that when using ACE Low Battery is reported to the end user if the system is set using ACE See BS8243 Portable ACE used for setting and unsetting Page 81 GT490X Engineer s Reference Guide Secondary Zones The Program Part Test Chime option has now been renamed to Program Zone Attributes Within this section you are able to allocate zones as Secondary Zones Secondary type zones would be used for detectors that may be deemed as having an over sensitive nature this will stop unwanted user call outs Zones that are entered as Secondary will follow the chain of events below During a set period triggering a Secondary Zone will start the Secondary Time Window This will be logged but no further action is taken If the second zone to alarm during the same set period is also a Secondary Zone then it will be logged and the Secondary Time Window will be restarted If the time set within the Secondary Time Window is still running and a zone that is not allocated as a Secondary Zone is triggered the event will be logged an Alarm A un confirmed and Alarm B confirmed will be transmitted This feature is not mandatory for BS8243 Comms Restore With Comms Restore turned on any outstan
16. system Zones on soak test Zones that are put on test must be indicated to the user When setting the system the user must acknowledge this by pressing No 37 If you do not wish to put a Zone s on Test press Yes and jump to Step 43 Otherwise Enter Zone _ 38 Press No The display will show lives onto 39 Enter the Zone number you wish to place on Test followed by Yes The display will show for example Test 003 40 To add more Zone s to the Test repeat from Step 38 Page 25 GT490X Engineer s Reference Guide 41 42 When you have finished adding Zones to Test press Yes Pt 1 None The display will show Three Part Sets are available on the GT490X control panel Zones added to the PT 1 Part 1 screen will be Removed Omitted when the system is Part 1 Set Zones added to the PT 2 Part 2 screen will be Removed Omitted when Part Set 2 is used When Part Set 3 is used Parts 1 amp 2 are combined and Removed Omitted 43 44 45 46 47 If you do not wish to enter PT 1 Zone press Yes and jump to Step 47 Otherwise Press No The display will show Eten ONG oa then YES or NO Enter the Zone number you require for PT 1 followed by Yes The display will show for example Pt 1 004 To add more Zones to PT 1 repeat from Step 43 When you have finished adding Zones
17. zero until the display shows Page 39 Program Entry Time 2 Program Entry Times 01 Jan 00 00 01 GT490X Engineer s Reference Guide Programming Bells Sounders 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 Program With the display showing Zones 2 Press No three times The display will show Program Za Bells Sounders 3 Press Yes The display will show Program Bell Type 4 Press Yes The display will show NovActive Off For information on NovActive refer to page 89 5 This option should remain Off unless you are mo ee using a NovActive Bell Box Type SAB Press Yes The display will show Normal Two Types of Bell may be programmed SAB Self Actuating Bell The Bell terminal stands at 12V and the Bell terminal switches negative on activation SCB Self Contained Bell The Bell and Bell stand at 12V and Ov The OV is removed on activation The majority of Bells sold in the UK are SAB you should only change the Bell Type if you are sure the Bell Type you have is SCB The other option on this screen may be programmed as Normal Normal UK trigger for the UK Irish A Pull Up resistor is required on the Bell Trigger this option is only required for the Irish Republic Page 40 GT490X Engine
18. Digicom Type or Test Digicom Type Mod FF Digicom Type Mod PID Digicom Type Mod SIA VoComm Off Program Digicom Type or Test Program Digicom Delay Part Program Digicom Channels Program Triggers GT490X Engineer s Reference Guide 11 Press Yes the display will show You MUST turn On the Triggers you require 12 Use the Yes amp No keys to accept or change the options on the following screens Page 92 Set Off Alrm Off UnSet Off PA Off Set Off Alrm Off UnSet Off PA Off 24Hr Off E E Off 12Hr Off Bat Off Tamp Off AC Off LF Off Alert Off Fire Off WID Off Duress Off Zone Remove Off Alrm Restore Off AC Restore Off LF Restore Off After Alarm Off Abort Call Off Perimeter Off PA Restore Off Radio Lost Off Radio Jamm Off Zone Fault Off Zone Mask Off Eng On Site Off GT490X Engineer s Reference Guide 5 i a Program Digicom 13 Press Yes The display will show Bide 14 Press 0 zero three times The display will show 01 Jan 00 00 01 Linefault Sounders Description The Line
19. Guide Press Yes The display will show Press No until the required setting is displayed Press Yes The display will show Press No until the required setting is displayed Press Yes The display will show Press No until the required setting is displayed Press Yes The display will show Press No until the required setting is displayed Press Yes The display will show Press No until the required setting is displayed Press Yes the display will show Page 51 Ch1 Off Ch4 gt Off Ch2 Panic Ch3 Alarm Ch2 Panic Ch3 gt Alarm Ch5 Off Ch6 Off Ch5 Off Ch6 gt Off Ch7 Off Ch8 Off GT490X Engineer s Reference Guide 29 30 31 32 33 34 35 36 37 38 Press No until he required setting is displayed Press Yes The display will show Press No until the required setting is displayed Press Yes The display will show Press No The display will show Press Yes The display will show Press No The display will show Press Yes The display will show Press Yes if you require connection to a local PC The display will show Otherwise Press No The display will show Page 52 Ch7 Off Ch8 gt Off Program Digicom Channels Program Digicom Functions
20. Programming Setting Modes Setting Modes are the modes that the control panel will use to set the system for a particular type of set An example of this may be that the Full Set Modes is programmed as Final Exit Door door opening and closing during exit will set te panel whilst the Setting Mode for Part Set 1 is timed Each type of Set Full Part 1 Part 2 Part 3 may have its own Setting Mode 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 gt A 5 k rogram paki With the display showing paces i i Program Z 2 Press No The display will show Setting Modes s te Program Setting 3 Press Yes The display will show ac a i R F Exit time 30s 4 Press Yes The display will show Set by TIME 5 Press No twice The display will show PE ress No twice The display will show Set by TIME 6 Enter the time you require as the Exit Time in seconds followed by Yes The display will show for example F Exit time 20s gt Set by TIME Page 31 GT490X Engineer s Reference Guide 7 Use the No key to scroll through the Setting Modes Options available for Setting Modes are Set By Time The system will Set after the Time shown in the Exit Time Set By ET The system will set when the Exit Terminator Button outside the premises is pushed this option will require a Zone to be programm
21. Route to settle before the system finally Sets The majority of PIRs will settle within the Default Time of 3 seconds but some may need a Final Setting Delay of up to 10 seconds Page 34 GT490X Engineer s Reference Guide 29 Press No twice The display will show Final Set Delay gt 30 Enter the Time required in seconds followed by Yes The display will show Program Setting Delay i i E Program Setting 31 Press No The display will show A Setting Sounders refers to Part Sets Only The Setting Sounders option determines if any or all Part Sets are audible Exit Tones or not This is a useful feature when part of the family may already be asleep when the system is being Part Set 32 Press Yes The display will show Exit Sounder Always Audible 33 Press the No key to scroll through the options Options available for Setting Sounders are Always Audible Exit Sounder will be audible for Full Set and all Part Sets Silent If Part 1 Exit Sounder will be silent during a Part 1 Set Silent If Part 2 Exit Sounder will be silent during a Part 2 Set Silent If Part 3 Exit Sounder will be silent during a Part 3 Set Always Silent Exit Sounder will be silent during ANY Part Set When using a silent Part Set a single beep will be heard at the end of the Exit Time to confirm the system has Set 34 When you have the required setting displayed p
22. The display will show If you do not wish to enter Ch2 Zone press Yes and jump to Step 62 Otherwise Press No The display will show Enter the Zone number you require for Ch2 followed by Yes The display will show for example Page 28 Enter Zone ____ then YES or NO Ch1 001 Ch2 None Enter Zone ____ then YES or NO Ch2 006 60 61 62 63 64 65 GT490X Engineer s Reference Guide To add more Zones to Ch2 repeat from Step 58 When you have finished adding Zones to Ch2 press Yes The display will show See notes on Sec amp Per after step 65 Sec None This concludes the Step by Step instruction for the Zone Programming You may continue within this section to program Secondary Zones Perimeter Zones Double Knock Time Window Zone Re Arm Zone Log Limit Zone E E Mode Event Tags Press 0 zero twice to return to Program erat Zones At this point you may press No to move to the next Header Or Press 0 zero until the display shows 01 Jan 00 00 01 Secondary Zones Zones programmed as secondary will not active any sounders or comms until a normal zone activates This will then trigger a confirmed signal and activate the sounders as programmed Perimeter Zone Zones programmed as per
23. a Panic will only send a signal to Central Station providing that a Digi Channel has been programmed as Panic Bells if LFIt As Silent Always but will revert to Bells if a Linefault is present Page 60 GT490X Engineer s Reference Guide 4 Press No until the required setting is displayed Bells Onl then press Yes The display will show RA Bells Ou gt Non Testable 5 Press No until the required setting is displayed rae then press Yes The display will show Off Please note that Confirmed PA can only be produced by activating two zones programmed as panic or a keypad panic and a Panic zone If Mod FF tis used the Alarm B channel will be transmitted for PA Intruder confirmation If Mod PID is used the confirmed PA will transmit E129 If Mod SIA is used the confirmed PA will transmit HV 6 Press Yes The display will show Duress oi Note Duress is defaulted to Off and cannot be changed 7 This concludes the programming for Program ee Panic Press 0 zero to return to Panic Duress Or Press 0 zero until the display shows Page 61 GT490X Engineer s Reference Guide Programming PGM2 3 Timers PGM2 refers to the PGM2 terminal on the control panel PCB situated near to the RKP terminals PGM3 Refers to the Strobe terminal if this is not used for the Strobe for example if a NovActive Bell Box is use
24. be changed LED Status Display Diagnostics Log List Event Log Change List Diagnostics PSU Diagnostics NovActive Diagnostics PSU Test Time Change List Test Limits Aux Volts Battery Volts On Charge Battery Volts Off Charge In conclusion the Yes and No Keys are used to navigate The No Key is also used to change a value may also require a numeric input and the Zero Key is used to move back a level not when display is expecting a numeric input If you are confident in programming the GT490X Control Panel please use the headers and options above to continue Otherwise Please continue with the next section for a Step by Step Guide to programming the GT490X Control Panel Only the major options will be covered in the Step by Step sections After completing the sections you should be confident to program the remaining options Page 16 GT490X Engineer s Reference Guide Common Options with Menu Numbers You are able to jump to various common options when programming by entering the relevant menu numbers With a Header showing key in the appropriate menu number then press Yes Menu Jumps to PGM 1 Output Timer 1 On Time Timer 1 Off Time PA Mode Chime Level Entry Exit Level Exit Sounder Mode Final Set Delay Full Set Setting Time Setting Mode Part 1 Set Setting Time Setting Mode Part 2 Set Setting Time Setting Mode Part 3 Set Setting Time Setting Mode Alert 1 Keys Mode On Off Alert 2 K
25. damage caused through overloading the Control Panel Supply will not be covered by the warranty We recommend that additional power supplies are used to supply detectors on long cable runs Page 100 GT490X Engineer s Reference Guide 6 4 WIRE Contour RKP WIRING INFORMATION Note 680 Ohm resistor should be fitted to ONE of the RKPs If RKPs are wired in daisy chain this should be the last RKP in the line 680 Ohm 8 3 g 5 o lt N A1 amp A2 if used are connected to the first reader antenna If using an second reader remove the link and connect between A3 amp A4 GT490X Keypad Connection Details wa za AO CvdAM SLOWSY SNOLLOANNOO QvdAay NZL Remove 2K2 if using Keypad Zones and use resistor EOL ol 4 Wire Contour RKP FES zo 10 ao fazano REMOTE KEYPAD S MAY BE WIRED IN STAR OR PROXIMITY DAISYCHAIN READER S FORMAT Keypad Zone Wiring Details RKP ISISIS S 9 Zone 12V OV D D2 Power Alarm N C Tamper N C 1st Detector Power Alarm N C Tamper N C 2nd Detector Note Both detectors must be run on a single cable from the Keypad to the first detector then the second The 2K2 resistor must be in the last final detector Power AlarmN C Tamper N C 2nd Detector Note Keypad zones are preset and cannot be changed E E 3K3 KP Zone 1 Part E E 5K6 KP Zone 2 EOL 2K2 Door Con
26. example Part Alarm gt On 14 Press No until the required setting is displayed Program Digicom then press Yes The display will show Delay Part Program Digicom 15 Press No The display will show Channels Page 49 GT490X Engineer s Reference Guide 16 Press Yes The display will show chto Ch4 Off When programming Digicom Channels Channel 1 is normally Fire Channel 2 is normally PA Panic Channel 3 is normally Alarm unconfirmed and Channel 4 is normally Open Close Channels 5 6 7 amp 8 will be advised by your Central Station Other signals you may require for BS8243 are Alarm Abort Zone Exclude Alarm B Confirmed Channel settings available are Off Zone 24Hr Gen Tamper Alert Fire Part Set Open Close Panic Alarm Alarm B Alarm Abort Power Fail Watchdog Mains Fail PSU Fail Perimeter Zone Exclude Const Lo Bat Radio Radio Lost Radio Const Jam Radio Any Fault Any Mask Power Fail Latch Global Fault This Global Fault is a fast format communication channel option With a channel programmed as Global Fault the channel will trigger when one of the following faults occur Mains Fail PSU Fail Battery Fault Line Fault others Engineer On Site 17 Press No until the required setting is displayed Page 50 18 19 20 21 22 23 24 25 26 27 28 GT490X Engineer s Reference
27. most telephone lines are Tone Dial 53 Press No until the required setting is displayed then ERENER press Yes The display will show Pe Tone Volts Settings available for Line Monitor are Tone Volts The Line Monitor will check the Dial Tone and the Line Voltage This setting should be used when the control panel is connected to a dedicated telephone line Off Line Monitor is turned Off Dial Tone The Line Monitor will only monitor the Dial Tone This setting should only be used on a dedicated telephone line Line Volts Then Line Monitor will monitor the Line Voltage This setting should be used when the control panel is connected to a telephone line that has other telephone equipment on it shared line 54 Press No until the required setting is displayed then press Yes The display will show ay eee Hig Settings available for Line Security are High Low The Line Voltage is monitored at a High Level This setting should be used on dedicated lines only The Line Voltage is monitored at a Low Level This setting should be used when the control panel is sharing the line with other telephone equipment Page 55 GT490X Engineer s Reference Guide 55 Press No until the required setting is displayed then press Yes The display will show Channel 12345678 R Rep 00010000 This option determines what Digi Channels will send a Restore Sign
28. to PT 1 press Yes The display will show pee al Page 26 48 49 50 51 52 GT490X Engineer s Reference Guide If you do not wish to enter PT 2 Zone press Yes and jump to Step 52 Otherwise Press No The display will show Enter Zone ___ then YES or NO Enter the Zone number you require for PT 2 followed by Yes The display will show for example Pt 2 005 To add more Zones to PT 2 repeat from Step 47 When you have finished adding Zones to PT 2 press Yes The display will show Ch1 None Two Chime suites are available on the GT490X control panel so for example you would have the Front Door on Zone 1 programmed into Ch1 and the Rear Door on say Zone 6 programmed into Ch2 When the system is Unset opening the Front Door will produce a Chime Opening the Rear Door will produce a different Chime It should be noted that Chime must be programmed as On from the user mode Please refer to the User Manual for details Page 27 GT490X Engineer s Reference Guide 53 54 55 56 57 58 59 If you do not wish to enter Ch1 Zone press Yes and jump to Step 57 Otherwise Press No The display will show Enter the Zone number you require for Ch1 followed by Yes The display will show for example To add more Zones to Ch1 repeat from Step 53 When you have finished adding Zones to Ch1 press Yes
29. will then show 1 BS 2 EN2 Selecting 1 BS Panel may be programmed to comply with the old BS4737 Standards DD243 requirements will still apply Selecting 2 EN2 Panel may be programmed to comply with EN50131 1 for Grade 2 Systems BS8243 requirements will still apply 5 Select 2 EN2 The display will then show klase yalt This may show for several minutes The display will then show Select TFD2004 2 PD2010 6 Select either 1 or 2 depending on which standard you require Note This document assumes that 2 EN2 and PD2010 have been selected The display will then show 01 Jan 00 01 50 7 Enter Engineer code 3 Enter Auth 1234 default The display will show ea 8 Enter the Authorisor code The Authorisor code is the Master User default 5678 o you want to The display will show Use ENGNR Mode Note It may be required that an engineer has to be authorised by a user before access to the engineer mode is granted Program Zones Zones 9 Press Yes The display will show From this point the panel is in Engineer Mode and all Tampers will be disabled Page 13 GT490X Engineer s Reference Guide 4 PROGRAMMING Moving Around Enter Engineer mode as described on page 13 The display will show Program ee Zones Whenever thre
30. 0 00 01 GT490X Engineer s Reference Guide Programming Reset Modes 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing Press No nine times The display will show Press Yes The display will show Press No twice then enter the Mains Fail Delay time you require Then press Yes The display will show Note Default is set at 20 minutes Will delay the display and the necessity to reset a mains fault for the time programmed Press No until the required setting is displayed Then press Yes The display will show Press No until the required setting is displayed Then press Yes The display will show Press No until the required setting is displayed Then press Yes The display will show Program Zones Program Reset Mains Mains Fail Delay 20m Alarm Reset Master Tamper Reset Eng Anti Fault Reset Any Code Alrm Restore Off Abort Time 60s When Alarm Restore is turned On the Digi channels programmed with Restore On will be restored when the system is unset rather than when the system is Reset 8 Press No until the required setting is displayed then press Yes The display will show for example Press No The display will show Page 66 Alrm Restore On Abort Time gt 60s Alrm Restore
31. 0 00 01 Page 96 GT490X Engineer s Reference Guide 5 SPECIFICATIONS Power Input Humidity Max Loop Resistance Loop Delay Time FUSES Mains Supply Fuse Aux Fuse Keypad Fuse Battery Fuse Low Voltage Output Maximum Output Current GT490X Battery Sizes Construction Complies with Conforms with Number of Zones Standard Expansion Type Number of Keypads Zone Descriptors Max No of Users 230V a c 10 50Hz 70 non condensing 2K not with E O L 400mS 20mm 125mA Anti Surge Resettable Resettable Resettable 13 65V dc Regulated 0 3V 0 8A plus 0 123mA for battery charge 12V 1 2A 2A 3A 7A Metal EN50131 1 PD6662 CE tested EMC Directive 89 336 EEC amp LVD Directive 73 23 EEC 8 2 Wire 9 EOL 8 8 EOL 1 Radio Expanders may be fitted 4 Normal 16 Characters last 3 omitted with tamper 15 Engineer Page 97 GT490X Engineer s Reference Guide Default Codes Code Length User Names Custom Screen Non Volatile Memory Quiescent Currents Control Panel plus Keypad Control Panel Keypad Control Panel plus 1 Keypad ALARM Wirless Expander Log Size Time amp Date Eng 1234 User 5678 BS EN2 4 5 or 6 digits 9 Characters 32 Characters Yes 135mA 12V d c 90mMA 12V d c 45mA 12V d c 160mA 12V d c 50mA 12V d c 250 Event Log 31 Event Modem Log Log amp Display Page 98 GT490X Engineer s Reference Guide Output Termina
32. 0 Fax 0161 655 5501 Internet www riscogroup com e mail sales riscogroup co uk Technical Support 0161 655 5600 Technical Support Fax 0161 655 5610 RISCO Group UK Ltd reserve the right to amend the software and features without prior notice BSIA THE THE BRITISH SECURITY INDUSTRY ASSOCIATION 5IN490PR C PR5851 Rev1 2
33. 14 15 16 Press No twice The display will show Enter the time you require in seconds followed by Yes The display will show This concludes the programming for Linefault Sounders Press 0 zero to return to Or Press 0 zero until the display shows For information on Linefault Sounders refer to page 93 Page 59 Detect gt __ Secs Program Linefit Detect Time Program Linefault Modes 01 Jan 00 00 01 GT490X Engineer s Reference Guide Programming Panic Note Duress is defaulted to Off and cannot be changed Duress 7 is now no longer available You should also check current legislation if Panic signals are allowed for the grade of system that you are fitting 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 a oe peers With the display showing ones i j i ro Program eee 2 Press No seven times The display will show Avi ace 3 Press Yes The display will show PA Bells Only Non Testable It should be noted that with PA Bells Only no PA signals will be sent to Central Station Available setting for PA are Bells Only Activating a Panic will only sound the Bells Bells Always Activating a Panic will Sound the Bells and send a signal to Central Station provided that a Digi Channel is programmed as Panic Silent Always Activating
34. 9 1 Low 9 High followed by Yes The display will show Press No The display will show Press Yes The display will show Press No twice The display will show Enter a value 1 to 9 1 Low 9 High followed by Yes The display will show This concludes the program Sounder Levels press 0 zero to move back to Then Press 0 twice to move back to Page 69 Ent Exit Level Program Sounder Ent Exit Level Program Sounder Keypad Level Keypad Level 05 Keypad Level Program Sounder Keypad Level Program Sounder Levels 01 Jan 00 00 01 GT490X Engineer s Reference Guide Programming PGM1 Custom PGM1 is located on the control panel PCB close to the Bell terminals Up to 8 custom outputs may be programmed on to PGM 1 to 3 A custom output may be used so that the output can follow a zone or a user code 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing Program es Zones 2 Press No eleven times The display will show Program oe PGM1 Custom 3 Press Yes The display will show PGM1 O P Pulse Off V The options available for PGM1 are shown on page 62 4 Press No until the required setting is displayed BENEOIE t
35. Modes When the Setting Mode you Require is displayed press Yes The display will show Page 33 Program Setting for PART 1 set Program Setting for PART 2 set P2 Exit time 30s Set by TIME P2 Exit time gt __s Set by TIME P2 Exit time 20s gt Set by TIME Program Setting for PART 2 set GT490X Engineer s Reference Guide 21 22 23 24 25 26 27 28 Press No The display will show Press Yes The display will show Press No twice The display will show Enter the time you require as the Exit Time in seconds followed by Yes The display will show for example Use the No key to scroll through the Setting Modes When the Setting Mode you Require is displayed press Yes The display will show Press No The display will show Press Yes The display will show Program Setting for PART 3 set P3 Exit time 30s Set by TIME P3 Exit time gt __s Set by TIME P3 Exit time 20s gt Set by TIME Program Setting for PART 3 set Program Setting Delay 03s Final Set Delay The Final Set Delay is a period of time in seconds after the expiry of the Exit Time and is intended to allow any PIRs for example that are on the Exit
36. No fifteen times The display will show Programs lt pee Diagnostics Log 3 Press Yes The display will show List Event Log 4 Press Yes if you wish to view the Event Log Eng Code The display will show for example 01 Jan 01 18 12 This is the last event in the Log Use the No key to move backward in the Log Use the Yes key to move forward in the Log 5 When you have finished viewing the Log press Program 0 zero The display will show Diagnostics Log Page 76 10 11 12 13 GT490X Engineer s Reference Guide Press Yes the display will show Press No The display will show Press Yes The display will show Press Yes The display will show A PSU Battery test will be carried out at the time interval set here and each time you leave Engineer Mode This may be turned Off by setting the Time interval to O zero Press No twice The display will show Enter the time you require in hours followed by Yes The display will show Press Yes The display will show In this example any voltage over 14V or below 13V will create a warning when the PSU test is performed by the system To change these limits Press No until the required setting for V Max is displayed then press Yes The display will show Page 77 List Event Log Change List Diagnostics
37. On Abort Time gt 60s 10 11 12 GT490X Engineer s Reference Guide Press No until the required abort time is set followed by Yes 0 180 seconds in increments of 20 seconds The display will show i Reset Mains Program This concludes the programming for Reset Modes Press 0 zero until the display shows 01 Jan 00 00 01 Page 67 GT490X Engineer s Reference Guide Programming Sounder Levels 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing Press No ten times The display will show Press Yes The display will show Press Yes The display will show Press No twice The display will show Enter a value 1 to 9 1 Low 9 High followed by Yes The display will show Press No The display will show Press Yes The display will show Page 68 Program Zones Program Sounder Levels Program Sounder Chime Level Chime Level 05 Chime Level Program Sounder Chime Level Program Sounder Ent Exit Level Ent Exit Level 05 10 11 12 13 14 15 GT490X Engineer s Reference Guide Press No twice The display will show Enter a value 1 to
38. RISC Creating Security Solutions 9 y Wee Core QG rago x Control Panel Engineer s Reference Guide GT490X Engineer s Reference Guide CONTENTS IMPORTANT Introduction System Installation Wiring Resetting Factory Defaults Programming Moving Around Headers amp Options Common Options with Menu Numbers Programming Zones Reporting a Mains Fail on a PSU Programming Setting Modes Programming Entry Times Programming Bells Sounders Programming Keypad kh wONnD Programming Digicom Vo Comm Off On Programming Linefault Modes Programming Panic Programming PGM2 PGM3 Timers Programming Reset Modes Programming Sounder Levels Programming PGM 1 Timers Programming Engineer Code Programming Service Programming Custom Screens Programming Diagnostics Log Programming Alarm Confirm Notes Programming Alarm Confirm NovActive Description amp Programming Programming Point ID amp SIA Protocols Linefault Sounders Description Engineer Reset Wiring Proximity E amp T Readers Clearing Test Fail Indication 5 Specifications 6 4 Wire Contour RKP Wiring Information Testing the Battery Charge Voltage 7 PD6662 2010 UPDATE New Features Page 1 GT490X Engineer s Reference Guide IMPORTANT Input AC230V 10 50Hz 125mA Max 35W Max Nominal Temp Range 0 50 C Humidity 70 non condensing GT490X Metal as For Indoor Use Only This equipment is intended
39. ading downloading data to the control panel via the PTM Program Transfer Module The Service Timer has the ability to Lock a user out of the system when the Service Time expires Trading Standards may take action if a Lockout occurs and no Service Contract exists Please use with care 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing Program Zones 2 Press No thirteen times The display will show Programi j Service PTM gt F Save Panel NVM 3 Press Yes The display will show papier aah 4 Press Yes if you require to save to PTM Otherwise 5 Press No The display will Load Panel NVM from PTM 6 Press Yes if you require to load from the PTM Otherwise 7 Press No The display will show ets Timet 8 Press No twice The display will show a i Next Service due 9 Press Yes The display will show in 00 Weeks Note To transfer data to and from the PTM a cable part number 04 091 will be required Cut off the BLUE plug at one end and wire to the RS485 terminal block on the GT490X control panel PCB following the colour code Connect the other end to the PTM Note When data transfer is in progress the LED on the PTM will flash rapidly Page 73 GT490X Engineer s Reference Guide 10 11 Note 12 13 14 15 16 Press No t
40. al to Central Station when the system is Reset Most Central Stations will require a Restore Report for all channels 56 Press No The display will show Channel 12345678 R Rep __ L 57 Enter eight ones so the display shows Channel 12345678 R Rep 11111111 58 Press Yes The display will show Open Close Channel s 4 Channel 4 normally needs an inversion of the signal that is sent to Central Station By having 4 as the setting for this option channel 4 will be inverted If you have reports from the Central Station that the Open Close channels are the wrong way around proceed as follows to remove the inversion on the control panel 59 If you do not need to change this option press Yes and jump to Step 61 Or To change the setting Press No The display will show Open Close Channel s gt _ _ 60 Press 0 followed by Yes The display will show Program Advanced Functions Page 56 GT490X Engineer s Reference Guide You may continue to program other Advanced options if required For the purpose of this Step by Step section Program 61 Press 0 zero three times The Display will show Digicom Page 57 GT490X Engineer s Reference Guide Programming Linefault Modes 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing Press No six time
41. art E E As Access if Control Panel is Full Set As Entry Exit if Control Panel is Part Set Panic 24Hour Personal Attack or Panic Attack Active if Control Panel is Set Unset or in Engineer Programming Mode May only be tested via Engineer code if programmed as testable Alert Internal Sounder Only Recorded to Log when Unset Recorded to Log when SET Fire Will give Fire alarm when activated pulsed sounders with Control Panel Set or Unset Remains active in Engineer Programming Mode ET Exit terminator Used for final setting of the system Exit Mode must be programmed for ET Monitor Will write to the log once only in any one set or unset unless chime is allocated then all activations are written to the log KSW Bat When used zone should be connected to the trouble status output of third party radio equipment that is capable of giving a low battery signal Line Fault When used acts as a Line Fault input to the control panel Fault When used will act as an Fault input to the control panel when an internal fault has been detected within the PIR Mask When used will act as an input to the control panel if the detector has been blocked or covered Note Fault and Mask are treated as 24Hr but trigger a Fault Sound in Day Unset Mode The Fault sound is a three tone sounder Page 19 GT490X Engineer s Reference Guide 10 When you are satisfied with your selection press Yes The display will show for example
42. ault Codes are Default Master User Code 5678 Default Engineer Code 1234 The Engineer code may be Locked into the system during engineer programming and it should be noted that if the Locked code is not known the only way to have it returned to the factory default is to return the PCB to the factory Option Formats When an option cannot be changed the display will show a rather than the usual sign Pressing the No key is disregarded and the panel will react as though the Yes key has been pressed i e it will move onto the next option Page 3 GT490X Engineer s Reference Guide 2 SYSTEM INSTALLATION WIRING Planning the Control Panel Location Consideration in locating the fixing position of the Control Panel should be given to Access for the routing of cables for the system from detection devices sounders internal and external remote keypads mains etc The position of the underside retaining screw The fixing of a 3 amp fused spur with disconnection facility When fitting the RKP s consideration should be given to Operation of the keypad Readability of the display The Panel should be fixed to the wall using appropriate wall plugs and No 8 screws at least 30mm long Do not tighten the screws at this stage wait until all your wiring is in place Wiring Considerations With the exception of the mains wiring all interconnections should be made with multicore 7 02 alarm cable Goo
43. d it may be re programmed for other uses One Timer is also available It should be noted that the times programmed will operate seven days per week you are not able to program separate time for weekends etc 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 B j i iA rogram ent With the display showing te 2 Press No eight times The display will show Bice iia a 3 Press Yes The display will show Ae eee as 4 Press Yes The display will show a ene aV Options available for PGM2 3 are Bell Strobe Latch Any Any Digi Status Perimeter Zone Exclude Custom 1 to 8 Int Sounder E E Timed 1 Alert Page 62 GT490X Engineer s Reference Guide cont Alarm B Confirmed Alm Abort Alarm Abort Any Fire Any Panic Gen Tamper General Tamper Zone 24Hr Power Fail Power OK Const LoBat Radio Low Battery Radio Lost Lost Radio Detector etc Const Jamm Radio Signal Jamming Any Fault Any Mask Watchdog Off Pulse Off Pulse On Any Set Alarm Unconfirmed After Alarm Open Close Pulse Set Part Set Walktest Mains Fail PGM2 O P 5 Press No until the required setting is displayed eal one then press Yes The display will show for example With the PGM2 programmed as Bell the output will operate with the Bell when this is set as V With this set as V the out
44. d lock out the keypad for 90 seconds This will be displayed as LOCK OUT Check and will require a valid User Code entry to stop the sounders only after 90 seconds If the system was Unset only the internal sounders will operate If the system was Set a full alarm will be generated Setting by digital key Setting the system must be initiated from within the premises when using a radio fob interaction with the keypad will be required Setting the system with a Gtag fob must be from a keypad not from a remote setting point to comply with the standards for monitored alarms Zones on soak test Zones that are put on test must be indicated to the user When setting the system the user must acknowledge this by pressing No Entry Procedure As per BS8243 2010 Annex G A confirmed alarm may now be generated on entry by straying off from the entry route into a normal alarm zone Engineer on site channel BS EN50131 3 2006 plus A1 2009 as per 8 3 1 When an Engineer code is entered a signal is sent to the ARC indicating an engineer is on site New Fast format channels Engineer on site See page 50 PA Confirm See page 61 New Contact ID and SIA triggers Engineer on site Off On See page 92 New option for the reset modes Fault Reset Anti Eng code Anti code See page 66 Page 105 GT490X Engineer s Reference Guide Notes Page 106 Gard lec G R O U P RISCO Group UK Ltd Tel 0161 655 550
45. d wiring practice should be observed throughout the installation and the following tips may prove useful Never run alarm cables parallel to mains cables telephone cables or any other cables that may be carrying inductive loads Whenever you have to cross mains cables with alarm cables ensure that you do so at 90 Whenever possible wire the mains connection for the control panel back to the consumer unit via a 3A fused spur with disconnection facility Never tap into ring main circuits that have fridges freezers on them Never tap into lighting circuits that have fluorescent lighting units on them Page 4 GT490X Engineer s Reference Guide A Mains Wiring WARNING Electricity can KILL Before connecting the control panel ALWAYS disconnect the supply at the consumer unit A 230V a c supply should be taken directly from the consumer unit In order to comply with the relevant current wiring regulations this should be via a 3 Amp fused spur with disconnection facility This must be carried out by a suitably qualified electri cian If you are in any doubt please contact your local electricity company for advice This control panel MUST be Earthed C N Mains Connection Colours I Live Brown Red Neutral Blue Black Earth Copper Consumer Unit N z Yellow Green sleeving should be used for Copper Earth Conductor o_o Fused Spur Control Panel Mains Terminal Block Page 5 GT490X Engi
46. ding alarm channels will be restored at the end of the Confirm Time Window This feature is mandatory for BS8243 Perimeter Zones Within the Program Zone Attribute section you are able to allocate zones as Perimeter Zones that are entered as Perimeter will follow the chain of events below When activated an unconfirmed alarm will be transmitted to the central station An output or digi channel may be programmed as perimeter or if using Point ID a new signal type of perimeter will be sent This will allow central station to inform the keyholder that an unconfirmed alarm has been received and is a perimeter type device i e window backdoor etc etc This feature is not mandatory for BS8243 Scenarios Relating to BS8243 Sounder Bell Considerations Please note careful consideration should be given when programming Confirm Sounder and Confirm Bell Modes If both are programmed for confirmed and any of the above scenarios occur no local sounders will activate Page 82 GT490X Engineer s Reference Guide Other BS8243 Notes to Consider When a system auto re arms with a zone in fault condition The GardTec control panel will omit the zone concerned A signal should be sent to the central station indicating that a detector s has have been isolated To achieve this a Digi channel should be programmed as Zone Exclude this will automatically send the required signal as the detector is omitted Output Option Status This option has three o
47. e Bell Tamper Ring On With the Bell Tamper Ring On tampering the Bell Box will also trigger the Bell Output from the control panel With Bell Tamper Ring of the Bell Trigger from the panel is not activated 22 23 24 25 26 Press No until your required setting is displayed then press Yes The display will show Press No The display will show Press Yes The display will show Press No until the required setting is displayed then press Yes The display will show This concludes the programming for Bells amp Sounders Press 0 zero to return to Or Press 0 zero until the display shows Page 43 Program Bell Tamper Mode Program Bell for Part Set Part Set Bells On Program Bell for Part Set Program Bells Sounders 01 Jan 00 00 01 GT490X Engineer s Reference Guide Programming Keypad Up to 4 RKPs Remote Keypads may be fitted to the GT490X control panel on a 4 wire BUS A four core connection will be required between the control panel and the remote keypad s keypads maybe in a daisy chain or star format Note A 680 Ohm resistor must be fitted to ONE RKP If the RKPs are wired in the daisy chain format then this should be the last in the line Note Each keypad must be programmed onto the system in o
48. e 7 Zone 6 etc Zone 8 Please note that half the zones on the system would be lost for processing the Mask and Fault signals and it would be more prudent to use the ELF1 or ELF2 modes as described previously Page 23 GT490X Engineer s Reference Guide 30 Press No until the setting you require is displayed Then press YES The display will show aN ZEX 31 With the display showing Radio ZEX Off 32 If you are not using Radio Detectors press Yes and jump to Step 33 Otherwise Press No until the display shows a AEA Page 24 GT490X Engineer s Reference Guide Comprehensive instructions on how to setup and program the Radio Expansion are given in the document Hybrid Wireless Set Up amp Programming Guide supplied with the Radio Receiver 33 Press Yes The display will show Program Radio Functions Program Zone 34 Press No The display will show Wiring 2 Program Zone 35 Press No The display will show Attributes Test None 36 Press Yes The display will show Any 12Hr type zone s may be placed on Test A Zone on Test will never trigger an alarm or send a central station signal If the Zone s fails the Test when the system is Set the display will show Test Fail when the user Un Sets the system After 20 successful Sets and Un Sets the Zone s will be taken out of Test by the
49. e underscores are shown on the display the screen is a header Pressing the NO key will move to the next header Pressing the YES key whilst viewing a header will enter into the options under that header Pressing 0 will escape back one step except when a numeric entry is required You are able to jump to various common options when programming by entering the relevant menu numbers With a Header showing key in the appropriate menu number then press Yes See Page 17 for Common Options with Menu Numbers Below is given a complete list of headers Shown in Bold Underline and options that appear under each header Headers amp Options Headers amp Options Program Zones Entry Times Zone Types Entry Time 1 Zone Descriptors Entry Time 2 Zone Wiring Zone Attributes Bells Sounders Test Part Sec Per Chime Zone Double Knock Arm Log Bell Type Zone E E Mode Bell Delay No Arms Event Tags Bell amp Sounder Ring Bell Tamper Mode Setting Modes Bell For Part Set Setting For Full Sets Setting For Part 1 Sets Setting For Part 2 Sets Setting For Part 3 Sets Setting Delay Setting Sounders Setting Conformation Auto Part Set Page 14 Headers amp Options Keypad Keyswitch Keypad Alert 1 Keys Keypad Alert 2 Keys Function Keys Number of Keypads Keypad Backlight Mode Ace Prox Digicom Type or Test Vo Comm Start Delay Channels Digicom Modem Functions Line Fault Modes Line Fault Sounders L
50. ed as Exit Terminator Set By E E Once the user has started to Set the system the Exit Tones will continue until the Final Exit Door is opened then closed This option will require a Door Contact Set By Time E E Once the user has started to Set the system the system will Set on either the Time expiring or the door opening and closing This option may require a Door Contact 8 When the Setting Mode you Require is displayed press Yes The display will show Program Setting for FULL set P Setti 9 Press No The display will show BART its P1 Exit time 30s 10 Press Yes The display will show Set by TIME A P1 Exit time gt __s 11 Press No twice The display will show Set by TIME 12 Enter the time you require as the Exit Time in seconds followed by Yes The display will show for example P1 Exit time 20s gt Set by TIME Page 32 13 14 15 16 17 18 19 20 GT490X Engineer s Reference Guide Use the No key to scroll through the Setting Modes When the Setting Mode you require is displayed press Yes The display will show Press No The display will show Press Yes The display will show Press No twice The display will show Enter the time you require as the Exit Time in seconds followed by Yes The display will show for example Use the No key to scroll through the Setting
51. efer to page 91 Page 48 GT490X Engineer s Reference Guide 5 Press No until the required setting is displayed then press Yes The display will show VoComm Note If On is selected the Vo Comm menu will now appear in the USER Off mode Please refer to GT490X User Guide for further programming information 6 Press No until the setting you require is displayed Test Digicom then press Yes The display will show Channels Program Digicom 7 Press No The display will show Type or Test 8 Press No The display will show Program Digicom Delay Part 9 Press Yes The display will show p ay Fire Zone Delay 90 Secs 10 Press No twice The display will show Fire Zone Delay gt Secs 11 Enter the number of seconds you require for the Fire Zone Delay followed by Yes Digi Delay 00s The display will show Part Alarm On With Digi Delay programmed the alarm transmission to Central Station will be delayed for the number of seconds programmed With Part Alarm programmed to Off there will be no transmission of Alarm Alarm B or Alarm Abort if the system is Part Set 12 Press No twice The display will show Digi Delay __s Part Alarm On 13 Enter the number of seconds you require for the Digi Delay in Part Set followed by Yes Digi Delay 99s The display will show for
52. en the exit terminator zone will terminate the exit procedure If ET Mode Door Lock and the ET zone door lock is operated on entry then all confirmed alarms will be disabled Bell Mode default Unconfirmed This option controls the bells fitted to the system options are confirmed or un confirmed If Bell Trigger Confirmed then Bell will only trigger with a confirmed alarm If Bell Trigger Unconfirmed then Bell will trigger with un confirmed alarms This feature is not mandatory for BS8243 Strobe Mode default Unconfirmed This option controls the Strobe s fitted to the system options are confirmed or un confirmed If Strobe Trigger Confirmed then Strobe will only trigger with a confirmed alarm If Strobe Trigger Unconfirmed then Strobe will trigger with un confirmed alarms This gives the ability to show to the keyholder from outside the premises that a previously unconfirmed alarm has is now confirmed This feature is not mandatory for BS8243 Confirmed Start Delay default 000m May be programmed between 0 amp 120 minutes default 0 If programmed to anything other than O the panel cannot send confirmed signals until the time programmed has expired This time starts when the system has set and will prevent confirmed alarms being generated in situations when a person has been accidentally locked in the building This feature is not mandatory for BS8243 Ace Low Battery default On Options are On or Off
53. er s Reference Guide 6 Press Yes The display will show Program Bell Type 7 Press No The display will show Program Bell Delay No Arms 8 Press Yes The Display will show Bell Delay 00 m No Arms 99 9 Press No twice The display will show Bell Delay m No Arms 99 10 Enter the number of minutes you require for the Bell Delay followed by Yes Bell Delay 00 m The display will show No Arms gt 99 Note Bell delay is defaulted to 0 but maybe programmed to a maximum of 10 minutes Be careful when using Bell delay the Bell will not sound for the period programmed after the the alarm has been activated Bell Delay used to be a Police requirement but is now not often used in the UK 11 Press No The display will show Bell Delay 00 m No Arms gt _ _ Number of Arms is the number of times the bell is capable of sounding during a Set period It is normal to set this option to 3 or 4 If left at 99 the number of Arms is infinite Note If this option is programmed to 0 the bell will not activate 12 Enter the required Number of Arms followed by Yes The display will show Program Sell Delay No Arms Page 41 GT490X Engineer s Reference Guide 13 14 15 16 Press No The display will show Press Yes The Display will show Press No twice T
54. eys Mode On Off Install Keypads Bell Delay No of Bell Arms Bell Ring Time Sounder Mode NovActive On Off Bell Tamper Ring On Off Entry Time 1 Entry Time 2 Warning Bell Fire Zone Delay Digicom Type Key Beep Level Zone Re Arm Double Knock Time Engineer Code Line Fault Sounders Line Fault Mode Line Fault Log PGM 1 Output Main Fail Delay Tamper Fault Reset Mode Backlight Mode Zone Response Zone Types Test Zone Attributes Save Panel NVM to PTM Service Timer Service Due Weeks Zone Log Limit Digicom Channels Alarm Restore Abort Time Test Digicom Channels E E Zones in Part Set Engineer Code Locked Unlocked Strobe Confirm Page 17 Menu 69 70 71 72 75 92 97 131 139 153 155 156 157 158 159 160 161 162 164 165 166 167 168 169 170 171 172 173 174 Jumps to Auto Part Set Part Set Bells Zone Types Enter Zones On Board Pairing Program Zone Wiring LCD Status List Event Log NovActive PSU Test Time Test Zones Confirm Time Window BS8243 Section Secondary Time Window Confirm on Entry On Off Sounder Trigger Unconfirm Reset Mode E T Mode Bell Trigger Confirm Start Delay Strobe Timer Strobe Trigger Custom 1 OP Mode Custom 2 OP Mode Custom 3 OP Mode Custom 4 OP Mode Custom 5 OP Mode Custom 6 OP Mode Custom 7 OP Mode Custom 8 OP Mode Comms Restore On Off GT490X Engineer s Reference Guide Programming Zones 1 2 3 4
55. fault Sounder option determines how the system sounders speakers will react when a Linefault is detected Below are the options available and a description of each option On if Set Linefault Sounders will operate when the system is Set and a Linefault is detected may be silenced by User Code On if Unset Linefault Sounders will operate when the system is Unset and a Linefault is detected may be silenced by User Code FLT if Off A fault tone will be generated when the system is Unset and a Linefault is detected may not be silenced by User Code Beep if Off A periodic beep will be generated when the system is Unset and a Linefault is detected may not be silenced by User Code Always On Linefault Sounders are always On Set or Unset may not be silenced by User Code Page 93 GT490X Engineer s Reference Guide Engineer Reset If the system is programmed as Engineer Reset the system will need to be Reset by the Engineer Code Please follow the procedure below to effect the Reset 1 If the system is still set unset it via a valid User Code 2 Enter the Engineer Code The display will show ae Authorson 3 Enter a valid User Code The display will show Do you want to Use ENGNR Mode 7 Do you want to 4 Press No The display will show SET the System 5 Press Yes The system will start to Set 6 Enter the Engineer Code again This will Abort the Set
56. he display will show Enter the Bell Ring Time you require in minutes followed by Yes The display will show Program Bell amp Sounder Ring Bell Ring 10 m Sounder Constant Bell Ring __ m Sounder Constant Bell Ring 15 m Sounder gt Constant Note Bell Ring is defaulted to 10 minutes and is programmable from a minimum of 1 minute to a maximum of 15 minutes The term Sounder refers to the Internal Speakers fitted to the system and also the speaker s fitted to the RKPs Options available for Sounder are Constant Will continue after the Bell Time has elapsed Timed Will Time out with the Bell Time 17 Press No until your required setting is displayed then press Yes The display will show Strobe Timer 000 m The Strobe light will normally continue after the Bell Time has elapsed You may Time the Strobe if required To do so 18 19 Press No twice The display will show Enter the time required in minutes followed by Yes The display will show Strobe Timer Program Bell amp Sounder Ring Note Strobe Timer is defaulted to 0 minutes but is programmable to a maximum of 120 minutes Page 42 20 21 GT490X Engineer s Reference Guide Press No The display will show Press Yes The display will show Program Bell Tamper Mod
57. hen press Yes The display will show Pulse Off sy With the PGM2 programmed as Bell the output will operate with the Bell when this is set as V With this set as V the output will be inverted e g On turning Off with the Bell 5 Press No until the required setting is displayed then press Yes The display will show Cus 1 Zone 000 Day Fol t 00 6 Press No to change the Cus 1 to Zone Code or Group as required to follow Press Yes Cus 1 Z gt 000 The display will show ase Day Fol t 00 Page 70 10 11 12 13 14 GT490X Engineer s Reference Guide Press No The display will show Enter the Zone Number or Customer Number that you wish the output to follow then press Yes The display will show for example Press No to select when you want the output to operate followed by Yes The display will show Press No until the mode you require is displayed then press Yes The display will show Press No The display will show Enter the time required followed by Yes The display will show The t 00 setting only applies to Fol Fol Pul Pul Repeat Steps 5 to 13 until all the Custom Outputs you require have been programmed When you have programmed Custom 8 the display will show Press 0 zero until the display shows Page 71
58. imeter will activate the alarm as normal but will also activate a comms channel programmed as perimeter DKnock Arm Log Note Note Zones on double knock are required to activate within the double knock time window or stay active for fifteen seconds to generate an alarm condition Arm is used to program the zones to automatically re arm after an activation It should be noted that a zone still violated when the system times out after an alarm will not re armed Zone Log Limit is defaulted to On and may not be changed Only five activations from any one zone will be recorded in the log during any set period E E in part set entry exit zones will start the entry timer if opened in part set 12Hr in part set entry exit zones will be instant when opened in part set Page 29 GT490X Engineer s Reference Guide Reporting a Mains Fail on a PSU In order to report a Mains Fail on a PSU the Fault output on Program Zone the PSU would be wired to a Zone on the Control Panel Event Tags The Zone Type would be programmed as Fault Program the Zone Descriptor as External PSU At the end of the Program Zones menu we have a menu called Program Events Tags enter this option and select the Zone number you have programmed as Fault Program the Tag as Mains Fail Then program a Digi Channel as Mains Fail This will allow for full reporting of External PSUs Page 30 GT490X Engineer s Reference Guide
59. inal 5 on on other extension sockets S Terminal 2 on other extension sockets S Terminal 3 on Jaa extension sockets Terminal 5 Ta 3 on existing BT Master socket on existing BT Master socket Terminal 2 on existing BT Master socket to W S 7 A5 B2 N IN WE Terminal 5 Terminal 2 on existing BT socket on existing BT socket OR OR Terminal A Terminal B on BT Terminal Block on BT Terminal Block Page 8 GT490X Engineer s Reference Guide Typical Novagard 2G 2G Connections NovaGard 2G 4G GT490X Control Panel Strobe terminals omitted Control Panel Input Zone Connection Please see following page for further wiring modes where Anti Mask detectors are used er td N C Devices O AK7 N C Devices S is N C Devices O gt O 4k7 N C Devices N a i N C Devices e z O rae N C Devices N cJ A Q td N C Devices jo o AKT N C Devices ss N A gt N C Devices _ _ j Tis o i7 N C Devices N o Z a Ed N C Devices Oul mn Ak7 gt E N C Devices 7 N O ak7 5 r eks N C Devices res T o N O Devices PA etc IE ak7 1 connect across Tamper amp Zone S N C Devices N Tamper Zone T becomes Zone 9 ONLY when 9 EOL m l is selected N C Devices KF 9zv SSS 0
60. ine Fault Mode in Exit Line Fault Log Mode Line Fault Detect Time Panic Duress PA Mode Bells Only Bells Always Silent Always Bells if Line Fault Testable Non Testable PA Confirm PA Confirm is defaulted to Off Off 8Hr 10Hr 12Hr 14Hr 16Hr 18Hr 20Hr Duress Off To conform with EN standards Duress is defaulted to Off and cannot be changed PGM2 PGM3 Timers PGM2 3 Operating Mode PGM 2 Mode PGM3 Mode Timer 1 On Time Timer 1 Off Time GT490X Engineer s Reference Guide Headers amp Options Reset Mains Mains Fail Delay Alarm Reset Tamper Reset Fault Reset Alarm Restore On Off Abort Time Sounder Levels Chime Level Entry Exit Level Key Beep Level PGM1 Custom PGM1 O P Custom Output 1 Custom Output 2 Custom Output 3 Custom Output 4 Custom Output 5 Custom Output 6 Custom Output 7 Custom Output 8 Engineer Code Engineer Code Engineer Code Locked Unlocked Page 15 GT490X Engineer s Reference Guide Headers amp Options Headers amp Options Service Alarm Confirm Mains OK 50Hz Window Time Save Panel NVM to PTM On Entry Load Panel NVM to PTM Sounder Mode Service Timer Reset Mode Time To Next Service Secondary Time Service Tel No ET Mode Lock Out On Off Bell Mode Engineer Mode Constant Timed Strobe Mode Start Delay Custom Screens Comms Restore Keypad Opening LCD Status Display ACE Battery Monitor To conform with EN standards LCD Status is defaulted to Off and cannot
61. it to be recognised by the system Depending on the variant of keypad fitted external G Tag Proximity Reader s may be fitted to each Remote Keypad Note 680 Ohm resistor should be fitted to ONE of the RKPs If RKPs are wired in daisy chain this should be the last RKP in the line SNOILOSNNOO X30NYdX3 O1dVe SerSy za NYO 334 one aay 680 Ohm 9 X 5 g gt 2 iS z a CvdASy SLOWSY SNOILOANNOO vd M AO ID2 B D1 A OV 12V REMOTE KEYPAD S MAY BE WIRED IN STAR OR DAISYCHAIN FORMAT GTAG PROXIMITY READER S Note Please refer to the back of this manual if the Control Panel has been supplied with a 4 Wire Contour RKP with added zones for wiring information Page 7 GT490X Engineer s Reference Guide Control Panel Output Connections Digi Modem I AAAA BELL SAB _ PGM1 SPR SPR AUX 12V Bell Trigger INTERNAL SPEAKERS MIN 16 OHM Strobe Trigger Bell Strobe Hold Off Bell Hold Off Supply Tamper Return EXTERNAL SOUNDER STROBE MODULE The GT490X control panel feature an onboard Digi modem The Digi provides all the features of an eight channel communicator whilst the Modem provides facilities for Gardtec Remote Upload Download software package Telephone Connections Serial Telephone Connection Depending on model Standard Telephone Connection ST erm
62. l power up will revert the Master Code and Engineer Code not locked engineer code back to factory defaults b Pressing 3 7 YES NO during initial power up will revert all system settings back to defaults with the exception of the User Names and Zone Descriptors c Pressing 4 6 YES NO during initial power up will revert all system settings back to factory defaults It is ESSENTIAL that a 4 6 YES NO reset is done to all new systems before commencement of programming d Pressing 5 5 YES NO during initial power up will revert all system settings to factory defaults and will also set the comms options up for GardTec Remote ie Modem On No Return For commissioning systems for use with GardTec Remote use this option Reset of the factory defaults and entering Engineer Mode Note Itis ESSENTIAL that a 4 6 YES NO reset is done to all new systems before commencement of programming 1 Remove all power from the system for at least ten seconds 2 Apply mains power to the control panel The display will show for example Display will differ dependant on panel version GT490X XX XX 3 Whilst this display is showing the first five seconds press the keys shown in a b c or d for the reset required E g 4 6 Yes No The display will show Please Wait This may show for several minutes Page 12 GT490X Engineer s Reference Guide Select Standard 4 The display
63. l show Enter the text required E g Front Wall Bell Then press Yes The display will show Note See Page 21 for entering text instructions NovA1 Off LEDS 0 Confirm Off NovA1 On LEDS gt 0 Confirm Off NovA1 On LEDS gt 0 Confirm gt Off NovA1 A PA 0 Alm 0 Tmp 0 NovA1 A PA 3 Alm gt 0 Tmp 0 NovA1 Text NovActive NovA1 Text I V Select NovActive 1 8 You should now repeat until all the NovActives on the system have been programmed When you have finished programming all the NovActives press 0 until the display shows Page 90 01 Jan 00 00 01 1 10 GT490X Engineer s Reference Guide Programming Point ID amp SIA Protocols Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing Press No five times The display will show Press Yes The display will show Press Yes The display will show for example Press No until the display shows Or As required Press Yes The display will show Press No until the setting you require is displayed Then press Yes The display will show Press No The display will show Press No The display will show Press Yes The display will show Page 91 Program Zones Program Digicom Program
64. l show Press Yes The display will show The term Sounder relates to the system speaker s Press No until the required setting is displayed then press Yes The display will show Press No The display will show Press Yes The display will show Page 85 Program Confirm Window Time Program Confirm On Entry Confirm on Entry On Program Confirm On Entry igi Program Confirm Sounder Mode Sounder Trigger Unconfirmed Program Confirm Sounder Mode Program Confirm Reset Mode Unconfirm Reset Any GT490X Engineer s Reference Guide 16 17 18 19 20 21 22 23 24 Press No until the required setting is displayed then press Yes The display will show Press No The Display will show Press Yes The display will show Press No twice The display will show Enter the time required then press Yes The display will show Press No The display will show Press Yes The display will show Press No until the required setting is displayed then press Yes The display will show Press No The display will show Page 86 Program Confirm Reset Mode Program Confirm Secondary Time Secondary Window 060m Secondary Window m
65. ls and Connectors RS485 Shares AUX 12V supply protection 1 1A resettable thermal fuse Speaker Combined impedance of speakers connected MUST NOT BE LESS THAN 16 ohms Speaker terminal is AUX12V speaker ve is drive output PGM 1 and PGM2 Internal 1K pull up to AUX12V internal 22ohm series resistor to output Maximum current sink 50mA Note that due to the 22ohm series resistor with 50mA sink the output will be at appronimately 1 1V AUX12V 1 1A resettable thermal fuse AUX12V also feeds RS485 Speaker Bell and Strobe This pair of terminals supply the and supply for the detectors Bell Strobe This pair of terminals are the output for the Bell Strobe The negative terminal is switched during an alarm period Strobe ve switch to OV max current for switch is 1A Shares AUX 12V supply protection 1 1A resettable thermal fuse Keypad OV 12V Connections Independently fused 12V supply protection 500mA resettable thermal fuse Page 99 GT490X Engineer s Reference Guide Power Supply Output voltage 10 5 to 14 0V Ripple 0 6V max Low battery detection threshold 11 0V 0 3V Low battery messages sent Fast Format will be PSU Fail Globel Fault Channel Contact ID E302 SIA YT Will charge 8 5AH Battery to 80 within 72 Hrs Sounders detectors and other auxiliary items including the control panel and keypad s should be included when calculating current drawn by the system Any
66. nce the Fault Mask as been triggered the response time for the Fault Mask will revert to the default time of 400ms until the fault mask problem has cleared 24 Press No until the required settings you require are i p p On Board Zones displayed then press Yes The display will show 9 lt FOL gt Wiring Modes available are 8 2 Wire Two wires are used for the zone and a global tamper is used 9 EOL Two wires are used in conjunction with two resistors to give End Of Line wiring this is the most secure wiring format 8 8 EOL This wiring method uses double EOL format to give 16 Zones from the control panel Note For information on how to wire for the various wiring modes please refer to the wiring section within this manual If selecting 9 EOL follow steps 24 through to 26 If selecting 8 8 EOL jump to step 28 On Board Zones 25 With the display showing ae Press Yes On Board EOL Norm 26 The display will show Page 22 GT490X Engineer s Reference Guide Three wiring options are available under 9 EOL Norm Standard GardTec wiring configuration without Mask or Fault detection Note Does not give any Fault or Masking detection and should only be used with Zone pairing ELF1 ELF1 wiring is used for detectors that have a relay output a pair of terminals for Fault or Mask ELF2 ELF2 wiring is used for detectors that have a transi
67. ndards and documents published by British Standards that add or vary requirements for alarm confirmation commissioning and maintenance and false alarm management PD 6662 2010 will replace the 2004 version when it is published but for a two year period ending May 31st 2012 systems may be installed under either the 2004 or 2010 version of PD 6662 The most significant changes are listed below Engineer Access Can now be turned off if the customer has agreed in writing When entering the engineer menu the panel will generate an audible sound for approximately 8 seconds to indicate that the engineer is on site grades 1 2 and 3 For grades 2 3 the ATS must also send an engineer on site signal Confirmed PA Confirmed PA has been added to the Control Panel menu Programming Panic Panic Please note that Confirmed PA can only be produced by activating two zones programmed as panic or a keypad panic and a Panic zone If Mod FF is used the Alarm B channel will be transmitted for PA Intruder confirmation If Mod PID is used the confirmed PA will transmit E129 If Mod SIA is used the confirmed PA will transmit HV Note This would normally be used on systems that have lost police response for Panic Page 104 GT490X Engineer s Reference Guide Keypad disabled for 90 seconds The keypad will monitor the number of attempts without a valid User Code being entered More than seven attempts will cause a keypad tamper an
68. neer s Reference Guide GT490X PCB iagrams D iring Ww Note 680 Ohm resistor should be fitted to ONE of the RKPs If RKPs are wired in daisy chain this should be the last RKP in the line 680 Ohm N wia aea no Neb REMOTE KEYPAD S MAY BE WIRED IN STAR OR DAISYCHAIN FORMAT Bell Trigger INTERNAL SPEAKERS MIN 16 OHM Strobe Trigger Bell Strobe Hold Off Bell Hold Off Supply Tamper Return EXTERNAL SOUNDER STROBE MODULE ITY READER S Connections available are model dependant Case Tamper Bypass Jumper JUMPER Default Engineer Code GONNEGTION 1234 Default User 5678 To Default Panel Power Up OTHER Whilst version No is displayed enter 46 Yes No This will not Default the Engineer Code if it has been locked TELEPHONE CONNECTIONS TAMPER SOCKETS 5 ON PREMISES Page 6 GT490X Engineer s Reference Guide Remote Keypads Up to four remote keypads may be fitted to the GT490X control panel Each Keypad offers a 32 character backlit LCD A four core connection will be required between the control panel and remote keypad s keypads may be in a daisy chain or star format Note Note Note 680 Ohm resistor must be fitted to ONE RKP If the RKPs are wired in daisy chain format this should be the last RKP in the line Each keypad must be programmed onto the system in order for
69. one Wiring EOL AZ Alarm AZ Alarm 4K7 6K8 N C Alarm N C Tamper N C Alarm Contact Contact Contact resistor value by the system Zone Doubling 8 8 AZ Alarm AZx Alarm N C Tamper N C 2nd Detector Alarm N C Tamper N C 1st Detector Page 10 GT490X Engineer s Reference Guide Radio Zone Expander One GardTec Radio Zone Expander may be fitted directly to the RS485 Bus connec tions on the control panel PCB without the need for any interface card A Radio Expander card will allow eight wireless zones amp eight wireless Fobs Radio Zone Programming When programming Radio Zones the zone numbering for the Radio Zones will start at 91 When programming Radio Fobs the numbering of the Fobs will start at 81 RADIO EXPANDER WIRING amp SWITCH SETTINGS SNOILOANNOD 4a QNVvdX4 OldVY S8rSy NYS THA a Gay KEY ZONE RECEIVER ID ID DIP SWITCH SETTINGS Resistor Colour Codes 6K8 12K 16K 27K 4K7 Blue Brown Brown Red Yellow Grey Red Blue Violet Violet Red Orange Orange Orange Red Brown Brown Brown Brown Brown Page 11 GT490X Engineer s Reference Guide 3 RESETTING FACTORY DEFAULTS Several reset to factory default routines are available to the engineer at system power up but it should be noted that none of these routines will Un Lock a Locked Engineer Code The following default routines are available a Pressing 1 9 YES NO during initia
70. only for use as a Security Alarm Control Panel Adequate ventilation away from heat and humidity must be provided The unit must be fixed securely to a non flammable surface using suitable fixings All mains wiring must conform to the relevant current IEEE wiring regulations or appropriate international regulatory standards See Mains Supply Connection section within this manual for more detailed instructions All wiring must be protected from sharp or jagged edges All low voltage alarm wiring must be to the appropriate international regulatory standards and comply to good wiring practice and should be routed away from the mains cables Replacement fuses should be of the same type and rating conforming to IEC 127 The GT490X Control Panel is fitted with resettable fuses The areas protected are Battery Aux and Keypad In the event of a fuse tripping or an input output not working remove the source of the load and check wiring for shorts Check any added devices for full functionality before any reconnection The maximum current draw from the unit for all output combinations must not exceed 1A Sounders detectors and other auxiliary items including the control panel and keypad s should be included when calculating current drawn by the system Any damage caused through overloading the Control Panel Supply will not be covered by the warranty We recommend that additional power supplies are used to supply detectors on long cable r
71. perating modes and is intended to provide a visual indication of the system status System Set Output On for 10 seconds System Unset Output On for 1s Output Off for 1s for a 10 second period Confirmed Alarm Output On for 3 seconds Output Off for 1s until system reset It is envisaged that this status output would be fitted to an indicator i e LED that can be seen from outside the premises Page 83 GT490X Engineer s Reference Guide Programming Alarm Confirm 1 2 3 4 5 6 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing Press No sixteen times The display will show Press Yes The display will show Press Yes The display will show Press No twice The display will show Enter the time you require followed by Yes The time MUST be between 30 amp 60 minutes Page 84 Program Zones Program Alarm Confirm Program Confirm Window Time Confirm Window 060m Confirm Window gt om 10 11 12 13 14 15 GT490X Engineer s Reference Guide The display will show Press No The display will show Press Yes The display will show Confirm on Entry may be On only if you are using an ACE device to Unset the system Press No until the required setting is displayed then press Yes The display will show Press No The display wil
72. put will be inverted e g On turning Off with the Bell PGM3 O P 6 Press No until the required setting is displayed Strobe gt V then press Yes The display will show Program PGM2 3 7 Press No until the required setting is displayed Operating Modes then press Yes The display will show Page 63 GT490X Engineer s Reference Guide i y Program PGM2 3 8 Press No The display will show E EA 5 z Timer 1 On Time 9 Press Yes The display will show ae iie ot as Timer 1 On Ti 10 Press twice No The display will will show he 00 a 11 Enter the On Time hours followed by Yes Tse CAH imer n lime The display will show 10 500 Hrs 12 Press No The display will show camer Ton Time 10 gt __ Hrs 13 Enter the On Time minutes followed by Yes Program PGM2 3 The display will show Timer 1 On Time 14 Press No The display will show Program PGM2 is Repeat for Timer 1 Off Time Timer TOWNS 15 Press Yes The display will Show Program PGM2 3 Timer 1 Off Time Page 64 16 17 GT490X Engineer s Reference Guide This concludes the programming for PGM2 3 Timer Press 0 zero to return to Or Press 0 zero until the display shows Page 65 Program oe PGM2 3 Timers 01 Jan 0
73. rder for it to be recognised by the system Note Depending on the variant of the keypad fitted external G Tag Proximity Reader s may be fitted to each keypad 1 Enter into Engineer Mode progran To do this follow Steps 1 to 4 on page 18 Zones Pag With the display showing 2 Press No four times The display will show Program Keypad 3 Press Yes The display will show Program Keypad Alert 1 Keys Alert 1 Keys refers to the PA keys being pressed together or keys 1 amp 3 being pressed together P amp F refers to PA keys S oS GA GA Alert 1 Off 4 Press Yes The display will show 183 Of P amp F On 5 Press the No Key to scroll through the settings for Alert 1 When the setting you require is displayed press Yes The display will show Alert 1 Off 183 gt Off P amp F On Alert 1 Off 183 gt On P amp F On 6 Press No The display will show Alert 1 Off F 1 amp 3 On P amp F gt On 7 Press Yes The display will show Page 44 GT490X Engineer s Reference Guide 8 Press Yes The display will show Program Keypad Alert 1 Keys 9 Press No The display will show Program Keypad Alert 2 Keys Alert 2 Keys refer to Key 7 amp 9 pressed together 10 Press Yes The display will show Alert 2 Off 7 amp 9 Key
74. ress Yes The display will show Program Setting Sounders Page 35 GT490X Engineer s Reference Guide 35 Press No The display will show Program Setting Confirmation Setting Confirmation uses the Strobe Light to confirm that the system has finally set 36 Press Yes The display will show ae ponam 37 Press the No key to scroll through the options Available options for Strobe Confirm are Off Strobe Confirm is turned Off Full Set The Strobe will Confirm only on Full Set Any Set The Strobe will Confirm on Any Set Full or Part 38 When the required setting is displayed press Yes The display will show Fob Arm Keypad Confirm Off Press No to select On Off If programmed to On when the radio fob is pressed to arm the system the keypad will display Press YES to Set If Yes is pressed the system will start to set Note If the No key is pressed or you take longer than 20 seconds the display will return to the time and date 39 When the required setting is displayed press Yes P Setti The display will show ODORA Confirmation Program Settin 4 Press No The display will show g g 0 ESS SS e display 19 for Auto Part Page 36 GT490X Engineer s Reference Guide Auto Part Set allows the system to decide if the Setting should be Full Set or Part 1 Set
75. s Confirm on Entry default On This option may be programmed to On or Off If Confirm on Entry Off then confirmed alarms to central station are disabled if the entry timer is started If ACE or G Tag is used then it is permissible to set this option to On Sounder Mode default Unconfirmed This option controls the system speakers fitted options are confirmed or un confirmed If Sounder Trigger Confirmed then internal sounder will only trigger with a confirmed alarm If Sounder Trigger Unconfirmed then internal sounders will trigger with un confirmed alarms This feature is not mandatory for BS8243 Reset Mode default Any Choose from Any or Normal If Unconfirm Any then any code can be used to reset an un confirmed alarm If Unconfirm Normal then the programmed reset mode for alarm will still be required i e if alarm reset has been programmed as engineer and Unconfirm reset is Normal then an engineer reset will be required for Un confirmed alarms Confirm Secondary Time Window default 60 minutes This time window may be programmed between 1 and 120 minutes we would suggest a time between 30 and 60 minutes but should typically be the same time as the confirm time window This option affects zones that have been allocated as secondary zones only For functionality please refer to Secondary Zones Below Page 80 GT490X Engineer s Reference Guide ET Exit Terminator Mode default Set If ET Mode Set th
76. s Off 11 Press No until the required setting is displayed 3 aed Alert 2 Off then press Yes The display will show 789 Keys gt Off Alert 2 Off 12 Press No The display will show 789 Keys gt On 13 Press Yes The display will show Program Keypad Alert 2 Keys 14 Press No The display will show Program Keypad Quick Key 15 Press Yes The display will show Quick Key Off Page 45 GT490X Engineer s Reference Guide The available options for the Quick Key are Off The Quick Key is disabled Quick Set Reduces the Exit Time after Exit has started Full Set Enter user code then Quick Key Part Set Enter user code then Quick Key for Part 1 Set 16 Press No until the required setting is displayed then press Yes The display will show 17 Press No The display will show This option is used to program the Number of Keypads you have on the system It should be noted the there are no jumpers in the RKP to ident them this is done from the program option 18 Press Yes The display will show 19 Press Yes The display will show 20 Enter the Number of the keypad you wish to program onto the system 1 to 4 then press Yes The display will show 21 Press the No amp the Yes buttons together on the selected keypad The display will show Page 46 Program Keypad Quick Key Program Keypad Number
77. s The display will show Press Yes The display will show Press Yes The display will show Press No until the required setting is displayed then press Yes The display will show Press No The display will show Press Yes The display will show Press No until the display shows the required setting then press Yes The display will show Page 58 Program Zones Program Linefault Modes Program Linefault Sounders Linefault Sounders ON if Un Set Program Linefault Sounders Program Linefit Mode in Exit Lineflt Mode Detect in Exit Program Lineflt Mode in Exit 10 11 12 13 GT490X Engineer s Reference Guide Press No The display will show Press Yes The display will show Note Line Fault is defaulted to Limited and may not be changed This limit is set to 3 events Press Yes The display will show Press No The display will show Press Yes The display will show Program Linefit Log Mode Linefit Log Limited Program Linefit Log Mode Program Linefit Detect Time Detect 30 Secs With Detect programmed as 00 Linefault detection is instant or it may be delayed if required
78. splay will show Comms Off Page 53 GT490X Engineer s Reference Guide 43 Press No twice The display will show omms O 44 Press Yes The display will show for example Site ID Code Is Un Programmed In the UK the Site ID Code is normally a four digit number your Central Station may have supplied you with a six digit number If this is so please use the last four digits 45 Press No The display will show Site ID Code 46 Enter your Site ID Code followed by Yes The display will show Phone Number 1 is Un Programmed We will be entering two Phone Numbers If your Central Station has only supplied you with one Phone Number please use the same one twice 47 Press No The display will show Phone Number 1 48 Enter Phone Number one followed by Yes The display will show inhibit Display of New Number 49 Press Yes The Display will show Phone Number 2 is Un Programmed 50 Press No The display will show Phone Number 2 Page 54 51 Enter Phone Number 2 followed by Yes The display will show Inhibit Display 52 Press Yes The display will show Dial Tone GT490X Engineer s Reference Guide of New Number This option refers to the line mode of the telephone line In the UK
79. stor output a single terminal for Fault or Mask Note We would recommend that either ELF1 Format or ELF2 Format dependant on detector output type Relay or Transistor is used ELF1 or ELF2 wiring modes will allow for Alarm Tamper Fault and Masking to be monitored from a single zone without the need for zone pairing Note The installer should check what output type the detector are noting that all the detectors should be of the same type with regards to the Fault Mask output 27 Press No until the setting you require is displayed Radio ZEX then press Yes The display will show Off If 8 8 EOL wiring option is required On Board Zones 28 With the display showing 9 lt EOL gt Press No until 8 8 lt EOL gt is displayed The display will show Op Board Zones gt 8 8 lt EOL gt 29 Press Yes The display will show On Board Pairing Off Zone Pairing A zone is used to monitor Masking and Fault This is achieved by selecting Zone Pairing as on Zone Pairing cannot be used in ELF1 or ELF2 wiring modes When using Zone Pairing each zone will have a corresponding paired zone that will be used for Masking and Fault signals This is done by using the Odd numbered zones for the normal alarm detection and the Even numbered zones for Masking and Fault Detection For example Alarm Zone Zone 1 Pared Zone for Mask Fault Zone 3 Zone 2 Zone 5 Zone 4 Zon
80. tact Note All keypads on the same system MUST be of the same type i e All four wire or all six Note All Keypads MUST be connected before powering up the Control Panel Page 101 GT490X Engineer s Reference Guide Testing the Battery Charge Voltage IMPORTANT To test the Battery Charge Voltage the battery must be connected to the battery leads first See figure 1 Battery connector on PCB Fig 1 Only if the battery is connected and the battery terminal voltage is greater than 8 5V will the charge circuit be switched on Page 102 GT490X Engineer s Reference Guide To test the charge voltage connect a test meter as per figure 2 Battery connector Multimeter Connect one meter lead to the battery by pushing the probe under the insulation of the battery spade Then remove the other battery lead and connect to the other meter lead The meter will now show the battery charge voltage Note that the voltage will drop off within 10 seconds Repeat the above if required Page 103 GT490X Engineer s Reference Guide 7 PD6662 2010 UPDATE NEW FEATURES EN50131 1 2006 and BS8243 PD 6662 the document describing how the European standards for Intrusion and Hold up Alarm systems I amp HAS should be applied in the UK has been completely revised The revision takes into account the publication of a number of new revised or amended European standards It also adds some new sta
81. th the instructions supplied with the unit 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 P Rae With the display showing ER i i i w Program Pee 2 Press No three times The display will show EER IRE 3 Press Yes The display will show Program Bell Type 4 Press Yes The display will show NovAclive Qf 5 Press No twice The display will show NovAcive op Select NovActi 6 Press Yes The display will show a RE Page 89 GT490X Engineer s Reference Guide 7 8 9 10 11 12 13 14 Press the number of the NovActive you wish to program The display will show Press No twice to turn NovActive 1 On Then press Yes The display will show To program the LED pattern press No until the setting required is displayed Choose from 0 Alternating LEDs 1 1 Static LED 2 2 Pulsing LEDs 3 No LEDs When you are happy with your selection press Yes The display will show To program the Setting Confirmation press No until the required setting is displayed then press Yes The display will show To programme the sound press No until the required setting is displayed then press Yes The display will show for example Repeat for Alm Tmp until the required settings are displayed Then press Yes The display will show Press No The display wil
82. ting 7 The System is now Reset The display will show for example 01Jan 00 00 01 Details of User Code Reset and Anti Code Reset are given in the User Manual Page 94 GT490X Engineer s Reference Guide Wiring Proximity E and I Readers Reader Terminals RKP Terminals Single E Reader up to 7 5m E Reader Wiring RKP Terminals 2 RED m BLUE Si g YELLOW SE d i BLACK S Single E Reader 7 5m to 15m E Reader Wiring RKP Terminals 2 RED GREEN Si 5 YELLOW NE d BLACK S Details on wiring multiple Readers are provided with the Reader Page 95 GT490X Engineer s Reference Guide Clearing Test Fail Indication If the display shows Unset Test Fail 01 Jan 00 00 01 The system has a zone On Test that has failed when the system was Set Please note we recommend that the Test Attribute is only used on 12Hr type zones To clear the display proceed as follows 1 Enter the Engineer Code The display will show pals Authorisor O0G eae ed 2 Enter a valid User Code The display will show Do you want to Use ENGNR Mode 3 Press No The display will show Do you want to SET the System 4 Press Yes The system will start to Set 5 Allow the system to fully Set 6 Enter the Engineer Code again to Unset the system The display will show 01 Jan 0
83. uns The unit is intended for use with a suitable re chargeable lead acid battery permanently connected to the appropriate terminals All documentation and manuals must be thoroughly read by suitably qualified installation personnel prior to installation Page 2 GT490X Engineer s Reference Guide A Important Safety Information Hazardous Voltages Inside The unit has no user serviceable parts inside No User Access Internal access should only be by suitably qualified personnel The unit MUST be Earthed It is the responsibility of the installation engineer to ensure that the earth connection to the unit lid is good on completion of the installation or after service 1 INTRODUCTION The GT490X Control Panel is a microprocessor based unit that has been designed to be suitable for all types of domestic and commercial installations All zones are fully programmable by the engineer On power up reset the Control Panel can be set to the old BS or EN2 Grade 2 operating standards It is ESSENTIAL that a 4 6 YES NO reset is done to all new systems before commencement of programming Upon completion of the installation the engineer may if required re program several factory set options so as to tailor the Control Panel to suit the requirements of the sys tem The GT490X Control Panel uses 32 character LCD Remote Keypads for control of the system via User Code s and programming of the system via an Engineer Code The Factory Def
84. wice The display will show Enter the number of weeks you require to the next Service then press Yes The display will show The system will start to warn the end user that the Service is due two weeks before the time expires Press No The display will show Enter the Telephone Number you wish your customer to dial for service followed by Yes The display will show With Lock Out turned On the system will Lock the users out when the Service Time expires With Lock Out turned Off the system will continue to warn of Service until the Service Timer is reset Press No until the required setting is displayed then press Yes The display will show With Engineer Mode programmed as Constant the panel will remain in Engineer Mode until the Engineer exits With Engineer Mode programmed as timed the panel will jump out of Engineer Mode after 1 hour if all the Tampers are clear This prevents the Engineer accidentally leaving the panel in Engineer Mode Press No until the required setting is displayed then press Yes The display will show This concludes the Program Service Press 0 zero twice to return to Page 74 Next Service due in__ Weeks Service Tel No is Un Programmed Service Tel No LOCK OUT On Engineer Mode Constant Program Service PTM 01 Jan 00 00 01
85. will show Zone 001 Name 18 You should now program the Descriptor you require using the template below for the key allocation in a similar way that you you would type a text message on a mobile telephone As the desired character is displayed press the Yes key to move on to the next character Continue until the line is complete 1 2 3 ABC DEF GHI 4 5 6 JKL MNO PQR 7 8 9 STU VWX YZ Space No 0 Yes Delete 1234567890 Enter Character 19 As you enter the last character the display Zone 001 Name will move on to the next Zone For example Zone 001 20 Repeat from Step 16 until all the Descriptors you require have been programmed Then press 0 zero key twice The display will show Program Zone Descriptors Page 21 GT490X Engineer s Reference Guide 21 Press No The display will show Program Zone Wiring 22 Press Yes The display will show Zone Response Note Zone Response time is defaulted to 400ms and may not 400 mS be changed Fault Mask Zones Response Norm 23 Press Yes The display will show Note Zone response time may be programmed as a global parameter The default time is 400ms and may be reprogrammed from 2 to 14 seconds increments of 2 seconds The time programmed for this option will apply to all zones there is no option for individual response times per zone It is a global setting O

Download Pdf Manuals

image

Related Search

Related Contents

FrontRow ToGo User Manual  Funkwerk elmeg ICT880xt-rack  User's manual  取扱説明書  Nilfisk-Advance America SD 43-165 User's Manual  

Copyright © All rights reserved.
Failed to retrieve file